Power Circuit Breakers
Theory and Operation
2
AgendaBreaker fundamentals– Types of Breakers– Ratings– Design Tests
Application & Operations– Application Considerations– Operation Considerations
2
3
Introduction
What does a breaker do?Circuit interruptionTypes of breakers
4
Power Circuit BreakersWaits for current zero to extinguish arc
Typical interrupting times 3-8 cycles
Attempts to prevent arc re-ignition (The interrupter must build up dielectric faster than the recovery voltage builds up)
Commutes plasma by removing energy which is in the form of heat
3
5
Power Circuit Breakers
The ability of the breaker to interrupt fault current is determined by two things:– the magnitude of the fault current– the magnitude and rate of rise of the voltage
across the contacts after the current goes out (both 60 hertz and transient voltages)
6
InterruptersArcing Contacts and medium (oil or gas) flow
4
7
Oil Interrupters:
I
Current zeros
Recoveryvoltage
t
Arc goes out
8
Types of Breakers:
OilAir blastAir magneticSF6 gasVacuumOthers
5
9
Circuit Breaker Year of Manufacture
0
20
40
60
80
100
120
140
1923
1949
1954
1959
1964
1969
1974
1979
1984
1989
1994
1999
Year
Num
ber airblast
vacuumairmagSF6OCB
10
Interrupting MediumsOil – Mineral oil is used to extinguish the arc and to
insulate the live parts to ground– Generally free breathing– May use a single tank or multiple tanks
Air Blast– Stored air is used to blow out the arc and cool
contacts– Very loud operation
6
11
InterruptersOil
12
InterruptersOil
7
13
Oil Breaker (Westinghouse 345G)
14
Oil Breaker(McGraw Edison CG38)
8
15
Interrupting Mediums
Air Magnetic – A magnetic field is place perpendicular to the
plane of the arc which drives the arc into insulating fins
– Sensitive to moisture– Compact
SF6 (Sulfur Hexa-flouride gas)– Multi-pressure or puffer operation– High speed
16
InterruptersAir Magnetic
Arcing Contacts
InsulatingFins
MagneticField
9
17
InterruptersSF6 Gas
18
Puffer Interrupter
10
19
Self-Blast Interrupter
20
Gas Breaker (ABB PM)
11
21
Gas Breaker (Westinghouse SP)
22
Gas Breaker (ABB PM)
12
23
Interrupting Mediums
Vacuum – Contacts incased in a sealed bottle which is under
vacuum– Compact
Others– Gas mixtures (N2, SF6 etc.)– Water– Solid State– Super-conductor???
24
Vacuum
13
25
Vacuum (GE PVDB-1)
26
Ratings
ContinuousInterruptingClose & latch – momentaryVoltage ratingsSwitching scenarios
14
27
Power Circuit Breaker Ratings
28
Power Circuit Breaker RatingsContinuous (load current)…typically 600,1200, 2000 or 3000 amperesANSI C37.04 Definition: The established limit of current in rms amps at rated frequency that it shall be required to carry continuously without exceeding temperature limits of its components.Select a breaker with a Continuous Current rating greater than the peak load current.
15
29
Power Circuit Breaker Ratings
30
Power Circuit Breaker Ratings
Interrupting Rating (fault current)…typically 20, 31.5, 40, or 63 kilo-amperesANSI C37.04 Definition: The highest value of the symmetrical component of the three-phase, short-circuit current in rms amps that the circuit breaker shall be required to interrupt at rated maximum voltage and on the standard operating duty.Select a breaker with a fault duty greater than the maximum available fault current.
16
31
Power Circuit Breaker Ratings
Cannot forget X/R!Standards assume X/R < 17.What do you do if X/R > 17?Delay opening.Increase kA interrupting requirements for the breaker.
32
Power Circuit Breaker Ratings
K Factor: Applies only to OCBs.Defined as the ratio of the rated maximum voltage to the lower limit of the range of operating voltage.The interrupting capabilities are inversely proportional to the operating voltage (i.e. a reduced voltage results in an increase in the current interrupting capability).Reference Engineering Manual Section 2 SI 4.0 –Application Guideline – AC High Voltage Circuit Breakers Based on Short Circuit Capability Criteria.
17
33
Power Circuit Breaker RatingsClose and Latch rating is expressed as a multiple of the rated short-circuit current.The maximum current for which the breaker will close and latch….stay closed.2.6 x rated short circuit current (Interrupting not Momentary).
34
Power Circuit Breaker RatingsRated Maximum Voltage is the highest rmsphase-to-phase voltage for which the circuit breaker is designed.The upper limit for operation.Typically 15kV, 84kV (25kV, 38kV, 46kV and 69kV), 145kV, 245kV, 362kV and 550kV
18
35
Power Circuit Breaker RatingsBasic Impulse Level (BIL) ,expressed in kV, is the maximum electrical impulse level (lightning strike) that the breaker can be exposed to and not flashover either internally or externally.Actual design BIL does not reflect the maximum impulse that can be generated because the magnitude of the impulse depends on the location of the strike.The designed BIL reflects the insulation coordination practices used in the design of electrical systems (Source: High Voltage Circuit Breakers: Design and Applications)
36
Power Circuit Breaker Ratings
A circuit breaker is a tie between two networks
Source Load
Source Load
TRV
19
37
Fault: faultV=0
TRV
v
t
Fault
i
Breaker opens
2 per unitTransient Recovery
Voltage
z
38
Power Circuit Breaker Ratings
The ability of the breaker to interrupt fault current is determined by the magnitude of the fault current and also by the rate of rise of the voltage across the breaker contacts as it opensTransient Recovery Voltage (TRV): is the transient voltage that appears across the contacts while interrupting a faulted circuit.
