PowerGard™Series C 18-Pulse Enclosed Drive ControllersCombining adjustable speed drive and power quality solutions
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
�
Combining adjustable speed drive and power quality solutions
For municipal and industrial pumping applications, the Square D® brand PowerGard™ Series C 18-Pulse enclosed drive controller features the new Telemecanique® brand Altivar® 61 or 71 adjustable frequency drives/power converters. Schneider Electric’s experience and expertise in power distribution and power quality measurement are combined with solid state motor control. The result: a robust, packaged, adjustable speed drive with a clean power solution.
PowerGard 18-Pulse drives are ideal for installations specifying “clean power” low harmonic content in compliance with IEEE 519 guidelines for harmonic mitigation. PowerGard 18-Pulse drives are UL 508C listed and are available in Type 1 general purpose or with fan filter options. PowerGard 18-Pulse drives are low voltage products available in the following ratings:
Constant torque (heavy duty ratings – 150% current limit)n Altivar 71 power convertern 40 HP to 450 HP, 460 V
Variable torque (normal duty ratings – 110% current limit)n Altivar 61 power convertern 50 HP to 500 HP, 460 V Technology makes a difference
Schneider Electric uses a patented 18-Pulse technology designed to meet IEEE 519 guidelines for harmonic control in electrical power systems. Using this technology enables PowerGard 18-Pulse drives to achieve in excess of 95% cancellation of characteristic harmonic currents. Other multi-pulse technologies vary greatly in design and the effectivity of their cancellation techniques. Many multi-pulse drives do not provide balanced cancellation of harmonic currents, which can result in only marginal harmonic mitigation.
One of many harmonic mitigation strategies
With extensive power management and motor control experience, Schneider Electric provides an array of harmonic solutions using a true cost vs. benefit approach to harmonic mitigation. This proactive approach helps users tailor the correct solution ranging from “C-less” technology to active harmonic filtering for an entire system. The result is a cost-effective balance of:
n Input (RMS) current reductionn Branch circuit conductor sizingn Equipment sizen Installation costn IEEE 519 compliance
PowerGard™ Series C 18-Pulse Enclosed Drive Controllers
18-Pulse enclosed drive controller
18-Pulse assembly (bottom compartment)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
�
The voltage and current waveforms, including the harmonic spectrum shown right, is an actual field measure-ment taken at the input terminals of a PowerGard 18-Pulse drive rated 400 HP @ 460 V. The harmonic profile is based on power distribution with 37,000 A RMS available.
RMS Voltage = 473.0 Fundamental = 60.0 HzRMS Current = 437.3 True Power = 115333.56
Voltage THD = 2.17% K-Factor = 1.26Current THD = 3.69% True P.F. = 0.97
Vab RMS Voltage Ia RMS Current Vab RMS Voltage Ia RMS Current
Hrm Mag Phase Mag Phase Hrm Mag Phase Mag Phase
