Date post: | 07-Nov-2014 |
Category: |
Documents |
Upload: | sajedarefin |
View: | 118 times |
Download: | 16 times |
Power System Power System ProtectionProtection
Dr. Ibrahim El-AminDr. Ibrahim El-Amin
Chapter FourChapter Four
Non-pilot Overcurrent Protection of Transmission Lines
Techniques for Line Techniques for Line ProtectionProtection
1. Instantaneous Overcurrent2. Time Overcurrent3. Directional instantaneous and/or time4. Step time overcurrent5. Inverse time distance6. Zone distance7. Pilot relaying
Selecting a Protective Selecting a Protective SystemSystem
1. Type of circuit
2. Line function and importance
3. Coordination and matching requirements
4. Economics
4.1 Introduction4.1 Introduction• Lines are subjected to phase-phase
or phase-ground faults.• Wide range of fault and load
currents.• System configuration and the issue
of directionality of fault current.• Line length has an impact on relay
setting.
• A Relay is set to protect a line and provide a backup for other line sections.
• Relays can not differentiate between faults at end of a line section and beginning of an adjacent section.
Short vs Long linesShort vs Long lines• Short line has lower
impedance than system’s
• Little difference of fault currents at ends of line.
• Relay will overreach in other sections.
• Long lines will not overreach but the fault and load currents may be closer.
Available Protective DevicesAvailable Protective Devices• Fuses• Sectionalizer and Reclosures• Instantaneous Overcurrent• Inverse time-delay overcurrent• Directional overcurrent• Distance• Pilot
4.2 Fuses, Sectionalizers, 4.2 Fuses, Sectionalizers, ReclosuresReclosures
• These devices are used in distribution system.
• A distribution system is made of mains(3-phase) & laterals (single phase).
• It is mostly radial.• Most common protection device is
the current-limiting fuse.
• Fuse characteristics are defined by minimum melt-time and total clearing time.
• Minimum melt-time is the time between the instant the element commences to melt & when arcing occurs. (pre-arcing time)
• Total Clearing Time (TCT)=melt-time +arcing time.
• Fuses are defined by1. Continuous load current is the maximum current to be carried without fuse melting.
2. Hot-load current can be carried, interrupted and re-energized without damage.
3. Cold-load current follows a 30min. Outage is the high current after service is restored.
• Sectionalizer 1. Can not interrupt a fault
2. It counts the number of times, it “sees” the fault current.
3. It opens after a preset number while circuit is de-energized.
• Reclosurer 1. It senses & interrupts faults. 2. Has limited fault-interrupting
capability 3. Recloses automatically in a
programmed sequence.
• Fault at A cleared by branch fuse.
• Fault at B cleared by recloser & sectionalizer.
• The sectionalizer. “sees” the fault and registers one count.
• The recloser sees the faults and trips.
• Sectionalizer opens and allows recloser to restore service.
• Faults at C cleared by recloser.
• Distribution systems are now more complex because of Independent Power Produces .
• Short circuits vary because of the Non-utility generators (NUG).
• Fuses and Reclosers must recognize this.
• The tie switch S is open.
• Fault F1 recloser will open automatically.
• Open down stream breaker and close S to supply load.
• Fault at F2 both breakers 1 & 2 will work.
• Load will be supplied from transformer 2
4.3 Inverse Time-Delay 4.3 Inverse Time-Delay Overcurrent RelaysOvercurrent Relays
• Applicationa. Used mostly on radial
systems.b. Two phase and one ground relays.
c. A third phase relay provides backup & redundancy.
c. Used in some industrial systems
ProtectionProtection SystemSystem for Phase Faults for Phase Faults
Time overcurrent 51
Instantaneous & time overcurrent 50/51
Directional time overcurrent 67
Instantaneous & directional time over current 50/67
Directional Instantaneous overcurrent 67
Step time overcurrent 51
Directional Instantaneous and directional 67
Zone Distance 21
Protection SystemProtection System for Ground Faults for Ground Faults
Time Overcurrent 51N
Instantaneous & Time Overcurrent 50N/51N
Product Overcurrent 67N
Instantaneous and Product Overcurrent 67N/50N
Directional time overcurrent 67N
Instantaneous and directional time overcurrent 67N
Directional Instantaneous Overcurrent 67N
Three-zone distance system 21N
Setting RulesSetting Rules
• Pickup Setting a. It should be above normal currents &
below minimum fault currents.
b. If possible, it may provide a backup role.
c. The setting is calculated using max load current and minimum fault current.
