POLYPHASE CIRCUITS
Introduction:
Three-phase systems are commonly used in generation, transmission and distribution of electric
power. Power in a three-phase system is constant rather than pulsating and three-phase motors start
and run much better than single-phase motors. A three-phase system is a generator-load pair in
which the generator produces three sinusoidal voltages of equal amplitude and frequency but
differing in phase by 120 from each other. As shown below:
(a) Schematic layout of generator of 3-
phase
(b) Waveform of induced emf in R,Y,B
coils
(c) phasor Diagram
VR = Vm sin ωt
VY = Vm sin (ωt-120o)
VB = Vm sin (ωt-240o)
OR
VR = Vm 0
VY = Vm -120o
VB = Vm 120o
Algebraic or Vector sum at any time of all emfs
V = VR + VY + VB = 0
Phase sequence: Order in which emfs or induced current attain their peak value, i.e. here
it is R – Y – B or sometimes also specified as a-b-c
Fig.1
A three-phase system is shown in Fig 1. In a special case all impedances are identical
Za = Zb = Zc = Z
Such a load is called a balanced load and is described by equations
IV
ZI
V
ZI
V
Za
ab
bc
c .
Using KCL, we have
I I I IZ
V V Vn a b c a b c 1
,
where
.02
3j
2
1
2
3j
2
11V240sinj240cos120sinj120cos1V
ee1VVVV
mm
240j120j
mcba
Setting the above result into (4), we obtain
In 0 .
Since the current flowing through the fourth wire is zero, the wire can be removed (see
Fig.2)
Fig. 2
The system of connecting the voltage sources and the load branches, as depicted in Fig. 2, is called
the Y system or the star system. Point n is called the neutral point of the generator and point n’ is
called the neutral point of the load.
Each branch of the generator or load is called a phase. The wires connecting the supply to the
load are called the lines. In the Y-system shown in Fig. 2 each line current is equal to the
corresponding phase current, whereas the line-to-line voltages ( or simply line voltages ) are not
equal to the phase voltages.
Methods of interconnection of three phase circuit. (i) Y- connection or Star connection (ii) Δ – connection or Delta connection
Y- connection:
n’ n
Ia Z Va
Ic Z Vc
Ib Z Vb
Useful Definitions:
(i) Phase voltage and Phase current: Voltage of any one of phases w.r.t. neutral or
star point
(ii) Line voltage and Line current: Voltage between any two phase and current in
any line
(iii) Balanced system or load: Voltage in all three phase are equal in magnitude
and displaced from each other by equal angle
(iv) Unbalanced system or load: if one of two above condition or both is not
satisfied it is known as unbalanced system of load.
Now we consider the Y-connected generator sources (see Fig. 3).
Fig.3
The phasors of the phase voltages can be generally written as follows
.
V V V e
V Ve
V Ve
a mj
bj
cj
120
240
o
o
We determine the line voltages Vab, Vbc, Vca ( see Fig.3). Using KVL, we obtain
.e3Ve2
3
2
3V
2
3j
2
3V
2
3j
2
11VVVV
30j
a3
3tanj
22
a
aabaab
1
Thus,
V V eab aj 3 30o
.
Holds and similarly we obtain
Vca
c Vbc
Vab
n
a Va
Vc
b Vb
V V ebc bj 3 30o
V V eca cj 3 30o
.
The phasor diagram showing the phase and line voltages is shown in Fig.4.
Fig.4
Thus, the line voltages Vab, Vbc, Vca form a symmetrical set of phasors leading by 30 the set
representing the phase voltages and they are 3 times greater.
V V V Vab bc ca a 3 .
Relationship between line and phase quantities in delta connection:
(i) Voltage:
The voltage between two lines is VL. As shown in fig.
the phase coils are connected between lines, the
magnitude of phase voltage will be equal to
magnitude of line voltage VL.
ERY = EYB = EBR =VL = VPh
(ii) Current:
Balanced 3 phase delta connected load
Phasor diagram
Since the system is balanced the magnitude of the phase currents i.e. IRY, IYB, IBR are equal
but they are displayed 120o from one another as shown in figure. The currents are assumed
as lagging behind the respective phase voltages by an angle of Φ.
Similarly IR, IY and IB are currents flowing through line R, Y and B respectively. The values
of line current can be easily determined by applying KCL at terminal R, Y and B. according
to KCL; IR = IRY - IBR = IRY + (-IBR)
= √(IRY2
+ IBR2 + 2 IRY * IBR cos 60o)
But IRY = IYB = IBR = IPh
Hence IR = √3 IPh
Thus IR = IY= IB= √3 IPh
Expression of Power:
Apparent Power:
For three phase power S = 3 *VPh * IPh
Here VPh=VL and IPh= (IL/ √3)
Hence S = 3 * VL * (IL/ √3)
= √3 VL IL
Active power P:
For three phase power P = 3 *VPh * IPh* cos Φ
= √3 VL IL cos Φ
Power measurement:
Three wattmeter method:
This method is employed for measurement of power in 3 phase, 4 wire system. It can
also be employed in 3 phase 3 wire delta connected load, where power consumed by
each load is required to be determined separately.
