The DANLERS range of passive infra-red occupancy switches is designed for the automatic control of lighting, heating, ventilation or air conditioning loads.
The PIR switch will switch on the connected load automatically when an area is occupied, and then switch it off automatically when the area has been vacant for a chosen duration. This has the benefits of reduced energy bills and automatic control. When being used to control lighting, the built-in photocell can be used to keep the lights off on bright days.
DANLERS also offer a Ceiling surface mounted passive infra-red absence switch which requires a wall switch to turn on the load - see page 38 for details.
• Offices • Staff rooms
• Factories • Corridors and stairwells
• Warehouses • Residential homes
• Schools • Military accommodation
• Leisure centres • Student accommodation
• Hospitals • Toilet blocks
• Canteens • Changing rooms
• Car Parks • Plus many other uses
PIR occupancy switches are ideal for:
Additional range products
Special variants of products are available on request with additional range lenses for installations requiring a greater detection area or longer thinner detection areas. In some cases this may require a greater range of movement to register detection.
PIR occupancy switches
PIR OCCUPANCY SWITCHES
PIR occupancy switch variants
Special variants of products are available on request such as 24V (a.c. or d.c.) versions of our PIR occupancy switches and photocell switches, ideal for low voltage control systems. 12V variants can also be supplied. Some variants are available from stock for next day delivery. To special order we can also supply volt free outputs for mains, 24V or 12V supplies (including versions with gold relays).
MADE IN
T H E U K
5 Y E A R
WA R R A NTY
9
PIR occupancy switch functions
Each PIR occupancy switch in the DANLERS range has a passive infra-red quad person detector (except COPD which has a passive infra-red dual person detector). This detects the movement of a warm body moving within its detection zone. When such a movement is detected the load is switched on. There is a time lag function which is adjusted using a spindle on the side of the product. The time lag is the time that must elapse with no movement detected before the PIR occupancy switch will switch off.
There is a built-in, adjustable, photocell override which can be used to keep lights off when there is sufficient daylight available (except “Intelligent” range of controls - see page 24). The photocell can only be used in this way if the amount of natural daylight exceeds the level of the artificial ligh§ts. The photocell can be set to inactive when controlling heating, ventilation or air conditioning. The photocell is also adjusted by a spindle on the side of the product.
Each PIR occupancy switch contains a relay suitable for switching most types of load, including fluorescent lights, LEDs and fans.
A few PIR occupancy switches may be wired in parallel to control the same load. However, there are minimum load restrictions with the WAPIR model only (see page 29). The PIR occupancy switches require a mains supply.
Simple adjustment spindles
Night, Unoccupied – Lighting OFF
Night, Occupied – Lighting ON
Enough daylight, Unoccupied – Lighting OFF
Enough daylight, Occupied – Lighting OFF
PIR occupancy switch brings lights on – only when needed
Function demonstrated with the lighting in an office
PIR OCCUPANCY SWITCHES
ControlZAPP
DANLERS ControlZAPP enabled PIR Occupancy Switches have functions similar to those of the traditional DANLERS range of PIR Occupancy Switches with many new features added to the easy to set up, programmable, bluetooth low energy interface.
For the more details on ControlZAPP see pages 6-7 or for the latest ControlZAPP product information telephone: +44 (0)1249 443377 or email: [email protected]
10
PIR detector
Passive infra-red quad person detector.
Adjustable time lag
Time lag adjustable in 9 steps (approximate values): 10 seconds, 20 seconds, 40 seconds, 1.25 minutes, 2.5 minutes, 5 minutes, 10 minutes, 20 minutes, 40 minutes.
Adjustable photocell
The "Inhibit on" photocell on most models will inhibit the lights from switching on when somebody enters an area with plenty of ambient light. However, if somebody is already occupying an area with the lights switched on, the lights will remain on while the area is occupied, regardless of any increase in the ambient light level. This is to avoid any nuisance switching off when somebody is in the middle of a task or meeting. Range 100-1000 lux (and photocell inactive), falling on the working plane.
The “Intelligent” photocell on some batten mount controls (see page 24) enables even greater energy savings because in its calibration process it learns to ignore the artificial lighting load (Patent pending, GB Patent application 1219746.3). It is recommended the “Intelligent” batten mount controls are only used in areas with some natural daylight. Range 100-3000 lux falling on the working plane.
Loading
All models can switch up to 6 amps (1500W at 230VAC) of resistive, transformer or fluorescent lighting loads, 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps. For the WAPIR model there are some minimum load requirements (details on page 29).
Wiring in parallel
A few PIR switches can be wired in parallel to control the same load.
Start-up Mode
When the mains supply is initially connected to the PIR occupancy switch it goes through its Start-up Mode. This means it switches on for about 1 minute, then switches off and enters its Operating Mode. If a manual wall switch is feeding the PIR occupancy switch (see wiring diagrams on appropriate product pages) then it will go through the Start-up Mode each time the wall switch is switched on (not applicable to WAPIR, see page 29).
By wiring the manual wall switch in the alternative position, the supply to the PIR occupancy switch is uninterrupted and it remains in Operating Mode. It does not go through its Start-up Mode each time the wall switch is switched on.
