INV ITEDP A P E R
Power System Security in aMeshed North Sea HVDC GridThe impact of wind power variation on ac grids is presented where the
challenges can be properly managed by the use of meshed high-voltage
dc (HVDC) grids.
By Temesgen M. Haileselassie and Kjetil Uhlen, Member IEEE
ABSTRACT | There are very ambitious plans in Europe for
changing the energy infrastructure in order to reduce green-
house gas emissions. This involves scenarios where renewable
energy sources by 2050 will meet almost 100% of the electric
power demand. This has spurred offshore wind farm develop-
ment activities in the North Sea due to the vast wind energy
potential in this region and the potential lack of suitable on-
shore sites in the future. Large-scale wind farms in the North
Sea pose grid integration challenges such as the need for long-
distance subsea power transmission and tackling the impact of
wind power variation on alternating current (ac) grids. These
challenges can be properly managed by the use of meshed
high-voltage direct current (HVDC) grids. Three of the regional
groups (RGs) in the European Network of Transmission System
Operators for Electricity (ENTSO-E), namely Regional Group
Great Britain (RG-GB), Regional Group Nordic (RG-N), and Re-
gional Group Continental Europe (RG-CE), surround the North
Sea area. A meshed North Sea HVDC interconnection between
offshore wind farms and these three asynchronous ac grids can
also enable market integration of the otherwise separate
regions. This, in turn, results in better utilization of generation
and transmission infrastructures, improved security of power
supply, and maximized utilization of renewable energy re-
sources. In this paper, a test scenario of a meshed North Sea
HVDC grid is studied to demonstrate the potential of such a
system for enhancing power supply security of the ac grids.
Simulation studies of the test case show that with proper con-
trol techniques, a meshed North Sea HVDC grid can mitigate the
effect of wind power variation by facilitating exchange of pri-
mary and secondary reserves between asynchronous ac grids.
KEYWORDS | Integration of offshore wind power; meshed high-
voltage direct current (HVDC) grid; power system security
I . INTRODUCTION
By adopting the Energy Roadmap 2050 [1], the European
Commission has committed to reducing the greenhouse gasemissions to 80%–95% below 1990 levels by 2050. The
share of renewable energy (RES) in this scenario will be
around 50% in gross final energy consumption. The share
of RES in electricity consumption could be as high as 97%
and wind power is expected to contribute approximately
50% of the renewable energy [2]. Given the limited size of
other available renewable energy sources, a lot of attention
has been given to development of wind farms in Europe.Due to the fact that most of the suitable sites for wind
power generation in continental Europe have already been
used up, more and more of the recent wind farms are being
located at offshore sites. The North Sea in particular is
endowed with vast amount of wind energy resources and,
hence, the most notable offshore wind farm developments
are concentrated in this region. Bard-1, Norfolk Bank, and
Dogger Bank wind farm projects could highlight some ofthe offshore wind farm development activities in this
region. By harnessing the vast potential of offshore wind
energy, the European Union can be able to significantly
reduce its energy dependency on imports from external
regions.
Despite the benefits of offshore wind farms, the varia-
bility of power production means that alternating current
(ac) grid systems must provide more balancing power. As aresult, the total cost of keeping reserves increases with
increasing wind power penetration. Integration of the
asynchronous ac grids in the North Sea region [i.e.,
Manuscript received September 13, 2011; revised May 20, 2012 and January 4, 2013;
accepted January 7, 2013. Date of publication February 22, 2013; date of current
version March 15, 2013.
The authors are with the Department of Electric Power Engineering,
Norwegian University of Science and Technology, Trondheim N-7491, Norway
(e-mail: [email protected]; [email protected]).
Digital Object Identifier: 10.1109/JPROC.2013.2241375
978 Proceedings of the IEEE | Vol. 101, No. 4, April 2013 0018-9219/$31.00 �2013 IEEE
Regional Group Great Britain (RG–GB), Regional GroupNordic (RG–N), and Regional Group Continental Europe
(RG–CE)] can help to alleviate this challenge in two
ways.
On the one hand, the total variation of wind power
production decreases with increasing geographical
distribution of wind farms (i.e., interconnection of widely
dispersed wind farms into a common power system pool).
The relative variations in total loads will also be smallerwith increasing power system size (and, hence, with in-
creasing interconnections). Hence, a stronger North Sea
interconnection can help to minimize the net demand of
balancing power created by higher penetration of wind
power.
Furthermore, the North Sea interconnections can ena-
ble exchange of primary and secondary reserves between
the three asynchronous ac grids and, as a result, enhancefrequency responses of the ac grids.
Recent developments of wind farms in remote loca-
tions, particularly in remote offshore sites, have steadily
increased the demand for more robust, efficient, and re-
liable grid integration solutions. In this respect, voltage
source converter (VSC)-based HVDC technology with
point-to-point connection is taking the lead in several new
offshore wind power projects due to its advantages for suchapplications. VSC-based HVDC offers long-distance bulk
power transmission capacity, enables interconnection of
asynchronous ac grids, and offers black start capability and
reactive power support [3]. In places where several HVDC
connections are located close to each other, an HVDC grid
(also called multiterminal HVDC) has the potential to in-
crease transmission capacity, system reliability, and elec-
tricity market opportunities.The objective of this paper is to demonstrate, with the
help of simulation results, the potential of a meshed
HVDC grid for power supply security and market integ-
ration in the North Sea region. The paper is outlined as
follows. Section II discusses power system security and
power flow control in traditional ac grids. Section III
deals with an overview of meshed HVDC grids and their
potential applications in the North Sea region. Control ofmeshed HVDC grids is discussed in Section IV. In
Section V, the performance of a meshed North Sea
HVDC grid is analyzed based on simulation results.
