+ All Categories
Home > Documents > Performance of DFIG during symmetrical and asymmetrical ...profile during severe faults. In this...

Performance of DFIG during symmetrical and asymmetrical ...profile during severe faults. In this...

Date post: 16-Feb-2021
Category:
Upload: others
View: 2 times
Download: 0 times
Share this document with a friend
12
Performance of DFIG during symmetrical and asymmetrical grid faults with damping controller based SSSC D.V.N.Ananth 1 , G.V.Nagesh Kumar 2 , D.Deepak Chowdary 3 , K.Appala Naidu 2 1 DADI Institute of Engg. & Technology, Anakapalli, Visakhapatnam, Andhra Pradesh, INDIA, [email protected], ph: +91-8500265310 2 Vignan’s Institute of Information Technology, Visakhapatnam, Andhra Pradesh, INDIA, [email protected] 3 Dr. L. Bullayya Engg. College for Women, Visakhapatnam, Andhra Pradesh, INDIA [email protected] Abstract The renewable energy resources like wind with doubly fed induction generator (DFIG) is playing a vital role in meeting the ever-increasing load demand. Most of the industrial and commercial loads are sensitive to fault, as surge current damages the system. The DFIG wind turbine set is very sensitive when grid fault occurs, which damages the stator and rotor winding and also the converters and the capacitor. To overcome these effects, DFIG grid connected system is equipped with damping controller based static synchronous series compensator (SSSC) based series FACTS device with a new control scheme for oscillations damping and quicker voltage injection technique. Voltage damping circuit is provided in the outer control loop of SSSC for improving voltage profile of stator and rotor. The inputs for the damping circuit are rotor speed and stator real power and controller is designed with cascaded 2nd order lead-lag compensator. The results are presented for single line, two lines and three lines to ground faults and system behavior is examined. Keywords: DFIG, static synchronous series compensator (SSSC), damping lead lag compensator, symmetrical and asymmetrical faults 1. Introduction With the latest trends in renewable energy resources, wind turbine based power generation is getting importance as conventional synchronous generator based power plants are not alone sufficient to convene with the ever growing load demand. The DFIG based wind generators are getting popular as real and reactive power sharing, load withstanding capability, low cost converters are better than other wind generators. Faults are inevitable for any power system and are very dangerous for DFIG wind turbine system [1]. Based on this paper, if fault current is not controlled, the inrush current will damage the converters, dc capacitor, stator and rotor winding. Crowbar type of protection is used to divert the fault inrush International Journal of Pure and Applied Mathematics Volume 114 No. 9 2017, 125-135 ISSN: 1311-8080 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu Special Issue ijpam.eu 125
Transcript
  • Performance of DFIG during symmetrical and

    asymmetrical grid faults with damping controller

    based SSSC

    D.V.N.Ananth1, G.V.Nagesh Kumar2, D.Deepak Chowdary3,

    K.Appala Naidu2 1DADI Institute of Engg. & Technology, Anakapalli,

    Visakhapatnam, Andhra Pradesh, INDIA, [email protected],

    ph: +91-8500265310 2Vignan’s Institute of Information Technology, Visakhapatnam,

    Andhra Pradesh, INDIA, [email protected] 3Dr. L. Bullayya Engg. College for Women, Visakhapatnam, Andhra

    Pradesh, INDIA

    [email protected]

    Abstract

    The renewable energy resources like wind with doubly fed induction generator (DFIG) is

    playing a vital role in meeting the ever-increasing load demand. Most of the industrial and

    commercial loads are sensitive to fault, as surge current damages the system. The DFIG

    wind turbine set is very sensitive when grid fault occurs, which damages the stator and

    rotor winding and also the converters and the capacitor. To overcome these effects, DFIG

    grid connected system is equipped with damping controller based static synchronous series

    compensator (SSSC) based series FACTS device with a new control scheme for oscillations

    damping and quicker voltage injection technique. Voltage damping circuit is provided in

    the outer control loop of SSSC for improving voltage profile of stator and rotor. The inputs

    for the damping circuit are rotor speed and stator real power and controller is designed

    with cascaded 2nd order lead-lag compensator. The results are presented for single line,

    two lines and three lines to ground faults and system behavior is examined.

