+ All Categories
Home > Documents > POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed...

POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed...

Date post: 10-Jan-2016
Category:
Upload: scot-fisher
View: 213 times
Download: 0 times
Share this document with a friend
41
POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department, Alexandria University -Egypt Ibrahim K.MADI Hanaa M.KARAWIA Alexandria Electrical Distribution Company-Egypt Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119
Transcript
Page 1: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER

DISTRIBUTION SUBSTATION

Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department, Alexandria University -Egypt

Ibrahim K.MADI Hanaa M.KARAWIA Alexandria Electrical Distribution Company-Egypt

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 2: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

ABSTRACT

Levels of Electromagnetic Fields (EMFs) in our environment have increased steadily over the past 50 years.

There are many ways to mitigate the power frequency magnetic field (PFMF) either by design modification of electrical facilities and equipment, or by shielding using Conductive shielding (Aluminum and Copper) or Ferromagnetic shielding (mu-metal).

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 3: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

In this paper the magnetic field management was applied using a developed SUBCALC program, also the magnetic field measurements were taken at distribution substation with and without shielding.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 4: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Different shielding materials are used in the measurements. The materials used were 3% silicon steel, primarily used for transformer core, mu-metal, and copper sheets. These materials were placed just adjacent to the transformer at the low voltage side and measurements were taken.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 5: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

The comparative results at each location are presented.

Comparison between the different materials is shown.

A comparison was made between the experimental results and the simulated ones.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 6: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

INTRODUCTION

In Egypt, it is usual, especially in dense area, to locate distribution substation in the ground floor inside buildings. These locations are very close to the public and to workplaces. Power frequency magnetic field (PFMF) emitted will interact with the living organisms and with the electronic equipments in the surrounding environment.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 7: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

So, magnetic field management becomes a very important aspect. Firstly, to minimize the impact of possible health effects of PFMF while maintaining power system reliability, and safety.

Secondly, when the PFMF is higher than 1 µT, it will produce interference with electronic beam devices such as TV, computer monitors, and industrial aspects.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 8: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

MAGNETIC FIELD MITIGATION

There is a real demand for effective and low-cost mitigation of extremely low frequency (ELF) magnetic fields. Due to these reasons, remarkable efforts have been devoted to search for suitable techniques to achieve the desired reduction of magnetic fields generated by distribution substations. Several techniques have been applied to mitigate the magnetic field.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 9: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Intrinsic methods, when they act on the basic factors affecting the field strength, such as phase arrangement.

External shielding techniques, would mean the use of shields made of ferromagnetic or conductive materials.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 10: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Intrinsic methods

A. Magnitude of phase currents: At power frequency,the magnetic field strength

is proportional to the phase current magnitude. Line currents on substation buses, vary widely in both their magnitudes and phase angles. Utilities normally calculate magnetic fields using estimated current magnitudes. With unbalanced currents the magnetic field strength is greater than the balanced ones.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 11: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

B. Height of conductors above/below ground: Increasing the height of the current- carrying

conductors will reduce the magnetic fields at or near ground level.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 12: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

C. Conductor configuration: The magnetic field level in substation is the

sum of the fields produced by the currents in all conductors and is dependent upon the distance between the observer and each current -carrying conductor. Placing the three conductors as close together as possible creates greater field cancellation and the magnetic field at or near ground level is reduced.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 13: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

EXTERNAL SHIELDING TECHNIQUES

Field management can also be achieved through the use of shielding materials. AC magnetic shielding uses either conductive materials or ferromagnetic materials.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 14: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

(I) Conductive Materials (flux cancellation)

Conductive materials (e.g. copper and aluminum) act as a shield because induced eddy currents produce a magnetic field that opposes the main existing magnetic field.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 15: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

(II)Ferromagnetic Materials (flux-shunting)

Ferromagnetic materials such as iron or steel, shunts the magnetic flux. Iron and steel have high permeabilities, but some alloys such as mu-metal( which is a mix of nickel, iron, copper and chromium) have higher permeability. These alloys with higher permeability are more effective than just iron or steel but they are more expensive.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 16: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

MEASURMENT AND SIMULATION CASE STUDY A typical indoor distribution substation for a

residential area which houses a (delta/star) transformer rated at 1MVA with 11kV circuit breakers and 3phase, 4 wire 380/220 V distribution panel as shown in Fig.1. The Magnetic field measurements were carried out at height of one meter above the ground level and the results are indicated in the measuring grid of (0.5m×0.5 m) Fig (2)

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 17: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Fig.1. Low voltage panel

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 18: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Fig.2. The magnetic field measurement inside transformer distribution substation

transformer

1000kV

A

Low

tens

ion

Pane

l

1

2

3

4

5

6

123456

4 8 .3 2 2 0 .7 7 1 2 .7 79 0 .3 9

6 1 .9 8 2 4 .5 2 1 2 .3 31 6 .8 81 8 .6 31 4 5 .7

1 6 4 .3 6 4 .1 6 2 9 .6 9 2 8 .3 7

3 7 .7

2 8 .3 2 1 5 .9 4

2 9 .9 1

8 7 .3 21 7 3 .96 8 .7 83 7 .7 5

9 5 .5 9

M VLV

1 2 .1 1

4 8 .9

8 .1 8 1

2 4 .6 8 7 .6 39 .1 0 11 0 .6 81 4 .2 1

8 .4 9 59 .4 0 31 6 .1 42 9 .2 3 6 .4 6 47 .7 9 3

Page 19: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

The 3D representation is illustrated in Fig.3.The currents measured during the magnetic field measurement is of an average value of 200A, and the neutral current was 48.7 A. The measurements were taken during the day.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 20: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Fig.3. 3D representation for the magnetic field measurements