Market integration of ac grids with a meshed HVDC grid
is discussed in Section VI. This is followed by Section VII,
which discusses further challenges of developing a meshed
North Sea HVDC grid. Finally, conclusions are drawn
in Section VIII.
II . POWER SYSTEM SECURITY AND GRIDFREQUENCY CONTROL
Power interruption in the modern society is a very costly
phenomenon. Power system operators put utmost efforts
to ensure maximum security and reliability of power
supply thereby minimizing the probabilities of occurrencesof such conditions. Security of a power system refers to the
degree of risk in its ability to survive disturbances (con-
tingencies) without interruption of customer services [4],
[5]. The contingencies include outages such as sudden and
unscheduled loss of service of one or more of the main
power system components (generators, transformers,
transmission lines, converter stations, etc.), usually due
to a fault or system malfunction.The level of power system security is dependent upon
the actual operating condition, the type and probability of
outages, and the response to the outage conditions. Due to
the fast system response required to mitigate the effects of
outage conditions, power system security is an important
factor that must be taken into consideration both during
system planning as well as control design and implemen-
tation phases. Power systems are normally operated ac-cording to the deterministic ðN � 1Þ criterion or possibly
with some risk-based adaptations to this. In [6], some of
the most commonly used security evaluation indices are
discussed.
The N � 1 security criterion means that if the service of
one power system component is lost permanently, the re-
maining system must be capable of stable operation,
compensating for the lost service and supply all loadswithout exceeding operating limits.
Due to redundancy in meshed ac networks, it is possi-
ble to enforce N � 1 security for power transmission. With
outage of one line or transformer, power flow can be
maintained via the other transmission paths without ex-
ceeding the transmission capacity of any of the transmis-
sion lines.
N � 1 security criterion in the context of powergeneration can be obtained accordingly. In the event of
outage of one generation unit, the remaining units in the
ac grid must be able to compensate for the lost gener-
ation without any one of them exceeding its operating
limits.
Frequency droop control is the means by which N � 1
security can be achieved for power generation in an inter-
connected system. Since frequency droop control enablesa shared responsibility of power balancing among several
generation units, power production levels change
smoothly, thereby reducing the stress associated with
abrupt changes in generated power.
In Fig. 1, typical characteristic curves for generation
and load are shown. The slope of the generation line is a
measure of frequency droop constant of the aggregate
generation. Assuming negligible transmission losses, thesteady-state operating point is determined by the inter-
section of aggregate load line and aggregate generation line
in the frequency ðfÞ versus power ðPÞ plane.
The intersection of the generation line and the load
line gives the operating point of the ac system at steady-
state conditions. The slope of the generation line comes
from frequency droop control of generator units whereas
Haileselassie and Uhlen: Power System Security in a Meshed North Sea HVDC Grid
Vol. 101, No. 4, April 2013 | Proceedings of the IEEE 979
the load line usually shows a small degree of frequency
dependency.
Grid frequency control traditionally consists of three
different control actions with differing times of responses.
These are primary control, secondary control, and tertiary
control [7], [8]. Primary control refers to the response ofgeneration control to load changes (or outage of a gener-
ation unit). In a droop controlled ac system, change in load
results in steady-state frequency deviation (compared to
the original level). This is shown in Fig. 2, where PG0 and
PL0 refer to the initial generation line and load line of the
ac grid system.
In Fig. 2, point A refers to the initial steady-state ope-
rating point. When load power is increased, the load lineshifts to the right (i.e., from PL0 to PL1), and as a result, the
steady-state operating point also moves from point A to
point B. This transition corresponds to primary frequency
control. Since the primary control results in a steady-state
frequency deviation (frequency decrement/increment
resulting in load increment/decrement), secondary control
is needed to restore system frequency back to the initial
(desired) level. The effect of secondary control is theshifting of the generation characteristic line so that the
system frequency gets restored to the original level. In
the case of Fig. 2, this (i.e., the secondary control) corre-
sponds to the shifting of the generation line from PG0 to
PG1. As a result, the steady-state operating point changes
from point B to point C, implying restoration of frequency.
Loss of one of the many generation units also leads tosimilar control responses as shown in Fig. 3.
In the event of an outage of a generator unit in a
multimachine grid system, the generation characteristic
line shifts to the left (corresponding to the shift from PG0
to PG1 in Fig. 3). This results in a drop in grid frequency
and, to a smaller degree, a reduction in power consumed
by the load. To restore system frequency back to the
nominal value, the generation line has to shift upwards(i.e., from PG1 to PG2). Secondary control is achieved by
load-frequency control in the case of interconnected ac
systems.
Apart from primary and secondary controls, the tertiary
control is used to reschedule generation based upon the
latest available data about the power system after the oc-
currence of load change or a unit outage. The time response
of frequency and reserves activation are shown in Fig. 4.As shown in Fig. 4, after occurrence of large frequency
disturbance, the primary control is responsible for the
frequency response ðRÞ in the first minute. Frequency re-
sponse ðRÞ is defined as the amount of extra power gener-
ated for each unit decrement of grid frequency. The
secondary controller frees up some of the primary reserves
Fig. 2. Change in the load line and responses of primary and
secondary controls (see [8, p. 263]).
Fig. 3. Change in the generation line (due to loss of a generator unit)
and responses of primary and secondary controls.
Fig. 4. Activation of reserves and time response of grid frequency.
Fig. 1. Determination of steady-state operating point in ac grids.
Haileselassie and Uhlen: Power System Security in a Meshed North Sea HVDC Grid
980 Proceedings of the IEEE | Vol. 101, No. 4, April 2013
already in use. The response time could span around15 min after the occurrence of the load change (or
outage of the generation unit). Finally, the tertiary
controller frees up the secondary reserves in the next
40–60 min.