    Keywords: DFIG, static synchronous series compensator (SSSC), damping lead

    lag compensator, symmetrical and asymmetrical faults

    1. Introduction With the latest trends in renewable energy resources, wind turbine based power

    generation is getting importance as conventional synchronous generator based

    power plants are not alone sufficient to convene with the ever growing load

    demand. The DFIG based wind generators are getting popular as real and reactive

    power sharing, load withstanding capability, low cost converters are better than

    other wind generators. Faults are inevitable for any power system and are very

    dangerous for DFIG wind turbine system [1]. Based on this paper, if fault current

    is not controlled, the inrush current will damage the converters, dc capacitor, stator

    and rotor winding. Crowbar type of protection is used to divert the fault inrush

    International Journal of Pure and Applied MathematicsVolume 114 No. 9 2017, 125-135ISSN: 1311-8080 (printed version); ISSN: 1314-3395 (on-line version)url: http://www.ijpam.euSpecial Issue ijpam.eu

    125

  • current, thereby damage can be prevented [2-4]. This type of protection has a major

    drawback that, it will draw huge reactive power from the grid as the DFIG now

    runs like squirrel cage induction generator. Therefore many recent works deal with

    new control strategies to overcome different types of faults. Improved

    demagnetizing, feed-forward transient current control, current-reversely-tracking

    control (CRTC) etc [5, 6] are recently proposed techniques for DFIG to improve

    fault ride through and the authors are almost successful.

    New controllers like PI + resonant (PIR) or P+ Resonant (PR), internal model

    control (IMC) [7], sliding mode control (SMC), fuzzy and many are used to improve

    the speed of operation instead of conventional PI controller. Metaheuristic control

    techniques like bacterial forging, particle swarm optimization etc techniques are

    also used for tuning of PI parameters under different fault conditions. Feed forward

    regulator, magnetization current compensation, LQR, impedance based high

    frequency resonance etc are new techniques to improve performance when DFIG

    tied to a week grid.

    The FACTS devices like dynamic voltage restorer (DVR), STATCOM [8, 11],

    UPFC, dual STATCOM [9], fault current limiters (FCL) [10], energy storage

    devices like SMES are extensively used in the literature to overcome any type of

    faults and to have better performance of DFIG. Among all these devices, DVR,

    STATCOM and FCL are more promising and help in maintaining nearly flat

    profile during severe faults. In this paper, static synchronous series compensator

    (SSSC) is used to overcome different types of fault occurring near the grid. In this a

    24 unit DFIG equivalent grid connected system is considered. The performance of

    the DFIG under single line, two lines and three lines to ground faults are observed

    with SSSC using MATLAB/ SIMULINK.

    2. Rotor and grid side converter design The direct and quadrature (d and q) axis DFIG rotor voltage equations and the

    rotor and stator windings double d and q axis fluxes are given by

    {

    ( )

    ( )

    ( )

    ( ) ( ) ( )

    (1)

    From the basic equations of DFIG [9], the rotor direct and quadrature axis

    voltages are expressed as

    (

    )

    (2a)

    (

    )

    ( ) (2b)

    where is synchronous speed and is rotor speed.

    The block diagram of RSC in Fig.1a is based control circuit for better

    performance under LVRT problem. The sub-circuit is EFOC technique using the

    equations 2a and 2b. These equations if rewritten as decoupled parameters as in

    equations 3a and 3b are developed for RSC controller.

    International Journal of Pure and Applied Mathematics Special Issue

    126

  • ( ) (3a)

    ( ) (3b)

    The rotor speed in general is and the stator synchronous speed. However, this is varied from to a new synchronous speed during abnormal

    conditions is or simply At ideal situations,

    which is reference stator d-

    axis vector flux is zero in magnitude and q-axis flux . These holds good for stator

    flux magnitude at a given back emf and the rotor speed. The rotor dq axis

    transient current are represented in the equations 4a and 4b as

    (4a)

    (

    )

    (4b)

    The rotor reference voltages in two axis Park’s dq transformation is rewritten

    with the help of equations 3a and 3b are given below. This is the output rotor

    windings voltage during normal and transient conditions are

    (

    (

    ) ) (5A)

    (

    (

    ) ) (5B)

    The direct (d-axis) and quadrature (q-axis) axis are two axis rotating frame of

    reference. Now again, the stator d axis and q axis currents in equations are written

    in terms of stator voltage and rotor currents

    dr

    s

    mdr

    s

    m

    s

    dsds i

    X

    X

    Xs

    Vsi

    L

    L

    Li

    (6a)

    ,qrs

    mqs i

    X

    Xi

    (6b)

    The grid two axis voltage in GSC current, voltage, grid resistance and

    inductance forms as

    1dgqgs

    dg

    dggdg VLidt

    diLiRV

    (7a)

