44
Features High reliability Simple installation and operation LCD display for self-guided controller operation RS232 interface for remote operation Intelligent battery management: Temperature compensation (requires optional cables) Programmable battery load testing with data logging Symmetry (requires optional cables) Programmable low voltage disconnect Optional Ethernet (SNMP compatible) interface module Natural convection cooling - no fans International standards compliance Description PPS 7 modular DC power shelf systems provide large power system features in cost-effective, rack-mounted form factors. These shelf power solutions provide rectification, system management, and power distribution while maintaining high reliability and offering flexibility for future expansion. The PPS 7 systems are based on hot-swappable rectifier modules output power available at 450, 560 or 670W per module. System management is accomplished through messages and alarms displayed on the system controller’s (PCU) LCD screen and can also be displayed remotely via the PC-based PowCom TM software package. PPS 7 Power System Shelf System www.power-one.com
Transcript
  • Features• High reliability• Simple installation and operation• LCD display for self-guided controller operation• RS232 interface for remote operation• Intelligent battery management:

    • Temperature compensation(requires optional cables)

    • Programmable battery load testing with data logging

    • Symmetry (requires optional cables)• Programmable low voltage disconnect

    • Optional Ethernet (SNMP compatible) interface module

    • Natural convection cooling - no fans• International standards compliance

    DescriptionPPS 7 modular DC power shelf systemsprovide large power system features incost-effective, rack-mounted form factors.These shelf power solutions providerectification, system management, andpower distribution while maintaining highreliability and offering flexibility for futureexpansion. The PPS 7 systems are basedon hot-swappable rectifier modules outputpower available at 450, 560 or 670W permodule.

    System management is accomplishedthrough messages and alarms displayedon the system controller’s (PCU) LCDscreen and can also be displayedremotely via the PC-based PowComTM

    software package. Note: All specifications are subject to change without notification.

    Input

    Output

    Mechanical

    Options

    Features

    Battery

    Model PPS 7-2100 PPS 7-2800 PPS 7-3500 PPS 7-4200

    Input230/400V 3-phase208-240V 1-phaseSite configurable

    230/400V 3-phase208-240V 1-phaseSite configurable

    230/400V 3-phase208-240V 1-phaseSite configurable

    230/400V 3-phase208-240V 1-phaseSite configurable

    Inputs (max.) Single input Single input Single input Single input

    Rectifier Modules (max.) 3 4 5 6

    Battery Outputs 1 1 2 2

    Load Outputs 6 1 20 24

    24V DC Version Yes N/A N/A N/A

    48V DC Version Yes Yes Yes Yes

    60V DC Version Yes (on request) Yes (on request) Yes (on request) Yes (on request)

    Supervision PCU PCU PCU PCU

    Battery Symmetry Inputs(max.)

    1 1 3 3

    Low Voltage BatteryDisconnection (LVBD) Yes Yes Yes Yes

    Dimensions (WxHxD) 485x133x305mm 485x133x305mm 485x133x305mm 582x266x305mm

    Mounting19”, ETSI, or flushETSI mount (site configurable)

    19”, ETSI, or flushETSI mount (site configurable)

    19”, ETSI, or flushETSI mount (site configurable)

    23”

    Cable Entry Top Top Top Top

    Temp. Comp. Charge Yes Yes Yes Yes

    Ethernet NetworkInterface Yes Yes Yes Yes

    Modem Interface Yes Yes Yes Yes

    PPS 7 Power SystemShelf System

    www.power-one.comwww.power-one.com

    Shelf System

    11V0005-036 PPS7 SY V3.0

    PPS 7 Power System

  • Rectifier Features

    Model Voltage Power(max.)Current(max.)

    PMP 5.24 SIC 110* 24V DC 448W 16A

    PMP 5.48 SIC 110* 48V DC 448W 8A

    PMP 7.24 SIC 24V DC 560W 20A

    PMP 7.48 SIC 48V DC 672W 12A

    PMP 7.60 SIC 60V DC 635W 9A

    The PPS 7 system utilizes plug-in rectifier modules that arebased on a soft-switching approach. Features include 3 LEDsfor rectifier status indication, thermal shutdown, and inputovervoltage disconnection with an automatic reset (only onPMP 7 modules).

    • Menu guided operation• RS232 interface for remote operation• Battery management and testing• Low voltage battery disconnect (LVBD)• Temperature compensation• Battery symmetry measurement• Optional Ethernet interface through SNMP and/or TCP/IP• Partial load disconnection (PLD)

    PCU Features

    Rectifier Modules

    Advanced system supervision is accomplished using amicroprocessor based control module that allows both localand remote system monitoring.

    Supervision Modules

    An all-in-one 3U high shelf system that can beinstalled in both 19” and ETSI telecom cabinetsolutions. The system subrack canaccommodate up to three rectifier modules, asupervision module (PCU) and DC distributionwith a single battery breaker and six loadbreakers.

    PPS 7-2100 SystemAn all-in-one 3U high shelf system that can beinstalled in both 19” and ETSI telecom cabinetsolutions. The system subrack canaccommodate up to four rectifier modules, asupervision module (PCU) and DCdistribution with a single battery breaker and asingle load breaker.

    PPS 7-2800 System

    An all-in-one 6U high shelf system that can beinstalled in 23” standard telecom cabinetsolutions. The system subrack canaccommodate up to six rectifier modules, asupervision module (PCU) and DC distributionwith up to two battery breakers and twentyfour load breakers.

    PPS 7-4200 SystemAn all-in-one 6U high shelf system that can beinstalled in 19” and ETSI telecom cabinetsolutions. The system subrack canaccommodate up to five rectifier modules, asupervision module (PCU) and DC distributionwith up to two battery breakers and twentyload breakers.

    PPS 7-3500 System

    *110V AC input

    System Configurations System Components

    PPS 7 Power SystemShelf System

  • Rectifier Features

    Model Voltage Power(max.)Current(max.)

    PMP 5.24 SIC 110* 24V DC 448W 16A

    PMP 5.48 SIC 110* 48V DC 448W 8A

    PMP 7.24 SIC 24V DC 560W 20A

    PMP 7.48 SIC 48V DC 672W 12A

    PMP 7.60 SIC 60V DC 635W 9A

    The PPS 7 system utilizes plug-in rectifier modules that arebased on a soft-switching approach. Features include 3 LEDsfor rectifier status indication, thermal shutdown, and inputovervoltage disconnection with an automatic reset (only onPMP 7 modules).

    • Menu guided operation• RS232 interface for remote operation• Battery management and testing• Low voltage battery disconnect (LVBD)• Temperature compensation• Battery symmetry measurement• Optional Ethernet interface through SNMP and/or TCP/IP• Partial load disconnection (PLD)

    PCU Features

    Rectifier Modules

    Advanced system supervision is accomplished using amicroprocessor based control module that allows both localand remote system monitoring.

    Supervision Modules

    An all-in-one 3U high shelf system that can beinstalled in both 19” and ETSI telecom cabinetsolutions. The system subrack canaccommodate up to three rectifier modules, asupervision module (PCU) and DC distributionwith a single battery breaker and six loadbreakers.

    PPS 7-2100 SystemAn all-in-one 3U high shelf system that can beinstalled in both 19” and ETSI telecom cabinetsolutions. The system subrack canaccommodate up to four rectifier modules, asupervision module (PCU) and DCdistribution with a single battery breaker and asingle load breaker.

    PPS 7-2800 System

    An all-in-one 6U high shelf system that can beinstalled in 23” standard telecom cabinetsolutions. The system subrack canaccommodate up to six rectifier modules, asupervision module (PCU) and DC distributionwith up to two battery breakers and twentyfour load breakers.

    PPS 7-4200 SystemAn all-in-one 6U high shelf system that can beinstalled in 19” and ETSI telecom cabinetsolutions. The system subrack canaccommodate up to five rectifier modules, asupervision module (PCU) and DC distributionwith up to two battery breakers and twentyload breakers.

    PPS 7-3500 System

    *110V AC input

    System Configurations System Components

    PPS 7 Power SystemShelf System

  • Features• High reliability• Simple installation and operation• LCD display for self-guided controller operation• RS232 interface for remote operation• Intelligent battery management:

    • Temperature compensation(requires optional cables)

    • Programmable battery load testing with data logging

    • Symmetry (requires optional cables)• Programmable low voltage disconnect

    • Optional Ethernet (SNMP compatible) interface module

    • Natural convection cooling - no fans• International standards compliance

    DescriptionPPS 7 modular DC power shelf systemsprovide large power system features incost-effective, rack-mounted form factors.These shelf power solutions providerectification, system management, andpower distribution while maintaining highreliability and offering flexibility for futureexpansion. The PPS 7 systems are basedon hot-swappable rectifier modules outputpower available at 450, 560 or 670W permodule.