Two wattmeter method:
The connection diagram for the measurement of power in a three-phase circuit using
two wattmeters is given in Fig. This is irrespective of the circuit connection – star or
delta. The circuit may be taken as unbalanced one, balanced type being only a special
case. Please note the connection of the two wattmeters. The current coils of the
wattmeters, 1 & 2, are in series with the two phases, R &B , with the pressure or voltage
coils being connected across Y R - and Y B - respectively. Y is the third phase, in which
no current coil is connected.
Measurement of power by Two wattmeter method:
One wattmeter method:
The circuit diagram for measuring power for a balanced three-phase load is shown in
Fig. The only assumption made is that, either the neutral point on the load or source
side is available. The wattmeter measures the power consumed for one phase only. The
total power is three times the above reading, as the circuit is balanced.
Measurement of power by single wattmeter method:
Comments on two wattmeter method:
a) When the balanced load is only resistive, i.e. power factor is 1( cos Φ = 0 ), the readings
of the two wattmeters are equal and positive.
b) When power factor is 0.5 lagging, one of the wattmeter W2 gives zero reading and whole
the power is measured by wattmeter W1.
c) When power factor is more than 0.5 but less than unity, both wattmeter reads positive, W1
reads more while W2 reads less than W1.
d) When power factor is less than 0.5 but more than zero, wattmeter W2 gives negative
whereas wattmeter W1 gives positive.
e) When power factor is zero, the readings of two wattmeters are equal in magnitude but in
opposite direction.
Per-Phase Analysis
In balanced three-phase circuits the currents and voltages in each phase are equal in magnitude and
displaced from each other by 120. This characteristic results in a simplified procedure to analyze balanced
three-phase circuits. In this procedure it is necessary only to compute results in one phase and subsequently
predict results in the other phases by using the relationship that exists among quantities in the other phases.
Example 1
Three balanced three-phase loads are connected in parallel. Load 1 is Y-connected with an impedance of
150 + j50 / ; load 2 is -connected with an impedance of 900 + j600 / ; and load 3 is 95.04 kVA at
0.6 pf leading. The loads are fed from a distribution line with an impedance of 3 + j24 / . The magnitude
of the line-to-neutral voltage at the load end of the line is 4.8 kV.
a) Calculate the total complex power at the sending end of the line.
b) What percent of the average power at the sending end of the line is delivered to the load?
Solution
The per-phase equivalent circuit is first constructed. For load 1, a Y-connected balanced load, the per-
phase impedance is 150 + j50 . For load 2, a -connected balanced load, the per-phase impedance is the
equivalent Y-connected load which is Z/3 = 300 + j200 . We will represent load 3 in terms of the
complex power it absorbs per-phase. This is given by
VAj
jS
344,25008,19
8.06.03
95040/3
The voltage across the per-phase equivalents of these loads has been specified as 4800 V which is the line-
to-neutral voltage at the load end.
The per-phase equivalent circuit is shown below in Figure bellow:
Fig.: Per-Phase Equivalent Circuit
Jj50 Jj200
Van
Iline-to-line
+ +Aa
Nn
3
150 300
Jj24
S3/4800 0 V
Iline
)(949.143725.45
)(7046.118369.43
28.596.33846.70769.116.98.28
4800
344,25008,19
200300
4800
50150
4800
rmsA
rmsAj
jjj
j
jj
I
In the above step, the total current I is obtained by summing the individual currents through the three
loads. For loads 1&2, we use the expression Z
VI , and for load 3 the current is determined using
VI
S.
In the distribution line,
VARXIQ
WRIP
effloss
effloss
34.224,148243725.4533
04.528,1833725.4533
22
22
In each load,
)(02.338,1062003846.70769.113
02.507,1593003846.70769.113
)(240,138506.98.283
720,4141506.98.283
2
2
2
2
2
1
2
1
absVARjQ
WjP
absVARjQ
WjP
)(546,168251,636
032,768.0040,95
024,576.0040,95
3
3
endloadVAjS
VARQ
WP
total
Check :
148.9710004.779,649
251,631%
34.770,31604.779,649
34.224,14804.528,18546,168251,631
546,168251,63174046.118369.4348003
P
VAj
VAjjS
VAjjS
sending
total
Example 2
A balanced 230 volt (rms) three phase source is furnishing 6 kVA at 0.83 pf lagging to two - connected
parallel loads. One load is a purely resistive load drawing 2 kW. Determine the phase impedance of the
second load.
Solution
The total complex power absorbed by the load is given by
VAjS 5577.083.0106 3
Note it is specified in the problem that
VAjS 58.33464980
5577.083.0cossinsin
83.0cos
1
Load 1 absorbs VAjS 020001
As a result, Load 2 must absorb VAjSS 58.334629801
The power absorbed by Load 2 per phase is VAjjS 5266.111533.99338.334629803
1/2
Z
VS LL
2
/2
Hence,
449.26552.235266.111533.993
2302
jj
Z
449.26552.23 jZ
************