+ All Categories
Home > Documents > Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN...

Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN...

Date post: 23-Jan-2021
Category:
Upload: others
View: 4 times
Download: 0 times
Share this document with a friend
36
Contents Description Page Table 1. Revision notes ................................................................ 3 Table 2. Breaker catalog number convention ............................................... 4 Table 3. Electronic trip unit catalog number convention....................................... 4 Table 4. Symmetrical RMS interruption ratings I cu (kA) for each breaker frame ..................... 5 Table 5. Curve notes .................................................................. 5 Labels Figure 1. Power Defense frame 5 trip unit front labels ........................................ 5 PXR electronic trip unit curves Figure 2. 800A frame PXR 20D / PXR 25 - I 2 t long delay and flat short delay . ..................... 6 Figure 3. 1200A frame PXR 20D / PXR 25 - I 2 t long delay and flat short delay . .................... 7 Figure 4. 1600A frame PXR 20D / PXR 25 - I 2 t long delay and flat short delay . .................... 8 Figure 5. 800A frame PXR 20 - I 2 t long delay and flat short delay . .............................. 9 Figure 6. 1200A frame PXR 20 - I 2 t long delay and flat short delay . ............................ 10 Figure 7. 1600A frame PXR 20 - I 2 t long delay and flat short delay . . ............................ 11 Figure 8. 800A frame PXR 20D / PXR 25 - I 2 t long delay and I 2 t short delay . ..................... 12 Figure 9. 1200A frame PXR 20D / PXR 25 - I 2 t long delay and I 2 t short delay . .................... 13 Figure 10. 1600A frame PXR 20D / PXR 25 - I 2 t long delay and I 2 t short delay . ................... 14 Figure 11. 800A frame PXR 20 I 2 t long delay and I 2 t short delay ................................ 15 Figure 12. 1200A frame PXR 20 I 2 t long delay and I 2 t short delay . ............................. 16 Figure 13. 1600A frame PXR 20 I 2 t long delay and I 2 t short delay . ............................. 17 Figure 14. 800A frame PXR 20D / PXR 25 - I 4 t long delay and flat short delay . ................... 18 Figure 15. 1200A frame PXR 20D / PXR 25 - I 4 t long delay and flat short delay . . . . . . . . . . . . . . . . . . . 19 Figure 16. 1600A frame PXR 20D / PXR 25 - I 4 t long delay and flat short delay .................... 20 Figure 17. PXR 20D / PXR 25 ground (earth) flat delay . . ...................................... 21 Figure 18. PXR 20D / PXR 25 - ground (earth) I 2 t delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Figure 19. PXR 20 - ground (earth) flat delay . .............................................. 23 Figure 20. PXR 20 - ground (earth) I 2 t delay . . .............................................. 24 Effective November 2019 Supersedes February 2018 Technical Data TD012067EN Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC
Transcript
Page 1: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

ContentsDescription Page

Table 1. Revision notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Table 2. Breaker catalog number convention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Table 3. Electronic trip unit catalog number convention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Table 4. Symmetrical RMS interruption ratings Icu (kA) for each breaker frame . . . . . . . . . . . . . . . . . . . . . 5Table 5. Curve notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Labels Figure 1. Power Defense frame 5 trip unit front labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

PXR electronic trip unit curves Figure 2. 800A frame PXR 20D / PXR 25 - I2t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . . . 6Figure 3. 1200A frame PXR 20D / PXR 25 - I2t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . . 7Figure 4. 1600A frame PXR 20D / PXR 25 - I2t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . . 8Figure 5. 800A frame PXR 20 - I2t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Figure 6. 1200A frame PXR 20 - I2t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Figure 7. 1600A frame PXR 20 - I2t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Figure 8. 800A frame PXR 20D / PXR 25 - I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . . . . . . 12Figure 9. 1200A frame PXR 20D / PXR 25 - I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . . . . . 13Figure 10. 1600A frame PXR 20D / PXR 25 - I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . . . . 14Figure 11. 800A frame PXR 20 I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Figure 12. 1200A frame PXR 20 I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Figure 13. 1600A frame PXR 20 I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Figure 14. 800A frame PXR 20D / PXR 25 - I4t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . 18Figure 15. 1200A frame PXR 20D / PXR 25 - I4t long delay and flat short delay. . . . . . . . . . . . . . . . . . . 19Figure 16. 1600A frame PXR 20D / PXR 25 - I4t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . 20Figure 17. PXR 20D / PXR 25 ground (earth) flat delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Figure 18. PXR 20D / PXR 25 - ground (earth) I2t delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Figure 19. PXR 20 - ground (earth) flat delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Figure 20. PXR 20 - ground (earth) I2t delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Effective November 2019Supersedes February 2018Technical Data TD012067EN

