Date post: | 08-Apr-2018 |
Category: |
Documents |
Upload: | antonio-isaac |
View: | 220 times |
Download: | 0 times |
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 1/13
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 2/13
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 3/13
ASIMINOAEI et al.: PERFORMANCE IMPROVEMENT OF SHUNT ACTIVE 249
TABLE ICALCULATION OF THE LINE CURRENT
I
FOR EACH CASE IN FIG. 3
For the feedback APF
(5)
which gives
(6)
Thus, one may describe the resultant line current as a func-
tion of the initial harmonic current from the ASD and the ex-
isting source voltages ( and , i.e., fundamental respective
harmonic voltages from the grid side). The analytical expression
of the line current determined for all six topologies in Fig. 3
is given in Table I.
As it can be noticed the line current in case-(a) does not
depend on the existing voltage harmonic distortion, and the re-
sultant transfer function is the direct effect of each individualtransfer function of the active power filters. Case-(c) is useful
for damping the resonances between the grid and possible ac-ca-
pacitor at the load side, because both and give the
effect of a damping in series with the grid impedance. However,
the harmonic current mitigation directly depends on the filter’sinductances, which may create design restrictions depending on
the grid impedance value . For case-(b) and case-(d), the com-
mand law depends on the imposed reference and
for each filter, which is useful for sharing the loading between
filters, during different operating conditions. Case-(f) achieves
better harmonic mitigation compared to case-(e) regarding the
influence of the harmonic grid voltages .
Furthermore, for case-(b), case-(d) and case-(f), the schemesuse just one pair of harmonic detection sensors, which reduce
the complexity of the hardware design, the number of analog
digital (AD) converters and possible the speed of the calcula-
tions.
However, case-(b) and case-(d) require a careful design re-
garding the imposed harmonic current references. In the sim-
plest way the reference can be given as half of the measuredharmonic current for each inverter, but then both inverters must
be rated at the same nominal power. For other references values,
additional processing is necessary in order to correctly balance
the reference signals and as it is shown in Fig. 3.
Finally, the actual study selects only the topology shown in
case-(f).
B. Description of the Selected Topology (Case-f)
The proposed topology is shown in Fig. 2. As it can be no-
ticed, the APF is composed of two separate inverters, each of
them using independent current and voltage controllers. To min-
imize the cost this structure may be furthermore reduced by
connecting the inverters together on the dc-link [4]. Thus, onlyone dc-link capacitor would be needed and implicitly a single
voltage controller. However, it makes the hardware design and
the control more complicated, as a zero sequence current cir-
culates between inverters [7]. In order to break the circulation
path of the zero sequence currents between inverters, a galvanic
isolation is inserted by means of either isolating transformer or
separate dc-capacitors. Thus, the inverters can be independently
controlled.
The load current sensor for harmonic detection is placed in
between the connection points of the inverters, thus achieving
a feedback path for the first inverter (PWM inverter 1), and a
feedforward path for the second inverter (PWM inverter 2). This
new topology may allow each inverter to perform different tasks,depending of the imposed current references.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 4/13
250 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
Thegenerationofharmonicreferencecurrentisdoneinmaster-
slave configuration, as thefirstinverter dictates theharmonic ref-
erence of the second. Two separate master-slave configurations
can be implemented,one is the harmonic-sharing and the other is
the load-sharing control. In the harmonic-sharing mode the first
invertermitigates only severalharmonic currents, and the second
inverter takes care of the rest of the harmonic spectrum.
It is also possible to operate the filters in load-sharing mode,
when both filters compensate the same harmonic spectrum but
with different imposed reference amplitudes. If the harmonic
reference is equally divided between inverters then each takes
50% of the total required power. Other ratio of harmonic refer-
ences in each inverter is also possible and useful for inverters
with different rated powers or when it is desired to control the
distribution of the power losses, but the reference generation al-
gorithm is more complicated.
A third possibility is to configure the proposed topology in a
redundant-mode,whichisabenefitprovidedbytheproposedcas-
caded configuration. The redundant-mode is a particular case of
the load-sharing mode, when the harmonic reference is not di-vided between inverters but setat maximum foronly oneinverter.
Thus,APF1hasthetaskofthemainharmoniccompensator.Since
APF2 follows APF1, when APF1 ceases its harmonic mitigation,
APF2automaticallycantakeover,ifitisconfiguredtodoso.This
offers a wireless independent control feature, because there are
no connectivity wires between the inverters to change informa-
tion aboutthe internalvariableor statesof each control loop.Each
APF’s control is only based on information available locally at
the inverter terminals.However,the redundant-modeimplies that
the rated power of APF2 is suf ficiently large to cover the overall
harmonic mitigation, which may not be cost-effective.
