SMA Solar Technology AG Planning and design of PV power plants Be a solar expert
Transcript
Page 1: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

SMA Solar Technology AG

Planning and design of PV power plantsBe a solar expert

Page 2: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

The information contained in this presentation is subject to amendment, revision and updating. Certain statements contained in thispresentation may be statements of future expectations and other forward-looking statements that are based on the management’s current

Disclaimer

presentation may be statements of future expectations and other forward looking statements that are based on the management s currentviews and assumptions and involve known and unknown risks and uncertainties. Actual results, performance or events may differ materiallyfrom those in such statements as a result of, among others, factors, changing business or other market conditions and the prospects for growthanticipated by the management of the Company. These and other factors could adversely affect the outcome and financial effects of theplans and events described herein. The Company does not undertake any obligation to update or revise any forward-looking statements,whether as a result of new information future events or otherwise You should not place undue reliance on forward looking statements whichwhether as a result of new information, future events or otherwise. You should not place undue reliance on forward-looking statements whichspeak only as of the date of this presentation.All information contained herein has been carefully prepared. Nevertheless, we do not guarantee its accuracy or completeness and nothingherein shall be construed to be a representation of such guarantee.The information contained in this presentation is subject to amendment, revision and updating. Certain statements contained in thispresentation may be statements of future expectations and other forward-looking statements that are based on the management’s currentviews and assumptions and involve known and unknown risks and uncertainties. Actual results, performance or events may differ materiallyfrom those in such statements as a result of, among others, factors, changing business or other market conditions and the prospects for growth

ti i t d b th t f th C Th d th f t ld d l ff t th t d fi i l ff t f thanticipated by the management of the Company. These and other factors could adversely affect the outcome and financial effects of theplans and events described herein. The Company does not undertake any obligation to update or revise any forward-looking statements,whether as a result of new information, future events or otherwise. You should not place undue reliance on forward-looking statements whichspeak only as of the date of this presentation.Thi t ti i f i f ti l d t b f th di t ib t d d t t whi h i t th dd fThis presentation is for information purposes only and may not be further distributed or passed on to any party which is not the addressee ofthis presentation. No part of this presentation must be copied, reproduced or cited by the addressees hereof other than for the purpose forwhich it has been provided to the addressee.This document is not an offer of securities for sale in the United States of America. Securities may not be offered or sold in theU it d St t f A i b t i t ti ti f i t ti d th U S S iti A t f 1933

SMA Solar Technology AG

United States of America absent registration or an exemption from registration under the U.S. Securities Act of 1933 asamended.

Page 3: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

The SMA Solar Academy

> Transfer of knowledge> Well-matched

comprehensive seminar program

> Small, medium and large scale PV plantsscale PV plants

SMA Solar Technology AG 3P-P-PD-1-DE-en_WW-124010

Page 4: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

Organizational Matters

> Escape routesEscape routes> Meeting point in case of a fire alarm> Toilets> Smoking area> Please mute your cell phones or switch them off> Badges

> Solar Academy contact data> Phone: +49 (0)561-9522-4884 > il S l d @SMA d> Badges

> Cafeteria> e-mail: [email protected]

> Download areas:> http://www.SMA.de/handoutp

SMA Solar Technology AG 4P-P-PD-1-DE-en_WW-124010

Page 5: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Seminar Contents

Introduction12 Design of large scale PV plants with SMA components3 Sunny Design 2 30

Option Code: SC, SSM, TCS, Communit3 Sunny Design 2.3045 W k h5 Workshop

SMA Solar Technology AG 5P-P-PD-1-DE-en_WW-124010

Page 6: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Large scale PV plant design

> Environment > Sunny Central> PV generator/module> Combiner Box

M

> Transformer Compact Station> Grid

M> Sunny String Monitor > Monitoring

SMA Solar Technology AG 6P-P-PD-1-DE-en_WW-124010

Page 7: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> Environment/cos φ: Germany/cos φ= 1 > Grid: 20 kV / 50 Hz

