Power Factor Correction Product Guide Solutions for Low and High Voltage Power Factor Correction
Transcript
Page 1: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

Power Factor Correction Product GuideSolutions for Low and High Voltage Power Factor Correction

Page 2: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

Our passion, specialist knowledge and a dedication to the best solution ensures your business will receive the power management outcome that is right for you.

Through our partnership with Circutor in Spain, Quality Energy offer a premium European components that are then assembled by quality engineers right here in Australia.

Page 3: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 3

Contents

Who are Quality Energy? .................................................................................................... 4Power Factor Explained ....................................................................................................... 5System Features ..................................................................................................................... 6Custom Modular PFC Solutions ......................................................................................... 7PFC Featured Components ................................................................................................ 8PFC Custom Range Assembly (Free-Standing) ........................................................... 10QEECO - Wall-Mount PFC Solution ................................................................................. 13Static Reactive Power Generators ................................................................................... 14Smart III Power Factor Regulator ...................................................................................... 16Tubular Capacitor .................................................................................................................. 17Three-Phase Harmonic Blocking Reactors ................................................................... 18Capacitor Switching Contactors ...................................................................................... 19Smart III Power Factor Regulator for Static Capacitor Banks ............................... 20Static Switching Module for Three-Phase Capacitors ............................................. 21PFC Compensation Applications in High Voltage ...................................................... 22High Voltage Capacitors ..................................................................................................... 24RMV Shock Reactors ............................................................................................................. 26LVC Vacuum Contactor ........................................................................................................ 27Capacitor Banks for High Voltage ................................................................................... 28

Page 4: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE4

Quality Energy was established in 1989 and is now a national market leading manufacturer that specialises in industrial power quality & efficiency. Our passion, professional knowledge and dedication to the best outcome, ensures your business will receive the power management solution that is right for you.

Understanding each and every business we work with is vital in achieving the desired results and this is why Australia’s biggest brand turn to Quality Energy for their cost reduction and power quality needs.

Reduce Energy Consumption & Costs Today—For a Brighter TomorrowQuality Energy has been adding value by providing professional products and services to companies all over Australia for almost 30 years. We help companies confront the reality of increasing energy costs and the challenges of poor power quality within their premises.

Clients we currently service

Page 5: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 5

Power Factor ExplainedOur world-class Power Factor Correction Systems will raise your business efficiency, lower your carbon footprint and reduce your risk of equipment failure. This saves your business time, energy and money.

What is Power Factor?Inefficient electrical systems tend to use a large quantity of ‘reactive’ power (kVAr), which represents the power

lost in the operation of inductive equipment such as transformers and electric motors. This invariably increases the total power load represented by your kVA –and reduces your overall energy efficiency, or ‘Power Factor’.

Power Factor is the ratio between your kVA, or total power load, and your kW, or the actual power working for your business. Power factor is measured on a scale between zero and one, with 1.0 representing optimal energy efficiency.

Why install Power Factor Correction (PFC)?Installing custom-built Capacitor Banks and Controllers minimizes wasted energy, improves plant efficiency and ultimately saves you money.

It also helps rectify any overloading issues you may have and gives you the opportunity to expand your plant without upgrading transformer or supply equipment.

It is not uncommon for the installation costs of a properly designed system to be recovered 6-30 months after installation.

Power Factor Coffee Analogy

Real Power kW coffee

Power Factor =

Apparent Power (kW2 + kVAr2) coffee + froth

Apparent Power

kVA

Reactive PowerkVAr

Real Power

kw

Page 6: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE6

System FeaturesBy choosing a Quality Energy PFC system you will receive a tailored solution at a highly competitive price, delivering maximum power efficiency and cost savings.

Quality Energy prides itself on its high quality of workmanship and customer service. Our revolutionary power factor correction systems are designed to maximise your equipment’s life expectancy and are assembled so that servicing and maintenance is as simple as possible.

Quality Energy’s custom designed Power Factor Correction Systems are built with premium European components and assembled in Australia by experienced engineers. The segregated design of Quality Energy’s PFC systems ensures that sensitive control components will not be effected by heat generated by harmonic blocking reactors. This full segregation design facilitates greater life expectancy and easy servicing of all system components.