    1qgdgs

    qg

    qggqg VLidt

    diLiRV

    (7b)

    The dynamic dc voltage across the dc link capacitor is given in equation (8) as a

    function of grid side converter (GSC) and rotor side converter (RSC) and dc link

    voltage.

    dc

    rgdc

    CV

    PP

    dt

    dV

    (8)

    So, the change in DC link voltage across the capacitor depends on rotor voltage

    and stator voltage. Hence based on the above discussion, the GSC and RSC control

    schemes are developed which is explained in the next section. It is observed that if

    rotor voltages are controlled effectively using proper control technique and PWM

    operation, the rotor current flow is controlled. When the stator voltage magnitude

    increase or decrease from normal value, consequently the rotor currents will be

    affected and vice-versa. This means, if there is a decrease or increase in the stator

    International Journal of Pure and Applied Mathematics Special Issue

    127

  • voltage, if rotor currents are adjusted, the stator voltage magnitude can be

    improved. In the similar way, with d and q axis control of rotor voltages, the

    electromagnetic torque (EMT) can be controlled. Also, it is observed that, the stator

    voltage is like a quadratic function with square of voltage term and a single stator

    voltage term. If stator voltage increase or decrease suddenly, it leads to an

    oscillations and change in magnitude respectively in the EMT. The leakage factor

    can be stated as .

    3. RSC and GSC design and operation The RSC refers to rotor side converter and GSC is for grid side converter. The

    RSC operation is to manage and preserve the speed of rotor during abnormal

    conditions like faults thereby stator frequency connected to grid must not deviate

    by using d-axis current control scheme. It also helps in regulating the grid reactive

    power using q-axis current control method as in Fig. 1a. The outer loop of RSC

    consists of speed and reactive power control loops and inner control loops has d and

    q two axis current control loops. The reference speed of rotor is derived using

    lookup table method from the wind turbine optimal power output PmOpt and grid

    power demand. Based on the value of Pm,gOpt, rotor is rotated at optimal speed to

    draw optimal (maximum) power from DFIG WECS set. The Speed error is

    minimized with PI controller to zero value and the output is the product of stator

    flux (Fs) and ratio of stator and rotor inductances (Ls and Lr) to obtain reference

    rotor q-axis current (Iqr*). The output from each PI controller is controlled with a

    disturbance voltage VdqR to get reference pulse generation voltage. It is to note

    that, the pulses are synchronized at slip frequency of RSC rather at fundamental

    nominal grid frequency. The synchronizing slip frequency is converted back using

    inverse Park’s transformation to get abc stationary rotor reference PWM voltage

    parameters as in the figure.

    Fig. 1a Rotor side converter (RSC) control scheme for DFIG,

    rs

    m

    LL

    L21

    International Journal of Pure and Applied Mathematics Special Issue

    128

  • Fig. 1b Grid side converter (GSC) control scheme for DFIG

    The GSC basic block diagram is depicted in Fig.1b. For a given wind speed, the

    turbine reference control power is predictable with a lookup table. The stator real

    power (Pstator) is calculated and the power error is the difference between two

    powers (dP) which are preserved near the zero value by using PI controller. The PI

    controller output is multiplied with constant (Kp) called real power constant gives

    actual convenient power after interruption. The difference in square of reference

    capacitor voltage across dc link (Vdc*) and square of actual dc link voltage (Vdc) is

    [Vdc*-Vdc] controlled using PI controller to get reference controllable real power.

    The error in the reference and actual controllable power is divided by using 2/3Vsd

    to get direct axis (d-axis) reference current near grid terminal (Igdref). Difference in

    Igdref and actual d-axis grid current is controlled by PI controller to get d-axis

    voltage. But to achieve better response to transient conditions, decoupling d-axis

    voltage is added as in case of separately excited DC motor. This decoupling term

    helps in controlling steady state error and fastens transient response from DFIG

    during low voltage ride through (LVRT) or during sudden changes in real or

    reactive powers from/ to the system.