Example:

> PV generator/module: 0,910 MWp / MPV120M> Sunny String Monitors: SSM XX-11

l

> Monitoring: DSL> NPR: 80-100%

> Sunny Central: SC XXX CP > Transformer Compact Station: TCS XXXX

SMA Solar Technology AG 7P-P-PD-1-DE-en_WW-124010

Page 8: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Data sheet: Module MPV 120-M -

SMA Solar Technology AG 8P-P-PD-1-DE-en_WW-124010Source: www.masdarpv.com

Page 9: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Module MPV 120-M

SMA Solar Technology AG 9

P-P-PD-1-DE-en_WW-124010Source: www.masdarpv.com

Page 10: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> Version 2.30

Sunny Design Software

> Electric properties> Temperature coefficients

SMA Solar Technology AG 10P-P-PD-1-DE-en_WW-124010

Page 11: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Design Software

SMA Solar Technology AG 11P-P-PD-1-DE-en_WW-124010

Page 12: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> PV string length

Sunny Design

> PV generator size > Nominal Power Ratio> P f t

> Power factor

SMA Solar Technology AG 12P-P-PD-1-DE-en_WW-124010

Page 13: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> Maximum PV voltage VOC (-10 ºC)

Sunny Design

M> Maximum PV current IMPP (+70 ºC, 1000 W/m2)

> Minimum PV voltage VMPP (+70 ºC)

M M

SMA Solar Technology AG 13P-P-PD-1-DE-en_WW-124010

Page 14: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> Annual energy yield M

Sunny Design

> Specific energy yield > Performance ratio > N i l ti

M M M> Nominal power ratio M

SMA Solar Technology AG 14P-P-PD-1-DE-en_WW-124010

Page 15: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - Option Code

1. Maximum DC-Voltage2. DC connection3. DC fuses4 d4. Grounding5. Insulation monitoring6 Communication6. Communication7. Fiber optic components8. Language/Country9. AC switch10. String current monitoring11. AC voltage12. Cabinet layout

SMA Solar Technology AG 15P-P-PD-1-DE-en_WW-124010

Page 16: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> Connecting solar modules (V MPP = 109 V) in series increases the voltage in string

Sunny Central 760 CP-10 - Maximum DC voltage

> Strings may not exceed the permissible system voltage (VMAX = 1000 V) under the worst conditions (low temperatures, high radiation, open circuit)

> Each of the strings connected to a Sunny Central must always have the same number of solar g y ymodules connected in series

MPV120M MPV120M MPV120M

. . .

SMA Solar Technology AG 16

V OC String < 1000 VV OC String < V DC MAX Sunny Central P-P-PD-1-DE-en_WW-124010

Page 17: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - Maximum DC voltage

SMA Solar Technology AG 17

MP-P-PD-1-DE-en_WW-124010

Page 18: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - DC connection

> PV module MPV 120M> Thin-film technology> Fuses in plus and isolating blades in minus

M

SMA Solar Technology AG 18P-P-PD-1-DE-en_WW-124010

Page 19: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - DC fuses

> PV module MPV 120M> Thin-film technology> Fuses in plus and isolating blades in minus> F i 125A/160A/200A/250A/315A/400A> Fuse sizes: 125A/160A/200A/250A/315A/400A

SMA Solar Technology AG 19P-P-PD-1-DE-en_WW-124010

Page 20: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> Maximum current of PV generator 1390.4 A

Sunny Central 760 CP-10 - DC fuses

> Fuses in plus: 5/7/8 fuses are possible> Possible fuse sizes: 400A/315A/250A> R d ti f t 0 7> Reduction factor: 0.7> Isolating blades in minus

Fuses 125 A 160 A 200 A 250 A 315 A 400 A

Maximum current of PV arrays 1390.4 A

Reduction factor 0.7 0.7 0.7 0.7 0.7 0.7

I Fuse-max 87.5 A 112 A 140 A 175 A 220 A 280 A

SMA Solar Technology AG 20

N Inputs DC + 16 13 10 8 7 5

P-P-PD-1-DE-en_WW-124010

Page 21: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> 5/7/8 inputs with fuses are possible

