+ All Categories
Home > Documents > PDS2-H Weather Compensator with Modbus … · with Modbus Communication ... The PDS-H controller...

PDS2-H Weather Compensator with Modbus … · with Modbus Communication ... The PDS-H controller...

Date post: 10-Jun-2018
Category:
Upload: lykhanh
View: 247 times
Download: 2 times
Share this document with a friend
9
Online store: www.syxthsense.com Enquiries: T: 0844 840 3100 F: 0844 840 3200 Copyright © 2011 SyxthSense Ltd. All rights reserved - 06/2011 PS CT2.40 - 1/9 PDS2-H Weather Compensator with Modbus Communication The PDS2-H is a weather compensator designed to control accurately heating systems. The controller calculates the required flow temperature setpoint based on the outside air temperature. This allows the heating water temperature to be adjusted according to the weather conditions outside. Room temperature sensor option can shift the supply water temperature setpoint based on the internal heat gains or losses providing improved energy efficiency and comfort. Outside ECO feature will disable automatically the pump output when the outside air temperature exceeds the ECO setpoint. The controller has built-in LCD display that indicates the current status of the controller and can be used for the controller configuration. The controller is easy to use and and has DIN-rail mounting. The built-in RS485 Modbus communication allows the controller to be connected to central supervisory system such as WebBiter embedded web-server or to a BMS system. Product sheet CT2.40 Type PDS2-H Model Types Model Description PDS2-H PDS2-H Weather Compensator with Modbus Communications Technical Data Power supply 24Vac/dc (20…26V), NOTE: 3-point and thermic actuators require separate AC supply. Inputs 3 x Pt1000 Temperature (WATER, OUTSIDE, ROOM) 1 x Analogue / Digital Outputs 4 x 0..10Vdc (Control Valve, Alarm, Night (ECO), and Time Switch Outputs 4 x 24Vac Triacs, 1A maximum (3-Point or Thermic Actuator, Pump and Alarm Output) Communications RS-485 Modbus RTU, 9600/19200/38400 bps, 8 data bits, Parity None, 1 Stop Bit (Up to 128 devices per segment) Internal Clock Inaccuracy max +/- 1min/year Battery Backup 1 Week (for clock) Set Point Adjustment CURVE SHIFT +/-25°C (Adjustable in the user mode) PUMP ECO SP +10..+35°C (Adjustable in the configuration mode) ROOM SETPOINT +10..+30°C (Adjustable in the configuration mode); INTERNAL OR EXTERNAL CURVE SHIFT +/-25°C (Adjustable in the configuration mode) Provides Boost / Setback using Internal Time Clock or External Contacts COMPENSATION CURVE Compensation curve (3 or 5 points) with minimum and maximum flow temperature settings Display LCD Display, Automatically Rotating Display for the User Access to all configuration parameters Buttons 4 Touch Buttons for the Programming and User Configuration Wiring Terminals 1.5 mm2 Operating Humidity 0..95% rH Protection Class IP20
Transcript

Online store: www.syxthsense.com

Enquiries: T: 0844 840 3100 F: 0844 840 3200

Copyright © 2011 SyxthSense Ltd. All rights reserved - 06/2011

PS CT2.40 - 1/9

PDS2-H Weather Compensator with Modbus Communication

The PDS2-H is a weather compensator designed to control accurately heating systems. The controller calculates the required flow temperature setpoint based on the outside air temperature. This allows the heating water temperature to be adjusted according to the weather conditions outside.

Room temperature sensor option can shift the supply water temperature setpoint based on the internal heat gains or losses providing improved energy efficiency and comfort.

Outside ECO feature will disable automatically the pump output when the outside air temperature exceeds the ECO setpoint.

The controller has built-in LCD display that indicates the current status of the controller and can be used for the controller configuration.

The controller is easy to use and and has DIN-rail mounting.

The built-in RS485 Modbus communication allows the controller to be connected to central supervisory system such as WebBiter embedded web-server or to a BMS system.

Product sheet CT2.40

Type PDS2-H

Model Types Model Description

PDS2-H PDS2-H Weather Compensator with Modbus Communications

Technical Data Power supply 24Vac/dc (20…26V),

NOTE: 3-point and thermic actuators require separate AC supply.

