+ All Categories
Home > Documents > PCPL-0532-4-407-04-08

PCPL-0532-4-407-04-08

Date post: 04-Jun-2018
Category:
Upload: tceterex
View: 220 times
Download: 0 times
Share this document with a friend

of 13

Transcript
  • 8/13/2019 PCPL-0532-4-407-04-08

    1/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 1 of 13

    DATE:22-06-2006

    ISSUE No: P0

    1.0 SCOPE

    1.1 This specification covers the design, material, construction features, manufacture,

    inspection and testing at the Vendors / his SUB-Vendors Works, delivery to site and

    performance testing of metal-enclosed Medium Voltage Switchgear of voltage notexceeding 1100 V AC.

    2.0 CODES & STANDARDS

    2.1 The design, construction, manufacture and performance of equipment shall conform to

    latest applicable standards and comply with all currently applicable statutes, regulations

    and safety codes in the locality where the equipment will be installed. Nothing in this

    specification shall be construed to relieve the VENDOR of this responsibility.

    2.2 Equipment shall conform to the latest applicable Standards as mentioned in Data Sheet

    A2. In case of conflict between the Standards and this specification, the requirements of

    this specification shall govern.

    3.0 SHEET METAL WORK

    3.1 The switchgear frame shall be fabricated using 1.6mm thick cold rolled mild steel plate

    as per general industry standard.

    3.2 Hinged doors shall be fabricated using sheet steel of thickness not less than 2 mm cold

    rolled and fixed covers using sheet steel not less than 1.6 mm cold rolled, smoothly

    finished levelled and free from flaws. Mounting plates shall be fabricated from 3.15mm

    thick cold rolled DD sheet steel.

    3.3 All panel edges and door edges shall be reinforced against distortion by rolling, bending

    or by the addition of welded reinforcement members.

    3.4 Cut outs shall be true in shape and devoid of sharp edges.

    3.5 The complete structure shall be rigid, self-supporting, and free from vibration, twists and

    bends.

    4.0 PAINTING

    4.1 All sheet steelwork shall be phosphated in accordance with the following procedure and

    in accordance with applicable standards mentioned in Data Sheet-A2.

    4.2 Oil, grease, dirt and swarf shall be thoroughly removed by emulsion cleaning.

    4.3 Rust and scale shall be removed by pickling with dilute acid followed by washing with

    running water, rinsing with slightly alkaline hot water and drying.

    4.4 After phosphating, thorough rinsing shall be carried out with clean water, followed by

    final rinsing with dilute dichromatic solution and oven drying.

    4.5 The phosphate coating shall be sealed by the application of two coats of ready mixed,

    stoving type zinc chromate primer. The first coat may be flash dried while the second

    coat shall be stoved.

    4.6 After application of the primer, two coats of finishing synthetic enamel paint shall be

    applied, with each coat followed by stoving. The second finishing coat for the external of

    panels shall be applied after completion of tests.

  • 8/13/2019 PCPL-0532-4-407-04-08

    2/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 2 of 13

    DATE:22-06-2006

    ISSUE No: P0

    4.7 Each coat of primer and finishing paint film on steel shall not be less than 100 microns,

    and shall not be more than 150 microns thickness.

    4.8 The final finished thickness of paint film on steel shall not be less than 100 microns, and

    shall not be more than 150 microns.4.9 Finished painted appearance of equipment shall present an aesthetically pleasing

    appearance, free from dents and uneven surfaces.

    5.0 CONSTRUCTIONAL FEATURES

    5.1 Switchgear shall be:

    a) Of the metal clad, indoor, floor mounted modular typeb) Made up of the requisite vertical sectionsc) Of dust and vermin proof constructiond) Provided with a degree of enclosure protection grade of IP 52.e) Easily extendable on both sides by the addition of vertical sections after removing

    the end covers

    f) Provided with a metal sill frame made of structural steel channel section properlydrilled for mounting the Switchgear along with necessary mounting hardware.