When renewable energy resources with variable power
production capacity are introduced into the ac grid, they
incur new challenges to the grid frequency control. These
challenges can be summarized as follows.1) Primary control: There will be less primary re-
serves if a new generation (such as a wind farm)
provides less/no frequency response, in which
case more spinning reserves will be required to
provide sufficient frequency response with the
new generation.
2) Secondary control: With further addition of a va-
riable generation such as wind farms into thepower system, there will be a need for more sec-
ondary reserves.
3) Tertiary control: Without new interconnections to
other areas (or ac grids), there will be limited
size of electricity market for the wind power in
times of an ample generation. New interconnec-
tions between ac grids, which otherwise are se-
parate from each other, will give access to largercontrol areas and, as a result, enable exchange of
reserves.
III . MESHED HVDC GRID ANDPOTENTIALS OF ITS APPLICATIONIN THE NORTH SEA REGION
A. Meshed HVDC GridCurrently, there are two types of HVDC transmission
technologies, namely: line commutated converter (LCC)-
based and VSC-based types. Both types of HVDC tech-
nologies have so far been limited to two-terminal (also
called point-to-point) power transmission. Early attempts
to use LCC–HVDC in multiterminal configuration have
given only limited results mainly due to the complexities ofthe controllers for such configuration and also due to the
need for fast communication between controllers of all
HVDC terminal stations.
Despite the many decades of experiences with
LCC–HVDC, the Sardinia–Corsica–Italy (SACOI) HVDC
transmission and the Quebec–New England HVDC
transmission have remained to be the only multipoint
LCC–HVDC transmissions currently in service. On theother hand, the arrival of VSC–HVDC technology a decade
ago has revived research and development activities in the
area of multiterminal HVDC operation. The main reasons
for this are flexibility and simple natures of the active
power controller, reactive power controller, and direct
current (dc) voltage controller used in VSC–HVDC,
which in turn enable autonomous control of individual
converters without involving fast communication be-
tween different terminals.
Hence, this paper focuses on the VSC-type HVDC for
the dc grid application. With this understanding, in the
rest of this paper, the terms HVDC grid and dc grid impli-
citly will refer to the VSC type of the HVDC grid.HVDC grids are formed by interconnecting the dc
busses of three or more converters to a common dc trans-
mission network, whereas the respective ac sides of the
converters may be connected either to the same (syn-
chronous) ac networks or different (asynchronous) ac
networks. HVDC grids can be roughly grouped into two
topologies, namely: radial and meshed. In the radial dc
grid topology, there is only one unique power transmis-sion route between any two terminals. Hence, if one of
the dc transmission lines that make up this route is dis-
connected, power flow between the two terminals will
be disrupted. An example of a radial topology is shown
in Fig. 5(a).
In the case of the meshed topology, there are two or
more alternative power transmission routes between two
specific terminals. An example of the meshed topology isshown in Fig. 5(b). Like in the case of the meshed ac
network, meshed dc grid can provide N � 1 security of
power transmission during outage of one of the dc trans-
mission lines.
In addition, the HVDC grid operation requires that at
least one of the converter stations be assigned as dc voltage
regulator. This implies that apart from enhancing security
of the dc transmission routes, it is necessary to ensureN � 1 security for operation of the VSC–HVDC stations.
Hence, N � 1 security in the context of the multiterminal
VSC–HVDC system must also fulfill the following
conditions.
1) The dc grid consists of two or more dc voltage
regulating HVDC stations.
2) In the event of the outage of one of the dc voltage
regulating converter stations, the remaining onesmust be able to manage dc voltage regulation
without any one of them exceeding its operating
limits.
N � 1 security in the dc grid operation can be achieved
by using dc voltage droop control for two or more of the
Fig. 5. HVDC grid topologies. (a) Radial topology. (b) Mesh topology.
Haileselassie and Uhlen: Power System Security in a Meshed North Sea HVDC Grid
Vol. 101, No. 4, April 2013 | Proceedings of the IEEE 981
VSC–HVDC terminals constituting the dc grid (in similarmanner as frequency droop control is used for synchro-
nous generators).
B. Potential Advantages of Using Meshed HVDC inthe North Sea Region
The North Sea region has unique features which make
meshed HVDC grid an attractive solution for the grid in-
tegration problem. Among these special features, the mostsalient ones are listed below.
1) The presence of three asynchronous ac grids,
namely: RG–N, RG–GB, and RG–CE grid systems.
Interconnecting asynchronous grids with the
HVDC transmission system enables fast and flexi-
ble power flow control in a wider region.
2) Large potential for developing offshore wind
farms in the North Sea. The variable generationfrom wind farms means that there must be more
primary and secondary reserves in the power sys-
tems to compensate for the power fluctuations.
This demand can be met by increasing intercon-
nection of the wind farms with ac grids with
power demands as well as increasing intercon-
nection with ac grids which have available balanc-
ing power. Interconnection between neighboringac grids will also enlarge the effective size of the
market, which is beneficial both for increased
competition and for integrations of large amounts
of variable wind power [9].
3) The large hydropower generation capacity of
Norway can be used for provision of the primary
and secondary reserves required for new large-
scale offshore wind farms in the North Sea.4) The offshore loads in the North Sea (i.e., oil and gas
platforms which mainly use gas fired turbines to
meet their power demand) can also benefit from
clean power supply from onshore grids and/or
from offshore wind farms via HVDC connections.
Moreover, the long offshore transmission distances
between the three mentioned ac grids mean that HVDC
technology will be an essential part of the grid integrationsolution.