PIR OCCUPANCY SWITCHES
PIR occupancy switch specifications
11
PIR OCCUPANCY SWITCHES
Selecting the appropriate PIR occupancy switch
CEILING MOUNTED WALL MOUNTED
360˚ detection zone
120˚ directional
detection angle
Long range directional
narrow beam
120˚ detection
angle
Flush-mounted (false or plasterboard
ceilings)
Surface mounted Batten mounted
Surface mounted Surface mounted Plaster depth (16mm) wall box
Hard wired
Plug and socket
Hard wired
Plug and socket
Hard wired to lamp ballast
Plug and socket
Plug and socket
Needs neutral
wire
No neutral wire
needed
CEFL PIR Page 14
CEFL PIR SEALED Page 15
CEFL PIR 10A
Page 15
CEFLP PIR + CESO
Page 14
CESF PIR Page 16
CESF PIR IP66
Page 17
CESFA PIR
(Absence switch)
Page 38
CELO + CESO SQ Page 20
BMINTPIR SP, 5M or 10M
Page 24
BMPIR SP, 5M or 10M
Page 25
BMEXPIR Page 26
CEDR 6P + CESO
Page 22
CEDR 6PLR + CESO Page 23
WACE PIR Page 28
WAPIR Page 29
5m 10m0
Scale
12
The diagram illustrates PIR occupancy switch siting within a typical office/factory facility. The coloured zones emanating from the controls show strong detection zones (darker tints with solid coloured line) and secondary detection zones (lighter tint with broken coloured line).
Ceiling flush-mounted CEFL PIR spaced every 5 metres to cover the open plan office and control the lights. The CEFL PIR can be wired in groups in parallel, to control the lighting in zones.
Long range directional CEDR 6PLR to detect people in the 25 metre corridor.
Two ceiling flush-mounted CEFL PIR controlling the lights in a meeting room. In this, and other offices, a manual wall switch is retained to override the lights to off, e.g. for a video presentation.
Small offices are covered by a single ceiling flush-mounted CEFL PIR or alternatively with an absence switch CESFA PIR.
The wall switch has been replaced by a wall mounted WAPIR.
MEETING ROOM OFFICE
OFFICE
OFFICE
CORRIDOR
OPEN PLAN OFFICES
RECEPTION
STAIRWELL
TOILETS
FACTORY AREA
HIGH BAY RACKING
RESTROOM
OP
EN
S
TAIR
CA
SE
HIGH BAY RACKING
SHOWER ROOM
TOILET LOBBY
PIR OCCUPANCY SWITCHES
Application diagram
13
Long range directional CEDR 6PLR detects people in a racking storage aisle.
Batten mounted BMINTPIR5M fitted to every other batten lamp fitting to give total coverage of the open plan factory area.
Ceiling flush-mounted CEFL PIR spaced every 5 metres to cover the open plan reception area and control the lights.
Ceiling plug-in CELO mounted on BESA box on ceiling conduit. Spaced at 5 metre intervals to control the lights in the restroom.
In the shower room a CEFL PIR SEALED is used, as it has protection against light splashes and condensation.
In the toilets a ceiling flush- mounted CEFL PIR has been wired in parallel with a wall mounted WACE PIR in the lobby, to control the lighting in both rooms together.
Two ceiling surface- mounted CESF PIR (one on each landing) wired in parallel to control the lighting in the stairwell.
Ceiling directional CEDR 6P covers the open staircase.
MEETING ROOM OFFICE
OFFICE
OFFICE
CORRIDOR
OPEN PLAN OFFICES
RECEPTION
STAIRWELL
TOILETS
FACTORY AREA
HIGH BAY RACKING
RESTROOM
OP
EN
S
TAIR
CA
SE
HIGH BAY RACKING
SHOWER ROOM
TOILET LOBBY
PIR OCCUPANCY SWITCHES
14
Special versions
Plug and socket version: CEFLP PIR
Model CEFLP PIR is provided with a plug suitable for the CESO Ceiling socket shown on page 21. CEFLP PIR is also suitable for use with HAGER marshalling boxes.
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Ceiling flush-mounted PIR occupancy switch
Control plugged into a CESO on
a BESA box
These neat and unobtrusive models are ideal for flush mounting through suspended or plasterboard ceilings. They have a 2m cable, for quick and easy installation.
Order code: CEFLP PIR
Order code: CEFL PIR
Specification
Detection zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 14a and 14b below
Dimensions: 72mm diameter x 68mm
NN
Fig. 201 Ceiling mounted PIR occupancy switch
Up to 5m
Up to 7m
Up to 5m
Up to 7m
Up to 5m
Up to5m
In open plan areas For best coverage the CEFL PIR should be spaced every 5m in either direction
CEFL PIR Strong detection zone
Secondary detection zone
Strong detection zone i.e. person moving arm
Secondary detection zone i.e. person walking (less sensitive when walking straight towards PIR switch)
For optimum coverage recommended mounting height between 2.4 and 5m.
PIR Quad detector gives 124 detection areas within the zone.
Plan view of detection zone Several PIR occupancy switchesPerspective view of detection zone
L
load
optional manual wall switch for overriding off
A few CEFL PIR230 VAC
L
load
CEFL PIR
optional manual wall switch for overriding off
14a. Single CEFL PIR
230 VAC
alternative position for optional wall switch (see p.10 “Start-up Mode”)
14b. A few CEFL PIR wired in parallel
alternative position for optional wall switch (see p.10 “Start-up Mode”)
Ideal for false or plasterboard
ceilings
55
3
2m cable
60
72
72
side plan
66
Requires 63 or 64mm (2.5") diameter hole in a false or plasterboard ceiling
38
PIR occupancy switch variants
Variants are available on request such as 24V or 12V (a.c. or d.c.), ideal for low voltage control systems. To special order we can also supply volt free outputs for mains, 24V or 12V supplies (including versions with gold contact relays). Please see page 19 for more information.
SL
SL SL SL
PIR OCCUPANCY SWITCHES
Detection diagrams
Dimensions in mm Wiring diagrams
15
Order code: CEFL PIR 10A
Splashproof ceiling flush-mounted PIR occupancy switch
Order code: CEFL PIR SEALED CEFL PIR XS
Model CEFL PIR SEALED is protected against light splashes and condensation when installed in the ceiling. Ideal for bathrooms, shower rooms, etc.
Specification
Detection zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 15a and 15b below
Dimensions: 72mm diameter x 68mm
An extra sealed version (order code: CEFL PIRXS) is also available on request. Ideal for domestic bathrooms and toilets (zone 2).