Sunny Central 760 CP-10 - DC fuses

> 5/7/8 Sunny String Monitor (SSM) are possible too> Maximum permissible DC current of SSM must be considerate> M i i ibl DC t f SSM d d bi t> Maximum permissible DC current of SSM depends on ambient

temperature

Sunny String Monitor

SMA Solar Technology AG 21

y g

P-P-PD-1-DE-en_WW-124010

Page 22: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - DC fuses

SSM24-11

SSM16-11

SMA Solar Technology AG 22P-P-PD-1-DE-en_WW-124010

Page 23: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - DC fuses

SSM24-11

SC 760 CP-10:8 x Fuse 250 A (I Fuse-max = 175 A) 7 x Fuse 315 A (I Fuse-max = 220 A) 5 x Fuse 400 A (I Fuse-max = 280 A)

SSM16-11

Sunny String Monitor

SMA Solar Technology AG 23P-P-PD-1-DE-en_WW-124010

Page 24: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

SC 760 CP-10:

Sunny Central 760 CP-10 - DC fuses

SSM24-11SC 760 CP-10:8 x Fuse 250 A (I Fuse-max = 175 A) 7 x Fuse 315 A (I Fuse-max = 220 A) 5 x Fuse 400 A (I Fuse max = 280 A) 5 x Fuse 400 A (I Fuse-max 280 A)

SSM16-11

SMA Solar Technology AG 24P-P-PD-1-DE-en_WW-124010

Page 25: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Option 1: Calculating with SSM 24-11 - DC fuses

> PV generator: 1264 strings> Inverter: 1 x SC 760 CP-10> SC 760 CP-10 fuses: 5 x DC + bar > SC 760 CP 10 f i 400A> SC 760 CP-10 fuse size: 400A> SC 760 CP-10 reduction factor: 0,7> Sunny String Monitor: 5 x SSM 24-11y g

Fuses SC 760 CP 125 A 160 A 200 A 250 A 315 A 400 A

Reduction factor 0.7 0.7 0.7 0.7 0.7 0.7

I Fuse-max 87.5 A 112 A 140 A 175 A 220 A 280 A

SMA Solar Technology AG 25

N Inputs 16 13 10 8 7 5

P-P-PD-1-DE-en_WW-124010

Page 26: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> 5 x SSM 24-11

Option 1: Calculating with SSM 24-11 - DC fuses

> SSM 24-11 I DC max : 312 A (50 ºC)> SSM 24-11 fuse sizes: 10A/12A/16A/20A> SSM 24 11 d ti f t 0 65 (50 ºC)> SSM 24-11 reduction factor: 0.65 (50 ºC)> IString = 1.10 A

Fuses SSM 24-11 10 A 12 A 16 A 20 A

Reduction factor 0.65 0.65 0.65 0.65

Max. I Fuse 6.5 A 7.8 A 10.4 A 13.0 A

Max. Strings Fuse 5 7 9 11

Max. Strings SSM24-11 120 168 216 264

SMA Solar Technology AG 26

Sunny String Monitor

P-P-PD-1-DE-en_WW-124010

Page 27: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> Fuse size 20 A

Option 1: Calculating with SSM 24-11 - DC fuses

> Up to 11 strings per SSM input> Up to 264 string per SSM> It i t i l bi b ith 11 i t> It is necessary to use a special combiner box with 11 inputs> High cost of DC cabling

Fuses SSM 24-11 10 A 12 A 16 A 20 A

Reduction factor 0.65 0.65 0.65 0.65

Max. I Fuse 6.5 A 7.8 A 10.4 A 13.0 A

Max. Strings Fuse 5 7 9 11

Max. Strings SSM24-11 120 168 216 264

SMA Solar Technology AG 27

Sunny String Monitor

P-P-PD-1-DE-en_WW-124010

Page 28: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> 5 x SSM 24-11 > Special combiner box is necessary

