FAN SCHEDULE 1. PROVIDE WITH FAN SPEED CONTROLLER. LOCATE FAN SPEED CONTROLLER ON VERTICAL DUCT GOING UP TO ASSOCIATED FAN ON ROOF. 2. PROVIDE WITH WALL SWITCH TO TURN FAN ON AND OFF. REFER TO PLANS FOR LOCATION OF WALL SWITCH. 3. FAN HOUSING SHALL HAVE A QUICK RELEASE LATCHING FOR EASE OF ACCESS TO INTERNAL COMPONENTS. TAG NAME AREA SERVED CFM S.P. IN. W.C. FAN RPM (NOTE E) DRIVE MAX. AMCA SONES BACKDRAFT DAMPER CURB TYPE (NOTE F) ELECTRICAL MANUFACTURER MODEL REMARKS BHP (NOTE D) MHP (NOTE D) VOLTAGE PHASES DISCONNECT CONTROLLER/ STARTER BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE EF-1 FRONT OF HOUSE TOILETS 635 0.50 1440 DIRECT 8.8 GRAVITY MFR 0.12 0.25 120 1 MFR NF MFR NOTE 1 COOK ACED NOTE 3 EF-2 FREEZER ENCLOSURE 900 0.25 1190 DIRECT 7.2 GRAVITY MFR 0.1 0.25 120 1 MFR NF MFR NOTE 1 COOK ACED NOTE 3 EF-3 BACK OF HOUSE TOILETS 475 0.50 1395 DIRECT 7.6 GRAVITY MFR 0.1 0.25 120 1 MFR NF MFR NOTE 1 COOK ACED NOTE 3 EF-4 BREAKROOM 1110 0.30 1625 DIRECT 9.8 GRAVITY MFR 0.09 0.125 120 1 MFR NF MFR NOTE 1 COOK ACED NOTE 2, 3 EF-5 BIOHAZARD 275 0.25 1520 DIRECT 7.6 GRAVITY MFR 0.09 0.125 120 1 MFR NF MFR NOTE 1 COOK ACED NOTE 3 EF-6 COPY ROOM 320 0.25 1345 DIRECT 7.2 GRAVITY MFR 0.07 0.125 120 1 MFR NF MFR NOTE 1 COOK ACED NOTE 3 LINEAR DIFFUSER SCHEDULE NOTES: 1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION. 2. PROVIDE WITH CONCEALED FASTENERS. 3. DIRECT ONE EXTERIOR SLOT STRAIGHT DOWN TO WASH EXTERIOR WALL/WINDOW AND SECOND SLOT TOWARD INTERIOR OF BUILDING. 4. DIRECT TWO EXTERIOR SLOTS STRAIGHT DOWN TO WASH EXTERIOR WALL/WINDOW AND REMAINING INTERIOR SLOTS TOWARD INTERIOR OF BUILDING. 5. DIRECT ALL SLOTS STRAIGHT DOWN TO WASH EXTERIOR WINDOW. TAG NAME MATERIAL SLOT WIDTH NO. OF SLOTS WIDTH LENGTH PLENUM REQUIRED PLENUM INSULATION TYPE PLENUM INLET SIZE PATTERN CONTROL REQUIRED BALANCING DAMPER REQUIRED FINISH MANUFACTURER MODEL REMARKS LD-1 ALUMINUM 3/4" 2 5" 4'-0" YES WRAPPED SEE DWG. YES NO WHITE TITUS ML NOTE 1, 2 & 3 LD-2 ALUMINUM 3/4" 3 6" 4'-0" YES WRAPPED SEE DWG. YES NO WHITE TITUS ML NOTE 1, 2 & 4 LD-3 ALUMINUM 3/4" 4 7" 4'-0" YES WRAPPED SEE DWG. YES NO WHITE TITUS ML NOTE 1, 2 & 4 LD-4 ALUMINUM 3/4" 4 7" 4'-0" YES WRAPPED SEE DWG. YES NO WHITE TITUS ML NOTE 1, 2, & 5 GRILLES REGISTERS & DIFFUSERS SCHEDULE NOTES: 1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION. TAG NAME MATERIAL CONFIGURATION MARGIN (NOTE 1) INLET SIZE (IN.) FACE SIZE (IN.) BALANCING DAMPER REQUIRED FINISH MANUFACTURER MODEL REMARKS CD-1 STEEL PANEL FACE LAY-IN SEE DWG. 24x24 NO WHITE TITUS OMNI FLUSH FACE PANEL CD-2 ALUMINUM CRITICAL ENVIRONMENT LAY-IN SEE DWG. 48x24 NO WHITE TITUS RADIATEC PROVIDE WITH 48x24 HEPA FILTER AND HEPA FILTER MOUNTING WITHIN PLENUM. PROVIDE WITH INSULATED BACKPAN. CD-3 STEEL PANEL FACE 1 1/4" SEE DWG. 24x24 NO WHITE TITUS OMNI FLUSH FACE PANEL, MOUNTED IN 4'x 4' CEILING TILE. EG-1 STEEL PERFORATED FACE LAY-IN SEE DWG. 24x24 NO WHITE TITUS PAR DUCTED EXHAUST EG-2 STEEL 35 DEGREE DEFLECTION 1 1/4" SEE DWG. INLET + 2 NO WHITE TITUS 350R DUCTED EXHAUST RG-1 STEEL PERFORATED FACE LAY-IN 16"Ø 24x24 NO WHITE TITUS PAR DUCTED RETURN AND TRANSFER AIR. 14" NECK W/FLEX CONNECTION. RG-2 STEEL 35 DEGREE DEFLECTION 1 1/4" SEE DWG. INLET + 2 NO WHITE TITUS 350R SG-1 STEEL DOUBLE DEFLECTION 1 1/4" SEE DWG. INLET +2 NO WHITE TITUS 300R SG-2 STEEL DOUBLE DEFLECTION LAY-IN SEE DWG. INLET +2 NO WHITE TITUS 300R SCHEDULE GENERAL NOTES: A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND INSTALLED BY: MFR = MANUFACTURER TCC = AUTOMATIC TEMPERATURE CONTROL CONTRACTOR B. DISCONNECT TYPE: NF = NON-FUSED C. CONTROLLER STARTER TYPE: FV = FULL VOLTAGE VFD = VARIABLE FREQUENCY DRIVE D. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR NAME PLATE RATING. E. MUST BE WITHIN +/- 10% OF SCHEDULED RPM. F. CURB TYPE: MFR = STANDARD CURB BY MANUFACTURER IF CELLS CONTAINS A '0', THAT VALUE IS N/A Drawing Previous Issue Dates Project Owner All reports, plans, specifications, computer files, field data, notes and other documents and instruments prepared by OPN Architects, Inc. as instruments of service shall remain the property of OPN Architects, Inc. OPN Architects, Inc. shall retain all common law, statutory and other reserved rights, including the copyright thereto. © 2014 OPN Architects, Inc. CEDAR RAPIDS - DES MOINES - MADISON OPN ARCHITECTS OPN Project No. 18 19 A ARCHITECTS 200 5TH AVENUE SE SUITE 201 CEDAR RAPIDS, IA 52401 319-363-6018 PHONE 319-363-7349 FAX www.opnarchitects.com [email protected] 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 B C D E F G H J K L M N Revision Dates Sheet Issue Date BIO-LIFE PLASMA SERVICES CENTER CONSTRUCTION SET M501 MECHANICAL SCHEDULES 14215000 CD SET 02/28/14 LONGMONT, CO UNIT HEATER SCHEDULE - HOT WATER TAG NAME AREA SERVED CONFIGURATION CFM MBH GPM EWT °F LWT °F W.P.D. FT. HEAD ELECTRICAL MANUFACTURER MODEL HP RPM (NOTE E) VOLTAGE PHASES DISCONNECT CONTROLLER / STARTER BY (NOTE A) BY (NOTE A) TYPE (NOTE B) UH-1 RECEIVING HORIZONTAL DISCHARGE 475 40 4.0 140 120 0.80 0.125 1550 115 1 MFR. NF MFR TRANE UHS TM ENGINEERING CONSULTANTS Experience you can build on. PROJECT # 515.334.9906 FAX: 515.334.9908 www.kjww.com 2882 106th STREET DES MOINES, IOWA 50322 KJWW ENGINEERING RESERVES PROPRIETARY SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF KJWW ENGINEERING. © 2014 KJWW, P.C. RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF KJWW ENGINEERING 13.0096.14
Transcript
Page 1: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

FAN SCHEDULE

1. PROVIDE WITH FAN SPEED CONTROLLER. LOCATE FAN SPEED CONTROLLER ON VERTICAL DUCT GOING UP TO ASSOCIATED FAN ON ROOF. 2. PROVIDE WITH WALL SWITCH TO TURN FAN ON AND OFF. REFER TO PLANS FOR LOCATION OF WALLSWITCH. 3. FAN HOUSING SHALL HAVE A QUICK RELEASE LATCHING FOR EASE OF ACCESS TO INTERNAL COMPONENTS.

TAGNAME AREA SERVED CFM

S.P.IN.

W.C.

FANRPM

(NOTE E) DRIVE

MAX.AMCASONES

BACKDRAFTDAMPER

CURBTYPE

(NOTE F)

ELECTRICAL

MANUFACTURER MODEL REMARKSBHP

(NOTE D)MHP

(NOTE D) VOLTAGE PHASES

DISCONNECT CONTROLLER/ STARTER

BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPEEF-1 FRONT OF HOUSE

TOILETS635 0.50 1440 DIRECT 8.8 GRAVITY MFR 0.12 0.25 120 1 MFR NF MFR NOTE 1 COOK ACED NOTE 3

EF-2 FREEZER ENCLOSURE 900 0.25 1190 DIRECT 7.2 GRAVITY MFR 0.1 0.25 120 1 MFR NF MFR NOTE 1 COOK ACED NOTE 3

EF-3 BACK OF HOUSETOILETS

475 0.50 1395 DIRECT 7.6 GRAVITY MFR 0.1 0.25 120 1 MFR NF MFR NOTE 1 COOK ACED NOTE 3

EF-4 BREAKROOM 1110 0.30 1625 DIRECT 9.8 GRAVITY MFR 0.09 0.125 120 1 MFR NF MFR NOTE 1 COOK ACED NOTE 2, 3

EF-5 BIOHAZARD 275 0.25 1520 DIRECT 7.6 GRAVITY MFR 0.09 0.125 120 1 MFR NF MFR NOTE 1 COOK ACED NOTE 3

EF-6 COPY ROOM 320 0.25 1345 DIRECT 7.2 GRAVITY MFR 0.07 0.125 120 1 MFR NF MFR NOTE 1 COOK ACED NOTE 3

LINEAR DIFFUSER SCHEDULE

NOTES: 1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION. 2. PROVIDE WITH CONCEALED FASTENERS. 3. DIRECT ONE EXTERIORSLOT STRAIGHT DOWN TO WASH EXTERIOR WALL/WINDOW AND SECOND SLOT TOWARD INTERIOR OF BUILDING. 4. DIRECT TWO EXTERIOR SLOTS STRAIGHT DOWN TO WASH

EXTERIOR WALL/WINDOW AND REMAINING INTERIOR SLOTS TOWARD INTERIOR OF BUILDING. 5. DIRECT ALL SLOTS STRAIGHT DOWN TO WASH EXTERIOR WINDOW.

TAGNAME MATERIAL

SLOTWIDTH

NO. OFSLOTS WIDTH LENGTH

PLENUMREQUIRED

PLENUMINSULATION

TYPEPLENUM

INLET SIZE

PATTERNCONTROLREQUIRED

BALANCINGDAMPER

REQUIRED FINISH MANUFACTURER MODEL REMARKSLD-1 ALUMINUM 3/4" 2 5" 4'-0" YES WRAPPED SEE DWG. YES NO WHITE TITUS ML NOTE 1, 2 & 3

LD-2 ALUMINUM 3/4" 3 6" 4'-0" YES WRAPPED SEE DWG. YES NO WHITE TITUS ML NOTE 1, 2 & 4

LD-3 ALUMINUM 3/4" 4 7" 4'-0" YES WRAPPED SEE DWG. YES NO WHITE TITUS ML NOTE 1, 2 & 4

LD-4 ALUMINUM 3/4" 4 7" 4'-0" YES WRAPPED SEE DWG. YES NO WHITE TITUS ML NOTE 1, 2, & 5

GRILLES REGISTERS & DIFFUSERS SCHEDULE

NOTES: 1. CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION.

TAGNAME MATERIAL CONFIGURATION

MARGIN(NOTE 1)

INLETSIZE(IN.)

FACESIZE(IN.)

BALANCINGDAMPER

REQUIRED FINISH MANUFACTURER MODEL REMARKSCD-1 STEEL PANEL FACE LAY-IN SEE DWG. 24x24 NO WHITE TITUS OMNI FLUSH FACE PANEL

CD-2 ALUMINUM CRITICALENVIRONMENT

LAY-IN SEE DWG. 48x24 NO WHITE TITUS RADIATEC PROVIDE WITH 48x24 HEPA FILTER AND HEPAFILTER MOUNTING WITHIN PLENUM. PROVIDEWITH INSULATED BACKPAN.

CD-3 STEEL PANEL FACE 1 1/4" SEE DWG. 24x24 NO WHITE TITUS OMNI FLUSH FACE PANEL, MOUNTED IN 4'x 4'CEILING TILE.

EG-1 STEEL PERFORATED FACE LAY-IN SEE DWG. 24x24 NO WHITE TITUS PAR DUCTED EXHAUST

EG-2 STEEL 35 DEGREEDEFLECTION

1 1/4" SEE DWG. INLET + 2 NO WHITE TITUS 350R DUCTED EXHAUST

RG-1 STEEL PERFORATED FACE LAY-IN 16"Ø 24x24 NO WHITE TITUS PAR DUCTED RETURN AND TRANSFER AIR. 14"NECK W/FLEX CONNECTION.

RG-2 STEEL 35 DEGREEDEFLECTION

1 1/4" SEE DWG. INLET + 2 NO WHITE TITUS 350R

SG-1 STEEL DOUBLE DEFLECTION 1 1/4" SEE DWG. INLET +2 NO WHITE TITUS 300R

SG-2 STEEL DOUBLE DEFLECTION LAY-IN SEE DWG. INLET +2 NO WHITE TITUS 300R

SCHEDULE GENERAL NOTES:A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND

INSTALLED BY:

MFR = MANUFACTURER

TCC = AUTOMATIC TEMPERATURE CONTROL CONTRACTOR

B. DISCONNECT TYPE:

NF = NON-FUSED

C. CONTROLLER STARTER TYPE:

FV = FULL VOLTAGE

VFD = VARIABLE FREQUENCY DRIVE

D. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR

NAME PLATE RATING.

E. MUST BE WITHIN +/- 10% OF SCHEDULED RPM.

F. CURB TYPE:

MFR = STANDARD CURB BY MANUFACTURER

IF CELLS CONTAINS A '0', THAT VALUE IS N/A

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

M501

MECHANICALSCHEDULES

14215000

CD SET 02/28/14

LONGMONT, CO

UNIT HEATER SCHEDULE - HOT WATER

TAGNAME

AREASERVED CONFIGURATION CFM MBH GPM

EWT°F

LWT°F

W.P.D.FT.

HEAD

ELECTRICAL

MANUFACTURER MODELHPRPM

(NOTE E) VOLTAGE PHASES

DISCONNECT CONTROLLER/ STARTER BY

(NOTE A)BY

(NOTE A)TYPE

(NOTE B)UH-1 RECEIVING HORIZONTAL

DISCHARGE475 40 4.0 140 120 0.80 0.125 1550 115 1 MFR. NF MFR TRANE UHS

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

Page 2: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

TERMINAL AIR BOX SCHEDULE - FAN POWERED WITH REHEAT

NOTES: 1. NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.0" INLET STATIC PRESSURE WHEN TESTED PER ARI STANDARD 885-98 USING 5/8" 20-LB DENSITY MINERAL FIBER CEILING TILE. 2. TOTAL AIR PRESSURE DROPOF TAB AND REHEAT COIL SHALL NOT EXCEED 0.50" WC. 3. REFER TO CONTROL DIAGRAM PLANS FOR DESCRIPTION OF CONTROL TYPE. 4. SENSOR TYPES: 2 - SENSOR WITH ADJUSTMENT. 5. TERMINAL AIR BOX AND SENSOR FURNISHED BY TRANE.

TAGNAME

AREASERVED CONFIGURATION

CFM HEATING COIL

MIN.INLETSIZE

FAN

CONTROLTYPE

(NOTE 3)

SENSORTYPE

(NOTE 4) MANUFACTURER MODEL REMARKSCOOLING

MAX.HEATING

MAX. MIN.EAT°F

LAT°F

EWT°F

LWT°F GPM CFM

S.P. IN.W.C. HP VOLTAGE PHASES

DISCONNECT CONTROLLER/STARTER BY

(NOTE A)BY

(NOTE A)TYPE

(NOTE B)101 SUPERVISED

PLAY 101PARALLEL 865 865 305 65 92 140 120 2.5 8" 560 0.5 0.33 277 1 MFR NF MFR F 2 TRANE VPWF NOTES 1, 2, 5

110 EXAM 110 PARALLEL 570 570 290 65 92 140 120 1.7 8" 280 0.5 0.125 277 1 MFR NF MFR F 2 TRANE VPWF NOTES 1, 2, 5

115A DONOR FLOOR115

PARALLEL 3175 1,570 915 65 92 140 120 4.6 14" 655 0.5 0.33 277 1 MFR NF MFR F 2 TRANE VPWF NOTES 1, 2, 5

115B DONOR FLOOR115

PARALLEL 2590 1,285 750 65 92 140 120 3.7 14" 535 0.5 0.33 277 1 MFR NF MFR F 2 TRANE VPWF NOTES 1, 2, 5

116 TRAININGSUPERVISOR

116

PARALLEL 300 230 100 65 92 140 120 0.7 6" 130 0.5 0.125 277 1 MFR NF MFR F 2 TRANE VPWF NOTES 1, 2, 5

135A DONOR FLOOR135

PARALLEL 2100 1,185 625 65 92 140 120 3.5 14" 560 0.5 0.33 277 1 MFR NF MFR F 2 TRANE VPWF NOTES 1, 2, 5

135B DONOR FLOOR135

PARALLEL 2825 1,580 835 65 92 140 120 4.6 14" 745 0.5 0.33 277 1 MFR NF MFR F 2 TRANE VPWF NOTES 1, 2, 5

141 ASSISTANTMANAGER 141

PARALLEL 495 425 135 65 92 140 120 1.2 6" 290 0.5 0.125 277 1 MFR NF MFR F 2 TRANE VPWF NOTES 1, 2, 5

142 CENTERMANAGER 142

PARALLEL 360 360 85 65 92 140 120 1.0 6" 275 0.5 0.125 277 1 MFR NF MFR F 2 TRANE VPWF NOTES 1, 2, 5

143 CONFERENCE143

PARALLEL 530 345 180 65 92 140 120 1.0 6" 165 0.5 0.125 277 1 MFR NF MFR F 2 TRANE VPWF NOTES 1, 2, 5

146A RECEPTION146

PARALLEL 1460 880 700 65 92 140 120 2.6 12" 180 0.5 0.125 277 1 MFR NF MFR F 2 TRANE VPWF NOTES 1, 2, 5

146B RECEPTION146

PARALLEL 1460 880 700 65 92 140 120 2.6 12" 180 0.5 0.125 277 1 MFR NF MFR F 2 TRANE VPWF NOTES 1, 2, 5

TERMINAL AIR BOX SCHEDULE - SINGLE DUCT

NOTES: 1. NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.0" INLET STATIC PRESSURE WHEN TESTED PER ARI STANDARD 885-98 USING5/8" 20-LB DENSITY MINERAL FIBER CEILING TILE. 2. TOTAL AIR PRESSURE DROP OF TAB AND REHEAT COIL SHALL NOT EXCEED 0.50" WC. 3. REFER TO CONTROL

DIAGRAM PLANS FOR DESCRIPTION OF CONTROL TYPE. 4. SENSOR TYPES: 4 - SENSOR WITH ADJUSTMENT AND OVERRIDE.5.TERMINAL AIR BOX SENSOR FURNISHED BY TRANE.

TAGNAME AREA SERVED

CFM HEATING COIL MIN.INLET

SIZE (IN.)

CONTROLTYPE

(NOTE 3)

SENSORTYPE

(NOTE 4) MANUFACTURER MODEL REMARKSCOOLING

MAX.HEATING

MAX. MIN.EAT°F

LAT°F

EWT°F

LWT°F GPM

105 WOMENS 105 350 350 350 60 92 140 120 1.2 6" E 4 TRANE VCWF NOTES 1, 2, 5

109 EXAM 109 170 135 135 60 82 140 120 0.3 6" D 4 TRANE VCWF NOTES 1, 2, 5

118 BREAK ROOM 118 1120 665 665 60 92 140 120 2.3 10" D 4 TRANE VCWF NOTES 1, 2, 5

120 UTILITY ROOM 120 435 435 0 60 92 140 120 1.5 6" D 4 TRANE VCWF NOTES 1, 2, 5

121 BIOHAZARD 121 250 250 250 60 92 140 120 0.9 6" E 4 TRANE VCWF NOTES 1, 2, 5

123 ELECTRICAL ROOM 123 535 155 0 60 92 140 120 0.5 8" D 4 TRANE VCWF NOTES 1, 2, 5

129 LOCKER ROOM 129 530 530 530 60 82 140 120 1.3 8" E 4 TRANE VCWF NOTES 1, 2, 5

137 QUALITY MANAGER 137 260 245 80 60 92 140 120 0.8 6" D 4 TRANE VCWF NOTES 1, 2, 5

139 CENTER SUPERVISOR 139 395 290 290 60 82 140 120 0.7 6" D 4 TRANE VCWF NOTES 1, 2, 5

140 TELE/DATA 140 675 0 0 0 0 0 0 0.0 8" C 4 TRANE VCCF NOTES 1, 2, 5

PUMP SCHEDULE

TAGNAME

AREASERVED GPM

PUMP FT.HEAD ATDESIGN

MINIMUMPUMP

EFFICIENCYINLETSIZE

IMPELLERSIZE

(INCHES)

ELECTRICAL

MANUFACTURER MODELHP RPM VOLTAGE PHASE

DISCONNECTCONTROLLER/

STARTER

BY(NOTE A)

BY(NOTE A)

TYPE(NOTE C)

HWP-1 HEATINGWATER

38.0 60.00 45 1 1/2" 8.000 3 1750 460 3 EC EC FV B & G SERIES 80

HWP-2 HEATINGWATER

38.0 60.00 45 1 1/2" 8.000 3 1750 460 3 EC EC FV B & G SERIES 80

ROOFTOP AIR HANDLING UNIT SCHEDULE -GAS/ELECTRIC - 1

NOTES: 1. LAT LISTED IS AT DISCHARGE OF RTU. 2. GAS HEAT SHALL BE FULLY MODULATING AND SHALL BE ABLE TO OPERATE AT 7,920 CFM. 3. TWO RELIEF FANS PROVIDED ON COMMON SHAFT DRIVEN BY ONE RELIEF FAN MOTOR. 4. P.C. SHALL PROVIDE EACH RTU WITH GAS PRESSURE REGULATOR. INCOMING GAS PRESSURE IS2 PSI. 5. PROVIDE WITH SPRING ISOLATED CURB. REFER TO SPECIFICATION SECTION 23 74 11 FOR REQUIREMENTS. 6. UNITS FURNISHED BY TRANE 7. RELIEF AND SUPPLY FANS SHALL BE CONTROLLED BY VFD.

TAGNAME

AREASERVED

SUPPLY FAN RELIEF FAN

MIN. OACFM

HEATING - GAS (NOTE 4) COOLING COIL - DX HOT GAS REHEAT COIL

CFMMIN.CFM

EXT S.P.IN W.C. TYPE

RPM(NOTE E)

BHP(NOTE D)

MHP(NOTE D) CFM

MIN.CFM

EXT S.P.IN W.C. RPM MHP

EAT °FDB

LAT °FDB

MIN. EFF.AFUE

MAX. INPUTMBH

MAX. OUTPUTMBH

GASPRESSURE

IN. W.C.EAT °F

DBEAT °F

WB

LAT °FDB

(NOTE 1)LAT °F

WBTOTALMBH

AMB.TEMP °F REFRIGERANT MIN. EER.

