Date post: | 14-Jan-2017 |
Category: |
Technology |
Upload: | kristenbarbourpf |
View: | 3,704 times |
Download: | 0 times |
Application of the Intrinsically Safe CHARMS
Modules for Project Savings
Session ID: 8-2387
Presenters
Not pictured : Klaus Erni
Introduction
Application of the Intrinsically Safe CHARMS Modules
Intrinsic Safety Basics IS CHARMSApplication of IS for DeltaV SystemsApplication of IS CHARMS
You Are All Familiar With Emerson’s Electronic Marshalling
ControllersVarious busses
Wireless I/O
Electronic Marshalling
Electronic Marshalling Structure & Definitions
Fast Facts– Electronic Marshalled I/O
Types– CHARMS available today
• AI 4-20 mA HART• AO 4-20 mA HART• DI NAMUR • DI 24 VDC Low Side• DO 24 VDC High Side• Thermocouple/mV• RTD• Voltage 0-10 VDC
Rules– 8 Base Plates per CIOC– 12 Terminal Blocks per Base
Plate– 96 CHARMS per CIOC– Install in Div 2 or Zone 2
CHARMS
CIOC Carrier
CIOC (Redundant)
Terminal Block
Base Plate
CHARM
Electronic Marshalling
Background on Hazardous LocationsAn area containing (or likely to contain) an ignitable concentration of flammable gas or vapor, where an electrical spark of sufficient power will cause an explosion.
HAZARDOUS
NOT HAZARDOUS
Oxidizer Fuel(Air) (Gas, Vapor or
Dust)
Energy(Thermal or Electrical)
Ex
Hazardous Location Explosion Triangle
All three must be present to cause an ignition
Basis for most protection methods
Eliminate one and the operation is safe
Class I; Division 1; Groups A,B,C,D; T6
Permitted Class
Permitted DivisionGas GroupsTemperature Class
Zone 1, Ex ib IIB T6
Gas GroupsTemperature Class
Type(s) of Protection
Hazardous Locations & Protection – Examples
Permitted Zone
Defined by FM & ANSI/ISA
Defined by IEC & CENELEC
Traditionally Zones have been
in Europe
Traditionally Divisions have been in the US
Intrinsic Safety – Methods of ProtectionIntrinsic Safety – Methods of Protection Methods of protection in hazardous environments
– Containment, e.g. Explosion Proof, Ex d• Contains an explosion (at the electronics) within an enclosure or housing;
prevents the explosion from propagating outside the enclosure to the process area
– Segregation, e.g. Purge/Pressurization, Ex p• Prevents the Oxidizer and Fuel from coming into contact with the electronics
– Prevention, e.g. Intrinsic Safety, Ex i (e.g. Ex ia, Ex ib, Ex ic)• Prevents the Energy at the electronics from being high enough to cause an
explosion Intrinsic Safety has emerged as the preferred method of protection
in most world areas
Protection Methods
Comparison of Protection Methods
An intrinsically safe circuit consists of the following:- Intrinsically Safe Equipment
- Interconnecting Wire- Associated Apparatus
IntrinsicallySafe
Equipment
Associated Apparatus
AssociatedApparatus
Intrinsic Safety: Basic Concept
Ignition Curves
• Intrinsically safe circuits operate below the minimum
ignition point during normal and abnormal operation
with a 50% safety factor
• Relevant standards• UL913• FM3610• CSA C22.2 No. 157• ISA 12.2.01• IEC 60079-11
Explosion Prevention Via Intrinsic Safety Intrinsic Safety “i”, example Ex ia
– Divisions 1, 2 / Zones 0, 1, 2
Intrinsic Safety Characteristics – A low power technique is used to limit voltage, current, and stored
energy to a level below the minimum required for ignition during both normal AND abnormal operation of the equipment under consideration.
Hazardous Area
VVRR LL
CC
Isc/Io
3x3x Voc/Uo
BarrierBarrier CableCable
+
-
When to use Intrinsic Safety
Intrinsic Safety circuits are used when field devices are located in hazardous environments; they protect the circuit by limiting the energy to the field devices.