Custom designed power factor correction systems. Built with premium European components and assembled in Australia by quality engineers.

Our revolutionary designed systems are engineered with:

C-tick Australian standard

Slide out trays for easy and fast maintenance

No access to live terminals for safe and secure operation

Premium grade European components that have been proven over time to deliver greater results and reliability

Connection Point

Power Factor Correction Controller

Cylindrical Capacitors

Capacitor switching contactors

Slide out trays for easy and fast maintenance

Page 7: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 7

Custom Modular PFC SolutionsOur custom Power Factor Correction System is the premier solution in the Quality Energy PFC family. Offering a fully modular design allows for many different system configurations. Design decisions include: top or bottom cable entry; load-break switch, MCCB or direct connect incomer; and your choice of colour. The use of functional trays facilitates selectable correction granularity and makes system servicing a breeze.

Product Features · IP33 Protection · Top and bottom entry options · Choice of incomer: direct connect, isolator switch or circuit breaker

· Integral ventilation system · Choice of over 100 colours · Wired, tested and commissioned · Large exhaust fan to remove heat · 6 watts of losses per 1kVAr (50kVAr module) · Communication Port

Optional Features · Panel mount air conditioner · Stainless steel enclosure · IP55, IP56 and IP65 options · Circuit breaker or isolator handle on door · Side entry · Taller options · Thyristor rapid switching control · Customised to suit any environment

3 year warranty on all standard systems

Modular units to cater for future expansion of plant or equipment

Online monitoring

Full segregation of heat generating harmonic blocking reactors from capacitors, critical switching and control equipment to ensure greater life expectancy for all components

3-4 weeks maximum build time on all standard sized systems

Large industrial fan to remove unwanted heat

Harmonic Blocking Reactors

Reactors segregated from capacitors and critical control equipment

Page 8: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE8

Robust, reliable & safe

More efficient

CLZ-HDThe CLZ Heavy Duty Capacitor series by CIRCUTOR includes a new comprehensive disconnection in the event of incidents and eliminates possible risks for the installation or collateral damage to the rest of the units.

Features · Greater current capacity: 1.8 In permanent · Greater tolerance to inrush currents: 400 x In · Longer useful life: 150,000 h · Higher temperature resistance: -50...60 °C · More secure and safe: Inert gas · More efficient: less losses, under 0.4 W/kvar · Longer warranty: 3 years · Altitude: up to 4,000 m above sea level

Longer lifetime150,000 h

Longer warranty3 years

Temperature strength higher

65 °C short time

PFC Featured Components

Page 9: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 9

Computer Smart IIIMeasurement with three current transformers guarantees an analogue reading of the company’s meter. The Computer SMART III is the only Power Factor Relay in the market that offers the possibility of using 3 measuring transformers in addition to the traditional method of measuring with a single current transformer, as well as providing the functions of an integral power analyzer and controlling the residual leakage currents.

Features · New conpensation concept · Easy to use · Serial communications · Plug & Play function · AUTO-ON-OFF function, by stage · Safety and maintenance

Measures the same as the company’s energy meter

Performs the functions of a powerful analyzer

Compensates over three-phases

Built-in leakage control

Easy preventive maintenance and maximum safety

Compensation based on real needs

Plug & PlayControl of the electrical parameters and

consumption of the installation

PFC Featured Components

Page 10: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE10

PFC Custom Range Assembly (Free-Standing)

QESD – SHORT DOUBLE

Size Incomer TypeMAX kVAr

ratingNo. of

ModulesMax.

Storages

1475 H 800 W 640 D

· Direct connection · Circuit Breaker · Isolator

Up to 150kVAr 4 3

QETD – TALL DOUBLE

Size Incomer TypeMAX kVAr

ratingNo. of

ModulesMax.

Storages

2075 H 800 W 640 D

· Direct connection · Circuit Breaker · Isolator

Up to 250kVAr 6 5

600

147

5 6

00

800

640

640

207

5

600

600

800

640

640

Page 11: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 11

QEST – SHORT TRIPLE

Size Incomer TypeMAX kVAr

ratingNo. of

ModulesMax.

Storages

1475 H 1250 W 640 D

· Direct connection Up to 350kVAr 8 7

1475 H 1250 W 640 H

· Circuit Breaker · Isolator Up to 300kVAr 8 6

QEST – TALL TRIPLE

Size Incomer TypeMAX kVAr

ratingNo. of

ModulesMax.