    Hardware shall be zinc plated and passivated.

    g) Provided with name plates on the front and rear indicating the switchgeardesignation

    h) Provided with cable entry facilities at top with thick removable gland plates ofthickness as per general industry standard on POWER panels with necessary cableglands. These plates shall be non-magnetic.

    i) Of uniform height of not more than 2450 mmj) Of single front execution as specified in Data Sheet-Ak) Provided with neoprene gaskets all round the perimeter of adjacent panels, panel

    and base frame, removable covers and doors

    l) Provided with busbars running at the top or bottom, as required, all along the lengthof the switchgear in a separate sheet steel enclosure.

    5.2 Operating devices shall be provided only at the front of the switchgear. No equipment

    requiring manual operation shall be located at less than 250mm above ground level.

    5.3 The switchgear shall be divided into distinct vertical sections each comprising:

    a) A completely metal enclosed busbar compartment running horizontally.b) Individual feeder modules arranged in multi-tier formation. It is essential that the

    modules are integral multiplies of the basic unit size to provide for flexibility in

    changes, if any, at site.

  • 8/13/2019 PCPL-0532-4-407-04-08

    3/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 3 of 13

    DATE:22-06-2006

    ISSUE No: P0

    c) Enclosed vertical busbars serving all modules in the vertical section. For safetyisolation of the vertical bus bars, insulating barrier with cut-outs shall be provided to

    allow the power stab contacts to engage with vertical busbars.

    d) A vertical cable alley covering the entire height. The cable alley shall be 500 mmwide for circuit breaker controlled modules.e) Separation barrier between Main bus bar auxiliary Power & control buses as

    required shall be located to enable easy identification, maintenance and segregation

    from the main power buses. Tap-off connections from these buses shall be arranged

    separately for each vertical section.

    5.4 Each vertical section shall be equipped with space heaters, which may be located in the

    cable alley.

    5.5 One metal sheet shall be provided between two adjacent vertical sections running to the

    full height of the switchgear except for the horizontal busbar compartment. However,

    each shipping section shall have metal sheets at both ends.

    5.6 All equipment associated with a single circuit shall be housed in a separate module

    compartment of the vertical section. The compartment shall be sheet steel enclosed on all

    sides and the rear, with rubber grommets provided on the cable alley side for power and

    control cable entry. The front of the compartment shall be provided with a hinged door.

    Components mounting details and panel fabrication details shall be submitted by

    VENDOR for PURCHASERs approval.

    5.7 For draw-out type modules, only the handles of control and selector switches, push

    buttons, knobs & cut-outs for lamps and meters shall be arranged on the front doors of

    the respective compartments to permit operation without opening the door. On circuit

    breaker controlled circuits, protective relays shall be mounted on the front door of the

    compartment. All other equipment pertaining to a circuit shall be mounted on the

    withdrawable chassis. All cut-outs shall be provided with gaskets for dust proofing.

    5.8 Current transformers shall not be directly mounted on the buses. Current transformers on

    circuit breaker controlled circuits shall be mounted on the fixed portion of the

    compartment.

    5.9 In breaker compartments, external cable connections shall be carried out in separate

    cable compartments for power and control cables.

    5.10 After isolation of the power and control connections of a circuit, it shall be possible to

    safely carry out maintenance in a compartment with the busbars & adjacent circuits live.

    5.11 The withdrawable chassis shall move on suitable guides and on suitable plated steel or

    stainless steel rollers or balls to facilitate easy and smooth withdrawal.

    5.12 Cable alleys shall be provided with suitable hinged doors. It shall be possible to safely

    carry out maintenance work on cable connections to any one circuit with the busbars and

    adjacent circuits live. Adequate number of slotted cable support arms shall be provided

    for clearing the cables.

    5.13 Rear of single front switchgear shall be provided with removable covers. It shall be

    possible for one person to remove and fix the removable panel.