The North Sea HVDC grid will not be developed as a
single large project, but in several steps of separate indi-
vidual projects. Offshore wind farm developments are
expected to continue based upon VSC–HVDC intercon-
nections with the three separate ac grids. Once there are a
substantial number of offshore wind farms in the North
Sea, the meshed VSC–HVDC grid can be formed on thebackbone of the already existing subsea power transmis-
sion infrastructure. Such scenario is shown in Fig. 6,
where the dark interconnection lines (encircled by solid
ellipses) show initial stage developments and the light
interconnection lines (encircled by dashed ellipse) show
the formation of the meshed North Sea HVDC grid
afterwards.
IV. CONTROL STRATEGY FOR MESHEDHVDC GRIDS
In the same manner as in the multimachine ac system, a
multiterminal HVDC system should have a mechanism for
instantaneous balancing of the power demand (outflow
from the dc grid via inverters) and power supply (inflow to
the dc grid via rectifiers). In the literature, two methods
are proposed, namely: master–slave control and dc voltage
droop control.In the master–slave control strategy, one converter
terminal (called master terminal) is dedicated for dc
voltage control, and hence for dc grid power balancing
[10], [11]. In the case of dc voltage droop control, two or
more terminals participate in dc voltage control [12]–[14].
The master–slave control strategy exposes the master
terminal to large stresses since this terminal will have to
handle all power fluctuations in the dc grid. In addition, ifthere is an outage of the master terminal, this will result in
an immediate outage of the entire HVDC grid.
In contrast, due to the distributed nature of dc voltage
regulation, dc voltage droop control enables the provision
of N � 1 security (in this case, an outage of an HVDC
terminal which could possibly be one of the terminals with
the droop control mode). In addition, since all dc grid
power fluctuations are distributed among several HVDCterminals, in the droop control mode, none of the
terminals will be exposed to excessive stress due to large
power flow fluctuations.
A VSC–HVDC link can be connected either to an active
ac grid or to a passive ac grid. In the active ac grid
connection, the grid will already have ac voltage prior to
the connection of the converter station. The converter
Fig. 6. Meshed North Sea HVDC grid scenario: blue lines show early
state developments and red lines show later stage development).
Haileselassie and Uhlen: Power System Security in a Meshed North Sea HVDC Grid
982 Proceedings of the IEEE | Vol. 101, No. 4, April 2013
controller then synchronizes the ac voltage output of the
VSC–HVDC terminal according to the external ac voltage.
A VSC–HVDC with the active ac grid can actively control
its current flow, which in turn enables us to adopt any one
of the following control mode options:
1) constant power control mode;
2) constant dc voltage control (integral dc voltagecontrol) mode;
3) dc voltage droop control mode.
Block diagrams of the three types of VSC–HVDC
control modes are found in the Appendix. Further details
of the controllers and VSC–HVDC models can be referred
to [21]. DC voltage versus power flow characteristics of the
three types of control modes are shown in Fig. 7.
In the constant power control mode, the power flow viathe converter station is independent of the dc voltage. The
power flow may be controlled actively by the VSC–HVDC
controller (in the case of active ac grid connection) or by
the ac grid power demand (in the case of passive grid
connection).
In the case of passive grid connected VSC–HVDC, the
converter becomes the main (or possibly the only) source
of ac voltage, while power flow via the converter is deter-mined by the loads connected in the ac grid. As a result, a
passive grid connected VSC–HVDC appears as the con-
stant power controlled terminal [Fig. 7(a)] when observed
from the dc bus (i.e., power flow is independent of dc bus
voltage). HVDC link supplying power to an oil/gas plat-
form or to an island can be a typical example for passive
ac grid connection.
Constant dc voltage control refers to the integral con-trol of dc bus voltage and by doing so this particular ter-
minal provides all demand of instantaneous balancing
power. Neglecting the dc line losses, dc grid power ba-
lancing can be defined as elimination of any nonzero net
power flow into or out of the dc grid.
DC voltage droop control is characterized by linear
interdependency of dc bus voltage and the power flow via
the HVDC terminal. DC voltage versus power character-istic curve of the VSC–HVDC terminal with the three dif-
ferent control modes is shown in Fig. 7(c). The sign
convention in Fig. 7 is such that positive power implies the
rectifier mode of operation and negative power implies the
inverter mode of operation.
The performance of the three modes of HVDC control
can be analyzed with the help of the two-terminal HVDC
link model shown in Fig. 8.
In Fig. 8, the two HVDC terminals can represent the
aggregates of rectifiers and the aggregates of inverters.Hence, ignoring the dc line losses, the intersection of the
source power ðPSÞ and the load power ðPLÞ characteristic
lines in Fig. 9 gives the steady-state operating point.
As the load line in Fig. 9(a) changes (from PL0 to PL1),
the dc bus voltage remains unchanged. When droop con-
trol is used for the source HVDC terminal and fixed con-
trol for the load HVDC terminal, a change in the load line
is followed by a change in the dc voltage; i.e., transitionfrom an initial operating point A to a new operating point B,
as shown in Fig. 9(b).
In the case of droop control applied to both sides, the
shifting of either the source line or the load line affects the
steady-state power flow and the dc voltage as well, as
shown in Fig. 9(c).
DC grid response to a sudden change in the power flow
(i.e., transition from A to B) is referred here as primary dcvoltage response (analogous to primary frequency response
of ac grids). Since primary dc voltage response of droop
controlled multiterminal VSC–HVDC involves a steady-
state change in operating dc voltage, secondary control is
required to restore the dc voltage back to the desired level
if needed. The secondary controller can be activated
sometime after a steady-state dc voltage drop is observed,
and it acts more slowly compared to the primary controlaction. In Fig. 9(b) and (c), for example, the secondary
controller is activated half a minute after the drop in dc
voltage is observed, and it takes about 20 s to restore the
dc voltage to the original level. In Fig. 9(c), we can see
that the dc voltage drop is lower (between t ¼ 20 s and
t ¼ 50 s) due to the contribution of the inverter to dc
voltage droop control. But this advantage comes at the cost
of the lower power flow (�925 MW) compared to thedesired level (1000 MW). The desired power flow level is
achieved after the action of secondary control, as shown in
the time plot of Fig. 9(c) (after t ¼ 50 s).