1 473.10 0.0 436.849 68.1 2 0.60 0.0 2.434 134.8 3 1.06 -171.0 7.934 -93.3 4 0.09 0.0 0.410 0.0 5 5.62 75.3 8.007 70.5 6 0.44 0.0 0.369 0.0 7 1.34 70.3 2.421 -163.4 8 0.83 0.0 0.675 0.0 9 0.58 0.0 1.294 83.9 10 1.69 159.8 1.071 84.211 1.71 -110.3 2.349 66.3 12 0.57 0.0 1.166 12.413 1.23 157.9 3.395 -88.4 14 0.24 0.0 0.648 0.015 0.22 0.0 0.606 0.0 16 0.48 0.0 0.674 0.017 3.93 11.5 6.401 162.9 18 0.19 0.0 0.408 0.019 4.23 -75.3 5.792 7.8 20 0.42 0.0 0.243 0.021 0.35 0.0 1.039 127.3 22 0.20 0.0 0.960 -96.623 1.51 -151.7 1.825 9.0 24 0.79 0.0 0.417 0.025 1.63 170.4 1.346 -163.0 26 0.87 0.0 0.671 0.027 0.66 0.0 0.197 0.0 28 1.17 -112.0 0.801 0.029 0.80 0.0 0.353 0.0 30 0.47 0.0 0.852 0.031 1.45 -137.7 1.215 167.4 32 0.22 0.0 0.584 0.033 0.47 0.0 0.201 0.0 34 0.35 0.0 0.612 0.035 0.96 92.7 1.573 91.9 36 0.33 0.0 0.540 0.037 1.45 31.1 0.834 0.0 38 0.88 0.0 0.358 0.039 0.47 0.0 0.791 0.0 40 0.71 0.0 0.224 0.041 0.36 0.0 1.398 -134.4 42 0.27 0.0 0.222 0.043 1.29 -65.5 0.747 0.0 44 1.06 105.7 0.338 0.045 0.18 0.0 0.285 0.0 46 0.91 0.0 0.505 0.047 0.64 0.0 0.159 0.0 48 1.00 -112.5 0.393 0.049 1.19 -75.5 0.756 0.0 50 0.37 0.0 0.307 0.051 0.32 0.0 0.399 0.0 52 0.74 0.0 0.406 0.053 0.48 0.0 0.280 0.0 54 0.60 0.0 0.554 0.055 0.78 0.0 0.800 0.0 56 0.55 0.0 0.581 0.057 0.45 0.0 0.349 0.0 58 0.51 0.0 0.623 0.059 0.17 0.0 0.268 0.0 60 0.70 0.0 0.305 0.061 1.07 -37.3 0.392 0.0 62 0.19 0.0 0.364 0.063 0.55 0.0 0.197 0.0 64 0.42 0.0 0.038 0.065 0.19 0.0 0.152 0.0 66 0.00 0.0 0.000 0.0
-800
-640
-480
-320
-160
0
160
480
320
640
800
-800
-640
-480
-320
-160
0
160
480
320
640
800
0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0
Time (msecs)
PowerGard Series C - 400 HP @ 460 V
Vol
tage
(vo
lts)
Cur
rent
(am
ps)
RMS Value:Crest Factor
Current
Voltage
Ia473.31.5
Vab473.01.5
In0.00.0
True Power:True P.F.:
Phase A115333.61000.00
Power quality counts when you have to measure it
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
�
High and optimized power converter performance
The Altivar 61 and 71 power converter offers evolutionary performance to meet even the most demanding applications. The power converter is optimized for motor control applications and is reliable, expandable and easy to control.
Custom performancen Clean power (low harmonic content) for high-horsepower ratingsn Customized for specific applicationsn Advanced technology platform increases reliability and uptimen Dedicated 18-Pulse transformer/reactor and bridge rectifiersn Altivar 61 and 71 power converters for peak performance
Ease of usen Intuitive door-mounted graphic display screen in plain text n Programming is clear, precise, and illustrated; diagnostics
are intuitive n Operators mounted on enclosure doors are pre-programmed to
save set-up time and expense
Fully protected n Patented 18-Pulse converter technology with premium
harmonic mitigationn 100,000 A SCCR coordinated, UL 508 listed and NEC article
409 ratedn Meets 2003 IBC and ASCE 7 standards for seismic
qualification (optional)
Expandable network capabilitiesn For building automation, add Lonworks, BACNet, MetaSYS N2 or
APOGEE P1 communications cardsn For industrial applications, add DeviceNet, Ethernet TCP/IP,
FIPIO®, Interbus-S, Modbus® Plus, Modbus Uni-Telway or Profibus DP communication cards
What Can the PowerGard 18-Pulse Enclosed Drive Controller Do For You?
Altivar 61/71 power converter
Expandable network cards
Intuitive graphic display terminal
Seismic qualification for new generation of building codes1st Drive manufacturer to meet this criteria!