    System management is accomplishedthrough messages and alarms displayedon the system controller’s (PCU) LCDscreen and can also be displayedremotely via the PC-based PowComTM

    software package. Note: All specifications are subject to change without notification.

    Input

    Output

    Mechanical

    Options

    Features

    Battery

    Model PPS 7-2100 PPS 7-2800 PPS 7-3500 PPS 7-4200

    Input230/400V 3-phase208-240V 1-phaseSite configurable

    230/400V 3-phase208-240V 1-phaseSite configurable

    230/400V 3-phase208-240V 1-phaseSite configurable

    230/400V 3-phase208-240V 1-phaseSite configurable

    Inputs (max.) Single input Single input Single input Single input

    Rectifier Modules (max.) 3 4 5 6

    Battery Outputs 1 1 2 2

    Load Outputs 6 1 20 24

    24V DC Version Yes N/A N/A N/A

    48V DC Version Yes Yes Yes Yes

    60V DC Version Yes (on request) Yes (on request) Yes (on request) Yes (on request)

    Supervision PCU PCU PCU PCU

    Battery Symmetry Inputs(max.)

    1 1 3 3

    Low Voltage BatteryDisconnection (LVBD) Yes Yes Yes Yes

    Dimensions (WxHxD) 485x133x305mm 485x133x305mm 485x133x305mm 582x266x305mm

    Mounting19”, ETSI, or flushETSI mount (site configurable)

    19”, ETSI, or flushETSI mount (site configurable)

    19”, ETSI, or flushETSI mount (site configurable)

    23”

    Cable Entry Top Top Top Top

    Temp. Comp. Charge Yes Yes Yes Yes

    Ethernet NetworkInterface Yes Yes Yes Yes

    Modem Interface Yes Yes Yes Yes

    PPS 7 Power SystemShelf System

    www.power-one.comwww.power-one.com

    Shelf System

    11V0005-036 PPS7 SY V3.0

    PPS 7 Power System

  • DescriptionThe Power-One PMP 5 rectifier moduleprovides a cost-effective power solutionin a high density footprint. Built on thelatest advances in the resonance switchmode approach (soft-switching), thePMP 5 is the next evolution in our smallconvection cooled rectifier series.

    Optimized for telecom applications, themodule is designed to work in amultitude of different subrack/shelfconfigurations incorporating the Power-One PCU controller and variousdistribution options.

    Features• 115/230 VAC input• 24V, or 48VDC output• Power factor correction• Active load sharing• Hot-swappable• International standards compliance• Natural convection cooling• Low weight

    PPS 5/7 SystemShown

    PMP 5Rectifier Module

    www.power-one.com

  • InputModel PMP 5.24 PMP 5.48 PMP5.24-110

    PMP5.48-110

    InputVoltage

    161-276V AC singlephase, (44-66Hz)

    80-138V AC singlephase, (44-66Hz)

    Current(max.) 87% >87%

    Tolerance Vout +/- 1%

    TransientResponse

    +/- 5% at load variation 10-90% or 90-10%,recovery time 10ms

    Load Sharing

  • DescriptionThe Power-One PMP 7 rectifier moduleprovides a cost-effective power solutionin the highest possible density. Built onthe latest advances in the resonanceswitch mode approach (soft-switching),the PMP 7 is the next evolution in oursmall convection cooled rectifier series.

    Optimized for telecom applications, themodule is designed to work in a multitudeof different subrack/shelf configurationsincorporating the Power-One PCUcontroller and various distributionoptions.

    Features• 208/240 VAC input• 24V, 48V, or 60V DC output• Input overvoltage disconnection• Thermal protection• Active load sharing• Hot-swappable• Up to 92% efficient• International standards compliance• Natural convection cooling• Low weightPPS 7 3500 System

    Shown

    PMP 7Rectifier Module

    www.power-one.com

  • InputModel PMP 7.24 PMP 7.48 PMP 7.60

    InputVoltage

    205-250V AC ±10% single phase, (44-66Hz) (-15% for PMP7.60)185-160V at reduced output power

    Current(max.)

  • The PCU 5/ 7Controllers are usedin PPS5 and PPS7Power Systems.

    DescriptionThe Power-One Control Unit (PCU 5/7) provides monitoring and control for the PPS 5 and PPS 7power systems. These hot-swappable controller modules supervise output voltages, currents, rectifierperformance, battery condition, and breaker status. Visual notification of an alarm condition isprovided with an LED. A description of the exact alarm condition is provided through an LCD.Additionally, four Form “C” contacts are provided to indicate a failure.

    FeaturesUser controls and interfaces:

    • Simple menu-guided operation using front panel mounted pushbuttons and an LCD

    • User-selectable alarm parameters

    • Data logging of last 40 events

    • SNMP interface adapter available

    • RS232 interface and Form “C” dry alarm contacts

    • Compatible with PowComTM PC-based software

    PCU 5/7Controller

    www.power-one.com

    Intelligent battery management:

    • Temperature compensation with programmable compensation factor

    • Automatic and manual load testing

    • Battery voltage and symmetry monitoring

    • Capacity testing

    • Low voltage disconnect

  • InputVoltage 18-72V DC

    Current

  • DescriptionThe Power-One PPR 5/7 3 and 6position rectifier backplane provides acost-effective power solution in a highdensity wall-mounted footprint. Thesepower solutions provide rectification,system management, and powerdistribution while maintaining highreliability and offering flexibility forfuture expansion. The PPS 5/7 3 & 6Position systems are based on hot-swappable rectifier modules outputpower available at 450, 560 or 670W permodule.

    Features• 115/230 VAC input• 24V, or 48VDC output• Serial or parallel alarm configurations• Active load sharing• Hot-swappable• International standards compliance• Natural convection cooling• Systems can be paralleled• Individual rectifier output adjustment6 Position SystemShown

    PPR 5/73 & 6 Position Power Systems

    www.power-one.com

  • www.power-one.com11V0005-065 PPR 5/7 V3.0

    PPR 5/73 & 6 Position Power Systems

    Note: All specifications are subject to change without notification.

    Input

    Output

    Mechanical

    Features

    Model PPR 5/7 3-Position PPR 5/7 6-Position

    Input115 or 230VAC single phase(Depending on rectifiermodule)"

    115 or 230VAC single phase(Depending on rectifiermodule)"

    Input Connections 3x4mm² terminal blocks 3x4mm² terminal blocks

    Rectifier Modules (max.) 3 6

    Load Outputs 2x10mm² - Qty 3 2x10mm² - Qty 6

    24V DC Version Yes Yes

    48V DC Version Yes Yes

    AlarmsCommon alarm for High Voltage/ Shutdown, Low Voltage/Module Failure, Unequal Load Sharing Normally Openedor Normally Closed.

    Dimensions (WxHxD) 271x193.5x305mm 484.4x193.5x305mm

    Weight 1.2kg (2.65lbs.) 2.5kg (5.5lbs.)

    Mounting Wall Mount Wall Mount

    Model Voltage Power (max.) Current (max.)

    PMP 5.24 24V DC 448W 16A

    PMP 5.24 SIC 110* 24V DC 448W 16A

    PMP 5.48 SIC 110* 48V DC 448W 8A

    PMP 7.24 SIC 24V DC 560W 20A

    PMP 7.48 SIC 48V DC 672W 12A

    *110V AC input

    Available Rectifiers

  • Features• High reliability• Simple installation and operation• Natural convection cooling - no fans• RS232 interface for remote operation• Form “C” dry alarm contacts• Intelligent battery management• Pluggable controller and DC distribution

    modules• Optional Ethernet (SNMP compatible) interface

    module • International standards compliance

    DescriptionThe Galero™ Power System provideslarge power system features in cost-effective, rack-mounted form factors.These power solutions providerectification, control and powerdistribution all in one compact systemwhile offering extensive local and remotepower system and battery monitoring.

    System management is accomplishedthrough the system controller (GMC).Status indication is made via LED’s, whiledetailed information and remote operationare accomplished through the PC-basedPowComTM software package.

    Note: All specifications are subject to change without notification.