REFRIGERANTCIRCUITING EAT °F DB EAT °F WB

COOLINGLAT °F DB

(WITHREHEAT )

TOTALMBH

RTU-1 DONOR/OFFICE 21450 7920 1.80 FC 1150 26.8 30 17750 4220 0.75 600 7.5 3700 33.7 60 0.81 500 405 12 76.9 53.6 53.0 41.0 660 100.0 R410A 13 2 0 0 0 °F 0

RTU-2 RECEIVING 3000 3000 1.00 FC 1284 1.5 2 0 0 0.00 0 0 1000 44.8 95 0.81 185 150 12 79.8 55.0 55.0 43.0 90 100.0 R410A 11.5 2 55 43 72 °F 55.1

ROOFTOP AIR HANDLING UNIT SCHEDULE -GAS/ELECTRIC - 2

FILTERTYPE

ROOFCURBTYPE

(NOTE F)

ELECTRICAL

MANUFACTURERMODEL

NUMBER REMARKSVOLTAGE PHASES MCA MOCP

DISCONNECTCONTROLLER/

STARTER

BY(NOTE A)

TYPE(NOTE B)

BY(NOTE A)

TYPE(NOTE C)

MERV8 NOTE 5 460 3 148.8 175 MFR NF MFR VFD TRANE SFH NOTE 2, 3, 6, 7

MERV8 MFR 460 3 21.6 25 MFR NF MFR FV TRANE YHC NOTE 6

BOILER SCHEDULE

NOTES: 1. EQUIPMENT PROVIDER TO PROVIDE WITH GAS PRESSURE REGULATOR BASED ON INCOMING GAS PRESSURE OF 2 PSI. ROUTE VENT FOR GAS PRESSURE REGULATING VALVE TO THE EXTERIOR.ROUTE AND SIZE VENT PER MANUFACTURER'S RECOMMENDATIONS.

TAGNAME FUEL

GASPRESSURE(IN. W.C.)

TURNDOWNRATIO

INPUTMBH

OUTPUTMBH MEDIA EWT °F LWT °F

ELECTRICAL

MANUFACTURER MODEL REMARKSAMPS VOLTAGE PHASE

DISCONNECT CONTROLLER/STARTER BY

(NOTE A)BY

(NOTE A)TYPE

(NOTE B)BLR-1 NAT. GAS 12 5:1 210 193 WATER 120 140 5 115 1 MFR NF MFR BURNHAM ALP210 NOTE 1

BLR-2 NAT. GAS 12 5:1 210 193 WATER 120 140 5 115 1 MFR NF MFR BURNHAM ALP210 NOTE 1

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

M502

MECHANICALSCHEDULES

14215000

CD SET 02/28/14

LONGMONT, CO

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

Page 3: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

EF-1. REFER TO 2/M301 FOR ROOFMOUNTED FAN (MEMBRANE ROOF)DETAIL (TYP. 5)

VTR

RD-14" (2,460)

RD-14" (1,705)

VTR

3

3

EF-2 REFER TO 4/M302 FORROOF MOUNTED EXHAUSTFAN WITH DRIP PAN DETAIL.

EF-6

VTR. REFER TO 6/P301FOR VENT THROUGHROOF DETAIL (TYP.)

2

2

RTU-2

2

ANTE ROOM CONDENSING

UNIT SHOWN FOR REFERENCE

ONLY.

RD-14" (1,705)RD-1

6" (4,485)

RD-16" (4,485)REFER TO 3/P301 FORROOF DRAIN DETAIL.(TYP.)

OFFSET DUCTWORK IN CURBTO CONNECT ROOFPENETRATION TO RA OPENINGIN BOTTOM OF RTU.

MAINTENANCECLEARANCE (TYP.)

RTU-1. REFER TO1/M301 FOR ROOFTOPUNIT DETAIL (TYP.2)

RD-14" (2,460)

RD-24" (1,705)

RD-26" (4,485)

RD-24" (2,460)

RD-24" (2,460)

RD-26" (4,485)

RD-24" (1,705)

RD-1

EF-4

EF-3

4

ROUTE 1 1/4"COND TO RD-1

CONDENSING UNITS SHOWN

FOR REFERENCE ONLY.

RTU FURNISHEDBY TRANE

92x40 DUCT CONNECTION TOBOTTOM OF RTU-1. 36x56DUCT THROUGH ROOF.

OA

EA

1"G-2

32x14

3/4" COND. REFER TO4/M301 FORCONDENSATE TRAP(DRAW-THROUGH)DETAIL (TYP.)

4ROUTE 3/4"COND TO RD-1

GAS REGULATOR GR-2AND SHUTOFF VALVEFURNISHED ANDINSTALLED BY P.C.

PROVIDE STAINLESS STEELPIPE STRAP TO SECURECONDENSATE PIPE TO LASTSUPPORT BEFORETERMINATION. (TYP. ALL)

2'-4

"

6'-9"

3'-1

0"

68X28 DUCT DOWN. 16'-8"

4

ROUTE 1 1/4"COND TO RD-1

A B B.7 C.9 D E.5 G G.6 H

1

1.2

3.3

2

2.2

2.3

2.7

2.8

3

3.8

4

KA.5 B.9 C E F G.9 J

3.2

1.8

1.4

1.5

2.4

2.6

3.5

3.6

EF-5

1

VTR

GAS REGULATOR GR-1AND SHUTOFF VALVEFURNISHED ANDINSTALLED BY P.C.

1"G-2

1/8" = 1'-0"1ROOF PLAN - MECHANICAL - HVAC & PLUMBING

1. 4" AIR INTAKE AND 4" FLUE EXHAUST SERVINGWATER HEATER. COORDINATE EXACT SIZE,MATERIAL, AND INSTALLATION WITHMANUFACTURER.

2. CONDENSING UNIT PROVIDED AND INSTALLED BYG.C.

3. 4" AIR INTAKE AND 4" FLUE EXHAUST SERVINGBOILER. COORDINATE EXACT SIZE, MATERIAL,AND INSTALLATION WITH MANUFACTURER.

4. FOAM BLOCKS SHALL BE USED TO SUPPORTROOF PIPING PER SPECIFICATION SECTION 22 0529. WOOD SUPPORT BLOCKS WILL NOT BEALLOWED.

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

M121

ROOF PLAN -MECHANICAL - HVAC &PLUMBING

14215000

CD SET 02/28/14

LONGMONT, CO

NO R HT

KEYNOTES #

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14EF­01

EF­06

EF­04

EF­05

EF­03

EF­02

RTU­01

RTU­02

Page 4: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

REF.

DW

REF.

DW REF.T

T

TT

TT T

T

T

TT

T

T

P

TT

T S

T

T

TH

T

T

S

T

5 14x14 UPTO EF-2

RG-214x14(TYP.4)

REFER TO 3/M301 FORTERMINAL AIR BOXDETAIL (TYP.)

105

LD-3

10/270(TYP.3)

101

LD-1

10/180(TYP. 2)

RG-1. REFER TO 5/M301FOR CEILING RETURNGRILL DETAIL. (TYP.)

140

SG-1

18x12/675

10ø

LD-2

10/250

141

RG-216x10

18x12 TD

REFER TO 7/M301 FORTRANSFER DUCT DETAIL.

(TYP.)

142

4

EG-1

10/320

CD-1

6/100

CD-1

6/85

12x12 UPTO EF-1

24x12 TD

24x12 TD

10x10 UPTO EF-5

18x18 UPTO EF-4

34x16 TD

10x10 UPTO EF-3

RG-212x8

RG-224x14(TYP.2)BOTTOM OF GRILL SHALL BE6" A.F.F. TOP OF CHASESHALL BE OPEN TO PLENUM.

LD-3

10/300(TYP.6)

CD-1

8/175

139

CD-1

10/295

SG-1

18x10/500(TYP.4)

LOCATE BETWEEN WALLSCONCES BELOW (TYP.)COORDINATE EXACTLOCATION HEIGHT WITHARCHITECT/OWNER.

INSTALL BOTTOM OF SG-1MAX. 12" A.F.F. (TYP. 2)

SG-1

6x6/55

EG-1

8/225EG-1

8/225

SG-2

6x6/50

EG-2

6x6/100

CD-1

8/175

CD-1

6/85

109

CD-1

8/245

REFER TO 6/M301 FORDIFFUSER CONNECTIONDETAIL (TYP.)

CD-1

8/175

RG-26x6

THIS AREA IS RESERVED FOR

LCD TOUCHSCREEN BUILDING

CONTROL UNITS. COORDINATE

EXACT LOCATION WITH ELECTRICAL

CONTRACTOR.

115A

34x22

6

24x18

PROVIDE BACK TOBACK 68x14 ELBOWSWITH TURNING VANES.68x28 UP TORTU-1

135B

36x56 UPTO RTU-1

50x64

16ø

HANG ALL MAIN DUCTRUNS AND VAV BOXES(FAN POWERED AND NONFAN POWERED) FROMSTRUCTURE AND NOTFROM ROOF DECK.

12ø

10x12

6x6

12x12

12x10

12ø

10x10

SG-1

16x6/270(TYP. 2)

20x16

142

140

143

101 109

110

115B

139

135A

135B

115A

INSTALL BOTTOM OF RG-2MAX. 12" A.F.F IN FREEZERENCLOSURE. (TYP.4)

32x14 UPTO RTU-2

10x10 UPTO EF-6

8x8

8x8 UP

OVERHEADDOOR

2

RG-218x10

18ø

20x12

CD-210/250

10ø

10ø

12ø 12ø

22x18

12ø

RTU-2 TSTAT ANDHUMIDISTAT PROVIDEDBY TRANE. LOCATENEXT TO YOKOGAWASENSOR.

105

VAV BOX TSTATSPROVIDED BYTRANE (TYP)

FAN POWERED VAV BOXESAND SINGLE DUCT VAVBOXES FURNISHED BYTRANE (TYP)

1

LD-4

10/300

CD-1

8/190(TYP.2)

LD-3

12/370(TYP. 6)

LD-4

12/370

6

CABINET HEATER

BY E.C.

CABINET HEATER TO BE

PROVIDED BY E.C. LOCATIONS

SHOWN FOR REFERENCE ONLY.

16ø

14ø

18ø

PROVIDE A 12" BACKDRAFTDAMPER AT WALLPENETRATION. RUSKIN-BDR2 OR APPROVED EQUAL.

12ø12ø

14ø

8ø8ø

10ø

1

44x22

18ø

8

146 A+B

7

10ø

10ø

146A

146B

PROVIDE BACK SUPPORTTO DIFFUSER FROMBUILDING STRUCTURE TOALIGN DIFFUSERSCENTERED IN 4x4 TILES.(TYP. 12)

RG-1

RG-1

RG-1

RG-1

RG-1

RG-1

RG-1

RG-1 RG-1

RG-1

RG-1

RG-1RG-1

RG-1

RG-1

RG-1

CD-3

12/430(TYP.6)

CD-3

12/500(TYP.6)

10ø

20ø18ø

20ø

RG-1

RG-1RG-114ø

20ø

16ø

18x20

10ø

EG-2

6x6/40

EG-1

6/45RG-26x6

10x10

RG-216X6(TYP.2)

12" A.F.F.

137

34x16 TD

LD-3

8/260

18x12

10ø8ø

EG-1

8/175

EG-1

8/175

EG-2

10x6/125

120

121

118 EF-4

121

116

129

RG-1

RG-1

RG-1

SG-1

18x10/430(TYP.7)

UH-1

12x8

RG-1

123

LD-3

10/300

20x12

116

18x10

SG-1

18x10/535

CD-1

6/70

129

CD-1

6/50

12ø

CD-1

6/100

CD-1

6/125

CD-1

6/125

120

12ø

SG-1

6x6/150

10ø

16x10

118

12x12

14x14LD-2

10/225(TYP.4)

EG-1

16/555(TYP.2)

LD-3

10/265(TYP. 2)

LD-3

8/260

LD-3

8/260

123

10x10

14ø

14ø

22ø

RG-28x8

135A

115B

CD-1

6/160

14x12

24x14

LD-2

10/220

6x6

22x18

137

1

M131

18x10

9

UH-1

OVERHEAD DOOR CONTACTSWITCH TO CONTROL UNIT HEATER,REFER TO M603 FOR ADDITIONALINFORMATION.

TOP OF THE UNIT HEATERELEVATION SHALL BE MOUNTEDTIGHT TO BOTTOM OF JOIST.

10ø

10ø

18ø

16ø

18x18

10ø

12ø

9

9

110

16ø

143

18x18

10x10

12x12 TD

RG-1

8

8

8

8

8

8

16x12 TD

A B B.7 C.9 D E.5 G G.6 H

1

1.2

3.3

2

2.2

2.3

2.7

2.8

3

3.8

4

K

SUPERVISEDPLAY

101

MEN

104

WOMEN

105

CLOSET

107

EXAM

109

EXAM

110

CLOSET

112

EXAM

113

EXAM

114

TOILET

102

CONFERENCE

143

CENTERMANAGER

142

TELE / DATA/ MECH

140

COPY ROOM

136

CENTERSUPERVISOR

139

ASSISTANTMANAGER

141

QUALITYMANAGER

137

CORRIDOR

144

HALL

111

PLASMAPROCESSING

150

CORRIDOR

138

RECEPTION

146

EDQ

145

EDQ

108

WAITING

148

DONORFLOOR

115

DONORPROCESSING

147

DONORFLOOR

135

HOST

149

HALL

106

VESTIBULE

100

FREEZER

132

ANTE ROOM

131

TRAININGSUPERVISOR

116

ISOTRAINING

117

BREAKROOM

118

LAB COATS

130

LOCKERROOM

129

MEN

126

WOMEN

127

CUSTODIAN

125

CORRIDOR

128

CORRIDOR

119

CORRIDOR

124

ELECTRICAL

123

BOILERROOM

122

BIOHAZARD

121

UTILITYROOM

120

PACKING

133

A.5 B.9 C E F G.9 J

3.2

1.8

3

EG-1

10/275

10x10

10ø

SG-1

8x8/185

10ø

LD-2

10/245

10ø

141

1/8" = 1'-0"1FIRST FLOOR PLAN - MECHANICAL - HVAC

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

M111

FIRST FLOOR PLAN -MECHANICAL - HVAC

14215000

CD SET 02/28/14

LONGMONT, CO

NO R HT

1. PROVIDE 50x64 OPENING IN TOP OF 74x18DUCT.

2. PROVIDE 30x28 OPENING IN TOP OF 32x14DUCT.

3. 4" AIR INTAKE AND 4" FLUE EXHAUST SERVINGWATER HEATER UP THROUGH ROOF.

4. DUCT STATIC PRESSURE SENSOR. TIEDIRECTLY INTO RTU-1 VFD.

5. PROVIDE MANUAL DAMPER TO PROVIDE AMEANS OF BALANCING EXHAUST FAN TOSCHEDULED AIRFLOW RATE.

6. PROVIDE SOUND PLENUM FOR SA AND RAMAINS FROM RTU. REFER TO 5/M302 FORSOUND PLENUM DETAIL.

7. VAV 146A AND 146B CONTROLLEDSIMUTANEOUSLY FROM TSTAT 146.

8. FLEX DUCT SHALL PENETRATE WALL ABOVECEILING TO ALLOW RETURN AIR BACK TOASSOCIATED PATH. TYPICAL FOR ALL RETURNGRILLES WITH FLEX DUCT.

9. POSITION THIS TSTAT NEXT TO YOKOGAWASENSOR.

KEYNOTES #GENERAL MECHANICAL NOTES1. ALL DUCTWORK RUNOUTS TO DIFFUSERS,

GRILLES, AND TABS SHALL BE SAME AS NECKSIZE UNLESS NOTED OTHERWISE.

2. REFER TO 1/M302, 2/M302 AND 3/M302 FORGENERAL DUCT CONSTRUCTION DETAILS.

3. HANG ALL MAIN DUCT RUNS AND VAV BOXES(FAN POWERED AND NON FAN POWERED)FROM STRUCTURE AND NOT FROM ROOF DECK.

4. MAXIMUM FLEX DUCT LENGTH SHALL NOTEXCEED 6'-0" TO DIFFUSERS AND 3'-0" TO TABS.

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

EF­01 RTU­02

EF­02

EF­03

EF­05

EF­04

EF­06

RTU­01

118116

121

120

129

123135B135A

139

137141

140

146A

146B

110109

105

115A115B

1

2

34

567

1

1

2

3 4

5

1

2

3

1 2 3 4 5

12

1

1

2

3

1

2

345

6 7

123456

7

1 2

1

2

3

12

12345

1

2

3

4

1

2341

234

1

2

1

2

1

112

1

12

1

2 3 4 5 6 7

1

2

3 4 5

67

1

101

142

143

Page 5: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

REF.

DW

REF.

DW REF.

101

105

109

115A

135B

142

141

140

139

3/4"HWS 3/4"HWR

1"HWS 1"HWR

1"HWS 1"HWR

REFER TO 2/M131FOR HEATINGWATER FLOWDIAGRAM.

FAN POWERED VAVBOXES AND SINGLE DUCTVAV BOXES FURNISHEDBY TRANE (TYP.)

REFER TO 2/M131 FORREQUIRED VALVING ATEACH TERMINAL UNIT(TYP.)

146A

146B

3/4"HWR 3/4"HWS

3/4"HWS

3/4"HWR

137

3/4"HWR

3/4"HWS

1 1/2"HWS 1 1/2"HWR

3/4"HWR

3/4"HWS

3/4"HWR

3/4"HWS

1"HWS 1"HWR

1"HWR 1"HWS

1 1/2"HWR

1 1/2"HWS

1"H

WS

1"H

WR

2"HWR

3/4"HWS

3/4"HWR123

129

120

121

116

118

UH-1

2"HWR 2"HWS

3/4"HWS 3/4"HWR

3/4"HWS 3/4"HWR

3/4"HWR 3/4"HWS

3/4"HWR 3/4"HWS

3/4"HWS

3/4"HWS 3/4"HWR

135A

115B

3/4" HWS SERVINGBOX 105.

3/4" HWR SERVINGBOX 105.

M131

1

2"HWS

1"HWS 1"HWR

3/4"HWR 3/4"HWS

1"HWR

1"HWS

1"HWR 1"HWS

2"HWS

2"HWR 1"HWS 1"HWR

2"HWR

2"HWS

1"HWR

1"HWS

110

143

3/4"HWR

3/4"HWS

A B B.7 C.9 D E.5 G G.6 H

1

1.2

3.3

2

2.2

2.3

2.7

2.8

3

3.8

4

K

SUPERVISEDPLAY

101

MEN

104

WOMEN

105

CLOSET

107

EXAM

109

EXAM

110

CLOSET

112

EXAM

113

EXAM

114

TOILET

102

CONFERENCE

143

CENTERMANAGER

142

TELE / DATA/ MECH

140

COPY ROOM

136

CENTERSUPERVISOR

139

ASSISTANTMANAGER

141

QUALITYMANAGER

137

CORRIDOR

144

HALL

111

PLASMAPROCESSING

150

CORRIDOR

138

RECEPTION

146

EDQ

145

EDQ

108

WAITING

148

DONORFLOOR

115

DONORPROCESSING

147

DONORFLOOR

135

HOST

149

HALL

106

VESTIBULE

100

FREEZER

132

ANTE ROOM

131

TRAININGSUPERVISOR

116

ISOTRAINING

117

BREAKROOM

118

LAB COATS

130

LOCKERROOM

129

MEN

126

WOMEN

127

CUSTODIAN

125

CORRIDOR

128

CORRIDOR

119

CORRIDOR

124

ELECTRICAL

123

BOILERROOM

122

BIOHAZARD

121

UTILITYROOM

120

PACKING

133

A.5 B.9 C E F G.9 J

3.2

1.8

3/4"HWR 3/4"HWS 3/4"HWR

3/4" HWS SERVINGBOX 110.

3/4" HWR SERVINGBOX 110.

3/4"HWR

3/4"HWS

1/8" = 1'-0"1FIRST FLOOR PLAN - MECHANICAL - PIPING

GENERAL MECHANICAL NOTES1. ALL BRANCH PIPING TO TABS SHALL BE 3/4"

UNLESS OTHERWISE NOTED.2. SHUTOFF VALVES SHOWN ARE IN ADDITION TO

SHUTOFF VALVES AT EACH COIL.3. REFER TO 2/P301 FOR PIPE THROUGH NON-FIRE

RATED WALL DETAILS.4. REFER TO 1/M604 FOR HEATING WATER SYSTEM

CONTROL DIAGRAM.5. PIPING AND EQUIPMENT SHALL NOT BE

SUPPORTED OR ATTACHED TO ROOF DECK. ALLCONNECTIONS SHALL BE MADE TO STRUCTUREOR CONTRACTOR PROVIDED SUPPORTS.

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

M112

FIRST FLOOR PLAN -MECHANICAL - PIPING

14215000

CD SET 02/28/14

LONGMONT, CO

NO R HT

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

Page 6: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

BLR-1

3

11

TYPICAL TAB/UNIT HEATER

PUMP HWP-2(38 GPM)

PUMP HWP-1(38 GPM)

6

3/4" NPW

BY P.C. BY H.C.

FLUE

F

2 "HWS

2"HWR

BLR-2

3

FLUE

F

2" HWR (TYP.)

2" HWS (TYP.)

MANUAL AIR VENT. INSTALL AT ALL HIGHPOINTS OF SYSTEM. PIPE TO ANACCESSIBLE LOCATION.

2" HWS

RELIEF VALVE.SET AT 30 PSIG.(TYP.)

BALANCETO 19 GPM(TYP.)

ROUTE CONDENSATE TONEAREST FLOOR DRAIN.PROVIDE CONDENSATENEUTRALIZER KIT IN DRAINLINE. (TYP.)

FLOW SWITCH. PROVIDED BYBOILER MANUFACTURER.(TYP.)

BFP-1 (HEATING WATERMAKE-UP). REFER TO2/P121 FOR EXACTLOCATION.

10

2

4

ROUTE TO NEARESTFLOOR DRAIN. (TYP.)

3/4" RELIEF VALVESET TO 25 PSIG.

SAME SIZE AS AIRSEPARATOR OUTLET

5

AIR SEPARATOR. SAMESIZE AS PIPING. SEE23 21 00 FORREQUIREMENTS.

8

7

CONNECT TO SIDE OF MAIN (NOT TOP ORBOTTOM) TO AVOID AIR OR DIRTENTERING PIPING

3/4

"HW

R

3/4

"HW

S

DRAIN VALVE WITH 3/4" MALEHOSE THREAD AND CAP.

9 11

SAMPLE PORT. PROVIDEWITH 3/4" MALE HOSETHREAD AND CAP.

2" HWS

6 2" HWS

2" HWS

DRAIN VALVE WITH 3/4" MALE HOSETHREAD AND CAP. INSTALL AT LOWPOINTS IN SYSTEM (TYP.)

2"HWR

2"HWS

BOILER ROOM FIRST FLOOR

2" HWS

PROVIDE HOUSEKEEPINGPADS PER SPECIFICATIONSECTION 23 05 29. (TYP)

LOW WATER CUT OFF PROBE.PROVIDED BY BOILERMANUFACTURER. (TYP.)

CONTRACTORS OPTION:PROVIDE AUTOMATIC FLOWCONTROL VALVE IN LIEU OF TWOMANUAL BALANCING VALVES.

EXPANSION TANK

T T

T

T

NEUTRALIZATION TANK

ROUTE CONDENSATE TONEAREST FLOOR DRAIN.

2" HWS

NEW DUCT

FLEXIBLE DUCT

MANUAL VOLUME DAMPER

DUCT DOWN

DUCT UP

SUPPLY/OUTSIDE AIR DUCT SECTION

RETURN AIR DUCT SECTION

EXHAUST/RELIEF AIR DUCT SECTION

CD-16/115

AIR TERMINAL PROPERTIES SYMBOLNECK SIZE/CFM

###

TERMINAL AIR BOX W/REHEAT COIL (REFERTO SCHEDULE)

HUMIDSTAT SENSOR (SUBSCRIPTINDICATES WHAT SENSOR IS SERVING)

H

MECHANICAL SYMBOLS LISTSYMBOL: DESCRIPTION:

101

THERMOSTAT SENSOR (SUBSCRIPTINDICATES WHAT SENSOR IS SERVING)

T101

ELECTRICAL SWITCH (SUBSCRIPTINDICATES WHAT SWITCH IS SERVING)

SEF-8

ABOVE FINISHED FLOORA.F.F.

PIPE CAP

PIPE DOWN

PIPE UP OR UP/DOWN

DIRECTION OF FLOW IN PIPE

UNION/FLANGE

HEATING WATER RETURNHWR

HWS HEATING WATER SUPPLY

###

TERMINAL AIR BOX W/O REHEAT COIL (REFERTO SCHEDULE)

STATIC PRESSURE SENSORP

MECHANICAL SYMBOLS LISTSYMBOL: DESCRIPTION:

SHUTOFF VALVE NORMALLY OPEN

SHUTOFF VALVE NORMALLY CLOSED

MANUAL BALANCING VALVE (NO. INDICATES GPM)0.5

CONTROL VALVE (THREE-WAY)

CHECK VALVE

SAFETY/RELIEF VALVE

"WYE" - STRAINER W/SHUTOFF VALVEAND HOSE CONNECTION WITH CAP

REDUCER - REFERENCE SPECIFICATIONFOR CONCENTRIC/ECCENTRIC AND FOT/FOB

METERM

PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P

AUTOMATIC AIR VENT

PRESSURE REDUCING VALVE (LIQUID/GAS)

P/T PORT

MANUAL AIR VENT

DRAIN VALVE WITH HOSE CONNECTION AND CAP

TEMPERATURE SENSOR WITH WELLT

THERMOMETER WITH WELL (DIAL TYPE)

FLOW SWITCHF

T

OA OUTDOOR AIR

EA EXHAUST AIR

PARALLEL FAN POWERED AIR BOXW/REHEAT COIL (REFER TO SCHEDULE)###

EXPANSION TANK

BYPASS FEEDER

SEE 2/M131 FORPIPING NOT SHOWNON THIS PLAN

ELECTRICAL

DISCONNECTS AND

OTHER ELECTRICAL

EQUIPMENT.