Time current curves Power Defense MCCBFrame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

Page 2: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

2

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 21. 800A frame PXR 20D / PXR 25 - instantaneous and override. . . . . . . . . . . . . . . . . . . . . . . . . . 25Figure 22. 1200A frame PXR 20D / PXR 25 - instantaneous and override. . . . . . . . . . . . . . . . . . . . . . . . 26Figure 23. 1600A frame PXR 20D / PXR 25 - instantaneous and override. . . . . . . . . . . . . . . . . . . . . . . . 27Figure 24. 800A frame PXR 20 - instantaneous and override. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Figure 25. 1200A frame PXR 20 - instantaneous and override. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Figure 26. 1600A frame PXR 20 - instantaneous and override. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Figure 27. PXR 20 / PXR 20D / PXR 25 - maintenance mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Figure 28. 400A frame PXR 20D / PXR 25 - I2t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . 32Figure 29. 400A frame PXR 20D / PXR 25 - I2t long delay and I2t short delay. . . . . . . . . . . . . . . . . . . . . 33Figure 30. 400A frame PXR 20D / PXR 25 - I4t long delay and flat short delay. . . . . . . . . . . . . . . . . . . . 34Figure 31. 400A frame PXR 20D / PXR 25 - instantaneous and override. . . . . . . . . . . . . . . . . . . . . . . . . . 35

Page 3: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

3

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Table 1. Revision notes

ote: N Unless noted below, all curves remain unchanged from their prior revision.

Revision Figure number Page Date1 Power Defense frame 5 initial release 12/14/2018

2 Edits to curve notes 02/06/2019

3 Short delay tolerances adjusted

Ground delay tolerances adjusted

400A frame curves added

2-16

17-20

28-31

11/07/2019

Page 4: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

4

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

This information is provided only as an aid to understand the catalog numbers.

It is not to be used to build catalog numbers for circuit breakers or trip units as all combinations may not be available.

Table 2. Circuit breaker catalog number convention

ote: N 1 See catalog for ## (protection type and available configured options).

Table 3. Electronic trip unit catalog number convention

ote: N IEC standard breakers include the CE mark; GB standard breakers include the CCC mark.

This information is provided only as an aid to understand the catalog numbers.

It is not to be used to build catalog numbers for circuit breakers or trip units as all combinations may not be available.

PDG5 3 M 0800 P5M J

Poles

2 = 2 pole

3 = 3 pole

4 = 4 pole (programmable N)

Interrupting rating designator

kA at 480 V (UL)

(kA) at 415 V (IEC)

K = 50 50

M = 65 70

N = 85 70

P = 100 100

T = 150 -

Continuous current rating

0400 = 400 A

0800 = 800 A

1200 = 1200 A

1600 = 1600 A (IEC / GB)

Terminals included

N = No terminals (imperial tapped conductors)

M = No terminals (metric tapped conductors)

Breaker family

PDG5 = Frame 5 global UL / CSA / IEC / GB

PDF5 = Frame 5 global-100% UL / CSA / IEC / GB (uses PDG trip units)

PDC5 = Frame 5 IEC / GB

Trip unit type

E## = PXR 20 (1)

D## = PXR 20D (1)

P## = PXR 25 (1)

KNS = Molded case switch

Poles

3 = 3 poles

4 = 4 poles with programmable neutral protection

Trip unit

PXR = Electronic trip unitAmpere frame rating

0400 = 400 A frame

0800 = 800 A frame

1200 = 1200 A frame

1600 = 1600 A frame

ETU trip unit style

B = -

E = PXR 20

D = PXR 20D

P = PXR 25

Style family

PDG5 = Frame 5 global UL / CSA / IEC / GB for PDG and PDF breakers

PDC5 = Frame 5 IEC / GB for PDC breakers

Features

N = None

R = Relays

Z = ZSI, relays

M = Modbus, relays

C = CAM interface, relays

D = Modbus, CAM interface, relays

W = ZSI & Modbus

X = ZSI, CAM interface. relays

Y = ZSI, Modbus, CAM interface, relays

ETU protection style

1 = -

2 = LSI

3 = LSIG

4 = LSI ARMS

5 = LSIG ARMS

PDG5 x PXR 3 0800 D 2 W

Accessories

x = Breaker accessory

Page 5: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

5

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Table 4. Symmetrical RMS interruption ratings Icu (kA) for each breaker frame