    Input

    Output

    Mechanical

    Options

    Features

    Battery

    Model Galero 1750 Galero 2450

    Input230/400V AC 3-phase205-240V AC 1-phaseSite configurable

    230/400V AC 3-phase205-240V AC 1-phaseSite configurable

    Inputs (max.) Single input Single input

    Rectifier Modules (max.) 5 7

    Battery Outputs 1 2 1 2

    Load Outputs 10 9 3 2

    48V DC Version Yes Yes

    Supervision GMC GMC

    Battery Symmetry Inputs (max.) 2 2

    Low Voltage BatteryDisconnection (LVBD) Yes Yes

    Temp. Comp. Charge Yes Yes

    Dimensions (WxHxD) 483x125x280mm 483x125x280mm

    Mounting 19”, ETSI 19”, ETSI

    Cable Entry AC - RearDC and signals -TopAC - RearDC and signals -Top

    Temp. Comp. Charge Yes Yes

    Battery SymmetryMeasurement Yes Yes

    Ethernet Network Interface Yes Yes

    Partial Load Disconnect N/A N/A

    Integrated Surge Arrestors N/A N/A

    Galero™ Power System

    www.power-one.comwww.power-one.com11V0005-033 Galero SY V3.0

    Galero™ Power SystemShelf SystemShelf System

  • Rectifier Features

    Model Voltage Power(max.)Current(max.)

    CMP 3.48 48V DC 364W 6.5A

    The Galero Shelf System utilizes plug-in rectifiermodules based on a soft-switching approach.Features include 2xLED for rectifier status indication,thermal protection with de-rating and input over-voltage disconnection with automatic reset.

    • Advanced system monitoring• RS232 interface for remote operation• Battery management and testing• Automatic testing• Low voltage battery disconnect (LVBD)• Temperature compensation• Battery symmetry measurement• Monthly logging of battery parameters including “temperature-hours”• Site programmable Flash EPROM• Programmable alarms• Programmable logic circuit• Optional Ethernet interface through SNMP and/or TCP/IP

    GMC Features

    Rectifier Module

    Advanced system supervision is accomplished using amicroprocessor based module that allows both local andremote system monitoring.

    Supervision Module - GMC

    All-in-one 125 mm high shelf system for integration into standard19” or ETSI cabinets. Complete subrack for five rectifier modules, supervision moduleand DC distribution with battery breakers (1-2) and load breakers(9-10).

    Galero 1750 System

    All-in-one 125 mm high shelf system for integration intostandard 19” or ETSI cabinets. Complete subrack for seven rectifier modules, supervisionmodule and DC distribution including battery breakers (1-2) andload breakers (2-3).

    Galero 2450 System

    System Configurations System Components

    Galero™ Power SystemShelf System

  • Rectifier Features

    Model Voltage Power(max.)Current(max.)

    CMP 3.48 48V DC 364W 6.5A

    The Galero Shelf System utilizes plug-in rectifiermodules based on a soft-switching approach.Features include 2xLED for rectifier status indication,thermal protection with de-rating and input over-voltage disconnection with automatic reset.

    • Advanced system monitoring• RS232 interface for remote operation• Battery management and testing• Automatic testing• Low voltage battery disconnect (LVBD)• Temperature compensation• Battery symmetry measurement• Monthly logging of battery parameters including “temperature-hours”• Site programmable Flash EPROM• Programmable alarms• Programmable logic circuit• Optional Ethernet interface through SNMP and/or TCP/IP

    GMC Features

    Rectifier Module

    Advanced system supervision is accomplished using amicroprocessor based module that allows both local andremote system monitoring.

    Supervision Module - GMC

    All-in-one 125 mm high shelf system for integration into standard19” or ETSI cabinets. Complete subrack for five rectifier modules, supervision moduleand DC distribution with battery breakers (1-2) and load breakers(9-10).

    Galero 1750 System

    All-in-one 125 mm high shelf system for integration intostandard 19” or ETSI cabinets. Complete subrack for seven rectifier modules, supervisionmodule and DC distribution including battery breakers (1-2) andload breakers (2-3).

    Galero 2450 System

    System Configurations System Components

    Galero™ Power SystemShelf System

  • Features• High reliability• Simple installation and operation• Natural convection cooling - no fans• RS232 interface for remote operation• Form “C” dry alarm contacts• Intelligent battery management• Pluggable controller and DC distribution

    modules• Optional Ethernet (SNMP compatible) interface

    module • International standards compliance

    DescriptionThe Galero™ Power System provideslarge power system features in cost-effective, rack-mounted form factors.These power solutions providerectification, control and powerdistribution all in one compact systemwhile offering extensive local and remotepower system and battery monitoring.

    System management is accomplishedthrough the system controller (GMC).Status indication is made via LED’s, whiledetailed information and remote operationare accomplished through the PC-basedPowComTM software package.

    Note: All specifications are subject to change without notification.

    Input

    Output

    Mechanical

    Options

    Features

    Battery

    Model Galero 1750 Galero 2450

    Input230/400V AC 3-phase205-240V AC 1-phaseSite configurable

    230/400V AC 3-phase205-240V AC 1-phaseSite configurable

    Inputs (max.) Single input Single input

    Rectifier Modules (max.) 5 7

    Battery Outputs 1 2 1 2

    Load Outputs 10 9 3 2

    48V DC Version Yes Yes

    Supervision GMC GMC

    Battery Symmetry Inputs (max.) 2 2

    Low Voltage BatteryDisconnection (LVBD) Yes Yes

    Temp. Comp. Charge Yes Yes

    Dimensions (WxHxD) 483x125x280mm 483x125x280mm

    Mounting 19”, ETSI 19”, ETSI

    Cable Entry AC - RearDC and signals -TopAC - RearDC and signals -Top

    Temp. Comp. Charge Yes Yes

    Battery SymmetryMeasurement Yes Yes

    Ethernet Network Interface Yes Yes

    Partial Load Disconnect N/A N/A

    Integrated Surge Arrestors N/A N/A

    Galero™ Power System

    www.power-one.comwww.power-one.com11V0005-033 Galero SY V3.0

    Galero™ Power SystemShelf SystemShelf System

  • DescriptionThe Power-One CMP 3.48, for use in theGalero™ series of power systems, is thenext evolution in our convection cooledrectifier series. This module provides thelatest advances in resonance switch modetechnology (softswitching). An onboardmicrocontroller and an RS 485 data busprovide monitoring of basic functions, statusand identification information to the systemcontroller (GMC).

    The CMP 3.48 rectifier module is optimizedfor telecom applications and is designed towork in numerous subrack/shelfconfigurations incorporating the GMCcontroller and varying distribution options.

    Features• 208/240 VAC input• 48 VDC output• Input over-voltage disconnection• Thermal protection, with de-rating• Active load sharing• Hot-swappable • Up to 91% efficient• Natural convection cooling• Low weight• International Standards Compliance

    Galero™ PowerSystem

    CMP 3.48Rectifier Module

    www.power-one.com

  • InputModel CMP 3.48

    Input Voltage205-240V AC +10% single phase,44-66Hz(185-160V at reduced power output)

    Current (max.) 91%

    Tolerance Vout +/- 1.0%,

    TransientResponse

    +/- 5% at load variation 10-90% or 90-10% recovery time 10ms

    Load Sharing Typical 250VAC.

    Indications

    Green LED

    Red LED

    Power ON

    High outputvoltage/ shut downLow voltage/module failure

    AudibleNoise

  • DescriptionThe Galero™ Microprocessor Controller (GMC) from Power-One provides comprehensive monitoring andcontrol of the Galero power system. This digital controller monitors total system conditions including DCvoltage, rectifier current, rectifier temperature, system capacity, battery parameters and circuit breakerstatus.

    The GMC enables data storage of system configuration information such as battery type, installation dateand system commission date. Visual notification of alarm and warning conditions are indicated by frontpanel LEDs, while descriptions of the alarms are provided through RS232 communication using PC-basedPowCom™ software package.

    To meet individual site requirements, the GMC contains a Programmable Logic Unit that can beprogrammed to monitor and control specified requirements. This allows actions to be set, alarms to betriggered and outputs to be activated based on internal and external signal monitoring, comparing andprocessing.

    FeaturesUser controls and interfaces:

    • User-selectable alarm parameters

    • 40 event data logging

    • Password controlled environment

    • RS232 Interface and Form “C” dry alarm contacts

    • Programmable routing alarm

    • Programmable logic unit

    GMCController Module

    www.power-one.com

    Intelligent battery management:

    • Temperature compensation with programmable compensation factor

    • Automatic and manual load testing

    • Battery voltage and symmetry monitoring

    • Capacity testing

    • Low voltage disconnect

    • Optional plug-in Ethernet interface (PNI module)

  • InputVoltage 30-60V DC

    Current

  • Input

    Input Voltage 180-264 VAC

    Frequency 47-63Hz

    Input Current 9.33A @180VAC

    Power Factor >.98 Typical

    Output

    Alarms

    Alarm History 40 event alarm history

    AlarmContacts

    Four free alarm contacts (max.60V, 1A) Two open collectoroutputs for LVD

    Alarms High DC VoltageLow DC VoltageLoad/ Battery DisconnectionBattery Fuse FailureDC Fuse FailureModule FailureMain AC FailureBattery FailureSymmetry FailureHigh TemperatureHigh Load

    Voltage 42V-58VDC (54VDC Nominal)

    Output up to 500A in 4 subrack/ shelfsystem

    Power (at 208/240VAC)

    1350W (up to 50°C) per rectifier1200W (up to 65°C) per rectifier

    Efficiency 90% typical

    MechanicalDimensions(WxHxD)

    584.2/482.6 x 133.35 x 274.32mm(23/19 x 5.25 x 10.8in.)