Storages

2075 H 1250 W 640 D

· Direct connection Up to 550kVAr 12 11

2075 H 1250 W 640 H

· Circuit Breaker · Isolator Up to 500kVAr 12 10

147

5

600

1250

600

64

0

640

1250

207

5

600

1250

600

64

0

640

Page 12: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE12

Larger systems and configurations on request.

Improve your power factor

Maximise your equipment’s life

expectancy

Easy to service and maintain

Size Incomer TypeMAX kVAr

ratingNo. of

ModulesMax.

Storages

2075 H 2050 W 640 D

· Direct connection Up to 850kVAr 18 17

2075 H 2050 W 640 H

· Circuit Breaker · Isolator Up to 800kVAr 18 16

QETTD – TALL TRIPLE DOUBLE

2050

207

5

640

2050

640

Page 13: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 13

Smaller units on request.

QEECO WALL-MOUNT PFC SOLUTIONComplementing the floor standing PFC solutions is the wall-mountable PFC system. This system offers reactive compensation from 6.25 kVAr up to 100 kVAr, all in a compact enclosure. Ideal for installations where floor space comes at a premium, such as inner city locations and commercial estates.

Product Features · Quality steel enclosure · Detuning reactors fitted as standard · IP54 protection · Top and bottom entry, direct connect/circuit breaker or isolator

· Integral ventilation system · RAL 7035 grey · Fully assembled, wired and tested, ready to install and connect

· 6 watts of losses per 1kVAr (50kVAr module)

Optional Features · Alternative colours available upon request · IP56 protection · Circuit breaker or isolator handle on door · Communication Port: RS232, RS485, Ethernet, GSM

Size Incomer Type MAX kVAr rating No. of Modules Max. Storages

1200 H 800 W 300 D

· Direct connection · Circuit Breaker · Isolator

Up to 100kVAr 3 3

Page 14: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE14

SVG100 / 200 kVAr

Static reactive power generators

DescriptionSVG static reactive power generators are the most accurate reactive power compensation solution, for both unbalanced three-phase systems and facilities with inductive and capacitive reactive power. It can be used in three-phase industrial, commercial or service installations and is not affected by the harmonics of the installation. A system with greater safety and very little maintenance. In this series, the racks are mounted in the standard cabinets available on the market and are designed for ease of installation.

The following features and functions are implemented:

· Reactive power compensation (inductive/capacitive) of 100 to 200 kVAr per cabinet · Compact rack-type module for ease of installation in standard cabinets. · Voltage and frequency multi-range (50/60 Hz) · Immunity to harmonic currents. · Cos ф range of 0.7 inductive…1…0.7 capacitive. · Online operation monitoring · Protection module includedIf higher power factor correction capacities are required, up to 100 units can be connected in parallel*.

ApplicationThe perfect solution for individual loads or facilities with a large number of single-phase or three-phase loads, both inductive and capacitive. Also for facilities where the load fluctuates over short periods of time, e.g. loads from bridge cranes, welding kits, lifts, drilling/grinding operations, and data centres.

Technical FeaturesNetwork voltage Voltage 230 - 480 V phase-phase +/- 10%

Frequency 50/60 Hz +/- 5%

Maximum THDv 25%

Power SVG-3Wx-100 / SVG-3Wx-200

Maximum consumption 4000 W / 8000 W

Maximum reactive power 100 kVAr / 200 kVAr

Maximum current (phase) 145 Arms / 290 Arms

Current measurement Type 3 or 2x transformer: 5/5 A ... 5000/5 A Class 1 or higher (0.5 – 0.2- 0.2 S) Frequency response up to 2500 Hz / 3000 Hz (60 Hz)

Consumption 1.5 VA per transformer

SVG-3WF-200

SVG-3WF-100*

Page 15: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 15

SVG100 / 200 kVAr

Static reactive power generators

Features Power factor correction Adjustable, target 0.7 inductive...0.7 capacitive

Parallel installation · Up to 100 devices/racks (SVG 100 kVAr) · Up to 50 devices/racks (SVG 200 kVAr) · Connection of CTs, only to the “master” unitAdvanced processing algorithm:

· Maximisation of the working life of units (alternating unit operation).