In addition to transferring power based on the predefined
time schedule, HVDC interconnection can also be used to
Fig. 7. DC voltage versus power characteristic of VSC–HVDC terminals
with: (a) constant power control; (b) constant dc bus voltage control;
and (c) dc voltage droop control.
Fig. 8. Two-terminal (point-to-point) HVDC connection.
Haileselassie and Uhlen: Power System Security in a Meshed North Sea HVDC Grid
Vol. 101, No. 4, April 2013 | Proceedings of the IEEE 983
enhance frequency response of ac grids. Currently, HVDC
links are utilized for exchange of balancing reserves
(secondary and tertiary control) across ac interconnections.
This is commonly used, for example, on Skagerrak HVDC
link between Norway and Western Denmark. Likewise,
HVDC control can be extended to include the primary
frequency support (i.e., for frequency response enhance-ment) of ac grids. This can easily be achieved by adding
frequency droop loop in the HVDC converter power con-
troller [15]. Block diagrams of frequency droop control im-
plementation for VSC–HVDC are included in the Appendix.
V. MESHED NORTH SEA HVDCSCENARIO: SIMULATION STUDIES
Different interconnection scenarios have been proposed
in the literature for the meshed North Sea HVDC inter-
connection (sometimes referred to as the North Sea
supergrid). Fig. 10 shows different meshed North Sea
HVDC grid scenarios envisioned by Airtricity [16], Sintef
[17], Statnett [18], and the European Wind Energy
Association [19].
In this paper, a rather simplified scenario of the North
Sea supergrid has been considered for demonstrating its
potentials with the help of simulation studies.As shown in Fig. 11, the test scenario includes two
interconnections to RG–GB, one interconnection to the
Nordic grid, one interconnection to the RG–CE grid,
one interconnection to an offshore wind farm, and one
interconnection to an offshore load (oil and gas
platform).
Converter power and voltage ratings are chosen for
demonstration purpose only and do not represent anyspecific future plan for the North Sea supergrid. The elec-
tromagnetic transient simulation tool EMTDC/PSCAD was
used for modeling the test scenario.
Fig. 9. Steady-state operating points and corresponding time-domain responses: (a) constant dc voltage control on the rectifier side and
constant power control on the inverter side; (b) dc voltage droop control on the rectifier side and fixed power control on the inverter side;
and (c) dc voltage droop control on both sides.
Haileselassie and Uhlen: Power System Security in a Meshed North Sea HVDC Grid
984 Proceedings of the IEEE | Vol. 101, No. 4, April 2013
A. Mitigation of Wind Power Fluctuation by PrimaryPower Balancing of HVDC Grid
In the test scenario, the offshore wind farm injects
variable wind power into the HVDC grid, and, as a result,
the dc bus voltages also show similar variations. The
HVDC terminals with dc voltage droop control (i.e., 1, 2,
and 4) respond by varying their power flow accordingly. In
contrast, the HVDC terminals with constant power control
(i.e., 3 and 5) remain unaffected by the dc bus voltage
variations.From the plots in Fig. 12 it is evident that the large
power flow variation from the offshore wind farm has
effectively been distributed to terminals 1, 2, and 4 (i.e.,
the HVDC terminals in the droop control mode), hence
demonstrating the capability of the meshed North Sea
HVDC grid for mitigating the impact of wind power
variation on the ac grid.
By varying the sizes of the dc voltage droop in thesethree HVDC terminals, it is possible to change the shares
of the dc grid balancing power coming from each converter
station. This is ultimately dependent upon the availability
of primary balancing power in the ac grids connected to
the meshed HVDC grids.
B. Coping With Loss of DC Line in the MeshedHVDC Grid
To show the supply security capability of a meshed
HVDC grid in the North Sea, outage of a dc line was
studied with the simulation model. DC line 1–2 is dis-
connected abruptly at t ¼ 90 s. This results in increased
power flow in some of the dc lines (line 1–3, line 1–4, and
line 3–4) such that the power injection at each of the
HVDC station remains nearly unaffected. A closer look at
Fig. 10. North Sea supergrid proposal by Airtricity (top left),
Sintef (top right), Statnett (bottom left), and the European Wind
Energy Association (bottom right).
Fig. 11. Test scenario of the meshed North Sea HVDC grid.
Fig. 12. Wind power variation and primary balancing by HVDC
terminals in the dc voltage droop mode.
Haileselassie and Uhlen: Power System Security in a Meshed North Sea HVDC Grid
Vol. 101, No. 4, April 2013 | Proceedings of the IEEE 985
the time plots in Fig. 13 shows that the terminals with dc
voltage droop control exhibit small amounts of power flow
deviations after outage of line 1–2. This is due to the dc
line resistances which result in unequal variations of the dc
bus voltages, which in turn affect the droop controllers.
Nonetheless, the simulation results show that the meshedHVDC grid with dc voltage droop control can ensure sup-
ply security even after loss of one of the dc lines consti-
tuting the meshed topology.
The dc line resistances dictate how much power each
dc line will transfer after the loss of line 1–2 (i.e., based on
Ohm’s law applied to the new dc grid topology as the
current injections at all nodes remain nearly the same as
prior to disconnection of line 1–2). Therefore, it is neces-sary that all the dc transmission lines with increased power
flow (i.e., line 1–3, line 1–4, and line 3–4) are dimen-
sioned to accommodate their respective power flows ob-
served after the line outage (i.e., after t ¼ 90 s in Fig. 13).