    Shelf withoutController

    584.2/482.6 x 88.9 x 274.32mm(23/19 x 3.5 x 10.8in.)

    Mounting 19/23in. rack mount

    Cooling Fan Cooled, speed controlled andalarmed

    Other Technical DataOperatingTemperature

    -40 to +65°C, (Derated to 700W from 65 to 75°C)

    StorageTemperature -40 to +85°C

    Vibration/ ShockTolerance (NEBS) GR-63-CORE Level 3

    Earthquake Zone 4 compliant

    Safety CSA C22-2 No. 950, UL 1950 andIEC60950/ EN 60950

    ESD Immunity EN61000-4-2, Level 4

    RF Immunity EN61000-4-2, Level 3

    Surge Immunity IEC/ EN61000-4-5, Level 4

    Fast Transient/Burst Immunity IEC/ EN61000-4-4, Level 4

    Battery

    BatteryDisconnection

    An optional feature that allowsvoltage or time controlleddisconnection of batteries.

    BoostCharging

    Manual time controlled orautomatic boost charging withadjustable time and voltagelevels.

    Battery Test

    Automatic or manual testing ofbatteries up to four times peryear. Variables include: testduration, end voltage, Ah, andallowable symmetry variation.

    SymmetryMeasurement

    Optional tool that measuresbatteries for early detection ofthermal runaway. Allows forseparate measurements of up tothree parallel battery branches,each divided into four blocks.

    TemperatureCompensationCharging

    Allows continuous adjustment ofoutput voltage according tobattery temperature. Featureincludes adjustablecompensation factor andseparate thresholds for alarms.

    Note: All specifications are subject to change without notification.

    DescriptionXscend™, the new shelf based power system from Power-One is designed to meet a broad range of customer applicationsthrough flexibility, simplicity and scalability.

    FlexibleThe Xscend power system offers solutions that meet today's demands by addressing tomorrow's problems, including: powerdensity, reliability, accessibility, upgrades, and space requirements. Utilizing state-of-the art rectifier technology, an integratedmicroprocessor controller platform and interchangeable distribution modules, the Xscend power system provides a diversefront-access power solution in only a 3 rack unit (5.25in.) vertical and a 300mm (12in.) deep cabinet area. Xscend rectifiersoperate using a phase shifted transitional resonant zero-voltage switching technology that offers increased system life andreliability by reducing component stresses. The same engineering strategy gives Xscend the ability to generate up to 1350Win just 3.5-inch (2RU) of vertical space, resulting in a power density of over 9 W/in

    3. In addition, Xscend’s forward thinking

    horizontal cooling design allows shelves to be placed directly above or below customer equipment, safely increasing theamount of space that can be used for revenue generating equipment and negating the need for airflow clearance above orbelow the unit.

    SimpleThe Xscend power system is designed for ease of use through itsinnovative control and monitoring system. To accomplish this theXscend is supervised by a single rack unit microprocessorcontroller (XCS) that offers user-friendly menus and commandsthat allow an operator to monitor system conditions, capacity,battery parameters and circuit breaker status.

    System control can also be accomplished by using an RS232digital communication bus that allows for remote operation througha Modem, Ethernet (SNMP capable), or standard form C contacts.The XCS controller also works hand-in-hand with the easy to usePower-One POWCOM software package that allows for totalsystem assessment and password controlled parameteradjustments.

    ScalableIn keeping with today's unpredictable market requirements, Power-One's Xscend design targets a mechanical package approach thatpermits the power system to expand with ease.

    Each 23 inch shelf can be fitted with up to five rectifier unitsdelivering up to 125A of system power, while each 19 inch rack canbe fitted with up to four rectifiers providing 100A. Additionalshelves, distributions and rectifiers can be added to a systemoffering a high system level density as well as system levelmodularity providing low start up costs and an easy growth path.

    Features• AC Input 180-264 Vac

    • 48VDC Rectifier with up to 1350W output

    • 24V available during 2nd release

    • Fan cooled rectifier modules

    • Front access design

    • Temperature hardened -40°C to +65°C

    • 19” or 23” mounting arrangement

    • Extensive remote monitoring capabilities

    • Modular DC distribution with LVD

    • Power Factor Correction

    • ETSI Compatible

    • Modular system from 25A to 500A

    Shelf System

    Xscend™ Power SystemShelf System

    www.power-one.comwww.power-one.com11V0005-060 Xscend SY V3.0

    Xscend™ Power System

  • Xscend Configuration OptionsIn today's changing market, companies require systems that can beeasily adjusted to meet a number of different configurations. To fillthis need, Power-One has designed Xscend to accommodatemultiple configurations through a modular system of shelf, rectifier,control and distribution options.

    Xscend's options vary from single 1350W rectifier shelf system withan internal hot-add distribution module up to four paralleled rectifiershelves with an external distribution providing 500A. This scalableformat allows Xscend to be upgraded from a basic configurationthrough the addition of shelves and rectifiers.

    Additional configuration designs are available upon request forcustomer specific racks, cabinets, or outdoor enclosures.

    Shelf Output Specifications(Maximum output)

    5 RectifiersOutput current: 125AOutput power: 6750W

    4 RectifiersOutput current: 100AOutput power: 5400W

    3 RectifiersOutput current: 75AOutput power: 4050W

    2 RectifiersOutput current: 50AOutput power: 2700W

    1 RectifiersOutput current: 25AOutput power: 1350W

    Quad Shelf System• Up to 20 rectifier modules• 1 external distribution module with various

    circuit breaker configuration options• Up to 27kW

    Single Shelf System• Up to 5 rectifier modules• 1-2 distribution modules• Up to 5 circuit breakers• Up to 2 battery breakers• Up to 6750W

    Double Shelf System• Up to 10 rectifier modules• 1-2 distribution modules• Up to 10 circuit breakers• Up to 4 battery breakers• Up to 13kW

    System Configurations

    Xscend™ Power SystemShelf System

    Xscend Rectifier ModulePower-One has addressed the critical issue of power density bydesigning the Xscend rectifier module to be more compact, sothat the maximum amount of power can be generated in theleast amount of space. The module incorporates the latest inpower monitoring solutions through an internal microprocessor,giving up to the second updates on system performance. The rectifier is cooled by a high-speed temperature controlledfan that allows operation at 1200W at temperatures up to 65°C(reduced capacity to 75°C). These features allow the Xscendrectifier to operate in many different environments andconfigurations.

    Xscend Distribution ModuleA common problem in today's power systems is cablecongestion. The Xscend system alleviates this problem throughan innovative module design that incorporates a standard cablemanagement area into the system. The result is a front access3-rack unit power system that allows for efficient and easyinstallation.This hot-add distribution modules have the option of beinginstalled into the two rightmost positions in the subrack, therebyallowing shelves and systems to be easily and quicklyconfigured as desired. This design allows each module todistribute and protect loads up to a total of 100A. Offered as anoption, the low voltage disconnect (LVD) function may beinstalled in each module to ensure system batteries areprotected against an irrecoverable discharge.

    System Components

  • Xscend Configuration OptionsIn today's changing market, companies require systems that can beeasily adjusted to meet a number of different configurations. To fillthis need, Power-One has designed Xscend to accommodatemultiple configurations through a modular system of shelf, rectifier,control and distribution options.

    Xscend's options vary from single 1350W rectifier shelf system withan internal hot-add distribution module up to four paralleled rectifiershelves with an external distribution providing 500A. This scalableformat allows Xscend to be upgraded from a basic configurationthrough the addition of shelves and rectifiers.

    Additional configuration designs are available upon request forcustomer specific racks, cabinets, or outdoor enclosures.