In order to optimizethe cost, onemay usethe feedback inverter
(PWMinverter1)tocompensateonlyapartoftheharmonicspec-trum, for instance, the low order harmonics as most of the power
densityiscontainedhere.Asthecompensationiscarriedoutinthe
feedback loop, the steady state response is expected to be much
more tolerant to nonlinearities and parameter variation [6].
Consequently, since the inverter is of high rated power a lower
switching frequency is desirable. Regarding the selection of the
switching frequency one choice is to use different switching
frequencies (i.e., APF1 low, APF2 high) in order to have re-duced power losses but still a good overall harmonic mitigation
performance. Another choice is to use the same switching fre-
quency for both, which allows implementation of interleaving
techniques to reduce the switching frequency ripple, and conse-
quently EMI and the line filter.In this paper, the second choice was used due to some hard-
ware limitation (APF1 and APF2 have the same switching fre-
quency), but a discussion presented in Section VI analyzes the
potential operational ef ficiency improvement if APF1 switches
at a lower frequency. In the case when both power inverters
have the same switching frequency, by interleaving their carriers
by 180 it may significantly reduce the line switching current
ripple. Thus, the highest ripple amplitude is seen at a doubled
switching frequency, which is much easier to filter out. As the
frequency of the switching current is higher it gives lower EMI
and is also damped much faster in the power lines due to their
inductive effect.
The feedforward inverter (PWM inverter 2) receives the in-formation of the harmonic content only after the first inverter
Fig. 4. Principle algorithm of harmonic extraction and reference current con-trol in synchronous fundamental frame.
has already mitigated part of the harmonic spectrum. The cur-
rent reference for the feedforward APF contains only the har-
monics left in the line currents. The second inverter is designed
for mitigation of high order harmonics. As a result, the second
inverter is configured for a faster dynamic response, thus com-
pensating the slower dynamic of the first inverter (which may
react slowly and imprecisely in transient conditions especially
if its switching frequency is lower).
The entire topology has the advantage of a good harmonicmitigation in stationary conditions (due to the feedback in-
verter), but also very good response in transient conditions (due
to the faster feedforward inverter) [8]. The power losses of the
second inverter are kept at a lower value since the high order
harmonics are not so large. Another advantage of this topology,
but not tested here, is that the feedback APF can provide an
active damping of existing resonances between the grid and a
possible installed ac-capacitor at the load side, e.g., EMI filter
or custom passive harmonic filter, although this requires an
increased bandwidth of the APF current controller.
III. CONTROL ALGORITHM
The control algorithm is developed in the synchronous funda-mental reference dq-frame. The input signals, measured in abc-
coordinates (i.e., stationary reference frame), are transformed
into the fundamental -rotating reference frame by means of
the Park transformation
(7)
where , and , , are the currents in the -frame, re-
spective in -frame; and is the angular position of the ref-
erence frame.
The frame rotates at fundamental angular frequency that
makes the fundamental current to appear as dc-component and
the harmonics as ac-signals. Thus, harmonic detection becomes
a matter of removing the dc-signal by means of a high-order
high pass filter [(HPF) in Fig. 4 with a cutoff frequency between
25 Hz and 120 Hz] [9]. The HPF outputs the harmonic current
to be compensated by the active filter. This is a fourth order
filter implemented in fundamental frame, which removes the
fundamental current, i.e., the dc-signal
(8)
where the cutoff frequency is 300 rad/s, and 0.8.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 5/13
ASIMINOAEI et al.: PERFORMANCE IMPROVEMENT OF SHUNT ACTIVE 251
Fig. 5. Control block diagram of the proposed topology in dq-frame. APF1 hasa single inner harmonic current controller tuned for mitigation of the 6th har-
monic order in dq-frame (i.e., fifth and seventh in stationary frame). APF2 hasa multituned inner current controller realized by superposing several harmoniccontrollers tuned at orders of 6
k
ind q
-frame.
For line synchronization purposes, the line voltages aremeasured, and the line frequency and phase are extracted
by means of a phase locked loop (PLL).
The block diagram of the proposed current control topology
is shown in Fig. 5.
The control contains one dc-voltage control loop for each
APF. The dc-voltage controllers are classical pro-
portional–integral (PI) units, which receive as inputs the dif-
ference between the reference voltage and the measured
dc-voltage . The output represents the fundamental active
current references, on the -axis of the synchronous frame
(9)
where and are the proportional and the integral
gains of each dc-voltage PI controllers.
The current controllers are, on the other hand, divided for
each APF into two distinct paths: the fundamental current con-
trol and the harmonic current control [11].
The APF reference voltage is the sum of all current controller
outputs and it is realized by a space vector modulation strategy
(SVM in Fig. 4).