Specification
Detection zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 10 amps (2500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 15a and 15b below
Dimensions: 72mm diameter x 68mm
10 amp rated ceiling flush-mounted PIR occupancy switch
Fig. 201 Ceiling mounted PIR occupancy switch
Up to 5m
Up to 7m
Up to 5m
Up to 7m
Up to 5m
Up to5m
In open plan areas For best coverage the CEFL PIR should be spaced every 5m in either direction
CEFL PIR Strong detection zone
Secondary detection zone
Strong detection zone i.e. person moving arm
Secondary detection zone i.e. person walking (less sensitive when walking straight towards PIR switch)
For optimum coverage recommended mounting height between 2.4 and 5m.
PIR Quad detector gives 124 detection areas within the zone.
Plan view of detection zone Several PIR occupancy switchesPerspective view of detection zone
L
optional manual wall switch for overriding off
A few PIR occupancy switches
230 VAC
L
load
PIR occupancy
switch
optional manual wall switch for overriding off
15a. Single PIR occupancy switch
230 VAC
alternative position for optional wall switch (see p.10 “Start-up Mode”)
15b. A few PIR occupancy switches wired in parallel
alternative position for optional wall switch (see p.10 “Start-up Mode”)
55
3
2m cable
60
72
72
side plan
66
Requires 63 or 64mm (2.5") diameter hole in a false or plasterboard ceiling
38
These neat and unobtrusive models are ideal for flush mounting through suspended or plasterboard ceilings. They have a 2m cable, for quick and easy installation.
N
SL SL SL
SL
N
PIR OCCUPANCY SWITCHES
Detection diagrams
Dimensions in mm Wiring diagrams
16
PIR OCCUPANCY SWITCHES
These surface-mounted models are ideal for solid ceilings.
Ceiling surface-mounted PIR occupancy switch
Can be mounted on a square pattress box, order code: PABO.
Order code: CESF PIR
The CESF PIR is a hard wired version and can be mounted on a square pattress box.
Specification
Detection zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 16a and 16b below
Dimensions: 86 x 86 x 22mm. Requires back box depth 16mm
L
Nload
A few CESF PIR230 VAC
L
N
load
CESF PIR
optional manual wall switch for overriding off
16a. Single CESF PIR
230 VAC
16b. A few CESF PIR wired in parallel
Fig. 201 Ceiling mounted PIR occupancy switch
Up to 5m
Up to 7m
Up to 5m
Up to 7m
Up to 5m
Up to5m
In open plan areasFor best coverage the CESF PIR should be spaced every 5m in either direction
CESF PIRStrong detection zone
Secondary detection zone
Strong detection zone i.e. person moving arm
Secondary detection zone i.e. person walking (less sensitive when walking straight towards PIR switch)
For optimum coverage recommended mounting height between 2.4 and 5m.
PIR Quad detector gives 124 detection areas within the zone.
Plan view of detection zone Several PIR occupancy switchesPerspective view of detection zone
plan side
22
86
86
alternative position for optional wall switch (see p.10 “Start-up Mode”)
alternative position for optional wall switch (see p.10 “Start-up Mode”)
optional manual wall switch for overriding off
Requires 16mm deep box
Ceiling surface-mounted PIR occupancy switch variants
Variants are available on request such as 24V or 12V (a.c. or d.c.), ideal for low voltage control systems. To special order we can also supply volt free outputs for mains, 24V or 12V supplies (including versions with gold contact relays).
Please see page 19 for more information.
SL SL SL
SL
Dimensions in mm Wiring diagrams
Detection diagrams
17
This IP66 rated surface-mounted model is ideal for solid ceilings.
IP66 rated ceiling surface-mounted PIR occupancy switch
Order code: CESF PIR IP66
The CESF PIR IP66 has an IP66 rated enclosure and is ideal for use in zone 2 in bathrooms, shower rooms, washdown areas etc.
CESF PIR IP66 is hard wired.
Unlike CESF PIR (see page 16) the 3 adjustment spindles for Time lag, Sensitivity and Lux settings are located on the back of the product.
Specification
Detection zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 17a and 17b below
Dimensions: 87 x 87 x 53mm.
Other CESF PIR IP66 variants include:
12 volt, 24 volt, 12 volt with volt free contacts, 24 volt with volt free contacts plus a tamperproof version. Please contact us for more information.
L
Nload
A few CESF PIR IP66
230 VAC
L
N
load
CESF PIR IP66
optional manual wall switch for overriding off
17a. Single CESF PIR IP66
230 VAC
17b. A few CESF PIR IP66 wired in parallel
Fig. 201 Ceiling mounted PIR occupancy switch
Up to 5m
Up to 7m
Up to 5m
Up to 7m
Up to 5m
Up to5m
In open plan areasFor best coverage the CESF PIR IP66 should be spaced every 5m in either direction
CESF PIR IP66Strong detection zone
Secondary detection zone
Strong detection zone i.e. person moving arm
Secondary detection zone i.e. person walking (less sensitive when walking straight towards PIR switch)
For optimum coverage recommended mounting height between 2.4 and 5m.
PIR Quad detector gives 124 detection areas within the zone.
Plan view of detection zone Several PIR occupancy switchesPerspective view of detection zone
alternative position for optional wall switch (see p.10 “Start-up Mode”)
alternative position for optional wall switch (see p.10 “Start-up Mode”)
optional manual wall switch for overriding off
SL SL SL
SL
PIR OCCUPANCY SWITCHES
Dimensions in mm Wiring diagrams
Detection diagrams
plan side
53
87
86
87
18
Ceiling flush-mounted PIR occupancy switch variants
DANLERS manufacture a range of variants of the Ceiling flush-mounted PIR for integrating into building management systems, low voltage applications etc.
Order code: CEFL PIR 12V CEFL PIR 12VVF CEFL PIR 24V CEFL PIR 24VVF
12 volt version: CEFL PIR 12V Operating voltage of the switch is 12 volt a.c. or d.c.