    Shelf Output Specifications(Maximum output)

    5 RectifiersOutput current: 125AOutput power: 6750W

    4 RectifiersOutput current: 100AOutput power: 5400W

    3 RectifiersOutput current: 75AOutput power: 4050W

    2 RectifiersOutput current: 50AOutput power: 2700W

    1 RectifiersOutput current: 25AOutput power: 1350W

    Quad Shelf System• Up to 20 rectifier modules• 1 external distribution module with various

    circuit breaker configuration options• Up to 27kW

    Single Shelf System• Up to 5 rectifier modules• 1-2 distribution modules• Up to 5 circuit breakers• Up to 2 battery breakers• Up to 6750W

    Double Shelf System• Up to 10 rectifier modules• 1-2 distribution modules• Up to 10 circuit breakers• Up to 4 battery breakers• Up to 13kW

    System Configurations

    Xscend™ Power SystemShelf System

    Xscend Rectifier ModulePower-One has addressed the critical issue of power density bydesigning the Xscend rectifier module to be more compact, sothat the maximum amount of power can be generated in theleast amount of space. The module incorporates the latest inpower monitoring solutions through an internal microprocessor,giving up to the second updates on system performance. The rectifier is cooled by a high-speed temperature controlledfan that allows operation at 1200W at temperatures up to 65°C(reduced capacity to 75°C). These features allow the Xscendrectifier to operate in many different environments andconfigurations.

    Xscend Distribution ModuleA common problem in today's power systems is cablecongestion. The Xscend system alleviates this problem throughan innovative module design that incorporates a standard cablemanagement area into the system. The result is a front access3-rack unit power system that allows for efficient and easyinstallation.This hot-add distribution modules have the option of beinginstalled into the two rightmost positions in the subrack, therebyallowing shelves and systems to be easily and quicklyconfigured as desired. This design allows each module todistribute and protect loads up to a total of 100A. Offered as anoption, the low voltage disconnect (LVD) function may beinstalled in each module to ensure system batteries areprotected against an irrecoverable discharge.

    System Components

  • Input

    Input Voltage 180-264 VAC

    Frequency 47-63Hz

    Input Current 9.33A @180VAC

    Power Factor >.98 Typical

    Output

    Alarms

    Alarm History 40 event alarm history

    AlarmContacts

    Four free alarm contacts (max.60V, 1A) Two open collectoroutputs for LVD

    Alarms High DC VoltageLow DC VoltageLoad/ Battery DisconnectionBattery Fuse FailureDC Fuse FailureModule FailureMain AC FailureBattery FailureSymmetry FailureHigh TemperatureHigh Load

    Voltage 42V-58VDC (54VDC Nominal)

    Output up to 500A in 4 subrack/ shelfsystem

    Power (at 208/240VAC)

    1350W (up to 50°C) per rectifier1200W (up to 65°C) per rectifier

    Efficiency 90% typical

    MechanicalDimensions(WxHxD)

    584.2/482.6 x 133.35 x 274.32mm(23/19 x 5.25 x 10.8in.)

    Shelf withoutController

    584.2/482.6 x 88.9 x 274.32mm(23/19 x 3.5 x 10.8in.)

    Mounting 19/23in. rack mount

    Cooling Fan Cooled, speed controlled andalarmed

    Other Technical DataOperatingTemperature

    -40 to +65°C, (Derated to 700W from 65 to 75°C)

    StorageTemperature -40 to +85°C

    Vibration/ ShockTolerance (NEBS) GR-63-CORE Level 3

    Earthquake Zone 4 compliant

    Safety CSA C22-2 No. 950, UL 1950 andIEC60950/ EN 60950

    ESD Immunity EN61000-4-2, Level 4

    RF Immunity EN61000-4-2, Level 3

    Surge Immunity IEC/ EN61000-4-5, Level 4

    Fast Transient/Burst Immunity IEC/ EN61000-4-4, Level 4

    Battery

    BatteryDisconnection

    An optional feature that allowsvoltage or time controlleddisconnection of batteries.

    BoostCharging

    Manual time controlled orautomatic boost charging withadjustable time and voltagelevels.

    Battery Test

    Automatic or manual testing ofbatteries up to four times peryear. Variables include: testduration, end voltage, Ah, andallowable symmetry variation.

    SymmetryMeasurement

    Optional tool that measuresbatteries for early detection ofthermal runaway. Allows forseparate measurements of up tothree parallel battery branches,each divided into four blocks.

    TemperatureCompensationCharging

    Allows continuous adjustment ofoutput voltage according tobattery temperature. Featureincludes adjustablecompensation factor andseparate thresholds for alarms.

    Note: All specifications are subject to change without notification.

    DescriptionXscend™, the new shelf based power system from Power-One is designed to meet a broad range of customer applicationsthrough flexibility, simplicity and scalability.

    FlexibleThe Xscend power system offers solutions that meet today's demands by addressing tomorrow's problems, including: powerdensity, reliability, accessibility, upgrades, and space requirements. Utilizing state-of-the art rectifier technology, an integratedmicroprocessor controller platform and interchangeable distribution modules, the Xscend power system provides a diversefront-access power solution in only a 3 rack unit (5.25in.) vertical and a 300mm (12in.) deep cabinet area. Xscend rectifiersoperate using a phase shifted transitional resonant zero-voltage switching technology that offers increased system life andreliability by reducing component stresses. The same engineering strategy gives Xscend the ability to generate up to 1350Win just 3.5-inch (2RU) of vertical space, resulting in a power density of over 9 W/in

    3. In addition, Xscend’s forward thinking

    horizontal cooling design allows shelves to be placed directly above or below customer equipment, safely increasing theamount of space that can be used for revenue generating equipment and negating the need for airflow clearance above orbelow the unit.

    SimpleThe Xscend power system is designed for ease of use through itsinnovative control and monitoring system. To accomplish this theXscend is supervised by a single rack unit microprocessorcontroller (XCS) that offers user-friendly menus and commandsthat allow an operator to monitor system conditions, capacity,battery parameters and circuit breaker status.

    System control can also be accomplished by using an RS232digital communication bus that allows for remote operation througha Modem, Ethernet (SNMP capable), or standard form C contacts.The XCS controller also works hand-in-hand with the easy to usePower-One POWCOM software package that allows for totalsystem assessment and password controlled parameteradjustments.

    ScalableIn keeping with today's unpredictable market requirements, Power-One's Xscend design targets a mechanical package approach thatpermits the power system to expand with ease.

    Each 23 inch shelf can be fitted with up to five rectifier unitsdelivering up to 125A of system power, while each 19 inch rack canbe fitted with up to four rectifiers providing 100A. Additionalshelves, distributions and rectifiers can be added to a systemoffering a high system level density as well as system levelmodularity providing low start up costs and an easy growth path.

    Features• AC Input 180-264 Vac

    • 48VDC Rectifier with up to 1350W output

    • 24V available during 2nd release

    • Fan cooled rectifier modules

    • Front access design

    • Temperature hardened -40°C to +65°C

    • 19” or 23” mounting arrangement

    • Extensive remote monitoring capabilities

    • Modular DC distribution with LVD

    • Power Factor Correction

    • ETSI Compatible

    • Modular system from 25A to 500A

    Shelf System

    Xscend™ Power SystemShelf System

    www.power-one.comwww.power-one.com11V0005-060 Xscend SY V3.0

    Xscend™ Power System

  • DescriptionThe Power-One Xscend™ rectifier providesextremely reliable DC power in the highestpossible density. The module incorporatesthe latest in power monitoring solutionsthrough an internal microprocessor giving upto the second updates to the systemcontroller and adjacent rectifiers. Thisguarantees tightly controlled load sharingamong rectifiers, and providing status andidentification information to the controller.

    At only two rack units high, these compactrectifiers provide up to 1350W and fit up tofive rectifier modules in a 23in. rack or fourmodules in a 19in. rack. Designed withdiversity in mind, the Xscend rectifier is ableto operate in a complete range of indoor andoutdoor applications.

    Features• Compact 2 rack unit height• Front or mid-mountable• 208/240 single phase input• Hot-swappable • No adjustments required• 90% typical efficiency• Active and droop current sharing• International Standards Compliance

    Xscend PowerSystem

    XR1448Rectifier Module

    www.power-one.com

  • InputModel XR1448

    Input Voltage 180-264VAC (47-63Hz)

    Current (max.) 9.3A @180VAC

    Inrush Current 25A @ 25°C

    Power Factor >0.98 typical

    Fuse 12.5A- line, 12.5A- neutral

    Connection FCI power connector™

    EMC EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B

    OutputModel XR1448

    Output Voltage 42-58VDC

    Power (max.) 1350W

    Current 25A

    Efficiency 90% typical

    Tolerance Vout +/- 1.0%, constantvoltage regulation

    TransientResponse +/- 4% recovery time 2ms

    Load Sharing +/- 5%

    Ripple

  • DescriptionThe Power-One Xscend™ Controller System (XCS) provides comprehensive monitoringand control for Power-One’s Xscend DC power systems. This digital controller monitorstotal system conditions including DC voltage, rectifier current, rectifier temperature,system capacity, battery parameters and circuit breaker status.

