132 kV River Crossing: Loading tree calculation River Crossing Span, L 500.00 m 330.00 m Normal Condition (NC) Worst wind and no conductor broken Broken wire condition (BWC) Worst wind with one conductor and one ew. broken Angle of deviation, a 10.00 degree Weight of insulator string, w 1 70.00 kg Length of insulator string, l 1 2000.00 mm Dia of insulator string, d 1 200.00 mm Qty. of Insulator per side of arm, N i 1.00 Dia of conductor, d c 25.10 mm Weight of conductor, w c 1302.00 kg/km Working tension in conductor, T C 45126.00 N Dia of earth wire, d E 9.50 mm Weight of earth wire, w e 460.00 kg/km Working tension in earth wire, T E 28430.00 N Damper weight for conductor, w dC 0.00 kg Damper weight for earth wire, w dE 0.00 kg Wind pressure on conductor, p c 1427.00 N/m 2 Wind pressure on earthwire, p e 1686.00 N/m 2 Wind direction, q 45.00 o Span reduction factor for BWC, r 1 1.00 Tension red. fact. for BWC for conductor, r 2 0.70 Min. unbal. Long. force per conductor 8000.00 N Min. unbal. Long. force per earthwire 2500.00 N Calculations Wind span, L 1 500.00 m Weight span, L 2 800.00 m VERTICAL LOAD Normal condition Broken wi Earth wire point Weight of earth wire w e L 2 3608.98 N w e L 2 r 1 Weight of damper (two dampers) 2w dE 0.00 N w dE 3608.98 N At cross arm Weight of insulator string w 1 N i 686.49 N w 1 N i Weight of conductor w c L 2 10214.97 N w c L 2 r 1 Weight of damper (two dampers) 2w dC 0.00 N w dC 10901.46 N LONGITUDINAL LOAD Earthwire point Unbalanced pull 2500.00 N T E cos(a /2 ) At cross arm Unbalanced pull 8000.00 N T C cos(a /2 )r 2 Wind force on insulator p c l 1 d 1 cosq 403.62 N p c l 1 d 1 cosq 8403.62 N TRANSVERSE LOAD Earthwire point Component of working tension 2T E sin(a /2 ) 4955.67 N T E sin(a /2 ) Wind force on earth wire p e sinq L 1 d E cos(a/2) 5641.19 N p e sinq L 1 d E cos(a/2)r 1 10596.86 N At cross arm Component of working tension 2T C sin(a /2 ) 7865.97 N T C sin(a /2 )r 2 Wind force on conductor p c sinq L 1 d C cos(a/2) 12614.99 N p c sinq L 1 d C cos(a/2)r 1 Wind force on insulator string p c l 1 d 1 sinq 403.61 N p c l 1 d 1 sinq 20884.57 N Span between Anchor and RC tower, L A Revised (m/d/y) 5/11/2014 Page 1 of 30
Transcript
Page 1: Power Transmisison Towers Loading Tree