Field devices can be located in hazardous environments that are rated – Zone 0, Zone 1, or Zone 2– Class I Division 1 or Class 1 Division 2
Protection levels for the circuits could be– Ex ia, Ex ib, or Ex ic
Circuits will have defined parameters for Voltage, Current, Power, Capacitance, and Inductance
When IS is not a Good Fit...When IS is not a Good Fit... Some plants are geographically dispersed meaning that the
presence of explosive hazards for any period of time is unlikely. Some plants do not have the possibility of explosive mixtures being
present If your customer already uses Explosive Proof methods, they are
unlikely to adopt IS in the same facility In North America, IS is not typically used.
– This is changing slowly. Some US plants with IS include• 3M • Bayer • BASF
Intrinsic Safety ProtectionIntrinsic Safety Protection
Lower initial cost Conduit not required; poured seals not
required Any suitable enclosure is acceptable in
Div 2 Reduced cost of ownership
(maintenance, calibration, repair) Use of simple apparatus offers
flexibility Suitable for all gasses Permits live maintenance; lowers cost
and increases safety Accepted globally
Can only be used for low power Cable parameters must be considered
for IS applications in loop proofing Perceived to be complex
Advantages Disadvantages
Intrinsic Safety Applications
NOTE: For Hazardous Environment applications, Intrinsic Safety is easier to understand and easier to apply; however, where Intrinsic Safety methods of protection will be applied, be sure that you have the proper experience, and please contact Pepperl+Fuchs or Emerson Intrinsic Safety experts
NOTE: Intrinsic Safety training and education is recommended and can be made available to you, please contact Pepperl+Fuchs or Emerson Intrinsic Safety experts
How to Achieve Intrinsic Safety with DeltaV
Numerous Options & Applications with Emerson DeltaV Traditional DeltaV I/O and external Pepperl+Fuchs IS modules
– M-Series– S-Series– Emerson Standard CHARMS I/O
Emerson IS CHARMS DeltaV SIS and external Pepperl+Fuchs IS modules
Via energy limiting devices, IS barriers, that limit energy in the circuit…
Hazardous Area
Intrinsic Safety “Apparatus” – Traditional
Associated Apparatus provides the protection Intrinsic Safety Approved Apparatus are the field devices
Approval Focus Area
ApprovedApparatus
ConnectingCable
AssociatedApparatus
DCS, e.g.DeltaV
Hazardous Area
Intrinsic Safety “Apparatus” – IS CHARMS Associated Apparatus provides the protection Intrinsic Safety Approved Apparatus are the field devices
Approval Focus Area
ApprovedApparatus
ConnectingCable
AssociatedApparatus
DCS, e.g.DeltaV
More details later in presentation!!
How to Achieve Intrinsic Safety with DeltaV
IS barriers can be external isolators
IS barriers can be embedded with DCS I/O as in the case of IS CHARMS
Via energy limiting devices, IS barriers, that limit energy in the circuit…
External IS Barriers IS CHARMS
Traditional IS modulesfrom Pepperl+Fuchs
IS CHARMSfrom Emerson
inside
External P+F IS Isolating Barriers
Only a few channels of IS neededOR
Customer preference for redundant, multi-channel traditional I/O cards in S-series
OR DetlaV SIS requires external IS barriers
OR Customer preference for external IS
barriers due to experience, spares, standard operating practice, etc.
OR Emerson has opted to sell M-series or
Ovation to the customer
Via energy limiting devices, IS barriers, that limit energy in the circuit…
Adding External IS Isolating Barriers to DeltaV or DeltaV SISDeltaV S-series
Hazardous Area
Intrinsic Safety with Traditional I/O
DeltaV M-series DeltaV S-series
Via energy limiting devices, IS barriers, that limit energy in the circuit…
Adding External IS Isolating Barriers to DeltaV or DeltaV SIS
Hazardous Area Hazardous Area
Intrinsic Safety with Traditional I/OVia energy limiting devices, IS barriers, that limit energy in the circuit…
Hazardous Area
Many wires!!Too much cabinet space
DeltaV S-series
Intrinsic Safety with Standard CHARMS I/OVia energy limiting devices, IS barriers, that limit energy in the circuit…
CHARMSDeltaV S-series External IS Barriers
Hazardous Area
Cables, labels, associated drawings, and installation/checkout in FAT can cost more than DCS I/O channel hardware or an external IS barrier/isolator.