UL / CSA IEC / CCC

Voltage Frame 240V 480V 600V 240V 415V 440V 480V 525V 690V

Globally rated

PDG5xK 85 50 25 85 50 35 35 25 10

PDG5xM 100 65 35 100 70 50 50 30 15

PDG5xN 150 85 50 150 70 70 65 35 20

PDG5xP 200 100 65 200 100 100 85 40 35

Globally rated(UL 100%)

PDF5xK 85 50 25 85 50 35 35 25 10

PDF5xM 100 65 35 100 70 50 50 30 15

PDF5xN 150 85 50 150 70 70 65 35 20

PDF5xP 200 100 65 200 100 100 85 40 35

IEC / GB only

PDC5xK - - - 85 50 35 35 25 10

PDC5xM - - - 100 70 50 50 30 15

Table 5. Curve notes

1. These curves apply for 50Hz and 60Hz applications

2. The maximum voltage rating for the frame style is stated in Table 4.

3. These curves are comprehensive for Power Defense style circuit breakers including frame sizes, ratings and constructions stated.

4. The total clearing times shown include the response time for the trip unit, the breaker opening and the interruption of the current. The bottom of the time band is the minimum commit to trip time.

5. The end of the curve is determined by the application or the interrupting rating of the circuit breaker.

8. All electronic trip units have an over temperature protection feature that will trip the breaker when the internal temperature of the ETU is over 105ºC

9 All time current data based on 3 phase testing.

Labels

PXR 25 and PXR 20D – unit with LSIG protection and maintenance mode pictured

PXR 20 – unit with LSIG protection and maintenance mode pictured

Figure 1. Power Defense frame 5 trip unit front labels.

ote: N Trip unit drawings in Figure 1 are representative of the face plates provided. Values on the trip unit dials will change based upon the specific breaker and trip unit. Refer to the time current curve of the breaker or the PXR User Guide for the specific settings.

Page 6: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

6

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Curves

Figure 2. 800A frame PXR 20D / PXR 25 - I2t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 800A PXR20D / PXR25 - I2t Long Delay and Flat Short Delay Curves

0.5

1.5 12

0.05

tr setting range

Isdsetting range

tsd setting range

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDC 800 A

Min. 320 AMax. 800 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10 A.

2. Long delay time settings adjustable from 0.5s - 14s at steps of 0.1s with +0%/-30% toler-ance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 12x at steps of 0.1x with ±5% tolerance.

5. Short delay time settings adjustable from 0.050s – 0.500s at steps of 0.010s with tolerances as follows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 7: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

7

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 3. 1200A frame PXR 20D / PXR 25 - I2t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 1200A PXR20D / PXR25 - I2t Long Delay and Flat Short Delay Curves

0.5

1.5 12

0.05

tr setting range

Isdsetting range

tsd setting range

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDC 1200 A

Min. 500 AMax. 1200 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10 A.

2. Long delay time settings adjustable from 0.5s - 24s at steps of 0.1s with +0%/-30% toler-ance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 12x at steps of 0.1x with ±5% tolerance.

5. Short delay time settings adjustable from 0.050s – 0.500s at steps of 0.010s with tolerances as follows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay set-tings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 8: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

8

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 4. 1600A frame PXR 20D / PXR 25 - I2t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 1600A PXR20D / PXR25 - I2t Long Delay and Flat Short Delay Curves

0.5

1.5 12

0.05

tr setting range

Isdsetting range

tsd setting range

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDC 1600 A

Min. 800 AMax. 1600 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10 A.

2. Long delay time settings adjustable from 0.5s - 20s at steps of 0.1s with +0%/-30% toler-ance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 12x at steps of 0.1x with ±5% tolerance.

