+ All Categories
Home > Documents > Pipe Sizing

Pipe Sizing

Date post: 21-Dec-2015
Category:
Upload: maxmorek
View: 664 times
Download: 35 times
Share this document with a friend
Description:
Pipe Sizing
75
BALANCING CIRCUITS A heating system may be divided up into several sub-circuits. If the circuits resemble electrical circuits wired in parallel then the resistance of each sub-circuit should be similar to maintain the correct distribution of fluid. The diagram below illustrates a system of parallel circuits. The pump should be able to develop a pressure to overcome the resistance of the Index Circuit. The other circuits should then have ‘extra’ resistance added to ensure that all three sub-circuits have equal resistance. This ‘extra’ resistance is added at the Balancing Valves. A Balancing Valve is manufactured so that small changes in resistance can be made by altering the valve setting.
Transcript

BALANCING CIRCUITS

A heating system may be divided up into several sub-circuits.

If the circuits resemble electrical circuits wired in parallel then the resistance of each sub-circuit should be similar to maintain the correct distribution of fluid.

The diagram below illustrates a system of parallel circuits.

The pump should be able to develop a pressure to overcome the resistance of the Index Circuit.

The other circuits should then have ‘extra’ resistance added to ensure that all three sub-circuits have equal resistance.

This ‘extra’ resistance is added at the Balancing Valves.

A Balancing Valve is manufactured so that small changes in resistance can be made by altering the valve setting.

If the index circuit in the above diagram is sub-circuit No.3, then the Balancing Valves of the other two circuits will be closed down to give an equal resistance in all three circuits.

The photos below show typical balancing valves.

The table below is a blank

PIPE SIZING TABLE<FONT< P>

EXAMPLE 7Size the pipework for the heating system shown below.

Determine which circuit is the Index Circuit.

Also determine the pressure drops in the three sub-circuits.

The total lengths of the section are:

The table below shows each of the 3 sub-circuit pressure drops.

The Index Circuit is therefore the Circuit to the Hot Water Indirect Cylinder with a pressure drop of 9918 Pa.

The system should be balanced by slightly closing the valve on the heating return pipe at the boiler.

The Index Circuit pressure drop is 9918 Pa

The pump should be capable of delivering 0.411 kg/s against a pressure of 9918 Pascals (1.01 metres head).

A margin may be added to these figures.

EXAMPLE 6Size the pipework for the heating system shown below. Also determine the pressure drops. The total lengths of the section are:

Pipe Sizing Example 8HEATER BATTERY

Size the pipe and the pump for the system shown below.Use mild steel pipe at average water temperature 75oC.

Length of run F&R = 65 metres.

BoilerCast iron

Heater BatteryOutput 45 kW = 20

3-port diverting valve, pressure drop = 0.5 bar.

PIPE SIZING TABLE

SectionRef.

1Heat

Outputin

section

kW

2Pipe Heat loss.15% of 1.

kW

3Total HeatCol. 1+2

kW

4Water FlowRate

kg/s

5Pipe Size

mm dia.

6Length of pipe

m

7Total Equivalent length of Fittings

m

8Tota

l Pipe LengthCol. 6+7m

9Pressure drop per

metre

Pa/m

10TOTAL

PRESSURE DROP

Col. 8 x 9Pa

1 6.75 51.75 51.75 / 42= 1.23

40 65 Heater battery = 20.0Boiler = 2.5

122.4

220 26,928

12 bends x0.5 = 6.06 valves x 0.25 = 1.5

Add div valve

1 tee = 0.2

0.5 bar =50,000 Pa

= 30.2

TOTAL= 76,928 Pa

TEL = 30.2 x 1.9 (le)TEL = 57.38 metres

= 7.7 metres head

Add margin of 20% on flow rate and 10% on the head.Flow rate = 1.23 + 20% = 1.48 kg/s.Pump head = 7.7 metres + 10% = 8.5 metres

Pump to be capable of 1.48 kg/s (l/s) flow rate against a head of 8.5 metres or ( 85 kPa or 85 kN/m2.)

Look up Biral Catalogue: HX 501 pump is specified.

EXAMPLE 1Determine the smallest pipe which will carry 0.4 kg/s of water at 75oC using Copper, Table 'X'.

Consult the FLOW of WATER in PIPES TABLE (Copper pipe at 75oC).

The pipe diameters are written in bold type across the top of the table.

The pressure loss per unit length (Pa/m) and velocity (m/s) are written down the LHS of the table.

A red horizontal line is drawn across the table below 300 Pa/m.

This means that suitable pipe sizes will be found above this line.

The velocity follows a stepped line the lower blue line is the

1.0 m/s velocity line.

A 22 mm pipe will carry 0.4 kg/s but the pressure loss per unit length is below the red horizontal line and outside the table.

The pressure loss is in fact (790 Pa/m) and is too high since the maximum should be 300 Pa/m.

The velocity is also too high at about 1.3 m/s, the optimum being 1.0 m/s.

If this is the case then look at the next pipe size up, at 28 mm.

The flow rates closest to 0.4 are 0.394 and 0.414 kg/s.

0.4 kg/s is in between these two flow rates.

A 28 mm pipe will carry 0.4 kg/s with a pressure loss of about 230 Pa/m and a velocity of 0.7 m/s.

This meets the design criteria and therefore 28 mm would be a suitable pipe size.

EXAMPLE 2Determine a suitable pipe size for L.T.H.W. copper pipe for a flow rate of 1.0 kg/s.

Answer:

A 42 mm pipe gives a flow rate of 1.0 kg/s with a pressure loss of 160 Pa/m and velocity of about 0.9 m/s.

EXAMPLE 3Choose a pipe diameter for a heating system (L.T.H.W.) with a heat output of 32 kW.

Answer: First find the mass flow rate of water required.

A 35 mm pipe will give a flow rate of 0.76 kg/s with a pressure loss of 250 Pa/m and a velocity of 0.95 m/s.

EXAMPLE 4Size the flow and return pipework to a 1.6 kW radiator.

A 15 mm pipe will give a flow rate of 0.038 kg/s with a pressure loss of 80 Pa/m and a velocity of about 0.25 m/s.

PIPE FITTING LOSSESPipework fittings such as bends, tees, reducers etc., cause pressure loss or resistance in a heating system. When making approximate calculations 10%, 15%, 20% or more may be added to the pressure loss in straight pipe runs.

For accurate calculations the fitting loss should be determined separately for each fitting.

The concept of equivalent length is used and is defined as the length of straight pipe which would give a friction pressure loss equivalent to one velocity head.

The D’Arcy equation is;

H = 4 . f . l . v2 / 2 . g . d

Where; H = head loss due to friction in a straight pipe (m)f = friction coefficientl = length of pipe (m)d = diameter (m)v = velocity of fluid (m/s)g = acceleration due to gravity (m/s2)

The D’Arcy equation can be rewritten for pressure instead of head.

Pressure drop (pl) = ( 4 . f . l ) / d x ( v2 . . g ) / 2 . g

Where; pl = Pressure loss in a pipe section (Pa)f = friction coefficient for pipe l = length of pipe (m)d = diameter of pipe (m)v = water velocity (m/s) = density of water (kg/m3)g = acceleration due to gravity (m/s2)

To simplify the above equation we get;

Pressure drop (pl) = ( 4 . f . l ) / d x ( v2 . ) / 2

or; Pressure drop (pl) = ( 4 . f . l ) / d x ( ½ . . v2 )

For the friction pressure loss to equal one velocity head;

Velocity pressure = ( � . . v2 )

Then 1.0 = ( 4 . f . l ) / d

The length (l) is now called equivalent length (le) and by rearranging the above formula we get;

1.0 x d = 4 . f . le

le = d / 4 .f

Values of equivalent length are given in the FLOW of WATER in PIPES TABLE for water at 75oC, see CIBSE guide C (2001) section 4 , Flow of Fluids in Pipes and Ducts, Tables 4.9 to 4.33 for various types of pipes.