M

ELEVATED METERAND PRESSUREREDUCING VALVEASSEMBLY.

12

NEUTRALIZEDCONDENSATETO FLOOR DRAIN

HEATING WATERMAKE-UP FROM BFPIN UTILITY ROOM

12

FLOOR DRAIN(TYP.)

HWP-1 AND HWP-2AND ASSOCIATEDVALVING STACKEDON THIS WALL. BLR-2

ELEVATED AIR SEPARATOR

NEUTRALIZATION TANK

BLR-1

THIS AREA IS RESERVED FORLCD TOUCHSCREEN BUILDINGCONTROL UNITS. COORDINATEEXACT LOCATION WITH TRANEAND ELECTRICAL CONTRACTOR.

2"HWS

2"HWR

2"HWR

REFER TO 2/P121FOR CONTINUATION.

2"HWS

2.7

2.8

K

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

M131

ENLARGED PLAN -MECHANICAL - PIPINGAND FLOW DIAGRAM

14215000

CD SET 02/28/14

LONGMONT, CO

NO SCALE2HEATING WATER FLOW DIAGRAM

KEYNOTES

1. PROVIDE 1 1/2" OR LARGER CONNECTION FOR CONNECTION OF FIRE HOSESFOR FLUSHING AND CLEANING OF SYSTEM.

2. 3/4" PRESSURE REDUCING VALVE. SEE SPECIFICATION SECTION 23 21 00 FORADDITIONAL REQUIREMENTS. FIELD SET TO 15 PSI.

3. INSTALL SAFETY RELIEF VALVE PROVIDED BY BOILER MANUFACTURER. PIPELINE SIZE TO NEAREST FLOOR DRAIN.

4. 3/4" NORMALLY CLOSED SHUTOFF VALVE FOR QUICKLY FILLING AND IN CASE OFFAILURE OF PRESSURE REDUCING VALVE.

5. HIGH CAPACITY AUTOMATIC AIR VENT WITH PIPE LINE SIZE TO DRAIN. SEESPECIFICATION SECTION 23 21 00 FOR ADDITIONAL REQUIREMENTS.

6. PRESSURE GAUGE WITH SNUBBER PER SPECIFICATION SECTION 23 09 13.INSTALL WITH MOUNTING ON WALL, STAND, OR VIBRATION-FREE PIPE ABOVEBRACKET PUMP FLEXIBLE CONNECTOR. INSTALL FLEXIBLE COPPER TUBING TOPIPING CONNECTION TO AVOID VIBRATION DAMAGE TO THE GAUGE. PREFERREDCONNECTION LOCATIONS ARE: (1) JUST UPSTREAM OF STRAINER. (2) GAUGETAPPING ON PUMP INLET FLANGE. (3) GAUGE TAPPING ON PUMP OUTLETFLANGE.

7. VALVE SHALL BE LOCKABLE IN OPEN POSITION.8. SIZE PER BLADDER TANK MANUFACTURER'S RECOMMENDATIONS BUT NOT

SMALLER THAN CONNECTION TO TANK.9. BLADDER TYPE EXPANSION TANK WITH 15 PSI INITIAL CHARGE, MINIMUM 5

GALLONS ACCEPTANCE AND 20 GALLONS TOTAL VOLUME. SEE SPECIFICATION23 21 00 FOR ADDITIONAL REQUIREMENTS.

10. 3/4" MAKE-UP WATER METER TO DETECT LEAKS.11. BYPASS (POT) FEEDER. SEE SPECIFICATION SECTION 23 25 00 FOR ADDITIONAL

REQUIREMENTS. MOUNT WITH BOTTOM APPROXIMATELY 24" ABOVE FLOOR.12. 4" AIR INTAKE AND 4" FLUE EXHAUST SERVING BOILER UP THROUGH ROOF.

#

NO R HT

1/2" = 1'-0"1ENLARGED PLAN - MECHANICAL - PIPING

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

Page 7: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

ROOFTOP UNIT

UNION

DIRT LEG

SHUTOFF VALVE.

GAS PIPING

SEAL AROUND CURB INSIDEPERIMETER WITH SILICONESEALANT.

1" RIGID GLASS FIBERBOARD (3 LB. DENSITY)

DUCT OPENING (MAX. 1" GAP) FILLVOID WITH FIBERGLASS INSULATIONAND SEAL WITH BACKER ROD ANDSILICONE SEALANT

NOTES:

1. ALL ROOF FLASHING SHALL BE PER ROOF MANUFACTURER'S RECOMMENDATIONS.2. ROOF CURB SHALL BE INSTALLED PER ROOF CURB MANUFACTURER'S

RECOMMENDATIONS.3. COORDINATE ALL ROOF PENETRATIONS WITH ROOFING CONTRACTOR TO MAINTAIN

ROOFING SYSTEM WARRANTY.4. REFER TO 5/M302 FOR SOUND PLENUM DETAIL.

2 LAYERS OF 5/8" FIRE RATEDGYPSUM WALL BOARD WITHSTAGGERED TAPE JOINTS.

INSULATED ROOF CURB PROVIDED BY M.C.

FLASHING FURNISHEDAND INSTALLED BY G.C.

G.C. SHALL SECUREFLASHING TO CURBNAILER STRIP. (TYP.)

1/8" NPT TESTPLUG

GASKET MATERIALFURNISHED WITHROOF CURB.

ROOF CURB FURNISHEDWITH ROOFTOP UNIT.

METAL ROOF DECK PROVIDEDAND INSTALLED BY G.C.

ROOF INSULATION PROVIDEDAND INSTALLED BY G.C.

EPDM ROOF MEMBRANEBY G.C. SECURE TORIGID INSULATION.

2"X2" WOOD NAILERFURNISHED WITHROOF CURB.

2 LAYERS OF 5/8" FIRERATED GYPSUM WALLBOARD

FLEXIBLE DUCT CONNECTIONON SUPPLY AND RETURNDUCTWORK.

6"

MIN

.

6"MIN.

12

" MIN

30

" M

IN (

RT

U-1

)

18

" M

IN (

RT

U-2

)

ROOF TOP UNIT FURNISHEDBY TRANE (TYP.)

CONDENSATE PIPEOUTLET. REFER TO4/M301 FOR DETAIL.

NOTE 4

FAN

FACTORY SUPPLIED BACKDRAFT DAMPER.MOTORIZED OR GRAVITY AS SCHEDULED.

DUCTWORK

NOTES:

1. ALL ROOF FLASHING SHALL BE PER ROOFING MANUFACTURERS RECOMMENDATIONS.2. COORDINATE ROOF PENETRATION WITH ROOFING CONTRACTOR TO MAINTAIN ROOFING

SYSTEM WARRANTY

FLASH ROOF MEMBRANETO CURB. (NOTE 1)

PREFABRICATED ROOFCURBFURN. WITH FAN. (WITH WOODNAILER AND INSULATED LINER.)

CADMIUM PLATED LAG SCREWS.PER MANUFACTURERSRECOMMENDATIONS

FRAME, ROOF, & ROOFING BYGENERAL CONTRACTOR.

18" ABOVE TOP OF ROOF INSULATION.

.

GFI OUTLET PROVIDED AND INSTALLED BY E.C.REFER TO ELECTRICAL PLANS ADDITIONALINFORMATION AND APPROPRIATE QUANTITY.

NOTES:1. APPLIES TO TERMINAL AIR BOXES WITH ROUND INLETS AND RECTANGULAR

OUTLETS.2. DUCT LEADING TO INLET MUST BE STRAIGHT FOR 1.5 DIAMETER UPSTREAM OF

INLET.

NYLON TIE WRAP, TWO REQUIREDFOR EACH END OF FLEXIBLE DUCT(TOTAL 4). INSTALL ONE TIE WRAPTO SECURE THE INNER LINER ANDONE TO SECURE THE OUTER SHELL.(TYP.)

PRE-MANUFACTURED CONICALTAKE-OFF WITH SELF-ADHESIVENEOPRENE GASKET (EQUAL TOSHEET METAL CONNECTORSCONICAL E-Z TAP)

FASTEN WITH SELF-TAPPINGSHEETMETAL SCREWS (MIN. 4)

CUT DUCT OPENING TO MATCHLARGER TAKEOFF DIAMETER

INSULATED GALVANIZED SHEETMETAL DUCT (SEE SPECIFICATIONSECTION 23 31 00 - DUCTWORK)

SECTION OF 26 GA. GALVANIZEDSHEET METAL DUCT. SAMEDIAMETER AS FLEX DUCT.

AIR FLOWTERMINAL AIR BOX

RECTANGULAR INSULATEDDUCT (SEE SPECIFICATIONSECTION 23 31 00 - DUCTWORK)

INSULATEDFLEX DUCT

INSULATED TRANSITION

REHEAT COIL, INSULATE PERSPECIFICATIONS

3' MAX.

6" MIN.

. D

TRIM INSIDE FLEX DUCT AT THISPOINT. SLIP & DRIVE CONNECTION

HANG ALL MAIN DUCTRUNS AND VAVBOXES (FANPOWERED AND NONFAN POWERED)FROM STRUCTUREAND NOT FROMROOF DECKING.

TERMINAL AIR BOX ANDREHEAT COIL FURNISHED BYTRANE (TYP)

H”

CLEANOUT PLUG (TYP.)

ROUTE TO ROOF DRAIN

FULL SIZE CONDENSATEDRAIN, CONNECT TO DRAINPAN AS RECOMMENDED BYMANUFACTURER.

4"

51

/64

" 2"

CEILING

STRUCTURE

PROVIDE 14"ø FLEXIBLEDUCT WITH A MINIMUMLENGTH OF 3'-0".

TRIM STRAPS AFTERTIGHTENING

SUSPEND ELBOWWITH TIE

DRAW BANDS SNUG,WITHOUT CRUSHINGFLEXIBLE DUCT

PROVIDE RADIUSFORMING ELBOW

RETURN GRILLE

1X DUCT DIAMETERMINIMUM STRAIGHTDUCT.

END OF FLEX DUCTSUPPORTED BY WALLOR STRUCTURE.

PROVIDE HANGER ATEND OF FLEX DUCT

NOTES:

1. "FLEXFLOW" ELBOW IS AN ACCEPTABLE PRODUCT FOR RADIUS FORMINGELBOW (1-800-459-4822).

SHEETMETAL ELBOW

NOTES:

1. TO ATTACH FLEX DUCT TO THE HARD DUCT, TAPE THE INNER LINER TO THEHARD DUCT THEN ATTACH WITH TWO NYLON TIE WRAPS; ONE FOR THEINNER LINER AND ONE FOR THE OUTER SHELL. FOLD THE OUTER SHELLINSIDE ITSELF SO IT HAS NEAT EDGES PRIOR TO TIE WRAPPING.

2. "FLEXFLOW" ELBOW IS AN ACCEPTABLE ALTERNATE TO SHEET METALELBOWS.

R = DUCT DIA.

FLEXIBLE DUCT

INSULATION

CEILING

STRUCTURE

DIFFUSER

6' MAX

DUCT LINER (REFERTO SECTION 23 31 00 -DUCTWORK)

REFER TODRAWINGFOR SIZE

ROOF

CEILING

WALL

X

6".

1/2

x 6".

KEEP DUCT AS HIGHAS POSSIBLE. DO NOTRESTRICT AIR INLET.

NO SCALE1ROOFTOP UNIT DETAIL

NO SCALE2ROOF MOUNTED FAN (MEMBRANE ROOF)

NO SCALE3TERMINAL AIR BOX DETAIL

NO SCALE4CONDENSATE TRAP DETAIL (DRAW-THROUGH)

NO SCALE5CEILING RETURN GRILLE

NO SCALE6DIFFUSER CONNECTION DETAIL

NO SCALE7TRANSFER DUCT DETAIL (ENDS UP)

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

M301

MECHANICAL DETAILS

14215000

CD SET 02/28/14

LONGMONT, CO

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

Page 8: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

R

R

W

H

Θ

Θ

W

H

H

W W

H

Θ

NOTES:

1. BEAD, CROSSBREAK, AND REINFORCE FLAT SURFACESAS IN STRAIGHT DUCT.

2. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

RADIUS ELBOW

SQUARE THROAT ELBOWWITH VANES

RADIUS ELBOWWITH VANES

MITERED ELBOW

CENTERLINE R=3W/2 UNLESSOTHERWISE SPECIFIED Θ ISNOT RESTRICTED TO 90°.

REFER TO SMACNA HVAC SYSTEMDESIGN, THIRD EDITION, TABLE 14-10,FITTING FOR VANE SPACING. R/WSHALL BE 0.5 UNLESS NOTEDOTHERWISE.

D1>D2

45 DEGREE

BUTT FLANGESTRAIGHT TAP

ENTRY Θ 45°45 DEGREE CONICAL

CLINCH LOCK

CORNER FILLERPIECE OR USEGASKET (TYP.)

45 DEGREE LEAD IN

NOTES:

1. DO NOT USE CONNECTIONS WITH SCOOPS.2. FIT ALL CONNECTIONS TO AVOID VISIBLE OPENINGS AND

SECURE THEM SUITABLY FOR THE PRESSURE CLASS.3. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

DOVETAIL JOINT

FLANGED

NOTE: STRAIGHT TAP WITH BUTTFLANGE FOR BRANCH AND TEECONNECTION IN RECTANGULAR DUCTSUNDER 1" PRESSURE CLASS ONLY.

ENTRY Θ 45°

D1

W

L

Θ

D2

R

R

JOINTS AT CONVENIENT

JOINTS AT CONVENIENT

R

R

2ND INTERVAL

1ST INTERVAL

INTERMEDIATEREINFORCEMENT

NOTES:

1. 'R' IS AN ALLOWABLE REINFORCEMENT INTERVAL.2. TOP AND BOTTOM JOINTS MUST QUALIFY AS REINFORCEMENT.3. DUCT SIZES 19" WIDE AND LARGER WHICH HAVE MORE THAN 10 SQ. FT. OF

UNBRACED PANEL SHALL BE BEADED OR CROSS BROKEN UNLESS DUCT WILLHAVE INSULATION COVERING OR ACOUSTICAL LINER. THIS REQUIREMENT ISAPPLICABLE TO 20 GAUGE OR LESS THICKNESS AND 3" W.G. OR LESS.

4. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

INTERMEDIATEREINFORCEMENT

UNREINFORCED SIDE

INTERVALS NEED NOTNECESSARILY COINCIDEON ADJACENT SIDES

JOINT

JOINT

JOINT

JOINT

DUCT REINFORCED ON TWO SIDES

DUCT REINFORCED ON ALL SIDES

HANG ALL MAIN DUCTRUNS AND VAV BOXES(FAN POWERED ANDNON FAN POWERED)FROM STRUCTURE.

2" MIN.

2" MIN.

12" MIN

NOTES:

1. ALL ROOF FLASHING SHALL BE PER ROOFING MANUFACTURERS RECOMMENDATIONS.2. COORDINATE ROOF PENETRATION WITH ROOFING CONTRACTOR TO MAINTAIN ROOFING SYSTEM WARRANTY

1" ELASTOMERIC FOAM. FASTENSECURELY TO BOTTOM OF DRIPPAN.

18 GA. SHEET METALDRIP PAN. TURN UP ATENDS.

18 GA. SHEET METALSUPPORT STRAPS.(TYP.4)

WIRE MESH BIRDSCREENFASTENED SECURELYTO OPEN ENDED DUCT.

FACTORY SUPPLIED BACKDRAFT DAMPER.MOTORIZED OR GRAVITY AS SCHEDULED. DUCTWORK

FLASH ROOF MEMBRANETO CURB. (NOTE 1)

PREFABRICATED ROOFCURB FURN. WITH FAN.(WITH WOOD NAILERAND INSULATEDLINER.)

CADMIUM PLATED LAG SCREWS.PER MANUFACTURERSRECOMMENDATIONS

18" ABOVE TOP OF ROOFINSULATION (MIN).

FRAME, ROOF, & ROOFING BYGENERAL CONTRACTOR.

1 1

7/6

4"

1/4"

5/3

2"

57

/64

"

FAN

NOTES:

1. MAINTAIN CLEARANCE BETWEEN DUCTWORK ANDINSIDE SURFACES OF ENCLOSURE.

2. CONTRACTOR SHALL PROVIDE TRAPEZE HANGERTO SUPPORT SOUND PLENUM FROM STRUCTURE.

TURNINGVANES(TYP.)

3 5/8" METAL STUDS WITH 3 1/2"FIBER GLASS BATT INSULATIONBETWEEN STUDS. SUPPORT FROMSTRUCTURE ABOVE,INDEPENDENTLY FROMDUCTWORK.

1/2" GYPSUM BOARD, TWOLAYERS, STAGGER SEAMS.

PROVIDE ACOUSTICAL SEALANT ATDUCTWORK PENETRATION THROUGHBULKHEAD.

NO SCALE1RECTANGULAR ELBOWS

NO SCALE2BRANCH CONNECTIONS

NO SCALE3DUCT REINFORCEMENT DETAIL

NO SCALE4ROOF MOUNTED EXHAUST FAN WITH DRIP PAN

GENERAL MECHANICAL NOTES1. HANG ALL MAIN DUCT RUNS AND VAV BOXES

(FAN POWERED AND NON FAN POWERED) FROMSTRUCTURE AND NOT FROM ROOF DECK.

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

M302

MECHANICAL DETAILS

14215000

CD SET 02/28/14

LONGMONT, CO

NO SCALE5SOUND PLENUM

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

Page 9: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

AI

AIAO

AI

AO

T

T

AI

AIAO

AI

AO

T

T

AIAO

AI

T

DO

AI

AO

T

WALL MTDTEMP SENSOR

SUPPLYAIR

ACTAIRFLOWMEASURING RING

PRESSURE INDEPENDENTTERMINAL AIR BOX (TAB)

VALVEMOD.

SUPPLYAIR TEMP

FACTORY MOUNTEDDAMPER ACTUATORDAMPER

MOD.

TABAIRFLOW

SEQUENCE OF OPERATION:

GENERAL:

• THE TAB IS CONTROLLED BY A DIRECT DIGITAL CONTROLLER (DDC) VIA THE FACILITY MANAGEMENTCONTROL SYSTEM (FMCS).

• DDC CONTROLS SHALL MODULATE THE TAB DAMPER, TAB REHEAT COIL, AND ASSOCIATED CONTROLVALVE TO MAINTAIN SPACE TEMPERATURE OF 72°F (ADJ.) BASED ON A SIGNAL FROM A WALLMOUNTED TEMPERATURE SENSOR. REFER TO SPECIFICATIONS FOR TEMPERATURE SENSORREQUIREMENTS.

• IN OCCUPIED MODE, THE SPACE TEMPERATURE SHALL HAVE A ±1°F (ADJ.) DEADBAND.• IN UNOCCUPIED MODE, THE SPACE TEMPERATURE SHALL HAVE A ±10°F (ADJ.) DEADBAND.

SPACE TEMP CONTROL:

• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION. THE CONTROL VALVESHALL BE CLOSED.

• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL BE CLOSED UNTIL SPACE SETPOINT ISMAINTAINED, OR UNTIL IT REACHES ITS MINIMUM SCHEDULED AIRFLOW POSITION. THE CONTROLVALVE SHALL BE CLOSED.

• UPON A FURTHER FALL IN SPACE TEMPERATURE, THE TAB AND CONTROL VALVE SHALL MODULATEOPEN IN UNISON UNTIL SETPOINT IS MAINTAINED OR UNTIL SPECIFIED HEATING CFM POSITION ISREACHED.

• IF RTU-1 IS IN COOLING OR ECONOMIZER MODE, THE TAB SHALL CLOSE TO MINIMUM SCHEDULEAIRFLOW POSITION WHEN REHEAT CONTROL VALVE IS OPEN TO PREVENT SIMULTANEOUS HEATINGAND COOLING.

ALARMS, INTERLOCKS & SAFETIES:

• IF THE ROOFTOP UNIT SERVING THE TERMINAL AIR BOX IS IN DEHUMIDIFICATION MODE, THE TABDAMPER SHALL BE FULLY OPEN. THE CONTROL VALVE SHALL MODULATE TO MAINTAIN SPACETEMPERATURE SETPOINT.

• THE FMCS SHALL UTILIZE FEEDBACK FROM ALL TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLYDUCT DIFFERENTIAL STATIC PRESSURE.

• AN ALARM SHALL BE TO THE FMCS OPERATOR INTERFACE IF THE OCCUPIED SPACE TEMPERATURE ISMORE THAN 2°F (ADJ.) ABOVE OR BELOW SETPOINT FOR A PERIOD OF 5 MINUTES OR LONGER.

• AN ALARM SHALL BE SENT TO THE FMCS OPERATOR INTERFACE IF THE UNOCCUPIED SPACETEMPERATURE IS MORE THAN 12°F (ADJ.) ABOVE OR BELOW SETPOINT.

PRIMARY AIR FROM ZONECONDITIONING AHU

HWR

HWS

3-WAY CONTROL VALVE

2' FT

WALL MTDTEMP SENSOR

SUPPLYAIR

ACTAIRFLOWMEASURING RING

PRESSURE INDEPENDENTTERMINAL AIR BOX (TAB)

VALVEMOD.

SUPPLYAIR TEMP

FACTORY MOUNTEDDAMPER ACTUATORDAMPER

MOD.

TABAIRFLOW

SEQUENCE OF OPERATION:

GENERAL:

• THE TAB IS CONTROLLED BY A DIRECT DIGITAL CONTROLLER (DDC) VIA THE FACILITYMANAGEMENT CONTROL SYSTEM (FMCS).

• DDC CONTROLS SHALL MODULATE THE TAB DAMPER TO MAINTAIN TAB AIRFLOW AND MODULATETHE TAB REHEAT COIL AND ASSOCIATED CONTROL VALVE TO MAINTAIN SPACE TEMPERATUREOF 72°F (ADJ.) BASED ON A SIGNAL FROM A WALL MOUNTED TEMPERATURE SENSOR. REFER TOSPECIFICATIONS FOR TEMPERATURE SENSOR REQUIREMENTS.

• IN OCCUPIED MODE, THE SPACE TEMPERATURE SHALL HAVE A ±1°F (ADJ.) DEADBAND.• IN UNOCCUPIED MODE, THE SPACE TEMPERATURE SHALL HAVE A ±10°F (ADJ.) DEADBAND.

SPACE TEMP CONTROL:

• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION AS SCHEDULED. THECONTROL VALVE SHALL BE CLOSED.

• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL REMAIN OPEN TO MAXIMUM CFMPOSITION AND THE CONTROL VALVE SHALL MODULATE OPEN UNTIL SETPOINT IS MAINTAINED.

ALARMS, INTERLOCKS & SAFETIES:

• IF THE ROOF TOP UNIT SERVING THE TERMINAL AIR BOX IS IN DEHUMIDIFICATION MODE, THECONTROL VALVE SHALL MAINTAIN NORMAL OPERATION.

• THE FMCS SHALL UTILIZE FEEDBACK FROM ALL AIR BOX POSITIONS TO RESET THE SUPPLY DUCTDIFFERENTIAL STATIC PRESSURE.

• AN ALARM SHALL BE TO THE FMCS OPERATOR INTERFACE IF THE OCCUPIED SPACETEMPERATURE IS MORE THAN 2°F (ADJ.) ABOVE OF BELOW SETPOINT.

• AN ALARM SHALL BE SENT TO THE FMCS OPERATOR INTERFACE IF THE UNOCCUPIED SPACETEMPERATURE IS MORE THAN 12°F (ADJ.) ABOVE OF BELOW SETPOINT.

PRIMARY AIR FROM ZONECONDITIONING RTU

HWR

HWS

3-WAY CONTROL VALVE

2 FT

GENERAL CONTROL NOTES:1. EACH D.I., D.O., A.I. AND A.O. POINT SHOWN FOR ALL

CONTROL DIAGRAMS SHALL BE DISCRETE FROM ALLOTHER POINTS EXCEPT AS SPECIFICALLY NOTED.

2. ALL WIRING, CONTROL COMPONENTS, DEVICES ANDPROGRAMMING SHOWN ON THESE CONTROL DRAWINGSSHALL BE PROVIDED BY THE TCC UNLESS SPECIFICALLYNOTED OTHERWISE.

3. ALL ACTUATORS SHALL BE OF THE ELECTRICAL TYPE FORTHIS PROJECT UNLESS AN ACTUATOR IS SPECIFICALLYINDICATED ON THE DRAWINGS OR SPECIFICATIONS TO BEPNEUMATIC.

4. MODULATING SIGNALS SHALL BE DISPLAYED AS % OPEN(SIGNALS DISPLAYED AS % CLOSED ARE NOTACCEPTABLE).

5. ALL CONTROL COMPONENTS SUCH AS RELAYS,SWITCHES, DDC CONTROLLERS, ETC. SHALL BEMOUNTED IN STEEL ENCLOSURES WITH STEEL MOUNTINGBACKPLATES PER SPECIFICATION 23 09 00.