Inputs 3 x Pt1000 Temperature (WATER, OUTSIDE, ROOM)1 x Analogue / Digital

Outputs 4 x 0..10Vdc (Control Valve, Alarm, Night (ECO), and Time Switch Outputs4 x 24Vac Triacs, 1A maximum (3-Point or Thermic Actuator, Pump and Alarm Output)

Communications RS-485 Modbus RTU, 9600/19200/38400 bps, 8 data bits, Parity None, 1 Stop Bit (Up to 128 devices per segment)

Internal Clock Inaccuracy max +/- 1min/year

Battery Backup 1 Week (for clock)

Set Point Adjustment CURVE SHIFT +/-25°C (Adjustable in the user mode)

PUMP ECO SP +10..+35°C (Adjustable in the configuration mode)

ROOM SETPOINT +10..+30°C (Adjustable in the configuration mode);

INTERNAL OR EXTERNALCURVE SHIFT

+/-25°C (Adjustable in the configuration mode)Provides Boost / Setback using Internal Time Clock or External Contacts

COMPENSATION CURVE

Compensation curve (3 or 5 points) with minimum and maximum flow temperature settings

Display LCD Display, Automatically Rotating Display for the UserAccess to all configuration parameters

Buttons 4 Touch Buttons for the Programming and User Configuration

Wiring Terminals 1.5 mm2

Operating Humidity 0..95% rH

Protection Class IP20

SyxthSense Ltd

PS CT2.40 - 2/9

APPLICATION PROFILE PDS2 controllers have two application profiles for different applications: PDS2-V and PDS2-H. PDS 2-V application profile is selected as a default. To change the application profile to PDS2-H follow the following instructions.

The application profile can be selected when the supply voltage is connected to the device.

1. Press the ”+” and ”-” buttons simultaneously for five seconds.

The device version shows on the display for five seconds.

1.1VER

2. Press the OK button when ”APPL” is shown on the display.

”APPL” text starts to flash.

APPL=VENT

WARNING: The device returns to user mode if the buttons are not pushed during 10 seconds.

3. Select the wanted application by pushing the "+" and "-" buttons.

4. Push the OK button.

The confirmation question appears on the display.

APPLSURE?

5. Press the OK button to accept the application selection.

NOTE: You can return to previous display without accepting the selection by pressing the M button.

APPLICATION DIAGRAM The PDS-H controller has been designed to operate stand-alone as a heating weather compensator. The diagram below illustrates the typical application.

TE2

BURNER

PDS2-H

TE1

TE3

ROOMSENSOR

*1

*1 OFF when TE2 > SPpump. Alternatively an external time clock,

TIMECLOCK

0..10Vdcor3-POINTorThermic

MODBUSCOMMS

OUTSIDESENSOR

PDS2-O or Modbus Master can switch to NIGHT (ECO) mode.

FLTA

WIRELESSROOMSENSOR

AI4

Technical Data Cont’d.. CE Approval Directive 2004/108/EYEN61000-6-3: 2001 (Emissions)EN61000-6-2: 2001 (Immunity)

Mounting DIN-rail Mounting

Overall size 53W x 90H x 58D mm

SyxthSense Ltd

PS CT2.40 - 3/9

The controller measures the outside air temperature and calculates the effective flow setpoint using a built-in compensation curve. When the outside air temperature is colder the supply water temperature is increased and when it is warm outside the required water temperature is lowered.

FLO

W T

EM

PE

RAT

UR

E

OUTSIDE TEMPERATURE

20

-20

80

-10 0 10 20 30

P5

P4P3

P2

P1

P5 works also asmax temperature limit

P1 works also asmin temperature limit

PDS2 COMPENSATION CURVE

The optional room temperature sensor will automatically compared the room temperature to the required setpoint and adjust the compensation curve upwards and downwards as required.