  • 8/13/2019 PCPL-0532-4-407-04-08

    4/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 4 of 13

    DATE:22-06-2006

    ISSUE No: P0

    5.14 All doors shall be provided with concealed type hinges and captive screws.

    5.15 The withdrawable chassis housing circuit breakers shall be of the fully draw out type.

    5.16 The withdrawable chassis housing feeder control equipment not incorporating circuit

    breakers/common control transformers of big size shall be of fixed type

    5.16.1 Fixed Type Withdrawable ChassisIn this type of construction, all power connections to the equipment mounted on the

    withdrawable chassis shall be of the bolted type. All control circuit connections to

    equipment mounted on the withdrawable chassis shall be carried out through

    conventional terminal blocks mounted in the respective chassis. It shall be possible to

    draw out the chassis after unbolting/unscrewing all the power and control circuit

    connections to the equipment mounted on the withdrawable chassis.

    5.17 Interchangeability

    5.17.1 All identical equipment and corresponding parts including chassis of draw out modulesof the same size and rating shall be interchangeable, without having to carryout

    modifications. For trouble free interchangeability, the draw out arrangements shall be

    designed such that normal dimensional variations are taken care of by self-aligning

    feature of the modules.

    5.17.2 Components and equipment of identical rating which are not fully interchangeable are

    liable for rejection. VENDOR shall replace all such equipment by interchangeable

    equipment at his cost.

    5.18 The draw-out contacts shall be only between copper/copper alloy/aluminium faces,

    which are silver or tinplated. The contact design shall be such that there should be no

    arcing/deformation under the associated peak short-circuit current to be carried.

    5.19 Switchgear shall be designed in such a way that all component equipment and bus-bars

    operate satisfactorily without exceeding their respective maximum permissible rise in

    temperature under ambient temperature conditions prevailing within the switchgear

    cubicle, with reference ambient temperature outside the switchgear cubicles as specified

    in Data Sheet-A1.

    5.20 Provision of ventilating louvers is considered undesirable. If ventilating louvers are

    considered essential by the VENDOR, these may be provided. However, all ventilating

    louvers shall be provided with fine-screened brass or GI meshes to prevent entry of

    vermin and dust.

    6.0 MODULE TYPES

    6.1 The various types of modules indicating the control requirements of each type are

    detailed in the enclosed Single line diagram.

    6.2 Physical size of compartment for each type of control and current rating shall be so

    chosen that all the basic and additional equipment can be housed in the compartment. No

    equipment/devices associated with any particular circuit shall be permitted to be

    mounted in any other circuit module.

    7.0 MAIN & AUXILIARY BUSES

  • 8/13/2019 PCPL-0532-4-407-04-08

    5/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 5 of 13

    DATE:22-06-2006

    ISSUE No: P0

    Main Buses & Taps

    7.1 Switchgear shall be provided with three phases or three phase and neutral busbars as

    specified in Data Sheets.

    7.2 Busbars shall be of uniform cross section throughout the length of the switchgear, and upto the terminals of the incoming feeder circuit breaker/ switch.

    7.3 The busbars shall be made of high conductivity copper or aluminium alloy of E91E

    grade as specified in Data Sheets.

    7.4 Busbars shall be provided with at least the minimum clearances in air as per applicable

    standards for a 500V, 3 phase system.

    7.5 All bus-bars, bus-taps shall be insulated with close fitting sleeve of hard, smooth, dustand dirt free plastic insulation of high dielectric strength (450 V/mil) to provide a

    permanent high dielectric non-ageing and non-tracking protection; impervious to water,

    tropical conditions and fungi. The insulation shall be non-inflammable and self-extinguishing and in fast colours to indicate phases. The joints shall be insulated in such

    a way as to provide for accessibility of contact bolts for maintenance. Joints shall be

    covered with removable moulded shrouds made out of fiber glass reinforced polyester.

    The dielectric strength and properties shall hold good for the temperature range of 0oC to

    90oC. If the insulating sleeve is not coloured but black, busbars shall be colour-coded

    with coloured bands at suitable intervals.

    7.6 Busbars shall be adequately supported and braced to withstand the stresses due to the

    specified short circuit currents for the associated switchgear. Busbar supports shall be

    made of Hylam sheets, glass reinforced moulded plastic material, Permali wood or cast

    resin.