These values should be corrected for each particular type of fitting.

The correction factors of Velocity pressure loss factors are called (Zeta) factors.

The resistance in a fitting is converted to equivalent straight lengths of pipe, e.g. a bend may have a resistance equivalent to 1.2 metres of straight pipe.

The TOTAL EQUIVALENT LENGTH OF A FITTING = Equivalent Length x Pressure Loss factor (Zeta).

TOTAL EQUIVALENT LENGTH OF A FITTING (m) = (le) x (Zeta factor).

See CIBSE guide C (2001) section 4.9 for more details of fittings zeta factors.

EXAMPLES OF zeta FACTORS

The following are some examples of pressure loss ( zeta) factors for pipe fittings:

Index CircuitThe Index Circuit is the circuit with the highest resistance.

This only applies to systems where the circuits are divided.

The Index Circuit needs to be identified so that the pump can be sized.

Example 1

The system shown below is divided into two sub-circuits A & B.

A pipe sizing calculation would determine which of the two sub-circuits had the most resistance and therefore which was the Index Circuit.

The reason for finding the Index Circuit is to size the pump.

The pressure developed by the pump should be capable of overcoming the resistance in the Index Circuit.

If the pump pressure can overcome the resistance in the Index Circuit, then it can overcome the resistance in other circuits of lesser resistance.

If it was found that the Index Circuit was Circuit (B) in the above diagram then we would include the flow of water through radiators No. 3, 4 and 5.

Pump

Sub-Circuit BSub-Circuit A

BOILER

No.1

No.2

No.3 No.4

No.5

Heat Emitters

If we examine Circuit (B) then the Index Circuit flows past Radiator No.3 and No.4 and through Radiator No.5. This would be the circuit with the highest resistance.

If the pump is capable of forcing water through the pipework to Radiator No.5 then there will be enough pressure to force the water through Rads. No.3 & No.4 since they are closer to the pump.

This is the reason why only one radiator is included in the calculations for resistance in the Index Circuit.

Pump

Sub-Circuit B is Index Circuit

Sub-Circuit A

BOILER

No.1

No.2

No.3 No.4

No.5

Heat Emitters

Radiator No.5 Included in Index Circuit

Example 2

A heating system is shown below.There are seven radiators and seven pipe sections.The pipe sections under the radiators are from tee to tee.

The Index circuit is the one with the highest resistance.This is normally the longest run to the radiator that is at the greatest distance from the pump.The first six radiators are not included in the Index circuit.The index circuit below includes all seven sections but only includes; the boiler and fittings around the boiler in section 1, tees in sections No.1 to No.6 and the last radiator and radiator valves in the section 7.

BOILERSection 1

Section 2 Section 3 Section 4 Section 5 Section 6 Section 7Radiator Radiator Radiator Radiator Radiator Radiator Radiator

Section 1BOILER

Section 2 Section 3 Section 4 Section 5 Section 6 Section 7

Radiator Nos.1 to 6 are not included in the Index Run

Radiator Radiator Radiator Radiator Radiator Radiator Radiator

Only Radiator No.7, the last rad., together with the rad. valves is included in the Index Run.

Index Circuit;Sections 1, 2, 3, 4, 5, 6 and 7.

Pipe Sizing for Heating Systems

All pipe sizing in building services is based on the D'Arcy equation, where:

H = 4 . f . l . v2 / 2 . g . d

where H = head loss due to friction in a straight pipe (m)f = friction coefficientl = length of pipe (m)d = diameter (m)v = velocity of fluid (m/s)g = acceleration due to gravity (m/s2)

The object of pipe sizing is to obtain the smallest diameter of pipe without too high a water velocity or too high a pressure drop and therefore large pumps.

It is more convenient to use pipe sizing tables when sizing pipes rather than the D'Arcy equation.

This is because the water velocity and head loss (or pressure loss) are unknown at the time of pipe sizing, and the friction coefficient (f) varies with Reynolds number which in turn varies with velocity and diameter.

A FLOW of WATER in PIPES TABLE is provided in these notes.

The CIBSE guide provide pipe sizing tables in sections C4.11 to C4.45.

L.T.H.W. (Low Temperature Hot Water) PIPE SIZING

When sizing pipes for heating systems the water velocity should not exceed 1.0 m/s. (Except for large diameters - see CIBSE guide tables B1.17 & B1.18).

This reduces noise and wear.

The pressure drop should not exceed 300 Pascals per metre run of pipework to keep pumps down to a reasonable size.

This means that for every metre of pipework the resistance to water flow should be no more than 300 Pa which is about 30 mm head.

FLOW of WATER in PIPES TABLE

The table below shows pipe sizes for 15mm to 76mm diameter copper pipe.

To find a suitable pipe size for a heating circuit the flow rate is used to find an appropriate diameter.

If the flow rate of water is known then look down under any pipe diameter column to ascertain the corresponding pressure drop and velocity.

If the pressure drop and velocity exceed the criteria in the previous section then try the next pipe size up.

If the pressure drop and velocity are within the criteria then the pipe is sized correctly

PIPE SIZING TABLE

The pipe sizing table shown below is an aid to sizing more complicated circuits.

A description is given in the Table below.

EXAMPLE 5Size the pipework for section (B) of a heating system shown below.

Section B is in red.

Also determine the pressure drop in section (B)

The total length of the section is 8 metres (includes flow and return)

Section B supplies hot water to Radiator No. 2 and No. 3.

The amount of heat to be transferred to radiators No. 2 & 3 is:

1.5 + 1.0 = 2.5 kW.

The downstream tees will be included in this section.

Sizing Example 9WARM AIR HEATERS

Size the pipes to Circuit A and Circuit B and the pump for the system shown below.Use mild steel pipe at average water temperature 75oC.Length of run Section 1 = 26 metres (F & R)Length of run Section 2 = 43 metres (F & R)Length of run Section 3 = 50 metres (F & R)

Pressure drop 3 –port valves = x g H = 1000 x 9.81 x 2 m = 19,620 Pa

3-port diverting valve,

BoilerCast

Industrial warm air heater.Output 70 kWHeater battery

3-port diverting valve,

Industrial warm air heater.Output 62 kWHeater battery

Section 2 Section 3

Section 1

PIPE SIZING TABLE

SectionRef.

1Heat

Outputin

section

kW

2Pipe Heat loss.

15% of 1.

kW

3Total Heat

Col. 1+2

kW

4Water FlowRate

kg/s

5Pipe Size

mm dia.

6Length of pipe

m

7Total

Equivalent length of Fittings

m

8Total Pipe

LengthCol. 6+7

m

9Pressure drop per

metre

Pa/m

10TOTAL

PRESSURE DROP

Col. 8 x 9Pa

1 132 19.8 151.8 3.61 65 26 le = 3.5 26 + 20.13

140 140 x 46.13

3Gate valves @ 0.15 = 0.451 NRV = 2.0

= 46.13 = 6,458

1 Boiler = 2.52 Elbows @ 0.4 = 0.8

5.75

3.5 x 5.75 = 20.13 m

2 70 10.5 80.5 1.92 50 43 le = 2.5 43 + 12.75

160 160 x 55.75

3 Gate valves @ 0.2 = 0.64 Elbows @ 0.5 = 2.0

= 55.75 = 8,920

2 Tees @ 0.5 + 0.5 + red.Reduction 502 / 652

=

+ 19,620 +8,100

Ratio = 0.59 = 0.252Tees @ 1.25 = 2.50

= 36,640

5.12.5 x 5.1

= 12.75 m 3 62 9.3 71.3 1.70 50 50 le = 2.5 50 +

17.75 =130 130 x 67.75

3 Gate valves @ 0.2 = 0.68 Elbows @ 0.5 = 4.0

67.75 = 8808

2 Tees @ 0.5 + 0.5 + red.Reduction 502 / 652

=

+ 19,620 +7,200

Ratio = 0.59 = 0.252Tees @ 1.25 = 2.50

= 35,628

7.12.5 x 7.1

= 17.75 m

Index circuit is therefore to Section 1 & 2 since this has the highest resistance.

