The new HV-CONNEX dry-type pluggable surge arres- ter for 72.5 kV voltage level offers various benefits compared to conventional surge arresters. Due to its insulation and field control made from solid sili- cone, no liquids or insulating gases relevant for the envi- ronment are present. This makes installation and opera- tion particularly easy because it does not require regulations for pressure vessels to be followed and gas monitoring is therefore not necessary. The solid insulation also allows for enormous space savings when installing the surge arrester which is easy to remove or replace. The new surge arrester is yet another component from the extensive HV-CONNEX series. Whether they are cable or overhead line connections, test fixtures or surge arres- ters: All transformer and GIS arrangements utilize the same universal dry-type pluggable sockets of the CON- NEX system. This allows for a high level of flexibility in design, commissioning and use of the transformers and GIS. Pluggable surge arresters with solid insulation Advantages Solid insulation and field control made from silicone No costly oil and gas work Contact-safe design of transformer and GIS Easy connection and pretestability of Transformer and GIS with utilization of the full CONNEX system
Transcript
Page 1: Pfiserer HV Connex Surge Arresters - Sizes 4 (72.5kV) & 5-S (145 kV)

The new HV-CONNEX dry-type pluggable surge arres-ter for 72.5 kV voltage level offers various benefits compared to conventional surge arresters.

Due to its insulation and field control made from solid sili-cone, no liquids or insulating gases relevant for the envi-ronment are present. This makes installation and opera-tion particularly easy because it does not require regulations for pressure vessels to be followed and gas monitoring is therefore not necessary. The solid insulation also allows for enormous space savings when installing the surge arrester which is easy to remove or replace.

The new surge arrester is yet another component from the extensive HV-CONNEX series. Whether they are cable or overhead line connections, test fixtures or surge arres-ters: All transformer and GIS arrangements utilize the same universal dry-type pluggable sockets of the CON-NEX system. This allows for a high level of flexibility in design, commissioning and use of the transformers and GIS.

Pluggable surge arresters with solid insulation

Advantages�� Solid insulation and field control made from silicone�� No costly oil and gas work�� Contact-safe design of transformer and GIS�� Easy connection and pretestability of Transformer and GIS with utilization of the full CONNEX system

Page 2: Pfiserer HV Connex Surge Arresters - Sizes 4 (72.5kV) & 5-S (145 kV)

© 2

012

PFI

STE

RE

R K

onta

ktsy

stem

e G

mbH

| w

ww

.pfis

tere

r.com

| W

e C

an A

ssum

e no

Lia

bilit

y fo

r Prin

ting

Err

ors/

Sub

ject

to T

echn

ical

Mod

ifica

tion.

www.pfisterer.com

The Data. The Details.