The fundamental current controller is of a feedback type,
which provides pole-zero cancellation for this plant, the line
inductor. Vector model of the line inductor, in synchronous fun-
damental frame, is
(10)
where and are the resistance and inductance of the line
inductor, is the filter voltage, is the instantaneous filter
current, and is the line voltage vector.
A complex-coef ficient PI controller ( and ),
with cross-coupling decoupling and line voltage feedforward
compensation can be used
(11)
where and are the proportional and the integralgains of each complex current controllers.
The reference for the fundamental current controller is re-
ceived from the dc-voltage controllers. The fundamental current
controllers regulate the -axes active current, while
the reactive current on the -axes is set to zero, as in this appli-
cation no reactive power needs to be controlled.
The harmonic current control is realized by separate control
of each harmonic, each controller for one pair 6 1 of
positive and negative sequence harmonics. The total harmonic
reference is the superposition of commands produced by all cur-
rent controllers. Harmonic current controllers are equiv-
alent harmonic integrators, one controller being tuned here for
each harmonic pair 6 1 [10].
In order to control at the same time, a pair of both positive
and negative characteristic harmonics from a typical ASDs with
six-pulse diode based front-end rectifier, with a single controller,
the controller transfer function is selected as in [11]
(12)
where and are the proportional and the integral gains
of the selected harmonic integrator.
Notably, represents the transfer function of an equiv-
alent harmonic integrator (resonant controller) tuned for fre-
quency (for both negative and positive sequences), which
provides zero gain for the dc-component and infinite gain at the
selected frequency . Such type of controller is implemented
in fundamental reference frame for each harmonic order , up
to the 31st harmonic [12].
Finally, the total harmonic current controller is realized as
the superposition of individual controllers given by (12). In a
general form the resultant harmonic controller is
(13)
Controller gains are selected so as , and
of small value in order to create a narrow selectivity, thus
avoiding the overlap between the neighbor harmonic controllers.
The number of harmonic pairs , which can be compensated
in this way, can be selected based on the available computa-
tional resources and on the sampling and switching frequency
[13]–[16].
The feedback APF1 harmonic current controller is imple-
mented as only for equal to 6. For APF1 there
is only a single harmonic controller, i.e., 6, sixth harmonic
order in -frame meaning compensation of fifth and seventhharmonic currents in stationary frame.
The feedforward APF2 has with
6,12,18,24,30 . The superposition of the individual har-
monic controllers is done by summing the output voltage
reference of each
(14)
(15)
if APF2 is set for redundant-mode 1, else 0.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 6/13
252 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
Fig. 6. Bode plots of (a) open loop transfer functionsH ( s )
for APF 1 (b)openloop transfer function
H ( s )
for APF 2, and (c) overall closed loop system
transfer function as in Table I.
By replacing (14) and (15) into the initial open loop transfer
functions of each active filter in (1) and (2), one can deter-
mine the Bode plots of each system as it is given in Fig. 6. The
behavior of the open loop transfer functions , of
each active filter APF1, respectively, APF2 is dominated by the
transfer functions of the harmonic integrators re-
spectively . Therefore, the close loop Bode plot of
the overall system (APF1 together with APF2) looks as a mul-
tiple notch filter tuned for the selected frequency in -frame
[see Fig. 6(c)].Thus, APF1 mitigates only the lower harmonic currents (fifth
and seventh) the controller having a very high selectivity (i.e.,
low value for gain) in order to determine a precise mitiga-
tion of these harmonics. However, it is known that lower values
of give also a slow dynamic response.
The filter APF2 mitigates the rest of the characteristic har-
monic currents up to 31st order. The selectivity of the equivalent
harmonic integrators is set wider (i.e., higher values for the
gains) in order to cope with the variation of the line frequency.
As the line frequency varies, the harmonics suffer also a small
frequency shift, which it is more severe as the harmonic goes
higher. Thus, in order to provide a better harmonic tracking, it
is advisable to have a wider selectivity of the higher order res-onant controllers. As the selectivity of the controller is wider,
the dynamic response of the APF2 becomes faster compared to
APF1.
The redundant-mode feature is implemented in the APF2
control by setting 1 [see Fig. 5 and (15)] which enables the
sixth harmonic inner current controller in . This can be
seen in Fig. 6(b) where the open loop transfer function
is plot in two cases, with and without a harmonic integrator
tuned for 300 Hz. If is not tuned for 300 Hz it means
that the filter APF2 cannot mitigate the same harmonics as the
first filter APF1. If is tuned for 300 Hz, it allows APF2
to mitigate also the fifth and seventh harmonics. But since its
mitigation follows after APF1, the effect is similar as sharingthe harmonic load when the first filter APF1 does not fulfill its
Fig. 7. Picture of laboratory setup where the proposed topology is tested.