Option 1: Calculating with SSM 24-11 - DC fuses

> PV generator has 1264 strings> Fuses can not be identical> 4 SSM 24 11 ith 20 A f

> High cost

SC 760 CP-10:> 4 x SSM 24-11 with 20 A fuse> 1 x SSM 24-11 with 16 A fuse

SC 760 CP 10:5 x Fuse 400 A (I Fuse-max = 280 A)

4 x SSM 24-11 Fuses SSM -11 10 A 12 A 16 A 20 A

1 x SSM 24-11 120 168 216 264

2 SSM 24 240 336 432 528

96 Fuses (20A) 96 Combiner box (11 strings)

2 X SSM 24-11 240 336 432 528

3 X SSM 24-11 360 504 648 7921 x SSM 24-11 24 Fuses (16A)

24 Combiner box (9 strings)

4 X SSM 24-11 480 672 864 1056

5 X SSM 24-11 600 840 1080 13205 x SSM 24-11 120 Combiner box (11/9 strings)

SMA Solar Technology AG 28

Customer combiner cox120 Fuses (20/10 A) 1264 Fuses (5A)

P-P-PD-1-DE-en_WW-124010

Page 29: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Option 2: Calculating with SSM 16-11 - DC fuses

> PV generator: 1264 strings> Inverter: 1 x SC 760 CP-10> SC 760 CP-10 fuses: 7 x DC + bus > SC 760 CP 10 f i 315 A> SC 760 CP-10 fuse size: 315 A> SC 760 CP-10 reduction factor: 0,7> Sunny String Monitor: 7 x SSM 16-11y g

Fuses SC 760 CP 125 A 160 A 200 A 250 A 315 A 400 A

Reduction factor 0.7 0.7 0.7 0.7 0.7 0.7

I Fuse-max 87.5 A 112 A 140 A 175 A 220 A 280 A

N 16 13 10 8 7 5

SMA Solar Technology AG 29

N Inputs 16 13 10 8 7 5

P-P-PD-1-DE-en_WW-124010

Page 30: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> 7 x SSM 16-11

Option 2: Calculating with SSM 16-11 - DC fuses

> SSM 16-11 I DC max : 260 A (50 ºC)> SSM 16-11 fuse sizes: 10A/12A/16A/20A/25A> SSM 16 11 d ti f t 0 65 (50 ºC)> SSM 16-11 reduction factor: 0.65 (50 ºC)> I String = 1.10 A

Fuses SSM 16-11 10 A 12 A 16 A 20 A 25 A

d fReduction factor 0.65 0.65 0.65 0.65 0.65

I Fuse-max 6.5 A 7.8 A 10.4 A 13 A 16.25 A

Strings Fuse 5 7 9 11 14g Fuse

Strings SSM16-11 80 112 144 176 224

SMA Solar Technology AG 30

Sunny String Monitor

P-P-PD-1-DE-en_WW-124010

Page 31: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> Fuse size 25 A

Option 2: Calculating with SSM 16-11 - DC fuses

> Up to 14 strings per SSM input> Up to 224 string per SSM> It i ibl t i l bi b ith 14 i t> It is possible to use a special combiner box with 14 inputs> It is possible to use the SMA Combiner Box with 12 inputs

Fuses SSM 16-11 10 A 12 A 16 A 20 A 25 A

d fReduction factor 0.65 0.65 0.65 0.65 0.65

I Fuse-max 6.5 A 7.8 A 10.4 A 13 A 16.25 A

Strings Fuse 5 7 9 11 14g Fuse

Strings SSM16-11 80 112 144 176 224

SMA Solar Technology AG 31

Sunny String Monitor

P-P-PD-1-DE-en_WW-124010

Page 32: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> Up to 1568 strings

