www.venetaisolatori.it [email protected]
PGSbushing air-SF
FEATURES t la
It is composed of two parts: A, red epoxy bushing cons tutes the core of the insulator with solid mechanical strength and suitable for SF6 use. B, silicone rubber cover gran ng great insula ng performances in highly polluted environments. Resin bushing “A” can be used alone thanks to its EN 50181 C connec on. It has to be connected with the silicon cover “B” or with cable termina on before pu ng into opera the electrical equipment Resin bushing is supplied with an EPDM O-ring gasket and plas c safety cap for C connec cone, while B part is supplied with a small bag of silicone grease and nuts/washers set made of nickel-plated copper for the outdoor cable connec on. It has to be to the tank through six OT58 brass fittings and, upon request, with an aluminium ange that improves stability. Opera ng temperature from -25°C to +100°C.
STANDARDSIEC 60137, IEC 60815, IEC 60507, IEC 61109 (annex C)
ROUTINE TESTS • Visual and dimensional check (A&B) • Glass trans on temperature (A) • Dry power frequency withstand (A)
• Pa al discharges (A) • Gas leakage test (helium) (A)
TESTS ON DEMAND
• Dry ligh ng impulse voltage (A orA&B)
• Temperature rise test (B)• cial pollu n test: 1000h salt
fog method (IEC 60507)• Ageing test under opera ng voltage,
simula ng weather condi ons –5000h mu ple stresses (IEC 61109)
Nam
e
A
B
Max
. O
pera
ting
volta
ge
Ligh
tnin
g im
puls
e vo
ltage
w
ithst
and
Pow
er
freq
uenc
y vo
ltage
w
ithst
and
Rat
ed c
urre
nt
Cre
epag
e di
stan
ce
PGS 24 1990 cable joint
24 kV 125 kV 55 kV
630 A
--- 1990 2000 >780
PGS 36
1990 cable joint 36 kV short type
170 kV 77 kV
--- 1990 3000
>10501996 cable joint 36 kV long type 1996 3000