It is foreseen that power and energy is dispatched in
the dc grid by some market arrangement (as in ac grids),
by, for example, flow-based market coupling. Note, how-
ever, that the power flow in the individual lines can only befully controlled if the number of branches is smaller than
the number of converters (since Ohm’s law applies here as
well). Therefore, it is necessary that N � 1 security for dc
transmissions take the power transfer capacity limits of the
transmission lines as well as that power ratings of HVDC
terminals into account.
C. Response to Loss of Connection to OffshoreWind Farm
In Section III, it was argued that dc voltage droop
control enables the provision of N � 1 security in a meshed
HVDC grid. This feature becomes useful during loss of
connection to offshore wind farm (or loss of power gener-
ation from offshore wind farm). This can be seen from the
simulation results in Fig. 14, which shows that the con-
nection loss of the wind farm at t ¼ 85 s was compensatedby the droop controlled terminals (1, 2, and 4).
In this particular case, converters 1 and 4 (i.e., HVDC
connections to Scotland and RG–N) responded by in-
creasing the power injection into the dc grid while con-
verter 2 (i.e., HVDC connection to England) responded by
reducing the power it takes away from the dc grid. HVDC
terminal connected to RG–CE (i.e., terminal 3) was as-
signed to constant power mode and hence remained unaf-fected by the loss of wind power supply into the meshed
HVDC grid. Similarly, the power supply to the offshore oil/
gas platform remained uninterrupted despite the loss of
wind power injection. Here too it is necessary that con-
verters 1 and 4 have the capacity to accommodate for the
increased power flow observed after t ¼ 85 s in Fig. 14.
D. Primary Reserves Exchange via HVDC GridExchange of primary and secondary reserves between
the three ac grids (RG–N, RG–GB, and RG–CE) is possible
by means of meshed North Sea HVDC grid. This requires
the use of frequency droop control on the HVDC terminalpower flow controller, in addition to the dc voltage droop
described previously. Block diagrams of frequency droop
control for use with constant power control mode and dc
voltage control mode are shown in Fig. 20.
To demonstrate primary reserves exchange via HVDC
with the help of simulation study, a frequency droop
element was added to the HVDC terminal connected to the
Fig. 13. Response of meshed HVDC for an outage of the dc line.
Fig. 14. Response of the dc grid to loss of connection to offshore wind
farm. (Positive power implies inverter mode and negative power
implies rectifier mode of operation.)
Haileselassie and Uhlen: Power System Security in a Meshed North Sea HVDC Grid
986 Proceedings of the IEEE | Vol. 101, No. 4, April 2013
RG–CE grid. Since this terminal was in constant power
control mode in previous cases, the new control structure
with the frequency droop control looks like Fig. 20(a) inthe Appendix.
A sudden loss of power generation unit of 1.2-GW
power rating inside the RG–CE was simulated and the
resulting responses are shown in Fig. 15. The RG–CE grid
is modeled with a frequency response of 10 GW/Hz.
The loss of power generation is followed by frequency
dipping in RG–CE, which in turn resulted in increased
power generation from synchronous generators in the gridsystem. Similarly, due to the frequency droop control,
converter 3 responds by injecting additional power into the
RG–CE grid after sensing the drop in frequency. Since the
additional power eventually comes from other ac grids (in
this case, from RG–N and RG–GB grid systems) frequency
oscillations will be observed in other ac grids as well (see
the frequency plots in Fig. 15).
Comparison of the frequency responses of the RG–CEgrid in the presence and absence of frequency support by
the North Sea HVDC grid is shown in Fig. 16. The ob-
served dipping in frequency of the RG–CE grid after loss of
generation unit is larger in the absence of frequency sup-
port from the meshed HVDC grid (compared to the case
where frequency support from the dc grid is available).
This demonstrates that a North Sea HVDC grid has the
potential for enhancing the frequency responses of theinterconnected ac grids.
VI. HIERARCHICAL MARKET-ORIENTEDPOWER FLOW CONTROL IN A POWERSYSTEM CONSISTING OF HVDC GRIDS
At the highest level of power flow control hierarchy,
generation and transmission scheduling in a deregulated
power system are governed by power market (specifically
the day-ahead market). At this level of control, there is
little distinction between ac and dc transmissions. This
means that the bids to the electricity market coupled with
power flow constraints (in both ac and dc transmissions)
will determine the market settlement and the final powerflow schedule. Similarly, in tertiary control, the original
power flow schedule is modified based upon the latest
available data about the power system including ac and dc
transmission networks.
As one goes down the control hierarchy, the distinction
between ac and dc grids becomes larger. In ac grids, power
flow is controlled by adjusting references to generating
units, whereas in dc grids, power flow is controlled byadjusting references to converter units. Like that of ac
grids, it is possible to impose a secondary control for dc
grids so that large dc voltage deviations as well as power
flow deviations can be compensated. The flow chart in
Fig. 17 describes the primary, secondary, and tertiary con-
trol sequences in a power system consisting of ac grid and
HVDC grid systems.
The secondary control in the dc grid is similar to the tie-line control in ac grid systems and has the objective of
restoring the power flow of the selected HVDC stations
back to scheduled levels after the occurrence of large
steady-state power flow deviations. As discussed in
Section IV, large power flow deviations in the dc grid
come from sudden outage of a converter station. The sim-
ulated case of wind power loss in Fig. 14 can be a good
example for steady-state power flow deviation due to anoutage of an HVDC station. In this particular case, although
Fig. 15. Primary reserves exchange via HVDC grid.
Fig. 16. Comparison of frequency responses of the RG–CE grid with
and without the frequency support by the North Sea HVDC grid.