132 kV River Crossing: Loading tree calculation

River Crossing Span, L 500.00 m

330.00 m

Normal Condition (NC) Worst wind and no conductor broken

Broken wire condition (BWC) Worst wind with one conductor and one ew. broken

Angle of deviation, a 10.00 degree

Weight of insulator string, w 1 70.00 kg

Length of insulator string, l 1 2000.00 mm

Dia of insulator string, d 1 200.00 mm

Qty. of Insulator per side of arm, N i 1.00

Dia of conductor, d c 25.10 mm

Weight of conductor, w c 1302.00 kg/km

Working tension in conductor, T C 45126.00 N

Dia of earth wire, d E 9.50 mm

Weight of earth wire, w e 460.00 kg/km

Working tension in earth wire, T E 28430.00 N

Damper weight for conductor, w dC 0.00 kg

Damper weight for earth wire, w dE 0.00 kg

Wind pressure on conductor, p c 1427.00 N/m2

Wind pressure on earthwire, p e 1686.00 N/m2

Wind direction, q 45.00o

Span reduction factor for BWC, r 1 1.00

Tension red. fact. for BWC for conductor, r 2 0.70

Min. unbal. Long. force per conductor 8000.00 N

Min. unbal. Long. force per earthwire 2500.00 N

Calculations

Wind span, L 1 500.00 m

Weight span, L 2 800.00 m

VERTICAL LOAD

Normal condition Broken wire condition

Earth wire point

Weight of earth wire w e L 2 3608.98 N w e L 2 r 1

Weight of damper (two dampers) 2w dE 0.00 N w dE

3608.98 N

At cross arm

Weight of insulator string w 1 N i 686.49 N w 1 N i

Weight of conductor w c L 2 10214.97 N w c L 2 r 1

Weight of damper (two dampers) 2w dC 0.00 N w dC

10901.46 N

LONGITUDINAL LOAD

Earthwire point

Unbalanced pull 2500.00 N T E cos(a /2 )

At cross arm

Unbalanced pull 8000.00 N T C cos(a /2 )r 2

Wind force on insulator p c l 1 d 1 cosq 403.62 N p c l 1 d 1 cosq

8403.62 N

TRANSVERSE LOAD

Earthwire point

Component of working tension 2T E sin(a /2 ) 4955.67 N T E sin(a /2 )

Wind force on earth wire p e sinq L 1 d E cos(a/2) 5641.19 N p e sinq L 1 d E cos(a/2)r 1

10596.86 N

At cross arm

Component of working tension 2T C sin(a /2 ) 7865.97 N T C sin(a /2 )r 2

Wind force on conductor p c sinq L 1 d C cos(a/2) 12614.99 N p c sinq L 1 d C cos(a/2)r 1

Wind force on insulator string p c l 1 d 1 sinq 403.61 N p c l 1 d 1 sinq

20884.57 N

Span between Anchor and RC tower, L A

Revised (m/d/y) 5/11/2014 Page 1 of 30

Page 2: Power Transmisison Towers Loading Tree

132 kV River Crossing: Loading tree calculation

Wind direction, q 45.00o

3609

Angle of deviation, a 10.00o

2500

Normal Condition

10597 (forces are in Newton)

8404

20885

Loading tree

Normal Condition 10901 10901

(forces are in Newton)

8404

20885

10901 10901

8404

20885

10901 10901

3609

28322

Earth wire broken condition

8119 (forces are in Newton)

8404

20885

Loading tree

Earth wire broken condition 10901 10901

(forces are in Newton)

8404

20885

10901 10901

8404

20885

10901 10901

Revised (m/d/y) 5/11/2014 Page 2 of 30

Page 3: Power Transmisison Towers Loading Tree

132 kV River Crossing: Loading tree calculation

Top-left conductor broken condition

Wind direction, q 45.00o

3609 (In analysis middle-left and bottom-left

Angle of deviation, a 10.00o

2500 conductor broken condition shall also be

included)

10597 (forces are in Newton)

31872

15772

Loading tree

Top-left conductor broken condition 10901 10901

(In analysis middle-left and bottom-left

conductor broken condition shall also be 8404

included)

(forces are in Newton)