6. EACH CONTROL PANEL SHALL HAVE A LAMINATED COPYOF THE APPLICABLE SEQUENCE OF OPERATION ANDCONTROL DIAGRAM INDICATING THE POINTS,COMPONENTS AND OPERATION OF EQUIPMENTASSOCIATED WITH EACH PANEL. REFER TO SECTION 23 0900 FOR ADDITIONAL REQUIREMENTS.

7. TCC SHALL TERMINATE CONTROL SIGNAL FROMADDRESSABLE RELAY DEVICE PROVIDED BY OTHERS ATEACH ROOFTOP AIR HANDLING UNIT AS REQUIRED FOREQUIPMENT SHUTDOWN FROM FIRE ALARM CONTROLPANEL.

8. CONTROL DIAGRAMS ARE SCHEMATIC IN NATURE AND DONOT SHOW ALL REQUIRED CONTROL DEVICES ANDCOMPONENTS. REFER TO FLOOR PLANS, FLOW DIAGRAMSAND DETAILS FOR ADDITIONAL CONTROL DEVICES,COMPONENTS AND REQUIREMENTS NOT SHOWN ONTHESE CONTROL DRAWINGS.

9. TEMPERATURE SETPOINT SHOWN IN CONTROL DIAGRAMSOR IN SEQUENCES OF OPERATION ARE GIVEN FOR INITIALPROGRAMMING AND EQUIPMENT SETUP. CONTRACTORSHALL COORDINATE FINAL TEMPERATURE SETPOINTSBASED ON SPECIFIC OWNER REQUIREMENTS IN THEFIELD.

TERMINAL AIR BOX REPORT & DUCT MOUNTED HOT WATER REHEAT COIL GENERATION:DDC FMCS SHALL BE PROGRAMMED TO GENERATE THE FOLLOWING REPORT BASED ON A MANUAL COMMAND FROM THE DDCFMCS WORKSTATION BY CLICKING ON A GRAPHICAL BUTTON. UPON INITIATING COMMAND THE DDC FMCS SHALL COMPILE AREPORT AS FOLLOWS:

WHEREAS THE SAMPLE REPORT ABOVE SHOWS ONLY A COUPLE TAB/COILS, THE FINAL PROGRAMMED REPORT SHALL LIST ALLTABS/COILS SERVED BY A SINGLE RTU. A SEPARATE REPORT SHALL BE PROGRAMMED FOR EACH RTU.

AFTER THE REPORT PRINTS OUT ALL TAB/HEATING COIL DATA, THE DDC FMCS SHALL AUTOMATICALLY TOTAL ALL THE INDIVIDUALTAB AIRFLOW TO A SINGLE VALUE.

AFTER PRINTING THE SUM OF THE TAB/HEATING COIL AIRFLOW CFM, THE DDC FMCS SHALL THEN AUTOMATICALLY PRINT OUTTHE AIR HANDLER REPORT FOR THE RTU WHICH SERVES THE TABS/HEATING COILS LISTED IN THE REPORT.

DDC FMCS SHALL ALLOW THE DDC FMCS OPERATOR TO ISSUE A SINGLE COMMAND THAT WILL AUTOMATICALLY CHANGE THELOCAL SETPOINT FOR EACH TAB SERVED BY A RTU TO A SINGLE VALUE (E.G. A SINGLE COMMAND WILL SET ALL TABS/HEATINGCOILS SERVED BY RTU-1 TO 80°F). A SEPARATE TAB/HEATING COIL SETPOINT OVERRIDE COMMAND SHALL BE PROGRAMMED INTHE FMCS FOR EACH RTU.

TAB/COILSYMBOL

******

AIRFLOW(CFM)MAX/ACTUAL/MIN

***/***/******/***/***

DMPR POS(% OPEN)

85%80%

VALVE POS(% OPEN)

10%60%

SUP AIR TEMP(DEG. F)

65.275.1

ROOM TEMP(DEG. F)

73.671.1

ROOM SETPOINT(DEG. F)

72.072.0

FAN STATUS(FAN POWERED BOXES)

ONOFF

SUPPLYAIR TEMP

ACTAIR FLOWMEASURING RING

FACTORY MOUNTEDDAMPER ACTUATOR

DAMPERMOD.

TABAIRFLOW

PRIMARY AIR SUPPLYAIR

RETURN PLENUMAIR

START/STOP

WALL MTDTEMP SENSOR

HWR

HWS

SEQUENCE OF OPERATION:

GENERAL:

• THE TAB IS CONTROLLED BY A DIRECT DIGITAL CONTROLLER (DDC) VIA THE FACILITY MANAGEMENTCONTROL SYSTEM (FMCS).

• DDC CONTROLS SHALL MODULATE THE TAB DAMPER, TAB REHEAT COIL, ASSOCIATED CONTROL VALVE,AND PARALLEL FAN TO MAINTAIN SPACE TEMPERATURE OF 72°F (ADJ.) BASED ON A SIGNAL FROM A WALLMOUNTED TEMPERATURE SENSOR. REFER TO SPECIFICATIONS FOR TEMPERATURE SENSORREQUIREMENTS.

• IN OCCUPIED MODE, THE SPACE TEMPERATURE SHALL HAVE A ±1°F (ADJ.) DEADBAND.• IN UNOCCUPIED MODE, THE SPACE TEMPERATURE SHALL HAVE A ±10°F (ADJ.) DEADBAND.

SPACE TEMP CONTROL:

• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION AS SCHEDULED. THE PARALLELFAN SHALL BE OFF AND THE CONTROL VALVE SHALL BE CLOSED.

• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL BE CLOSED UNTIL SPACE SETPOINT ISMAINTAINED, OR UNTIL IT REACHES ITS MINIMUM SCHEDULED AIRFLOW POSITION. THE CONTROL VALVESHALL BE CLOSED AND THE PARALLEL FAN SHALL BE OFF.

• UPON A FURTHER FALL IN SPACE TEMPERATURE, THE PARALLEL FAN SHALL BE ENABLED AND THEPRIMARY AIR FLOW SHALL REMAIN AT ITS MINIMUM SCHEDULED AIRFLOW POSITION. THE CONTROL VALVESHALL BE CLOSED.

• UPON A FURTHER FALL IN SPACE TEMPERATURE WITH THE PARALLEL FAN ON, THE CONTROL VALVE SHALLMODULATE OPEN TO MAINTAIN SPACE TEMPERATURE. THE PRIMARY AIR FLOW SHALL REMAIN AT ITSMINIMUM POSITION.

• UPON A RISE IN SPACE TEMPERATURE, THE CONTROL VALVE SHALL MODULATE CLOSED UNTIL SETPOINTIS MAINTAINED.

• UPON A FURTHER RISE IN SPACE TEMPERATURE, THE PARALLEL FAN SHALL TURN OFF AND THE TABPRIMARY AIR FLOW SHALL MODULATE OPEN UNTIL SPACE SETPOINT IS MAINTAINED.

• IF RTU-1 IS IN COOLING OR ECONOMIZER MODE, THE TAB SHALL CLOSE TO MINIMUM SCHEDULE AIRFLOWPOSITION WHEN REHEAT CONTROL VALVE IS OPEN TO PREVENT SIMULTANEOUS HEATING AND COOLING.

ALARMS, INTERLOCKS & SAFETIES:

• IF THE ROOF TOP UNIT SERVING THE TERMINAL AIR BOX IS IN DEHUMIDIFICATION MODE, THE PRIMARY AIRFLOW SHALL BE FULLY OPEN AND THE CONTROL VALVE SHALL MODULATE TO MAINTAIN SPACETEMPERATURE SETPOINT.

• THE FMCS SHALL UTILIZE FEEDBACK FROM ALL TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLYDUCT DIFFERENTIAL STATIC PRESSURE.

• AN ALARM SHALL BE SENT TO THE FMCS OPERATOR INTERFACE IF THE OCCUPIED SPACE TEMPERATUREIS MORE THAN 2°F (ADJ.) ABOVE OR BELOW SETPOINT FOR A PERIOD OF 5 MINUTES OR LONGER.

• AN ALARM SHALL BE SENT TO THE FMCS OPERATOR INTERFACE IF THE UNOCCUPIED SPACETEMPERATURE IS MORE THAN 12°F (ADJ.) ABOVE OR BELOW SETPOINT.

VALVEMOD.

2 FT

HUMIDISTAT/SENSOR (DUCT MOUNTED)H

TEMPERATURE SENSOR (DUCT MOUNTED)T

TEMPERATURE SENSORT

HUMIDISTAT SENSORH

CONTROL SYMBOLS LISTSYMBOL: DESCRIPTION:

PUMP

ACTUATORACT

SP STATIC SWITCH

FAN

CS CURRENT SWITCH

HEATING WATER SUPPLYHWS

HEATING WATER RETURNHWR

CONTROL VALVE (THREE-WAY)

AO

DI

AI

DO

ANALOG INPUT

ANALOG OUTPUT

DIGITAL INPUT

DIGITAL OUTPUT

TERMINAL AIR BOX W/REHEAT COIL (REFERTO SCHEDULE)

P PRESSURE SENSOR

PS PRESSURE SENSOR

DSD DUCT SMOKE DETECTOR

DP DIFFERENTIAL PRESSURE SWITCH

FS FLOW SWITCH

FAN POWERED TERMINAL AIR BOXW/REHEAT COIL (REFER TO SCHEDULE)

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

M601

MECHANICAL CONTROLS

14215000

CD SET 02/28/14

LONGMONT, CO

NO SCALE1VAV TAB WITH HOT WATER REHEAT CONTROL - TYPE D

NO SCALE3

CONSTANT VOLUME TAB CONTROLW/ HOT WATER REHEAT - TYPE-E

NO SCALE4TERMINAL AIR BOX REPORT GENERATION

NO SCALE2

TAB CONTROL PARALLEL FAN POWERED- W/ HOT WATER REHEAT - TYPE-F

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

Page 10: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

AI

AI

DI

AO AO AI AO AI AI AO DI DI

DI

DI

AO

DI AO

DO

AI

AI

AI

AI

AI

AI

DSD

DSD T

T

H

A

B

C

D

E

F

R

A

B

C

D

E

F

AUX CONTACT TOFMCS TO INITIATECONTROL TERMINAL

STRIP SPEEDCONTROLSIGNALRELIEF FAN

VFD SECTION

SPEEDCONTROLSIGNALSUPPLY FAN

VFD SECTION

TERMINALSTRIP

AUX CONTACT TOFMCS TO INITIATECONTROL

SAFETYCIRCUITS

NH

FIR

E A

LA

RM

SY

ST

EM

DU

CT

HIG

H S

TA

TIC

SUPPLY & RELIEF FAN VFD CONTROL

RTU REPORT GENERATION:DDC FMCS SHALL MONITOR THE FOLLOWING POINTS ON 10 MINUTE (ADJ.) INTERVALS WITHIN A SINGLETREND. THE TREND SHALL RUN FOR A 14-DAY (ADJ.) DURATION AT WHICH POINT THE NEWEST VALUESSHALL AUTOMATICALLY OVERWRITE THE OLDEST VALUES:

• DATE• TIME• GLOBAL OUTSIDE AIR TEMP [°F]• GLOBAL OUTSIDE AIR DEWPOINT [°F]• GLOBAL OUTSIDE AIR HUMIDITY [%RH]• SUPPLY AIR TEMP (SAT) [°F]• RETURN AIR TEMP (RAT) [°F]• RETURN AIR RELATIVE HUMIDITY [%]• OUTSIDE AIRFLOW [CFM]• SUPPLY FAN VFD OUTPUT [% FULL SPEED]• RELIEF FAN VFD OUTPUT [% FULL SPEED]• OUTSIDE AIR DAMPER POSITION [% OPEN]• RELIEF AIR DAMPER POSITION [OPEN/CLOSE]

THIS INFORMATION SHALL BE ACCESSIBLE TO VIEW IN EITHER TABULAR OR GRAPHICAL FORM ON THEFMCS OPERATOR WORKSTATION.

ONCE PER MONTH, THE DDC FMCS SHALL RECORD THE LARGEST RTU AIRFLOW WHICH OCCURREDDURING THAT MONTH. THE DATE, TIME, OUTSIDE AIR TEMP (AND ALL OTHER VALUES LISTED ABOVE)THAT COINCIDED WITH THAT EVENT SHALL ALSO BE RECORDED. THIS INFORMATION SHALL BE STOREDTO A MEMORY LOCATION ON THE FMCS OPERATOR WORKSTATION THAT IS MAINTAINED (NOTAUTOMATICALLY OVERWRITTEN).

RTU-1 REPORT GENERATION

FILTERS:• PROVIDE STATIC PRESSURE SWITCH ACROSS FILTER BANK. PROVIDE AN ALARM TO THE FMCS WHEN THE

DIFFERENTIAL STATIC PRESSURE EXCEEDS 0.6" W.C. (ADJ.)

DEHUMIDIFICATION CONTROL:• INSTALL A HUMIDITY SENSOR IN THE RETURN DUCTWORK JUST UPSTREAM OF THE RETURN INLET OF THE

ROOFTOP UNIT. IF THE RETURN AIR RELATIVE HUMIDITY EXCEEDS 55% (ADJ.), AN ALARM SHALL BE SENT TO THELCD TOUCHSCREEN BUILDING CONTROL UNIT(S). THE DX COOLING COIL SHALL MODULATE TO PROVIDE 53 DEG. F.SUPPLY AIR. THIS SHALL CONTINUE TO OCCUR UNTIL THE RETURN AIR RELATIVE HUMIDITY DROPS 5% (ADJ.)BELOW SETPOINT.

NIGHT SETBACK MODE OVERRIDE:

• IN THE EVENT ANY NIGHT SETBACK OVERRIDE BUTTON IS PRESSED WHEN THE BUILDING IS IN UNOCCUPIEDMODE, THE AIR HANDLING SYSTEM SHALL BE PLACED INTO OCCUPIED MODE FOR A TWO HOUR (ADJ.) TIMEPERIOD.

UNIT SHUTDOWN CONTROLS:

• SIGNAL FROM FIRE ALARM CONTROL PANEL SHALL SHUTDOWN ROOFTOP AIR HANDLING UNIT (REGARDLESS OFTHE COMMAND BEING SENT FROM THE FMCS) VIA AN EMERGENCY STOP INPUT.

• IN THE EVENT A ROOFTOP AIR HANDLING UNIT IS SHUTDOWN (BY EITHER THE FIRE ALARM CONTROL PANEL ORTHE FMCS) THE FOLLOWING SHALL OCCUR:

- COMPRESSORS AND FULLY MODULATING GAS-FIRED HEAT EXCHANGER SHALL BE DE-ENERGIZED.- SUPPLY FAN VFD AND RELIEF FAN VFD SHALL BE DE-ENERGIZED.- OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL FULLY CLOSE.- ALL FAN POWERED TERMINAL AIR BOX FANS SHALL BE DE-ENERGIZED.

ALARMS, INTERLOCKS AND SAFETIES:AN ALARM SHALL BE INDICATED AT THE LCD TOUCHSCREEN BUILDING CONTROL UNIT(S) IN THE EVENT ANY OF THEFOLLOWING OCCUR (SHALL NOT INTERRUPT OPERATION OF THE ROOFTOP AIR HANDLING UNIT):

• FMCS COMMANDS THE RTU TO RUN AND THE STATUS CONTACT AT THE UNIT MOUNTED PACKAGED UNITARYCONTROLLER INDICATES THE UNIT IS NOT RUNNING.

• AN ALARM EVENT IS INDICATED AT THE UNIT MOUNTED PACKAGED UNITARY CONTROLLER (INDICATED BY ACHANGE IN STATE OF THE SUMMARY ALARM CONTACT).

• ANY DIRTY FILTER SWITCH CHANGES STATE (INDICATING DIRTY "FILTER". THIS ALARM SHALL BE SEPARATE FROMTHE SUMMARY ALARM AND SHALL BE IDENTIFIED AT THE LCD TOUCHSCREEN BUILDING CONTROL UNIT(S).

AN ALARM SHALL BE INDICATED AT THE LCD TOUCHSCREEN BUILDING CONTROL UNIT(S) IN THE EVENT ANY OF THEFOLLOWING OCCUR AND THE ROOFTOP UNIT SHALL SHUTDOWN REQUIRING MANUAL RESET:

• SUPPLY AIR TEMP DROPS BELOW 40 DEG. F. FOR MORE THAN 5 MINUTES (ADJ.) AS MEASURED BY DISCHARGETEMP SENSOR AT RTU DISCHARGE.

SUPPLY FAN CONTROL:• UNIT MOUNTED CONTROLS SHALL MODULATE THE OUTPUT SIGNAL TO THE SUPPLY FAN VFD AS REQUIRED TO

MAINTAIN 1.0" W.C. (ADJ.) STATIC PRESSURE IN THE SUPPLY DUCT.

SUPPLY AIR STATIC PRESSURE LIMIT:

• IN THE EVENT THE SUPPLY DUCT STATIC PRESSURE EXCEEDS 4.0" W.C. (ADJ.) AT THE DISCHARGE OF THEROOFTOP AIR HANDLING UNIT, THE UNIT MOUNTED CONTROLS SHALL AUTOMATICALLY DE-ENERGIZE THE SUPPLYFAN VFD. UNIT MOUNTED CONTROLS SHALL ALLOW THE UNIT TO AUTOMATICALLY RESTART THREE TIMES. IF THEOVER-PRESSURIZATION OCCURS THE THIRD TIME, THE UNIT SHALL SHUT DOWN AND A MANUAL RESET DIAGNOSTICSHALL BE SET AND DISPLAYED AT THE FMCS LCD TOUCHSCREEN IN THE BOILER ROOM.

RELIEF FAN CONTROL (BUILDING PRESSURIZATION):

• PRESSURE SENSOR SHALL BE MOUNTED WITHIN THE BUILDING FOR THE ROOFTOP AIR HANDLING UNIT TOMONITOR THE INTERIOR BUILDING PRESSURE.

• PRESSURE SENSOR SHALL BE MOUNTED AT ROOFTOP AIR HANDLING UNIT TO MONITOR THE OUTSIDE AIRPRESSURE.

• THE SIGNAL FROM EACH BUILDING MOUNTED AND UNIT MOUNTED PRESSURE SENSOR SHALL BE WIRED TO THEUNIT CONTROL PANEL AND SHALL BE USED TO MODULATE THE RELIEF AIR FAN VFD TO MAINTAIN A POSITIVEBUILDING STATIC PRESSURE OF 0.01" W.C. (ADJ.)

SUPPLY AIR SETPOINT:SUPPLY AIR TEMPERATURE SHALL RESET AS FOLLOWS:• WHEN O.A. TEMP IS LESS THAN 40°F (ADJ.) , SUPPLY AIR TEMP SETPOINT SHALL BE 60°F (ADJ.).• WHEN O.A. TEMP IS HIGHER THAN 60°F (ADJ.) , SUPPLY AIR TEMP SETPOINT SHALL BE 53°F (ADJ.)• WHEN O.A. TEMP IS BETWEEN 40°F (ADJ.) AND 60°F (ADJ.) , SUPPLY AIR TEMP SETPOINT SHALL BE CALCULATED

BASED ON A LINEAR EQUATION BETWEEN THE SUPPLY AIR TEMP SETPOINTS LISTED ABOVE.

COOLING OPERATION:WHENEVER THE SUPPLY AIR TEMPERATURE IS ABOVE SETPOINT, THE FOLLOWING SHALL OCCUR IN SEQUENCE:• MODULATE GAS BURNER OFF.• IF THE OUTSIDE AIR ENTHALPY IS BELOW THE RETURN AIR ENTHALPY THE OUTSIDE AIR DAMPER SHALL MODULATE

OPEN. THIS SHALL CONTINUE UNTIL SETPOINT IS ACHIEVED OR THE DAMPER IS FULLY OPEN.• IF THE OUTSIDE AIR ENTHALPY IS ABOVE THE RETURN AIR ENTHALPY THE OUTSIDE AIR DAMPER SHALL CLOSE TO

ITS MINIMUM POSITION. IF SETPOINT IS NOT ACHIEVED BY MODULATION OF THE OUTSIDE AIR DAMPER, THECOMPRESSORS SHALL BE ENABLED AND IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 4°F (ADJ.) ABOVESETPOINT, ONE STAGE OF REFRIGERATION SHALL BE ADDED.

HEATING OPERATION:WHENEVER THE DISCHARGE AIR TEMPERATURE IS BELOW SETPOINT, THE FOLLOWING SHALL OCCUR IN SEQUENCE:• IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 4°F (ADJ) BELOW SETPOINT, ONE STAGE OF COOLING SHALL

BE DISABLED.• IF THE OUTSIDE AIR ENTHALPY IS BELOW THE RETURN AIR ENTHALPY THE OUTSIDE AIR DAMPER SHALL MODULATE

CLOSED. THIS SHALL CONTINUE UNTIL THE SETPOINT IS ACHIEVED OR THE DAMPER IS IN THE MINIMUM POSITION.• IF THE SETPOINT IS NOT ACHIEVED BY DAMPER MODULATION AND ALL COMPRESSORS ARE OFF, MODULATE GAS

BURNER ON TO MAINTAIN SETPOINT.

PACKAGE ROOFTOP UNIT SYSTEM DESCRIPTION: (CONTROLS PROVIDED WITH UNIT)

GENERAL:REFER TO SECTION 23 74 11 FOR A DESCRIPTION OF THE RTU AND THE CONTROLS PROVIDED BY THE RTUMANUFACTURER PER THE PROTOCOL SPECIFIED IN SECTION 23 09 00. THE TCC SHALL PROVIDE ALL ADDITIONALCONTROL COMPONENTS REQUIRED TO ACCOMPLISH THE SEQUENCE OF OPERATION LISTED BELOW.

BUILDING OCCUPANCY SCHEDULING:FMCS SHALL BE PROGRAMMED WITH THE FOLLOWING TENTATIVE OCCUPANCY SCHEDULE. PROVIDE WITHSEPARATE SCHEDULE FOR EACH DAY OF THE WEEK.

• OCCUPIED MODE: MONDAY THROUGH FRIDAY 5:00AM-7:00PM (ADJ.) SATURDAY 7:00AM-2:00PM (ADJ.)

• UNOCCUPIED MODE: ALL HOURS NOT INDICATED ABOVE AS OCCUPIED.

MORNING START-UP OPERATION:• TWO HOURS PRIOR TO OCCUPIED OPERATION, THE FMCS SHALL MEASURE EACH OF THE SPACE

TEMPERATURES AND OUTSIDE AIR TEMPERATURE TO DETERMINE THE MINIMUM RUNTIME TO WARM OR COOLTHE SPACES TO THEIR SETPOINT.

• WHEN THE COMPUTED START TIME IS REACHED THE FMCS SHALL RESET ALL SPACE TEMPERATURE SETPOINTSTO OCCUPIED SPACE TEMPERATURE SETPOINTS.

• THE RETURN AIR, OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL BE OPEN TO ALLOW MINIMUM SCHEDULEDOUTSIDE AIR INTO BUILDING UNLESS OVERRIDDEN BY ECONOMIZER OPERATION.

OCCUPIED OPERATION:SUPPLY AND RELIEF FAN SHALL RUN CONTINUOUSLY, OUTDOOR AIR AND RELIEF AIR DAMPERS SHALL NOT CLOSEBELOW THEIR MINIMUM SETPOINTS. IN ADDITION, THE FOLLOWING SHALL OCCUR:

• ENABLE OPERATION OF OUTSIDE AIR AND RELIEF AIR DAMPERS.• ENABLE OPERATION OF COMPRESSORS OR FULLY MODULATING GAS-FIRED HEAT EXCHANGER.• MODULATE COMPRESSORS OR GAS-FIRED HEAT EXCHANGER TO SATISFY SUPPLY AIR CONTROL.• TRANSMIT SIGNAL TO UNIT MOUNTED PACKAGED UNITARY CONTROLLER TO OPEN THE OUTSIDE AIR DAMPER TO

MINIMUM POSITION.• THE EXHAUST FANS EF-1, EF-2, EF-3, EF-5, EF-6 SHALL RUN CONTINUOUSLY DURING OCCUPIED MODE.• EXHAUST FAN EF-4 IS OPERATED BY WALL SWITCH.

UNOCCUPIED OPERATION:SUPPLY AND RELIEF FAN SHALL RUN CONTINUOUSLY, OUTDOOR AIR DAMPER SHALL CLOSE TO 700 CFM, REFER TOOUTDOOR AIRFLOW RATE SETBACK CONTROL SEQUENCE. IN ADDITION, THE FOLLOWING SHALL OCCUR:

• THE EXHAUST FANS EF-1, EF-3 AND EF-6 SHALL REMAIN OFF DURING UNOCCUPIED MODE.• EXHAUST FAN EF-5 SHALL RUN CONTINUOUSLY.• EXHAUST FAN EF-2 SHALL RUN CONTINUOUSLY, PER RTU-2 CONTROL SEQUENCE ON M603.• EXHAUST FAN EF-4 IS OPERATED BY WALL SWITCH.• SPACE TEMP HEATING AND COOLING DEADBANDS SHALL BE RESET PER TAB CONTROL SEQUENCES.