Resistance of Index Circuit = 6,458 + 36,640 = 43,088 Pa.

Pump to be capable of (Minimum) 3.61 kg/s (l/s) flow rate against a head of 4.31 metres or ( 43.1 kPa or 43.1 kN/m2.)

Pipe Sizing Example 10Size the pipes and the pump in the system shown below.The heating system is for Factory Radiant Panel Heaters and the design

inside temperature is 15oCUse welded mild steel pipe and fittings at average water temperature 75oC.

Section Length (F&R) (Metres)

1 252 303 184 155 406 187 15

BoilerCast Iron

Each 3-port diverting valve, pressure drop = 3.6 metres head

Section 2

Section 5

Section 1

Section 3

Section 4

Section 6

Section 7

4No. Radiant Panels – 4 horizontal tubes each.To be sized from catalogue.Required output each 40 kW.Hydraulic resistance from

N.R.V.D.R.V.D.R.V.

Pressure Drops from Equipment

3-Port Diverting Valve

Pressure drop 3 –port valves = x g x H = 1000 x 9.81 x 3.6 m = 35,316 Pa

Radiant Panels

Powermatic Radiant Panels, type Aquamatic ARP (see http://www.powrmatic.co.uk/)

Total emissions from catalogue , 75 MWT, 15oC ambient, 4 tubes horizontal - 734 W per m run. (from Table 5)Pipe length of each panel is; 40,000 Watts output / 734 W/m = 56

metres.

Mass flow rate for each panel is 40 kW / 42 = 0.95 kg/s.For each tube mass flow rate is 0.95/4 = 0.25 kg/s + 15% heat loss =

0.28 kg/sFrom hydraulic resistance graph (on website), resistance for each panel = 38 Pa/m runTotal resistance for each panel 38 x 56 m = 2128

Pa.

Pipe Sizing Table

SectionRef.

1Heat

Outputin

section(kW)

2Pipe Heat loss.15% of 1.(kW)

3Total HeatCol. 1+2

(kW)

4Water FlowRate(kg/s)

5Pipe Size(mm dia.)

6Length of pipe

(m)

7Total Equivalent length of

Fittings

(m)

8Total Pipe

LengthCol. 6+7

(m)

9Pressure drop per

metre(Pa/m)

10TOTAL

PRESSURE DROPCol. 8 x 9

(Pa)

40 6 46 1.1 40 18 18 + 3.15= 21.15

1806,3 2elbow weld @ 0.4 = 0.81 st. thro’ tee = 0.23 gate valve @ 0.25 = 0.75

Total = 1.75T.E.L. = Total x le

= 1.75 x 1.8 = 3.15m

21.15 x 180= 3807 + panel 2128+ 3 port valve = 35,316= 41,251

40 6 46 1.1 40 15 15 + 4.59=19.59

1807 4elbow weld @ 0.4 = 1.61 st. thro’ tee = 0.23 gate valve @ 0.25 = 0.75

Total = 2.55T.E.L. = Total x le

= 2.55 x 1.8 = 4.59m

19.59x 180= 3526 + panel 2128+ 3 port valve = 35,316= 40,970

40 6 46 1.1 40 15 15 + 3.15= 18.15

1804 2elbow weld @ 0.4 = 0.81 st. thro’ tee = 0.23 gate valve @ 0.25 = 0.75

Total = 1.75T.E.L. = Total x le

= 1.75 x 1.8 = 3.15m

18.15 x 180= 3267+ panel 2128+ 3 port valve = 35,316= 40,711

Pipe Sizing Table

SectionRef.

1Heat

Outputin

section(kW)

2Pipe Heat loss.15% of 1.(kW)

3Total Heat Col 1+2(kW)

4Water FlowRate(kg/s)

5Pipe Size(mm dia.)

6Length of pipe

(m)

7Total Equivalent length of Fittings

(m)

8Total Pipe

LengthCol. 6+7

(m)

9Pressure drop per

metre(Pa/m)

10TOTAL

PRESSURE DROP

Col. 8 x 9(Pa)

2 80 12 92 2.19 65 30 le = 3.31 DRV 60ooblique = 2.0 2 Tees @ 0.5 + 0.3 + red.Reduction 652 / 802 = Ratio = 0.59 = 0.252 Tees @ 1.25 = 2.502 Tees @ 0.5 + 0.3 + red.Reduction 402 / 652 = Ratio = 0.38 = 0.402 Tees @ 1.20 = 2.40

Total = 6.90T.E.L.= 6.90x 3.3 = 22.77m

30+ 22.77= 52.77

55 55 x 52.77= 2,902

5 80 12 92 2.19 65 40 le = 3.31 DRV 60ooblique = 2.0 4 elbows@ 0.3 = 1.20 2 Tees @ 0.5 + 0.3 + red.Reduction 652 / 802 = Ratio = 0.59 = 0.252 Tees @ 1.25 = 2.502 Tees @ 0.5 + 0.3 + red.Reduction 402 / 652 = Ratio = 0.38 = 0.402 Tees @ 1.20 = 2.40

Total = 8.10T.E.L.= 8.1 x 3.3 = 26.73m

40 + 26.73= 66.73

55 55 x 66.73 = 3,670

Pipe Sizing Table

Ref.

1Heat

Outputin

section(kW)

2Pipe Heat loss.15% of 1.(kW)

3Total HeatCol. 1+2

(kW)

4Water FlowRate(kg/s)

5Pipe Size(mm dia.)

6Length of pipe

(m)

7Total

Equivalent length of Fittings

(m)

8Total Pipe

LengthCol. 6+7(m)

9Pressure

drop per

metre(Pa/m)

10TOTAL

PRESSURE DROP

Col. 8 x 9(Pa)

1 160 24 184 4.38 80 25 le = 4.23 Gate valves @ 0.10 = 0.301 NRV = 2.01 Boiler = 2.52 Elbows @ 0.3 = 0.6

Total = 5.4T.E.L. = 4.2 x 5.4 = 22.68 m

25 + 22.68= 47.68

92.5 = 4,410

Index Circuit

SectionsPressure Drop (Pa) Total P.D. (Pa)

1,2,3 4410 + 2902 + 41,251 48,5631,2,4 4410 + 2902 + 40,711 48,0231,5,6 4410 + 3670 + 41,251 49,3311,5,7 4410 + 3670 + 40,970 49,050

The circuit containing sections No. 1,5 & 6 have the highest resistance and are therefore the index run with a 49,331 Pa pressure drop.

The pump should be capable of a minimum 4.38 kg/s (l/s) flow rate against a minimum head of 4.93 metres or ( 49.3 kPa or 49.3 kN/m2.) Allowance to pump size may be made for margin or inefficiencies.

Regulating Valves

A commissioning engineer would balance the system using double regulating valves (D.R.V.’s) or metering stations. This process is briefly outlined in BSE Notes Pipe Sizing section, page 9 entitled Balancing Circuits.

The drawing of the system for this example shows two D.R.V.’s; one in section 2 and one in section 5. Before these can be adjusted the sub-circuits No.3 and No.4 must be balanced as well

as sub-circuits No.6 and No.7. When these sub-circuits are balanced then the D.R.V.’s can be regulated.

The amount of extra resistance needed in the D.R.V. in section 2 is;

Resistance in section 5 = 3670 PaResistance in section 2 = 2902 PaDifference between these resistances = 3670 - 2902 = 768 Pa.Therefore the D.R.V. in section 2 is to be turned down to give a resistance to flow of 768 Pa.This means that the circuits are balanced.

Diverting Valves By-Pass Pipe

The by-pass pipe for the 3-port Diverting valves should also be regulated with a D.R.V so that when the valve is fully closed to the panel and fully open to the by-pass port, the resistance of the by-pass section of pipework is equal to that of the radiant panel. This means that the D.R.V in the by-pass pipework should be turned down to give a resistance of 2128 Pa. from the panel (see Radiant panel section) plus the resistance of two gate valves.