    The block diagram of GSC control circuit is shown in Fig. 1b and RSC is

    designed to get better performance for LVRT issues at (PCC) point of common

    coupling. During normal conditions like steady average wind speed and good

    ambient temperature, the reactive power will be zero or very low and hence stator

    power pumped to the grid will be high. This power control can do use the outer

    control loop of GSC. The reference power is obtained from the characteristic lookup

    table with characteristics of DFIG adopted for desired operation. This reference

    power is compared to actual power and is maintained using the PI control of GSC

    as shown in Fig.1. During faults, the stator power varies based on the reactive

    power demand, which will is supplied by GSC through the capacitor at the back to

    back converters. As reactive power demand increases, stator power changes

    accordingly, and hence the terminal voltage at GSC change respectively and

    thereby direct axis current injecting at PCC changes. During steady sate, stator

    rms voltage and reactive power are constant. But when the fault occurs, the stator

    voltage changes, hence reference rms stator voltage changes. This will make the

    quadrature component of GSC current to vary. This total mechanism is fast and

    can work for symmetrical as well as asymmetrical faults.

    International Journal of Pure and Applied Mathematics Special Issue

    129

  • 4. Design of FACTS and energy storage devices

    for LFC The FACTS and energy storage devices are being used in power system for

    many applications like voltage mitigation, power quality improvement, power

    transfer capability improvement, power oscillations damping, frequency regulation

    etc. Among many FACTS devices SSSC is an excellent series FACTS device used

    for real and reactive power control. Voltage stability will be improved with reactive

    control and frequency control is with real power control. The block diagram of

    SSSC is shown in Fig.2a and with transfer function based control design in Fig. 2b.

    The SSSC produces three phases voltage in quadrature with the line current follow

    an inductive or capacitive reactance based on the current flow in the transmission

    line. The magnitude and polarity of Vq decides the compensation to be inductive or

    capacitive to stabilize the frequency and real power deviations during wind speed

    or load change.

    Fig. 2a Block diagram of DFIG with SSSC device

    Fig. 2b transfer function based control of SSSC

    5. Result Analysis For the DFIG network in Fig.2a, the simulation results are presented in this

    section. A fault is situated near the PCC at 0.3s and cleared at 0.5s. The behavior of

    DFIG system and the compensation of SSSC for different faults under cases three,

    double and single phases to ground are analyzed.

    5.1 Case A: Three phases to ground or symmetrical fault

    International Journal of Pure and Applied Mathematics Special Issue

    130

  • For the symmetrical fault at PCC with 0.002Ω resistance between 0.3 and 0.5,

    the waveforms are given in Fig.3. The voltage at grid is decreased from 1pu to

    0.5pu (per unit) and the current shrink from 1pu to 0.4pu as shown in Fig. 3a.

    When the fault is suppressed at 0.5s, the voltage of grid raised to 1pu slowly than

    the current with surge of 1.1pu. It is due to the fact that sudden change in load

    impedance leads to current increase in the network. The similar behavior is

    observed with stator as it is also linked to the same phases directly. The rotor

    voltage and current are shown in the figure 3b. The rotor voltage is almost constant

    and there is a small dip in the current from 0.55pu to 0.4pu. The RSC and GSC

    helps in maintaining the voltage and SSSC helps in still maintain at a better

    voltage profile by mitigating the surge currents. So, voltage and current profiles are

    maintained with converters and SSSC.

    Cur

    rent

    (p.u

    .)

    V

    olta

    ge (p

    .u.)

    Time (S)Time (s)

    Cur

    rent

    (p.u

    .)

    V

    olta

    ge (p

    .u.)

    Fig. 3a Grid voltage (top) and current (bottom) in pu Fig. 3b rotor voltage (top)

    and current (bottom) in pu for three phases to ground fault

    Time (S)

    Torqu

    e (p.u

    .) ro

    tor sp

    eed (

    p.u.)

    Cap

    . Volt

    (p.u.

    )

    Time (S)

    Vol

    tage

    (p.

    u.)

    Fig. 3c dc caapcitor voltage, rotor speed and electromagnetic torque (EMT) in pu Fig. 3d SSSC injecting voltagein pu for three phases to ground fault

    From the Fig 3(c), the capacitor voltage is nearly constant dc voltage magnitude

    during and after the fault. The ripples decreased due to reversal of current in the

    RSC and GSC towards rotor and grid PCC. The dynamics of these are given by the

    equations (3a) to (8) as given in section 2. The rotor speed is almost constant at

    1.2pu i.e., during the fault from 0.3 to 0.5s and maintained constant then at 1.22pu.

    The electromagnetic torque (EMT) is initially at 0.6pu at 14m/s wind speed and

    reached to 0.05pu during fault without ripples and when fault is cleared, the EMT

    attained its pre-fault value. The oscillations in torque are damped because of the

    RSC control scheme with better control strategy and with SSSC damping control

    nature proposed in the paper. The SSSC injecting voltage is shown in Fig. 3(d). At

    the instant of fault, the voltage dip will be very high and surge currents increases.