5. Short delay time settings adjustable from 0.050s – 0.500s at steps of 0.010s with tolerances as follows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 9: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

9

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 5. 800A frame PXR 20 - I2t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 800A PXR20 - I2t Long Delay and Flat Short Delay Curves

0.5

1.5

6

54

3

12

2

8

0.4

0.05

0.1

0.2

0.3

0.15

10

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -PXR 20

Irsetting

PDG 800 A

1 320 A2 350 A3 400 A4 450 A5 500 A6 550 A7 600 A8 630 A9 700 A10 800 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance.2. Long delay time settings as shown have +0%

/-30% tolerance.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve.4. Short delay pickup settings as shown have ±5%

tolerance.5. Short time delay slopes are shown with toler-

ance. 6. If the long delay time is projected to be faster

than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 10: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

10

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 6. 1200A frame PXR 20 - I2t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 1200A PXR20 - I2t Long Delay and Flat Short Delay Curves

0.5

1.5

6

54

3

12

2

8

0.4

0.05

0.1

0.2

0.3

0.15

10

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -PXR 20

Irsetting

PDG 1200 A

1 500 A2 550 A3 600 A4 630 A5 700 A6 800 A7 900 A8 1000 A9 1100 A10 1200 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance.2. Long delay time settings as shown have +0%

/-30% tolerance.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve.4. Short delay pickup settings as shown have ±5%

tolerance.5. Short time delay slopes are shown with toler-

ance. 6. If the long delay time is projected to be faster

than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 11: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

11

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 7. 1600A frame PXR 20 - I2t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Sec

onds

Current in Multiples of Long Delay Setting (Ir)

PD5 1600A PXR20 - I2t Long Delay and Flat Short Delay Curves

0.5

1.5

6

54

3

12

2

8

0.4

0.05

0.1

0.2

0.3

0.15

10

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -PXR 20

Irsetting

PDG 1600 A

1 800 A2 900 A3 1000 A4 1100 A5 1200 A6 1250 A7 1300 A8 1400 A9 1500 A10 1600 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance.2. Long delay time settings as shown have +0%

/-30% tolerance.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve.4. Short delay pickup settings as shown have ±5%

tolerance.5. Short time delay slopes are shown with toler-

ance. 6. If the long delay time is projected to be faster

than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 12: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

12

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 8. 800A frame PXR 20D / PXR 25 - I2t long delay and I2t short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 800A PXR20D / PXR25 - I2t Long Delay and I2t Short Delay Curves

1.5

0.067

0.3

8

tr setting range

Isdsetting range

tsd setting range

12

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDG 800 A

Min. 320 AMax. 800 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10A.

2. Long delay time settings adjustable from 0.5s - 14s at steps of 0.1s with +0%/-30% tolerance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 12x at steps of 0.1x with ±5% tolerance.

5. Short delay I2t slope time settings adjustable from 0.067s – 0.300s at steps of 0.010s with tolerances as follows: I2t slope time delay settings 0.300s to 0.200s have tolerances of +0/-30%, time delay set-tings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.067s have toler-ances of +0%/-50%. After approximately 8x the I2t slope will go flat and those times have tolerances as follows: time delay settings 0.300s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +0/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 13: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

13

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 9. 1200A frame PXR 20D / PXR 25 - I2t long delay and I2t short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 1200A PXR20D / PXR25 - I2t Long Delay and I2t Short Delay Curves

1.5

0.067

0.3

8

tr setting range

Isdsetting range

tsd setting range

12

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDG 1200 A

Min. 500 AMax. 1200 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10 A.

2. Long delay time settings adjustable from 0.5s - 24s at steps of 0.1s with +0%/-30% tolerance.

3 If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 12x at steps of 0.1x with ±5% tolerance.

5. Short delay I2t slope time settings adjustable from 0.067s – 0.300s at steps of 0.010s with tolerances as follows: I2t slope time delay settings 0.300s to 0.200s have tolerances of +0/-30%, time delay set-tings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.067s have toler-ances of +0/-50%. After approximately 8x the I2t slope will go flat and those times have tolerances as follows: time delay settings 0.300s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +0/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 14: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

14

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 10. 1600A frame PXR 20D / PXR 25 - I2t long delay and I2t short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 1600A PXR20D / PXR25 - I2t Long Delay and I2t Short Delay Curves

1.5

0.067

0.3

8

tr setting range

Isdsetting range

tsd setting range

12

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDG 1600 A

Min. 800 AMax. 1600 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10 A.