    The XCS enables data storage of system configuration information such as battery type,installation date and system commission date. Visual notification of alarm and warningconditions are indicated by front panel LEDs, while descriptions of the alarms are providedthrough an LCD, or as an option, may be accessed remotely through a modem or aNetwork Interface (PNI) module.

    To meet individual site requirements, the XCS contains a logic operator that can beprogrammed to monitor and control specified requirements. This allows actions to be set,alarms to be triggered, and outputs to be activated based on internal and external signalmonitoring, comparing and processing.

    FeaturesUser controls and interfaces:

    • Simple menu-guided operation using front panel mounted pushbuttons and an LCD

    • User-selectable alarm parameters

    • 40 event data logging

    • Password controlled environment

    • Multiple language options

    • RS232 Interface and Form “C” dry alarm contacts

    XCSController

    www.power-one.com

    Intelligent battery management:

    • Temperature compensation with programmable compensation factor

    • Automatic and manual load testing

    • Battery voltage and symmetry monitoring

    • Capacity testing

    • Low voltage disconnect

    • Monthly data logging

  • InputVoltage 18-72V DC

    Current

  • Note: All specifications are subject to change without notification.

    Input

    Output

    Mechanical

    Components

    Model Compac 48V Compac 24V

    Input Voltage 180 - 264 VAC, 50-60 HzSingle or three-phase180 - 264 VAC, 50-60 HzSingle or three-phase

    Current (at full load) 15A per rectifier at full load 15A per rectifier at full load

    Input Breaker Rating 40A per rectifier 40A per rectifier

    Input Wire Size 8 AWG (max.) 8 AWG (max.)

    DC Bus Rating 800 or 1200A options 800 or 1200A options

    Output Current 50-1200A 100-800A

    Efficiency >86% >86%

    Current Rating per BreakerPanel (max.) 400A 400A

    Controller DMAC Controller DMAC Controller

    Rectifier NHS48/50 NHS24/100

    Width 19 or 23in.

    Battery Tray Depth 21, 25 or 29in.

    Mounting (base) Mounting holes provided

    Altitude Range 13,000 ft., derate 7°C/1000ft. above 8,000 ft.

    Operating Temperature -0 to +50°C

    Storage Temperature -50 to +85°C

    Temperature Coefficient +/- 0.0008%/°C from 0-50°C, after one hour warm up

    Humidity 10-90% RH, operating, 5-95% storage, non-condensing

    Heat Dissipation per Rectifier 1,255 BTU’s per hour at full load

    DescriptionCompac Racks are modular power systemsdesigned for applications requiring 50 to 1200 amps.An almost limitless combination of rectifiers, breakerpanels, and battery shelves are available. Stand-alone configurations with up to 750 Ah of batterybackup are available. Each rack can hold up to 24rectifiers or a maximum of five battery trays.Systems can be ordered with ultimate capacity forfuture additions of rectifiers and batteries.

    Standard features include timer-controlled equalizeand battery test functions, current and voltagedisplay meters, LED’s for local alarm indications,user-programmable alarm set inputs, and a set ofform “C” alarm contacts for remote monitoring.Optional features include low voltage disconnect,complete battery systems, and battery temperaturecompensation.

    The Compac systems distribution architecture can bedesigned for load shedding during power outages,allowing critical loads to stay up longer on batterypower by eliminating non-critical equipment loadsearlier in the discharge cycle.

    Features• Modular systems from 50-1200A• 24V or 48V outputs• 180-264 VAC single or three-phase inputs• Rack widths of 19in. or 23in.• Hot-swappable rectifiers• Small footprint• Scalable N+1 redundancy with current sharing

    Low Voltage Disconnect (LVD)

    Power System

    Compac Rack System™Power System

    www.power-one.comwww.power-one.com11V0005-047 CMPSYS V3.0

    Compac Rack System™

    Contactor Rating 800-1200A options 800-1200A options

    Disconnect Voltage(User Adjustable)

    42V 21V

    LVD Disconnect Range 31 - 51V 18 - 26V

    Reconnect Voltage 6.5V above disconnectvoltage4.7V above disconnectvoltage

    • Power factor correction (PFC)• Extensive monitoring capabilities• Options include integrated battery systems and extensive

    breaker and fuse layouts• A single seven foot rack can provide distribution, 400A of

    rectifiers, and 750Ah of batteries• International standards compliance

  • The Compac Power System is available in three different configurations, allowing customers to choosethe solution that is right for them. Each system uses the same basic components, systems include:

    Breaker Panels• Twenty positions for 5 to 100A

    breakers• Two positions for 125 to 250A

    breakers• A single position for a 450A or 525A

    breaker

    Low Voltage Disconnect• Optional Feature• Provides protection against deep

    discharge of batteries• Emergency Power Off (EPO) switch

    provided for emergency shutoff• Remote contacts for EPO

    Rectifier Shelves• Interfaces with controller• 23” shelf allows up to 4

    rectifiers each• Active current sharing• Single or three-phase input

    DMAC Controller• Single point system voltage adjust• Programmable timer for battery test

    or equalization

    • Digital meters and test points monitor plant voltages and current

    • User-adjustable set points for under/over voltage and low voltage disconnect

    NHS Rectifiers• 4 Rectifiers into each 3U 23” shelf • Available in 24 or 48VDC• Thermal protection• Fan cooled modules • Hot swappable• Low weight• High reliability

    System ConfigurationsSystem Components

    Compac Rack System™Power System

    Temperature Compensation• Works in conjunction with the DMAC

    controller• Automatically adjusts the float

    voltage according to the ambient temperature

    • Sets off alarms when battery thermal runaway or sensor failure is indicated

    48VDC 1200A SystemThe Compac full rack systemallows for up to 1200A at 48V in asingle bay by using combinationsof distribution options. Eachrack is capable of holding up tosix rectifier shelves, a DMACcontroller panel, variousdistribution options and rearconnection points for externalbattery strings.

    48VDC 400A SystemThe Compac full rack systemwith battery shelves allows for upto 400A at 48V in a single bay.Each rack is capable of holdingup to five battery trays for 100 to150 Ah battery reserve strings.

    24VDC 800A SystemThe Compac full rack systemwithout battery shelves allows forup to 800A at 24V in a single bay.Each rack is open at the bottomto allow room for user installedequipment.

  • The Compac Power System is available in three different configurations, allowing customers to choosethe solution that is right for them. Each system uses the same basic components, systems include:

    Breaker Panels• Twenty positions for 5 to 100A

    breakers• Two positions for 125 to 250A

    breakers• A single position for a 450A or 525A

    breaker

    Low Voltage Disconnect• Optional Feature• Provides protection against deep

    discharge of batteries• Emergency Power Off (EPO) switch

    provided for emergency shutoff• Remote contacts for EPO

    Rectifier Shelves• Interfaces with controller• 23” shelf allows up to 4

    rectifiers each• Active current sharing• Single or three-phase input

    DMAC Controller• Single point system voltage adjust• Programmable timer for battery test

    or equalization

    • Digital meters and test points monitor plant voltages and current

    • User-adjustable set points for under/over voltage and low voltage disconnect

    NHS Rectifiers• 4 Rectifiers into each 3U 23” shelf • Available in 24 or 48VDC• Thermal protection• Fan cooled modules • Hot swappable• Low weight• High reliability

    System ConfigurationsSystem Components

    Compac Rack System™Power System

    Temperature Compensation• Works in conjunction with the DMAC

    controller• Automatically adjusts the float

    voltage according to the ambient temperature

    • Sets off alarms when battery thermal runaway or sensor failure is indicated

    48VDC 1200A SystemThe Compac full rack systemallows for up to 1200A at 48V in asingle bay by using combinationsof distribution options. Eachrack is capable of holding up tosix rectifier shelves, a DMACcontroller panel, variousdistribution options and rearconnection points for externalbattery strings.

    48VDC 400A SystemThe Compac full rack systemwith battery shelves allows for upto 400A at 48V in a single bay.Each rack is capable of holdingup to five battery trays for 100 to150 Ah battery reserve strings.

    24VDC 800A SystemThe Compac full rack systemwithout battery shelves allows forup to 800A at 24V in a single bay.Each rack is open at the bottomto allow room for user installedequipment.

  • Note: All specifications are subject to change without notification.

    Input

    Output

    Mechanical

    Components

    Model Compac 48V Compac 24V

    Input Voltage 180 - 264 VAC, 50-60 HzSingle or three-phase180 - 264 VAC, 50-60 HzSingle or three-phase

    Current (at full load) 15A per rectifier at full load 15A per rectifier at full load

    Input Breaker Rating 40A per rectifier 40A per rectifier

    Input Wire Size 8 AWG (max.) 8 AWG (max.)