827 542 450 827 542 525 827 542 613 827 542 650 827 542 725

Rated voltage Ur (kV) 45.0 52.5 61.3 65.0 72.5

Max. continuous operating voltage Uc (kV) 63 42 49 52 58

Temporary overvoltage UTOV(1s)(kV) 45.2 56.2 65.6 69.6 77.6

Temporary overvoltage UTOV(10s)(kV) 46.4 51.1 63.1 67.0 74.7

Max. residual voltage Ures at 1/2 μs 10 kA (kV) 132 154 179 190 212

Max. residual voltage Ures at 8/20 μs 5 kA (kV) 112 131 152 162 180

Max. residual voltage Ures at 8/20 μs 10 kA (kV) 119.9 139.9 163.2 173.2 193.2

Max. residual voltage Ures at 8/20 μs 20 kA (kV) 136 159 185 196 219

Max. residual voltage Ures at 30/60 μs 125 A (kV) 88 103 120 127 142

Max. residual voltage Ures at 30/60 μs 500 A (kV) 94 109 127 135 151

Surge Arrester, Size 4 for GIS

827 541 450 827 541 525 827 541 613 827 541 650 827 541 725

Rated voltage Ur (kV) 45.0 52.5 61.3 65.0 72.5

Max. continuous operating voltage Uc (kV) 63 42 49 52 58

Temporary overvoltage UTOV(1s)(kV) 45.2 56.2 65.6 69,6 77.6

Temporary overvoltage UTOV(10s)(kV) 46.4 51.1 63.1 67.0 74.7

Max. residual voltage Ures at 1/2 μs 10 kA (kV) 132 154 179 190 212

Max. residual voltage Ures at 8/20 μs 5 kA (kV) 112 131 152 162 180

Max. residual voltage Ures at 8/20 μs 10 kA (kV) 119.9 139.9 163.2 173.2 193.2

Max. residual voltage Ures at 8/20 μs 20 kA (kV) 136 159 185 196 219

Max. residual voltage Ures at 30/60 μs 125 A (kV) 88 103 120 127 142

Max. residual voltage Ures at 30/60 μs 500 A (kV) 94 109 127 135 151

Surge Arrester, Size 4 for Transformer

Technical dataNominal discharge current 10 kA, 8/20 μs

Rated short circuit current 40 kA, 0.2s

High current impulse 100 kA, 4/10 μs

Long duration current impulse 420 A, 2000 μs

Rated frequency 50 - 60 Hz

Line discharge class 2

Energy absorption capacity 4.28 kJ/kVUr

Weight approx. 40 kg

Page 3: Pfiserer HV Connex Surge Arresters - Sizes 4 (72.5kV) & 5-S (145 kV)

The new HV-CONNEX dry-type pluggable surge arres-ter for 145 kV voltage level offers various benefits compared to conventional surge arresters.

Due to its insulation and field control made from solid sili-cone, no liquids or insulating gases relevant for the envi-ronment are present. This makes installation and opera-tion particularly easy because it does not require regulations for pressure vessels to be followed and gas monitoring is therefore not necessary. The solid insulation also allows for enormous space savings when installing the surge arrester which is easy to remove or replace.

The new surge arrester is yet another component from the extensive HV-CONNEX series. Whether they are cable or overhead line connections, test fixtures or surge arres-ters: All transformer and GIS arrangements utilize the same universal dry-type pluggable sockets of the CON-NEX system. This allows for a high level of flexibility in design, commissioning and use of the transformers and GIS.

Pluggable surge arresters with solid insulation

Advantages�� Solid insulation and field control made from silicone�� No costly oil and gas work�� Contact-safe design of transformer and GIS�� Easy connection and pretestability of Transformer and GIS with utilization of the full CONNEX system

Page 4: Pfiserer HV Connex Surge Arresters - Sizes 4 (72.5kV) & 5-S (145 kV)

© 2

013

PFI

STE

RE

R K

onta

ktsy

stem

e G

mbH

| w

ww

.pfis

tere

r.com

| W

e C

an A

ssum

e no

Lia

bilit

y fo

r Prin

ting

Err

ors/

Sub

ject

to T

echn

ical

Mod

ifica

tion.

www.pfisterer.com

The Data. The Details.

827 546 115 827 546 120 827 546 145

Rated voltage Ur (kV) 115 120 145

Max. continuous operating voltage Uc (kV) 92 96 116

Max. residual voltage Ures at 1/2 μs 20 kA (kV) 316 330 398

Max. residual voltage Ures at 8/20 μs 10 kA (kV) 270 282 340

Max. residual voltage Ures at 8/20 μs 20 kA (kV) 295 308 371

Max. residual voltage Ures at 8/20 μs 40 kA (kV) 324 339 408

Max. residual voltage Ures at 30/60 μs 500 A (kV) 228 239 287

Max. residual voltage Ures at 30/60 μs 1000 A (kV) 235 245 296

Surge Arrester, Size 5-S for GIS

827 545 115 827 545 120 827 545 145

Rated voltage Ur (kV) 115 120 145

Max. continuous operating voltage Uc (kV) 92 96 116

Max. residual voltage Ures at 1/2 μs 20 kA (kV) 316 330 398

Max. residual voltage Ures at 8/20 μs 10 kA (kV) 270 282 340

Max. residual voltage Ures at 8/20 μs 20 kA (kV) 295 308 371

Max. residual voltage Ures at 8/20 μs 40 kA (kV) 324 339 408

Max. residual voltage Ures at 30/60 μs 500 A (kV) 228 239 287

Max. residual voltage Ures at 30/60 μs 1000 A (kV) 235 245 296

Surge Arrester, Size 5-S for Transformer

Technical dataNominal discharge current 20 kA, 8/20 μs

Rated short circuit current 40 kA, 0.2s

High current impulse 100 kA, 4/10 μs

Long duration current impulse 900 A, 2800 μs

Rated frequency 50 - 60 Hz

Line discharge class 4

Weight approx. 115 kg