· Maximisation of the operating efficiency (only required filters are activated).

· Allows redundancy (system operation in the event of unit failure).

User interface Colour 3.5” touch screen Web server and datalogger

RS-485 Modbus RTU 9600 Stop 1 Parity None

Ethernet TCP/IP Modbus TCP

Installation Installation category CAT III 300V

Pollution degree 2

Operating temperature -10 °C…45 °C

Storage temperature -20 °C…50 °C

Relative humidity 0…90% (without condensation)

Maximum altitude 2000 m

Degree of protection IP21 (or other degrees of protection on request)

Connection Grid End sleeve of 35 mm2. Tightening torque 6 Nm

CTs 6-pole connector. Maximum conductor crosssection 2.5 mm2. Tightening torque < 0.8 Nm

RS-485 3-pole connector. Maximum conductor crosssection 2.5 mm2. Tightening torque 0.5-0.6 Nm

Ethernet RJ45

Build features Dimensions 600 x 1836 x 822 (width x height x depth)

Weight SVG-3WF-100 Weight 206 kg

SVG-3WF-200 Weight 276 kg

Noise < 65 dBA

Standards EN 62477-1:2012, EN 55011:2011, EN 61000-6-2:2006, EN 61000-6-4:2007, IEC 61439-1:2011

ReferencesType Code Phase current (A) Total reactive power (kVAr) EMI filter

SVG-3WF-100-480 R7NST5 145 100 •

SVG-3WF-200-480 R7NST7 290 200 •

Page 16: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE16

Computer SMART III

DescriptionMeasurement with three current transformers guarantees an analogue reading of the company meter. The Computer SMART III reactive energy regulator is the only regulator on the market that offers the possibility of using 3 measurement transformers in addition to the conventional method of measuring with a single current transformer, as well as providing the functions of an integral power analyzer and controlling residual leakage currents.

Computer SMART III is a regulator that ensures excellent preventive maintenance by means of programming its alarms and the options for testing the capacitor status, offering maximum supervision and safety of your compensation unit.

ApplicationThe connection of 1 or 3 transformers makes Computer SMART III the perfect regulator in any installation, allowing the following:

· Changing from 1 to 3 transformers in the following cases: · Changes in reactive energy penalties · Changes in consumption habits · Significant imbalances in the system

· Replacing the regulator of any capacitor bank · Perfect for installations with up to 4 objective cos ф, since it can adapt to any compensation need (different time periods).

· It can be used with Medium Voltage compensation units.

Technical FeaturesVoltage circuit Power supply voltage 110...480 Vac

Tolerance 10%

Consumption 6 VA

Frequency 45...65 Hz

Measurement circuit Measurement voltage 525 Vac P-P

300 Vac P-N

Current measurement x1 or x3 transformers .../5 A or .../1 A

Leakage current Measurement range IΔprim = 10 mA...1 A AC

Current transformers WGC series

Accuracy Voltage and Current 1%

Cos ф 2% ±1 digit

Temperature measurement Measurement range 0 °C...80 °C ±3 °C

Alarm relay Output contact Switched

Umax and Imax (operation) 250 Vac / 6 A

Output relay No. of relays 6 or 12, depending on the type

Umax and Imax (operation) 250 Vac / 6 A

Fan relay Output contact Not switched

Umax and Imax (operation) 250 Vac / 6 A

Digital outputs No. of outputs 2

Type NPN transistor

Umax and Imax (operation) 24 Vdc /50 mA

Digital inputs No. of inputs 2

Alarms No. of alarms 17, fully configurable

Communications Port RS-485

Protocol Modbus / RTU

Operating conditions Temperature -20 °C...+60 °C

Relative humidity 95% without condensation

Maximum altitude 2,000 m

Control system PFC (Program that minimises the number of operations)

Safety Insulation Category III Class II EN 61010-1

Protection degree IP 40 assembled IP 30 not assembled, in accordance with EN-60529

Standards IEC 62053-23 (2003-01), IEC 61326-1, EN 61010-1, UL 508

Smart III Power Factor regulator

Page 17: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 17

CLZ-FP-HDCLZ-FPT-HD

DescriptionCLZ-HD (Heavy duty) capacitor range is composed of capacitors with a tubular casing, of the dry-type, covering a wide range of power and voltage ratings, at 50 and 60 Hz. The CLZ-HD capacitors are designed to be installed in installations with extreme working conditions. The design, manufacturing and testing processes guarantee the production of top quality and long lasting capacitors. Those CLZ-HD capacitors offer a new refrigeration technology by means of nitrogen gas*, being a refrigerating system of high benefits, inert and non flammable.