20885

10901 10901

8404

20885

10901 10901

Revised (m/d/y) 5/11/2014 Page 3 of 30

Page 4: Power Transmisison Towers Loading Tree

Broken wire condition

3608.98 N

0.00 N

3608.98 N

686.49 N

10214.97 N

0.00 N

10901.46 N

28321.82 N

31468.00 N

403.62 N

31871.61 N

2477.84 N

5641.19 N

8119.02 N

2753.09 N

12614.99 N

403.61 N

15771.69 N

Revised (m/d/y) 5/11/2014 Page 4 of 30

Page 5: Power Transmisison Towers Loading Tree

8404

20885

8404

20885

8404

20885

Earth wire broken condition

8404

20885

8404

20885

8404

20885

Revised (m/d/y) 5/11/2014 Page 5 of 30

Page 6: Power Transmisison Towers Loading Tree

Top-left conductor broken condition

(In analysis middle-left and bottom-left

conductor broken condition shall also be

8404

20885

8404

20885

8404

20885

Revised (m/d/y) 5/11/2014 Page 6 of 30

Page 7: Power Transmisison Towers Loading Tree

132 kV Angle Tower: Loading tree calculation

Basic Span, L 330.00 m

330.00 m

Normal Condition (NC) Worst wind and no conductor broken

Broken wire condition (BWC) Worst wind with two conductor and one ew. broken

Angle of deviation, a 60.00 degree

Weight of insulator string, w 1 70.00 kg

Length of insulator string, l 1 2000.00 mm

Dia of insulator string, d 1 200.00 mm

Qty. of Insulator per side of arm, N i 2.00

Dia of conductor, d c 25.10 mm

Weight of conductor, w c 1302.00 kg/km

Working tension in conductor, T C 45126.00 N

Dia of earth wire, d E 9.50 mm

Weight of earth wire, w e 460.00 kg/km

Working tension in earth wire, T E 28430.00 N

Damper weight for conductor, w dC 0.00 kg

Damper weight for earth wire, w dE 0.00 kg

Wind pressure on conductor, p c 1427.00 N/m2

Wind pressure on ew., p e 1686.00 N/m2

Wind direction, q 45.00o

Span reduction factor for BWC, r 1 1.00

Tension red. fact. for BWC for conductor, r 2 0.70

Min. unbal. Long. force per conductor 8000.00 N

Min. unbal. Long. force per earthwire 2500.00 N

Calculations

Wind span, L 1 365.00 m

Weight span, L 2 680.00 m

VERTICAL LOAD

Normal condition

Earth wire point

Weight of earth wire w e L 2 3067.63 N

Weight of damper (two dampers) 2w dE 0.00 N

3067.63 N

At cross arm

Weight of insulator string w 1 N i 1372.98 N

Weight of conductor w c L 2 8682.73 N

Weight of damper (two dampers) 2w dC 0.00 N

10055.71 N

LONGITUDINAL LOAD

Earthwire point

Unbalanced pull 2500.00 N

At cross arm

Unbalanced pull 8000.00 N

Wind force on insulator p c l 1 d 1 cosqN i 807.23 N

8807.23 N

TRANSVERSE LOAD

Earthwire point

Component of working tension 2T E sin(a /2 ) 28429.98 N

Wind force on earth wire p e sinq L 1 d E cos(a/2) 3580.00 N

32009.98 N

At cross arm

Component of working tension 2T C sin(a /2 ) 45125.97 N

Wind force on conductor p c sinq L 1 d C cos(a/2) 8005.64 N

Wind force on insulator string p c l 1 d 1 sinqN i 807.21 N

53938.82 N

Span between Angle tower and Pole/Anchor tower, L A

Revised (m/d/y) 5/11/2014 Page 7 of 30

Page 8: Power Transmisison Towers Loading Tree

132 kV Angle Tower: Loading tree calculation

Wind direction, q 45.00o

3068

Angle of deviation, a 60.00o

2500

32010

8807

53939

Loading tree

Normal Condition 10056

(forces are in Newton)

8807

53939

10056

8807

53939

10056

3068

24621

17795

8807

53939

Loading tree

Earth wire broken condition 10056

(forces are in Newton)

8807

53939

10056

8807

53939

10056

Revised (m/d/y) 5/11/2014 Page 8 of 30

Page 9: Power Transmisison Towers Loading Tree

132 kV Angle Tower: Loading tree calculation

Wind direction, q 45.00o

3068

Angle of deviation, a 60.00o

2500

32010

28163

24607

Loading tree

Top-left conductor broken condition 10056

(In analysis middle-left and bottom-left

conductor broken condition shall also be 8807

included)