    The dc capacitor voltage between the RSC and GSC of DFIG is increased. To

    International Journal of Pure and Applied Mathematics Special Issue

    131

  • mitigate them all, voltage injection of SSSC has to be high as shown in this figure

    3d. Then during the fault, because of voltage injection, the voltage profile of SSSC

    is maintained at 0.28pu for compensation and then decreased to a smaller value

    after the fault is cleared. The fifth order lead lag compensator helps to maintain

    generator speed and active powers from oscillations. This is done when the inputs

    are given command to the outer control loop of SSC. The inner control loops helps

    in controlling the current parameters, thereby with proper tuning of PI controllers,

    the voltage injection will be quicker and accurate. So, system performance during

    three phase to ground fault is improved with proposed SSSC control scheme and

    RSC and GSC control, schemes of DFIG.

    5.2 Case B: Two phases to ground fault

    The same system behavior with two lines to ground asymmetrical fault in

    phases A and B is shown in Fig.4. It is observed that A and B phases voltage

    magnitude decreased while phase C magnitude is having better voltage profile. But

    voltage surges are produced in the faulty phases during the fault. The grid current

    in two faulty phases increased and the healthy phase decreased to a smaller value

    as in Fig.4a. such type of fault is less severe than symmetrical fault for

    conventional synchronous generator plant. But, it is very dangerous for wind

    generator and too for DFIG as it has low rating converter.

    Curre

    nt (p

    .u.)

    Vol

    tage

    (p.u

    .)

    Time (S)

    Curre

    nt (p

    .u.)

    Volt

    age

    (p.u

    .)

    Time (S)

    Fig. 4a Grid voltage (top) and current (bottom) in pu Fig. 4b rotor voltage (top) and current (bottom) in pu for two phases to ground fault

    Time (S)

    Torq

    ue (p

    .u.)

    rot

    or s

    peed

    (p.u

    .) C

    ap. V

    olt (

    p.u.

    )

    Time (S)

    Vol

    tage

    (p.

    u.)

    Fig. 4c dc caapcitor voltage, rotor speed and electromagnetic torque (EMT) in pu Fig. 4d SSSC injecting voltagein pu for three phases to ground fault

    The rotor voltage and current with SSSC control scheme proposed is shown in

    Fig. 4b. It is observed that voltage and current profile of SSSC are improved. The

    voltage of rotor is almost constant and the current is having ripples without surges

    International Journal of Pure and Applied Mathematics Special Issue

    132

  • and rise in magnitude and has harmonic nature during the fault. the sudden

    change in flux do not decay instantly in the stator. The rotor mutual flux exchange

    with oscillating and damping nature of RSC makes it to have the waveform like

    this. If current limiting control wit faster decay control helps in improving the

    profile but the control scheme becomes little complicated. However, the behavior is

    better than the earlier system behavior without two times surge. In fig. 4c, the dc

    voltage across the capacitor between the back to back converters is having small

    oscillations between 1 and 0.9pu. The rotor speed is nearly constant at 1.2pu

    during and after the fault. The EMT is having oscillatory nature with the two

    phases to ground fault. It is not decaying to zero or reversing the polarity as with

    conventional systems. The SSSC voltage injection is shown in Fig. 4d, the faulty A

    and B phase voltages increased while the healthy phase voltage injection is like

    normal value during and before the fault. Hence, voltage injection of SSSC is better

    with the proposed control scheme.

    6. Conclusion In this paper, DFIG grid connected system is analyzed with two and three

    phases to ground fault in two cases. The performance is better with proposed RSC

    and GSC control scheme and further improved with proposed SSSC control scheme

    than with the literature survey. The voltage and current profile of rotor is improved

    and dc voltage across the back to back converters is nearly constant without swell

    during the fault. The EMT is having lesser swings than conventional system with

    symmetrical or asymmetrical fault without changing the polarity of torque to

    negative. The rotor speed is almost constant. The SSSC injecting voltage is quick

    and accurate as damping controller based fifth order transfer function is newly

    proposed in this paper. The RSC and GSC control schemes are proposed with

    lookup table based technique to have better reactive power to rotor speed profile.

    hence our proposed scheme is better than conventional control schemes with DVR

    or SSSC arrangement with easier control scheme, faster and accurate and holds

    good for symmetrical or asymmetrical fault with any decrease in the grid voltage.