12 volt version with volt free contacts: CEFL PIR 12VVF Operating voltage of the switch is 12 volt a.c. or d.c. Comes with 4-core flex.
24 volt version: CEFL PIR 24V Operating voltage of the switch is 24 volt a.c. or d.c.
24 volt version with volt free contacts: CEFL PIR 24VVF Operating voltage of the switch is 24 volt a.c. or d.c. Comes with 4-core flex.
Specification
Detection zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: 12V to 240V: 10mA to 6 amps of resistive, transformer or fluorescent lighting loads, up to 2 amps of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp of fans or most metal halide lamps
Wiring diagram: See diagrams 18a and 18b below
Dimensions: 72mm diameter x 68mm
Other PIR occupancy switch variants
DANLERS also manufacture other variants of their PIR occupancy switches (see table opposite).
Fig. 201 Ceiling mounted PIR occupancy switch
Up to 5m
Up to 7m
Up to 5m
Up to 7m
Up to 5m
Up to5m
In open plan areasFor best coverage the PIR should be spaced every 5m in either direction
PIRStrong detection zone
Secondary detection zone
Strong detection zone i.e. person moving arm
Secondary detection zone i.e. person walking (less sensitive when walking straight towards PIR switch)
For optimum coverage recommended mounting height between 2.4 and 5m.
PIR Quad detector gives 124 detection areas within the zone.
Plan view of detection zone Several PIR occupancy switchesPerspective view of detection zone
55
3
2m cable
60
72
72
side plan
66
Requires 63 or 64mm (2.5") diameter hole in a false or plasterboard ceiling
38
18a. Volt free, normally open
18b. Volt free, normally closed
Volt Free, Normally Open
SupplyVoltage
Neutralor 0V
NO
Load
Volt Free, Normally Closed
SupplyVoltage
Neutralor 0V
NC
Load
SupplyVoltage
Neutralor 0V
Volt Free, Change Over
C
NO
NC
Load(s)
PIR OCCUPANCY SWITCHES
Detection diagrams
Dimensions in mm Wiring diagrams
19
PIR OCCUPANCY SWITCH VARIANTS
DANLERS manufacture many other variants of their PIR occupancy switches including those listed below, many of which can be combined in the same product. For example: A Ceiling Flush Mounted PIR Occupancy Switch (CEFL PIR) with a sealed enclosure (S) to be used with an operating voltage of 12 volts requiring volt free contacts for switching a secondary signal (VF) would be CEFL PIR S12VVF.
If your requirement does not feature on this list please call us to discuss your requirements as other options can be considered. Grid PIR modules and Interior batten mount controls are not available in any of the variants.
NOTE: In the table below if the product has a within its column the product can be manufactured in that variant.
Product code Suffix
Functionality
CE
FL P
IR
CE
SF P
IR
CE
SF P
IR I
P66
CE
LO
CE
DR
6P
CE
DR
6P
CE
FLP
IRLR
WA
CE
PIR
WA
PIR
CO
PD
S or SEALED
Sealed enclosure against light splashes and condensation within zone 2. (For CESF PIR see CESF PIR IP66).
XSExtra sealed enclosure against light splashes, condensation and draughty ceiling voids. Ideal for domestic bathrooms and cloakrooms.
10A Relay load rated up to 10 amp (2500W) resistive load.
12V 12 volt operating voltage a.c. or d.c.
24V 24 volt operating voltage a.c. or d.c.
VFVolt free contacts for switching a secondary signal, rather than the supply voltage. The CEFLPIRVF version is supplied with a 5-core flex.
NCNormally closed relay contacts - The relay contacts will open when the PIR detects and remain open until the time lag has expired.
2DDouble detection - Switches the load ON after it detects twice in succession, to help prevent false triggering in small application areas.
RS Reduced sensitivity - to help prevent false triggering in small application areas.
AR Additional range - Some products can be manufactured with alternative lens types enabling greater detection areas.
HL Hard lens - A hard lens can be fitted to some products to prevent false triggering in draughty environments.
OC Open collector, 30VDC max, 100mA max
G Gold contacts - High voltage, low current
LG Logic Gold contacts - Low voltage, low current
3M, 4M, 5M etc
Various cable lengths can be supplied with Ceiling flush mounted products if you do not require the standard 2 metre length.
DANLERS ControlZAPP enabled PIR Occupancy Switches have functions similar to those of the traditional DANLERS range of PIR Occupancy Switches with many new features added to the easy to set up, programmable, bluetooth low energy interface. For the more details on ControlZAPP see pages 6-7.
20
Ceiling surface-mounted plug-in PIR occupancy switch
These surface-mounted models are ideal for solid ceilings.
Order code: CELO Requires socket, order code: CESO SQ or CESO (see page 21)
The CELO has a built-in plug suitable for the CESO SQ Ceiling socket (or CESO Ceiling socket). CESO SQ can be mounted on a square pattress box (the CESO can be mounted on a BESA box).
Specification
Detection zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: (Each circuit) up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps.
Wiring diagram: See diagrams 20a, 20b, 20c below
Dimensions: 88 x 88 x 47mm
L
load
optional manual wall switch for overriding off
CELOCELOCELO230 VAC
20a. Single CELO 20b. A few CELO wired in parallel 20c. Ceiling mounted socket (CESO SQ or CESO)
L N SL CELO Not to scale
CESO SQ or CESO
Pattress box or BESA box
luminaire
L N
SL
N
L
load
CELO
optional manual wall switch for overriding off
230 VAC
N
plan side
47
88
88
(CESO SQ)
alternative position for optional wall switch (see p.10 “Start-up Mode”)
alternative position for optional wall switch (see p.10 “Start-up Mode”)
Up to 5m
Up to 7m
Up to 5m
Up to 7m Up to 5m
Up to5m
In open plan areasFor best coverage the CELO should be spaced every 5m in either direction
CELOStrong detection zone
Secondary detection zone
Strong detection zone i.e. person moving arm
Secondary detection zone i.e. person walking (less sensitive when walking straight towards PIR switch)
For optimum coverage recommended mounting height between 2.4 and 5m.