ApplicationsIts application is based on compensation in installations with static or variable loads (capacitor banks). Especially designed to be installed in roughly environments with the most extreme conditions due to its longer life and high temperature resistance.

Technical FeaturesElectrical features Overcurrent 1,8 times the rated current (permanently)

Inrush current 400 x rated current

Overvoltage 10 %, 8 over 24 hours 15 %, up to 30 minutes over 24 hours 20 %, up to 5 minutes over 24 hours 30 %, up to 1 minute over 24 hours

Insulation level 3/8 kV (CLZ-FP-HD) - 3/12 kV (CLZ-FPT-HD)

Frequency 50 or 60 Hz

Tolerance -5...+10 %

Discharge resistance 50 V / 1 minute (0,5 - 30 kvar) 75 V / 3 minutes (33 - 50 kvar)

Losses Dielectric: < 0,2 W / kvar Total: < 0,4 W / kvar

Protections Dielectric regeneration Expansion system

Mechanical features Enclosure Aluminium

Power terminals M10

Fixing screws M12

Life time ≥ 150.000 hours

Protection degree IP 20 for CLZ-FP without terminal IP 54 for CLZ-FP with terminal (optional) (for diameters of 85,100 and 116 mm)

Environmental features Temperature (Class D) Daily: +45 °C Annual: +35 °C Maximum: +65 °C Minimum: -50 °C

Humidity 95% without condensation

Altitude 4000 m

Construction features Type of assembly Vertical / Horizontal

Ventilation Natural or forced, depending on the cabinet design

Distance between capacitors Minimum 2 cm

Standard IEC 60831:2014

* From 7.5 kvar.

Tubular capacitor

Page 18: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE18

RE / RBE

DescriptionCIRCUTOR has standardised the reactors of the RE / RBE series for their use in static capacitor banks. The best operation of the unit requires the reactors to be connected within the triangle made p of the capacitor-reactor group. At the same power rating, the RE / RBE reactors have a nominal current value that is 1.73 times lower and an inductance value that is 3 times higher than that in an R / RB reactor.

There is a standard range of 400 V rejection reactors with p = 7%, with a resonance frequency of 189 Hz for 50 Hz networks (or 227 Hz on demand for 60 Hz networks). In addition, reactors can be manufactured on demand for static capacitor banks adapted to any value of the power rating, p%, voltage and frequency.

RE-type low-power reactors are built with low-loss plates and are coiled with copper wire. The connection is made using suitable terminals. In the case of higher power ratings, RBE reactors are used, with a magnetic plate nucleus and multiple air gaps, which offer excellent features and a low loss ratio. The coils are made with an aluminium band (or copper band, on demand). The input and output connections run through a busbar. Both RE and RBE type reactors are impregnated with a varnish in a vacuum to increase insulation and reduce noise levels.

ApplicationsThe rejection reactors of the RE / RBE series have been specifically designed for use in static capacitor banks in installations with a high harmonic content. The reactors must be connected in series with each capacitor for adequate protection of the capacitors and the static operations module, and to avoid resonance effects in the installation.

Technical FeaturesFeatures Voltage 400 V

On demand: up to 1,000 V

Mains frequency 50 Hz On demand: 60 Hz

Power According to the table Other values on demand

Value of p% 7% (189 Hz) Other values on demand

Type of conductor RE: copper wire RBE: aluminium band

Tolerance L ± 5%

Linearity (5% L) 1.8 InInsulation voltage 4 kV

Maximum room temperature -10 °C...+45 °C

Internal insulation Class F (155 °C) On demand: Class H (180 °C)

Maximum overload Permanent 1.17 InTemporary (1 min) 2 In

Safety Protection thermostat Opening at 90 °C

Protection degree IP 00

Installation Interior

Standards UNE-EN60289, IEC 60076

Three-phase harmonic blocking reactors

Page 19: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 19

CMC-B

DescriptionCMC-B series are contactors adjusted for switching single-step or multiple step capacitor banks. They have high operating times and a high electrical endurance that make the most robust and durable contactors.