• Time-Delay Settinga. A time dial provides relative positions between the moving and fixed contacts.
b. Dial setting from ½ (fastest) to 10 (slowest)
• The operating speed is determined by the operating current.
• The operating time is determined by the distance it has to travel.
• This an inverse time-current characteristics.
• Time delay allows coordination between relays.
• A family of curves must be provided so that relays seeing same fault current can operate at different operating times.
• Addition of time delay will convert a single characteristics into a set of curves
• Examples 4.2 and 4.3
• Setting of Phase Relays
Relay setting is between 2* maximum load current and 1/3 of
minimum fault current.
The minimum fault current is taken as the phase-phase fault current.
• Closer to maximum load current: Increase dependability and reduce security.
• Closer to minimum fault current: decrease dependability and increase
security.
• Setting of Ground Relays: must see all phase-to-ground faults.
No need to consider load current.
Relay setting is between 2* normal ground current and 1/3 of
minimum ground fault current.
The normal ground current is taken as the 10% of load current.
• Example 4.4
Relay co-ordinationRelay co-ordination• For fault at F1, Rd
operates first.• Rcd has higher
time lever including co-ordination time S to provide a backup
• Rab has the longest time delay
• For faults Between 3-4, Rd will not see the current & will not operate.
• Rcd will trip first before Rbc
• Fault should be cleared by Rd and CB4.
• Rcd sees the fault and start to close its contacts.
• Rcd will reset after some over travel.
• Rcd must be set longer than: -Rd operating time U - CB4 clearing time V - Safety factor X (including over travel W) Usually 0.3-0.5
Example 4.5Example 4.5
• In a network, relay co-ordination is complicated by the problems of infeed or outfeed.
• There might be different current in downstream relays than the setting.
Example 4.6Example 4.6
4.4 Instantaneous Overcurrent4.4 Instantaneous Overcurrent Relays Relays
• Application -Used when short circuit current
reduces substantially as fault moves away from the source.
• The closer fault to the source, the higher is the current.
• If 51 Relays used, yet the
longer the time• Relay 50 can be set to see
faults almost up to the end of line but not including next bus.
• Setting Rules Instantaneous Relays as follows: Set at about 125-135 % above
maximum current for which Relay should not work.
And 90 % of the minimum value for which
it should operate.
• Example 4.7
4.5 Directional Overcurrent 4.5 Directional Overcurrent (67) Relays(67) Relays
• Application-Used in multiple source
circuits.
- Require two inputs; an operating current and a reference or polarizing quantity
(Voltage/current)
• If X is open, breakers 4 & 5 receives no current for fault F1.
• If X is closed, Breaker 4 can not be set above B5 to be selective for F2 and still maintain coordination for fault F1.
• Use 67 Relays if ratio between forward & backward current is 4:1
• Example 4.8
• There are two method to provide directionality:
1. Directional Control
2. Directional Overcurrent
1. Directional Control• Overcurrent element will not
operate till the directional element has worked.
• Directional contact in series with overcurrent contact
2. Directional Overcurrent• Has Independent contacts
in series
• Both contact must close for relay operation.
• Directional Control is more secure.
• Consider directional overcurrent below.
• If fault occurs , overcurrent element of breaker 4 picks up, but the directional contact will not close.
• Assume breaker 2 has opened.
• • Current direction
changed.
• There will be a race between overcurrent & directional elements.
• If Directional element of 4 closes, that is a false trip.
• This case can not happen in directional control design.
• Directional contact at 3 will close, but the overcurrent will not close as it has to co-ordinate with 2.
• But it is difficult to apply the directional control relay
4.6 Polarization4.6 Polarization• Directional relay works by comparing
an operating quantity (fault current) and a constant parameter (system voltage) .
• The constant parameter is referred to as Polarizing Quantity.
• Power Directional Relays : 1.Relays work for balanced V, I &
high Power factor. 2. Vectors are almost in phase. 3. Relay will pick for power in one
direction and reset for opposite direction
4. An auxiliary Transformer is needed.
• Fault Directional Relays 1. System voltage collapse under
faults. 2. Polarizing must not include faulted
phase. 3. Power factor is very low.
Potential PolarizingPotential Polarizing
• For ground faults, The current is obtained fro residual circuits of the CTs (In=3I0).
• Use polarizing voltage (3E0). It has same direction regardless of fault location.
• The mag. of 3E0 depends on fault location, ground impedance, zero sequence impedance.