    DC Bus Rating 800 or 1200A options 800 or 1200A options

    Output Current 50-1200A 100-800A

    Efficiency >86% >86%

    Current Rating per BreakerPanel (max.) 400A 400A

    Controller DMAC Controller DMAC Controller

    Rectifier NHS48/50 NHS24/100

    Width 19 or 23in.

    Battery Tray Depth 21, 25 or 29in.

    Mounting (base) Mounting holes provided

    Altitude Range 13,000 ft., derate 7°C/1000ft. above 8,000 ft.

    Operating Temperature -0 to +50°C

    Storage Temperature -50 to +85°C

    Temperature Coefficient +/- 0.0008%/°C from 0-50°C, after one hour warm up

    Humidity 10-90% RH, operating, 5-95% storage, non-condensing

    Heat Dissipation per Rectifier 1,255 BTU’s per hour at full load

    DescriptionCompac Racks are modular power systemsdesigned for applications requiring 50 to 1200 amps.An almost limitless combination of rectifiers, breakerpanels, and battery shelves are available. Stand-alone configurations with up to 750 Ah of batterybackup are available. Each rack can hold up to 24rectifiers or a maximum of five battery trays.Systems can be ordered with ultimate capacity forfuture additions of rectifiers and batteries.

    Standard features include timer-controlled equalizeand battery test functions, current and voltagedisplay meters, LED’s for local alarm indications,user-programmable alarm set inputs, and a set ofform “C” alarm contacts for remote monitoring.Optional features include low voltage disconnect,complete battery systems, and battery temperaturecompensation.

    The Compac systems distribution architecture can bedesigned for load shedding during power outages,allowing critical loads to stay up longer on batterypower by eliminating non-critical equipment loadsearlier in the discharge cycle.

    Features• Modular systems from 50-1200A• 24V or 48V outputs• 180-264 VAC single or three-phase inputs• Rack widths of 19in. or 23in.• Hot-swappable rectifiers• Small footprint• Scalable N+1 redundancy with current sharing

    Low Voltage Disconnect (LVD)

    Power System

    Compac Rack System™Power System

    www.power-one.comwww.power-one.com11V0005-047 CMPSYS V3.0

    Compac Rack System™

    Contactor Rating 800-1200A options 800-1200A options

    Disconnect Voltage(User Adjustable)

    42V 21V

    LVD Disconnect Range 31 - 51V 18 - 26V

    Reconnect Voltage 6.5V above disconnectvoltage4.7V above disconnectvoltage

    • Power factor correction (PFC)• Extensive monitoring capabilities• Options include integrated battery systems and extensive

    breaker and fuse layouts• A single seven foot rack can provide distribution, 400A of

    rectifiers, and 750Ah of batteries• International standards compliance

  • DescriptionThe Power-One NHS rectifier modulesprovide extremely reliable DC poweroutput for use in our Compac™ series ofpower systems. NHS rectifier modulesare hot-swappable and provide a completeset of interface signals.

    At only 3 rack units high, these compactrectifiers allow for up to four modules ineach 23in. rack and provide up to 50A at48V or up to 100A at 24V. With full poweravailable up to 50°C, these rectifiers areideal for any indoor and outdoorapplications.

    Features• Compact 3 rack-unit height• 24V and 48V rectifiers• 50A output at 48V• 100A output at 24V• 180-264 single or three phase inputs• Hot-Swappable, plug-and-play rectifiers• High power density (9.8W/in3)• High reliability, >700,000 hours MTBF• Power factor correction• Active current sharing• International Standards Compliance

    NHSRectifier Module

    www.power-one.com

  • InputModel NHS24/100 NHS48/50

    InputVoltage 180 - 264V AC single phase, (50-60Hz)

    Current 15A @ 230V 15A @ 230V

    Soft Start 0.99 (50-100% load)

    ACTransient 3000V, 2 Joules

    Output

    MechanicalDimensions 5 x 5 x 12.25 in. (12.7 x 12.7 x 31.1cm )

    Weight 12.6 lbs.

    Cooling Fan

    Other Technical Data

    Model NHS24/100 NHS48/50

    Power (max.) 2400W 2400W

    OutputVoltage 25-29V DC 51-59V DC

    Current (max.) 100A 50A

    Efficiency(@ 40-90%Load)*

    >86% >86%

    VoltageRegulation +/- 0.4%

    TransientResponse

    +/- 4% at load variation 10-90% or 90-10%, recovery time 10ms

    Load Sharing

  • Features• Single point system voltage adjust• Programmable timer for battery test or

    equalization• Digital meters and test points monitor plant

    voltages and current• User-adjustable set points for under/over voltage

    and low voltage disconnect

    DMACController

    DescriptionThe Power-One Digital Meter, Alarm and Control Panel (DMAC) provides comprehensivemonitoring and control for Power-One’s Compac™ power systems. This digital controllermonitors system conditions including DC voltage and load current, while providing avariety of alarm and control functions.

    DMAC features include user-configurable battery testing, measurement of battery voltageand current & battery equalization.

    Front panel LED’s for alarms, including:• Equalize alarm• OV/UV alarm• Major alarm• Minor alarm• Rectifier fail• Breaker alarm

    www.power-one.com

  • Temperature Compensation

    Other Technical DataOperatingTemperature -0 to +50°C

    StorageTemperature -50 to +85°C

    Humidity 10-90% RH, operating, 5-95%storage, non-condensing

    AltitudeRange

    13,000 ft., derate 7°C/100 ft.above 8000 ft.

    Overview

    The temperaturecompensation panel works inconjunction with the DMACcontroller. Temperaturecompensation automaticallyadjusts the float voltageaccording to the ambienttemperature.

    TemperatureCompensationAlarms

    Alarms include temperaturedelta, which indicates batterythermal runaway and sensorfailure. In the event of asensor or panel failure, thecompensation defaults to thenormal float voltage set by thecontroller.

    Interface

    Note: All specifications are subject to change without notification.

    Display Digital amp and digital volt meters

    Digital Meters 3.5 digits, +/-2% accuracy

    UV/OVAdjustment

    22V/29V for 24VDC +/- 1.5V 44V/58V for 48VDC +/- 1.5V

    Equalization &Battery TestTimer Range

    0.5 seconds to 130 hours

    CurrentMeasurementDC Shunt

    1200A:50mA

    User Controls

    Timer reset buttonSystem voltage adjustmentNormal/Bypass test switchEqualize/Battery test switchEqualize Under/Over voltage adjustmentUndervoltage/Overvoltage

    ConnectionPoints

    System voltage test pointsSystem amperage test points

    www.power-one.com11V0005-050 DMAC V3.0

    DMACController

    Alarms

    Alarms

    Equalize alarmOV/UV alarmMajor alarmMinor alarmRectifier failBreaker alarm

  • Note: All specifications are subject to change without notification.

    Input

    Output

    Mechanical

    Components

    Model Integrity-One 48V Integrity-One 24V

    Input 176 < Vin < 275V 176 < Vin < 275V

    Inputs Single or individual Single or individual

    Current (at full load) 16A per rectifier (max.) 16A per rectifier (max.)

    Fuse 25A per rectifier 25A per rectifier

    Rectifier Modules 50-1250A 110-1100A

    Voltage 50-1250A 110-1100A

    Efficiency >91% >89%

    Controller PCS Controller PCS Controller

    Rectifier PMP 25.48 PMP 25.24

    Dimensions (WxHxD) 23 x 84 x 23 in.(584 x 2133 x 584mm)23 x 46 x 23 in.(584 x 1168 x 584mm)

    Mounting (rack) 23” 23”

    Mounting (base) Mounting holes provided Mounting holes provided

    Audible Noise

  • The Integrity-One system is available in three different configurationsallowing customers to choose the solution that is right for them. Eachsystem uses the same basic components, including:

    • System Interface Shelf• Alarm Output Connections• Network Interface (Optional)• Battery LVD (Optional)

    • PCS Controller• PMP25 Rectifier Modules• SDS / PDS Distribution Shelves• Single or Individual Rectifier AC Inputs to Each Rectifier Shelf

    Full Rack SystemThe Integrity-One full rack system allows for up to 1250A at 48V in asingle bay by using combinations of Secondary or PrimaryDistributions. Each rack is capable of holding up to five rectifiershelves for 48V applications providing 1250A or two rectifier shelves for24V applications providing 1100A. Multiple racks may be paralleled toproduce a maximum total system capability of 5000A using a singlecontroller in the primary rack.

    Half-Height Rack SystemThe Integrity-One Half-Height rack system is available at up to 1100Aand can be installed above existing battery stands. The Half-Heightsystem is ideal for systems requiring extended battery backup. Up to44 load breakers can distribute up to 500A at -48V, or up to 1000A at+24V.