    7.7 Separate supports shall be provided for each phase of the busbars. If a common support

    is provided for all three phases, anti-tracking barriers shall be incorporated.

    7.8 Busbar joints shall be complete with high tensile steel bolts and Belleville washers and

    nuts. Busbars shall be thoroughly cleaned at the joint locations and suitable contact

    grease shall be applied just before making a joint.

    7.9 Auxiliary BusesAuxiliary buses for control power supply, space heater power supply or any other

    specified service shall be provided. These buses shall be insulated, adequately supported

    and sized to suit specific requirements. The material of control power supply buses shall

    be electrolytic copper. The material for space heater power supply buses shall be same

    as that for the main power buses. Auxiliary busbars and necessary connections to the

    associated circuits shall be in the VENDORS scope.

    8.0 CIRCUIT BREAKERS

    8.1 Circuit breakers shall be provided with:

    8.1.1 The air break draw out type, mounted along with its operating mechanism on a wheeled

    carriage moving on guides, designed to align correctly and allow easy movements.

    8.1.2 The shunt and/or series trip type as specified in Data Sheet-A1

  • 8/13/2019 PCPL-0532-4-407-04-08

    6/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 6 of 13

    DATE:22-06-2006

    ISSUE No: P0

    8.1.3 An operating mechanism of the type specified in Data Sheet-A1

    8.1.4 Mechanically operated targets to show Open, Closed, Service and Test positions

    of the circuit breaker

    8.1.5 Mechanically operated, red trip push button, shrouded to prevent accidental operation

    8.1.6 Locking facilities in the Service, Test, and Isolated, positions. In test position, the

    breaker will be tested without energising the power circuits. The breaker shall remain

    fully housed inside the compartment in the test position.

    8.1.7 6 N/O and 6 N/C potential free auxiliary switch contacts, rated for 6A at 240V AC and

    1A (inductive breaking at 220V DC).

    8.1.8 Red, Green and Amber indicating lamps to show Closed, Open, and Auto-tripconditions of the circuit breaker when breaker operation is controlled by a control

    switch.

    8.1.9 Circuit breakers shall be provided with in-built microprocessor based over load, shortcircuit and earth fault releases with adjustable time delay settings.

    8.2 Circuit breakers shall be provided with the following interlocks:

    8.2.1 It shall not be possible to plug-in a closed circuit breaker, or to draw out a circuit breaker

    in the closed position.

    8.2.2 It shall not be possible to operate a circuit breaker unless it is in the fully plugged-in, test,

    or fully isolated position.

    8.3 Circuit breaker closing and trip coils shall be rated for satisfactory operation on a control

    supply system indicated in Data Sheet-A1.

    8.4 Whenever specified in Data Sheet-A1, breakers shall be provided with castle key

    interlocking device to prevent paralleling of two breakers.

    8.5 Closing and trip coil shall operate satisfactorily under the following conditions of supply

    voltage variation:

    8.5.1 Closing coils - 85% to 110% of rated voltage

    8.5.2 Trip coils - 50% to 110% of rated voltage

    8.6 In addition to the adjustable current setting range specified in the Data Sheet, short

    circuit releases shall be provided with at least four adjustable time delay settings. If it is

    not possible to provide the specified adjustable current setting range for the short circuitreleases, shunt trip circuit breakers shall be offered as indicated in Data Sheet - B by the

    VENDOR.

    8.6.1 Each of the foregoing releases shall be provided with a single pole, double throw, and

    potential free alarm contact rated for 0.5A, 220V DC.

    8.7 Operating Mechanism

    8.7.1 Circuit breaker shall be provided with a manual operating mechanism or power operated

    mechanism as specified in Data Sheet-A1.

  • 8/13/2019 PCPL-0532-4-407-04-08

    7/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 7 of 13

    DATE:22-06-2006

    ISSUE No: P0

    8.7.2 Manually operated mechanism shall be of the spring charging stored energy type, unless

    otherwise specified in Data Sheet-A1.

    8.7.3 Power operated mechanism shall be of the motor wound spring charging stored energy

    type.8.7.4 The closing action of the circuit breaker shall charge the tripping spring ready for

    tripping.