2. Long delay time settings adjustable from 0.5s - 20s at steps of 0.1s with +0%/-30% tolerance.

3 If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 12x at steps of 0.1x with ±5% tolerance.

5 Short delay I2t slope time settings adjustable from 0.067s – 0.300s at steps of 0.010s with tolerances as follows: I2t slope time delay settings 0.300s to 0.200s have tolerances of +0/-30%, time delay set-tings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.067s have toler-ances of +0/-50%. After approximately 8x the I2t slope will go flat and those times have tolerances as follows: time delay settings 0.300s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +0/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 15: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

15

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 11. 800A frame PXR 20 I2t long delay and I2t short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 800A PXR20 - I2t Long Delay and I2t Short Delay Curves

1.5 6

0.067

0.3

0.15

3 42

12

85

10

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release

-PXR 20Irsetting

PDG 800 A

1 320 A2 350 A3 400 A4 450 A5 500 A6 550 A7 600 A8 630 A9 700 A10 800 A

Notes: 1. Long delay pickup is 110% of the Ir set-

ting with ±5% tolerance.2. Long delay time settings as shown have

+0% /-30% tolerance.3. If thermal memory is enabled, trip times

may be shorter than indicated in this curve.

4. Short delay pickup settings as shown have ±5% tolerance.

5. Short delay I2t slope time settings are as follows: I2t slope time delay setting 0.300s has a tolerance of +0/-30%, time delay setting 0.150s has a tolerance of +0/-40% and time delay setting 0.067s has a tolerance of +0/-50%. After approximately 8x the I2t slope will go flat and those times have tolerances as follows: time delay setting 0.300s has a tolerance of +0/-20%, time delay setting 0.150s has a tolerance of +0/-40% and time delay setting 0.067s has a tolerance of +0/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 16: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

16

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 12. 1200A frame PXR 20 I2t long delay and I2t short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 1200A PXR20 - I2t Long Delay and I2t Short Delay Curves

1.5 6

0.067

0.3

0.15

3 42

10

8

5 12

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert

Release -PXR 20Irsetting

PDG 1200 A

1 500 A2 550 A3 600 A4 630 A5 700 A6 800 A7 900 A8 1000 A9 1100 A10 1200 A

Notes: 1. Long delay pickup is 110% of the Ir

setting with ±5% tolerance.2. Long delay time settings as shown

have +0% /-30% tolerance.3. If thermal memory is enabled, trip

times may be shorter than indicated in this curve.

4. Short delay pickup settings as shown have ±5% tolerance.

5. Short delay I2t slope time settings are as follows: I2t slope time delay setting 0.300s has a tolerance of +0/-30%, time delay setting 0.150s has a tolerance of +0/-40% and time delay setting 0.067s has a tolerance of +0/-50%. After approximately 8x the I2t slope will go flat and those times have tolerances as follows: time delay setting 0.300s has a tolerance of +0/-20%, time delay setting 0.150s has a tolerance of +0/-40% and time delay setting 0.067s has a tolerance of +0/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 17: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

17

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 13. 1600A frame PXR 20 I2t long delay and I2t short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 1200A PXR20 - I2t Long Delay and I2t Short Delay Curves

1.5 6

0.067

0.3

0.15

3 42

10

8

5 12

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert

Release -PXR 20Irsetting

PDG 1200 A

1 500 A2 550 A3 600 A4 630 A5 700 A6 800 A7 900 A8 1000 A9 1100 A10 1200 A

Notes: 1. Long delay pickup is 110% of the Ir

setting with ±5% tolerance.2. Long delay time settings as shown

have +0% /-30% tolerance.3. If thermal memory is enabled, trip

times may be shorter than indicated in this curve.

4. Short delay pickup settings as shown have ±5% tolerance.

5. Short delay I2t slope time settings are as follows: I2t slope time delay setting 0.300s has a tolerance of +0/-30%, time delay setting 0.150s has a tolerance of +0/-40% and time delay setting 0.067s has a tolerance of +0/-50%. After approximately 8x the I2t slope will go flat and those times have tolerances as follows: time delay setting 0.300s has a tolerance of +0/-20%, time delay setting 0.150s has a tolerance of +0/-40% and time delay setting 0.067s has a tolerance of +0/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 18: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

18

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 14. 800A frame PXR 20D / PXR 25 - I4t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

100000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Pickup (Ir)

PD5 800A PXR20D / PXR25 - I4t Long Delay and Flat Short Delay Curves

0.5

0.05

1.5 12Isd

setting range

tsd setting range

tr setting range

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDG 800 A

Min. 320 AMax. 800 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10A

2. Long delay time settings adjustable from 0.5s - 7s at steps of 0.1s with +0%/-30% tolerance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 12x at steps of 0.1x with ±5% tolerance.