Option 2: Calculating with SSM 16-11 - DC fuses

> Special combiner box with 14 fuses> High cost of DC cabling

Fuses SSM 16-11 10 A 12 A 16 A 20 A 25 A

1 x SSM 16-11 80 112 144 176 224

2 X SSM 16-11 160 224 288 352 448

3 X SSM 16-11 240 336 432 528 672

4 X SSM 16-11 320 448 576 704 896

5 X SSM 16-11 400 560 720 880 1120

6 X SSM 16-11 480 672 864 1056 1344

7 X SSM 16-11 520 784 1008 1232 1568

SMA Solar Technology AG 32

7 X SSM 16 11 520 784 1008 1232 1568Sunny String Monitor

P-P-PD-1-DE-en_WW-124010

Page 33: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Option 2: Calculating with SSM 16-11 - SMA Combiner Box

> Up to 24 DC fuses (12 plus/12 minus)> Fuse sizes 5 A, 10 A, 12 A, 15 A, 20 A, 25 A> Reduction factor 0.55> U t 2 t i DC f> Up to 2 strings per DC fuses> Equipped with a DC switch-disconnector> Overvoltage protectiong p

SMA Solar Technology AG 33

SMA Combiner Box

P-P-PD-1-DE-en_WW-124010

Page 34: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> Maximum allowable reverse current is 5 A

Option 2: Calculating with SSM 16-11 - SMA Combiner Box

> Recommended circuit configuration is 5 strings x 6 modules per cluster> There is no need for a serial fuse per string in the case of a 5 strings per cluster > F 6 t i d i l f f 5 A t i i t b d> From 6 strings onward, a serial fuse of 5 A per string is to be used > Bear in mind that the minus pole of PV generator must be grounded

I Cluster = 5,50 A

P = 120 Wp, V OC = 142,2 V, I SC = 1,34 A, I MPP = 1,10 A

+

6 6 6 6 6

I String = 1,10 AV OC = 853,2 V

1 1 1 1 1

SMA Solar Technology AG 34

_P-P-PD-1-DE-en_WW-124010

Page 35: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> SMA Combiner Box reduces cost

Option 2: Calculating with SSM 16-11 - SMA Combiner Box

> 12 strings per SMA Combiner Box> 12 DC + fuses> F i 5 A> Fuse size 5 A > 1 string per fuse> 192 strings per SSM 16-11

F SSM 16 11 10 A 12 A 16 A 20 A 25 A 25 A

g p

SMA Combiner Box

Fuses SSM 16-11 10 A 12 A 16 A 20 A 25 A 25 A

Reduction factor 0.65 0.65 0.65 0.65 0.65 0.65

I Fuse-max 6.5 A 7.8 A 10.4 A 13 A 16.25 A 13.20 AFuse-max

Strings Fuse 5 7 9 11 14 12

Strings SSM16-11 80 112 144 176 224 192

SMA Solar Technology AG 35SMA Combiner Box

P-P-PD-1-DE-en_WW-124010

Page 36: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> 7 x SSM 16-11 > 6 x SSM 16-11 with 25 A fuse

Option 2: Calculating with SSM 16-11 - DC fuses

> 1264 strings> Fuses can not be identical

SMA Combiner Box (12 strings)SC 760 CP-10:

SMA Combiner Box (7 strings)

> 1 x SSM 16-11 with 12 A fuse

Fuses SSM 16-11 10 A 12 A 16 A 20 A 25 A 25 A

1 x SSM 16-11 80 112 144 176 224 192

SMA Combiner Box (12 strings)7 x Fuse 315 A (I Fuse-max = 220 A)

6 x SSM 16-11 96 fuses (25 A)

SMA Combiner Box (7 strings)

2 X SSM 16-11 160 224 288 352 448 384

3 X SSM 16-11 240 336 432 528 672 576

96 fuses (25 A) 96 combiner box (12 strings)

1 x SSM 16-11

4 X SSM 16-11 320 448 576 704 896 768

5 X SSM 16-11 400 560 720 880 1120 960

16 fuses (12 A) 16 combiner box ( 7 strings)