PDS 2-HGo

G12

3456789

12

14

Go

1011

13Go

A+

B-

16

18

15

17

A1

B1

AL

P

TE2

TE3

AI4

TE1

AO1

AO2

AO3

AO4

Supply24 Vac/dc

Modbus

TemperaturesensorsPt 1000

Analog Input

Control Valve out 0-10V / 10-0V

0V

Modbus

Fuse1,5A

Open

Pump Relay out

CloseMotor out

Alarm Relay out

24 Vac/dc

0 V

Pt 1000 WATER

Thermal

24VacFeed

M

3-Point

M

Pt 1000 OUT

Pt 1000 ROOM

0V

Alarm (0V normal 10V fault )

OUT=

SETB

ACK/

BOO

ST/N

IGH

T

TIME SWITCH ”OFF”=0V ”ON”= 10V

NIGHT (ECO) MODE

BOO

ST/

SETA

BCK

Pump

Alarm

EXTE

RN

ALC

ON

TAC

TS /

CLO

CK

0V

CONNECTION DIAGRAM WARNING:The electrical installation, device connection and commissioning can only be carried out by qualified professionals and according to the local wiring regulations!

USER DISPLAY

M 'PROGRAM' Key

'+' and '-' Keys

'OK' KeyM OK

43.3C

OK

effSP

PDS2-H controller auto-rotates on its display the typical measurements and the plant status. This display is activated after a timeout of 30 seconds.

The controller has four (4) touchsensitive buttons for the user interaction (see figure). During the display rotation the rotation can be paused by pressing the "OK" key. The rotation

can be re-activated by pressing the "OK" key again. By repeatedly pressing the "OK" key the required parameter can be selected.

After pausing the rotation, the controller returns to the auto-rotation mode automatically after 60 seconds.

SyxthSense Ltd

PS CT2.40 - 4/9

The display rotates between the following readings:

PU 1PUMP

28.7OUT%

14.8CTE OUT

52.6CWATER

47.3CeffSP

21.6CROOM

Room Temperature

Pump OutputStatus (0/1)

Mixing ValveOutput (%)

Calculated FlowSetpoint

Water Flow Temperature

OutsideTemperature

LI L22°C

Low Limit Active (at temperature)

HI L75°C

High Limit Active(at temperature)

OPTIONAL DISPLAYS (SPECIAL CONDITIONS AUTOMATICALLY ADDED TOTHE ROTATION):

ERRWATER

Water Sensor Error

ERRTE OUT

Outside Sensor Error

ERRROOM

Room Sensor Error

Optional displays provide additional information in abnormal conditions e.g Flow Temperature High Limit is active or a sensor has been disconnected.

USER SETTINGS By pressing the "PROGRAM’ key the user can adjust the heating compensation curve upwards or downwards (+/-25°C).

• Press ’PROGRAM’ key to display the current CURVE SHIFT setting.• Press ’+’ and ’-’ keys to shift the compensation curve vertically upwards or downwards.• Once the required setting is found press ’OK’ to accept the new setting. The controller returns to

the normal user display.

5.0CSP 43C

Curve ShiftSetting (+ or -)

Effective CalculatedFlow SetpointNote: The effective calculated setpointis automatically updated as and whenthe curve shift setting is changed.

FLO

W T

EMPE

RAT

UR

E

OUTSIDE TEMPERATURE

20

-20

80

-10 0 10 20 30

Curve ShiftParameter(+ or -)

PDS2 COMPENSATION CURVEMax FlowTemperature

Min FlowTemperature

M

M OK

CurCURVE

OK

To enter programming mode, press the following

OK

The 'CURVE' menu selectionis displayed on the screen.

Press 'OK' to enter to 'CURVE'(Compensation Curve) menu.

PROGRAMMING MODE The controller is operational without need for any programming. The controller expects to see flow and outside air temperature sensors. If a room temperature sensor is connected, this needs to be enabled in the input menu.

The controller compensation curve, 3-point actuator running time, the room setpoint etc. can be adjusted to meet the site requirement by entering to the programming mode.

To enter prgramming mode press the following keys ’+’, ’OK’, ’OK’ and ’M’.