TABLE II
PARAMETERS USED IN CONTROL FOR BOTH INVERTERS APF1 AND APF2
task. This may happen in transient conditions due to the slow
response of the APF1 as previously presented.
Another particular case is when the APF1 is programmed to
reduce (but not completely) the amount of mitigated harmonics
due to different operating conditions, which automatically en-
ables the second filter APF2 to take over the harmonic miti-
gation without any special communication between both active
power filters. However, as initially mentioned, in this case the
power rating of the second filter should be sized for that pur-
pose.
IV. IMPLEMENTATION
The proposed topology and control method are tested on a
laboratory setup (Fig. 7) composed of two Danfoss inverters
VLT 5006 rated as 400 V/7.6 kVA each. The switching fre-
quency was set to 12.6 kHz for both inverters. The control algo-
rithm is implemented with a dSpace system DS1103, using the
Matlab/Simulink Real Time Workshop toolbox [17], having the
control parameters set as in Table II.
In practice a proper the design of the inductors depends on
the mitigated harmonic current spectrum and its power level.
A higher power inverter requires a lower inductance in order
to reach lower iron losses. A faster inverter (i.e., compensationof higher harmonic orders) requires also a lower inductance to
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 7/13
ASIMINOAEI et al.: PERFORMANCE IMPROVEMENT OF SHUNT ACTIVE 253
Fig. 8. General diagram of the laboratory setup.
TABLE IIIMEASURED HARMONIC CURRENT OF ASD LOAD AT 5.9 kVA POWER
achieve a higher output current gradient . APF1 compen-
sates here only fifth and seventh, but due to the higher power
level of the first inverter its boost inductance is of a lower value.
The second inverter APF2 compensates here the high order har-
monic currents, and even if the inverter is of a smaller power
it still requires a lower inductor to achieve a high bandwidth
and high . The selected values of the boost inductors are
5.6 mH for the feedback APF1 and 3.0 mH for the feedforward
APF2 (Fig. 8).
The nonlinear load that creates the harmonic currents is a
three-phase diode rectifier, which replicates the behavior of atypical adjustable speed drive (ASD). The rectifier may be set
as dc-smoothed capacitor or inductor by switching “sw1” and
“sw2” such that different cases may be created.
The load is a variable resistor with values between 50–200 .
This way one may create different levels of harmonic currents.
Harmonic distortion created by the ASD is measured as indi-
cated in Table III and Fig. 9, for a typical industrial ASD of a
rated power of 5.9 kVA.
A. Feedback Compensation
This section describes the mitigation performance of only the
APF1-feedback compensation loop (the APF2-feedforward is
disconnected). Here the reference is set for mitigation of onlythe fifth and seventh harmonics. As it can be seen in Fig. 10,
Fig. 9. Measured line current and supply voltage when noneof theactive filtersis running. The line current consists of the ASD current.
Fig. 10. Measured steady-state response of the APF1—feedback compensa-tion. The harmonic compensation reference is set for mitigation of fifth andseventh harmonics.
and more detailed in Table V column 3, the reduction of the
fifth and seventh harmonics currents is from the initial values
of 25% respective 8.7% down to 0.2% respective 0.6%. As the
higher harmonics are not compensated, the resultant waveform
of the line current is still distorted (see Fig. 10).
B. Feedforward Compensation
This experiment was carried out with only the APF2-feed-
forward loop (the APF1-feedback is disconnected). The refer-
ence is set for mitigation of the high order harmonics, from 11th
up to 31st. As discussed in Section III the feedforward inverter
is able to take over all harmonic currents, including the fifth
and seventh by enabling the redundant mode [ 1 in (15)].
Two tests are performed with and without this functionality en-
abled, in order to show its harmonic mitigation performance. It
is clear that, if the filter is able to compensate for high order har-
monics, it is also able to compensate for low orders as the fifth
and seventh. However, this feature would require a considerableincrease of the inverter power rating, not evaluated here.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 8/13
254 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
TABLE IVCHARACTERISTICS OF THE PROPOSED TOPOLOGY DEPENDING ON THE DESIRED COMPENSATED
SPECTRUM AND SELECTED SWITCHING FREQUENCY OF EACH INVERTER
Fig. 11. Measured steady-state response of the APF2—feedforward compen-sation. The harmonic compensation reference is set for mitigation of the highorder (11th to 31st) harmonic currents.
A typical stationary response for the feedforward APF2 is
given in Fig. 11, where the total line current still contains a sig-
nificant quantity of harmonic distortion, but with smoother cur-
rent gradients. As the current spectrum indicates (see Table V
column 5) the APF2 filter compensates only for the harmonic
currents higher than 11th order.