7 SSM 16 11

6 X SSM 16-11 480 672 864 1056 1344 1152

7 X SSM 16-11 520 784 1008 1232 1568 1344

7 x SSM 16-11 112 combiner box (12/7 strings) 112 fuses (25/12 A) 1264 fuses (5 A)

SMA Solar Technology AG 36

( )

P-P-PD-1-DE-en_WW-124010

Page 37: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Option 2: Calculating with SSM 16-11 - SMA Combiner Box

> Optimal solution> 7 x SSM 16-11> 112 Combiner Box

SMA Solar Technology AG 37P-P-PD-1-DE-en_WW-124010

Page 38: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-11 - DC fuses

> 7 fuses per pole> Fuse size: 315 A

M

SMA Solar Technology AG 38P-P-PD-1-DE-en_WW-124010

Page 39: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - Grounding

> PV module MPV 120M> Thin-film technology> GFDI and minus grounding

M

SMA Solar Technology AG 39P-P-PD-1-DE-en_WW-124010

Page 40: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - Grounding

SMA Solar Technology AG 40P-P-PD-1-DE-en_WW-124010

Page 41: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - Insolation monitoring

> With GFDI

M

SMA Solar Technology AG 41P-P-PD-1-DE-en_WW-124010

Page 42: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - Communication

> Touch display

M

SMA Solar Technology AG 42P-P-PD-1-DE-en_WW-124010

Page 43: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

COM-CInverter 01SC 760 CP-10

Inverter 02SC 760 CP-10

Sunny Central 760 CP-10 - Fiber optic components

in control center/grid operationInternet

1 500 m

5 m

SMA Service900 m

5 m

InverterInverter

75 m

Inverter

Fiber optics multi mode

Copper (100m max. length between 2 participants)

Fiber optics single mode (15 km max. length between 2 participants)

Fiber optics multi mode (2km max. length between 2 participants)

M

SMA Solar Technology AG 43

M

P-P-PD-1-DE-en_WW-124010

Page 44: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - Language /Country of destination

> Germany

M M

SMA Solar Technology AG 44P-P-PD-1-DE-en_WW-124010

Page 45: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - AC switch

> With AC circuit breaker

M

SMA Solar Technology AG 45P-P-PD-1-DE-en_WW-124010

Page 46: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - String current monitoring

> 7 x SSM 16-11

Fiber optic or Ethernet (Cu)

(optional)Splicebox

> 7 x 16 = 112 channels> Max. 8 channels per SMU> M 10 SMU´ h b

ServiceSwitch(E h )

(optional)Fiber optic converter> Max. 10 SMU s per hub

> Max. 3 hubs per SC 760 CP-10

RS485Inverter

WebBox

RS485

(Ethernet )

SCSMC

SSM 1

Sunny StringMonitor

Hub

RS485

SSM 2SSM 3

SSM N

SC xxx CP

RS485

SMA Solar Technology AG 46

SSM N SCSMC: Sunny Central String Monitor Controller

P-P-PD-1-DE-en_WW-124010

Page 47: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> 112 channels

Sunny Central 760 CP-10 - String current monitoring

Fiber optic or Ethernet (Cu)

(optional)Splicebox

> 14 SMUs> 2 hubs> H b1 48 h l

ServiceSwitch(E h )

(optional)Fiber optic converter> Hub1: 48 channels

> Hub 2: 64 channels 1 SSM 16-112 SSM 16-11

Hub 1RS485

RS485Inverter

WebBox

RS485

(Ethernet )3 SSM 16-11

SCSMC

4 SSM 16-11 Hub 2

RS485

RS485

5 SSM 16-11 6 SSM 16-11

7 SSM 16-11

SC 760 CP-10

SMA Solar Technology AG 47

SCSMC: Sunny Central String Monitor Controller

P-P-PD-1-DE-en_WW-124010

Page 48: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny Central 760 CP-10 - String current monitoring