See pipe sizing table – pipe section 3.2 No. 40mm gate valve @ = 0.4 therefore total = 0.8. Equivalent length is 0.8 x le 1.8 = 1.44 metres.1.44 x 180 Pa/m pressure drop = 259 Pa pressure drop for 2 gate valves.

The total resistance applied by the D.R.V. is therefore 2128 Pa + 259 Pa = 2387 Pa

Diverting Valve Schematic Detail at Radiant Panel

3-port diverting valve (may be installed on return depending on manufacturer).

Flow

Return

By-passD.R.V.

Standard manometer tappings to measure pressure difference across an orifice

Radiant Panel

Isolating Gate Valves

Panel pipework resistance = 2128 Pa (from catalogue)

Boiler SizingThe boiler output is based on the total heat losses for the building plus hot water boiler power.Other additional items that can be considered are; heater battery outputs and other equipment that require heat.

For details of Boiler Power for Hot Water cylinder see Hot and Cold water section – Hot water generation & storage page 2.

Boiler output (kW) = heat loss (kW) + boiler power for cylinder (kW)

Boiler margin.

It is useful to add a margin to the previous figure for;

1. In case of future extension.2. Quick heat up when the system is cold.3. In case of mistakes in heat loss calculations.4. Loss of efficiency later in boiler life.

We could add between 15% and 33% as a boiler margin.A large margin means the boiler is less efficient since it is firing for less time.The more time a boiler sits idle with a full capacity of hot water, the more heat is lost up the flue and to a lesser extent from the casing.A suitable margin for most projects is 20% margin.

Total Boiler output (kW) = heat loss (kW) + boiler power for cylinder (kW) + 20% margin.

Note:In most cases a margin has already been added to the heat loss to size heat emitters. It should be remembered that if this margin is 10% and a further 20% margin is added for boiler sizing then the net resultant margin is 32%.In continuously operated heating systems such as hospitals, a smaller margin is acceptable since the system is not heated from cold each morning.

Multiple Boiler Installations

In the past if two boilers were to be installed, each one was sized at 2/3rds of the total capacity. This overall margin of 33% is on the high side so a lower margin is more acceptable.A multiple boiler installation is a more efficient method of providing heating since the more boilers that are installed the more they will operate at full load when switched on.

]

Recommendations

CIBSE guide F (2002) section 10.1.2.2 and BSRIA Guidance Note 12/97 Oversized Heating Plant gives details of plant sizing.

As a guide to boiler capacity (heating load) the following yard sticks can be used; 90 W/m2 for offices and industrial buildings, 110 W/m2 for retail, health care and education establishments.

Also for Hot Water calorifier sizing the following yard sticks can be used; 4 l/person for offices, retail, education and restaurant establishments, 23 l/person for hotels, 33 l/person for health care.

Other considerations for oversizing are;

1. Oversizing boilers is a greater capital cost.2. Seasonal efficiency will be less is boilers are oversized.3. Oversizing of control valves means that they don’t control the flow of water

effectively.4. Oversizing pumps means that they consume more electricity than is necessary.5. Also oversizing pumps means that it is more difficult to control the water flow.6. Pumps that are too large will not be operating at the most efficient part of the

characteristic curve.7. Pipe heat losses are increased.8. Oversizing heat emitters mean that the system is more difficult to control with

temperature sensors since the room temperature will drift easily beyond the set point.9. The heat gains from; lights, people and machinery will offset the heat loss in a

building. This is not usually considered when calculating boiler outputs but helps to reduce the amount of heat required in winter time.

Plant Size Ratio

CIBSE guide B1 (2002) section 4.7 gives details of Plant Size Ratio (PSR).

This is defined as; PSR = installed heat emission / design heat loss

Factors for PSR of between 1.2 and 2.0 are common.

A building with low thermal inertia heats up more quickly than one with high thermal inertia and therefore a lower plant size ratio may be used.

The optimum plant size ratio is a compromise between the following factors;

1. occupancy pattern.2. pre-heat time.3. thermal response of the building.4. greater capital cost and maintenance cost.5. stability of controls..6. seasonal efficiency.

Pump SizingThere are two items required to size a pump;

Fluid flow rate Pressure to be developed.

The pressure that should be developed by the pump shouldequal the Pressure Drop in the system.This is usually found from pipe sizing tables or from other methods. See Science section of these notes - Fluids section; Head Loss due to friction in a pipe.

The flow rate of fluid is also found from pipe sizing tables or given in other data.

Add 20% margin to pump pressure to allow for future extensions and the system getting less efficient. The designer must be careful when adding a margin to pump pressure since too much pressure can lead to ‘pumping over’ in open systems and other problems.Some pump catalogues have units of head instead of pressure.

For conversion;

Pressure (Pa) = density of water x acceleration due to gravity x head (m)Or P = x g x H

Where, P = Pump pressure (Pa) Density of waterapprox.1000 kg/m3.g = Acceleration due to gravity 9.81 m/s2.H = Head (m)

Therefore; H = P / x g

H = P / 1000 x 9.81

H = P / 9810

The flow rate of water that the pump delivers will be the flow rate in the section in which the pump is installed.A 20% margin may be added to this flow rate to allow for future extensions to the system.

A pump catalogue may be consulted to choose a suitable unit.

The operating point can be super-imposed on the pump graph for pressure (head) against flow rate in kg/s or l/s. It is best to choose a pump with the operating point near the lower speeds or the bottom end of the performance curve so that the pump will not be operating at its maximum capacity, thus allowing little room for error or margin.

A typical pump sizing curve is shown below with a system operating point superimposed on the curve.

Not all system operating points are directly on top of a pump graph or curve as shown below.It would be best to choose a pump on the curve above the operating point, i.e. Pump B since the output of both pressure and flow rate will be slightly above that required and not below.

Flow rate (l/s) or (kg/s)

Pressure (Pa) (kPa) or Head (m)

Operating point

Typical Pump Sizing Curve

Pump graph or curve

Systemflowrate

SystemPressure or

head

Similarly if a pump has three speeds then three curves will be shown.It would be best to operate a pump at a lower speed if possible to prolong the life of the pump and bearings. The diagram below shows a 3-speed pump with the operating point between speed No.1 and No.2. The pump would then be installed to run at speed No.2; this means that if the system is extended at a later date the pump speed may be increased to accommodate this increase in flow rate and pressure.

Flow rate (l/s) or (kg/s)

Pressure (Pa) (kPa) or Head (m)

Operating point

3 Pump graphs or curves

Systemflowrate

SystemPressure or

head

Pump A

Pump B

Pump C

Flow rate (l/s) or (kg/s)

Pressure (Pa) (kPa) or Head (m)

Operating point

Typical Pump Sizing Curve - 3 Speed Pump

Pump with 3 speeds

Systemflowrate

SystemPressure or

head

Speed 3

Speed 2

Speed 1

Example 1

Size a suitable in-line glanded pump to deliver 10 litres/second of water against a head of 7 metres (70 kPa).Use the information from the Smedegard pump curves shown below.The pump should have a duty and standby facility, that is; a twin pump abbreviated (D).

Manufacturer’s InformationThe pumps shown are 1400 and 900 rpm.Each pump is given a 3 number reference; the first number is the pipe size in inches, the second number is the impellor diameter, the third number is the number of motor pole pairs.

Answer

The operating point can be super-imposed on the pump curves below for head (kPa) against flow rate in l/s.

At first look at the pump curves the; 8-200-4(D) pump is close to the operating point.It is sometimes best to choose a pump with the operating point on the flat part of the pump curve, this gives some anti-stall facility and means that if the volume flow rate fluctuates then the pressure developed will not change.So, a 10-210-4(D) pump may be better suited to a load where the volume flow rate is not steady.This might happen in a circuit where control valves alter water flow rates.Also the 10-210-4(D) pump has more margin for pressure and flow rate above the duty given in the question.A commissioning engineer would have to regulate the flow of water through the pump with a regulating valve to achieve the design flow rate.