5. Short delay time settings adjustable from 0.050s – 0.500s at steps of 0.010s with tolerances as fol-lows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay set-tings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 19: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

19

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 15. 1200A frame PXR 20D / PXR 25 - I4t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

100000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Pickup (Ir)

PD5 1200A PXR20D / PXR25 - I4t Long Delay and Flat Short Delay Curves

0.5

0.05

1.5 12Isd

setting range

tsd setting range

tr setting range

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDG 1200 A

Min. 500 AMax. 1200 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10 A.

2. Long delay time settings adjustable from 0.5s - 7s at steps of 0.1s with +0%/-30% tolerance.

3 If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 12x at steps of 0.1x with ±5% tolerance.

5 Short Delay time settings adjustable from 0.050s – 0.500s at steps of 0.010s with tolerances as fol-lows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay set-tings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 20: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

20

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 16. 1600A frame PXR 20D / PXR 25 - I4t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

100000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Pickup (Ir)

PD5 1600A PXR20D / PXR25 - I4t Long Delay and Flat Short Delay Curves

0.5

0.05

1.5 12Isd

setting range

tsd setting range

tr setting range

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDG 1600 A

Min. 800 AMax. 1600 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 10 A.

2. Long delay time settings adjustable from 0.5s - 7s at steps of 0.1s with +0%/-30% tolerance.

3 If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 12x at steps of 0.1x with ±5% tolerance.

5. Short delay time settings adjustable from 0.050s – 0.500s at steps of 0.010s with tolerances as fol-lows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay set-tings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 21: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

21

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 17. PXR 20D / PXR 25 ground (earth) flat delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10

Tim

e in

Sec

onds

Current in Multiples of Rating(In)

PXR20D / PXR25 - Ground (Earth) Flat Delay Curves

0.2 1.0

0.1

1.0

Igsetting range

tg setting range

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25

Notes: 1. Ground pickup settings adjustable from 0.2x - 1.0x

at steps of 0.010x for residual sensing with a toler-ance of ± 10%.

2. Ground time delay settings adjustable from 0.100s – 1.00s at steps of 0.010s with tolerances as follows: time delay settings 1.00s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40%.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 22: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

22

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 18. PXR 20D / PXR 25 - ground (earth) I2t delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10

Tim

e in

Sec

onds

Current in Multiples of Rating(In)

PXR20D / PXR25 - Ground (Earth) I2T Delay Curves

0.2 1.0

0.067

0.300

①Ig

setting range

tg setting range

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25

Notes: 1. Ground pickup settings adjustable from 0.2x - 1.0x

at steps of 0.010x for residual sensing with a toler-ance of ± 10%.

2. Ground I2t slope time settings are adjustable from 0.067s – 0.300s at steps of 0.010s with tolerances as follows: I2t slope time delay settings 0.300s to 0.200s have tolerances of +0/-30%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.067s have tolerances of +20%/-50%. After approximately 1x the I2t slope will go flat and those times have tolerances as follows: time delay settings 0.300s to 0.200s have tolerances of +0/-20%, time delay set-tings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have toler-ances of +0/-50%.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 23: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

23

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 19. PXR 20 - ground (earth) flat delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10

Tim

e in

Seco

nds

Current in Multiples of Rating(In)

PXR20 - Ground (Earth) Flat Delay Curves

0.2

0.2 0.4 0.6 0.8 1.0

0.1

0.3

0.75

0.5

0.3

0.15

1.0

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -PXR 20

Notes: 1. Ground pickup settings as shown are for residual

sensing with a tolerance of ± 10%. 2. Ground slope flat time setting are shown with toler-

ances.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve. 4. With ZSI enabled and no auxiliary power, tripping

times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 24: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

24

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 20. PXR 20 - ground (earth) I2t delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10

Tim

e in

Sec

onds

Current in Multiples of Rating(In)

PXR20 - Ground (Earth) I2T Delay Curves

0.150

0.2 0.5 1.0

0.067

0.300

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -PXR 20

Notes: 1. Ground pickup settings as shown are for residual

sensing with a tolerance of ± 10%.2. Ground slope I2t time settings are shown with

tolerances.3. If thermal memory is enabled, trip times may be

shorter than indicated in this curve. 4. With ZSI enabled and no auxiliary power, tripping

times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 25: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

25

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 21. 800A frame PXR 20D / PXR 25 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 800A Frame Instantaneous Curves

Max182

IiSetting range

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Seco

nds

Current in Amps

800A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25

Notes: 1. The instantaneous pickup settings adjustable from

2x – 18x (max) at steps of 0.10x with a ±10% tolerance.