SyxthSense Ltd

PS CT2.40 - 5/9

MENU STRUCTURE

ROOM RESET CONTROL PDS2-H controller has room reset control feature (if AI3 room sensor input has been enabled). This function will automatically adjust the water flow temperature according to the space conditions. To activate this function connect TEHR-PT1000 sensor or wireless room sensor via FLTA receiver to the PDS2-controller input AI3 (terminal 12).

CURCURVE

Point P1 of the compensationcurve.

TOP LEVEL MENU

CONCONTR

INPINPUT

CL0SET

Compensation Curve Menu

Control ParametersMenu

Measurement Input Menu

TIME Set Menu

Press 'OK' toenter 20.0C

P1 20C

Outside TemperaturePress 'M' and '+' or '-' to adjust, 'OK' to accept.

Required (Minimum) Flow Setpoint. Press '+' or '-' to adjust.

‘OK'

35.0CP2 15C

Point P2

80.0CP5 0C

Point P5

Required (Maximum) Flow Setpoint.

Press '+' or '-' to adjust.

Press 'OK' to continue

Pre

ss 'M

'

ProportionalBand [1..200]

Press 'OK' 50.0XP °C

Control Mode[P/PI]

=PISEL

1000Tint s

ON 23-P

[1=Thermic Actuator,2=3-Point Actuator]

180Tmot s

Actuator RunningTime [30..300s]

AO1=DIR

AO1 Operation[DIR = direct,REV = reverse]

OnPUMP

Pump Output[ON =Enabled, OFF=Disabled]

1MOD=

Modbus Address[1..247]

Pre

ss 'M

'

Integral ActionTime [50..5000s]

9.6kBaud

Modbus BaudRate [9.6/19.2/38.4]

'OK' 'OK' 'OK' 'OK'

'OK'

Pre

ss 'M

'

A1 1WATER

TE1 Settings

50FLT %

0.0CCAL

A1 2OUT

TE2 Settings

20.0CPU_SP

A1 3ROOM

TE3 Settings

OFFSEL

21.0CROOM°C

4RATIO

0.0CCAL

AO1 Output inCase of SensorFault [0..100]

Sensor Calibration[-2..+2]

Sensor Calibration[-2..+2]

Outside Eco Setpoint for Pump (pump off when TE2 > PU-SP)

Room Sensor[ON/OFF/AI4]

Room Setpoint[17..30]

Room InfluenceRatio [-6..+6]

'OK' 'OK' 'OK' 'OK'

'OK'

'OK'

'OK''OK'

‘OK'

50.0CP3 10C

Point P3‘OK'

65.0CP4 5C

Point P4‘OK'

'OK' 'OK''OK''OK'

0.0CCAL

Sensor Calibration[-2..+2]

'OK' 'OK' 'OK'

18.0CECOSP

Night ECO modeSetpoint [0..50]

'OK' 'OK'

XX.00TIME

Set Hours

12.XXTIME

Set Minutes

'OK'

X.00ON

“ON” Time Hours

'OK'

0.XXON

“ON” Time Minutes

'OK'

X.00OFF

“OFF” Time Hours

0.XXOFF

“OFF” Time Minutes

'OK'

'OK'

ECO/CUR

INTERNAL TIME controlselection. ECO (Night)or Curve Shift ModeDEFAULT = CURVE

MODE/SHIFT

'OK'

0.0CCurve Shift (+/-25°C)If CUR selected and AI4 MODE = OFF

CL1SET

Pre

ss 'M

'

'OK' 'OK'

A1 4INPUT

AI4 INPUT modeSelection (no adjustment)

ONMODE

If “ON”, PDS2 usesAI4 (term 13) to overridemode to ECO (Night) or to a Curve Shift Setting (Boost/Setback)

'OK' 'OK'

0.0CCurve Shift (+/-25°C)Activated when AI4 Mode = “ON”and AI4 (term 13) is connected to 0V

OFFMODE

If “OFF”, PDS2 usesInternal Clock to overridemode to ECO (Night) or to a Curve Shift Setting (Boost/Setback)

'OK'

A1 3ROOM

TE3 Settings

ONSEL

21.0CROOM°C

4RATIO

Enable Room Sensor[ON = EnabledAI4 = Wireless RoomSensor via AI4]

Room Setpoint[17..30]

Room InfluenceRatio [-6..+6].