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 21: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Magnetic Fields Modelling Program was developed to model, simulate and calculate the magnetic field at any point on the grid. The program models the power frequency magnetic fields substation.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 22: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

In this research, the program is used to model the magnetic field in 11/0.4 kV distribution substation. The magnetic field output of the simulation program for the same measured substations and for the same loading conditions is also presented in 3D format for the simulated output of the substation model as shown in Fig.4.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 23: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Fig.4. 3D format for the magnetic field simulation

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 24: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

COMPARISON BETWEEN MEASUREMENTS AND SIMULATION RESULTS It can be observed that the simulation

profile agrees with the measurements profile on the overall distribution of the magnetic field. This indicates the effectiveness of the developed program. This good agreement will encourage us to use the program in applying many modifications in the LV cables and the low voltage panel boards arrangements.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 25: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Management application

The developed program was used to find out the effect of the new arrangements in the distribution substation with the same current loads. The new arrangements were as follows: Reduce the separation distance between the LV

cable side Re-arrange the low voltage panel boards by

making the LV busbars in the same horizontal level with lateral distance between phases of 5cm, instead of the vertical arrangement

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 26: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

These new arrangements are applied and the simulated results are presented in 3 D format as shown in Fig.5. The maximum calculated magnetic field was 250µT, while before these modifications the maximum values was about 600µT.

This means that we can reduce the magnetic field emission without added cost.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 27: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Fig.5. 3D format for the magnetic field simulation

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 28: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

External Shielding Experiments

Measurements were taken over the LV cables trench before shielding and after putting shielding and were compared for the different materials used.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 29: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

1. sheets of electrolytic copper 1mm thickness, and area 0.5×0.5 m2, with conductivity σ=58×106 S/m, and Relative Permeability μr=1.

2. Aluminum sheets 2mm thickness and area 0.5×0.5 m2 ,σ= 38× 106 S/m, and μr=1.

3. Low-loss silicon steel with 0.5mm thickness , 0.5×0.5m2, and μr = 1000.

4. and mu-metal 90µm thickness and area 0.5×0.5m2, σ= 2×106 S/m, μr = 105.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 30: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Magnetic field measurement results were taken along the z-axis at a different heights of 0.5 m over the shielding material. As shown in Fig.7

To discuss the shielding effectiveness we should calculate the shielding efficiency (SE) which depends on the ratio of the field measured at the point (x,y,z) for two different circumstances with shielding and without shielding.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 31: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Fig.7. The measurements before and after shielding with different material

Page 32: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

For power frequency magnetic field Shielding effectiveness the following equation can be used:

 Where:

Bo : is the field without shield,

Bshielding : is the field when the shield is present.

dBB

BSE

shielding

olog20

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 33: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Fig.8. illustrates the shielding efficiency for the different used materials

Fig.8. Shielding efficiency results

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 34: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

RESULTS AND DISCUSIONS

The results indicates that the magnetic field measured is the highest one at distance 1.5m. This is because in this position the magnetic meter was adjacent to the low voltage panel.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 35: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

The best shielding efficiency value was for the low-loss silicon steel which reaches 3.81dB, then for the mu-metal which reaches 2.17 dB taking into consideration that the mu-metal thickness was 90µm and the low-loss silicon steel thickness was 0.5mm.Their high permeability attract the field lines.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 36: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

RESULTS AND DISCUSIONS

The shielding efficiency for Aluminum and copper were the lowest values. The reason may be because that the penetration depth (δ at 50 Hz) for copper is 9.44 mm and for Aluminum is 12.33 mm, while the penetration depth in magnetic materials (low-loss silicon steel or mu-metal) are much smaller than that of aluminum or copper.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 37: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

Therefore, it is common to regard conductive flat shielding with thin non-magnetic materials at power frequencies as inherently inefficient (since any practical shield would have thickness less than the penetration depth δ)

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 38: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

CONCLUSIONS

This paper useds the developed SUBCALC simulation program to find out the results of the magnetic field managements by rearranging the distribution substation components. These applicable managements gave the best reduction values for the magnetic field exposure without additional cost.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 39: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

For the shielding experiment the obtained results show that the use of low-loss silicon steel give best shielding results, then the mu- metal which is very thin compared to the rest of the used materials ;but it has higher cost. Their high permeability makes them attract the field lines.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 40: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

The conductive materials (copper and aluminum) are not good shielding materials for power frequency magnetic fields.

It is recommended to apply the intrinsic method (no cost or low cost solution) before external shielding which has higher cost.

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119

Page 41: POWER FREQUENCY MAGNETIC FIELD MANAGEMENT IN POWER DISTRIBUTION SUBSTATION Prof. Ahmed A.HOSSAM-ELDIN Prof. Ahmed S.FARAG Electrical Engineering Department,

Frankfurt (Germany), 6-9 June 2011

THANK YOU FOR YOUR ATTENTION

Prof. Ahmed HOSSAM-ELDIN– Egypt – Session 2 – Paper ID 0119


Recommended