2. For high fault current levels a fixed instantaneous override is provided at 14400 A and has a ±15% tolerance.

Page 26: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

26

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 22. 1200A frame PXR 20D / PXR 25 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 1200A Frame Instantaneous Curves

2

Max12

IiSetting range

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Seco

nds

Current in Amps

1200A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25

Notes: 1. The instantaneous pickup settings adjustable from

2x – 12x (max) at steps of 0.10x with a ±10% tolerance.

2. For high fault current levels a fixed instantaneous override is provided at 14400 A and has a ±15% tolerance.

Page 27: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

27

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 23. 1600A frame PXR 20D / PXR 25 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR 20D / PXR 25 - 1600A Frame Instantaneous Curves

2

Max9

IiSetting range

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Seco

nds

Current in Amps

1600A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20D / PXR 25

Notes: 1. The instantaneous pickup settings adjustable from

2x – 9x (max) at steps of 0.10x with a ±10% tolerance.

2. For high fault current levels a fixed instantaneous override is provided at 14400 A and has a ±15% tolerance.

Page 28: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

28

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 24. 800A frame PXR 20 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

sdnoceS ni emiT

Current in Mul�ples of Ra�ng (In)

PXR 20 - 800A Frame Instantaneous Curves

2

①Max188 12

10

6

5

43

15

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Sec

onds

Current in Amps

800A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20 / PXR 10

Notes: 1. The instantaneous pickup settings as shown with a

±10% tolerance.2. For high fault current levels a fixed instantaneous

override is provided at 14400 A and has a ±15% tolerance.

Page 29: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

29

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 25. 1200A frame PXR 20 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

sdnoceS ni emiT

Current in Mul�ples of Ra�ng (In)

PXR 20 - 1200A Frame Instantaneous Curves

2

Max128

9

10

6

5

43

7

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Sec

onds

Current in Amps

1200A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20 / PXR 10

Notes: 1. The instantaneous pickup settings as shown with a

±10% tolerance.2. For high fault current levels a fixed instantaneous

override is provided at 14400 A and has a ±15% tolerance.

Page 30: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

30

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 26. 1600A frame PXR 20 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

sdnoceS ni emiT

Current in Mul�ples of Ra�ng (In)

PXR 20 - 1600A Frame Instantaneous Curves

2

Max9

8

2.5

7

6

5

43

3.5

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Sec

onds

Current in Amps

1600A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20 / PXR 10

Notes: 1. The instantaneous pickup settings as shown with a

±10% tolerance.2. For high fault current levels a fixed instantaneous

override is provided at 14400 A and has a ±15% tolerance.

Page 31: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

31

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 27. PXR 20 / PXR 20D / PXR 25 - maintenance mode. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000

Tim

e in

Sec

onds

Current in Multiples of Rating (In)

PXR 20 / PXR 20D / PXR 25 - Maintenance Mode Curves

10

8

6

4

2.5

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 and 4-polesTrip unit type: Power Xpert Release -

PXR 20 / PXR 20D / PXR 25

Notes: 1 Reduction pickup settings have a ±20% tolerance.

Page 32: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

32

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 28. 400A frame PXR 20D / PXR 25 - I2t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 400A PXR20D / PXR25 - I2t Long Delay and Flat Short Delay Curves

0.5

1.5 12

0.05

tr setting range

Isdsetting range

tsd setting range

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3-poleTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDG 800 A

Min. 150 AMax. 400 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 1A.

2. Long delay time settings adjustable from 0.5 - 24 sec. at steps of 0.1s with +0%/-30% toler-ance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 12x at steps of 0.1x with ±5% tolerance.

5. Short delay time settings adjustable from 0.050s – 0.500s at steps of 0.010s with tolerances as fol-lows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay set-tings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 33: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

33

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 29. 400A frame PXR 20D / PXR 25 - I2t long delay and I2t short delay. November 2019

0.01

0.1

1

10

100

1000

10000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Setting (Ir)

PD5 400A PXR20D / PXR25 - I2t Long Delay and I2t Short Delay Curves

1.5

0.067

0.3

8

tr setting range

Isdsetting range

tsd setting range

12

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3-poleTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDG 800 A

Min. 150 AMax. 400 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 1A.