All PowerGard Series C 18-Pulse enclosed drive controllers meet IBC and ASCE 7 seismic qualification requirements in accordance with the ICC ES AC156 shaker table testing protocol. Many states and jurisdictions are beginning enforcement of the seismic guidelines for installed equipment contained in the IBC. The PowerGard Series C 18-Pulse enclosed drive controllers were subjected to actual shaker table tests, not just theoretical calculations for seismic ratings or obsolete requirements of the UBC. This enclosed drive controller meets the structural integrity requirements when installed to our published guidelines, and can be specified for use in applications that require an Ip = 1.5, which means operational status can be restored after a seismic event.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
�
A Platform Engineered to Your Specifications
Precharge resistors
Precharge contactor
User-specified 22 mm dedicated door mounted operators
Altivar 61 or 71 power converter (application specific)
Optimized thermal management with sequenced inlet fans
Series line reactor for improved resistance to voltage imbalance
Integrated phase shifting, copper-wound, 18-Pulse fork transformer (patent design)
ANSI #49 gray corrosion-resistant, two-coat epoxy paint enclosure
125 HP unit shown
Construction methodologyn Assembled in the USAn 100,000 A symmetrical SCCRn ANSI #49 powder-coat steel enclosuresn Seismic qualification option
Top conduit entry access
Flange disconnect switch
100,000 A SCCR circuit breaker rating without fuses
Flange-mounted disconnect handle with three-point door latch interlock
Customer-specified control logic
Dedicated 18-Pulse bridge rectifier module with thermal protection
Bottom conduit access
Switchboard-style enclosures (24" depth)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
�
Specifications for Drive Controllers
Input voltage 460 V ±10%
Displacement power factor 98% through speed range
Input frequency 50/60 Hz ± 5%
Output voltageThree-phase output Maximum voltage equal to input voltage
Galvanic isolation Galvanic isolation between power and control (inputs, outputs, and power supplies)
Frequency range of power converter 0.1 Hz to 500 Hz (factory setting of 60 Hz)
Torque/overtorqueVT: 110% of nominal motor torque for 60 s CT: 150% of nominal motor torque for 60 s
Current (transient)VT: 110% of controller rated current for 60 s CT: 150% of controller rated current for 60 s
Switching frequency
Selectable from 0.5 kHz to 16 kHz. [1] Factory setting: CT: 2 kHz for 40 HP–450 HP @460 V VT: 2 kHz for 50 HP–500 HP @460 V The drive reduces the switching frequency automatically in the event of excessive heat sink temperature.
Speed reference
AI1: 0 to +10 V, Impedance = 30 kW. Can be used for speed potentiometer, 1 to 10 kW AI2: Factory setting: 4 mA to 20 mA. Impedance = 242 W (reassignable, X–Y range with graphic display terminal) Factory modification J10 allows 0–10 Vdc reference signal to AI2, Z = 30 kW
Frequency resolution in analog reference 0.1 for 100 Hz (11 bits)
Speed regulationV/f control: equal to the motor’s rated slip. SFVC: 10% of the motor’s rate slip from 20% to 100% of nominal motor torque
Efficiency 95% at full load typical
Reference sample time 2 ms ±0.5 ms
Acceleration and deceleration ramps 0.1 to 999.9 s (definition in 0.1 s increments)
Drive controller protection• Thermal protection of power converter • Phase loss of AC mains • Circuit breaker protected
Motor protection• Class 10 electronic overload protection (power converter) • Class 20 bypass overload protection (with various factory engineered bypass circuits)
Graphic display terminalSelf diagnostics with fault messages in three languages; also refer to the programming manual supplied on CD with the power converter
Temperature
Storage for all enclosures: -13 to +149 °F (-25 to +65 °C). Operation: +14 to +104 °F (-10 to 40 °C). For 40 HP to 75 HP, CT and 50 HP to 100 HP, VT drives operating between 104 and 122 °F (40 and 50 °C), derate the current 2% per °C above 40 °C. For 100 HP to 450 HP, CT and 125 HP to 500 HP, VT drives operating between 104 and 122 °F (40 and 50 °C), derate the current 3.3% per °C above 40 °C
Humidity 95% with no condensation or dripping water, conforming to IEC 60068-2-3
Altitude3,300 ft (1000 m) maximum without derating; derating of the current by 1% for each additional 330 ft (100 m)