C. Combined Compensation
Different tests can be performed with the proposed topologydepending on the imposed compensated spectrum and the se-
lected switching frequency of each inverter, as it can be seen in
Table IV. In this paper only Case-1 and Case-3 are tested.
First, both feedback and the feedforward loops are connected
together and set as in Case-1, Table IV. The result, seen in the
line current waveform, represents the cumulative effect of both
loops. Thus, both low order and high order harmonics are com-
pensated, as shown in Fig. 12. Table V compares the harmonic
current spectrum for each of the measured cases. The proposed
topology brings the THD from the initial value of 27%, without
any filtering, down to less than 2% with both APF filters active.
The control method uses harmonic integrators, which ideally
present infinite amplification at the selected harmonic. There-fore, the mitigation performance of each branch should theo-
Fig. 12. Measured steady-state response of the proposed topology. Both loworder and high order harmonic currents are mitigated down to 2% THD , by
enabling APF1 and APF2 together.
retically be identical (see columns 2 and 4). Furthermore, it is
proven in [6], that although some of the gains are different,
the transfer functions of the feedforward and feedback loops
are equivalent. This should give the same harmonic mitigation
performance of the feedback compared to the feedforward re-
spective the proposed topology. However, it is experimentally
noticed that the proposed topology provides a better harmonic
current mitigation, presumably due to the cascade configuration
(see columns 6 respective 7 of Table V). In order to measure thedata presented in columns 2 and 4 of Table V, the control of each
branch APF1 or APF2 is configured as in (13) by enabling all
five orders of the harmonic integrators, 6,12,18,24,30 .
The second test is with the proposed topology set as in Case-3
Table IV, but in a particular case as redundant-mode, which is
done by setting the parameter 1 in (15) and Fig. 5. The
steady state harmonic mitigation performance can be seen in
Table V column 7, which is the best compared to the other pre-
sented cases. Fig. 13 shows the dynamic response of the entire
APF for a load step of 5 kW due to the ASD. Active filter APF1
responds slower because of the lower gain of its equiva-
lent harmonic integrator. Active filter APF2 responds faster and
takes over the compensation of the fifth and seventh harmonicsduring the transient. This is possible due the enabled redun-
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 9/13
ASIMINOAEI et al.: PERFORMANCE IMPROVEMENT OF SHUNT ACTIVE 255
TABLE VCOMPARISON OF THE APF’S HARMONIC MITIGATION PERFORMANCE FOR EACH MEASURED
CASE: F EEDBACK, FEEDFORWARD AND THE PROPOSED PARALLEL TOPOLOGY
Fig. 13. Dynamic response of the proposed topology in redundant-mode, for aload step of 5 kW created by the ASD. APF1 responds slower than APF2 dueto different parameters set for the current controller.
dant-mode as it is also shown in Fig. 6. As APF1 reaches the
steady-state conditions, APF2 ceases to mitigate the fifth and
seventh harmonic currents.
Another measurement with the redundant-mode is presented
in Fig. 14, with APF1 starting up (reproducing a possible
maintenance intervention when APF1 had to be stopped and
restarted). Fig. 14 shows the dynamic response of the proposed
topology when APF1 starts. The active filter APF2 is running,replacing the harmonic mitigation tasks of APF1. As soon as
Fig. 14. Dynamic response of the proposed topology in redundant-mode, when
the APF1 is powered on while APF2 was compensating the overall harmoniccurrent spectrum. Once APF1 becomes active APF2 keeps its main task of com-pensating only the higher harmonic orders.
APF1 becomes active, both active filters return to normal oper-
ation (i.e., APF1 takes out lower harmonics and APF2 higher
harmonics), due to the load-sharing feature. As APF1 has to
start from zero-conditions, its dc-voltage has to be increased
to the reference value, which explains the fundamental current
drained at the beginning. As it can be seen the output current of
both APF inverters are similar, which means that both must besized to withstand the maximum harmonic current.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 10/13
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 11/13
ASIMINOAEI et al.: PERFORMANCE IMPROVEMENT OF SHUNT ACTIVE 257
Fig. 15. Estimated ef ficiency limit based on the switching frequency and theload current THD .
is output inverter current, which can be expressed as a function
of the load current and filter THD , is a constant
including all other constant parameters, and is the abso-
lute value function.
Assuming that in the harmonic-sharing mode the inverter
switches at a lower frequency, the switching losses of APF1
inverter are reduced by a factor of
THD
THD (21)
Switching losses in harmonic-sharing mode are
THD THD
(22)
Switching losses in load-sharing mode are equally distributed
between inverter
THD (23)
The ef ficiency improvement of the harmonic-sharing compared
to load-sharing mode is estimated as
THD THD
THD (24)
Fig. 15 gives a graphical interpretation of (24), as a function of
the switching frequency factor .