ApplicationsThey are installed in switching single-step or multiple step capacitor banks.

Technical FeaturesElectrical features Operating voltage 230...690V

Frequency 50 / 60 Hz

Rated operational current @ 400 V 11...116 A

Coil voltage 230 V |50-60 Hz

Coil voltage tolerance 0,85...1,1 Un

Rated impulse withstand voltage 8 kV

Frequency of switching operations (break operation 15 s)

240/h for CMC-7,5B - CMC-12B 120/h for CMC-20B 100/h for CMC-32B to CMC-150B

Contact endurance (break operation: 15 s)

200.000 for CMC-7,5B, CMC-40B 100.000 for CMC-75B to CMC-150B

Build features Insulation rating 690...1000 V

Protection Degree IP 00

Auxiliary contacts Type NC x2

Environmental conditions Working temperature -25...+55 °C

Relative Humidity 5...95% without condensation

Altitude 2000 m

Standards IEC 60947-4-1, VDE 0660

References

Maximum operation power (kvar)

Type Code 230 V 400-440-480 V 500-550 V 660-690 V Dumping resistors

CMC-7,5B R281A5 4 7,5 9 11 not available

CMC-12B R281A6 6,7 12,5 15 18 included

CMC-20B R281A4 11 20 24 30 included

CMC-32B R281A8 14 25 30 35 included

CMC-40B R281A1 20 30 35 40 included

CMC-75B R281A9 29 50 60 70 included

CMC-85B R281A3 32 60 70 80 included

CMC-150B R281AD 45 80 100 115 included

Capacitor switching contactors

Page 20: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE20

Computer Smart III Fast

DescriptionMeasurement with three current transformers guarantees an analogue reading of the company meter. The Computer SMART III Fast reactive energy regulator is the only regulator on the market that offers the possibility of using 3 measurement transformers in addition to the conventional method of measuring with a single current transformer, as well as providing the functions of an integral power analyzer and controlling residual leakage currents.

Computer SMART III Fast is a regulator that ensures excellent preventive maintenance by means of programming its alarms and the options for testing the capacitor status, offering maximum supervision and safety of your compensation unit.

ApplicationComputer Smart III Fast it’s the ideal solution to compensate installations with a variation of quick load, between 40 ms and 4 seconds, and/or large unbalances between phases, such as welding units, cranes, lifts and lifting units, smelters, hospitals, automotive industry or any other sector or unit that requires an efficient compensation of the power factor. The connection of 1 or 3 transformers makes Computer SMART III Fast the perfect regulator in any installation, allowing the following:

· Changing from 1 to 3 transformers in the following cases: · Single-phase fast changing equipment · Example: Single-phase welding

· Replacing the regulator of any capacitor bank · Perfect for installations with up to 4 objective cos ф, since it can adapt to any compensation need (different time periods).

Technical FeaturesVoltage circuit Power supply voltage 100...480 Vac

Tolerance 10%

Consumption 6 VA

Frequency 45...65 Hz

Measurement Circuit Measurement voltage 525 Vac P-P 300 Vac P-N

Current measurement x1 or 3x transformers .../5 A or .../1 A

Leakage current Measurement range IΔprim = 10 mA... 1 A AC

Current transformers WGS series

Accuracy Voltage and Current 1%

Cos ф 2% ±1 digit

Temperature measurement Measurement range 0 °C...80 °C ±3 °C

Alarm relay Output contact Switched

Umax and Imax (operation) 250 Vac / 6 A

Output No. of outputs 6 or 12, depending on type

Type OPTOMOS transistor

Umax and Imax (operation) 60 Vc.c. / 0,2 A

Fan relay Output contact Not switched

Umax and Imax (operation) 250 Vac / 6 A

Digital outputs No. of outputs 2

Type NPN transistor

Umax and Imax (operation) 24 Vdc /50 mA

Digital inputs No. of inputs 2

Alarms No. of alarms 17, fully configurable

Communications Port RS-485

Protocol Modbus / RTU

Operating conditions Temperature -20 °C... +60 °C

Relative humidity 95% without condensation

Maximum altitude 2,000 m

Control system PFC (Program that minimises the number of operations)