> 112 channels> 14 SMUs> 2 hubs> H b1 48 h l> Hub1: 48 channels> Hub 2: 64 channels

M

SMA Solar Technology AG 48P-P-PD-1-DE-en_WW-124010

Page 49: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> 342 V

Sunny Central 760 CP-10 - AC voltage and cabinet layout

> Standard

M M

SMA Solar Technology AG 49P-P-PD-1-DE-en_WW-124010

Page 50: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny String Monitor SSM 16-11 - Option Code

> Optimal solution> 7 x SSM 16-11> 112 Combiner Box

SMA Solar Technology AG 50P-P-PD-1-DE-en_WW-124010

Page 51: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny String Monitor SSM 16-11 - Option Code

SMA Combiner Box

PV strings

Sunny Central SC 760 CP-10y

Sunny String Monitor SSM 16-11

SMA Solar Technology AG 51P-P-PD-1-DE-en_WW-124010

Page 52: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> 6 x SSM 16-11

Sunny String Monitor SSM 16-11 - Option Code

> 96 x SMA Combiner Box> 1152 strings

5 A

25 A16 X PVM 120M

1

SMA Combiner Box

12

Sunny Central (315 A fuse)

16

y ( )

Sunny String Monitor SSM 16-11

16

SMA Solar Technology AG 52P-P-PD-1-DE-en_WW-124010

Page 53: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> 1 x SSM 16-11

Sunny String Monitor SSM 16-11 - Option Code

> 16 x SMA Combiner Box> 112 strings

5 A

25 A16 X PVM 120M

1

SMA Combiner Box

7

Sunny Central (315 A fuse)

16

y ( )

Sunny String Monitor SSM 16-11

16

SMA Solar Technology AG 53P-P-PD-1-DE-en_WW-124010

Page 54: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

X 6

Sunny String Monitor SSM 16-11 - Option Code

X 6

X 6

X 6

1

2

7

X 6

X 6Sunny String Monitor

SSM 16-11

SMA Solar Technology AG 54P-P-PD-1-DE-en_WW-124010

Page 55: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

1. Cabinet

Sunny String Monitor SSM 16-11 - Option Code

2. Device type3. Version4 f4. String fuse5. DC switch6 Connections per input6. Connections per input 7. Connector8. Cable glands with sealing area9. DC output10. Language

SMA Solar Technology AG 55

Sunny String Monitor SSM 16-11

P-P-PD-1-DE-en_WW-124010

Page 56: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny String Monitor SSM 16-11 - Option Code

SMA Solar Technology AG 56

P-P-PD-1-DE-en_WW-124010

Page 57: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Sunny String Monitor SSM 16-11 - Option Code

SMA Solar Technology AG 57P-P-PD-1-DE-en_WW-124010

Page 58: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

X 6

SMA Combiner Box - Option Code

X 6

X 6

X 6

1

2

7

X 6

X 6

SMA Combiner Box

SMA Solar Technology AG 58P-P-PD-1-DE-en_WW-124010

Page 59: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

SMA Combiner Box - Option Code

SMA Solar Technology AG 59

P-P-PD-1-DE-en_WW-124010

Page 60: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

SMA Combiner Box - Option Code

SMA Solar Technology AG 60P-P-PD-1-DE-en_WW-124010

Page 61: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

COM-CInverter 01SC 760 CP-10

Inverter 02SC 760 CP-10

Sunny Central 760 CP-10 - Communication Concept

in control center/grid operationInternet

1 500 m

5 m

SMA Service900 m

5 m

InverterInverter

75 m

Inverter

Fiber optics multi mode

Copper (100m max. length between 2 participants)

Fiber optics single mode (15 km max. length between 2 participants)

Fiber optics multi mode (2km max. length between 2 participants)

SMA Solar Technology AG 61P-P-PD-1-DE-en_WW-124010

Page 62: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

COM-CInverter 01SC 760 CP-10

Inverter 02SC 760 CP-10

Sunny Central 760 CP-10 - Communication Concept

Communitin control center/grid operation

Internet1 500 m

5 m

SMA Service900 m

5 m

InverterInverter75 m

Inverter

Fiber optics multi mode

Copper (100m max. length between 2 participants)