Thus, assuming a reduction by half of the switching fre-
quency, i.e., 0.5, the ef ficiency improvement of the
harmonic-sharing is
for theoretical
ASD model for measured data (25)
One may determine the boundary limit of the switching fre-
quency where the ef ficiency of the harmonic-sharing is lower
compared to the load-sharing. Considering also the data inTable VI, it seems that in load-sharing the inverters have an
Fig. 16. Steady-state response of theAPF filters’ currents and theirduty-cycles.
overall smaller power, even though the ef ficiency may not be
very high. The ef ficiency of the harmonic-sharing mode is
attractive only if the switching frequency of the APF1 inverter
(mitigating the lower order harmonics) is at maximum two
times smaller than the switching frequency of the APF2 inverter
(mitigating the higher order harmonics).
As it was previously mentioned, another advantage of the
topology is that, having two separately controlled inverters, they
can be interleaved by 180 , to reduce the line switching current
ripple.
Fig. 16 shows the filter currents and along with their
duty-cycles. It can be noticed that, even the output currents aredifferent, the duty-cycles look similar. This is because the in-
verter voltage must be comparable to the line voltage in order
to make the current flowing through the line inductors. Thus,
the duty-cycles contain a fundamental component that makes
their waveforms to resemble. This property is used to reduce
the switching ripple of the line current if one uses two carriers
shifted by 180 . A simplified illustration of the interleaving is
provided in Fig. 17 for one phase only. The amplitude of the
current ripple in each inverter depends on the used inductors.
Furthermore, even though the carriers are interleaved by
180 , the duty-cycles are ac-signals, therefore determining
different pulse width lengths in each inverter. Thus a complete
cancellation of the current ripple at the switching frequencyis not possible. However, the interleaving helps in minimizing
the total line current ripple. The switching frequency is only
partially canceled, as it can be seen in Fig. 18, which reduces
the requirement of a stronger line filter against EMIs. A smaller
EMI filter is assumed to be inexpensive, as it requires smaller
line connected capacitors. Furthermore, smaller capacitors
mean an increase of the system stability, because possible
power system resonances between the capacitors and source
impedances are shifted to higher frequencies. The resonances
may be easily damped and may not interfere with the control.
If the rated power of APF2 is of a small value, as it is cal-
culated in (17), then the load-sharing feature cannot be used.
Therefore, one may need to assign a higher rated power for thesecond inverter (APF2), in order to operate in load-sharing. This
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 12/13
258 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
Fig. 17. Simplified description of the current ripple based on the on-off con-
duction instants with the carriers interleaved by 180 .
Fig. 18. Harmonic spectrum of thefilters’ currents and total line current. Spec-trum shows the reduction of the switching frequency
f
in the source current
I
due to 180 interleaved carriers.
means a higher cost for the second inverter, but the advantage
is the achievement of redundancy and ride-through functions
when one inverters fails. The ratio of the inverter’s size becomes
a matter of practical design. For instance if APF2 is only used
for mitigation of transient conditions due to slower APF1 re-
sponse, then its rated power may be selected in the range of
25%–50% of APF1 power. If APF2 is going to be permanently
used for load-sharing, then its rated power would be comparableto APF1.
VI. CONCLUSION
This paper describes a new topology for dual operation of ac-
tive power filters. The novelty consists in a parallel connection
of two active filters, one working in feedforward current loop
and the other in feedback current loop, both sharing the same
load current sensor. The proposed topology is theoretically an-
alyzed and then practically tested on a laboratory platform.The most significant features of the proposed solution are as
follows.
— It improves the stationary performance compared to an
APF based on a single inverter.
— It provides an improved dynamic response in frequency-
sharing operation due to the fact that one filter is pro-
grammed for fast compensation, while the other is effec-
tive in stationary operation.
— Load distribution with or without redundancy is possible
in load-sharing operation.
—Wireless operation of the twofilters is an intrinsic property
of this topology in all operating situations.
—Current ripple reduction is possible and was confirmed ininterleaving operation.
— The overall achieved THD performance is below 2% from
uncompensated THD value of 27%.
The proposed solution is targeted for medium power Ad-
justable Speed Drives applications where the harmonic pollu-
tion is a significant issue.
REFERENCES
[1] IEEE Recommended Practice and Requirement for Harmonic Control
in Electrical Power Systems, IEEE Std. 519-1992, 1993.[2] S. Hansen, P. Nielsen, P. Thoegersen, and F. Blaabjerg, “Line side har-
monic reduction techniques of pwm adjustable speed drives—a cost-benefit analysis,” in Proc. PCIM’01, 2001, pp. 39–46.[3] W. M. Grady, M. J. Samotyj, and A. H. Noyola, “Survey of active
power line conditioning methodologies,” IEEE Trans. Power Delivery,vol. 5, no. 3, pp. 1536–1542, Aug. 1990.