To choose a pump the engineer has to be aware of the type of system to which it is connected and choose accordingly.

Consult; http://www.smedegaard.dk/media(93,1033)/Omega_UK_explanation_datasheets.pdf for further information on pump sizing from Smedegard.

Some manufacturer’s curves give more details.Pump efficiency and pump power can also be shown so that it is possible to choose a pump operating at the highest efficiency part of the curve.Another way to reduce flow rate is to change the impellor to a smaller size.

Heating Pump SizingThe heating pump must overcome the resistance to water flow in the pipework system.This resistance will be a combination of straight pipe losses and fittings losses.

To calculate the fittings losses + the pipe losses:

1. Look up the Zeta factor for the fitting in table C4.36.2. Multiply all the Zeta factors in the section by the Equivalent Length for the pipe (l e) found in Table C4.14.3. Add the EQUIVALENT LENGTH of fittings for the section to the actual length of the section in metres.

This gives the TOTAL EQUIVALENT LENGTH in metres.4. Multiply the TOTAL EQUIVALENT LENGTH by the pressure drop in the section (N/m2 per m run).

The pressure drop in the section is found from Table C4.14.This gives the PRESSURE DROP in the section (N/m2 ) or (Pa).

The pressure that should be developed by the pump should equal the Pressure Drop inthe Index Circuit.The Index Circuit is the part of the system with the highest pressure drop.Therefore:

Pump pressure = pressure drop in Index Circuit.

Add 20% margin to pump pressure to allow for future extensions and the system getting less efficient. The designer must be careful when adding a margin to pump pressure since too much pressure can lead to ‘pumping over’ in open systems and other problems.

Some pump catalogues have units of head instead of pressure.

For conversion;

Pressure (Pa) = density of water x acceleration due to gravity x head (m)Or P = x g x H

Where, Density of water ( = 1000 kg/m3.Acceleration due to gravity (g) = 9.81 m/s2.

Therefore; H = P / x g

H = P / 1000 x 9.81

H = P / 9810

The flow rate of water that the pump delivers will be the flow rate in the section in which the pump is installed.A 20% margin may be added to this flow rate to allow for future extensions to the system.

A pump catalogue may be consulted to choose a suitable unit.Smaller pumps can be in-line, that is installed in the pipeline.Larger pumps may be seated on a concrete base, these tend to be end suction pumps where the water is sucked into the pump end and comes out at 90 degrees at the outlet.

The operating point can be super-imposed on the pump graph for pressure (head) against flow rate in kg/s or l/s. It is best to choose a pump with the operating point near the lower speeds or the bottom end of the performance curve so that the pump will not be operating at its maximum capacity, thus allowing little room for error or margin.

Gas Properties

The Table below lists some of the more useful properties in building services for natural gas and liquid petroleum gas (LPG).

Properties Natural Gas Liquid Petroleum Gas (LPG)

Propane

Composition & Chemical symbol 92.6% Methane CH43.6% Ethane C2H60.8% Propane C3H80.2% Butane C4H10

100% C3H8

Gross Calorific Value (GCV)(MJ/m3)(kJ/litre)

41.6 95as gas

Gross Calorific Value (GCV)(MJ/litre)

0.0416 25.5 as liquid

Gross Calorific Value (GCV) (MJ/kg) 53.3 50Net Calorific Value (NCV)(MJ/m3)

38.7 86

Density of gas at 15oC(kg/m3)

0.78 1.85

Density of liquid under pressure(kg/litre) or (kg/m3)

- 0.512 kg/litre or512 kg/m3

Ignition temperature (oC) 650 510Operating pressure (millibars) 20 37Volume of gas per volume of liquid (m3/m3) or (m3/litre)

- 274 m3gas /m3 liquid or0.274 m3 gas / litre liquid

Volume of gas per kg mass of liquid (m3/kg)

- 0.54

LPG (Gas) Pipe Sizing Notes

Allowable pressure drops

Medium pressure lines- 450 Pa per m run ( 2 P.S.I. per 100 foot )Low pressure lines - 4.1 Pa per m run ( �” w.g. /100 ft)

- Maximum 1300 Pa total pressure drop in any run.Gas Pressures

First stage regulation at tank pressure is reduced from 6 bar to 0.7 bar.Second stage regulation at building pressure is reduced to 50 mbar (0.05 bar) At equipment and appliances - 37 millibar (0.037 bar)

Natural Gas Pipe Sizing

Allowable pressure drops

The allowable pressure drop between the outlet of the meter and appliances must not exceed 1 mbar or 0.001 bar or 100 Pa.Pressure loss is generally limited to between 75 Pa and 125 Pa from the meter to the point of use.

Gas Pressures

At equipment and appliances - 20 millibar (0.020 bar)

Gas Pipe Sizing - Introduction - Page 1 2 3 4

SIMPLE METHOD OF NATURAL GAS PIPE SIZING

A simple method of sizing Natural Gas pipes is to use the tables below.The three tables are for Steel, thin wall copper and thick wall copper.An allowance may be made for fittings. This allowance is to add to the measured pipe lengths, 0.3 metres for 90o bends and 0.6 metres for an elbow or tee.

Procedure

1. Measure the length of pipe in each section.2. Add equivalent lengths for fittings.3. Determine heat output of appliance or heat to be carried in pipe in MW4. Divide this by Gross Calorific Value (GCV) of gas i.e. 38.7 MJ/m3 to give gas flow rate in m3/s.5. Determine pipe size from relevant Table.

Example 1

Determine the steel pipe size for a gas boiler if the boiler rating is 28 kW and the measured pipe run is 10.2 metres with 3 elbows.

Procedure

1. Measure the length of pipe in each section – answer 10.2 m 2. Add equivalent lengths for fittings – answer 3 x 0.6 = 1.8 m. Add to 10.2 m gives 12.0 metres.3. Determine heat output of appliance or heat to be carried in pipe in MW. – answer 28 / 1000 = 0.028 MW4. Divide this by Gross Calorific Value (GCV) of gas i.e. 38.7 MJ/m3 to give gas flow rate in m3/s – answer 0.025 / 38.7 =

0.0007235 m3/s5. Determine pipe size from relevant Table – answer from Table 1 gives 20mm pipe because the flow rate lies between two

values on the table and the larger pipe size is chosen.

Table 1 below is used for Mild Steel pipe, BS 1387: medium grade.

Table 1 – Gas Pipe Sizing for Steel PipePipe length (m)

3.0 6.0 9.0 12.0 15.0 18.0 21.0 24.0Nominal Pipe size

(mm) Gas Flow Rate (m3/s)

15 0.00104 0.00072 0.00057 0.00050 0.00044 0.00039 0.00036 0.00034

20 0.00219 0.00149 0.00120 0.00102 0.00090 0.00083 0.00076 0.00071

25 0.00409 0.00275 0.00224 0.00193 0.00169 0.00153 0.00142 0.00134

32 0.00826 0.00574 0.00464 0.00393 0.00346 0.00315 0.00291 0.00275

40 0.01258 0.00865 0.00700 0.00598 0.00527 0.00480 0.00440 0.00417

Table 2 below is used for Copper Tube Table ‘X’ or EN 1057 thin wall, half hard temper.

Table 2 – Gas Pipe Sizing for Copper Tube Table ‘X’Pipe length (m)

3.0 6.0 9.0 12.0 15.0 20.0 25.0 30.0Nominal Pipe size

(mm) Gas Flow Rate (m3/s)

15 0.00079 0.00054 0.00043 0.00035 0.00032 0.00027 0.00025 0.00024

22 0.00244 0.00165 0.00126 0.00102 0.00110 0.00079 0.00070 0.00063

28 0.00495 0.00330 0.00260 0.00220 0.00197 0.00165 0.00142 0.00134

Table 3 below is used for Copper Tube Table ‘Y’ or EN 1057 thick wall, half hard temper.