    8.7.5 Speed of closing of contacts shall be independent of the speed with which the handle is

    operated.

    8.7.6 All stored energy mechanisms shall be provided with mechanical indicators to show the

    Charged and Discharged conditions of the spring.

    8.7.7 Circuit breakers provided with stored energy operating mechanisms shall be provided

    with the following interlocks:

    a) The circuit breaker shall not close unless the spring is fully charged.b) Shocks, vibrations, or failure of springs shall not operate the breaker or prevent

    intended tripping.

    8.7.8 Power operated mechanisms shall be:

    a) Provided with a universal motor suitable for operation on AC and DC controlsupplies specified in Data Sheet-A1 with voltage variation from 85% to 110% rated

    voltage.

    b) Designed to enable a continuous sequence of closing and opening operation as long

    as power is available and at least one opening operation on power supply failure.

    c) Provided with emergency manual charging facilitiesd) Provided with facilities for remote panel closing and opening operations whenever

    specified in Data Sheets as per breaker module designation and respective enclosed

    control scheme drawing.

    8.7.9 Spring charging time for power operated mechanism shall not exceed 15 seconds.

    8.7.10 Power operating mechanisms shall be provided with the following additional features:a) Closing of the circuit breaker shall automatically initiate recharging of the spring

    ready for the next closing stroke

    b) The motor shall be mechanically de-coupled as soon as the emergency manualcharging handle is coupled

    c) The circuit breaker mechanism shall make one complete closing operation once thecontrol switch has been operated and the first device in the control scheme has

    responded even though the control switch is released before the closing operation is

    complete provided there is no counter trip impulse.

    d) Closing controls shall be so arranged that only one closing operation of the circuitbreaker shall result from each close initiating impulse, even if the breaker trips while

    the initiating device is held in the Close position. An electrical anti-pumping relay

  • 8/13/2019 PCPL-0532-4-407-04-08

    8/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 8 of 13

    DATE:22-06-2006

    ISSUE No: P0

    shall be provided on the circuit breaker chassis for this purpose, incorporated in the

    circuit breaker.

    8.8 Protection Co-ordination:

    It shall be the responsibility of the VENDOR to fully co-ordinate the overload and shortcircuit tripping of the circuit breakers with the upstream and downstream circuit

    breakers/motor starters, to provide satisfactory discrimination.

    9.0 MOULDED CASE CIRCUIT BREAKERS

    9.1 Moulded case circuit breakers (MCCBs) shall be provided when called for in Data Sheet-

    A1, for use in lieu of switch fuse units. The MCCBs shall conform to the latest

    applicable standards.

    9.2 MCCBs in AC circuits shall be of triple pole construction arranged for simultaneous 3pole manual closing and opening and for automatic instantaneous tripping on short

    circuit. If indicated in Data Sheet-A1, power closing device for remote operation may beprovided. Operating mechanism shall be quick-make, quick-break and trip-free type.

    The ON, OFF & TRIP positions of the MCCB shall be clearly indicated and visible to

    the operator when mounted as in service. Front of board operating handle shall be

    provided.

    9.3 MCCBs shall be capable of withstanding the thermal stresses caused by overloads and

    the mechanical stress caused by the peak short circuit current of value associated with the

    switchgear rating. The maximum tripping time under short circuit shall not exceed 20

    milliseconds.

    9.4 The instantaneous short circuit release shall be so chosen by the VENDOR as to operate

    at a current in excess of the peak transformer inrush current and a range of settings shallbe provided for the PURCHASERs selection.

    9.5 MCCB terminals shall be shrouded and designed to receive cable lugs for cable sizes

    relevant to circuit ratings.

    10.0 MINIATURE CIRCUIT BREAKERS

    10.1 Miniature circuit breakers for use on cubicle space heater control circuits shall comply

    with the requirements of applicable standards, unless otherwise mentioned in Data Sheet-

    A1.