[4] H. Akagi and K. Nabae, “Control strategy of active power filters usingmultiple voltage source PWM converters,” IEEE Trans. Ind. Appl., vol.lA-22, no. 3, pp. 460–466, May/Jun. 1985.
[5] P. Mattavelli, “A closed-loop selective harmonic compensation for ac-
tive filters,” IEEE Trans. Ind. Appl., vol. 37, no. 1, pp. 81–89, Jan./Feb.2001.
[6] S. Khositkasame and S. Sangwongwanich, “Design of harmonic cur-
rent detector and stability analysis of a hybrid parallel active filter,” inProc. Power Conversion’97 , 1997, vol. 1, pp. 181–186.
[7] L. Asiminoaei, E. Aeloiza, J. H. Kim, P. Enjeti, F. Blaabjerg, L. T.Moran, and S. K. Sul, “An interleaved active power filter with reducedsize of passive components,” in Proc. APEC’06 , 2006, vol. 1, pp.
969–976.[8] S. Kim and P. Enjeti, “A new hybrid active power filter (APF)
topology,” in Proc. APEC’01, 2001, vol. 2, pp. 835–841.[9] V. Soares, P. Verdelho, and G. Marques, “Active power filter con-
trol circuit based on the instantaneous active and reactive current id-iqmethod,” in Proc. PESC’97 , 1997, vol. 2, pp. 1096–1101.
[10] N. Mendalek, K. Al-Haddad, F. Fnaiech, and L. A. Dessaint, “Slidingmode control of 3-phase 3-wire shunt active filter in the dq frame,” inProc. Electron. Comp. Eng. Conf., 2001, vol. 2, pp. 765–769.
[11] C. Lascu, L. Asiminoaei, I. Boldea, and F. Blaabjerg, “High perfor-mance currentcontroller for selectiveharmonic compensation in activepower filters,” in Proc. OPTIM’06 , 2006, [CD ROM].
[12] H. Akagi, “Control strategy and site selection of a shunt active filterfor damping of harmonic propagation in power distribution systems,”IEEE Trans. Power De1ivery, vol. 12, no. 1, pp. 354–362, Feb. 1997.
[13] R. I. Bojoi, G. Griva, V. Bostan, M. Guerriero, F. Farina, and F. Pro-
fumo, “Currentcontrol strategy for powerconditioners using sinusoidalsignal integrators in synchronous reference frame,” IEEE Trans. Power Electron., vol. 20, no. 6, pp. 1402–1412, Nov. 2005.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DA PARAIBA. Downloaded on May 17,2010 at 20:33:59 UTC from IEEE Xplore. Restrictions apply.
8/7/2019 Performance Improvement of Shunt Active_TPE_2007
http://slidepdf.com/reader/full/performance-improvement-of-shunt-activetpe2007 13/13
ASIMINOAEI et al.: PERFORMANCE IMPROVEMENT OF SHUNT ACTIVE 259
[14] J. Allmeling, “A control structure for fast harmonics compensation inactive filters,” IEEE Trans.Power Electron., vol.19,no. 2,pp.508–514,Mar. 2004.
[15] M. J. Newman, D. N. Zmood, and D. G. Holmes, “Stationary frameharmonic reference generation for active filter systems,” IEEE Trans.Ind. Appl., vol. 38, no. 6, pp. 1591–1599, Nov./Dec. 2002.
[16] R. Teodorescu, F. Blaabjerg, M. Liserre, and P. C. Loh, “Proportional-resonant controllers and filters for grid-connected voltage-source con-
verters,” Proc. Inst. Elect. Eng., vol. 153, no. 5, pp. 750–762, 2006.[17] Matlab/Simulink, “Software installation and management guide,” in
Proc. Real-Time Workshop dSPACE DS1103 Hardware, 2004, [CD
ROM].[18] A. M. Hava, R. J. Kerkman, and T. A. Lipo, “A high performance gen-
eralized discontinuous PWM algorithm,” IEEE Trans. Ind. Appl., vol.34, no. 5, pp. 1059–1071, Sep./Oct. 1998.
Lucian Asiminoaei (S’03–M’06) was born inGalati, Romania, on April 3, 1973. He received theB.Sc. and M.Sc. degrees in electrical engineeringfrom “Dunarea de Jos” University of Galati, in 1996and 1997, respectively, and is currently pursuing thePh.D. degree at the Institute of Energy Technology,Department of Power Electronics and Drives, Aal-borg University, Aalborg, Denmark.