Fiber optics single mode (15 km max. length between 2 participants)

Fiber optics multi mode (2km max. length between 2 participants)

SMA Solar Technology AG 62P-P-PD-1-DE-en_WW-124010

Page 63: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Inverter 01SC 760 CP-10

Inverter 02SC 760 CP-10

Sunny Central 760 CP-10 - Communication Concept

CInternet 1 500 m

5 m

Communit

SMA Service900 m

5 m

InverterInverter

75 m

Inverter

Fiber optics multi mode

Copper (100m max. length between 2 participants)

Fiber optics single mode (15 km max. length between 2 participants)

Fiber optics multi mode (2km max. length between 2 participants)

SMA Solar Technology AG 63P-P-PD-1-DE-en_WW-124010

Page 64: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Communit - Option Code

SMA Solar Technology AG 64P-P-PD-1-DE-en_WW-124010

Page 65: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Communit - Option Code

SMA Solar Technology AG 65P-P-PD-1-DE-en_WW-124010

Page 66: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> Transformerless inverter must not be used (e.g. Sunny Tripower)

Transformer Compact Station and SC 760 CP-10

> Sunny Centrals require always a medium voltage transformer

UU UG idUWRUPV-MPP

~~~UGrid

SMA Solar Technology AG 66

Medium voltage transformerSunny Central

P-P-PD-1-DE-en_WW-124010

Page 67: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Transformer Compact Station and 760 CP-10

SMA Solar Technology AG 67P-P-PD-1-DE-en_WW-124010

Page 68: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

C i

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

CommunitTransformer Compact Station and 760 CP-10X 6

X 6

1

23 x 342 V 3 x 20 kV

X 6

X 6

7

TCS 1600 SC

X 6

Inverter 01 Inverter 02TCS 1600 SCX 6

X 6

SMA Solar Technology AG 68P-P-PD-1-DE-en_WW-124010

Page 69: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Transformer Compact Station TCS 1600 SC - Option Code

SMA Solar Technology AG 69P-P-PD-1-DE-en_WW-124010

Page 70: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Design of large scale PV-Plant Communit

X 6

X 6

1

23 x 342 V 3 x 20 kV

X 6

X 6

7

TCS 1600 SC

X 6

Inverter 01 Inverter 02TCS 1600 SCX 6

X 6

SMA Solar Technology AG 70P-P-PD-1-DE-en_WW-124010

Page 71: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

> Environment/cos φ: Milan (Italy)/cos φ= 1 > Grid: 20 kV / 50 Hz

Workshop

> PV generator/module: 1,9 MWp / E19 / 318> Sunny String Monitors: SSM XX-11> S C t l SC XXX CP XT

> Topology: Ring> Monitoring: DSL> NPR 80 100%> Sunny Central: SC XXX CP XT

> Transformer Compact Station: TCS XXXX> NPR: 80-100%

SMA Solar Technology AG 71P-P-PD-1-DE-en_WW-124010

Page 72: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Design

1. PV module data sheet2. PDF file Sunny Design 2.303. Sunny Central data sheet4 SSM d t h t4. SSM data sheet5. Communit data sheet6. TCS data sheet7. Sunny Central option code8. SSM option code9. Communit option code10. TCS option code

SMA Solar Technology AG 72P-P-PD-1-DE-en_WW-124010

Page 73: Planning and design of PV power plants - SMA Solar · PDF filePlanning and design of PV power plants ... Large scale PV plant design ... Power factor SMA Solar Technology AG P-P-PD-1-DE-en_WW-124010

1. Introduction | 2. Design | 3. Sunny Design | 4. Option Code | 5. Workshop

Allways up to date with the Sunny Newsletter

go.sma.de/newsSMA Solar Technology AG 73P-P-PD-1-DE-en_WW-124010