PIR Quad detector gives 124 detection areas within the zone.
Plan view of detection zone Several PIR occupancy switchesPerspective view of detection zone
L N ASL SL SL
SL
PIR OCCUPANCY SWITCHES
Detection diagrams
Dimensions in mm
Wiring diagrams
Ceiling socket (CESO SQ)
21
Ceiling socket: CESO
For use with DANLERS plug-in ceiling controls. Can be mounted on a BESA box.
Wiring diagram: See diagram 21a below
Dimensions: 74mm diameter x 13mm
Order code: CESO
Sockets for plug-in ceiling controls
21a. Ceiling mounted socket (CESO or CESO SQ) for plug-in ceiling controls
L N SLplug-in ceiling control Not to scale
CESO or CESO SQ
BESA box or pattressbox
luminaire
L N
SL
L1
N1
CE2SLplus plug-in switch
separate circuit
230 VAC
optional manual wall switch for overriding off
SL1
load
L1
SL2N/C
N1
CESLplus plug-in switch
separate circuit
optional manual wall switch for overriding off
230 VAC load
SL1
SL2N/O
C2 SL2N/O
SL2N/C
SL3N/O
SL3N/C
C3C2
separate circuit
21c. Plug-in control plus double slave relay with volt free changeover contacts (CE2SL) controlling two extra circuits
21b. Plug-in control plus slave relay with volt free changeover contacts (CESL) controlling one extra circuit
Ceiling socket (CESO)
side
plan
74
13
Ceiling slave relays (CESL / CE2SL)
plan side
41
87
87
87
Order code: CESO SQ
plan side
13
87
87
87
Slave relays for plug-in ceiling controls
Ceiling socket with slave relay: CESL
Ceiling socket with slave relay with isolated changeover contacts. Enables the switching of an additional circuit with its own supply, e.g. the corridor lights outside an office or a separate low voltage control circuit. A no socket version is available on request.
Loading: (Each circuit) up to 6 amps (1500W) incandescent or mains halogen lamps. Up to 4 amps (1000W) electronic or wire wound transformers, fluorescent lamps (high frequency or switch start). Up to 2 amps (500W) compact fluorescent or LED lamps. Up to 1 amp (250W) most fans and metal halide discharge lamps.
Wiring diagram: See diagram 21b below
Dimensions: 87 x 87 x 41mm Ceiling socket with double slave relay: CE2SL
Ceiling socket with a double slave relay with isolated changeover contacts. Enables the switching of two additional circuits, each with its own supply, e.g. the corridor lights outside an office, plus the extractor fans inside the office. Also ideal for controlling two separate low voltage control circuits. A no socket version is available on request.
Loading: As CESL above
Wiring diagram: See diagram 21c below
Dimensions: 87 x 87 x 41mm
Order code: CESL or CE2SL
Also available as a square socket.
Ceiling socket: CESO SQ
Can be mounted on a square pattress box.
Wiring diagram: See diagram 21a below
Dimensions: 87 x 87 x 13mm
L N A
ANCILLARY PRODUCTS
Dimensions in mm
Wiring diagrams
22
Ceiling directional PIR occupancy switch
Standard range Order code: CEDR 6P Requires socket, order code: CESO (see page 21)
Standard range version
Designed to give a directional view of the activity to be monitored. Detection angle 120°.
Specification
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 22a, 22b, 22c below
Dimensions: See below
CEDR 6P can be rotated and lowered
to a 45º angle
These directional PIR switches plug into a ceiling mounted socket. The socket can be mounted on a BESA box.
L
load
optional manual wall switch for overriding off
A few CEDR 6P230 VAC
L
load
CEDR 6P
optional manual wall switch for overriding off
22a. Single CEDR 6P
230 VAC
22b. A few CEDR 6P wired in parallel 22c. Ceiling mounted socket (CESO)
Up to 5m Up to 10m
Strong Detection Zone
Secondary Detection Zone
60° 120°
CEDR 6P
Up to 5m Up to 10m
Strong Detection Zone
Secondary Detection Zone
60° 120°
CEDR 6P
Strong Detection Zonei.e. person moving arm
Secondary Detection Zonei.e. person walking across the zone
Plan view Side elevation
CEDR 6P
L N SL CEDR 6P Not to scale
CESO
BESA box
luminaire
L N
SL
NN
alternative position for optional wall switch (see p.10 “Start-up Mode”)
alternative position for optional wall switch (see p.10 “Start-up Mode”)
60
74
64
102
side
(CESO)
Perspective view
L N ASL SL SL
SL
PIR OCCUPANCY SWITCHES
Detection diagrams
Dimensions in mm
Wiring diagrams
23
Ceiling directional PIR occupancy switch
Long range Order code: CEDR 6PLR Requires socket, order code: CESO (see page 21)
Long range version
With a long range, narrow detection beam. Designed for corridors and storage aisles.
Specification
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 23a, 23b, 23c below
Dimensions: See below
DANLERS also manufacture a Long range ceiling flush mounted PIR occupancy switch, order code CEFL PIR LR see page 27 for details.
These directional PIR switches plug into a ceiling mounted socket. The socket can be mounted on a BESA box.