2. Long delay time settings adjustable from 0.5s - 24s at steps of 0.1s with +0%/-30% tolerance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 12x at steps of 0.1x with ±5% tolerance.

5. Short delay I2t slope time settings adjustable from 0.067s – 0.300s at steps of 0.010s with tolerances as follows: I2t slope time delay settings 0.300s to 0.200s have tolerances of +0/-30%, time delay set-tings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.067s have toler-ances of +0/-50%. After approximately 8x the I2t slope will go flat and those times have tolerances as follows: time delay settings 0.300s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay settings between 0.090s to 0.050s have tolerances of +0/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 34: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

34

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 30. 400A frame PXR 20D / PXR 25 - I4t long delay and flat short delay. November 2019

0.01

0.1

1

10

100

1000

10000

100000

0.1 1 10 100

Tim

e in

Seco

nds

Current in Multiples of Long Delay Pickup (Ir)

PD5 400A PXR20D / PXR25 - I4t Long Delay and Flat Short Delay Curves

0.5

0.05

1.5 12Isd

setting range

tsd setting range

tr setting range

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3-poleTrip unit type: Power Xpert Release -

PXR 20D / PXR 25Irsetting

PDG 800 A

Min. 150 AMax. 400 A

Notes: 1. Long delay pickup is 110% of the Ir setting with

±5% tolerance. Ir is set from min to max at steps of 1A

2. Long delay time settings adjustable from 0.5s - 7s at steps of 0.1s with +0%/-30% tolerance.

3. If thermal memory is enabled, trip times may be shorter than indicated in this curve.

4. Short delay pickup settings adjustable from 1.5x - 12x at steps of 0.1x with ±5% tolerance.

5. Short delay time settings adjustable from 0.050s – 0.500s at steps of 0.010s with tolerances as fol-lows: time delay settings 0.500s to 0.200s have tolerances of +0/-20%, time delay settings between 0.190s to 0.160s have tolerances of +0/-30%, and time delay settings between 0.150s to 0.100s have tolerances of +0/-40% and time delay set-tings between 0.090s to 0.050s have tolerances of +20%/-50%.

6. If the long delay time is projected to be faster than the short delay time, the long delay trip time will go no faster than the short delay time value.

7. With ZSI enabled and no auxiliary power, tripping times for 3-phase faults will be a maximum of 60ms for 60Hz and 63ms for 50Hz.

Page 35: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

35

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units Standards: UL, CSA, IEC, CCC

EATON www.eaton.com

Figure 31. 400A frame PXR 20D / PXR 25 - instantaneous and override. November 2019

0.01

0.1

1

10

100

1000

10000

1 10 100 1000 10000

Tim

e in

Seco

nds

Current in Multiples of Rating (In)

PXR20D / PXR25 - 400A Frame Instantaneous Curves

Max36

2 ①

IiSetting range

0.01

0.1

1

10

1000 10000 100000

Tim

e in

Seco

nds

Current in Amps

400A Frame Override Curve

Time current curves Power Defense circuit breakersStyle: Frame 5Configuration: 3 poleTrip unit type: Power Xpert Release -

PXR 20D / PXR 25

Notes: 1. The Instantaneous pickup settings adjustable from

2x – 36x (max) at steps of 0.10x with a ±10% tolerance.

2. For high fault current levels a fixed instantaneous override is provided at 14400 A and has a ±15% tolerance.

Page 36: Power Defense time current curve Frame 5 - PD5 · 2020. 12. 23. · 3 Technical Data TD012067EN Effective November 2019 Time current curves Power Defense MCCB Frame 5 PXR electronic

Eaton 1000 Eaton BoulevardCleveland, OH 44122United States877-ETN-CARE (877-386-2273)Eaton.com

© 2019 Eaton All Rights ReservedPrinted in USAPublication No. TD012067EN / TBG001424November 2019

Eaton is a registered trademark.

All other trademarks are property of their respective owners.

Technical Data TD012067ENEffective November 2019

Time current curves Power Defense MCCB Frame 5 PXR electronic trip units

Standards: UL, CSA, IEC, CCC


Recommended