Safety Insulation Category III Class II EN 61010-1

Protection degree IP 51 assembled IP 31 not assembled, in accordance with EN-60529

Standards UNE EN 61010:2010, UNE-EN 61000:2007, UNE-EN 61000-6-2:2005, UNE-EN 6100-6-4:2005

Smart III Power Factor regulator for static capacitor banks

Page 21: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 21

EMB-2PH

DescriptionEMB-2PH static switching modules series are the building blocks for the construction of static capacitor banks for Power Factor Correction.

These capacitor banks use thyristors instead of the classic contactors for the connection of each capacitor stage and they are ideal in installations with fast and large load fluctuations (load changes from tents of seconds up to 8 or 10 seconds).

ApplicationEMB-2PH static switching modules have been designed to connect and disconnect capacitors in some milliseconds. They can be used to build capacitors with some stages, or for the individual compensation of a load that must be compensated instantly and which is not able to be disconnected such as welding machines, cranes, lifts, etc.

Technical FeaturesElectrical features Standard voltages Up to 3 x 440 Va.c. without detuned filters

Up to 3 x 415 Va.c. with detuned filters

Frequency 50/60 Hz

External activation signal 12 Vd.c. (Terminals A+,B-)

Nominal switched power Described on selection table

Overload capacity 1,5 In during 1 min

Protections Fuses Not included. External protection against overload and short-circuit are required

Fan 1 x 230 Va.c. auxiliary voltage (on terminals A1, A2)

du / dt RC protection at 1000 V/µs

Thermostat 90 °C

di / dt 100 A/µs (L=12 µH, not included, it must be installed seried with the capacitor)

Environmental features Maximum ambient temperature 45 °C

Maximum temperature of the dissipator 90 °C

Construction features Protection degree IP 00

Weight From 5,1 kg to 5,4 kg

Standards IEC 61439

ReferencesType Code kvar 230 V kvar 400 V Weight (kg) Dimensions L x H x W (mm)

EMB-2PH-25-400 R41321 12,5 25 5,1 165 x 222 x 200

EMB-2PH-50-400 R41323 27,5 50 5,2 165 x 222 x 200

EMB-2PH-80-400 R41325 45 80 5,4 165 x 222 x 200

Maximum operation voltage: 3 x 440 Va.c. (415 Va.c. with detuned reactors)

Accessories

Cover EMB-2PH R41329 Policarbonate cover for EMB-2PH series

Static switching module for three-phase capacitors

Page 22: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE22

PFC Compensation applications in High Voltage · Petrochemistry · Water Treatment · Cement · Automotive industry · Energy distribution · Renewable energies · Iron and steel industry · Paper manufacture

Paper Manufacturing

Generation and Renewable energy

Energy Distribution

Page 23: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 23

Iron and steel industry Automative

industry

Petrochemistry

Cement industry

Desalination plants, purification plants, water

purification plants and pumping plants

Page 24: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE24

High Voltage CapacitorsCIRCUTOR has its own technology for the design and manufacture of medium voltage capacitors, whether single phase or three-phase.

CHV-M

Composition of the capacitorsThe CHV High Voltage capacitors are comprised of several basic capacity elements.

These basic units are connected in series and parallel groups with the objective of achieving the required power and voltage.

Capacitor protection for internal fusesOperational advantages

· Exclusive disconnection from any damaged element · Minimal generation of gases in the interior of the capacitor, therefore there is negligible internal excess pressure

· Continuity of service. The elimination of the damaged unit enables the continuation of the connected equipment

· Possibility of planning the maintenance of the bank · Easier maintenance

Design advantages

· Greater capacitor power · Use of fewer capacitors · Reduction of the frame or cabinet sizes · More economical cost from the bank.