    11.0 EARTH LEAKAGE CIRCUIT BREAKERS

    11.1 Earth leakage breakers for use on cubicle space heater control circuits shall comply with

    the requirements of applicable standards, unless otherwise mentioned in Data Sheet-A1.

    12.0 RCBO (With Overload and Short Circuit protection)

    12.1 RCBO breakers for use on VT secondary for overload and short circuit protection shall

    comply with the requirements of applicable standards, unless otherwise mentioned in

    Data Sheet-A1.

    13.0 CURRENT TRANSFORMERS

    13.1. Current transformers shall be of the cast resin dry type.

  • 8/13/2019 PCPL-0532-4-407-04-08

    9/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 9 of 13

    DATE:22-06-2006

    ISSUE No: P0

    13.2. Current transformer shall have a short time current withstand rating equal to the shorttime current withstand rating of the associated switchgear for one second for breaker

    feeders. CTs on feeders with fuse shall have withstand capacity equal to let through

    fault current of associated fuse.

    13.3. The minimum performance requirements of current transformers shall be as per thesingle line diagram enclosed.

    13.4. Notwithstanding the above clause 11.3, it shall be the Vendors responsibility to co-ordinate the current transformer burden with the requirements of relays, instruments and

    leads associated with that particular current transformer.

    13.5. Test links shall be provided in both secondary leads of the CTs to easily carry outcurrent and phase angle measurement tests.

    13.6. All current transformers shall be earthed through a separate earth link on the terminalblock to permit easy measurement of the current transformer insulation resistance.

    14.0 VOLTAGE TRANSFORMERS

    14.1 Voltage transformers shall be of cast resin dry type.14.2 The minimum performance requirements of voltage transformers shall be as per the

    single line diagram enclosed.

    14.3 All secondary windings of voltage transformers including open delta windings shall berated for 110 V/ 3 per phase.

    14.4 Voltage transformer shall have a continuous over voltage factor of 1.2 and short timeover voltage factor as follows :

    1.5 for 30 seconds in case of effectively earthed system

    1.9 for 8 hours in case of non-effectively earthed system

    14.5 Voltage transformers shall be complete with suitable rated primary and secondaryMCBs. The rupturing capacity rating of the associated switchgear shall be brought down

    to the capacity of MCB by use of fault limiting devices mounted close to the bus.

    14.6 It shall be possible to replace voltage transformers without having to de-energise themain bus bars.

    14.7 The terminals of V.T. secondary and tertiary windings, which are required to beconnected to earth, shall be earthed by an isolating link without fuse.

    15.0 INDICATING INSTRUMENTS & METERS

    15.1 Electrical indicating instruments shall be of minimum 96mm square size, 90 degree scaledeflection with a class of accuracy of 0.5/1.0 as applicable, suitable for flush mounting.

    15.2 Indicating instruments shall have provision for zero adjustment from outside the cover.15.3 Instrument dials shall be parallex free with black numerals on a white background dial.15.4 Watt-hour metes shall be of the direct reading electrodynamometer type complete with

    cyclometer type registering dials and reverse running stop.

  • 8/13/2019 PCPL-0532-4-407-04-08

    10/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 10 of 13

    DATE:22-06-2006

    ISSUE No: P0

    16.0 INDICATING LAMPS

    16.1 Indicating lamp shall be:* Of the multiple LED type and of low watt consumption

    * Provided with step-down transformer

    * Provided with translucent lamp covers of colours Red, Green and Amber as

    Indicated in the control wiring diagrams.

    16.2 Bulbs and lenses shall be easily replaceable from the front17.0 CONTROL & SELECTOR SWITCHES

    17.1 Control and selector switches shall be:Of the rotary type with shrouded contacts

    Adequately rated for the purpose intended (min. acceptable rating is 10A continuous at240V AC and 1A (inductive break) 220V DC.

    Provided with escutcheon plates clearly marked to show the positions

    17.2 Control switches shall be:

    Of the spring return to normal type

    Provided with pistol grip type handles

    17.3 Control switches for circuit breaker control shall be provided with:

    Contact development as specified in bill of material of enclosed drawings.