OUTDOOR AIRFLOW RATE SET-BACK:• DURING OCCUPIED MODE AND WHEN ECONOMIZER MODE IS NOT ENABLED, THE FMCS SHALL MAINTAIN THE

SCHEDULED MINIMUM OUTDOOR AIRFLOW RATE.• DURING OCCUPIED MODE AND WHEN ECONOMIZER MODE IS ENABLED, THE OUTDOOR AIR DAMPER SHALL BE

CONTROLLED AS STATED IN THE ECONOMIZER CONTROL SEQUENCE.• DURING UNOCCUPIED MODE, THE OUTDOOR AIRFLOW RATE SHALL BE REDUCED TO 700 CFM TO REFLECT THE

EXHAUST FANS THAT ARE DISABLED. THE RELIEF FAN AND OUTDOOR AIR DAMPER SHALL BE CONTROLLED TOMAINTAIN POSITVE BUILDING PRESSURIZATION, AS DESCRIBED IN THE RELIEF FAN CONTROL SEQUENCE.

RELIEF AIR

OUTSIDE AIR

RTU CONTROLLER

EXTERNAL CONTROLS PROVIDED BY AND/OR WIRED BY TCC'S:

• HIGH STATIC SWITCH• SUPPLY/RETURN TEMPERATURE SENSOR• RETURN DUCT HUMIDITY SENSOR• SUPPLY DUCT DIFFERENTIAL PRESSURE SENSOR• BUILDING DIFFERENTIAL PRESSURE SENSOR• DUCT SMOKE DETECTORS, BY E.C.• COMPRESSOR STATUS (EACH)• ALL REQUIRED POINTS FROM RTU CONTROLLER TO FMCS• ALL REQUIRED POINTS FROM FMCS TO RTU CONTROLLER• DUCT SMOKE DETECTOR INTERLOCK• SPACE AND OUTDOOR PRESSURE SENSORS - COORDINATE EXACT

LOCATION OF SENSORS IN FIELD• SUPPLY AND RELIEF FAN STATUS• MANUAL RESET DIAGNOSTIC

PS

DUCT SMOKE DETECTOR: PROVIDED, WIRED, ANDINSTALLED BY ELECTRICAL CONTRACTOR.INTERLOCK TO RTU CONTROL PANEL BY TCC (TYP.)

RETURN AIR DUCTMTD TEMP & HUMIDITY

SENSORS

SUPPLYTEMPERATURE

SENSOR

RETURNAIR

SUPPLYAIR

CS

COMPRESSORSTATUS (TYP. 4)

LONTALK INTERFACETO FMCS BY RTUMANUFACTURER

TO/FROM FMCS

OUTSIDE AIR DAMPER

CS

RELIEF FANSTATUS

CS

SUPPLY FANSTATUS

RTU ENABLE/DISABLE

DISCHARGE TEMPSETPOINT

SUPPLY DUCT DIFFERENTIALSTATIC PRESSURE

SUPPLY DUCTDIFFERENTIAL STATICPRESSURE SETPOINT

SUPPLY FAN VFD OUTPUT

DIRTYFILTER

GENERALALARM

OA CFMSETPOINT

BUILDING DIFFERENTIALSTATIC PRESSURE SETPOINT

RELIEF FAN(TYP. 2)

DUCT MOUNTEDPRESSURE SENSOR

RELIEF FAN VFD OUTPUT

MOD

VFD(TYP.)

START/STOP

ALRM

COMMUNICATION LINKBETWEEN VFD GATEWAY &FMCS (TYP EACH VFD)

BUILDING DIFFERENTIALPRESSURE SENSOR

DP

COORDINATE EXACT LOCATIONAND QUANTITY OF OUTDOORPRESSURE SENSOR WITHMANUFACTURER.(TYP)

ROOF

COORDINATE EXACT LOCATION OFINDOOR PRESSURE SENSOR WITHMANUFACTURER.

AVERAGED OUTSIDESTATIC PRESSURE

OA CFM FLOW RATE

SP

HIGH SUPPLY AIRDUCT STATICPRESSURE SENSOR

OUTSIDE AIR FLOWMEASURING

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

M602

MECHANICAL CONTROLS

14215000

CD SET 02/28/14

LONGMONT, CO

NO SCALE1ROOFTOP AIR HANDLING UNIT CONTROLS - RTU-1

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

Page 11: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

AI

AI

DI

AO

DO

DI

DO AO DI DI

AI

AI AI

DI

DO

SEQUENCE OF OPERATION:PROVIDE GLOBAL O.A. TEMP AND HUMIDITY TRANSMITTERS.

GLOBAL O.A. TEMP AND HUMIDITY SENSORS SHALL CONTINUOUSLY UPDATE FMCS FORUSE IN CONTROLLING MECHANICAL EQUIPMENT AS REQUIRED IN SEQUENCES OFOPERATION.

GRAPHICAL DISPLAY:DISPLAY THE GLOBAL OUTSIDE AIR TEMPERATURE AND HUMIDITY ON RTU GRAPHICPAGE.

MOUNT ABOVE ROOF ON NORTHFACE OF MECHANICAL WELL WALL.

GLOBAL O.A.TEMP SENSORW/ SUNSHIELD

GLOBAL O.A.HUMIDITYSENSOR

H

T

RTU-2 SYSTEM REPORT GENERATION

DDC SHALL MONITOR THE FOLLOWING POINTS ON 10 MINUTE (ADJ.) INTERVALS WITHIN A SINGLE TREND.THE TREND SHALL RUN FOR A 14-DAY (ADJ.) DURATION AT WHICH POINT THE NEWEST VALUES SHALLAUTOMATICALLY OVERWRITE THE OLDEST VALUES:

• DATE• TIME• GLOBAL OUTSIDE AIR TEMP. (°F)• GLOBAL OUTSIDE AIR DEWPOINT ( °F)• GLOBAL OUTSIDE AIR HUMIDITY (% RH)• SUPPLY AIR TEMP (SAT) (°F): AS MEASURED BY ROOFTOP MOUNTED TEMP SENSOR.• SPACE TEMPERATURE (°F)• SPACE RELATIVE HUMIDITY (%)• COMPRESSOR STATUS (EACH COMPRESSOR) (ON/OFF)

THIS INFORMATION SHALL BE ACCESSIBLE TO VIEW IN EITHER TABULAR OR GRAPHICAL FORM ON THE LCDTOUCHSCREEN BUILDING CONTROL UNIT(S).

ONCE PER MONTH, THE DDC SHALL RECORD THE RTU LOAD (IN TONS) WHICH OCCURRED DURING THATMONTH. THE DATE, TIME, OUTSIDE AIR TEMPERATURE, (AND ALL OTHER VALUES LISTED ABOVE) THATCOINCIDED WITH THAT EVENT SHALL ALSO BE RECORDED. THIS INFORMATION SHALL BE STORED TO AMEMORY LOCATION ON THE LCD TOUCHSCREEN BUILDING CONTROL UNIT(S) THAT IS MAINTAINED (NOTAUTOMATICALLY OVERWRITTEN).

RTU CONTROLLER

HT

BACnet INTERFACE TOFMCS BY RTU

MANUFACTURER

OUTSIDE AIRDAMPER(BY MFR.)

T

SUPPLY AIRTEMPERATURE SENSOR,BY MFR IN UNITDISCHARGE

RETURNAIR

SUPPLYAIR

GENERALALARM

RTUENABLE/DISABLE

SPACE MTD TEMP& HUMIDITYSENSORSPROVIDED BYMFR, WIRED BYTCC.

SPACE TEMPSETPOINT ADJUST DIRTY

FILTER

RELIEFAIR

OUTSIDEAIR

TO/FROM FMCS

PACKAGE ROOFTOP UNIT SYSTEM DESCRIPTION (CONTROLS PROVIDED WITH UNIT)

GENERAL:

REFER TO SECTION 23 74 11 FOR A DESCRIPTION OF THE RTU AND THE CONTROLS PROVIDED BY THE RTUMANUFACTURER. THE RTU IS CONTROLLED BY A FACTORY MOUNTED CONTROL PANEL AND CONNECTED TO THEFACILITY MANAGEMENT CONTROL SYSTEM (FMCS). PER THE PROTOCOL SPECIFIED IN SECTION 23 09 00. THE RTUMANUFACTURER SHALL PROVIDE ALL COMPONENTS REQUIRED TO ACHIEVE THE SEQUENCE OF OPERATION ASDESCRIBED BELOW.

BUILDING OCCUPANCY SCHEDULING:FMCS SHALL BE PROGRAMMED WITH AN OCCUPANCY SCHEDULE TO ALLOW FOR OCCUPIED MODE AND UNOCCUPIEDMODE. PROVIDE WITH SEPARATE SCHEDULE FOR EACH DAY OF THE WEEK.

· OCCUPIED MODE: MONDAY THROUGH FRIDAY 5:00 AM - 7:00 PM (ADJ.) SATURDAY 7:00 AM - 2:00 PM (ADJ.)

· UNOCCUPIED MODE: ALL HOURS NOT INDICATED ABOVE AS OCCUPIED.

OCCUPIED MODE OPERATION:· SUPPLY FAN SHALL RUN CONTINUOUSLY.. EF-2 SHALL RUN CONTINUOUSLY.. OUTSIDE AIR DAMPER SHALL OPEN TO ALLOW MINIMUM SCHEDULED OUTSIDE AIR INTO BUILDING.· SPACE TEMPERATURE SET POINTS SHALL BE SET TO:

COOLING - 75° F (ADJ.)HEATING - 70° F (ADJ.)

UN-OCCUPIED MODE OPERATION:· RTU SHALL RUN CONTINUOUSLY.· OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL REMAIN OPEN TO SCHEDULED MINIMUMS.. EF-2 SHALL RUN CONTINUOUSLY.· SPACE TEMPERATURE SET POINTS SHALL BE RESET TO:

COOLING - 80° F (ADJ.)HEATING - 65° F (ADJ.)

SEQUENCE OF OPERATION:

WHEN RTU IS INDEXED TO RUN, THE RTU CONTROL PANEL SHALL ENABLE THE FOLLOWING TO OCCUR:· RELIEF AIR DAMPER SHALL OPEN.· OUTSIDE AIR DAMPER SHALL OPEN TO MINIMUM SCHEDULED POSITION.· SUPPLY FAN SHALL BE ENABLED TO RUN AFTER A 30 SECOND DELAY (ADJ.)· EF-2 SHALL BE ENABLED TO RUN AFTER A 30 SECOND DELAY (ADJ.)

SUPPLY FAN CONTROL:· SUPPLY FAN SHALL RUN CONTINUOUSLY WHENEVER THE RTU IS ENABLED.

SPACE TEMPERATURE CONTROL:· RTU SUPPLY DISCHARGE TEMP SENSOR SHALL MONITOR DISCHARGE AIR TEMPERATURE.· RTU UNIT CONTROLS SHALL ENABLE AND MODULATE DX COOLING, MODULATING GAS HEAT, AND CONDENSER

REHEAT AS REQUIRED TO MAINTAIN SPACE TEMPERATURE SETPOINT AND HUMIDITY SETPOINT.

EXTERNAL CONTROLS PROVIDED BY AND/OR WIRED BY TCC'S:

· SUPPLY TEMPERATURE SENSOR (FURNISHED BY MFR, WIRED BY TCC)· ALL REQUIRED POINTS FROM RTU CONTROLLER TO FMCS· ALL REQUIRED POINTS FROM FMCS TO RTU CONTROLLER· DUCT SMOKE DETECTOR INTERLOCK· SPACE TEMPERATURE AND HUMIDITY SENSORS (PROVIDED AND WIRED BY TCC). COMPRESSOR STATUS

DEHUMIDIFICATION CONTROL:INSTALL A HUMIDITY SENSOR IN RECEIVING 134. IF THE SPACE RELATIVE HUMIDITY EXCEEDS 55% (ADJ.) AN ALARM SHALLBE SENT TO THE LCD TOUCHSCREEN BUILDING CONTROL UNIT(S). THE DX COOLING COIL SHALL MODULATE TO PROVIDE 55°FSUPPLY AIR. THE HOT GAS REHEAT COIL SHALL MODULATE TO MAINTAIN SPACE TEMPERATURE. THIS SHALL CONTINUE TOOCCUR UNTIL RETURN AIR RELATIVE HUMIDITY DROPS 5% (ADJ.) BELOW SETPOINT.

ECONOMIZER OPERATION:WHEN UNIT IS IN COOLING MODE AND O.A. TEMP DROPS BELOW 65°F (ADJ.) AND THE O.A. ENTHALPY IS LESS THAN THESPACE RETURN AIR ENTHALPY, THE RTU CONTROLLER SHALL ENABLE ECONOMIZER CONTROLS, WHEN O.A. TEMP RISESABOVE 68°F (ADJ.) OR WHEN O.A. ENTHALPY IS GREATER THAN THE SPACE AIR ENTHALPY, THE RTU CONTROLLER SHALLDISABLE ECONOMIZER CONTROLS AND SHALL RETURN THE UNIT TO MINIMUM O.A. MODE.

ONCE ECONOMIZER CONTROLS HAVE BEEN ENABLED OR DISABLED, THE UNIT SHALL CONTINUE TO OPERATE IN THAT MODEFOR A MIN. OF 10 MINUTES (ADJ.) BEFORE BEING ALLOWED TO SWITCH BACK. (TO PREVENT SHORT CYCLING).

IN ECONOMIZER MODE, THE RTU CONTROLLER SHALL MODULATE THE RETURN, RELIEF, AND O.A. DAMPERS AS REQUIRED TOMAINTAIN SPACE TEMP SETPOINT.

UNIT HEATER OPERATION:WHEN THE OUTSIDE AIR TEMPERATURE IS LOWER THAN 40°F (ADJ.) AND THE OVERHEAD DOOR SWITCH INDICATES THEDOOR IS OPEN, THE UNIT HEATER FAN SHALL TURN ON AND CONTROL VALVE SHALL FULLY OPEN TO PROVIDE HEATREGARDLESS OF SPACE TEMPERATURE.WHEN THE OVERHEAD DOOR SWITCH INDICATES THE DOOR IS CLOSED, THE UNIT HEATER FAN TURN OFF AND CONTROLVALVE SHALL BE CLOSED.

ALARMS, INTERLOCKS AND SAFETIES:THE FOLLOWING SAFETIES SHALL BE INSTALLED BY THE TCC IN THE FIELD.· FIRE ALARM RELAY (WIRED TO SUPPLY AND RELIEF FAN)

SEND AN ALARM TO THE FMCS FOR THE FOLLOWING:· DIRTY FILTERS (WHEN PRE-FILTER PRESSURE DROP EXCEEDS 0.6" W.C. (ADJ.))· IF SPACE AIR TEMPERATURE IS MORE THAN 15°F (ADJ.) ABOVE OR BELOW SETPOINT.· IF THE FIRE ALARM SYSTEM IS ACTIVATED.· IF OVERHEAD DOOR CONTACT SWITCH INDICATES THE OVERHEAD DOOR IS OPEN FOR MORE THAN 30 MINUTES AND

WHEN OUTSIDE AIR TEMPERATURE IS LOWER 40°F (ADJ.).

UNIT SHUT DOWN CONTROLS:. SIGNAL FROM FIRE ALARM CONTROL PANEL SHALL SHUT DOWN ROOFTOP AIR HANDLING UNIT (REGARDLESS OF THE

COMMAND BEING SENT FROM THE FMCS) VIA AN EMERGENCY STOP INPUT.

WHENEVER RTU IS SHUTDOWN, THE RTU CONTROLLER SHALL COMMAND THE FOLLOWING TO OCCUR:. SUPPLY FAN SHALL BE DE-ENERGIZED.· OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL FULLY CLOSE. THE RETURN AIR DAMPER SHALL FULLY OPEN.· DX COOLING SHALL BE DISABLED.· GAS-FIRED HEAT EXCHANGER SHALL BE DISABLED.

CS

COMPRESSORSTATUS

DSD DSD

HWR

HWS

FAN START/STOP

OVERHEADDOOR CONTACT

SWITCH

SUH-1

VALVE MOD

CS

START/STOP

FANSTATUSEXHAUST

FAN

GRAVITYBACKDRAFTDAMPER

EXHAUST AIR

TYPICAL FOR EXHAUST FANS

EXHAUST AIR

FAN INTERLOCK SCHEDULE

SYSTEM INTERLOCKED EXHAUST FANS REMARKS

RTU-1 EF-1, EF-3, EF-5, EF-6 NOTE 1

NOTES:1. INTERLOCK EXHAUST FAN OPERATION THROUGH THE FMCS WITH RESPECTIVE RTU IN

ACCORDANCE WITH RTU SEQUENCE OF OPERATION.2. FMCS WILL SUPERVISE EF-4 VIA FAN STATUS CURRENT SWITCH.

WALL MOUNTEDFAN SWITCH(EF-4 ONLY)NOTE 2

RTU-2 EF-2 NOTE 1

S

TYPICAL FOR EF-1, 2, 3, 5 & 6

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

M603

MECHANICAL CONTROLS

14215000

CD SET 02/28/14

LONGMONT, CO

NO SCALE2GLOBAL OA TEMP/HUMIDITY

NO SCALE3RTU-2 REPORT GENERATION

NO SCALE1ROOFTOP AIR HANDLING UNIT CONTROLS - RTU-2

NO SCALE4EXHAUST FAN CONTROL

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

DUCT SMOKE DETECTOR: PROVIDED, WIRED,AND INSTALLED BY ELECTRICALCONTRACTOR. INTERLOCK TO RTU CONTROLPANEL BY TCC (TYP.)

Page 12: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

AO DI DO DI

AI

DI

DO

AI

AI

DI

DO

T

AI

SEQUENCE OF OPERATION:

GENERAL:

THE HEATING SYSTEM IS CONTROLLED BY THE BOILER MANAGEMENT SYSTEM CONTROL PANEL (BMCP). THE HEATINGSYSTEM SHALL BE ENABLED AND DISABLED VIA THE FMCS.

HEATING WATER PLANT CONSISTS OF TWO BOILERS. BLR-1 AND BLR-2 ARE EACH SIZED AT 50% OF FULL LOAD HEATINGDEMAND.

BOILER SYSTEM IS ARRANGED AS A CONSTANT VOLUME PUMP OPERATION. REDUNDANT PUMPS (HWP-1 AND HWP-2) SERVETHE PIPING LOOP.

A FACTORY MOUNTED BOILER CONTROL PANEL SHALL BE PROVIDED FOR EACH BOILER BY THE BOILER MANUFACTURER.EACH OF THE FACTORY BOILER CONTROL PANELS SHALL COMMUNICATE VIA THE BMCP.

HEATING WATER SUPPLY SETPOINT RESET SCHEDULE:

WHEN THE OUTSIDE AIR DRY BULB TEMPERATURE IS 40°F (ADJ.) AND BELOW, THE HEATING WATER SUPPLY TEMPERATURESETPOINT SHALL BE 140°F (ADJ.) AND SHALL RESET TO 120°F (ADJ.) AT 60°F (ADJ.) AND ABOVE OUTSIDE AIR DRY BULBTEMPERATURE. THE HEATING WATER SUPPLY TEMPERATURE SETPOINT SHALL BE RESET LINEARLY BETWEEN THESE TWOSETPOINTS.

BOILER CONTROL: HOT WATER CONDENSING BOILERS (BLR-1 AND BLR-2)

START/STOP : THE FMCS SHALL START THE LEAD BOILER WHENEVER THE OUTSIDE AIR DRY BULB REFERENCETEMPERATURE IS BELOW 65°F (ADJ.) OR ON A CALL FOR HEAT. THE LAG BOILER SHALL REMAIN OFF.

THE BMCP SHALL ROTATE THE LEAD BOILER ON A WEEKLY BASIS.

THE BMCP SHALL ENABLE AND DISABLE BOILERS AS NEEDED TO MAINTAIN THE HEATING WATER SUPPLY TEMPERATURE.WHEN THE BOILER MANAGEMENT SYSTEM CONTROL PANEL ENABLES A BOILER TO OPERATE, A CONSTANT VOLUMECIRCULATION PUMP SHALL TURN ON. INSTALL A CURRENT STATUS SWITCH TO PROVE CIRCULATION PUMP OPERATION FOREACH PUMP.

THE BMCP SHALL CONTROL BOILER START-UP AND OPERATION. FLOW SHALL BE PROVEN FOR THE BOILER TO START-UPBY A MANUFACTURER PROVIDED FLOW SWITCH.

IF LEAD BOILER FAILS TO START, FMCS SHALL ATTEMPT TO RESTART LEAD BOILER. IF LEAD BOILER DOES NOT STARTAFTER TWO ATTEMPTS, AN ALARM SHALL BE SENT TO THE OPERATOR INTERFACE AND FMCS SHALL START THE LAGBOILER.

HEATING WATER PUMP CONTROL: (HWP-1) AND (HWP-2)

START/STOP: THE FMCS SHALL START THE LEAD PUMP WHENEVER THE OUTSIDE AIR DRY BULB REFERENCETEMPERATURE IS BELOW 65°F (ADJ.) OR ON A CALL FOR HEAT. THE STAND BY PUMP SHALL REMAIN OFF.

PUMP STATUS: LOCATE CURRENT STATUS SWITCHES ON EACH PUMP TO SENSE PUMP STATUS.

THE FMCS SHALL ROTATE THE LEAD PUMP ON A WEEKLY BASIS.

IF LEAD PUMP FAILS TO START, FMCS SHALL ATTEMPT TO RESTART LEAD PUMP. IF LEAD PUMP DOES NOT START AFTERTWO ATTEMPTS, AN ALARM SHALL BE SENT TO THE OPERATOR INTERFACE AND FMCS SHALL START THE STAND BY PUMP.

ALARMS, INTERLOCK, AND SAFETIES

SEND AN ALARM TO THE OPERATOR INTERFACE UPON THE OCCURRENCE OF ANY OF THE FOLLOWING CONDITIONS:

• IF A PUMP CURRENT STATUS SWITCH DOES NOT PROVE PUMP OPERATION.

• AN ALARM AT ANY BOILER CONTROL PANEL.

• IF HEATING WATER SUPPLY TEMPERATURE IS MORE THAN 5°F (ADJ.) ABOVE OR BELOW SETPOINT FOR MORE THAN 10MINUTES (ADJ.)

REPORT GENERATION

FMCS SHALL MONITOR THE FOLLOWING POINTS ON 5 MINUTE (ADJ.) INTERVALS WITHIN A SINGLE TREND. THE TREND SHALLRUN FOR A 14 DAY (ADJ.) DURATION AT WHICH POINT THE NEWEST VALUES SHALL OVERWRITE THE OLDEST VALUES:

• DATE• TIME• GLOBAL OUTSIDE AIR TEMP. (°F)• HEATING WATER TEMP. SETPOINT (°F)• HEATING WATER SUPPLY TEMP. (°F)• HEATING WATER RETURN TEMP. (°F)• OPERATION STATUS OF EACH BOILER AND CIRCULATION PUMP

THIS INFORMATION SHALL BE ACCESSIBLE TO VIEW IN EITHER TABULAR OR GRAPHICAL FORM ON THE FMCS OPERATORINTERFACE.

CONTROLS

BLR-1

CONTROLS

BLR-2

HWP-1

HWP-2

CS

CS

PUMPSTATUS START/

STOP

LOOP HWRTEMP

LOOP HWSTEMP

START/STOP

PUMPSTATUS

LOOP HWSTEMP

BOILER CONTROL ANDCOMMUNICATION LINKBETWEEN BOILERS ANDBMCP.

BOILER MANAGEMENTSYSTEM CONTROLPANEL (BMCP)

LOOP HWSSETPOINT

BOILERSTATUS(TYP.2)

HEATING WATERSYSTEMENABLE/DISABLE

BOILERALARM(TYP.2)

COMMUNICATION CABLETO NETWORK AREACONTROLLER. POINTSINDICATED AS HARDWIREDMAY BE COMMUNICATEDAS SOFTWARE POINTS.

HW

R

HW

S

HWR

FS

FS

AO

AI

ACT

PRESSURE INDEPENDENTTERMINAL AIR BOX (TAB)

VELOCITY ANDSTATICSENSOR

DAMPER ACTUATOR

WALLMOUNTED

TEMPERATURESENSOR

DAMPERMOD.

TABAIRFLOW

PRIMARY AIR FROM RTU-1 SUPPLY AIR

SEQUENCE OF OPERATION

• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER TO MAINTAIN SPACE TEMPERATUREOF 75°F (ADJ.) WITH 2°F (ADJ.) DEAD BAND BASED ON A SIGNAL FROM A WALL MOUNTEDTEMPERATURE SENSOR. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS. SPACESWITH ADJUSTABLE THERMOSTATS WILL ALLOW A +/- 3°F (ADJ.) OFFSET FROM THE DDC SETPOINT.

• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION.

• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL MODULATE CLOSED UNTIL SPACE SETPOINTIS MAINTAINED, OR UNTIL IT REACHES ITS MINIMUM SCHEDULED CFM POSITION PER THE TABSCHEDULE.

ALARMS, INTERLOCKS & SAFETIES:

• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE IS MORE THAN10°F (ADJ.) ABOVE OR BELOW SETPOINT.

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

M604

MECHANICAL CONTROLSAND FLOW DIAGRAM

14215000

CD SET 02/28/14

LONGMONT, CO

NO SCALE1HEATING WATER SYSTEM CONTROL DIAGRAM

NO SCALE2COOLING ONLY TAB CONTROL - TYPE C

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

Page 13: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

GRADE

BLACKTOP OR CLEANTAMPED EARTH.

ALL AROUND

MINIMUM 9"

FLEXIBLE PVC COUPLING WITHSTAINLESS STEEL BAND CLAMPS.SUITABLE FOR UNDERGROUNDINSTALLATION. INDIANA SEAL,MODEL NO. 156-88 OR EQUIVALENT.

NEOPRENE GASKET

LINE OF UNDISTURBEDEARTH.

SEE SPECIFICATIONSECTION 22 10 00 FORMATERIAL.

1/8 BEND.

CLEANOUT ASSEMBLY. SEEPLUMBING MATERIAL LIST.

CONCRETE SLAB (5")REINFORCED WITH WIREMESH OR 3/8" DIAMETERRODS 6" CENTERS EACHWAY. SLOPE AWAY FROMCLEANOUT ASSEMBLYTOP.

EXTEND CONCRETE PAD6" BEYOND THE LINE OFUNDISTURBED EARTH.

SAND BACKFILL ORCLEAN TAMPED EARTH.

FROST SLEEVE

PREDICTED DEPTH OFFROST. REFER TOGEOTECHNICAL REPORTFOR FROST DEPTHINFORMATION.

.

FROST SLEEVE TO BE 6"BELOW PREDICTEDDEPTH OF FROST,

ISLAND SINK & TRIM

ROUTE TOP OF VENTLOOP AS HIGH ASPOSSIBLE .

DRAINBOARD

2-WAYCLEANOUT

1 1/2" V

2" SAN

2" V SLOPE 1/4"/FT. MIN.

SAN

SLOPE

ROUTE VENT LINE TONEAREST WALL.

2-WAY CLEANOUT

1 1/2" SAN

FLOOR

CL

CL

BACKFLOW PREVENTER ASSEMBLY

BFP

SHUTOFF VALVE(TYPICAL)

WALL OROBSTRUCTION

FLOOR

12" MINIMUM (TOBOTTOM OFASSEMBLY)5'-0" MAXIMUM

.

.

16"

ELEVATION VIEW

BACK

CEILING OROBSTRUCTION

.

18" MINIMUM

4" MINIMUM

WALL OROBSTRUCTION

TEST COCKS(TYPICAL)

AIR GAP FITTING

4" STANDPIPE.

WALL OROBSTRUCTION

FRONT

.

.

4" MINIMUM

24" MINIMUMTOP VIEW

TEST COCKS(TYPICAL)

WALL OROBSTRUCTION

NOTES:

1. REFER TO MATERIAL LIST FOR ASSEMBLY TYPE, AND CONFIGURATION.2. REFER TO PLANS FOR SIZE.

4" MINIMUM

THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLYOPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.

CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THECONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FORCOMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONSBEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THECATALOG NUMBER. THE FIRST MANUFACTURER IS THE BASIS OF DESIGN.

CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLESTATE, LOCAL AND GOVERNING AUTHORITIES.ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874

PLUMBING MATERIAL LIST (CONTINUED ON P501)

BFP-1

DESCRIPTION: BACK FLOW PREVENTER - REDUCED PRESSURE ZONE, BRONZE OR FDAAPPROVED EPOXY COATED CAST IRON CONSTRUCTION, SIZE SAME AS PIPE, NON-CORROSIVE INTERNAL PARTS, STAINLESS STEEL SPRINGS, DIFFERENTIAL PRESSURERELIEF VALVE BETWEEN SPRING-LOADED CHECK VALVES, SHUT-OFF VALVES ON INLETAND OUTLET OF UNIT, AIR GAP DRAIN FITTING, TEST PORTS WITH SHUT-OFF VALVES,FACTORY TESTED, RATED FOR 175 PSI AT 33°F TO 140°F, 15 PSI (MAXIMUM) PRESSUREDROP AT 10 FPS, ALL PARTS TO BE SERVICEABLE WITHOUT REMOVING UNIT FROM LINE,APPROVED BY USC FCCC & HR, AWWA C511-92, ASSE 1013, IAPMO AND SBCCI LISTED.

MANUFACTURER & CATALOG NO.: WATTS (009/909), CONBRACO (40-200), FEBCO (860),WILKINS (975XL/375)

CP-1

DESCRIPTION: CIRCULATING PUMP - 3/4" FLANGED CONNECTIONS, 1/6 HP, 115 VOLT, 1 PHASE,3,300 RPM, BRONZE CONSTRUCTION, PERMANENTLY LUBRICATED SEALED BEARINGS,MECHANICAL SEAL, OIL LUBRICATED, OPEN, DRIP-PROOF NON OVERLOADING MOTOR WITHTHERMAL OVERLOAD PROTECTION, UL LISTED, RATED FOR 125 PSIG AT 225 DEGREE F. CP-1SHALL DELIVER 2.5 GPM AT 38 FEET OF HEAD.

MANUFACTURER & CATALOG NO.: B & G PL SERIES, TACO, GRUNDFOS

DESCRIPTION: AQUASTAT - LINE VOLTAGE, ADJUSTABLE 90-180°F, WITH STRAPON SENSORBULB, UL LISTED. PROVIDE WITH TRANSFORMER IF REQUIRED. INSTALL PER MANUFACTURERSINSTRUCTIONS.

MANUFACTURER & CATALOG NO.: HONEYWELL, WHITE-RODGERS, JOHNSON CONTROLS, SAMEAS PUMP MANUFACTURER

DURING OCCUPIED HOURS, CP SHALL OPERATE VIA AQUASTAT. DURING UNOCCUPIED HOURS,CP SHALL NOT OPERATE. PROVIDE WITH TIME CLOCK FOR SCHEDULINGOCCUPIED/UNOCCUPIED HOURS.

BFP-2

DESCRIPTION: BACK FLOW PREVENTER - DUAL CHECK, STAINLESS STEEL BODY, HEAVY DUTYFDA APPROVED RUBBER DIAPHRAGMS, 3/8" SIZE, RATED FOR 150 PSI AT 33°F TO 110°F,APPROVED BY ASSE 1032.

MANUFACTURER & CATALOG NO.: WATTS (SD-2)

EE-1

DESCRIPTION: EMERGENCY EYE WASH - SWIVEL, DECK MOUNTED ADJACENT TO SINK. TWINCHROME PLATED SPRAY HEADS WITH CAPS AND RETAINING CHAINS/STRAPS MOUNTED ONBRASS SUPPLY ARMS, MINIMUM FLOW RATE OF 0.4 GPM AT 30 PSI, INTEGRAL FLOW CONTROLFITTING. BRASS PIPING AND FITINGS WITH BRASS/BRONZE STAY OPEN BALL VALVE WITH 1SECOND OR LESS ACTIVATION TIME. SINGLE ACTION ACTIVATION BY METAL FLAG.BRASS/BRONZE PIPING, FITTINGS AND VALVES TO BE CHROME PLATED OR CHEMICALRESISTANT POWDER COATED. UNIVERSAL IDENTIFICATION SIGN. ANSI Z358.1-2004 COMPLIANT.

MANUFACTURER & CATALOG NO.: BRADLEY S19-270B

INSTALL MV-1 PER MANUFACTURERS RECOMMENDATIONS IN ACCESSIBLE LOCATION UNDERSINK.

INSTALL EYEWASH TO THE RIGHT SIDE OF THE SINK AS INDICATED ON PLAN. THE HOLETHROUGH COUNTER TOP FOR THE EYEWASH SHALL BE 2-1/4" FROM THE RIGHT EDGE OF SINKCUTOUT AND 8-1/2" BACK FROM THE FRONT OF THE SINK CUTOUT.

ET-1

DESCRIPTION: EXPANSION TANK - WELDED BLACK STEEL CONSTRUCTION, GUARANTEEDAIRTIGHT AND LEAKPROOF WITH ASME STAMP, STAINLESS STEEL SYSTEM CONNECTION,HEAVY DUTY BUTYL DIAPHRAGM AND RIGID POLYPROPYLENE LINER MECHANICALLY BONDEDTO TANK TO PROVIDE A 100% NON-CORROSIVE WATER RESERVOIR. DIAPHRAGM AND LINERSHALL BE APPROVED FOR USE IN POTABLE WATER SYSTEMS. ALL WETTED COMPONENTS OFFDA APPROVED MATERIALS. TANK SHALL HAVE A WORKING TEMPERATURE OF 200°F AND AWORKING PRESSURE OF 150 PSIG. MINIMUM TANK VOLUME TO BE 14 GALLONS, MINIMUMACCEPTING VOLUME TO BE 9 GALLONS. FACTORY PRE-CHARGED TO 55 PSIG. PROVIDESTANDARD SCHRADER AIR VALVE FOR FIELD CHARGING.

MANUFACTURER & CATALOG NO.: AMTROL THERM-XTROL ST-C, TACO, WESSELS, ELBI, HIRISER

EWC-1

DESCRIPTION: ELECTRIC WATER COOLER - WALL HUNG, BI-LEVEL UNITS, PUSH BAR OR LEVEROPERATING CONTROLS ON FRONT AND BOTH SIDES, BUILT-IN FLOW REGULATOR, DRAIN &TRAP ASSEMBLY. 18 GAUGE STAINLESS STEEL CABINETS AND NON-SPLASH BASINS. STREAMPROJECTORS WITH PROTECTIVE HOODS. ADA COMPLIANT WITH APRON INSTALLED UNDERUPPER UNIT. 7.8 GPH OF WATER FROM 80 DEGREES F. TO 50 DEGREES F. AT 90 DEGREES F.ROOM TEMPERATURE. TANK TESTED TO 125 PSIG. 1/5 HP, 115 VOLT. ADJUSTABLETHERMOSTAT, MOUNTING ACCESSORIES, TANK DRAIN AND ANGLE STOPS. HERMETICCOMPRESSOR. CORD AND PLUG. COMPRESSOR TO OPERATE ON HFC-134a REFRIGERANT.EWC SHALL CONFORM TO ANSI A117.1-1986. WATER SYSTEM SHALL BE OF LEAD FREECONSTRUCTION.

ORIFICE SHALL BE MAXIMUM OF 36" ABOVE FLOOR ON LOWER UNIT AND 40" ABOVE FLOOR ONUPPER UNIT. BOTTOM OF APRON SHALL BE 27" ABOVE FLOOR ON LOWER UNIT IN COMPLIANCEWITH ADA SECTIONS 4.4 AND 4.15.

MANUFACTURER & CATALOG NO.: ELKAY EZSTL8C, OASIS, HALSEY-TAYLOR, ACORN, HAWS

FCO-1

DESCRIPTION: FLOOR CLEANOUT - CAST IRON THREADED ADJUSTABLE HOUSING, FLANGEDFERRULE WITH PLUG AND SECURED NICKEL BRONZE TOP. TOP STYLE SHALL MATCH FLOORFINISH AS FOLLOWS:

UNFINISHED FLOOR - ROUND SOLID SCORIATED TOPTILE OR TERRAZZO - ROUND RECESSED TOPCARPET - ROUND TOP WITH CARPET MARKER

MANUFACTURER & CATALOG NO.: ZURN Z1400, SMITH, WADE, JOSAM, WATTS, MIFAB

FD-1

DESCRIPTION: FLOOR DRAIN - 6" NICKEL BRONZE ADJUSTABLE TOP, 3" BOTTOM OUTLET, CASTIRON BODY, FLASHING COLLAR, DEEP SEAL TRAP, TRAP PRIMER CONNECTION.

MANUFACTURER & CATALOG NO.: ZURN Z415, SMITH, WADE, JOSAM, WATTS, MIFAB

OUTSIDE WALL

GRADE

FROM WATER MAIN

STEEL PIPE SEE SPECIFICATION

CAST IRON FLANGE ANDSPIGOT PIECE.

FLOOR

MECHANICAL WATERTIGHTSEAL. "LINK SEAL" BYTHUNDERLINE OR EQUAL.

CAST IRON BELL ANDSPIGOT PIPE.

TIE ROD (TYP)

MAIN ENTERING BLDG.

TIEROD (TYP).

CLAMP (TYP).

WATER MAIN (TYP).TEE ANCHOR

ANCHOR FOR LONG SPIGOT 1/4 BEND.

ONE-EIGHT BEND,BELL TO PIPE SPIGOTSPIGOT TO PIPE BELL

ONE-EIGHT BEND,

BEARING AREA

CONCRETE THRUSTBLOCK

ONE-QUARTER BEND

BEARING AREA

CONCRETE THRUSTBLOCK

Ø+

3"

(MIN

)

THRUST BLOCKS

AREA OF BEARING FACE OFCONCRETE THRUST BLOCKS

ANCHOR RODS

ROD AND CLAMP ANCHORAGE

PIPINGNOMINAL

SIZE(IN.)

CLAMPSIZE(IN.)

BOLTSIZE(IN.)

WASHER(IN.)

2 1/2" 1/2x2 5/8 5/8x3 1/2x3

CASTIRON STEEL

90°1/4 BEND

45°1/8 BEND

MECHANICAL JOINT

NUMBER OF RODS AND ROD SIZE(IN.)FOR ROD AND CLAMP ANCHORAGE

PUSH ON JOINT

45°1/8 BEND

90°1/4 BEND

TEE,HYDRANT CAP,

PLUG

TEE,HYDRANT CAP,

PLUG

23/4

23/4

23/4

23/4

23/4

23/4

PIPINGNOMINAL

SIZE(IN.)

MIN. SQ. FT.

CAST IRON AND DUCTILE IRON

TEES,PLUGS,CAPS,HYDRANTS

1/4BEND

1/8BEND

2 1/2" 3 32

BASIS: 2,000 LB/SQ.FT. SOIL RESISTANCE. 250 PSI WATER PRESSURE. CORRECTION FACTORS FOR OTHER SOILS:

SOFT CLAY........4 SAND.................2 SAND&GRAVEL...1.33 SHALE................0.4

NOTES:

1. AFTER INSTALLATION, PROTECT TIE RODS, BOLTS, NUTS, WASHERS AND CLAMPS AGAINST CORROSION WITH AHEAVY COAT OF ASPHALT MATERIAL.

2. THE LENGTH OF THE ROD REQUIRED WILL VARY WITH THE PIPE FITTING, AND MUST BE DETERMINED BY FIELDMEASUREMENT. IF THE DISTANCE BETWEEN THE JOINTS IS LESS THAN 12 FEET, EXTEND THE ANCHORAGE TOTHE SECOND BELL.

NOTES:

1. BOTH THRUST BLOCKING AND ANCHOR RODS ARE REQUIRED.2. REFER TO THE GOVERNING CODE AND NFPA 24 FOR ADDITIONAL REQUIREMENTS.

6" 1/2x2 5/8 5/8x3 1/2x32

3/42

3/42

3/42

3/42

3/42

3/46" 7 54

PLUMBING FIXTURE ROUGH-IN SCHEDULE

FIXTURE DESCRIPTIONDOMESTIC

C.W.(NOTE 3)

DOMESTICH.W.

(NOTE 3)

SANITARY(NOTE 3)

VENT(NOTE 3)

REMARKS

WATER CLOSET 1" - 4" 2" FLUSH VALVE

URINAL 3/4" - 2" 1 1/2" FLUSH VALVE - WASHDOWN

LAVATORY 1/2" 1/2" 1 1/4" 1 1/4" NOTE 1 & 2

SINK 3/4" 3/4" 1 1/2" 1 1/2" NOTE 1 & 2

MOP BASIN 3/4" 3/4" 3" 2" -

ELECTRIC WATER COOLER 1/2" - 1 1/2" 1 1/4" NOTE 1 & 2

FLOOR DRAIN - - 3" 2" -

FLOOR SINK - - 3" 2" -

HOSE BIBB 3/4" - - - -

NOTES:

1. SANITARY RISER UP IN WALL TO FIXTURE SHALL BE A MINIMUM OF 2".2. 1/2" CW AND HW APPLIES ONLY TO THE FINAL VERTICAL RISE-DROP TO EACH FIXTURE. BRANCH

PIPING TO VERTICAL RISE-DROP SHALL BE A MINIMUM OF 3/4" INCH UNLESS NOTED OTHERWISE.3. SIZES SHOWN ARE MINIMUMS. SIZES SHOWN ON THE DRAWING THAT ARE LARGER THAN THE

SIZES LISTED IN THE SCHEDULE SHALL DICTATE THE ROUGH-IN SIZE.4. 1/2" CW, 1/2" HW TO MIXING VALVE. 1/2" TEMPERED WATER FROM MIXING VALVE TO EYEWASH.

EMERGENCY EYEWASH 1/2" 1/2" - - NOTE 4

TRAP PRIMER 3/4" - - - -

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

P302

PLUMBING DETAILS ANDMATERIAL LIST

14215000

CD SET 02/28/14

LONGMONT, CO

NO SCALE1YARD CLEANOUT DETAIL

NO SCALE4ISLAND SINK VENT DETAIL

NO SCALE2BACKFLOW PREVENTER DETAIL

NO SCALE3UNDERGROUND WATER MAIN ANCHORING DETAIL

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

Page 14: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

REF.

DW

REF.

DW REF.

4" VTRSEE DETAIL6/P301 (TYP.)

CO

4" RD

SK-1

1" G-2 UP TO GAS REGULATORON ROOF TO SERVE RTU-1.REFER TO SHEET M121 FORGAS PIPE ROUTING.

SK-1

6" RD

CO

SK-1

FS-1

1" G-2 UP TO GASREGULATOR ON ROOFTO SERVE RTU-2. REFERTO SHEET M121 FOR GASPIPE ROUTING.

4" RD

SK-1

SK-1

4" ST (2,460)DN

CO

6" ST(6,190) DN

6" ST(6,190) DN

6"RD 4" RD

RD-3

1-1/4" HW DN

CO

4" RD

CO

RD-3INSTALL 18" ABOVEGRADE (TYP.)

CO

RD-34" STS (2,460) DN

CO

3" RD

2" V

2" V DN

HB-1

3"ST

4"STS (1,705)

6"STS (4,485) 6"STS (6,190)

1"C

W

1"CW

4"STS (1,705)

4

5

5

5

1

1

1

5

WC-2

WC-2

SK-2

GD-1

MB-1

0.5 GPM

4"ST (1,705)

0.5 GPM

6" RD

6"RD

SK-1

4" RD

WC-1

1 1/2" G-2(1,230 CFH @ 2PSI)

2"V

2" V DN

P121

1

WHA-1

3/4" HWC DN

4

CO

0.5 GPM

3/4" HWC, 3/4" HW, AND3/4" CW.

2"V

3

3

3

CO

3" ST DN

6"STS (4,485) 4"ST (1,705) CO

6"ST (4,485)

6"ST (6,190)

2"V

2 1/2"CW

1 1/4"HW

3/4"HWC

FS-1

4"ST (2460)

4"STS (2,460)

FD-1

FD-1

FCO-1

FD-1WC-2 WC-2

FD-1

WC-1

WC-1

WC-3

L-3

SK-1UR-2

UR-1

EWC-1

L-1(TYP.2)

L-1(TYP.2)

L-2

6" STS(6,190) DN

WCO-1

FD-1

FD-1

1"G-2

1"G

-2

FD-1

FD-1

FD-1

2 1/2"CW 3/4"HWC

1 1/4"HW

1 1/2"HW

HB-1

1"C

W

2 1/2"CW

HB-1

6" STS (6,190) DN

ET-1 CP-1

6" ST(4,485)

2"V 1"G-2

P121

2

L-1

UR-1

L-1

2

2"V

WCO-1

WCO-1

4" RD

6"ST (6,190)

WCO-1

WCO-1

3/4

"HW

C

A B B.7 C.9 D E.5 G G.6 H

1

1.2

3.3

2

2.2

2.3

2.7

2.8

3

3.8

4

K

SUPERVISEDPLAY

101

MEN

104

WOMEN

105

CLOSET

107

EXAM

109

EXAM

110

CLOSET

112

EXAM

113

EXAM

114

TOILET

102

CONFERENCE

143

CENTERMANAGER

142

TELE / DATA/ MECH

140

COPY ROOM

136

CENTERSUPERVISOR

139

ASSISTANTMANAGER

141

QUALITYMANAGER

137

CORRIDOR

144

HALL

111

PLASMAPROCESSING

150

CORRIDOR

138

RECEPTION

146

EDQ

145

EDQ

108

WAITING

148

DONORFLOOR

115

DONORPROCESSING

147

DONORFLOOR

135

HOST

149

HALL

106

VESTIBULE

100

FREEZER

132

ANTE ROOM

131

TRAININGSUPERVISOR

116

ISOTRAINING

117

BREAKROOM

118

LAB COATS

130

LOCKERROOM

129

MEN

126

WOMEN

127

CUSTODIAN

125

CORRIDOR

128

CORRIDOR

119

CORRIDOR

124

ELECTRICAL

123

BOILERROOM

122

BIOHAZARD

121

UTILITYROOM

120

PACKING

133

A.5 B.9 C E F G.9 J

3.2

1.8

CO

YCO-1

YCO-1

REFER TO 1/P302 FORYARD CLEANOUTDETAIL (TYP.)

6"STS (6,190)

1-1/4" CW DN

MV-2

8

7

2 1/2" CW

SEAL WALL PENETRATIONWEATHER TIGHT.

10

WH-1. REFER TO4/P301 FOR WATERHEATER AND MIXINGVALVE PIPING DETAIL.

TRAP PRIMER SHALL BEACCESSIBLE FROM THISSIDE.

1" NPW FOR IRRIGATION.

REFER TO FP111FOR CONTINUATION.

BFP-1

BFP-1

BFP-1

6" W DN

M

2 1/2"CW

3/4"HWC

2"HW

9

6

METER PROVIDED BYLOCAL UTILITYINSTALLED BY P.C.

3/4" NPW

2"V

1 1/4"G-2

3/4"HWC 3/4"HW

3/4"CW

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

P111

FIRST FLOOR PLAN -PLUMBING

14215000

CD SET 02/28/14

LONGMONT, CO

GENERAL PLUMBING NOTES

1. REFER TO P302 FOR PLUMBING FIXTUREROUGH-IN SCHEDULE AND REFER TOP121 FOR SYMBOLS LIST.

2. REFER TO 2/P301 FOR PIPE THROUGHNON-FIRE RATED WALL DETAIL.

3. PROVIDE A WCO AT BASE OF EACHSANITARY AND STORM RISER.

4. ALL STORM PIPING SHALL BE INSTALLEDAT A 1/8"/ FT. SLOPE UNLESS OTHERWISENOTED.

5. REFER TO 1/M121 FOR ROOF PLAN-MECHANICAL -PLUMBING.

6. STORM PIPING SHALL BE ROUTED HIGHBETWEEN AND THROUGH STRUCTURALJOISTS TO AVOID DUCTWORK CONFLICTS.

7. PIPING AND EQUIPMENT SHALL NOT BESUPPORTED OR ATTACHED TO ROOFINGDECK. ALL CONNECTIONS SHALL BE MADETO STRUCTURE OR CONTRACTORPROVIDED SUPPORTS.

8. REFER TO 3/P301 FOR ROOF DRAINDETAIL.

9. IF HOT WATER MAINS ARE INSTALLEDDIFFERENTLY THAN SHOWN ON PLANSUCH THAT THE TIME HOT WATERREACHES THE FIXTURE EXCEEDS 15SECONDS, CONTRACTOR SHALL PROVIDEANOTHER HOT WATER RECIRCULATIONLOOP, WITH REQUIRED VALVING ANDMAKE APPROPRIATE ADJUSTMENTS TOCP-1 AND MV-2 SIZING.

10. REFER TO 5/P301 FOR TRAP PRIMERDETAIL.

1. SECONDARY ROOF DRAIN SHALLDISCHARGE ONTO SPLASH BLOCKPROVIDED BY G.C.

2. GAS METER AND ASSOCIATED PRESSUREREDUCING VALVE INSTALLED ANDPROVIDED BY LOCAL UTILITY.CONTRACTOR SHALL COORDINATE EXACTREQUIREMENTS WITH LOCAL UTILITY.

3. PROVIDE CLEANOUTS AT BASE OF 2” VRISERS SERVING ISLAND SINKS.

4. CONNECT HWC TO HW UNDER SINK ANDPROVIDE SHUT-OFF VALVE IN HWC LINE INACCESSIBLE LOCATION. PROVIDE WHA-1IN CW AND HW UNDER SINK.

5. INSTALL EE-1 TO SIDE OF SINK. PROVIDEMV-1 SERVING EE-1. PROVIDE SHUT OFFVALVES IN PIPING BEFORE CONNECTIONTO SINK. COORDINATE EXACT LOCATIONWITH OWNER.