(forces are in Newton)

53939

10056

8807

53939

10056

Revised (m/d/y) 5/11/2014 Page 9 of 30

Page 10: Power Transmisison Towers Loading Tree

Broken wire condition

w e L 2 r 1 3067.63 N

w dE 0.00 N

3067.63 N

w 1 N i 1372.98 N

w c L 2 r 1 8682.73 N

w dC 0.00 N

10055.71 N

T E cos(a /2 ) 24621.11 N

T C cos(a /2 )r 2 27356.19 N

p c l 1 d 1 cosqN i 807.23 N

28163.42 N

T E sin(a /2 ) 14214.99 N

p e sinq L 1 d E cos(a/2)r 1 3580.00 N

17794.99 N

T C sin(a /2 )r 2 15794.09 N

p e sinq L 1 d C cos(a/2)r 1 8005.64 N

p c l 1 d 1 sinqN i 807.21 N

24606.95 N

Revised (m/d/y) 5/11/2014 Page 10 of 30

Page 11: Power Transmisison Towers Loading Tree

8807

53939

10056

8807

53939

10056

8807

53939

10056

8807

53939

10056

8807

53939

10056

8807

53939

10056

Revised (m/d/y) 5/11/2014 Page 11 of 30

Page 12: Power Transmisison Towers Loading Tree

8807

53939

10056

8807

53939

10056

8807

53939

10056

Revised (m/d/y) 5/11/2014 Page 12 of 30

Page 13: Power Transmisison Towers Loading Tree

132 kV Road Crossing: Loading tree calculation

Road Crossing Span, L 365.00 m

365.00 m

Normal Condition (NC) Worst wind and no conductor broken

Broken wire condition (BWC) Worst wind with one conductor and one ew. broken

Angle of deviation, a 3.00 degree

Weight of insulator string, w 1 70.00 kg

Length of insulator string, l 1 2000.00 mm

Dia of insulator string, d 1 200.00 mm

Qty. of Insulator per side of arm, N i 1.00

Dia of conductor, d c 25.10 mm

Weight of conductor, w c 1302.00 kg/km

Working tension in conductor, T C 45126.00 N

Dia of earth wire, d E 9.50 mm

Weight of earth wire, w e 460.00 kg/km

Working tension in earth wire, T E 28430.00 N

Damper weight for conductor, w dC 0.00 kg

Damper weight for earth wire, w dE 0.00 kg

Wind pressure on conductor, p c 1427.00 N/m2

Wind pressure on ew., p e 1686.00 N/m2

Wind direction, q 90.00o

Span reduction factor for BWC, r 1 0.75

Tension red. fact. for BWC for conductor, r 2 0.70

Min. unbal. Long. force per conductor 8000.00 N

Min. unbal. Long. force per earthwire 2500.00 N

Calculations

Wind span, L 1 365.00 m

Weight span, L 2 680.00 m

VERTICAL LOAD

Normal condition Broken wire condition

Earth wire point

Weight of earth wire w e L 2 3067.63 N w e L 2 r 1 2300.72 N

Weight of damper (two dampers) 2w dE 0.00 N w dE 0.00 N

3067.63 N 2300.72 N

At cross arm

Weight of insulator string w 1 N i 686.49 N w 1 N i 686.49 N

Weight of conductor w c L 2 8682.73 N w c L 2 r 1 6512.04 N

Weight of damper (two dampers) 2w dC 0.00 N w dC 0.00 N

9369.22 N 7198.53 N

LONGITUDINAL LOAD

Earthwire point

Unbalanced pull 2500.00 N T E cos(a /2 ) 28420.26 N

At cross arm

Unbalanced pull 8000.00 N T C cos(a /2 )r 2 31577.38 N

Wind force on insulator p c l 1 d 1 cosq 0.00 N p c l 1 d 1 cosq 0.00 N

8000.00 N 31577.38 N

TRANSVERSE LOAD

Earthwire point

Component of working tension 2T E sin(a /2 ) 1488.42 N T E sin(a /2 ) 744.21 N

Wind force on earth wire p e sinq L 1 d E cos(a/2) 5844.20 N p e sinq L 1 d E cos(a/2)r 1 4383.15 N