    17.3.1 Wherever specified in data sheets, control switches with built-in flashing typediscrepancy lamps shall be provided to control circuit breakers in lieu of the normal

    control switch, red, green and amber indicating lamps. The discrepancy lamp shall be

    replaceable from the front of the module door.

    17.3.2 Selector switches shall be:Of the maintained contact stay put type. Switches in ammeter circuits shall have make-

    before-break type contact

    Provided with oval handles

    18.0 PUSH BUTTONS

    18.1 Push buttons shall be:Of the momentary contact, push to actuate type rated to carry 10A at 240V AC & 1A

    (inductive breaking) at 220V DC

    Fitted with self reset, 2 NO and 2 NC contacts

    Provided with integral escutcheon plates marked with its function

    18.2 Start, Open, Close push buttons shall be green in colour18.3 Stop push buttons shall be red in colour

  • 8/13/2019 PCPL-0532-4-407-04-08

    11/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 11 of 13

    DATE:22-06-2006

    ISSUE No: P0

    18.4 All other push buttons shall be black in colour19.0 SPACE HEATER

    Space heaters for switchgear panels shall be:

    Suitable for operation on a supply system specified.

    Provided with single pole MCB with overload and short circuit release whenever space

    heater transformer is provided.

    Provided with humidistat to cut off the heaters at 45 degree centigrade.

    20.0 POWER CABLE TERMINATIONS

    20.1 Suitable compression type, heavy duty brass cable glands with check nuts, rubber sealingring and brass washers mounted on a removable gland plate shall be provided to support

    all power and control cables entering the switchgear, if asked for in Data Sheet-A1.

    Cable glands shall incorporate built-in facilities for earthing the wire armour of cables.Cable glands shall be plated to avoid correction.

    20.2 Power cable glands and crimping type lugs shall be supplied to suit the cable sizesindicated. Approximate quantity of control cable glands for different types of modules

    are indicated in the module drawing, bill of material. If during course of detailed

    engineering of the switchgear it is found necessary to provide more glands or glands of

    higher size than those envisaged, the VENDOR shall provide and accommodate the same

    20.3 The VENDOR shall select the power cable glands and lugs based on the cable sizesprovided at Data Sheet conforming to:

    Type of power cable: 650/1100 V grade stranded aluminium conductor, PVC insulated,

    PVC sheathed, armoured and overall PVC sheathed cable conforming to IS.

    20.4 For supporting and clamping power cable cores at regular intervals inside the cablealleys, suitable slotted angles, up to the respective terminal blocks, shall be provided.

    20.5 Necessary crimping type of tinned-copper cable lugs for connecting the individual coresto the respective terminals shall be provided.

    21.0 INTERNAL WIRING

    21.1 Wiring inside the switchgear shall be carried out with 650/1100 V grade, FRLS PVCinsulated, stranded conductor wires. Min. size of conductor for power circuits is 4

    sq.mm copper or equivalent size aluminium conductor. Control circuits shall be wired

    with copper conductor of at least 2.5 sq.mm for CT circuits and 1.5 sq.mm for othercircuits, the number and size of strands shall be 7 of 0.67 mm and 0.5 mm diameter

    respectively.

    21.2 Engraved identification ferrules, marked to correspond with the wiring diagrams shall befitted to each wire. Ferrules shall be of yellow colour with black lettering.

    21.3 Wires forming part of a tripping circuit of circuit breaker shall be provided with anadditional red ferrule marked T.

    21.4 Spare auxiliary contacts of all equipment forming part of the switchgear shall be wiredup to the terminal blocks.

  • 8/13/2019 PCPL-0532-4-407-04-08

    12/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 12 of 13

    DATE:22-06-2006

    ISSUE No: P0

    21.5 Wiring for equipment if supplied by the PURCHASER for which the VENDOR has toprovide cut-outs (where indicated in the data sheets) shall be provided upto the terminal

    blocks.

    21.6 Spare and unassigned modules shall be complete with internal wiring.21.7 Wiring shall be terminated on preferably stud type terminal blocks such that the wires

    are connected by cable lugs with nuts and washers/lock nuts.