Intrinsic Safety with Standard CHARMS I/OVia energy limiting devices, IS barriers, that limit energy in the circuit…
CHARMSDeltaV S-series External IS Barriers
Hazardous Area
Cables, labels, associated drawings, and installation/checkout in FAT can cost more than DCS I/O channel hardware or an external IS barrier/isolator.
Now IS CHARMs are Available
ControllersVarious busses
Wireless I/O
Electronic Marshalling
Intrinsic Safety & Emerson IS CHARMS
Makes it EASY!! Combines Emerson I/O CHARMS and Pepperl+Fuchs
Intrinsic Safety Barrier technologies into a single, small, integrated package … IS CHARMS
Associated Apparatus
inside
IS CHARMS – Integrated I/O & IS ProtectionIS CHARMS – Integrated I/O & IS Protection
inside
IS CHARMS
Fast Facts– I/O plus IS protection– IS protection plus galvanic isolation
Types– IS CHARMS available 4Q 2011
• AI 4-20 mA HART• AO 4-20 mA HART• DI NAMUR • DO 11V @45mA VDC High Side
– IS CHARMs available 3Q 2012• Thermocouple/mV• RTD
Rules– 8 Base Plates per CIOC– 12 Terminal Blocks per Base Plate– 96 IS CHARMS per CIOC– Install in Div 2 or Zone 2– Can mix Standard CHARMS Base Plates
with IS CHARMS Base Plates
CIOC CarrierCIOC (Redundant)
IS Terminal Block
IS Base Plate
IS CHARM
Intrinsic Safety with IS CHARMS I/OVia energy limiting devices, IS barriers, that limit energy in the circuit…
IS barriers built into IS CHARMS!!IS CHARMS
• Smaller Footprint • Less Design• Lower Project Costs• Long Term Benefits• Emerson Unique
DeltaV S-series
IS CHARMS replaces many wires with 2 wires!
Hazardous Area
Why the IS CHARMS Solution?Why the IS CHARMS Solution? Project Benefits
– Smaller cabinet footprint, than external IS barriers– Less Design– Fewer cabinets; smaller cabinets– Fewer drawings– Fewer wires to connect and label– Easy last minute project changes– Lowest Total Installed Cost
Long Term Customer Benefits– One warranty. One company responsible.– Falls under standard Emerson life cycle plan– Fewer points of failure (screw terminal reduction)– Highest availability with single point integrity– Fewer spares– Less maintenance and inspection requirements– Higher safety and availability
Emerson is unique in this offering; others cannot compete
IS CHARMS Replace IS Barriers
IS CHARMS
120 I/O
CONVENTIONAL
IS BARRIERS
120 I/O
Cost Comparison – Business Results Achieved
IS CHARMS Savings
Area of SavingsPer 144 AI I/O
(a cabinet)Per 1000 AI I/O
(7 cabinets)Per 144 DI I/O
(a cabinet)Per 1000 DI I/O
(7 cabinets)Hardware 29,897$ 207,619$ 15,470$ 107,432$
Labor 5,557$ 38,591$ 5,557$ 38,591$
Floor Space 9,000$ 62,500$ 9,000$ 62,500$
Savings 44,454$ 308,711$ 30,027$ 208,523$ (less any additional cost of IS CHARM relative to conventional I/O or Standard CHARM)
Cost Savings with IS CHARMS Cost Savings with IS CHARMS
IS CHARMS CONVENTIONAL
IS BARRIERS
Intrinsic Safety with DeltaV SIS I/O
DeltaV SISDeltaV S- or M-series
Via energy limiting devices, IS barriers, that limit energy in the circuit…
Adding External IS Isolating Barriers to DeltaV or DeltaV SIS
BPCS
Hazardous Area
SIS
Hazardous Area
Summary
Discussed Intrinsic Safety Basics Discussed Application of the Intrinsically Safe
CHARMS Modules for Project Savings Use of IS CHARMS reduces project cost and
improves safety
Questions??
Where To Get More Information Attend Short Course Session ID: 4-2391
“Intrinsic Safety Fundamentals & IS CHARMS” Attend Emerson DeltaV Roadmap Visit us in the exhibition hall for a live demos
www.pepperl-fuchs.us Order a Free:
Pepperl+Fuchs Interface
Technology
Engineer’s Guide