6. REFER TO 1/P301 FOR DOMESTIC WATERENTRANCE DETAIL.

7. ROUTE 1" G-2 TO SERVE WH-1.PROVIDE GR-3 AND SHUTOFF VALVE.ROUTE GAS PRESSURE REDUCING VALVEVENT TO EXTERIOR THROUGH ROOF.

8. 3/4" CW DN TO TP-1 SERVING UTILITYROOM 120, MEN 126, WOMEN 127 ANDBOILER ROOM 122 FLOOR DRAINS ANDSTANDPIPES.

9. 2" BFP-1 (DOMESTIC WATER) AND 3/4"BFP-1 (HEATING WATER MAKEUP)STACKED. PROVIDE 4" STANDPIPE UNDERBFP-1. REFER TO 2/P302 FOR BACKFLOWPREVENTER DETAIL .

10. 1" BFP-1 FOR IRRIGATION WATER.PROVIDE 4" STANDPIPE UNDER BFP-1.REFER TO 2/P302 FOR BACKFLOWPREVENTER DETAIL.

1/8" = 1'-0"1FIRST FLOOR PLAN - PLUMBING

NO R HT

KEYNOTES #

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

CP­01

V­01

V­02

V­03

V­04

V­05

Page 15: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

DW

DWREF.

WHA-1

2"CW

2"V3

2"C

W

5

2 1/2"CW

WCO-1

1 1/4"HW

4" VTRSEE DETAIL6/P301(TYP.)

2" V(TYP.2)

FCO-1 FORFUTURE WCLOCATION.

4" STS(2,460) DN

CO

2" SAN DN

STUB 1" CW OUT OF WALLAND CAP FOR FUTURE WC.

0.5GPM

4

2"V

1 1

/2"C

W 3"V

4"RD

WHA-1

4" RD

WHA-1

REFER TO P111FORCONTINUATION

2 1/2"CW

2" V DN

2" V(TYP.5)

1

0.5 GPM

3/4"HWC

1 1

/2"C

W

3/4

"HW

3/4"HWC

1"H

W

1 1/4"HW

CO

4" ST(2,460) DN

RD-3 INSTALL 18"ABOVE GRADE

3"V

2" SAN INWALL TO UR

2"V 2

"V

2"V

2" V DN

1-1/2" CW

2

4"ST (2,460)

4"STS (2,460)

WHA-2

2"V

3/4"HWC

WCO-1

3/4"CW

3/4"HW

3/4"HW

3/4"CW

2"C

W 3"V

TRAP PRIMER SHALL BEACCESSIBLE FROM THIS SIDE.

B B.7 B.9 C

1.8

1.4

1.5

2 1/2" V DN

4" VTR

2" SAN DN

4" VTR

ROUTE 1" G-2 TO SERVE BLR.PROVIDE GR-4 AND SHUT OFFVALVE. ROUTE GAS PRESSUREREDUCING VALVE VENT TOEXTERIOR THROUGH ROOF.

2" V DN

2" V DN

6

WCO-1

2"V

2"V

2 1/2"CW

3/4"HWC

2"HW

3"V

WCO-1

BLR-1

BLR-2

REFER TO P111 FORCONTINUATION.

REFER TO P111 FORCONTINUATION.

REFER TO P111 FORCONTINUATION.

REFER TO P111 FORCONTINUATION.

WCO-1

REFER TO 1/M131FOR CONTINUATION.

3/4" NPW

WHA-2 WHA-1 2"CW

2" V DN

2" V DN

3"V 3"V

PIPE DROPSSERVING BACKTO BACKLAVATORIES.

2"V 1 1/4"G-2

1" G-2

2" V

1"G-2 1 1/4"G-2

2"CW

1"HW

1"CW

3"V

2"V

WCO-1

1 1/4"HW 3/4"HWC 2"CW

H

3.3

2.7

2.8

3

KG.9 J

3.2

1 1

/4"G

-2

2"V

2 1/2"CW

3/4"HWC

2"HW

2"C

W 3

/4"H

WC

1 1

/4"H

W

2 1/2"CW

1 1/2"HW

3/4"HWC

REFER TO P111 FORCONTINUATION.

REFER TO P111 FORCONTINUATION.

1" G-2

3/4"HWC

3/4"HW 3/4"CW

NEW

PLUMBING SYMBOLS LISTSYMBOL: DESCRIPTION:

CW COLD WATER - POTABLE

G-2 NATURAL GAS - 2PSI

HW HOT WATER - POTABLE

HWC HOT WATER CIRCULATING - POTABLE

HW140 HOT WATER - POTABLE NO. INDICATES TEMP.

SAN SANITARY DRAINAGE

ST(1,000) STORM DRAINAGE (ROOF SQUARE FOOTAGE)

STS(1,000) STORM DRAINAGE SECONDARY (ROOF SQUARE FOOTAGE)

V VENT

PIPE DOWN

PIPE UP OR UP/DOWN

PIPE SERVING FIXTURE ON FLOOR ABOVE.(EXAMPLE: FD = FLOOR DRAIN)FD

PITCH PIPE IN DIRECTION

DIRECTION OF FLOW IN PIPE

RD-16"(1000)

ROOF DRAIN PROPERTIES SYMBOLSIZE (ROOF SQ. FT.)

SHUTOFF VALVE NORMALLY OPEN

SHUTOFF VALVE NORMALLY CLOSED

BALANCING VALVE (NO. INDICATES GPM)0.5

CHECK VALVE

SAFETY/RELIEF VALVE

THERMOMETER WITH WELL (DIAL TYPE)T

EWC ELECTRIC WATER COOLER

FCO FLOOR CLEANOUT

FD FLOOR DRAIN

FS FLOOR SINK

LAV LAVATORY

MB MOP BASIN

SK SINK

VTR VENT THROUGH ROOF

WC WATER CLOSET

WF WATER FILTER

WCO WALL CLEANOUT

YCO YARD CLEANOUT

CLEANOUT

HB HOSE BIB

RD ROOF DRAIN

UR URINAL

WHA WATER HAMMER ARRESTOR

CO

C.C. CIVIL CONTRACTOR

P.C. PLUMBING CONTRACTOR

H.C. HEATING CONTRACTOR

ELECTRICAL CONTRACTORE.C.

PRESSURE REDUCING VALVE

PRESSURE GAUGE

P

WATER HAMMER ARRESTOR

BFP BACKFLOW PREVENTER

STRAINER

GENERAL CONTRACTORG.C.

PRV PRESSURE REDUCING VALVE

NPW NON - POTABLE WATER

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

P121

ENLARGED PLAN -PLUMBING

14215000

CD SET 02/28/14

LONGMONT, CO

1/4" = 1'-0"1ENLARGED PLAN - PLUMBING

1. ROUTE 3/4" HW BELOW COUNTER TODISHWASHER. EXTEND SANITARY DRAINFROM DISHWASHER TO SANITARY RISERDOWNSTREAM OF SK P-TRAP.

2. 3/4" CW DN TO TP-1 SERVING TOILET 102,MEN 104, WOMEN 105 AND CLOSET 112 ANDFLOOR DRAINS.

3. PROVIDE WF-1 FAUCET ADJACENT TO SINKFAUCET. PROVIDE CW LINE UNDER THECABINET OFF CW LINE SERVING SINK.

4. SECONDARY ROOF DRAIN SHALL DISCHARGEONTO SPLASH BLOCK PROVIDED BY G.C.

5. CW PIPE SERVING EWC WILL BE TAPPED OFFFROM CW PIPE SERVING L-1 IN MENSRESTROOM.

6. ROUTE 3/4” HW BELOW COUNTER TODISHWASHER. EXTEND DRAIN FROMDISHWASHER TO SINK TAILPIECE. ROUTE3/4” CW & HW UNDER CABINET TO SINK.ROUTE SEPARATE 3/4” CW WITH BFP-2 TOCOFFEE MAKER AND ANOTHER 3/4" CW TAPOFF TO SERVE WF-1. WF-1 FAUCET SHALLBE MOUNTED NEXT TO SINK FAUCET.

GENERAL PLUMBING NOTES

1. REFER TO P302 FOR PLUMBING FIXTUREROUGH-IN SCHEDULE.

2. REFER TO 2/P301 FOR PIPE THROUGH NON-FIRE RATED WALL DETAIL.

3. PROVIDE A WCO AT BASE OF EACH SANITARYAND STORM RISER.

4. ALL STORM PIPING SHALL BE INSTALLED AT A1/8"/ FT. SLOPE UNLESS OTHERWISE NOTED.

5. REFER TO 1/M121 FOR ROOF PLAN-MECHANICAL -PLUMBING.

6. STORM PIPING SHALL BE ROUTED HIGHBETWEEN AND THROUGH STRUCTURALJOISTS TO AVOID DUCTWORK CONFLICTS.

7. PIPING AND EQUIPMENT SHALL NOT BESUPPORTED OR ATTACHED TO ROOFINGDECK. ALL CONNECTIONS SHALL BE MADE TOSTRUCTURE OR CONTRACTOR PROVIDEDSUPPORTS.

8. REFER TO 3/P301 FOR ROOF DRAIN DETAIL.9. IF HOT WATER MAINS ARE INSTALLED

DIFFERENTLY THAN SHOWN ON PLAN SUCHTHAT THE TIME HOT WATER REACHES THEFIXTURE EXCEED 15 SECONDS, CONTRACTORSHALL PROVIDE ANOTHER HOT WATERRECIRCULATION LOOP, WITH REQUIREDVALVING AND MAKE APPROPRIATEADJUSTMENTS TO CP-1 AND MV-2 SIZING.

10. REFER TO 5/P301 FOR TRAP PRIMER DETAIL.

NO R HT

KEYNOTES #

1/4" = 1'-0"2ENLARGED PLAN PLUMBING

NO R HT

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

V­04

V­05

Page 16: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

OVERFLOW ROOF DRAIN RD-2

INTERNAL WATER DAM

WATER CUTOFF MASTIC

ADJUSTABLE EXTENSIONUNDERDECK CLAMP

BEARING PAN(TYP.)

DOME STRAINER ROOF DRAINRD-1

ROOF MEMBRANE

ROOF INSULATION

ROOF DECK

SUMP (TYPICAL)

UNDERDECK CLAMP

NOTES:

1. REFER TO ARCHITECTURAL DRAWINGS FOR DISTANCE BETWEEN ROOF DRAIN AND OVERFLOWROOF DRAIN. SOME LOCATIONS REQUIRE ONLY RD-1.

2. INSULATE SUMP AND DRAIN PIPING. SEE SPECIFICATIONS.

INSTALL AN ESCUTCHEON AROUND PIPESEXPOSED IN FINISHED ROOMS. FOR ALLINSULATED PIPING INSTALL A PLASTIC JACKETEXTENDING 6" BEYOND THE WALL TO PROTECTINSULATION FROM DAMAGE.

MAKE A SMOOTH ROUND OPENING IN WALLSLIGHTLY LARGER THAN OUTSIDEDIAMETER OF THE PIPE AND INSULATION.

ADD A BEAD OF NON-HARDENINGCAULK IN THE ANNULAR SPACE.

NOTES:

1. THIS DETAIL APPLIES TO ALL INSTALLED PIPES. THE INTENTION IS TO CONTINUE THE INSULATION ANDVAPOR BARRIER THROUGH ALL PENETRATIONS. PERMIT THERMAL EXPANSION WITHOUT DAMAGINGINSULATION, AND TO SEAL AIRTIGHT AROUND INSULATED AND UNINSULATED PIPES FOR NOISETRANSMISSION CONTROL.

2. SEE SPECIFICATION SECTION 22 05 29 - PLUMBING FOR ADDITIONAL INFORMATION.

TT

T

T

HW

140

T

2" CW 1-1/2" CW

2" HW140

3/4" HWC

1-1

/2"

CW

2"

HW

140

3/4" HWC

2" HW

3/4" TEST VALVE WITHTHREADED OUTLET ANDCAP.

PIPE BYPASS DIRECTLY TOMIXING VALVE INLIEU OF CW INLET.

THERMOMETER IN WELL(0-200°F)

CP-1

3/4" HOT WATERCIRCULATION SET-UPBYPASS (NORMALLYCLOSED)

VACUUM BREAKER.WATTS MODEL 8A OR EQUAL.

VACUUM RELIEF VALVE.WATTS N36 OR EQUIVALENT(TYP.)

THERMOMETER IN WELL(TYP.)

A.S.M.E. PRESSUREAND TEMPERATURERELIEF VALVE (TYP.)

AQUASTAT AND TIMER

MIXING VALVE MV-2 . LOCATEBELOW TOP OF WATERHEATER OR PROVIDE 24" DEEPHEAT TRAP. VERIFY EXACTPIPING AND BALANCINGREQUIREMENTS WITHMANUFACTURER.

EXPANSION TANK ET-1

GAS INPUT(TYP.)

WATER HEATER,WH-1

DRAIN (TYP.)

CW

FLUE BY MC

COMBUSTION AIRINTAKE BY MC

PROVIDE HOUSE KEEPINGPAD PER SPECIFICATIONSECTION 22 05 29.

VENT PIPE

WATER CUTOFF MASTIC

PRE MOLDED PIPE SEAL

SPLICING CEMENT

LAP SEALANT

ROOF DECK

INSULATION, SEE SPECIFICATIONS.

INSULATION

STAINLESS STEELCLAMPING RING

EPDMMEMBRANE

PROVIDE SUPPORTAROUND PIPE ATROOF PENETRATION.

4" STAND PIPE

SEE SITE PLAN FORCONTINUATION.

TO STAND PIPE

TO STANDPIPE

P

HEATING WATER MAKEUP.SEE DETAIL 1/M131 FORCONTINUATION AND P111FOR LOCATION.

P.C.H.C.

2 1/2" CW

METER PROVIDED BYLOCAL UTILITY ANDINSTALLED BY P.C.

SEE DETAIL 2/P302

3/4" CW

BFP-1

BFP-1BUILDINGDOMESTICWATERSUPPLY

2-1/2" CW

M

REFER TO FP301 FORCONTINUATION.

4" FP

1/2" CONDUIT AND (2) 2x4JUNCTION BOXES FORREMOTE READOUTINSTALLATION. VERIFYLOCATION WITH UTILITY.

+ 48" ABOVEGRADE

M

P

1" FUTUREIRRIGATION

(6.5 GPM)

IRRIGATION METERPROVIDED BYLOCAL UTILITY ANDINSTALLED BY P.C.

PROVIDE 6" PVC PIPEFOR IRRIGATION PIPECONDUIT.

BFP-1

4" STAND PIPE

3/4"

COLD WATERMAIN

TRAP PRIMER.(TP-1)

FLOOR SLAB

1/2" PEX PIPE

MIN. 4" ABOVE TRAPSEAL ELEVATION

TO ADDITIONALFLOOR DRAINSOR TRAPS ASINDICATED ONP110.

REFER TO FLOOR PLANSFOR QUANTITY OF TRAPSTHAT ARE SERVED BYEACH TP-1

NOTE: CONTRACTOR SHALL PROVIDE ACCESS PANEL IN WALL TO PROVIDE ACCESS TO THIS FIXTURE.

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

P301

PLUMBING DETAILS

14215000

CD SET 02/28/14

LONGMONT, CONO SCALE3ROOF DRAIN DETAIL

NO SCALE2PIPE THROUGH NON-FIRE RATED WALL

NO SCALE4WATER HEATER AND MIXING VALVE PIPING DETAIL

NO SCALE6VENT PIPE THROUGH ROOF FLASHING

NO SCALE1DOMESTIC WATER ENTRANCE

NO SCALE5TRAP PRIMER DETAIL

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14

Page 17: M501jedibalancing.com/jedi_filecenter/data/BIOLIFE PLASMA-LONGMONT.pdf · linear diffuser schedule ... direct one exterior slot straight down to wash exterior wall/window and second

THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTORSHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS,WHETHER SPECIFIED OR NOT.

CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THECONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR COMPLETEDESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THEDESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRSTMANUFACTURER IS THE BASIS OF DESIGN.

CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE,LOCAL AND GOVERNING AUTHORITIES.ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874

PLUMBING MATERIAL LIST (CONTINUED FROM P302) PLUMBING MATERIAL LIST

FS-1

DESCRIPTION: FLOOR SINK - CAST IRON BODY, NICKEL BRONZE RIM AND GRATE, 12" ROUND, 3" BOTTOMOUTLET, DEEP RECEPTOR WITH ALUMINUM SEDIMENT BUCKET AND DOME STRAINER, ACID RESISTANTCOATED INTERIOR, SEEPAGE FLANGE WITH CLAMP, DEEP SEAL TRAP.

MANUFACTURER & CATALOG NO.: ZURN Z1950, SMITH, JOSAM, WATTS

L-1

DESCRIPTION: LAVATORY INTEGRAL TO COUNTER TOP - PROVIDED BY OTHERS.

DESCRIPTION: PROVIDE PRE-MANUFACTURED P-TRAP, STOP VALVE, AND SUPPLY LINE INSULATION KIT.ARMAFLEX WITH TAPE IS NOT ACCEPTABLE.

MANUFACTURER & CATALOG NO.: TRUEBRO HANDI LAV-GUARD, BROCAR PRODUCTS TRAP WRAP, MCGUIREPROWRAP, PLUMBEREX PRO-EXTREME

DESCRIPTION: LAVATORY TRIM - SENSOR ACTIVATED MIXING FAUCET, BATTERY POWERED, BRASSCONSTRUCTION, CHROME-PLATED FINISH, CONVENTIONAL SPOUT WITH VANDAL-RESISTANT AERATOR,SINGLE HOLE, PERFORATED DRAIN GRATE WITH 1-1/4" 17 GAUGE TAILPIECE, SOLID BRASS SOLENOID WITHBUILT-IN FILTER, UNDERCOUNTER SOLID BRASS MANUAL MIXING VALVE (MIXING VALVE SHALL NOT BE WYEPATTERN STYLE) WITH ADJUSTABLE TEMPERATURE LIMIT STOP AND INTEGRAL CHECK VALVES, WATERPROOF CONNECTORS AND CABLE.

MOUNT CONTROLS AND BATTERIES IN WATERPROOF VANDAL-RESISTANT ENCLOSURE BELOW LAVATORY.MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992 AND ASME/ANSISTANDARD A112.18.1M. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEON PLATE AS REQUIRED.

MANUFACTURER & CATALOG NO.: SLOAN EBF-615

L-3

DESCRIPTION: ACCESSIBLE LAVATORY - WALL MOUNTED, WHITE VITREOUS CHINA, 4" HIGHCONTOURED BACKSPLASH, 20" X 18", SINGLE FAUCET HOLE, QUARTER-TURN 3/8" CHROMEPLATED HEAVY BRASS ANGLE SUPPLY LOOSE KEY STOPS WITH CHROME PLATED SOFTCOPPER RISERS, 1-1/4" 17 GAUGE CAST BRASS "P" TRAP WITH CLEAN-OUT. DRILLED FORCONCEALED ARM CARRIER. FURNISH SUPPORT CARRIER BOLTED SECURELY TO FLOOR. TOPOF BASIN RIM TO BE MAXIMUM OF 24" ABOVE FLOOR. PROVIDE OFFSET DRAIN AND TAILPIECE.

MANUFACTURER & CATALOG NO.: AMERICAN STANDARD (0356.421), KOHLER (K-2007), SLOAN(SS-3103), TOTO (LT307), ZURN (Z5361)

DESCRIPTION: PRE-MANUFACTURED P-TRAP, STOP VALVE AND SUPPLY LINE INSULATION KIT.ARMAFLEX WITH TAPE IS NOT ACCEPTABLE.

MANUFACTURER & CATALOG NO.: TRUEBRO HANDI LAV-GUARD, BROCAR PRODUCTS TRAPWRAP, MCGUIRE PROWRAP, PLUMBEREX PRO-EXTREME

DESCRIPTION: LAVATORY TRIM - SENSOR ACTIVATED MIXING FAUCET, BATTERY POWERED,BRASS CONSTRUCTION, CHROME-PLATED FINISH, CONVENTIONAL SPOUT WITH VANDAL-RESISTANT AERATOR, SINGLE HOLE, PERFORATED DRAIN GRATE WITH 1-1/4" 17 GAUGETAILPIECE, SOLID BRASS SOLENOID WITH BUILT-IN FILTER, UNDERCOUNTER SOLID BRASSMANUAL MIXING VALVE (MIXING VALVE SHALL NOT BE WYE PATTERN STYLE) WITH ADJUSTABLETEMPERATURE LIMIT STOP AND INTEGRAL CHECK VALVES, WATER PROOF CONNECTORS ANDCABLE.

MOUNT CONTROLS AND BATTERIES IN WATERPROOF VANDAL-RESISTANT ENCLOSURE BELOWLAVATORY. MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992AND ASME/ANSI STANDARD A112.18.1M. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEONPLATE AS REQUIRED.

MANUFACTURER & CATALOG NO.: SLOAN EBF-615

MB-1

DESCRIPTION: MOP BASIN - MOLDED STONE, 24" X 24" X 10", WHITE WITH BLACK ACCENTS,STAINLESS STEEL DRAIN WITH COMBINATION DOME STRAINER AND LINT BASKET, 3" OUTLET.VINYL BUMPER GUARD ON EXPOSED SIDES. MOP HANGER, HOSE AND HOSE BRACKET. CAULKBETWEEN MOP BASIN AND WALL WITH SILICONE BASED CAULK. DEEP SEAL TRAP.

MANUFACTURER & CATALOG NO.: FIAT MSB-2424, WILLIAMS, SWAN, ZURN

TRIM - TWO HANDLE EXPOSED MIXING FAUCET, SINGLE WING HANDLES, POLISHED CHROMEPLATED, 3/4" HOSE THREAD SPOUT WITH INTEGRAL VACUUM BREAKER, WALL BRACE, PAILHOOK, INTEGRAL STOPS.

MANUFACTURER & CATALOG NO.: CHICAGO FAUCET 897, T & S BRASS, ZURN, DELTA, MOEN

MV-1

DESCRIPTION: THERMOSTATIC MIXING VALVE FOR EYEWASH ONLY FIXTURE. THERMOSTATICMIXING AND PRESSURE REGULATING VALVES TO DELIVER 0.4 GPM OF TEMPERED WATER (65-90DEGREES) WITH 5 PSI PRESSURE DIFFERENTIAL. BRONZE BODY CONSTRUCTION, COLDWATER BYPASS, INLET AND OUTLET THERMOMETERS, INTEGRAL CHECKSTOPS, MOUNTINGBRACKET. UNIT TO MEET ANSI STANDARD Z358.1.

PROVIDE SURFACE MOUNTED 18 GAUGE PAINTED STEEL CABINET WITH 16 GAUGE PAINTEDSTEEL LOCKING DOOR TO ENCLOSE VALVE, INLET STOPS, OUTLET THERMOMETER, ANDOUTLET VALVES.

MANUFACTURER & CATALOG NO.: LEONARD TA, BRADLEY, LAWLER, POWERS

MV-2

DESCRIPTION: THERMOSTATIC MIXING VALVE - MIXING VALVE FOR TEMPERED WATERCONTROL. ALL BRONZE/BRASS CONSTRUCTION, ROUGH BRASS FINISH. UNION INLETSWITH STRAINERS AND CHECK STOPS. DIAL THERMOMETER ON OUTLET. RATED FOR 8 GPMOUTPUT MAXIMUM AT 15 PSI DIFFERENTIAL AND 0.5 GPM OUTPUT MINIMUM. UNIT TO MIX 140DEGREE F. HOT WATER SUPPLY AND 40 DEGREE F. COLD WATER SUPPLY FOR 120 DEGREEF. OUTLET. SHALL CONFORM TO THE REQUIRMENTS OF ASSE 1017 AND SHALL BE ASSE1017 APPROVED.

PROVIDE SURFACE MOUNTED 18 GAUGE PAINTED STEEL CABINET WITH 16 GAUGE PAINTEDSTEEL LOCKING DOOR TO ENCLOSE VALVE.

PROVIDE FIELD ADJUSTMENT BY FACTORY AUTHORIZED REPRESENTATIVE.

MANUFACTURER & CATALOG NO.: LEONARD MODEL 210, APOLLO, BRADLEY, LAWLER,POWERS, SYMMONS, SPARCO, WATTS, WILKINS, HOLBY

PLUMBING MATERIAL LIST

RD-1

DESCRIPTION: ROOF DRAIN - CAST IRON BODY, 15" DIAMETER, BOTTOM OUTLET, FLASHINGCLAMP, GRAVEL STOP, UNDERDECK CLAMP, BEARING PAN, SECURED CAST IRON DOME,ADJUSTABLE EXTENSION TO MATCH INSULATION THICKNESS. OUTLET SIZE AS LISTED ONDRAWINGS.