7332.62 N 5127.36 N

At cross arm

Component of working tension 2T C sin(a /2 ) 2362.52 N T C sin(a /2 )r 2 826.88 N

Wind force on conductor p c sinq L 1 d C cos(a/2) 13068.98 N p e sinq L 1 d C cos(a/2)r 1 9801.74 N

Wind force on insulator string p c l 1 d 1 sinq 570.80 N p c l 1 d 1 sinq 570.80 N

16002.30 N 11199.42 N

Span between RC tower and Pole/Anchor

tower, L A

Revised (m/d/y) 5/11/2014 Page 13 of 30

Page 14: Power Transmisison Towers Loading Tree

132 kV Road Crossing: Loading tree calculation

Wind direction, q 90.00o

3068

Angle of deviation, a 3.00o

2500

7333

8000 8000

16002 16002

Loading tree

Normal Condition 9369 9369

(forces are in Newton)

8000 8000

16002 16002

9369 9369

8000 8000

16002 16002

9369 9369

2301

28420

5127

8000 8000

16002 16002

Loading tree

Earth wire broken condition 9369 9369

(forces are in Newton)

8000 8000

16002 16002

9369 9369

8000 8000

16002 16002

9369 9369

Revised (m/d/y) 5/11/2014 Page 14 of 30

Page 15: Power Transmisison Towers Loading Tree

132 kV Road Crossing: Loading tree calculation

Wind direction, q 90.00o

3068

Angle of deviation, a 3.00o

2500

7333

31577 8000

11199 16002

Loading tree

Top-left conductor broken condition 7199 9369

(In analysis middle-left and bottom-left

conductor broken condition shall also be 8000 8000

included)

(forces are in Newton)

16002 16002

9369 9369

8000 8000

16002 16002

9369 9369

Revised (m/d/y) 5/11/2014 Page 15 of 30

Page 16: Power Transmisison Towers Loading Tree

132 kV Road Crossing: Loading tree calculation

Road Crossing Span, L

Normal Condition (NC)

Broken wire condition (BWC)

Angle of deviation, a

Weight of insulator string, w 1

Length of insulator string, l 1

Dia of insulator string, d 1

Qty. of Insulator per side of arm, N i

Dia of conductor, d c

Weight of conductor, w c

Working tension in conductor, T C

Dia of earth wire, d E

Weight of earth wire, w e

Working tension in earth wire, T E

Damper weight for conductor, w dC

Damper weight for earth wire, w dE

Wind pressure on conductor, p c

Wind pressure on ew., p e

Wind direction, q

Span reduction factor for BWC, r 1

Tension red. fact. for BWC for conductor, r 2

Min. unbal. Long. force per conductor

Min. unbal. Long. force per earthwire

Calculations

Wind span, L 1

Weight span, L 2

VERTICAL LOAD

Earth wire point

Weight of earth wire

Weight of damper (two dampers)

At cross arm

Weight of insulator string

Weight of conductor

Weight of damper (two dampers)

Span between RC tower and Pole/Anchor tower, L A

Page 17: Power Transmisison Towers Loading Tree

LONGITUDINAL LOAD

Earthwire point

Unbalanced pull

At cross arm

Unbalanced pull

Wind force on insulator

TRANSVERSE LOAD

Earthwire point

Component of working tension

Wind force on earth wire

At cross arm

Component of working tension

Wind force on conductor

Wind force on insulator string

Wind direction, q ###

Angle of deviation, a 3.00

###

Loading tree

Normal Condition

(forces are in Newton)