L
load
optional manual wall switch for overriding off
A few CEDR 6PLR230 VAC
L
load
CEDR 6PLR
optional manual wall switch for overriding off
23a. Single CEDR 6PLR
230 VAC
alternative position for optional wall switch (see p.10 “Start-up Mode”)
23b. A few CEDR 6PLR wired in parallel
alternative position for optional wall switch (see p.10 “Start-up Mode”)
23c. Ceiling mounted socket (CESO)
L N SL CEDR 6PLR Not to scale
CESO
BESA box
luminaire
L N
SL
Up to 25m
CEDR 6PLR
Strong Detection Zonei.e. person walking towards PIR
Secondary Detection Zonei.e. person walking across the zone
Up to 10m Up to 25m
CEDR 6PLR
15mUp to 10m
15m
6°
Plan view
Side elevation
CEDR 6PLR
Ideal mounting height between 2.2 and 3m
NN
60
74
64
115
side
(CESO)
CEDR 6PLR can be rotated and lowered
to a 45º angle
Perspective view
L N ASL SL SL
SL
PIR OCCUPANCY SWITCHES
Wiring diagrams
Dimensions in mm
Detection diagrams
2524
BATTEN MOUNT PIR OCCUPANCY SWITCHES
‘Intelligent’ active photocell versions
Ideal for use in factories, warehouses, offices, schools etc.
Unique one touch calibration process removes the site specific addition of artificial light from any decision to automatically switch the lights on/off - eliminates risk of load ‘cycling’ on/off. To maximise on the energy saving potential of the ‘Intelligent’ photocell, these products are recommended for areas with some natural daylight.
If lighting load is ON and ambient light rises above the preset threshold - the load is switched OFF. Inhibits load from switching ON if lux is greater than the preset threshold.
Active photocell operation to maximise energy saving with Overlux timer (passing cloud timer) to minimise unnecessary switching.
Real time photocell status indicator. Test function which switches load on/off when testing.
IP53 rated enclosure.
Specification
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 3000 lux (adjustable)
Loading: Up to 10 amps (2500W) of resistive and tungsten. Up to 6 amps (1500W) of fluorescent (switch start) or mains halogen lamps*. *Recommended with integral thermal safety fuse. Up to 3 amps (750W) of electronic or wire wound transformers or compact fluorescent or LED lamps.
Wiring diagram: See diagram 24 below
Dimensions: See below
BMINTPIRSP Spot detection, 1.5 metre at 2.4m - 5m mounting height
BMINTPIR5M 5 metre detection at 2.4m - 5m mounting height
BMINTPIRRH Reduced height version to avoid detection spillage onto lower floors, 2.5 metre detection at 2.5m mounting height)
BMINTPIR10M 10 metre detection at 2.4m - 5m mounting height
These easy to fit controls can be mounted onto the end of lighting battens via the 20mm knock out. 1 metre wire tails to connect to the lighting ballast.
These products have a GB Patent Pending. GB Patent application number 1219746.3
front
50
120
36
105
side
20mmthreadedentry spout
Up to 5m
BMINTPIR5M orBMPIR5M
For optimum coverage recommended mounting height between 2.4 and 5m.
Perspective view of detection zone
Detection zone
100°
Up to 10m
BMINTPIR10M orBMPIR10M
For optimum coverage recommended mounting height between 2.4 and 5m.
Detection zone
112°
Up to 1.5m
BMINTPIRSP orBMPIRSP
For optimum coverage recommended mounting height between 2.4 and 5m.
20°
Dimensions in mm
Detection diagrams
L
load
BMINTPIR (SP, 5M, 10M, RH)
optional manual wall switch for overriding off
24. Single BMINTPIR (SP, 5M, 10M or RH)
230 VAC
N
SLN
Wiring diagram
Order codes: BMINTPIR5M, BMINTPIRRH
Order code: BMINTPIR10M
Order code: BMINTPIRSP
2524
Passive photocell versions
Ideal for use in factories, warehouses, offices, schools etc
Photocell override facility. This is ideal for areas with no natural light such as some warehouses and corridors without external windows.
Switches lights on when somebody is detected. Switches lights off when nobody has been detected for a chosen period. The photocell can be set so that lights do not switch on during the day.
Realtime photocell status indicator (glows green when active or red when inactive).
IP53 rated enclosure.
Specification
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 3000 lux (adjustable) and inactive
Loading: Up to 10 amps (2500W) of resistive and tungsten. Up to 6 amps (1500W) of fluorescent (switch start) or mains halogen lamps*. *Recommended with integral thermal safety fuse. Up to 3 amps (750W) of electronic or wire wound transformers or compact fluorescent or LED lamps.
Wiring diagram: See diagram 25 below
Dimensions: See below
BMPIRSP Spot detection, 1.5 metre at 2.4m - 5m mounting height
BMPIR5M 5 metre detection at 2.4m - 5m mounting height
BMPIRRH Reduced height version to avoid detection spillage onto lower floors, 2.5 metre detection at 2.5m mounting height)
BMPIR10M 10 metre detection at 2.4m - 5m mounting height
These easy to fit controls can be mounted onto the end of lighting battens via the 20mm knock out and come with 1 metre wire tails to connect to the lighting ballast.
BATTEN MOUNT PIR OCCUPANCY SWITCHES
front
50
120
36
105
side
20mmthreadedentry spout
Up to 5m
BMINTPIR5M orBMPIR5M
For optimum coverage recommended mounting height between 2.4 and 5m.
Perspective view of detection zone
Detection zone
100°
Up to 10m
BMINTPIR10M orBMPIR10M
For optimum coverage recommended mounting height between 2.4 and 5m.
Detection zone
112°
Up to 1.5m
BMINTPIRSP orBMPIRSP
For optimum coverage recommended mounting height between 2.4 and 5m.