Table 1 – Gas Pipe Sizing for Copper Tube Table ‘Y’Pipe length (m)

3.0 6.0 9.0 12.0 15.0 20.0 25.0 30.0Nominal Pipe size

(mm) Gas Flow Rate (m3/s)

15 0.00071 0.00047 0.00037 0.00032 0.00028 0.00027 0.00024 0.00020

22 0.00220 0.00149 0.00118 0.00094 0.00087 0.00072 0.00064 0.00057

28 0.00456 0.00307 0.00244 0.00205 0.00181 0.00149 0.00134 0.00118

It must be remembered that the above method of pipe sizing is not as accurate as using the CIBSE guide method as detailed in page 3, but can be useful for checking pipe sizes quickly.

Gas Pipe Sizing - Simple Sizing Method- Page 1 2 3 4

CIBSE method of Gas Pipe Sizing

Use CIBSE guide Table C4.45 (steel) and C4.46 (copper) for natural and LPG pipe sizing.If LPG is used then refer to correction factors on page C4.76 of the CIBSE guide.Most domestic natural gas appliances operate at a pressure of 20 millibar (0.020 bar)Domestic LPG appliances operate at a gas pressure of 37 mbar (0.037 bar).For natural gas it is usual to limit the pressure loss to 75 Pa to 125 Pa from the gas meter to the point of use. A maximum pressure drop from meter to appliance of 1millibar (100 Pa) can be used.

Natural Gas Pipe Sizing Example

Size the gas supply pipe shown below. Copper pipework is used.Appliance pressure is 20 mbar.Use the maximum pressure drop given above of 100 Pa from meter to appliance.

Section Length(metres)

1 82 43 134 55 4

25 kW boiler

Cooker with hob.(12 kW)

4 kW gas fire

Section 1 Section 2 Section 3

Section 4 Section 5Gas Meter

Example 1 – Gas Pipe System

To calculate the gas flow rates use the following formula:

Q = H / GCV

Where;Q = Gas flow rate in pipe section (m3/s)H = Heat output in pipe section (convert to MW)GCV = Gross Calorific Value of gas (MJ/m3) given in Pipe Sizing Table.

For example, in Pipe section 1 the Heat output to all appliances is 25 + 12 + 4 kW = 41 kW.Flow rate Q = H / GCV

Q = 41 x 10-3 (MW) / 38.7 (MJ/m3) from Pipe Sizing Table.Q = 1.05943 x 10-3 m3/sQ = 0.00105943 m3/sQ = approximately 0.00106 m3/s

GAS GROSS CALORIFIC VALUEMJ/m3

Natural gas 38.7

L.P.G. ( Commercial propane) 96

Gas Pipe Sizing Table

SectionRef.

1Heat

Outputin

section

kW

2Flow ratem3/s

3Pipe Size

mm dia

4Length of pipe

m

5Total Equivalent length of Fittings

m

6Total Pipe

LengthCol. 4+5m

7Pressure

drop per

metre

Pa/m

8TOTAL

PRESSURE DROP

Col. 6 x 7Pa

9Pressure at start of sectionPa

10Pressure at end

of sectionPa

1 41 0.00106 28 8

Zeta factor for Tee = 0.5 + 1.0 + 0.25 = 1.75T.E.L. = x le

= 1.75 x 0.7

= 1. 23 m

8 + 1.23= 9.23

2.2 20.31

2 16 0.000413 15 4

Tee 0.5 + 1.0 = 1.5T.E.L. = x le

= 1.5 x 0.4= 0.6 m

4 + 0.6= 4.6

8.3 38.18

3 4 0.000103 15 13

3 bends @ 1.0 = 3.01 plug valve = 1.0

Total = 4.0T.E.L = 4.0 x 0.2

= 0.8 m

13 + 0.8= 13.8

1.3 17.94

4 25 0.00065 22 5

2 bends @ 1.0 = 2.01 plug valve = 1.0T.E.L. = x leT.E.L = 3.0 x 0.5

= 1.5 m

5 + 1.5= 6.5

3.0 19.5

5 12 0.00031 15 4

1 plug valve = 1.0T.E.L. = x leT.E.L = 1.0 x 0.4

= 0.4 m

4 + 0.4= 4.4

4.0 17.6

Gas pipe sizes and pressure drops can now be put on the drawing.

25 kW boiler

Cooker with hob.(12 kW)

4 kW gas fire

Section 1(28mm)20.31 Pa p.d.

Section 2 (15mm)38.18 Pa p.d.

Section 3(15mm)17.94 Pa p.d.

Section 4(22mm)19.50 Pa p.d.

Section 5(15mm)17.60 Pa p.d.

Gas Meter

Example 1 – Gas Pipe System with Sizing Information

The pressure drops as shown in the following Table:

Sections Pressure drop(Pa)

Pressure drop (Pa)

1,4 20.31 + 19.50 39.81

1,2,5 20.31 + 38.18 + 17.60 76.09

1,2,3 20.31 + 38.18 + 17.94 76.43

The maximum pressure drop is in sections 1, 2 and 3 and amounts to 76.43 Pa.This is less than the recommended maximum of 100 Pa; therefore the pipe sizes are appropriate.If the pressure drop in sections 1, 2 and 3 and was too high then the pipe size in section 2 could have been increased to 22mm, and a second calculation of pressure drop carried out.

Gas Pipe Sizing - Table - Page 1 2 3 4

GAS GROSS CALORIFIC VALUE(MJ/m3)

Natural gas 41.6

L.P.G. ( Commercial propane) 96

Gas Pipe Sizing Table

SectionRef.

1Heat

Outputin

sectionkW

2Flow ratem3/s

3Pipe Sizemm dia

4Length of pipe

m

5Total

Equivalent length of Fittings

m

6Total Pipe

LengthCol. 4+5m

7Pressure

drop per

metrePa/m

8TOTAL

PRESSURE DROP

Col. 6 x 7Pa

9Pressure at start

of section

Pa

10Pressure

at endof

sectionPa

Gas Pipe Sizing - Table - Page 1 2 3 4

Non-pressurised Cold Water Pipe Sizing

The method is similar to L.T.H.W. pipe sizing except that the pressure available is not from a pump but from the head available from the tank. The higher the tank is above the outlets the more head will be available to force the water through the outlets and overcome pipework resistances.

Head Available

The Head Available develops water pressure and this water pressure is used up in overcoming the frictional resistance of the pipe and in creating the velocity pressure for water flow at the outlet.

p1 - p2 = frictional resistance + velocity pressure or,

h1 - h2 = head loss in pipe due to friction + velocity head

where p = pressure (N/m2)h = head (m)

Cold Water Storage Tank

Outlet

Head Available

Water flow in pipe

Water level in tank

In practice, to avoid additional velocity pressure calculations, it is usual to calculate the available pressure by considering the difference in levels between the bottom of the storage tank and the height of the draw-off points.

The pressure losses in the system are frictional pipe losses and velocity pressure loss through sanitary fittings such as taps, cistern ball valves and shower heads.

Velocity head loss through fittings is as follows :-Pillar tap 1mShower head 1.5mBall valve 1m

Water Flow Rates

Cold water flow rates for sanitary appliances for small installations may be found from the table below.

Approximate hot or cold water demand Flow rate (l/s)

Basin (spray tap) 0.05Basin (tap) 0.15Bath (private) 0.30Bath (public) 0.60Flushing cistern 0.10Shower (nozzle) 0.15Shower (100mm rose) 0.40Sink (15mm tap) 0.20Sink (20mm tap) 0.30Wash fountain 0.40

In larger more complex buildings where many sanitary appliances are installed simultaneous demand should be considered from tables CIBSE Guide B (1986) B4.20 and B4.21

Pipe Size Procedure

1. Divide system into sections.

2. Calculate demand units if simultaneous demand is effective.

3. Estimate flow rates in each section.

4. Estimate pipe diameter.

5. Measure the pipe run for the section.

6. Calculate length of pipe equal to resistance of fittings.

7. Calculate effective pipe length.

8. Determine pressure loss due to friction for pipe from CIBSE guide tables.

9. Calculate pressure consumed by friction.

10. Calculate cumulative pressure consumed.

11. Calculate pressure available at the end of the section.Subtract pressure loss in section from static pressure available.