Haileselassie and Uhlen: Power System Security in a Meshed North Sea HVDC Grid
Vol. 101, No. 4, April 2013 | Proceedings of the IEEE 987
converters 1, 2, and 4 are participating in the primary
control, there may be a more urgent need to restore power
flow in certain HVDC stations than in the others.Here we have considered a scenario where there is a
need to restore power flow in converters 1 and 2 (i.e.,
RG–GB connections) at the expense of more power
injection from the RG–N grid via converter 4. This is based
on the premise that the huge installed capacity of Norway in
the RG–N grid is capable of such provision. Based on this
scenario, the responses of the secondary control in the
meshed North Sea HVDC grid model are shown in Fig. 18.As shown in Fig. 18, the secondary control action is
capable of restoring the power flow of converters 1 and 2 to
the same level as prior to the loss of connection to offshore
wind farm. Power flow via converter terminals 3 and 5
remained intact throughout the primary and secondary
control actions.
In conclusion, the well-established knowledge on ope-
ration and market integration of ac power systems caneasily be adapted to a meshed North Sea HVDC grid.
VII. CHALLENGES IN DEVELOPINGMESHED NORTH SEA DC GRID
While the potentials of the meshed HVDC grid in the
North Sea appear to be enormous, there are challenges in
employing the technology on the ground. The most promi-
nent challenges are discussed as follows.
1) DC Fault Handing Issues: DC fault protection based
upon converters ac side protection and dc isolators has
been proposed in the literature, thereby avoiding the need
for dc circuit breakers [20]. The method involves dis-connecting all converters on their respective ac sides, then
isolating part of the dc grid with dc fault and reconnecting
all the healthy converter stations to their respective ac
grids. Although the method is capable of disconnecting
the faulty part and restoring normal operation of the rest
of the dc grid, the momentary disconnection of the entire
dc grid involved in this process could undermine security
of supply unless the restoration time is sufficiently small.DC circuit breakers on the other hand could instanta-
neously disconnect the faulty part without the need to
temporarily disconnect the dc grid from all ac connections.
However, dc circuit breakers in the high-voltage and high-
current ranges have not been commercially available yet.
2) Standardization of DC Transmission Voltage Level andRequirements for Dynamic Responses: Current suppliers ofVSC–HVDC technology use different dc voltage ratings for
HVDC solutions, which usually are specifically chosen to
suit the applications. Since a meshed HVDC grid is ex-
pected to involve various technology suppliers and trans-
mission system operators, there is a clear need for
determining standard dc voltage level as well as HVDC
terminal response requirements (such as droop level for dc
voltage control, droop level for frequency support byHVDC, responses to ac and dc faults, etc.).
3) Ambiguity Surrounding Ownership and Management ofthe North Sea Supergrid: Since the North Sea supergrid will
Fig. 17. Flow chart describing primary, secondary, and tertiary
controls of ac/dc grids.
Fig. 18. Secondary control response of the HVDC grid for loss of
connection to offshore wind farm.
Haileselassie and Uhlen: Power System Security in a Meshed North Sea HVDC Grid
988 Proceedings of the IEEE | Vol. 101, No. 4, April 2013
most likely span several transmission system operators, it
may not be very clear who will have ownership andresponsibility for its operation. These are crucial questions
that should be addresses properly since these directly
affect sharing of investment and maintenance costs as well
as operation and market integration of the dc grid.
VIII . CONCLUSION
If the vast potential of wind energy in the North Sea is tobe fully utilized, strategies for increased security of supply
should be put in place, especially to deal with power fluc-
tuations from offshore wind farms. In this regard, a
meshed HVDC grid is an emerging technology whichVif
employed in the North Sea regionVcan potentially en-
hance the security of supply of the ac grids connected to it.
A meshed HVDC grid in the North Sea can potentially
have several benefits, which include exchange of reservesbetween RG–GB, RG–N, and RG–CE grid systems,
integration of offshore wind farms with balancing power
provision from Nordic area (particularly from Norway),
and access to wider power market areas. As a result, the
North Sea ‘‘supergrid’’ (as it is often called) can increase
security of supply as well as enable better utilization of
energy resources in the interconnected areas.
Results from simulation studies show that withappropriate control schemes, a meshed HVDC grid in
the North Sea can enhance grid frequency control and help
in dealing with outage conditions such as loss of wind
power production.
The need for fast and reliable dc fault protection as well
as ambiguity regarding ownership and management of the
meshed HVDC grid are mentioned as main challenges inthe development process of the North Sea supergrid. h
APPENDIXThe block diagrams of the various control modes of
VSC–HVDC terminals discussed in this paper are shown in
Fig. 19. In the upper parts of Fig. 19, the steady-state dc
voltage versus power characteristics are shown, and below
are the block diagrams of the corresponding controllers.
Proportional–integral (PI) controllers are used in all threecases, ensuring that the desired characteristics are ob-
tained when the error signal e is controlled to zero.
P and U refer to power and dc voltage measurements of
the VSC–HVDC terminal whereas P� and U� refer to
power reference and dc voltage reference, respectively. Rdc
is the dc voltage response constant. i�d is the reference
input for active current controller (not shown here). d�qreference-frame-based current control of VSC has beenused for the simulations in this paper. Readers are referred
to [21] for further details on the current control.
In Fig. 20, the block diagram of frequency droop
control in VSC–HVDC is shown. In Fig. 20(a), constant
power controller is supplemented with frequency droop
control, and in Fig. 20(b), the controller consists of both
dc voltage droop and frequency droop control elements. In
the simulation case of Section V-D, the controller shown inFig. 20(a) was implemented for terminal 3 (converter
connected to the RG–CE grid).
RE FERENCES
[1] European Commission, Energy Roadmap2050, Brussels, Belgium, EU COM(2011)885 Final, 2011. [Online]. Available:http://ec.europa.eu/energy/energy2020/roadmap/index_en.htm.