E.g. with setting 4, one degreechange in the room temperatureequals four degrees change in theflow setpoint.

'OK' 'OK' 'OK'

SyxthSense Ltd

PS CT2.40 - 6/9

WIRELESS ROOM SENSOR If required, PDS2 controller can be connected to a wireless room sensor via FLTA receiver. The diagram below illustrates the configuration. The wireless room sensor is activated from the AI3 menu by selecting the AI4 option. The FLTA output is then connected to the AI4 input of the PDS2 controller (terminal 13).

PDS2-H

MODBUSCOMMS FLTA

WIRELESSROOMSENSOR

AI4

TEFL

AO1[0..10V]

A1 3ROOM

TE3 Settings

=AI4SEL

Room Sensor[AI4 = use inputAI4 for the room sensor)

'OK'

AI3 INPUT CONFIGURATION

If the AI4 voltage drops below 2V, the controller will consider this as a sensor fault. 2..10Vdc input signal equal to 0..50°C room temperature.

NOTE: If wireless room sensor is used with the PDS2-H, the external clock input (boost/setback) is disabled.

ANALOGUE INPUT4 OVERRIDE CONDITIONS (BOOST / SETBACK / NIGHT [ECO] )

If the PDS2 controller AI4 external input mode is enabled (= internal clock disabled) the controller monitors the Analogue Input AI4 (Terminal 13) for override conditions.

A1 4INPUT

AI4 INPUT modeSelection

ONMODE

If “ON”, PDS2 usesAI4 (term 13) to overridemode to ECO (Night) or to a Curve Shift Setting (Boost/Setback)

'OK'

0.0CCurve Shift (+/-25°C)Activated when AI4 Mode = “ON”and AI4 (term 13) is connected to 0V

'OK'

NORMAL OPERATION

AI4 OPEN = The controller is in normal Operation (valve modulating, pump output running if enabled, and the effective setpoint calculated based on the outside air temperature).

SETBACK/BOOST

AI4 connected to 0V = The controller is in CURVE shift mode (boost or setback, +/-25°C).

When AI4 is connected to 0V the controller effective setpoint is shifted upwards (boost) or downwards (setback), otherwise the operation is as in the normal mode.

NIGHT (ECO) MODE

NOTE: This override is only active if the room sensor has been activated (AI3) and a room sensor has been installed.

AI4 connected to AO3 Terminal = Night Energy Saving (ECO) mode. The controller is OFF (valve closed and pump output off), unless the room temperature drops below night frost setpoint - see Night (ECO) Mode paragraph for further details.

NOTE: Night (ECO) Mode override is only available if a room sensor has been connected to input AI3 and the input has been enabled.

BOOST / SETBACK USING INTERNAL CLOCK (AI4 DISABLED)

If AI4 input mode has been disabled, the controller can be switched to Boost or Setback (shifting the compensation curve) using the internal time schedule, or the controller can be overdriven to Night ECO Mode by the internal time schedule.

SyxthSense Ltd

PS CT2.40 - 7/9

To activate the internal clock based mode selection, set AI4 to OFF mode and set the system time, and the switching times (one on/off period available).

NOTE: If AI4 has been set to follow internal clock, the external override input (terminal 13) is disabled.

A1 4INPUT

AI4 INPUT modeSelection

'OK'

OFFMODE

If “OFF”, PDS2 usesInternal Clock to overridemode to ECO (Night) or to a Curve Shift Setting (Boost/Setback)

X.00ON

“ON” Time Hours

'OK'

0.XXON

“ON” Time Minutes

'OK'

X.00OFF

“OFF” Time Hours

0.XXOFF

“OFF” Time Minutes

'OK' ECO/CUR

INTERNAL TIME controlselection. ECO (Night)or Curve Shift ModeDEFAULT = CURVE

MODE/SHIFT

'OK'

0.0CCurve Shift (+/-25°C)If CUR selected and AI4 MODE = OFF

'OK'

PUMP OUTPUT The optional pump output is normally on. The pump output switches off when the outside air temperature exceeds the PU_SP Pump Economy setpoint.