From1996 to1999, hewas withIron& Steelworks
Sidex S.A., Galati, as a Maintenance Engineer and in1999 moved to the IT Department, IspatSidex LNM
Group, Galati, as a Hardware Engineer. In February 2003, he joined the Instituteof Energy Technology, Department of Power Electronics and Drives, AalborgUniversity, and is involved in projects sponsored by Danfoss Drives A/S, Den-mark and Power Lynx A/S, Denmark. His areas of interests include harmonicmitigation, harmonic measurement, and design of active and hybrid filters.
Cristian Lascu received the M.S. and Ph.D. de-grees in electrical engineering from the UniversityPolitehnica Timisoara, Timisoara, Romania, in 1995and 2002, respectively.
In 1995, he joined the Department of ElectricalEngineering, University PolitehnicaTimisoara wherehis research was focused on power electronics andhigh performance electrical drives. He was a VisitingResearcher at the Institute of Energy Technology,
Aalborg University, Aalborg East, Denmark, in 1997and 2005, and with the Department of Electrical
Engineering, University of Nevada, Reno, from 1999 to 2000. From 2002 to
2004, he was with SIEI S.p.A., Italy, working on advanced power electronicsand drives for electrical vehicles under a European Marie Curie Fellowship.
Dr. Lascu received the IEEE IAS Prize Paper Award in 1998.
Frede Blaabjerg (S’86–M’88–SM’97–F’03) wasborn in Erslev, Denmark, on May 6, 1963. Hereceived the M.Sc.EE. and Ph.D. degrees fromAalborg University, Aalborg, Denmark, in 1987 and1995, respectively.
He was with ABB-Scandia, Randers, Denmark,from 1987 to 1988. He became an Assistant Pro-fessor in 1992 at Aalborg University, in 1996 an
Associate Professor, and in 1998 a Full Professorin power electronics and drives. In 2000, he was aVisiting Professor with the University of Padova,
Padova, Italy, as well as a part-time Programme Research Leader in windturbines at the Research Center Risoe. In 2002, he was a Visiting Professorat Curtin University of Technology, Perth, Australia. He is involved in morethan ten research projects within the industry. Among them is the DanfossProfessor Programme in Power Electronics and Drives. He is the author orcoauthor of more than 350 publications in his research fields including Controlin Power Electronics (New York: Academic, 2002). He is an Associate Editorfor the Journal of Power Electronics and Elteknik . He has been very involved inDanish Research policy in the last ten years. His research interests are in powerelectronics, static power converters, ac drives, switched reluctance drives,modeling, characterization of power semiconductor devices and simulation,wind turbines, and green power inverters.
Dr. Blaabjerg received the 1995 Angelos Award for his contribution inmodulation technique and control of electric drives, the Annual Teacher Prize
from Aalborg University, in 1995, the Outstanding Young Power ElectronicsEngineer Award from the IEEE Power Electronics Society in 1998, five IEEEPrize paper awards during the last five years, the C. Y. O’Connor fellow-ship from Perth, Australia in 2002, the Statoil-Prize for his contributions inpower electronics in 2003, and the Grundfos-prize for his contributions inpower electronics and drives in 2004. He is an Associate Editor of the IEEETRANSACTIONS ON INDUSTRY APPLICATIONS and the IEEE TRANSACTIONS ON
POWER ELECTRONICS. He is a member of the Danish Academy of TechnicalScience, the European Power Electronics and Drives Association, and theIEEE Industry Applications Society Industrial Drives Committee. He is also amember of the Industry Power Converter Committee and the Power Electronics
Devices and Components Committee, IEEE Industry Application Society.
Ion Boldea (M’77–SM’81–F’96) received the B.S.
and Ph.D. degrees in electrical engineering from theUniversity Politehnica, Timisoara, Romania, in 1967and 1973, respectively.
He is currently a Full Professor at the UniversityPolitehnica Timisoara. He has worked and publishedextensively on linear and rotary electric machinesand their power electronics control, with and withoutmotion sensors. He co-authored Induction MachineHandbook (Orlando, FL:CRC, 2001), Linear Motion
Electromagnetic Devices (London, U.K.: Taylor &Francis, 2001), Electric Drives (Boca Raton, FL: CRC, 2006), and The ElectricGenerators Handbook (Boca Raton, FL: CRC, 2006). He spent about five yearsas a Visiting Scholar in the U.S. and U.K., and presented keynote addresses,intensive courses, and does consultant work in the U.S., Europe, and Asia. He is
Associate Editor of the Electric Power Components and Systems Journal, andDirector and Founder of the Internet-only, Journal of Electrical Engineering.
Dr.Boldeais an active memberof the Industrial Drivesand Electric Machines
Committee, IEEE Industry Applications Society, and Co-chairman of the IEEEIAS Technically Sponsored OPTIM 96, 98, 00, 02, 04, and 06 InternationalConferences.