    21.8 Not more than two connections shall be made on any one terminal.22.0 TERMINAL BLOCKS

    22.1 Terminal blocks (both for power and control circuits) shall be of reputed make speciallyfor CT and VT circuits. It shall comprise finely threaded pairs of brass studs of at least 6

    mm diameter, links between each pair of studs, washers, nuts and lock nuts. The studs

    shall be securely locked within the mounting base to prevent their turning. Insulated

    barriers shall be provided between adjacent terminals.22.2 Terminals for circuits with voltage exceeding 125 V shall be shrouded. Terminal blocks

    shall be grouped depending on circuit voltage. Different voltage groups of terminal

    blocks shall be segregated.

    22.3 Terminal blocks shall be adequately rated to carry the current of the associated circuit.Minimum rating of the terminal block is 10A.

    22.4 Terminals shall be numbered for identification as per enclosed drawings. Engravedwhite-on-black labels shall be provided on the terminal blocks, describing the function of

    the circuit.

    22.5 Where duplication of a terminal block is necessary, it shall be achieved by solid bondinglinks.22.6 Terminal blocks for CT secondary lead wires shall be provided with shorting and

    disconnecting/earthing facilities.

    22.7 Terminal blocks shall be arranged with at least 100 mm clearance between two sets ofterminal blocks.

    23.0 LABELS

    23.1 All labels shall comprise white letters on a black background23.2 Labels shall be made of non-rusting metal or 3-ply lamicoid, or engraved PVC23.3 Labels shall be properly fixed, with provision to prevent dis-rotation due to expansion23.4 .Size of lettering shall be 6 mm, unless otherwise specified.24.0 EARTHING

    24.1 Each POWER circuit shall be provided with a earth busbar running along with entirelength of the board. Materials and size of the earth busbar shall be as specified in data

    sheets. At either end of the earth bus, one (1) clamp type terminal with nuts, bolts and

    washers shall be provided for connecting the PURCHASERS earthing conductor of size

    and material indicated in data sheets. In case the earth bus is provided near top of the

  • 8/13/2019 PCPL-0532-4-407-04-08

    13/13

    DOCUMENT No

    PCPL-0532-4-407-04-08

    MV SWITCHGEAR SECTION - 4

    PAGE: 13 of 13

    DATE:22-06-2006

    ISSUE No: P0

    switchgear, one down comer at either end shall be provided for connection to the

    PURCHASERs earthing conductor.

    24.2 Earth busbar shall be supported at regular intervals.24.3 Positive connection between all the frames of equipment mounted in the switchboard and

    earth busbar shall be provided by using insulated copper wire/bare busbars of cross

    section equal to that of the busbar, or equal to half the size of circuit load current

    carrying conductor, whichever is smaller.

    25.0 TESTS

    25.1 Switchgear shall be subjected to following tests as per relevant standards along withfollowing tests:

    25.1.1 Temperature rise test on power circuits.25.1.2 Short time current tests on power circuits.25.1.3 Mechanical operation test.25.1.4 Insulation resistance at 500V D.C before/after 1 minute H.V. Test.25.1.5 Electrical control, interlock and sequential operation tests.25.1.6 Verification of wiring as per approved schematic25.1.7 BIDDER shall submit available type test reports of temperature rise and short circuit

    tests of similar switchgear. In addition, calculations of temperature rise shall be

    submitted for approval.

    25.1.8 Routine tests shall be carried out on all associated equipment supplied with switchgear,as per relevant standards. Type test certificates of all associated equipment shall befurnished.

    25.1.9 Certified copies of all type and routine test certificates shall be submitted for thePURCHASERs approval before dispatch of the switchgear.

    26.0 DRAWINGS & DATA

    26.1 As part of proposal BIDDER shall furnish the following drawings and data:a) For each switchgear, overall dimension drawing showing front view, plan, elevation

    and Cross-section in advance soon after the receipt of order.

    b) Data Sheet-B shall be completely filled in.

    26.2 All drawings and data sheets shall be annotated in English.


Recommended