[2] European Wind Energy Association, EUenergy policy to 2050VAchieving 80–95%emissions reductions, Mar. 2011. [Online].Available: http://www.ewea.org.
[3] J. Arrillaga, Y. H. Liu, and N. R Watson,Flexible Power Transmission. The HVDCOptions. New York, NY, USA: Wiley,2009.
[4] D. S. Kirschen, ‘‘Power system security,’’Power Eng. J., vol. 16, no. 5, pp. 241–248,Oct. 2000.
[5] P. Kundur, J. Paserba, V. Ajjarapu,G. Andersson, A. Bose, C. Canizares,N. Hatziargyriou, D. Hill, A. Stankovic,C. Taylor, T. Van Cutsem, and V. Vittal,
‘‘Definition and classification of powersystem stability,’’ IEEE Trans. Power Syst.,vol. 19, no. 3, pp. 1387–1401, May 2004.
[6] S. Liang, M. Fan, and F. Yang, ‘‘Researchon security standards of power system inChina and UK,’’ in Proc. Int. Conf. Power Syst.Technol., 2010, DOI: 10.1109/POWERCON.2010.5666133.
[7] P. Kundur, Power System Stability andControl. New York, NY, USA: McGraw-Hill,1994.
Fig. 19. DC terminal control configurations and the corresponding
dc voltage versus power characteristics: (a) dc bus power controller;
(b) dc voltage regulator; and (c) dc voltage droop controller.
Fig. 20. Frequency droop control provision for VSC–HVDC: (a) with
constant power control; and (b) with dc voltage droop control.
Haileselassie and Uhlen: Power System Security in a Meshed North Sea HVDC Grid
Vol. 101, No. 4, April 2013 | Proceedings of the IEEE 989
[8] J. Machowski, J. W. Bialek, and J. R. Bumpy,Power System Dynamics and Stability.Chichester, U.K.: Wiley, 1997.
[9] L. Meeus, K. Purchala, and R. Belmans,‘‘Development of the internal electricitymarket in Europe,’’ Electricity J., vol. 18, no. 6,pp. 25–35, 2005.
[10] T. Nakajima and S. Irowaka, ‘‘A controlsystem for HVDC transmission by voltagesourced converters,’’ in Proc. IEEE PowerEng. Soc. Summer Meeting, 1999, vol. 2,pp. 1113–1119.
[11] W. Lu and B.-T. Ooi, ‘‘Optimal acquisitionand aggregation of offshore wind powerby multi-terminal voltage-source HVDC,’’IEEE Trans. Power Delivery, vol. 18, no. 1,pp. 201–206, Jan. 2003.
[12] W. Lu and B. T. Ooi, ‘‘Premium quality powerpark based on multi-terminal HVDC,’’ IEEETrans. Power Delivery, vol. 20, no. 2, pt. 1,pp. 978–983, Apr. 2005.
[13] R. L. Hendriks, G. C. Paap, and W. L. Kling,‘‘Control of a multi-terminal VSCtransmission scheme for interconnectingoffshore wind farms,’’ in Proc. Eur. WindEnergy Conf. Exhibit., pp. 1–8, Dec. 4–6, 2007.
[14] L. Xu, B. W. Williams, and L. Yao,‘‘Multi-terminal DC transmission systems forconnecting large offshore wind farms,’’ inProc. IEEE Power Energy Soc. General Meeting,2008, DOI: 10.1109/PES.2008.4596508.
[15] T. M. Haileselassie and K. Uhlen, ‘‘Primaryfrequency control of remote grids connectedby multi-terminal HVDC,’’ in Proc. IEEEPower Energy Soc. General Meeting, 2010,DOI: 10.1109/PES.2010.5589327.
[16] Airtricity, European offshore supergridproposal. [Online]. Available: http://www.trec-uk.org.uk/resources/airtricity_supergrid_V1.4.pdf.
[17] Integrating wind: Developing Europe’s powermarket for the large-scale integration of
wind power, TradeWind Rep., May 2009,pp. 57–58.
[18] Wind Energy: The Facts, Transnationaloffshore grids: The case for an offshoregrid. [Online]. Available: http://www.wind-energy-the-facts.org/en/part-2-grid-integration/chapter-4-grid-infrastructure-upgrade-for-large-scale-integration/transnational-offshore-grids.html.
[19] European Wind Energy Association, Oceansof opportunity: Harnessing Europe’s largestdomestic energy resource, Sep. 2009, p. 31.
[20] L. Tang and B.-T. Ooi, ‘‘Locating and isolatingDC faults in multi-terminal DC systems,’’IEEE Trans. Power Delivery, vol. 22, no. 3,pp. 1877–1884, Jul. 2007.
[21] T. M. Haileselassie and K. Uhlen, ‘‘Impactof DC line voltage drops on power flow ofMTDC using droop control,’’ IEEE Trans.Power Systems, vol. 27, no. 3, pp. 1441–1449,Aug. 2012.
ABOUT THE AUT HORS
Temesgen M. Haileselassie received the M.Sc.
degree in electric power engineering from the
Norwegian University of Science and Technology
(NTNU), Trondheim, Norway, in 2008, where he is
currently working toward the Ph.D. degree.
His research interests include multiterminal
HVDC, grid integration of wind farms, and control
and dynamics of power systems.
Kjetil Uhlen (Member, IEEE) received the M.S. and
Ph.D. degrees in control engineering from the
Norwegian University of Science and Technology
(NTNU), Trondheim, Norway, in 1986 and 1994,
respectively.
He is currently a Professor of Power Systems at
NTNU. His main interests are control and opera-
tion of power systems, power system dynamics,
and wind power integration.
Haileselassie and Uhlen: Power System Security in a Meshed North Sea HVDC Grid
990 Proceedings of the IEEE | Vol. 101, No. 4, April 2013