20
39
Transient Recovery Voltage:
t
V
TRVline = 1 - cos t/sqrtLC
Total TRV = bus - line
Initial Rate of rise Crest recovery
voltage
TRV
fault
TRVbus = 1 - cos t/sqrtLC
bus line
Time in hundreds of microseconds
40
Power Circuit Breaker Ratings
Standard C37.011 defines the TRV envelope that breakers must meet for rated current (Maximum TRV per standards is 2.4 per unit of rated breaker voltage)
21
41
42
Power Circuit Breaker Ratings
Some breakers were able to clear bus faults with no problem but were unable to interrupt faults a short distance out on the line even though the fault current was less than the bus fault. The cause of this becomes clear when the transient recovery voltage is analyzed for both scenarios:
22
43
Power Circuit Breaker Ratings
Short Line Fault: A fault that occurs a relatively short distance downstream from the circuit breaker on its load side.Also known as a kilometric fault since this is generally considered to be the critical distance for maximum severity of the recovery voltage. Allegheny specifies full nameplate interrupting for a 90% short line fault
44
Vbus
TRV= Vbus - Vline
TRV
Vbus Vline
Short Line Fault:
Vline
23
45
t
V
Fault i
Very steep rate of rise for TRV caused by the short length of the transmission line
TRV
46
t
V
Fault i
Adding shunt capacitance attenuates the rise
24
47
TRV= Vbus - Vline
TRV
Vbus Vline
Short Line Fault:Insert bushing shunt capacitance on line side
48
Bushing shunt capacitance
25
49
Power Circuit Breaker Ratings
50
Short Line Fault:– SF6 breakers up to 50 kA don’t require external
shunt bushing capacitors. – Most breakers rated at 63 kA require external
shunt bushing capacitors to meet Short Line Fault requirements of the standards.
– Mainly breakers above 100 kV.
Power Circuit Breaker Ratings
26
51
Power Circuit Breaker Ratings
1200pf, 3000pf and 12,000pf are typical values for external bushing capacitors.
52
Power Circuit Breaker Ratings
Operating Duty Cycle: A series of circuit breaker operations and time delays.Defined by ANSI as:O-15 SEC-CO-3 MIN.-CO.The first time delay can be reduced to 0.3 seconds for breakers designed for high-speed reclosing.0.3 seconds is the mechanical resetting time.
27
53
Power Circuit Breaker Ratings
A derating factor R is applied to OCBsbased on their reclosing duty.This does not apply to SF6 breakers.
54
Power Circuit Breaker Ratings
Asymmetrical Current Rating: Maximum RMS current, at rated frequency, including DC component against which the breaker is required to operate.Function of the system X/RStandards assume X/R of 17
28
55
Power Circuit Breaker Ratings
Momentary Rating:– Short time current rating– The current, equal to the rated symmetrical
short circuit current, that the breaker is required to carry for a specified time.
– Time = Allowable Tripping Delay
56
Application of Circuit Breakers
29
57
Switching Surges:
Z0= L/C
Voltage doubles when closing in on an open line = 2 P.U. at open line terminal
Assume that High Speed Re-closing traps a negative 1 P.U. charge on the line. Then when the breaker re-closes the maximum voltage at the open end can approach a maximum of 3.5 - 4.0 P.U. for multiple reflections depending on damping (R):
Trapped charge = -1.0 P.U.
3.5 P.U.
58
Breaker Applications
Closing resistors are used to reduce the switching surge created at the far end of a transmission line when it is energized– Once breaker is closed the resistor is
removed from the circuit.– Not designed to handle continuous load
current or fault current.– AP uses closing resistors on EHV breakers– Typical value: 400-450 ohms.
30
59
Closing resistors:
Z0= L/CRc
Rc
Z0 V0
Z0
(Rc + Z0)V0 = VS
bypass
VS
60
Z0 V0
Z0 (Rc + Z0)
V0R first close
V0B second close
Rc > Z0
V0R first close
V0B second close
Rc < Z0
Rc
V0R first close = V02 second close
Rc = Z0
2.0 P.U.
2.0 P.U.
2.0 P.U.Optimum closing resistor size = surge impedance
Closing resistors:
V0 = VS
31
61
Breaker Applications
Grading capacitors.– Applied on circuit breakers with more than one
gap per pole– Grading capacitors are applied across the
contacts of each interrupter to divide the recovery voltage during interruption
– Insures that the first gap to interrupt does not see the whole TRV
62
500kv PM breaker
Grading capacitors