12. If pressure loss due to friction is less than pressure available,

Notes:-1. Keep velocity below 2.0 m/s for noise reduction see Table 2.19 in CIBSE Guide G (2004) Public Health Engineering.2. An alternative method of pipe sizing is to use a nomogram.

This can be found in CIBSE Guide G (2004) Public Health Engineering Figure 2.21.

Example 1

Determine a suitable pipe size for the system shown below.DATAFittings include the following; exit from tank or large vessel, 3No. bends, 1No. gate valve, 1No. 15mm tap, Length of pipe run is 8 metres and copper pipe is to be used.The flow rate for a 15mm Sink Tap from above Table is 0.2 l/s.

The pressure available to force the water through the pipework and tap comes from the head of water above the tap.The formula below gives the relationship between pressure and head.

P = x g x hWhere;P = pressure (N/m2) = density (1000 kg/m3 for water)g = acceleration due to gravity (9.81 m/s2)h = head (m)

Therefore: P = 1000 x 9.81 x 2.0 = 19,620 N/m2

The resistance to flow is from the fittings and pipework.

Cold Water Storage Tank

15mm Sink Tap

2 metres head

Example 2

Determine suitable pipe sizes for the system shown below.The building is a three-storey Nursing Home.DATACopper pipe is to be used.Flow rates are to be obtained from above Table.

Cold Water Storage Tank

3 m

Bath (Private)

3 m

Bath (Private)

Bath (Private)

3 m

5 m

3 m

3 m

3 m

3 m

3 m

4 m

B

A

C

D

E

Answer:

From above Table the flow rate for a private bath is 0.3 l/s.The pipe sizes, flow rates and pressures are indicated on the drawing below.

HOT AND COLD WATER PIPE SIZING TABLE

1 2 3 4 5 6 7 8 9 10 11 12

Ref Demand

Units if require

d

Flow

Rate

(l/s)

Estimated

Pipe Dia.

(mm)

MeasuredPipe Run

(m)

Length ofPipe Equal to Resistance’s

(m)

EffectivePipe

LengthCol . 5 + 6

(m)

Pipe Pressure Loss (Pa/m)

PressureConsumedCol. 7 x 8

(Pa)

TotalPressureConsume

d(Pa)

PressureAvailable at End of

Section(Pa)

Final PipeSize

(mm)

A 0.9 28 8.0 Factors for fittings:1No.Exit large vessel = 0.41No.Gate Valve = 0.31 No. Bend = 1.01 No.28 x 28 x 22 tee = 0.2

-----------Total 1.9

T.E.L. = Total x le = 1.9 x 1.1= 2.09 m

8 + 2.09 = 10.09 m

1250 12,613 12,613 Static pressure = 3m x 9810 = 29,430

Press. Available = 29,430 – 12,613 = 16,817 Pa

28

B 0.6 28 3.0 1No.28 x 22 x 22 tee = 0.20with 28 x 22 reducer:A2 / A1 = x 0.0112 / x 0.0142.

= 0.617 gives = 0.25-----------

Total 0.45T.E.L. = Total x le

= 0.45 x 1.0= 0.45m

3.0 + 0.45 = 3.45 m

600 2,070 12,613 + 2,070 = 14,683

Static pressure = 6m x 9810 = 58,860Press. Available = 58,860 – 14,683 = 44,177 Pa

28

1 2 3 4 5 6 7 8 9 10 11 12

C 0.3 22 7.0 1No.Bend = 1.01No. Angle valve bath tap = 5.0

-----------Total 6.0

T.E.L. = Total x le = 6.0 x 0.7= 4.2 m

7.0 + 4.2= 11.2 m

625 7,000 14,683 + 7,000 = 21,683

Static pressure = 9 m x 9810 = 88,290Press. Available = 88,290 – 21,683 = 66,607 Pa

22

D 0.3 22 3.0 1No. Angle valve bath tap = 5.0T.E.L. = Total x le

= 5.0 x 0.7= 3.5 m

3.0 + 3.5 = 6.5 m

625 4,063 12,613 + 4,063 = 16,676

Static pressure =

3m x 9810 = 29,430Press. Available = 29,430 – 16,676 = 12,754 Pa

22

E 0.3 22 3.0 1No. Angle valve bath tap = 5.0T.E.L. = Total x le

= 5.0 x 0.7= 3.5 m

3.0 + 3.5 = 6.5 m

625 4,063 4,063 Static pressure = 6m x 9810 = 58,860Press. Available = 58,860 – 14,683 = 44,177 Pa – 4,063 = 40,114 Pa

22

Re-calculate pipe ref. C for 15mm pipe

C 0.3 15 7.0 1No. 28 x 15 x 22 tee (already included)with 2 No.28 x 15 reducers:A2 / A1 = x 0.00752 / x 0.0142.

= 0.287 gives = 0.47 2No. Reducers = 0.94 1No.Bend = 1.01No. Angle valve bath tap = 5.0

-----------Total 6.94

T.E.L. = Total x le = 6.94 x 0.5= 3.47 m

7.0 + 3.47= 10.47 m

4000estimat

ed

41,880 41,880 +14,683 = 56,563

Static pressure = 9 m x 9810 = 88,290Press. Available = 88,290 – 56,563 = 31,727 Pa

15

Cold Water Storage Tank

Bath

Bath

Bath

B

A

C

D

E

28mm0.9 l/s

28mm0.6 l/s

15mm0.3 l/s

22mm0.3 l/s

22mm0.3 l/s

16,817 Pa

44,177 Pa

12,754 Pa

40,114 Pa

31,727 Pa

Example 3

Determine suitable pipe sizes for the system shown below.The building is a three-storey hotel.DATACopper pipe is to be used.Flow rates and simultaneous demand data are to be obtained from the CIBSE guide.

Cold Water Storage Tank

5 m

WCWHBBath

7 m2 m 7 m 2 m

1 m

WC WHB Bath

WHBBath

1 m

WC WHB Bath

WHBBathWC WHB Bath

3 m

3 m

3 m

7 m

Hot and Cold Water Pipe Sizing Table

1 2 3 4 5 6 7 8 9 10 11 12

Ref Demand

Units if require

d

FlowRate

(l/s)

Estimated

Pipe Dia.

(mm)

Measured

Pipe Run

(m)

Length ofPipe

Equal to

Resistance’s

(m)

Effective

Pipe Length

Col . 5 + 6

(m)

Pipe Pressu

re Loss

(Pa/m)

Pressure

Consumed

Col. 7 x 8

(Pa)

TotalPressu

reConsumed(Pa)

PressureAvailable at End of Section

(Pa)

Final PipeSize

(mm)

Mains Water Pipe Sizing

Pipe Sizing Procedure1. Reference the pipe section.

2. Calculate flow rates from Table below.

3. Estimate flow rates in each section. Keep velocity below 2 m/s. See also CIBSE Guide G

(2003) part 2, Table 2.19.

4. Estimate pipe diameter from pipe sizing tables in CIBSE Guide C.

5. Measure the pipe run from drawings.

6. Calculate length of pipe equal to resistance of fittings. The Total equivalent length of a fitting = Equivalent

Length x Pressure Loss factor (Zeta).

7. Calculate effective pipe length.

8. Determine pressure loss due to friction from CIBSE Tables.

9. Calculate pressure consumed due to friction (Pa) =effective pipe length (m) x pressure loss due to friction (Pa/m)

10. Calculate total pressure consumed = Friction loss + Static pressure loss

11. Determine pressure at start of section.

12. Calculate pressure available at end of section =Pressure at start of section - Total pressure consumed

If pressure available at end of section is less than the maximum allowable pressure drop then we can accept this pipe size.