    Integrity-One Rack with Battery TraysThe Integrity-One System with battery trays accommodates up to tworectifier shelves and up to three battery trays creating a complete powersystem in a single rack. Distribution can be achieved through up to 44load breakers or fuses (up to 100A rating).

    Integrity-One FullRack System

    Integrity-One Half-Height Rack System

    System Configurations System Components

    Integrity-One™ Power SystemRack System

    Distribution Panels• Hot-swappable distribution shelves• Front, middle and rear distribution

    positions (waterfall effect) allow for system cable management

    • SDS: Secondary Distribution Shelf• Rated at 500A• Plug in CB’s up to 100A rating• Plug in fuses up to 100A rating• Accommodates up to 22 circuit

    breakers or fuses

    • PDS: Primary Distribution Shelf (rated at 1000A)• Up to qty 8 single pole fuses

    (100-600A)• Up to qty 8 single pole CB’s

    (up to 250A rating)• Up to qty 3 double pole CB’s

    (up to 400A rating)• Up to qty 2 triple pole CB’s

    (up to 600A rating)

    System Interface Shelf• Easy connection of system alarm

    signals and wiring• Optional battery symmetry and

    temperature probes• Optional Power-One Network Interface

    box (featuring ethernet and SMNPprotocol capability)

    • Optional low voltage disconnect• Battery shunt

    Rectifier Shelves• RS485 communication bus• 23” shelf allows up to 5

    rectifiers each• Digital current sharing• Individual rectifier or single

    shelf AC feed options

    PCS Controller• RS485 digital signal data bus • Fully programmable• 6 programmable alarms

    (upgradeable to 24)• Battery test: manual or

    automatic• Alarm relay test• Adjustable battery current• Software controlled start-up

    after mains outage

    PMP25 Rectifier• 5 rectifiers into each 4U 23” shelf • Available in 24 or 48VDC• Thermal protection• Fan cooled modules with speed

    control and alarms• Hot-swappable• RS485 interface• Low weight• Up to 91% efficiency

    Integrity Shown withOptional AC Distribution

    Box

  • The Integrity-One system is available in three different configurationsallowing customers to choose the solution that is right for them. Eachsystem uses the same basic components, including:

    • System Interface Shelf• Alarm Output Connections• Network Interface (Optional)• Battery LVD (Optional)

    • PCS Controller• PMP25 Rectifier Modules• SDS / PDS Distribution Shelves• Single or Individual Rectifier AC Inputs to Each Rectifier Shelf

    Full Rack SystemThe Integrity-One full rack system allows for up to 1250A at 48V in asingle bay by using combinations of Secondary or PrimaryDistributions. Each rack is capable of holding up to five rectifiershelves for 48V applications providing 1250A or two rectifier shelves for24V applications providing 1100A. Multiple racks may be paralleled toproduce a maximum total system capability of 5000A using a singlecontroller in the primary rack.

    Half-Height Rack SystemThe Integrity-One Half-Height rack system is available at up to 1100Aand can be installed above existing battery stands. The Half-Heightsystem is ideal for systems requiring extended battery backup. Up to44 load breakers can distribute up to 500A at -48V, or up to 1000A at+24V.

    Integrity-One Rack with Battery TraysThe Integrity-One System with battery trays accommodates up to tworectifier shelves and up to three battery trays creating a complete powersystem in a single rack. Distribution can be achieved through up to 44load breakers or fuses (up to 100A rating).

    Integrity-One FullRack System

    Integrity-One Half-Height Rack System

    System Configurations System Components

    Integrity-One™ Power SystemRack System

    Distribution Panels• Hot-swappable distribution shelves• Front, middle and rear distribution

    positions (waterfall effect) allow for system cable management

    • SDS: Secondary Distribution Shelf• Rated at 500A• Plug in CB’s up to 100A rating• Plug in fuses up to 100A rating• Accommodates up to 22 circuit

    breakers or fuses

    • PDS: Primary Distribution Shelf (rated at 1000A)• Up to qty 8 single pole fuses

    (100-600A)• Up to qty 8 single pole CB’s

    (up to 250A rating)• Up to qty 3 double pole CB’s

    (up to 400A rating)• Up to qty 2 triple pole CB’s

    (up to 600A rating)

    System Interface Shelf• Easy connection of system alarm

    signals and wiring• Optional battery symmetry and

    temperature probes• Optional Power-One Network Interface

    box (featuring ethernet and SMNPprotocol capability)

    • Optional low voltage disconnect• Battery shunt

    Rectifier Shelves• RS485 communication bus• 23” shelf allows up to 5

    rectifiers each• Digital current sharing• Individual rectifier or single

    shelf AC feed options

    PCS Controller• RS485 digital signal data bus • Fully programmable• 6 programmable alarms

    (upgradeable to 24)• Battery test: manual or

    automatic• Alarm relay test• Adjustable battery current• Software controlled start-up

    after mains outage

    PMP25 Rectifier• 5 rectifiers into each 4U 23” shelf • Available in 24 or 48VDC• Thermal protection• Fan cooled modules with speed

    control and alarms• Hot-swappable• RS485 interface• Low weight• Up to 91% efficiency

    Integrity Shown withOptional AC Distribution

    Box

  • Note: All specifications are subject to change without notification.

    Input

    Output

    Mechanical

    Components

    Model Integrity-One 48V Integrity-One 24V

    Input 176 < Vin < 275V 176 < Vin < 275V

    Inputs Single or individual Single or individual

    Current (at full load) 16A per rectifier (max.) 16A per rectifier (max.)

    Fuse 25A per rectifier 25A per rectifier

    Rectifier Modules 50-1250A 110-1100A

    Voltage 50-1250A 110-1100A

    Efficiency >91% >89%

    Controller PCS Controller PCS Controller

    Rectifier PMP 25.48 PMP 25.24

    Dimensions (WxHxD) 23 x 84 x 23 in.(584 x 2133 x 584mm)23 x 46 x 23 in.(584 x 1168 x 584mm)

    Mounting (rack) 23” 23”

    Mounting (base) Mounting holes provided Mounting holes provided

    Audible Noise

  • DescriptionThe Power-One PMP 25 rectifier providesextremely reliable DC power in a compactmodule. Digital interfaces areincorporated using an RS485 data bus tocommunicate with the system controllerand adjacent rectifiers guaranteeingtightly controlled load sharing amongrectifiers, and providing status andidentification information to the controller.

    At only 4 rack units high, these compactrectifiers allow for up to five modules ineach 23in. rack (4 units in 19in. rack)providing up to 250A at 48V or up to 550Aat 24V. With full power available up to65°C, these rectifiers are ideal for bothindoor and outdoor applications.

    Features• Compact 4 rack-unit height• 24V and 48V rectifiers• 50A output at 48V• 110A output at 24V• 208 / 240 single phase input• Hot-swappable rectifiers• No adjustment required• High efficiency, up to 91%• Active current sharing• International standards compliance

    Integrity-One™ FullHeight System

    PMP 25Rectifier Module

    www.power-one.com

  • InputModel PMP 25.24 PMP 25.48

    InputVoltage

    196 - 250V AC ±10% single phase, (44-66Hz)176-160V AC at reduced output power

    Current(max.)

  • FeaturesUser controls and interfaces:

    • Simple menu-guided operation using front panel mounted pushbuttons and an LCD

    • User-selectable alarm parameters

    • 40 event data logging

    • Password controlled environment

    • Multiple language options

    • RS232 Interface and Form “C” dry alarm contacts

    PCSController

    DescriptionThe Power-One Power Controller System (PCS) provides comprehensive monitoring and control fora broad range of Power-One’s DC power systems. This digital controller monitors total systemconditions including DC voltage, rectifier current, rectifier temperature, system capacity, batteryparameters and circuit breaker status.

    The PCS enables data storage of system configuration information such as battery type, installationdate and system commission date. In addition, the PCS is capable of monitoring up to 128 rectifiersand 128 sub-controllers within a power system. Visual notification of alarm and warning conditionsare indicated by front panel LEDs, while descriptions of the alarms are provided through an LCD oras an option may be accessed remotely through a modem or a Network Interface (PNI) module.

    To meet individual site requirements, the PCS contains a logic operator that can be programmed tomonitor and control specified requirements. This allows actions to be set, alarms to be triggered, andoutputs to be activated based on internal and external signal monitoring, comparing and processing.

    Intelligent battery management:

    • Temperature compensation with programmable compensation factor

    • Automatic and manual load testing

    • Battery voltage and symmetry monitoring

    • Capacity testing

    • Low voltage disconnect

    • Monthly data logging

    www.power-one.com

  • Input

    Voltage 18-72V DC

    Current


Recommended