MANUFACTURER & CATALOG NO.: ZURN Z-100, SMITH, WADE, JOSAM, WATTS, MIFAB

RD-2

DESCRIPTION: ROOF DRAIN - CAST IRON BODY, 15" DIAMETER, BOTTOM OUTLET, FLASHINGCLAMP, GRAVEL STOP, UNDERDECK CLAMP, BEARING PAN, SECURED CAST IRON DOME,EXTENSION TO MATCH INSULATION THICKNESS, 2" TALL INTERNAL STANDPIPE. OUTLET SIZEAS LISTED ON DRAWINGS.

MANUFACTURER & CATALOG NO.: ZURN Z-100, SMITH, WADE, JOSAM, WATTS, MIFAB

SK-2 (BREAK ROOM)

DESCRIPTION: SINK - STAINLESS STEEL, ADA DEPTH SINGLE COMPARTMENT WITH FAUCETDECK, 18 GAUGE, COMPLETELY UNDERCOATED, SELF-RIMMING, 25" (SIDE-TO-SIDE) x 21"(FRONT-TO-BACK) OVERALL SIZE 21" x 15-3/4" x 6" DEEP BOWL WITH 3-1/2" DIAMETER DRAINOUTLET, REMOVABLE STAINLESS STEEL BASKET STRAINER AND NEOPRENE STOPPER. 1-1/2" 17GAUGE CHROME PLATED BRASS TAILPIECE. CHROME PLATED CAST BRASS "P" TRAP WITHCLEANOUT. QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE SUPPLIES AND LOOSEKEY STOPS WITH CHROME PLATED SOFT COPPER RISERS.

MANUFACTURER & CATALOG NO.: ELKAY LRAD 2521

DESCRIPTION: SINK TRIM - SINGLE HANDLE MIXING FAUCET, CHROME PLATED, ALL BRASSCONSTRUCTION, CONVENTIONAL SWING SPOUT WITH 8" REACH AND AERATOR FLOW OUTLET,LEVER HANDLE WITH SUPPLIES AT 8" CENTERS, SPRAY HOSE WITH LEVER CONTROL. MAXIMUMFLOW TO BE 2.2 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992 AND ASME/ANSISTANDARD A112.18.1M. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEON PLATE ASREQUIRED.

MANUFACTURER & CATALOG NO.: DELTA 420, AMERICAN STANDARD, CHICAGO FAUCET,ELKAY, KOHLER, MOEN

UR-1

DESCRIPTION: ACCESSIBLE URINAL - WALL HUNG, FLUSH VALVE TYPE, WHITE VITREOUS CHINA,WASHOUT ACTION, WATER SAVING, 3/4" TOP SPUD, 2" OUTLET, ELONGATED RIM AND EXTENDEDSIDE SHIELDS. FURNISH SUPPORT CARRIER WITH TOP AND BOTTOM BEARING PLATES. BOLTCARRIER SECURELY TO FLOOR. TOP OF BOWL RIM SHALL BE 17" MAXIMUM ABOVE FLOOR INCOMPLIANCE WITH ADA SECTION 4.18.

MANUFACTURER & CATALOG NO.: AMER. STAND. 6501.010, KOHLER, ELJER, GERBER, TOTO,ZURN

FLUSH VALVE - EXPOSED, SENSOR OPERATED, BATTERY POWERED, CHROME PLATED 3/4" I.P.S.SCREWDRIVER STOP-CHECK VALVE, CHEMICAL RESISTANT MATERIAL, VACUUM BREAKER, WALLAND SPUD FLANGES, 1 GALLON PER FLUSH. OVER-RIDE BUTTON, RANGE ADJUSTMENT SCREW,BEAM DEFLECTOR, LOW BATTERY INDICATOR LIGHT. 3 YEAR WARRANTY.

MANUFACTURER & CATALOG NO.: SLOAN ROYAL 8186-1, DELANY, HYDROTEK, MOEN, TOTO

UR-2

DESCRIPTION: URINAL - WALL HUNG, FLUSH VALVE TYPE, WHITE VITREOUS CHINA, WASHOUTACTION, WATER SAVING, 3/4" TOP SPUD, 2" OUTLET, ELONGATED RIM AND EXTENDED SIDESHIELDS. FURNISH SUPPORT CARRIER WITH TOP AND BOTTOM BEARING PLATES. BOLTCARRIER SECURELY TO FLOOR. TOP OF BOWL RIM AT 22" ABOVE FLOOR.

MANUFACTURER & CATALOG NO.: AMER. STAND. 6501.010, KOHLER, ELJER, GERBER, TOTO,ZURN

FLUSH VALVE - EXPOSED, SENSOR OPERATED, BATTERY POWERED, CHROME PLATED 3/4"I.P.S. SCREWDRIVER STOP-CHECK VALVE, CHEMICAL RESISTANT MATERIAL, VACUUMBREAKER, WALL AND SPUD FLANGES, 1 GALLON PER FLUSH. OVER-RIDE BUTTON, RANGEADJUSTMENT SCREW, LOW BATTERY INDICATOR LIGHT. 3 YEAR WARRANTY.

MANUFACTURER & CATALOG NO.: SLOAN ROYAL 8186-1, DELANY, HYDROTEK, MOEN, TOTO

PLUMBING MATERIAL LIST

WC-1

DESCRIPTION: WATER CLOSET - FLOOR MOUNTED, FLUSH VALVE TYPE, WHITE VITREOUSCHINA, SIPHON JET, WATER SAVING, ELONGATED BOWL, 1-1/2" TOP SPUD, 10" ROUGH-IN,BOLT CAPS. TOP OF SEAT AT 16" TO 17" ABOVE FINISHED FLOOR. VERIFY EXACT MOUNTINGHEIGHT WITH MANUFACTURER.

MANUFACTURER & CATALOG NO.: AMER. STAND. 2234.015, KOHLER, ELJER, GERBER,TOTO,ZURN

WHITE EXTRA HEAVY OPEN FRONT INJECTION MOLDED SOLID ANTI-MICROBIAL PLASTIC SEAT,WITH CHECK HINGE AND STAINLESS STEEL OR PLATED STEEL POSTS AND NUTS.

MANUFACTURER & CATALOG NO.: BEMIS 3155C, CHURCH, BENEKE, OLSONITE

FLUSH VALVE - EXPOSED, SENSOR OPERATED, BATTERY POWERED, CHROME PLATED 1"I.P.S.SCREWDRIVER STOP-CHECK VALVE, CHEMICAL RESISTANT MATERIAL, VACUUMBREAKER, WALL AND SPUD FLANGES, 1.6 GALLONS PER FLUSH. OVER-RIDE BUTTON, RANGEADJUSTMENT SCREW, LOW BATTERY INDICATOR LIGHT. 3 YEAR WARRANTY.

MANUFACTURER & CATALOG NO.: SLOAN ROYAL 8111, DELANY, HYDROTEK, MOEN, TOTO

WC-2

DESCRIPTION: ACCESSIBLE WATER CLOSET - FLOOR MOUNTED, FLUSH VALVE TYPE, WHITEVITREOUS CHINA, SIPHON JET, WATER SAVING, ELONGATED BOWL, 1-1/2" TOP SPUD, BOLT CAPS.TOP OF SEAT AT 17" TO 19" ABOVE FINISHED FLOOR.

MANUFACTURER & CATALOG NO.: AMER. STAND. 3043.102, KOHLER, ELJER, GERBER, TOTO, ZURN

WHITE EXTRA HEAVY OPEN FRONT INJECTION MOLDED SOLID ANTI-MICROBIAL PLASTIC SEAT WITHCHECK HINGE AND STAINLESS STEEL OR PLATED STEEL POSTS AND NUTS.

MANUFACTURER & CATALOG NO.: BEMIS 3155C, CHURCH, BENEKE, OLSONITE

FLUSH VALVE - EXPOSED, SENSOR OPERATED, BATTERY POWERED, CHROME PLATED 1" I.P.S.SCREWDRIVER STOP-CHECK VALVE, CHEMICAL RESISTANT MATERIAL, VACUUM BREAKER, WALL ANDSPUD FLANGES, 1.6 GALLONS PER FLUSH. OVER-RIDE BUTTON, RANGE ADJUSTMENT SCREW, LOWBATTERY INDICATOR LIGHT. 3 YEAR WARRANTY.

MANUFACTURER & CATALOG NO.: SLOAN ROYAL 8111, DELANY, HYDROTEK, MOEN, TOTO

WC-3

DESCRIPTION: WATER CLOSET - FLOOR MOUNTED, FLUSH VALVE TYPE, WHITE VITREOUS CHINA,SIPHON JET, WATER SAVING, ELONGATED 10" HIGH BOWL, 1-1/2" TOP SPUD, 10" ROUGH-IN, BOLTCAPS. TOP OF BOWL RIM 10" ABOVE FINISHED FLOOR FOR USE BY CHILDREN.

MANUFACTURER & CATALOG NO.: AMER. STAND. 2282.010, KOHLER, ELJER, ZURN

WHITE EXTRA HEAVY OPEN FRONT INJECTION MOLDED SOLID ANTI-MICROBIAL PLASTIC SEATWITH CHECK HINGE AND STAINLESS STEEL OR PLATED STEEL POSTS AND NUTS.

MANUFACTURER & CATALOG NO.: BEMIS BB955C, BENEKE, KOHLER, OLSONITE, CHURCH

FLUSH VALVE - EXPOSED, SENSOR OPERATED, BATTERY POWERED, 1.6 GALLONS PER FLUSH,11-1/2" ROUGH-IN, CHROME PLATED, 1" I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH VANDALRESISTANT CAP, HIGH BACK PRESSURE VACUUM BREAKER, CLOG RESISTANT BYPASS,NON-HOLD-OPEN HANDLE, ADJUSTABLE TAILPIECE, SPUD COUPLING AND FLANGE, WALL FLANGEWITH SET SCREW, CHLORAMINE RESISTANT MATERIALS, ADA COMPLIANT, 3 YEAR WARRANTY.

MANUFACTURER & CATALOG NO.: SLOAN (81110AV), HYDROTEK, MOEN, TOTO

WCO-1

DESCRIPTION: WALL CLEANOUTS SHALL HAVE CAST IRON ACCESS BODY, GAS AND WATERTIGHTTHREADED PLUG, ROUND VINYL, PAINTABLE ACCESS COVER AND EXTENDED MACHINE SCREW.

MANUFACTURER & CATALOG NO.: ZURN Z-1441, SMITH, WADE, JOSAM, WATTS

WF-1

DESCRIPTION: BOTTLE FILLER AND UNDER SINK WATER FILTRATION SYSTEM - METALCONSTRUCTION, CARBON BLOCK FILTER TECHNOLOGY, ELECTRIC FILTER LIFE, FLOW SHALL BELIMITED TO 1 GPM, SYSTEM SHALL BE CERTIFIED TO ANSI/NSF 61/9, COMPLY WITH FEDERAL SAFEWATER DRINKING ACT, INSTALL FILTER BELOW COUNTER, CERTIFIED TO ANSI/NSF 61/9, COMPLYWITH FEDERAL SAFE WATER DRINKING ACT, AND SHALL COMPLY WITH NSF/ANSI STANDARD 42.

QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE SUPPLY AND LOOSE KEY STOP WITHCHROME PLATED SOFT, COPPER RISER. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEON PLATE ASREQUIRED.

SHALL BE PROVIDED WITH 5 YEAR LIMITED WARRANTY AGAINST LEAKS, DRIPS AND FINISH DEFECTS,FILTER SHALL HAVE 30 DAY LIMITED WARRANTY ON MANUFACTURER'S DEFECTS.

MANUFACTURER & CATALOG NO.: MOEN 77200 WITH CHOICE FLO 9600 FILTER OR OWNER/ENGINEERAPPROVED EQUAL

WH-1

DESCRIPTION: WATER HEATER - GAS FIRED, MINIMUM 94% EFFICIENT, SEALED COMBUSTION, GLASS-LINED, VERTICAL, WELDED STEEL, ASME STAMPED TANK, MULTIPLE ANODE RODS, VENT PIPING KIT,HIGH TEMPERATURE SENSOR IN TANK SHALL SHUT OFF ENTIRE GAS SUPPLY. 160 PSI WORKINGPRESSURE, METAL CABINET WITH BAKED ENAMEL FINISH, FIBERGLASS OR FOAM INSULATION.AUTOMATIC WATER THERMOSTAT AND BUILT-IN GAS REGULATING VALVE, ADJUSTABLETEMPERATURE RANGE. BRASS WATER CONNECTIONS, DIP TUBE, DRAIN AND RELIEF VALVES.ASME/CSA T&P RELIEF VALVE. SHALL MEET THE MINIMUM REQUIREMENTS OF THE NATIONALAPPLIANCE ENERGY CONSERVATION ACT, ASHRAE 90.1, AND ASHRAE 90A - GOVERNING ISSUES. ULLISTED. 3-YEAR WARRANTY.

PROVIDE 120 VOLT CIRCUIT FOR BLOWER AND CONTROLS.

100 GALLON CAPACITY, 150,000 BTUH INPUT NATURAL GAS, 192 GPH RECOVERY AT 90 DEGREE F.RISE.

SET WATER HEATER TEMPERATURE AT 140 DEGREES F.

SET WATER HEATER GAS PRESSURE AT 10.5" W.C. INCOMING GAS PRESSURE IS 2 PSI.CONTRACTOR SHALL ROUTE GAS REGULATING VALVE VENT THROUGH ROOF PER MANUFACTURER'SRECOMMENDATIONS.

MANUFACTURER & CATALOG NO.: A.O. SMITH BTH, BOCK, BRADFORD WHITE, RHEEM, STATE

WHA-1

DESCRIPTION: WATER HAMMER ARRESTER - PRE-CHARGED, BELLOWS TYPE, ALL STAINLESSSTEEL CONSTRUCTION, ASSE 1010 APPROVED, PDI CERTIFIED, 1-11 FIXTURE UNITS.

MANUFACTURER & CATALOG NO.: ZURN Z-1700-100, SMITH, WADE, JOSAM, WATTS, MIFAB

WHA-2

DESCRIPTION: WATER HAMMER ARRESTER - PRE-CHARGED, BELLOWS TYPE, ALL STAINLESS STEELCONSTRUCTION, ASSE 1010 APPROVED, PDI CERTIFIED, 33-60 FIXTURE UNITS.

MANUFACTURER & CATALOG NO.: ZURN Z-1700-300, SMITH, WADE, JOSAM, WATTS, MIFAB

YCO-1

DESCRIPTION: YARD CLEANOUT - ROUND DURA-COATED CAST IRON CLEANOUT AND DOUBLEFLANGED HOUSING, HEAVY DUTY SECURED SCORIATED DURA-COATED CAST IRON COVER WITHLIFTING DEVICE. BRONZE CLEANOUT PLUG AND GAS/WATERTIGHT SEAL. SIZE AS LISTED ONDRAWINGS.

MANUFACTURER & CATALOG NO.: ZURN Z-1474, SMITH, WADE, JOSAM, WATTS

GD-1

DESCRIPTION: GARBAGE DISPOSER - CONTINUOUS FEED, SINGLE DIRECTION, CORROSION PROTECTIONSHIELD, SERVICE WRENCH, STAINLESS STEEL GRINDING ELEMENTS, MANUALLY RESET OVERLOADPROTECTION, FULL 4 YEAR WARRANTY.

MANUFACTURER & CATALOG NO.: IN-SINK-ERATOR (BADGER 1), SINKMASTER, WASTE KING

ELECTRICAL REQUIREMENTS - 115V-1 PHASE, CORD AND PLUG, 3/4 HP MOTOR, 6.7 AMPS

SK-1

DESCRIPTION: SINK - STAINLESS STEEL, SINGLE COMPARTMENT WITH FAUCET DECK, 18GAUGE, SELF-RIMMING, 19-1/2" (SIDE-TO-SIDE) x 22" (FRONT-TO-BACK) OVERALL SIZE, 16" x16" x10" DEEP BOWL, COMPLETELY UNDERCOATED, 3-1/2" DIAMETER DRAIN OUTLET,REMOVABLE STAINLESS STEEL BASKET STRAINER AND NEOPRENE STOPPER. CHROMEPLATED CAST BRASS "P" TRAP WITH CLEANOUT, 1-1/2" 17 GAUGE CHROME PLATED BRASSTAILPIECE, QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE SUPPLIES ANDLOOSE KEY STOPS WITH CHROME PLATED SOFT COPPER RISERS.

MANUFACTURER & CATALOG NO.: ELKAY DLR 202210

DESCRIPTION: SINK TRIM - SENSOR OPERATED MIXING FAUCET, BATTERY POWERED,CHROME PLATED, ALL BRASS CONSTRUCTION, GOOSENECK SPOUT WITH 6" REACH ANDAERATOR, ADJUSTABLE SENSOR EYE, ADJUSTABLE TEMPERATURE CONTROL, AND MANUALOVERRIDE. WATER PROOF CONNECTORS AND CABLE. MOUNT CONTROLS AND BATTERIES INWATERPROOF VANDAL-RESISTANT ENCLOSURE BELOW LAVATORY. MAXIMUM FLOW TO BE 2.2GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992 AND ASME/ANSI STANDARDA112.18.1M. PROVIDE RESTRICTIVE DEVICE AS REQUIRED.

MANUFACTURER & CATALOG NO.: SLOAN SF-2150-4

HB-1

DESCRIPTION: HOSE BIBB - FREEZELESS WALL HYDRANT, AUTOMATIC DRAINING, VACUUM BREAKER, 3/4"MALE HOSE THREAD, BRASS VALVE BODY AND SEAT, NON-FERROUS METAL STEM, STANDARD FINISH, WALLCLAMP. FURNISH TWO KEY OPERATORS. ASSE 1019 APPROVED AND LISTED. MOUNT AT 18" ABOVE GRADEUNLESS NOTED OTHERWISE ON DRAWINGS.

MANUFACTURER & CATALOG NO.: WOODFORD 65, ZURN, JOSAM, WATTS, PRIER, MIFAB, SMITH

RD-3

DESCRIPTION: ROOF DRAIN OUTLET - LAMBS TONGUE DOWNSPOUT NOZZLE WITH BRONZEBODY AND INTEGRAL ANCHORING FLANGE, REMOVABLE STAINLESS STEEL SCREEN. OUTLETSIZE AS LISTED ON DRAWINGS.

MANUFACTURER & CATALOG NO.: ZURN Z-199, SMITH, WADE, JOSAM, WATTS, MIFAB

TP-1

TRAP PRIMER - ELECTRONIC SOLENOID ACTIVATED, FLUSH MOUNTED, MANUAL OVERRIDE,3/4" FNPT INLET AND 1/2" COMPRESSION OUTLET, BUILT-IN VACUUM BREAKER, CAPABLE OFSERVING 4 TO 30 TRAPS.

ELECTRICAL REQUIREMENTS - 120VAC, 3-WIRE CONNECTION

MANUFACTURER & CATALOG NO.: PRECISION PLUMBING PRODUCTS (PT)

L-2

DESCRIPTION: ACCESSIBLE LAVATORY - WALL MOUNTED, WHITE VITREOUS CHINA, 4" HIGH CONTOUREDBACKSPLASH, 20" X 18", SINGLE FAUCET HOLE, QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLESUPPLY LOOSE KEY STOPS WITH CHROME PLATED SOFT COPPER RISERS, 1-1/4" 17 GAUGE CAST BRASS "P"TRAP WITH CLEAN-OUT. DRILLED FOR CONCEALED ARM CARRIER. FURNISH SUPPORT CARRIER BOLTEDSECURELY TO FLOOR. PROVIDE 29" MINIMUM CLEARANCE FROM FLOOR TO BOTTOM OF APRON INCOMPLIANCE WITH ANSI A117.1-1986 AND ADA SECTION 4.19. TOP OF BASIN RIM TO BE MAXIMUM OF 34"ABOVE FLOOR IN COMPLIANCE WITH ADA SECTION 4.19. PROVIDE OFFSET DRAIN AND TAILPIECE.

MANUFACTURER & CATALOG NO.:AMERICAN STANDARD (0356.421), KOHLER (K-2007), SLOAN (SS-3103), TOTO(LT307), ZURN (Z5361)

DESCRIPTION: PRE-MANUFACTURED P-TRAP, STOP VALVE AND SUPPLY LINE INSULATION KIT. ARMAFLEXWITH TAPE IS NOT ACCEPTABLE.

MANUFACTURER & CATALOG NO.: TRUEBRO HANDI LAV-GUARD, BROCAR PRODUCTS TRAP WRAP,MCGUIRE PROWRAP, PLUMBEREX PRO-EXTREME

DESCRIPTION: LAVATORY TRIM - SENSOR ACTIVATED MIXING FAUCET, BATTERY POWERED, BRASSCONSTRUCTION, CHROME-PLATED FINISH, CONVENTIONAL SPOUT WITH VANDAL-RESISTANT AERATOR,SINGLE HOLE, PERFORATED DRAIN GRATE WITH 1-1/4" 17 GAUGE TAILPIECE, SOLID BRASS SOLENOID WITHBUILT-IN FILTER, UNDERCOUNTER SOLID BRASS MANUAL MIXING VALVE (MIXING VALVE SHALL NOT BE WYEPATTERN STYLE) WITH ADJUSTABLE TEMPERATURE LIMIT STOP AND INTEGRAL CHECK VALVES, WATERPROOF CONNECTORS AND CABLE.

MOUNT CONTROLS AND BATTERIES IN WATERPROOF VANDAL-RESISTANT ENCLOSURE BELOW LAVATORY.MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992 AND ASME/ANSISTANDARD A112.18.1M. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEON PLATE AS REQUIRED.

MANUFACTURER & CATALOG NO.: SLOAN EBF-615

GR-4

DESCRIPTION: GAS PRESSURE REGULATOR - CAST IRON BODY, INTERNAL PRESSURE RELIEF, THREADEDCONNECTIONS, ADJUSTABLE PRESSURE SETTING, TIGHT SHUTOFF.

2PSI INLET PRESSURE, 14" W.C. OUTLET PRESSURE, 210 CFH CAPACITY.

MANUFACTURER & CATALOG NO.: FISHER HSR, ITRON, SENSUS, MAXITROL

GR-3

DESCRIPTION: GAS PRESSURE REGULATOR - CAST IRON BODY, INTERNAL PRESSURE RELIEF, THREADEDCONNECTIONS, ADJUSTABLE PRESSURE SETTING, TIGHT SHUTOFF.

2PSI INLET PRESSURE, 14" W.C. OUTLET PRESSURE, 150 CFH CAPACITY.

MANUFACTURER & CATALOG NO.: FISHER HSR, ITRON, SENSUS, MAXITROL

GR-2

DESCRIPTION: GAS PRESSURE REGULATOR - CAST IRON BODY, INTERNAL PRESSURE RELIEF, THREADEDCONNECTIONS, ADJUSTABLE PRESSURE SETTING, TIGHT SHUTOFF.

2PSI INLET PRESSURE, 14" W.C. OUTLET PRESSURE, 160 CFH CAPACITY.

MANUFACTURER & CATALOG NO.: FISHER HSR, ITRON, SENSUS, MAXITROL

GR-1

DESCRIPTION: GAS PRESSURE REGULATOR - CAST IRON BODY, INTERNAL PRESSURE RELIEF, THREADEDCONNECTIONS, ADJUSTABLE PRESSURE SETTING, TIGHT SHUTOFF.

2PSI INLET PRESSURE, 14" W.C. OUTLET PRESSURE, 500 CFH CAPACITY.

MANUFACTURER & CATALOG NO.: FISHER HSR, ITRON, SENSUS, MAXITROL

Drawing

Previous Issue Dates

Project

Owner

All reports, plans, specifications, computerfiles, field data, notes and other documentsand instruments prepared by OPN Architects,Inc. as instruments of service shall remain theproperty of OPN Architects, Inc. OPNArchitects, Inc. shall retain all common law,statutory and other reserved rights, includingthe copyright thereto.

© 2014 OPN Architects, Inc.

CEDAR RAPIDS - DES MOINES - MADISON

OPN ARCHITECTS

OPN Project No.

18 19

A

A R C H I T E C T S

200 5TH AVENUE SE SUITE 201CEDAR RAPIDS, IA 52401319-363-6018 PHONE319-363-7349 [email protected]

1716151413121110987654321

B

C

D

E

F

G

H

J

K

L

M

N

Revision Dates

Sheet Issue Date

BIO-LIFE PLASMASERVICES CENTER

CONSTRUCTION SET

P501

PLUMBING MATERIALLIST

14215000

CD SET 02/28/14

LONGMONT, CO

TM

ENGINEERINGCONSULTANTSExperience you can build on.

PROJECT #

515.334.9906 FAX: 515.334.9908www.kjww.com

2882 106th STREETDES MOINES, IOWA 50322

KJWW ENGINEERING RESERVES PROPRIETARY

SHALL NOT BE USED OR REPRODUCED FORANY OTHER PROJECT WITHOUT THE EXPRESSWRITTEN APPROVAL AND PARTICIPATION OFKJWW ENGINEERING. © 2014 KJWW, P.C.

RIGHTS, INCLUDING COPYRIGHTS, TO THISDRAWING AND THE DATA SHOWN THEREON.SAID DRAWING AND/OR DATA ARE THEEXCLUSIVE PROPERTY OF KJWW ENGINEERING

13.0096.14


Recommended