###

###

Page 18: Power Transmisison Towers Loading Tree

###

Loading tree

Earth wire broken condition

(forces are in Newton)

###

###

Wind direction, q ###

Angle of deviation, a 3.00

###

Loading tree

Top-left conductor broken condition

(In analysis middle-left and bottom-left

conductor broken condition shall also be

Page 19: Power Transmisison Towers Loading Tree

included)

(forces are in Newton)

###

###

Page 20: Power Transmisison Towers Loading Tree

365.00 m

365.00 m

Worst wind and no conductor broken

Worst wind with one conductor and one ew. broken

3.00 degree

70.00 kg

2000.00 mm

200.00 mm

1.00

25.10 mm

1302.00 kg/km

45126.00 N

9.50 mm

460.00 kg/km

28430.00 N

0.00 kg

0.00 kg

1427.00 N/m2

1686.00 N/m2

45.00o

0.75

0.70

8000.00 N

2500.00 N

365.00 m

680.00 m

Normal condition Broken wire condition

w e L 2 3067.63 N w e L 2 r 1

2w dE 0.00 N w dE

3067.63 N

w 1 N i 686.49 N w 1 N i

w c L 2 8682.73 N w c L 2 r 1

2w dC 0.00 N w dC

Page 21: Power Transmisison Towers Loading Tree

9369.22 N

2500.00 N T E cos(a /2 )

8000.00 N T C cos(a /2 )r 2

p c l 1 d 1 cosq 403.62 N p c l 1 d 1 cosq

8403.62 N

2T E sin(a /2 ) 1488.42 N T E sin(a /2 )