20°
Detection diagrams
Dimensions in mm
L
load
BMINTPIR (SP, 5M, 10M, RH)
optional manual wall switch for overriding off
25. Single BMPIR (SP, 5M, 10M or RH)
230 VAC
N
SLN
Wiring diagram
Order codes: BMPIR5M, BMINTPIRRH
Order code: BMPIR10M
Order code: BMPIRSP
Dimensions in mm Wiring diagrams
26
Batten mounted PIR occupancy switch - IP66 rated
Order code: BMEXPIR
Specification
Weatherproof: IP66 rating
Detection range: Up to 10m
Detection angle: 120°
Time lag: 2 to 20 minutes (adjustable)
Photocell range: 10 lux to infinite lux (adjustable)
Loading: Up to 6 amps (1500W) incandescent or mains halogen lamps. Up to 4 amps (1000W) electronic or wire wound transformers, fluorescent lamps (high frequency or switch start). Up to 2 amps (500W) compact fluorescent or LED lamps. Up to 1 amp (250W) most fans and metal halide discharge lamps.
Wiring diagram: See diagram 26 below
Dimensions: 75 x 60 x 37mm plus 1 metre wire tails
Cost effective, quick and easy to fit PIR occupancy switch designed to fit onto the end of lighting battens.
230 VAC
L
N
load
BMEXPIR
optional manual switch for overriding off
10
65
37
24 24
60
front side
Cablegland
5
17
DANLERS Batten mount PIR occupancy switch can be mounted onto the end of lighting battens via the 20mm knock out. The switch includes the connection 20mm thread and 1 metre of 3-core flex to connect to the lighting ballast.
Ideal for use in factories, warehouses, offices, schools etc., but also wetrooms, damp areas and outdoor environments such as car parks due to its tough IP66 rated enclosure.
Switches lights on when somebody is detected.
Switches lights off when nobody has been detected for a chosen period.
The photocell can be set so that lights do not switch on during the day.
Tough, compact IP66 rated polycarbonate moulding.
7m
Detection zone
7m
50°
100°
BMEXPIR
Side elevation and end elevation
For optimum coveragerecommended mounting height between 2.4 and 5 m
26. Single PIR occupancy switch
SL
PIR OCCUPANCY SWITCHES
Detection diagram
BMEXPIR fitted on the end of a lighting batten.
27
Order code: CEFL PIR LR
Ceiling mounted long range PIR occupancy switch
27a. Single CEFL PIR LR 27b. A few CEFL PIR LR wired in parallel
L
load
optional manual wall switch for overriding off
A few CEFL PIR LR230 VAC alternative
position for optional wall switch (see p.10 “Start-up Mode”)
N
L
load
CEFL PIR LR
optional manual wall switch for overriding off
230 VAC
alternative position for optional wall switch (see p.10 “Start-up Mode”)
N
With a long range, narrow detection beam. Designed for warehouses and storage aisles with a narrow point of access.
CEFL PIR LR is also suitable for building into luminaires.
Specification
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 27a and 27b below
Dimensions: See below
A photocell override version of the above is available on request.
DANLERS also manufacture a PIR occupancy switch module suitable for mounting onto Eurodata plates with a 12 metre range for storage aisles and warehouses (order code GREUW PIR12E). Please call for further details.
This long range PIR occupancy switch is ideal for storage aisles and high bay applications where a height of up to 20m is required.
55
3
2m cable
60
72
72
side plan
66
Requires 63 or 64mm (2.5") diameter hole in a false or plasterboard ceiling
38
17
CEFL PIR LR
Strong Detection Zonei.e. person moving arm
Secondary Detection Zonei.e. person walking across the zone
Up to 10m
Up to 20m
15m
6°
SL
SL SL SL
PIR OCCUPANCY SWITCHES
Detection diagram
Dimensions in mm Wiring diagrams
28
Wall or ceiling mounted PIR occupancy switch
The WACE PIR is suitable for either wall or ceiling mounting. It fits either into a plaster depth (16mm) wall box or onto a ceiling mounted square pattress box. It requires a neutral wire.
Order code: WACE PIR
Applications
Suitable for stairwells, corridors, toilet lobbies, etc.
Version incorporating override off button, enabling lights to be held off during video presentations etc, available by request.
Specification
Detection angle: 120°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 28a and 28b below
Dimensions: 86 x 86 x 22mm. Wall box depth 16mm
28a. Single WACE PIR 28b. A few WACE PIR wired in parallel, eg. in a stairwell
Requires 16mm deep box
Up to 5m Up to 10m
WACE PIR Strong Detection Zone
Secondary Detection Zone 60°
120°
Up to 5m Up to 10m
StrongDetectionZone
SecondaryDetectionZone45°
90° WACE PIR
Up to 5m Up to 10m
WAPIR Strong Detection Zone
Secondary Detection Zone 60°
120°
Up to 5m Up to 10m
Strong Detection Zone
Secondary Detection Zone 45°
90° WAPIR
Strong Detection Zonei.e. person moving arm
Secondary Detection Zonei.e. person walking across the zone
Strong Detection Zonei.e. person moving arm
Secondary Detection Zonei.e. person walking across the zone
Plan view Side elevation
Wall mounted PIR occupancy switch
Ideal mounting height between 1 and 1.8m
L
Nload
A few WACE PIR
230 VAC
load
L
N
WACE PIR
230 VAC
plan side
2286
86
Perspective view
SL
SL SL SL
PIR OCCUPANCY SWITCHES
Dimensions in mm Wiring diagrams
Detection diagrams
29
The WAPIR model replaces an existing wall switch – no neutral wire is needed. It fits into a plaster depth (16mm) wall box. The WAPIR model also has a manual override off switch on the front of the plate.
Wall mounted PIR occupancy switch
Order code: WAPIR
The WAPIR is suitable for small offices, meeting rooms, tutoring rooms, etc. For wall mounting only. The WAPIR is supplied with a load capacitor to augment small loads.
The override off button (out position) enables the lights to be held off during video presentations, etc. A version without the manual override button is also available on request (order code WAPIRX).
Specification
Detection angle: 120°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Maximum load: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Minimum load: 40W resistive or approximately 100W inductive per WAPIR in the circuit. A load capacitor (CAPLOAD) is supplied to augment small loads.