13. Determine pressure required at end of section, this can be the minimum pressure that is required for terminal equipment.

14. If the pressure available at the end of the section is more than or equal to the pressure required at the end of the section then the pipe size is correct.

Water Flow Rates

Cold water flow rates for sanitary appliances for small installations may be found from the table below.

Approximate hot or cold water demand Flow rate (l/s)

Basin (spray tap) 0.05Basin (tap) 0.15Bath (private) 0.30Bath (public) 0.60Flushing cistern 0.10Shower (nozzle) 0.15Shower (100mm rose) 0.40Sink (15mm tap) 0.20Sink (20mm tap) 0.30Wash fountain 0.40

In larger more complex buildings where many sanitary appliances are installed simultaneous demand should be considered from tables CIBSE Guide B (1986) B4.20 and B4.21.

Notes:-An alternative method of pipe sizing is to use a nomogram.This can be found in CIBSE Guide G (2004) Public Health EngineeringFigure 2.21.

Pipe Sizing table

Pressurised Cold Water Pipe Sizing Table

1 2 3 4 5 6 7 8 9 10 11 12 13 14

Ref DemandUnits if

required

FlowRate

(l/s)

EstimatedPipe Dia.

(mm)

MeasuredPipe Run

(m)

Length ofPipe Equal to Fittings

Resistance’s(m)

EffectivePipe

LengthCol . 5 +

6(m)

Pipe Pressure

Loss (Pa/m)

From CIBSE Tables

PressureConsumed

due to Friction

Col. 7 x 8(Pa)

Friction loss + Static

pressure loss = Total

PressureConsumed

(Pa)

Pressure at Start

of Section

(Pa)

PressureAvailable at End of Section

(Pa)

Pressure Required at End of Section

(Pa)

Final PipeSize

(mm)

Example 1

Calculate an appropriate pipe size for the system shown above.Use Copper Table X pipework for water at 10oC..

Answer

The maximum allowable pressure drop along the length of pipe = 300,000 Pa – 250,000 Pa = 50,000 Pa

Pressurised Cold Water Pipe Sizing Table

1 2 3 4 5 6 7 8 9 10 11 12 13 14

Ref DemandUnits if

required

FlowRate

(l/s)

EstimatedPipe Dia.

(mm)

MeasuredPipe Run

(m)

Length ofPipe

Equal to

Fittings

Resistance’

s(m)

EffectivePipe

LengthCol . 5 +

6(m)

Pipe Pressure

Loss (Pa/m)

From CIBSE Tables

PressureConsumed

due to Friction

Col. 7 x 8(Pa)

Friction loss

+ Static pressure loss

= Total

Pressure

Consumed(Pa)

Pressure at Start

of Section

(Pa)

Pressure

Available at End of

Section

(Pa)

Pressur

e Required at End of

Section

(Pa)

Final PipeSize

(mm)

A none 0.8 22 50 none 50 3500 175,000 175,000

300,000 125,000

250,000

Too smal

l

A none 0.8 28 50 none 50 1000 50,000 50,000

300,000 250,000

250,000

28

Pressurised Cold Water Pipe Sizing Table

1 2 3 4 5 6 7 8 9 10 11 12 13 14

Pipe Sizing Procedure

1. Reference the pipe section - section A.

2. Calculate demand units or loading units from Tables in CIBSE guide (attached). – not required, see No.3 below.

3. Estimate flow rates in each section. Keep velocity below 2 m/s. -given

4. Estimate pipe diameter from pipe sizing tables in CIBSE Guide C. – 22mm (velocity too high at approx 2.4 m/s) or 28mm (velocity is 1.5 m/s).

5. Measure the pipe run from drawings. – 50m

6. Calculate length of pipe equal to resistance of fittings. – no fittings

7. Calculate effective pipe length. - 50m

8. Determine pressure loss due to friction from CIBSE Tables. See Table 4.18 in Guide C (CD version).

9. Calculate pressure consumed due to friction (Pa) = effective pipe length (m) x pressure loss due to friction (Pa/m). Column 7 x 8 in Pipe Sizing Table.

10. Calculate total pressure consumed = Friction loss + Static pressure loss. There are no vertical pipe sections and therefore no static pressure loss.

11. Determine pressure at start of section. Given in drawing as 300,000 Pa.

12. Calculate pressure available at end of section = Pressure at start of section - Total pressure consumed.

300,000 – 175,000 = 125,000 Pa. (22mm) …………..300,000 –50,000 = 250,000 Pa (22mm).

If pressure available at end of section is less than the maximum allowable pressure drop then we can accept this pipe size.

13. Determine pressure required at end of section, this can be the minimum pressure that is required for terminal equipment. Given in drawing as 250,000 Pa.

14. If the pressure available at the end of the section is more than or equal to the pressure required at the end of the section then the pipe size is correct.

28mm pipe is correct, 22mm is too small since there is not enough pressure available at the end of the section and the water velocity is also too high.

Example 2

Calculate an appropriate pipe size for the system shown above.Use Copper Table X pipework for water at 10oC..

Answer

The maximum allowable pressure drop along the length of pipe = 120,000 Pa – 90,000 Pa = 30,000 Pa

Pressurised Cold Water Pipe Sizing Table

1 2 3 4 5 6 7 8 9 10 11 12 13 14

Ref DemandUnits if

required

FlowRate

(l/s)

EstimatedPipe Dia.

(mm)

MeasuredPipe Run

(m)

Length ofPipe Equal to Fittings

Resistance’s(m)

EffectivePipe

LengthCol . 5 +

6(m)

Pipe Pressure

Loss (Pa/m)

From CIBSE Tables

PressureConsumed

due to Friction

Col. 7 x 8(Pa)

Friction loss + Static

pressure loss = Total

PressureConsumed

(Pa)

Pressure at Start

of Section

(Pa)

PressureAvailable at End of Section

(Pa)

Pressure Required at End of Section

(Pa)

Final PipeSize

(mm)

A none 0.5 22 14 1.6 15.6 1500 23,400 23,400 120,000 96,600 90,000 22

Pipe Sizing Procedure

1. Reference the pipe section - section A.

2. Calculate demand units or loading units from Tables in CIBSE guide (attached). – not required

3. Estimate flow rates in each section. Keep velocity below 2 m/s. -given

4. Estimate pipe diameter from pipe sizing tables in CIBSE Guide C. – 22mm (velocity is 1.5 m/s).

5. Measure the pipe run from drawings. – 14m

6. Calculate length of pipe equal to resistance of fittings. – 2 bends.

The Total equivalent length of a fitting = Equivalent Length x Pressure Loss factor (Zeta).See Pipe Sizing Heating Section - page 4 - pipe fitting losses.Copper pipe elbow (Zeta) = 1.0 x 2 bends = 2.0Determine equivalent length from CIBSE table C4.18, le = 0.8Total equivalent length of fittings = 0.8 x 2.0 = 1.6 metres.

7. Calculate effective pipe length. - 15.6m

8. Determine pressure loss due to friction from CIBSE Tables. See Table 4.18 in Guide C (CD version).

9. Calculate pressure consumed due to friction (Pa) = effective pipe length (m) x pressure loss due to friction (Pa/m). Column 7 x 8 in Pipe Sizing Table.

10. Calculate total pressure consumed = Friction loss + Static pressure loss. There are no vertical pipe sections and therefore no static pressure loss.

11. Determine pressure at start of section. Given in drawing as 120,000 Pa.

12. Calculate pressure available at end of section = Pressure at start of section - Total pressure consumed. 120,000 – 23,400 = 96,600 Pa.

If pressure available at end of section is less than the maximum allowable pressure drop then we can accept this pipe size.

13. Determine pressure required at end of section, this can be the minimum pressure that is required for terminal equipment. Given in drawing as 90,000Pa.

14. If the pressure available at the end of the section is more than or equal to the pressure required at the end of the section then the pipe size is correct.

22mm pipe is correct.


Recommended