Page 25: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 25

CHV-T

CHV-M CHV-T

Type Single phase Three-phase

Power (kvar) 50 ... 600 50 ... 500

Voltage (kV) 1 ... 24 1 ... 12

Insulation (kV) 7,2 - 12 - 17,5 - 24 - 36 7,2 - 12

Location Indoor / Outdoor

Impregnating agent Biodegradable JARYLEC C101D (without PCB)

Dielectric Rugged polypropylene

Resistors Descharge at 75 V/10 minutes

Standards IEC 60.871-1

Insulators Porcelain

Casing Stainless steel (2 mm thick)

Internal fuses Yes

Temperature “C” -40 ... +50 °C. Average 40 °C

Overload 1.3 In constant

Overvoltage 110% 12/24 hours

Individual test of 100 % of the capacitors in accordance with IEC 60871-1

Page 26: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE26

To limit transitory voltage phenomenons and high currents associated with the connection of capacitor banks, it is essential to use RMV shock reactors to ensure that the peak values are below that indicated in the Standard IEC 60871-1 (less than 100 times the nominal current), and therefore maintain the integrity of the capacitors, as well as of the installation regarding voltage surges.

The value of the inductance is variable depending on the conditions of the installation, basically depending on the following parameters:

· Short-circuit power of the installation · The existence of more capacitor banks · Breaking capacity of the automatic switches. The peak residual connection current, once the reactance is installed, must also be lower than the shutdown power of the equipment.

RMV-260

Type I (A) L (µH)

RMV - 260 - 50 - 350 50 350

RMV - 260 - 60 - 250 60 250

RMV - 260 - 100 - 100 100 100

RMV - 260 - 125 - 50 125 50

RMV - 260 - 175 - 30 175 30

RMV-330

Type I (A) L (µH)

RMV - 330 - 60 - 450 60 450

RMV - 330 - 75 - 350 75 350

RMV - 330 - 90 - 250 90 250

RMV - 330 - 125 - 100 125 100

RMV - 330 - 200 - 50 200 50

RMV - 330 - 250 - 30 250 30

RMV, shock reactance

RMV Shock Reactors

Page 27: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 27

LVC vacuum contactor

The LVC vacuum contactor is the perfect equipment for the handling of capacitor banks from 3.3 up to 6.6 kV. Their general characteristics are:

· Interrupting methods, vacuum · Perfect control of the electric arc in capacity handling · Long life · High insulation of the bank, made up of three independent vacuum poles assembled in a insulated structure

· Small size · Light equipment with optimised weight · Easy to maintain

LVC-6Z44ED

Rated operation voltage 6,6 kV

Rated voltage 7,2 kV

Rated operational current 400 A

Rated frequency 50/60 Hz

Rated breaking current 4 kA

Isolation level BIL 20/60

Excitation method E: continuous L: instantaneous (optional)

Control voltage 110 V c.a.; 220 V c.a.; 110 V c.c.

Maximum applicable

Motors 3 000 kW

Transformers 4 000 kV·A

Capacitors 2 000 kvar

Weight 24 kg

LVC Vacuum Contactor

Page 28: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE28

Capacitor Banks for High Voltage

Insulation levels

7.2 kV 12 kV 17.5 kV 24 kV 36 kV Forma Types

CMF7T CMF7D

CMF12T CMF12D

CMF17D CMF24D CMF36D Standard

FixedCMFR7T CMFR7D

CMFR12D CMFR17D CMFR24D CMFR36DWith rejection

filters

CMA7T CMA7D

CMA12T CMA12D

CMA17D CMA24D CMA36D Standard

AutomaticCMAR7T CMAR7D

CMAR12D CMAR17D CMAR24D CMAR36DWith rejection

filters

Capacitor banks are vital for the adequate technical and economic management of the electrical system, optimising its operation.

The capacitor banks for HV have the following advantages:

· Fixed automatic or regulated compensation models · 7%, 14%, and 5.6% rejection filters · Modular cabinet design · Different cabinet finishes (to order) · IP 00 to IP 43 degree of protection · Use of recognised protective and control system brands · Remote monitoring of the capacitor bank (optional for banks regulated by the plus system)

Page 29: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 29

Notes

Page 30: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE30

Notes

Page 31: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems

POWER FACTOR CORRECTION PRODUCT GUIDE 31

Page 32: Power Factor Correction Product Guide - qualityenergy.com.au€¦ · POWER FACTOR CORRECTION PRODUCT GUIDE 5 Power Factor Explained Our world-class Power Factor Correction Systems