p e sinq L 1 d E cos(a/2) 4132.38 N p e sinq L 1 d E cos(a/2)r 1

5620.80 N

2T C sin(a /2 ) 2362.52 N T C sin(a /2 )r 2

p c sinq L 1 d C cos(a/2) 9240.95 N p e sinq L 1 d C cos(a/2)r 1

p c l 1 d 1 sinq 403.61 N p c l 1 d 1 sinq

12007.08 N

o3068

o2500

5621

8404

9369 9369

8404

9369 9369

8404

9369 9369

Page 22: Power Transmisison Towers Loading Tree

2301

28420

3843

8404

9369 9369

8404

9369 9369

8404

9369 9369

o3068

o2500

5621

31981

7199 9369

8404

Page 23: Power Transmisison Towers Loading Tree

9369 9369

8404

9369 9369

Page 24: Power Transmisison Towers Loading Tree

Broken wire condition

2300.72 N

0.00 N

2300.72 N

686.49 N

6512.04 N

0.00 N

Page 25: Power Transmisison Towers Loading Tree

7198.53 N

28420.26 N

31577.38 N

403.62 N

31980.99 N

744.21 N

3099.28 N

3843.49 N

826.88 N

6930.71 N

403.61 N

8161.20 N

8404

12007

8404

12007

8404

12007

Page 26: Power Transmisison Towers Loading Tree

8404

12007

8404

12007

8404

12007

8404

12007

8404

Page 27: Power Transmisison Towers Loading Tree

12007

8404

12007

Page 28: Power Transmisison Towers Loading Tree

132 kV Anchor Tower: Loading tree calculation

Basic Span, L 330.00 m

330.00 m

Normal Condition (NC) Worst wind and no conductor broken

Broken wire condition (BWC) Worst wind with two conductor and one ew. broken

Angle of deviation, a 45.00 degree

Weight of insulator string, w 1 70.00 kg

Length of insulator string, l 1 2000.00 mm

Dia of insulator string, d 1 200.00 mm

Qty. of Insulator per side of arm, N i 3.00

Dia of conductor, d c 25.10 mm

Weight of conductor, w c 1302.00 kg/km

Working tension in conductor, T C 45126.00 N

Dia of earth wire, d E 9.50 mm

Weight of earth wire, w e 460.00 kg/km

Working tension in earth wire, T E 28430.00 N

Damper weight for conductor, w dC 0.00 kg

Damper weight for earth wire, w dE 0.00 kg

Wind pressure on conductor, p c 1427.00 N/m2

Wind pressure on ew., p e 1686.00 N/m2

Wind direction, q 45.00o

Span reduction factor for BWC, r 1 1.00

Tension red. fact. for BWC for conductor, r 2 0.70

Min. unbal. Long. force per conductor 8000.00 N

Min. unbal. Long. force per earthwire 2500.00 N

Calculations

Wind span, L 1 365.00 m

Weight span, L 2 680.00 m

VERTICAL LOAD

Normal condition Broken wire condition

Earth wire point

Weight of earth wire w e L 2 3067.63 N w e L 2 r 1 3067.63 N

Weight of damper (two dampers) 2w dE 0.00 N w dE 0.00 N

3067.63 N 3067.63 N

At cross arm

Weight of insulator string w 1 N i 2059.47 N w 1 N i 2059.47 N

Weight of conductor w c L 2 8682.73 N w c L 2 r 1 8682.73 N

Weight of damper (two dampers) 2w dC 0.00 N w dC 0.00 N

10742.20 N 10742.20 N

LONGITUDINAL LOAD

Earthwire point

Unbalanced pull 2500.00 N T E cos(a /2 ) 26265.90 N

At cross arm

Unbalanced pull 8000.00 N T C cos(a /2 )r 2 29183.70 N

Wind force on insulator p c l 1 d 1 cosqN i 1210.85 N p c l 1 d 1 cosqN i 1210.85 N

9210.85 N 30394.55 N

TRANSVERSE LOAD

Earthwire point

Component of working tension 2T E sin(a /2 ) 21759.36 N T E sin(a /2 ) 10879.68 N

Wind force on earth wire p e sinq L 1 d E cos(a/2) 3819.15 N p e sinq L 1 d E cos(a/2)r 1 3819.15 N

25578.51 N 14698.83 N

At cross arm

Component of working tension 2T C sin(a /2 ) 34537.92 N T C sin(a /2 )r 2 12088.27 N

Wind force on conductor p c sinq L 1 d C cos(a/2) 8540.45 N p e sinq L 1 d C cos(a/2)r 1 8540.45 N

Wind force on insulator string p c l 1 d 1 sinqN i 1210.82 N p c l 1 d 1 sinqN i 1210.82 N

44289.19 N 21839.55 N

Span between Anchor tower and Pole/Angle

tower, L A

Revised (m/d/y) 5/11/2014 Page 28 of 30

Page 29: Power Transmisison Towers Loading Tree

132 kV Anchor Tower: Loading tree calculation

Wind direction, q 45.00o

3068

Angle of deviation, a 45.00o

2500

25579

9211 9211

44289 44289

Loading tree

Normal Condition 10742 10742

(forces are in Newton)

9211 9211

44289 44289

10742 10742

9211 9211

44289 44289

10742 10742

3068

26266

14699

9211 9211

44289 44289

Loading tree

Earth wire broken condition 10742 10742

(forces are in Newton)

9211 9211

44289 44289

10742 10742

9211 9211

44289 44289

10742 10742

Revised (m/d/y) 5/11/2014 Page 29 of 30

Page 30: Power Transmisison Towers Loading Tree

132 kV Anchor Tower: Loading tree calculation

Wind direction, q 45.00o

3068

Angle of deviation, a 45.00o

2500

25579

30395 9211

21840 44289

Loading tree

Top-left conductor broken condition 10742 10742

(In analysis middle-left and bottom-left

conductor broken condition shall also be 9211 9211

included)

(forces are in Newton)

44289 44289

10742 10742

9211 9211

44289 44289

10742 10742

Revised (m/d/y) 5/11/2014 Page 30 of 30