    Appendix The simulation parameters of DFIG used are, Rated Voltage = 690V, Rated

    Power = 1.5MW, Stator Resistance Rs = 0.0049pu, , Stator Leakage Inductance Lls

    = 0.093pu, rotor Resistance Rrӏ = 0.0049pu, Rotor Leakage inductance Llr1 =

    0.1pu, Number of poles = 4, Mutual Inductance Lm = 3.39 pu, Inertia constant =

    4.54pu, DC link Voltage = 415V, DC link capacitance = 0.2F, Grid Voltage = 25 KV,

    Grid requency = 60 Hz. nominal wind speed = 14 m/sec. Grid side Filter: Lfg =

    0.6nH, Rfg = 0.3Ω, Rotor side filter: Lfr = 0.6nH, Rfr = 0.3mΩ, wind speed

    variations considered here in seconds: 8, 15, 20 and 10 at 15, 25 and 35s. variation

    in grid voltage: 0.8 to 1 and to 1.2pu at 20 and 30s, Reactive power variation: -0.6

    to 0 and +0.6pu at 20 and 30s.

    References 1. Ananth, D.V.N. and Kumar, G.N., “Performance Evaluation of DFIG

    During Asymmetrical Grid Disturbances Using Internal Model

    Controller and Resonant Controller”, International Journal on Electrical

    Engineering and Informatics, 8(3), p.494, 2016.

    International Journal of Pure and Applied Mathematics Special Issue

    133

  • 2. G. Pannell, D. J. Atkinson and B. Zahawi, "Minimum-Threshold

    Crowbar for a Fault-Ride-Through Grid-Code-Compliant DFIG Wind

    Turbine," in IEEE Transactions on Energy Conversion, vol. 25, no. 3, pp.

    750-759, Sept. 2010.

    3. Y. Tan, K. M. Muttaqi, L. Meegahapola and P. Ciufo, "Deadband Control

    of Doubly-Fed Induction Generator Around Synchronous Speed," in

    IEEE Transactions on Energy Conversion, vol. 31, no. 4, pp. 1610-1621,

    Dec. 2016.

    4. J. Y. Ruan, Z. X. Lu, Y. Qiao and Y. Min, "Analysis on Applicability

    Problems of the Aggregation-Based Representation of Wind Farms

    Considering DFIGs’ LVRT Behaviors," in IEEE Transactions on Power

    Systems, vol. 31, no. 6, pp. 4953-4965, Nov. 2016.

    5. Q. Huang, X. Zou, D. Zhu and Y. Kang, "Scaled Current Tracking

    Control for Doubly Fed Induction Generator to Ride-Through Serious

    Grid Faults," in IEEE Transactions on Power Electronics, vol. 31, no. 3,

    pp. 2150-2165, March 2016.

    6. R. Zhu, Z. Chen, Y. Tang, F. Deng and X. Wu, "Dual-Loop Control

    Strategy for DFIG-Based Wind Turbines Under Grid Voltage

    Disturbances," in IEEE Transactions on Power Electronics, vol. 31, no. 3,

    pp. 2239-2253, March 2016.

    7. Ananth, D. V. N., and GV Nagesh Kumar. "Performance Evaluation of

    DFIG During Asymmetrical Grid Disturbances Using Internal Model

    Controller and Resonant Controller." International Journal on Electrical

    Engineering and Informatics 8, no. 3, pp. 494-517, 2016.

    8. D.V.N. Ananth, G.V. Nagesh Kumar, Fault ride-through enhancement

    using an enhanced field oriented control technique for converters of grid

    connected DFIG and STATCOM for different types of faults, ISA

    Transactions, Volume 62, pp. 2-18, May 2016.

    9. D.V.N. Ananth, G.V. Nagesh Kumar, Mitigation of voltage dip and power

    system oscillations damping using dual STATCOM for grid connected

    DFIG, Ain Shams Engineering Journal, Available online 28 December

    2015.

    10. Md Emrad Hossain, Performance analysis of diode-bridge-type non-

    superconducting fault current limiter in improving transient stability of

    DFIG based variable speed wind generator, Electric Power Systems

    Research, Volume 143, February 2017, Pages 782-793.

    11. CH.AppalaNarayana, D.V.N.Ananth, K.D.Syam Prasad, CH. Saibabu,

    S.SaiKiran, T. PapiNaidu “Application of STATCOM for Transient

    StabilityImprovement and Performance Enhancement for aWind

    Turbine Based Induction Generator”, Volume-2, Issue-6, January 2013,

    pp. 158-163.

    International Journal of Pure and Applied Mathematics Special Issue

    134

  • 135

  • 136


Recommended