If the controller is overridden to Night (ECO) Mode via input AI4, the pump output switches off unless the temperature falls below the Night (ECOSP) setpoint set in the AI3 menu.

NIGHT (ECO) MODE If the controller is overridden to Night (ECO) mode via an external contact or an internal time clock, the controller switches the pump output off and closes the heating valve outputs. If the room temperature drops below Night (ECO)SP Frost setpoint, the controller returns to the normal day mode until the room temperature exceeds ECOSP + 2°C.

2120

18

Room Temperature [°C]

Time

EC

O O

N

EC

O O

FF

Hysteresis [2°C]ECOSP

COMMISSIONING The PDS2 factory default application is a standard compensator with the outside and flow temperature sensors. Typical settings to modify during the installation are:-

• select the actuator type and set the actuator running time correctly in the control menu (not required for the 0..10Vdc control actuators)

• set the 5-point compensation curve (default curve is 20/80°C) in the curve menu

• if the room influence is required enable the room sensor in the input menu and set the room setpoint and room correction ratio

If no overrides are present, the controller operates in a normal (24/7) mode. It is possible to configure the controller to use internal time clock or external AI(4) input to override the controller to Night ECO mode or to shift the compensation curve (boost or setback).

CLOSET

'OK'

--:--TIME

12.00TIME

'OK'

Hours flash.Set the hours by“+” and “-” buttons.

12.30TIME

Minutes flash.Set the minutes by“+” and “-” buttons.Press”OK” to accept and return to menu.

CLOCK The clock is set as follows

SyxthSense Ltd

PS CT2.40 - 8/9

The clock is disbaled by removing the time and replacing it by "--:--". By disabling the clock the time display is removed from the user display (rotating display) and the menu to set the switching times is hidden.

CLOSET

'OK'

12:30TIME

12.00TIME

Hours is reset to zero first.

After resetting the hours, the lines areset by pressing “-” key.Once completed press “OK.

SETTING SWITCHING TIMES Once the clock has been set, switching times menu is displayed on the controller configuration level. When the clock is activated (ON), the AO4 = 10V and when the clock is OFF AO4 = 0V.

X.00ON

“ON” Time Hours

0.XXON

“ON” Time Minutes

'OK'

X.00OFF

“OFF” Time Hours

0.XXOFF

“OFF” Time Minutes

'OK'

CL1SET

'OK' 'OK'

Time SwitchMenu

'OK' backto menu

NETWORK DIAGRAMS Up to 128 PDS2 controllers can be connected to a single network segment. The diagrams below illustrate the typical installation options.

It possible to connect the controllers to an existing BMS (e.g. to TREND BMS) via a Modbus gateway. Please contact SyxthSense for more information. Or the controllers can be connected to the WebBiter embedded web-server that provides BMS front-end capability and access via a standard web-browser.

Modbus RTU (RS-485)WebBiter

Ethernet (TCP/IP Network)

HLS34RoomController

Web-Browser

PDS2-HWeather Compensator

PDS2-VVentilationController

MODBUS REGISTERS (PDS2 Version 1.1)

The controller supports the following Modbus registers and function codes. The default communication speed is 9600 bps, 8 data bits, Parity None and 1 Stop Bit.

Please note that Modbus register space is specified from the Modbus master perspective as in the Modbus Application Protocol specification. The Modbus registers for Function Codes 02, 03, 06 and 16 have presentation for both Modbus "address blocks" and for actual Modbus register offsets. For example, the Temperature 1 is read from Modbus register 9 using Function Code 04. Some Modbus masters will require Function Code 04, register 9 to be entered, whereas the others will require register 30009 and Function Code 04. The actual message string will always be sent as a stripped register value of 9 but the data entered to the Modbus master depends on the implementation of the master.

