Date post: | 18-Aug-2015 |
Category: |
Engineering |
Upload: | paulo-chong-santos |
View: | 40 times |
Download: | 3 times |
Mission Critical Applications
INFINITE POWER
UPS
prestige series
PC´s and Servers, Small to Midsized Networks,CCTV and Security Systems, Railway Signaling.
High output power factor (PF=0.9)
Double Conversion On Line TechnologyRack / Tower Convertible Design
Advanced Digital Control Technology Wide Range Input Window from 110~300Vac Active Harmonic Current ControlMulti-Mode OperationSmart cooling Fan Design
Remote Emergency Power Off
Personalization & Intelligent Self-diagnostic Easily Program Upgrade
UNINTERRUPTIBLE POWER SUPPLY
GROUP
From 1000 VA to 3000 VA
overview
02
UNITY INPUT POWER FACTOR
Meet today’s industry standard for energy saving and low reflected harmonic pollution to the utility.
SINGLE CHIP MICROPROCESSOR CONTROL
The SYS PRESTIGE uses a field proven MPU to substantially reduce the component count.This provides greater reliability, functionality and smaller size than other designs. Using the latest high frequency techniques and quality components reliability is further increased. High system efficiencyis achieved in all operating modes saving electricity.
In today´s world we are heavily reliant on technology and the power that drives it. If you do not have the correct protection you are putting your business at risk of downtime, lost data and evencomponent damage. The SYS PRESTIGE is a cost effective way of meeting your critical power needs and integrated seamlessly into the modern network environment.
powerfull LCD Display
SYS PRESTIGE ON-LINE UPS
From 1000 VA to 3000 VA
EASY COMMUNICATION PLUG & PLAY SELF DIAGNOSTICS
03
Complete Protection Circuitry
Convertible design
The SYS PRESTIGE was designed with today’s technology in mind and is particularly suited tocomputer and telephony switch mode power supply. Through careful design, maximum security is provided to the load. In particular the units feature high overload handling without transfer to bypass. Short circuit and over temperature are protected as standard. The input circuitry can handle very wide range of AC input voltages to avoid the frequent use of battery energy. Consequently, the systemsecurity and battery life can be maximized ensuring that the batteries are available when you need them most... Power failures!
User friendly display
An easy-to-read LED/LCD display provides real time indication of all major system parameters and status such as operation modes AC voltage, frequency, battery voltage, load level, temperature, etc.
SYS PRESTIGE ON-LINE UPS
From 1000 VA to 3000 VA
Double conversionon-line technology
The SYS PRESTIGE is a true VFI (voltage and frequency independent) with bypass UPS and completely re-generates the utility power to correct the power disturbance in the Mains. The unit provides clean AC power 24 hours a day 365 days a year.
Battery Speci�cations
Title Contents 1KVA 2KVA 3KVA
Battery
Rated Battery Voltage
Battery Type 12V / 7Ah or 9Ah (Sealed, non-spillage, maintenance-free, lead acid)
24 48 72
Prestige Series Model RT 1kVA RT 2 kVA RT 3kVA
Input
Phase Single + G
Voltage 110~300Vac
Frequency 45~65Hz(Auto sensing)
Power Factor ≧0.99 @ Full Load
Output
E�cency
Capacity 1000VA/900W 2000VA/1800W 3000VA/2700W
Voltage 110/115/120/127Vac or 220/230/240Vac
Power Factor
Harmonic Distortion
Voltage Regulation
0.9
≦3% @ 100% Linear load
≦7% @ 100% non-linear load
±1%
Frequency(Synchronized Range)
±1Hz or ±3Hz (Selectable)
Crest Factor 3:1
Waveform Pure Sine Wave
Line Mode Up to 92%
High E�cency Mode Up to 96%
BatteryType & Number 12V/9Ah x (2) 12V/7Ah x (4) 12V/7Ah x (6)
Recharge Time (to 90%) 4 hours
DisplayLCD
Self-Diagnostics
Normal, Ba ery, Bypass, Programmable Outlet 1, Programmable Outlet 2, Self-Test, Ba ery Weak & Bad, Site Wiring Fault , Fa ery Level
Upon Power-on, Front Panel Se ng & So ware Control, 24 hours ro ne check
Alarm Audible or Visual
Full Protection
Multi-Mode
Line Failure / Ba ery Low / Transfer to Bypass / System Fault
Protection
Function
Overload, Over temperature, Short circuit, Discharge, Overcharge
Normal/ ECO/ CVCF
DC start Yes
Programmable Outlet Yes
Physical
Dimensions (WxHxD, mm)
440x88x390 (2U) 440x88x475 (2U) 440x88x600 (2U)
Net Weight (kgs)
Operation Temperature
12 17 26.5
Environmental
0- 40℃
Operation Humidity
Altitude
0-95 % (Without condensing)
without Dera ng
Noise Level ≦45dBA
Interface
Standard
Option
Compatible Platforms
RS-232 - EPO
2nd RS232, USB, RS485, Dry Contact Relay, SNMP/WEB Card
Micr Windows series, Linux, Mac, etc.
Standards and Certi�cations
Safety EN62040-1, UL1778
EMC EN62040-2, EN61000-3-2, EN61000-3-3, FCC Class A
Marks CE, UL, cUL, FCC
SYS PRESTIGE ON-LINE UPS
From 1000 VA to 3000 VA
04
www.sensysgroup.com