Enclosure NEMA Type 1 or Type 1 with fan filters
Pollution degree Type 1, 1B: Pollution degree 2 per NEMA ICS-1 Annex A and IEC 60664-1
Operational test vibrationConforms to IEC 60721-3-3-3M3 amplitude • 1.5 mm peak to peak from 3 Hz to 13 Hz • 1 g from 13 Hz to 200 Hz
Transit test to shockConforms to National Safe Transit Association and International Safe Transit Association test for packages
Operational shock 15 g, 11 ms
Seismic qualification2003 IBC, NFPA 5000 and ASCE 7 (optional) ICC ES AC156 acceptance criteria test protocol with an importance factor of 1.5
Codes and standards
UL listed per UL 508C under category NMMS Conforms to applicable NEMA ICS, NFPA and IEC standards Manufactured under ISO 9001 standards Factory modification G10 provides Canadian cUL certification
1. On 40 HP to 75 HP CT and 50 HP to 100 HP VT controllers, above 4 kHz CT/8 kHz VT, select the next largest size drive controller. If the duty cycle does not exceed 60% (36 s maximum for a 60 s cycle), this is not necessary.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
�
Combination Device 8839 = Circuit breaker disconnect
Design CPD = PowerGard 18-Pulse controller
Horsepower Rating N = 40 HP W = 200 HP P = 50 HP X = 250 HP Q = 60 HP Y = 300 HP R = 75 HP Z = 350 HP S = 100 HP 4 = 400 HP T = 125 HP 5 = 450 HP U = 150 HP 6 = 500 HP
Enclosure Environmental Rating G = Type 1 general purpose B = Type 1 with fan filters
Series Designation C = Altivar 61/71 Power converter platform
Modifications (120+ options are available) A07 = Hand-Off-Auto selector switch with manual speed potentiometer
Power Circuit Type R = Barriered bypass – RVAT S = Barriered bypass – soft start T = Isolation and transfer W = Combination device (drive only) Y = Integrated bypass (IEC) Z = Barriered bypass – full voltage
Application Type C = Constant torque (150% current limit) V = Variable torque (110% current limit)
Voltage Code 4 = 460/480 V, 60 Hz
Class 8839 Type CPD T G 4 V W Forms A07, etc. Series C
Catalog Number Explanation
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Typical weights and estimated heat loss
Typical dimensions
Power circuit description: R – Barriered bypass with autotransformer reduced voltage starter S – Barriered bypass with soft start T – Isolation and transfer (separate starter) W – Combination: Drive with disconnect means only Y – Integrated bypass: Drive with full voltage starter in same enclosure compartment Z – Barriered bypass: Drive with full voltage starter in separate enclosure compartment
HP @ 480 V
PowerGard Series C Enclosure Width Dimensions
Combination Drive Only
W
Integrated Bypass Full Voltage
Y
Barriered Bypass Full Voltage/
Separate Starter Z or T
Barriered Bypass Soft Start
S
Barriered Bypass RVAT
R
Total Extender Total Extender Total Extender Total Extender Total
50 to 75 36" - 36" 20" 56" 20" 56" 42" 78"
100 36" - 36" 20" 56" 36" 72" 42" 78"
125 36" 20" 56" 20" 56" 36" 72" 42" 78"
150 42" 20" 62" 20" 62" 36" 78" 48" 90"
200 42" 20" 62" 20" 62" 36" 78" 48" 90"
250 42" 20" 62" 20" 62" 42" 84" 54" 90"
300 48" 25" 73" 25" 73" 42" 90" 54" 102"
350 48" 25" 73" 25" 73" 42" 90" 54" 102"
400 48" 25" 73" 25" 73" 42" 90" 54" 102"
450 48" or 54" 36" 84" 36" 84" 48" 96" 54" 102"
500 48" or 54" 36" 84" 36" 84" 48" 96" 54" 102"
PowerGard Series C – Power Circuit W
HP @ CT ratingWeight
lbs.
Estimated Heat LossHP @ VT rating
Weight lbs.
Estimated Heat Loss
Watts Loss BTU/Hour Watts Loss BTU/Hour
40 1603 2478 8457 - - - -
50 1603 2674 9126 50 1603 2674 9126
60 1603 2838 9686 60 1603 2838 9686
75 1603 3027 10331 75 1603 3027 10331
100 1703 4776 16301 100 1703 3756 12819
125 2070 6333 21615 125 1703 4843 16529
150 2070 6637 22652 150 2070 6637 22652
200 2086 7074 24144 200 2086 7074 24144
250 2682 9582 32703 250 2086 9582 32703
300 2682 11216 38280 300 1682 11216 38280
350 2682 11684 39878 350 2682 11684 39878
400 2682 12894 44007 400 2682 12894 44007
450 3148 13793 47076 450 3148 13793 47076
- - - - 500 3148 14691 50140
© 2
007
Sch
neid
er E
lect
ric.
All
right
s re
serv
ed.
11-06 dc Order Number 8839BR0502R11/06
Schneider Electric - North American Operating Division
1415 S. Roselle Road Palatine, IL 60067 Tel: 847-397-2600 Fax: 847-925-7500 www.us.squared.com
Product Information
All enclosures are configured in 94.65" height and 24.5" depth standard switchboard style construction