Register Parameter Description Data Type Raw Data Range

FUNCTION CODE 01 - READ COILS

2 CurveShift Setting Mode by Modbus Bit 0 On - Off

3 Night (ECO) by Modbus Bit 1 On - Off

4 Overdrive Mode Enable Bit 2 On - Off

5 Modbus Setpoint Enable Bit 3 On - Off

SyxthSense Ltd

PS CT2.40 - 9/9

Note 1. Register 1793 returns registers 6 and 7 as 4-byte value (Timechannel format). To remove the times write "--:-- : --:--" = 65535 65535 (0xFFFF 0xFFFF) to register 1793.

6 Alarm Bit 4 On - Off

FUNCTION CODE 02 - READ DISCRETE INPUTS

10002 CurveShift Setting Mode Asked by PDS2 Bit 0 On - Off

10003 Night (ECO) by PDS2 Bit 1 On - Off

10004 CurveShift Setting Mode Active Bit 2 On - Off

10005 ECO Active Bit 3 On - Off

10006 Pump Bit 4 On - Off

FUNCTION CODE 03 - READ HOLDING REGISTERS

40004 Overdrive Value Signed 16 0..1000 0..100.0%

40005 Set Point by Modbus Signed 16 -500..1500 -50.0..+150.0°C

40006 Modbus CurveShiftSetting (Boost/Setback) Signed 16 -250..250 -25.0..+25.0°C

40007 ON-TIME in Minutes Signed 16 TIME SET 0..1439 or TIME OFF 65535

40008 OFF-TIME in Minutes Signed 16 TIME SET 0..1439 or TIME OFF 65535

41793 ON-TIME OFF-TIME (see Note 1) Timechannel hh:mm hh:mm (see note 1)

FUNCTION CODE 04 - READ INPUT REGISTERS

30004 Overdrive Value Signed 16 0..1000 0..100.0%

30005 Set Point by Modbus Signed 16 -500..1500 -50.0..+150.0°C

30006 Modbus CurveShiftSetting (Boost/Setback) Signed 16 -250..250 -25.0..+25.0°C

30007 ON-TIME in Minutes Signed 16 TIME SET 0..1439 or TIME OFF 65535

30008 OFF-TIME in Minutes Signed 16 TIME SET 0..1439 or TIME OFF 65535

30009 Temperature TE1 Signed 16 -500..1500 -50.0..+150.0°C

30010 Temperature TE2 Signed 16 -500..1500 -50.0..+150.0°C

30011 Temperature TE3 Signed 16 -500..1500 -50.0..+150.0°C

30012 Analogue Input 4 Signed 16 0..100 0.0..10.0 Volt

30013 Effective Setpoint Signed 16 -500..1500 -50.0..+150.0°C

30014 Potentiometer Signed 16 -500..1500 -50.0..+150.0°C

30015 Output Signed 16 0..1000 0.0..100.0 %

FUNCTION CODE 05 - WRITE SINGLE COIL

2 CurveShift Setting Mode by Modbus Bit 0 On - Off

3 Night (ECO) by Modbus Bit 1 On - Off

4 Overdrive Mode Enable Bit 2 On - Off

5 Modbus Setpoint Enable Bit 3 On - Off

6 Alarm Bit 4 On - Off

FUNCTION CODE 06 - WRITE SINGLE REGISTER

40004 Overdrive Value Signed 16 0..1000 0..100.0%

40005 Set Point by Modbus Signed 16 -500..1500 -50.0..+150.0°C

40006 Modbus CurveShiftSetting (Boost/Setback) Signed 16 -250..250 -25.0..+25.0°C

40007 ON-TIME in Minutes Signed 16 TIME SET 0..1439 or TIME OFF 65535

40008 OFF-TIME in Minutes Signed 16 TIME SET 0..1439 or TIME OFF 65535

FUNCTION CODE 16 - WRITE MULTIPLE REGISTER

40004 Overdrive Value Signed 16 0..1000 0..100.0%

40005 Set Point by Modbus Signed 16 -500..1500 -50.0..+150.0°C

40006 Modbus CurveShiftSetting (Boost/Setback) Signed 16 -250..250 -25.0..+25.0°C

41793 ON-TIME OFF-TIME (see Note 1) Timechannel hh:mm hh:mm (see note 1)

Register Parameter Description Data Type Raw Data Range


Recommended