PF Coils Quench Protection Design of EAST Superconducting Tokamak
Oct. 5, 2005
PF power supply teamPF power supply teamInstitute of Plasma Physics,Chinese Academy of SciencesInstitute of Plasma Physics,Chinese Academy of Sciences
Hefei Anhui 230031Hefei Anhui 230031P.R.ChinaP.R.China
ASIPP
EAST
ASIPPPF Coil Distribution
The whole EAST PF
magnet system consists
of 14 coils, among them
PF1 to PF6 are the CS
coils, PF7 to PF10 are the
diverter coils, and PF11
to PF14 are the PF big
coils. They located
symmetrically around the
equatorial plane
ASIPP
PF Coil current in EAST operation
I (KA)
t (s)
ASIPPThe connection between PF coils
and PFPS
The PF system consists of 14 upper and lower SC coils around the plasma in the EAST tokamak, due to the series connection in diverter, 12 set of PFPS is essential.
ASIPP
Parameter for PF Magnet and Plasma Operation
Nominal cycle period 2800 s
PF magnetization 20 s
PF dwell time to keep magnetization 20 s
Plasma initiation 0.06 s
Plasma current ramp up 4 s
Maximum plasma flat top 1000 s
Plasma current ramp down 4 s
ASIPP
PF Coil Parameters and Requirements
Tab. 1 EAST PF magnet parameters
Rated current 15kA
Excited time 20s
Voltage (terminal to terminal) 10000V
Voltage (magnet to ground) 10000V
Limited heat condition 5.1108 A2s
Quench protection delay 1s
Self inductance 17.6~129.5mH
Mutual inductance 0.33~ 21.6mH
Storage energy in operation 42MJ (max. 140MJ)
ASIPP
The power supply circuit of EAST PF coil
ASIPP
The requirements of quench protection
★ to discharge the magnets in such a way that is less than a prescribed limit under all conditions;
★ to limit the maximum instantaneous voltages imposed on the magnet (terminal to terminal, and terminal to ground);
★ to ensure successful discharge with a prescribed reliability for a given number of events over the design lifetime.
ASIPP
QP Feature for PF Coil
★ Frequent switching off. the high current rate, and plasma disrup
tion in operation, The PF coil has possibly more quench,
★ strong coupling. The 12 pairs of coil have strong decoupling in each other, in QP the coil energy dissipation will be different from single coil.
★ Positive and negative current. in PF coil,it is important for QP design to use artificial current zero technology
★High power in input power supply. In PF magnet system, the primary power supply usually is quite high voltage, therefore it is necessary to suppress the input power supply in QP
ASIPP
PF Coil Storage Energy
ASIPP
PF Coil Storage Energy for Each energy
ASIPP
不同运行方式下各线圈最大储能 ( MJ )
托卡马克运行方式 \ 线圈号
1 , 2 3, 4 5, 6 7,8 9,10 11,12 13,14
大拉长运行 3.8 4.3 3.4 2.4 12.1 3.0 2.6
大截面运行 3.8 4.3 3.4 0.73 3.5 3.9 1.4
大体积运行 3.8 4.3 3.4 1.75 9.1 5.5 1.03
最大能量 3.8 4.3 3.4 2.4 12.1 5.5 2.6
ASIPP
QP System configuration
The QP consists of bypass, DCCB, PB, fuse, resistor
ASIPP
QP Operation Scenario
★ Bypass primary PS. Upon command, the quench protection system will suppress the power supply, close the bypass CU3.
★ Open DCCB. open the DCCB1, after 100ms, and open DCB2.
★ Open PB. If the current detected by sensor DCCT after 200ms is not zero, the pyrobreaker PB will open.
★ Fuse melt, and Energy is dissipated in R . The current flowing through the magnet then follows the circuit through CU3, R and L, and the majority of the energy is deposited in R.
ASIPP
DC Current Breaker
Rated voltage 1.5kV
Rated current 15kA
Max. breaking current 50kA
Max. breaking voltage 3.0kV
Closing time 110ms
Switching time 30ms
Operation numbers 104 times
Weight 210kg
ASIPP
Current and voltage curve for DCCB test
B– breaker current ; C– arc voltage
ASIPP
Backup Breaker--PB
Rated current 20kA
Max. breaking voltage 2.0kV
Max. voltage 10kV
Breaking time 100µs
weight 110kg
ASIPP
Discharge Resister and Fuse
0]][[][
][ iRdt
idL
][|][ 00 ii t
max00 ]][][[2
1EiLi T
......,12) 2, 1,(j 2 mj Adti
) 12 ........, 2, , 1(j mjj uRi
The QP in each power supply will work during the quench of any PF coil. Therefore the PF QP system consists of 12 R-L branches that have magnetic coupling, the total maximum energy Emax store
d in all coils should be dissipated in these resistor R of each QP. In R design it is necessary to consider whole energy transfer and max. energy storage in each PF coil and different operation time
ASIPP
Fuse
Pay attention:
★ at high current, melt rapidly
★ at low current, melt longer
★ shunt current from parallel switch
★ Suitable fuse parameter match with SC magnet heat condition.
★ two diodes in opposite parallel are in series with fuse
Current Melting time
400A Not melt
1000A 850s
2000A 80s
5000A 0.8s
15000A 0.01s
ASIPP
Coil Current in Quench protection
5s /elongation
ASIPP
Coil energy in Quench protection
5s /elongation
ASIPP
I2t in Quench protection
5s /elongation
Control Unit for QP
ASIPP
QP controllers consist of two parts: one is hardware controller realized by electronic circuit and relay; others is software controller realized by realtime operation system and industrial computers.
Up commands …
ASIPP
Parts of PF power supply equipment (7)
The end
Thanks