Wiring diagram: See diagrams 29a and 29b below
Dimensions: 86 x 86 x 22mm. Wall box depth 16mm
NOTE: Because WAPIR requires a permanent live supply the following restrictions apply: - WAPIR should only be used in applications where the lights would not be ON for
more time than they are OFF. This is to allow its rechargeable battery enough time to recharge itself from the mains supply.
- Wiring WAPIR’s in parallel will increase the ON status of a load and therefore the battery may not have sufficient time to recharge.
- The load MUST be able to pass parasitic current. The battery may not charge with some low energy / high efficiency luminaire products that do not pass sufficient parasitic current.
- If power factor correction capacitors are inbuilt to the luminaire, it is not advised to add additional CAPLOADs to the switching circuit.
29a. Single WAPIR 29b. A few WAPIR wired in parallelRequires 16mm deep wall box
Up to 5m Up to 10m
WACE PIR Strong Detection Zone
Secondary Detection Zone 60°
120°
Up to 5m Up to 10m
StrongDetectionZone
SecondaryDetectionZone45°
90° WACE PIR
Up to 5m Up to 10m
WAPIR Strong Detection Zone
Secondary Detection Zone 60°
120°
Up to 5m Up to 10m
Strong Detection Zone
Secondary Detection Zone 45°
90° WAPIR
Strong Detection Zonei.e. person moving arm
Secondary Detection Zonei.e. person walking across the zone
Strong Detection Zonei.e. person moving arm
Secondary Detection Zonei.e. person walking across the zone
Plan view Side elevation
Wall mounted PIR occupancy switch
Ideal mounting height between 1 and 1.8m
L
Nload
WAPIR WAPIR WAPIR
230 VAC
L
N
230 VAC
load
WAPIRplan side
2286
86
Perspective view
SL
SL SLSL
PIR OCCUPANCY SWITCHES
Dimensions in mm Wiring diagrams
Detection diagrams
These modules are suitable for mounting onto Eurodata plates and fit into a 35mm deep wall box. They are also suitable for building into luminaires (see page 76 for fixing bezel). They require a neutral wire.
Order code: GREUW PIR5X
5m detection - concealed adjustment spindles
Adjustment spindles hidden behind front surface lid for a neat finish (module must be removed from wall plate or luminaire to adjust). Can be suited in with other Eurodata modules.
Specification
Detection zone: 360°
Detection angle: 100°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 15 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 30a and 30b below
Dimensions: 50 x 25 x 38mm, minimum wall box depth of 35mm
30a. Single PIR occupancy switch module 30b. A few PIR occupancy switch modules wired in parallel, eg. in a stairwell
L
Nload
A few PIR occupancy switch modules
230 VAC
load
L
N
PIR occupancy switch module
230 VAC
30
Dimensions in mm GREUW PIR5X, GREUW PIR5E. Requires wall box depth of 35mm
3825
50
front side
Order code: GREUW PIR5E
5m detection - visible adjustment spindles
Adjustment spindles visible on front surface for quick and convenient adjustment. Can be suited in with other Eurodata modules.
Specification
Detection zone: 360°
Detection angle: 100°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 15 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 30a and 30b below
Dimensions: 50 x 25 x 38mm, minimum wall box depth of 35mm
Up to 7m
GREUW PIR5X or GREUW PIR5E
Detection zone
For optimum coveragerecommended mounting height between 2.4 and 5m
Up to5m
Plan view (wall mounted)
GREUW PIR5X or GREUW PIR5E
Side elevation (wall mounted)
GREUW PIR5X or GREUW PIR5E
Perspective view (ceiling mounted)
Up to 5m
DetectionZone40°
80°
Up to 5m
DetectionZone50°
100°
SL
SL SL SL
PIR OCCUPANCY SWITCH MODULES
Dimensions in mm Wiring diagrams
Detection diagrams
These modules are suitable for ceiling mounting onto Eurodata plates. They are also suitable for building into luminaires (see page 76 for fixing bezel). They require a neutral wire. These versions are best suited for use in areas such as warehouses, sports halls and circulation areas, where there is likely to be a significant level of movement.
Order code: GREUW PIR10X
10m detection - concealed adjustment spindles
Adjustment spindles hidden behind front surface lid for a neat finish (module must be removed from plate or luminaire to adjust). Can be suited in with other Eurodata modules.
Specification
Detection zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 15 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 31a and 31b below
Dimensions: 50 x 25 x 38mm, minimum back box depth of 35mm
A photocell override version is available on request.
31a. Single PIR occupancy switch module 31b. A few PIR occupancy switch modules wired in parallel, eg. in a stairwell
L
Nload
A few PIR occupancy switch modules
230 VAC
load
L
N
PIR occupancy switch module
230 VAC
Dimensions in mm GREUW PIR10X, GREUW PIR10E. Requires back box depth of 35mm
3825
50
front side
Order code: GREUW PIR10E
31
10m detection - visible adjustment spindles
Adjustment spindles visible on front surface for quick and convenient adjustment. Suitable for mounting onto a Eurodata plate. Can be suited in with other Eurodata modules.
Specification
Detection zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 15 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, transformer or fluorescent lighting loads, up to 2 amps (500W) of low energy lighting loads (LED lamps and compact fluorescent) or up to 1 amp (250W) of fans or most metal halide lamps
Wiring diagram: See diagrams 31a and 31b below
Dimensions: 50 x 25 x 38mm, minimum back box depth of 35mm
A photocell override version is available on request.
Up to 15m
GREUW PIR10X or GREUW PIR10E
Detection zone
For optimum coveragerecommended mounting height between 5 and 10m
Up to12m
Perspective view (ceiling mounted)
optional manual wall switch for overriding off
SL
SL SL SL
PIR OCCUPANCY SWITCH MODULES
Dimensions in mm Wiring diagrams
Detection diagram 12 metre (mounting height) versions of the above are available on request (order codes: GREUWPIR12E and GREUWPIR12X).