of 20
7/30/2019 Practical Tips Danffos
1/20
Danoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 125
Practicaltips
Fitters notes Practical tips
Page
Installation requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
The installation process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
This chapter is devided into two sections:
7/30/2019 Practical Tips Danffos
2/20
7/30/2019 Practical Tips Danffos
3/20
Fitters notes Practical tips - installation requirements
Danoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 127
Practicaltips
Contents Page
Installation requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Tubing must be kept clean . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Particularly damaging impurities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Problems caused by moisture in the system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Problems caused by atmospheric air. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Problems caused by oil and rerigerant breakdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Problems caused by other impurities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Component and material requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Impurities and moisture. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Copper tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Rerigerant requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
C o m p r e s s o r o i l r e q u i r e m e n t s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3 2
7/30/2019 Practical Tips Danffos
4/20
128 DKRCC.PF.000.G1.02 / 520H1459 Danoss A/S (AC-DSL/MWA), 10 - 2006
Notes
7/30/2019 Practical Tips Danffos
5/20
Fitters notes Practical tips - installation requirements
Danoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 129
Practicaltips
More and more commercial rerigeration systemsand air conditioning plants o a similar size arebuilt up around hermetic and semihermeticcompressors. These compressors, as comparedto the open type, are normally more vulnerable
to impurities in the rerigerant system and toincorrect operating conditions.
Thereore, in modern rerigeration systems, thereare special demands on the quality o installationwork and commissioning.
Ac0_0003
Ac0_0010
A well-dimensioned, correctly installed andcorrectly commissioned rerigerant system isundamental to a reliable rerigeration systemwith a long operating lie.An absolute requirement on the rerigerant
system is that it shall remain completely ree ooreign bodies (impurities).Installation work must thereore be perormedwith a high degree o cleanliness. This appliesespecially to systems containing the newrerigerants.
Ac0_0037
Moisture
Atmospheric air
Soldering ux
Rust, copper oxide, scaleMetal swar
Unstable oils
Certain uorinated solutions (e.g. R11or carbon tetrachloride)
Dirt or dust o any description.
Installation requirements
Tubing must be kept clean
Particularly damagingimpurities
Water separation and ice ormation(blockage) in the expansion valve
Acid ormation
Ageing and breakdown o the oilCorrosion
Copper precipitation (dissolved copperrom tubing deposited on bright steelparts in the compressor)
Damage to the insulating lacquer onmotor windings.
Ac0_0027
Problems caused by moisture inthe system
7/30/2019 Practical Tips Danffos
6/20
Fitters notes Practical tips - installation requirements
130 DKRCC.PF.000.G1.02 / 520H1459 Danoss A/S (AC-DSL/MWA), 10 - 2006
Ac0_0038
Aeration
Chemical reaction between rerigerantand oil
Increased condensing pressure.
Ac0_0046
Formation o organic and inorganic acids
Corrosion
Poor lubrication
Abnormal wearOil discolouration (darkening)
Sludge ormation
Leaking discharge valves because ooil carbon deposits
Increased discharge gas temperature
Compressor damage
Motor burnout
The other impurities mentioned can cause:
Accelerated chemical processes(breakdown)
Mechanical or electrical aults
High temperature accelerates the breakdownprocesses, thereore abnormally high condensingtemperatures and, especially, abnormally highdischarge pipe temperatures must be avoided.
For the reasons just mentioned, a number orequirements must be met. Some o these aredescribed in the next chapter.
Ac0_0047
Problems caused byatmospheric air
Problems caused by oiland rerigerant breakdown
Problems caused by otherimpurities
Ac0_0048
Compressors or rerigeration and heat pumpsystems are put through a comprehensive clea-
ning process by the manuacturer so that, prac-tically speaking, all traces o moisture and otherimpurities are removed.
All other components in the system should be othe same standard.
All components must ull cleanliness require-ments. In cases o doubt, components should bechecked.
Component andmaterial requirements
Components
7/30/2019 Practical Tips Danffos
7/20
Fitters notes Practical tips - installation requirements
Danoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 131
Practicaltips
Ac0_0001
Impurities that might appear i componentmanuacturers are less thorough than theyshould be:
Rust and scale (loose or embedded)
Old oil
Flux
Metal swar
Moisture
Ac0_0005
Moisture in smaller quantities in componentscan be removed by simultaneous heating andblowing through with dry nitrogen (N2).
It is almost pointless to try removing otherimpurities. Components containing such impu-
rities should not be used in systems withhalogenous rerigerants.
Ac0_0049
Special copper tubing must be used or reri-gerant systems, tubing that is completely cleanand dry. In addition, the ends o tubes must behermetically sealed.
Tubing other than the type just described mustnot be used in rerigerant systems, unless it ullsthe same cleanliness requirements.
All components must remain tightly sealed untilthe moment they are installed in the system.
Ac0_0006
Rerigerants should only be purchased romaccredited distributors.Rerigerants or hermetic systems must notcontain more than:
10 ppm = 0.001% water
100 ppm = 0.01% high-boiling rerigerant
0 ppm = 0% acid
15000 ppm = 1.5% non-condensablegases
Care must thereore be exercised when usingregenerated rerigerant.
Impurities and moisture
Copper tubing
Rerigerant requirements
7/30/2019 Practical Tips Danffos
8/20
Fitters notes Practical tips - installation requirements
132 DKRCC.PF.000.G1.02 / 520H1459 Danoss A/S (AC-DSL/MWA), 10 - 2006
Ac0_0007
Compressor oil must be approved by thecompressor manuacturer and must not containmore than 25 ppm (0.0025%) water and 0% acid.
Compressor oil requirements
7/30/2019 Practical Tips Danffos
9/20
Danoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 133
Practicaltips
Fitters notes Practical Tips - The installation process
Contents Page
I n s t a l l a t i o n p r o c e s s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3 5
Planning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
L o c a t i o n o m a i n c o m p o n e n t s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 3 5
Installation o rerigeration system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Piping installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Location o other components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Compressors in parallel installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Important installation processes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Component storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Pipe cutting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Pipe cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Silver soldering (brazing) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Phosphor solder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Use o inert gas when soldering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139Economic soldering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Be careul with the temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Flare connections (copper piping) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Evacuation, ushing and charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
N e c e s s a r y e q u i p m e n t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 4 0
Vacuum pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Vacuum hoses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
First evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
System vacuum test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Flushing and provisional leak testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Second evacuation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Provisional setting o saety equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Checking the electrics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Rerigerant charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Condensing pressure too high . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Setting and testing saety equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Setting and testing regulation equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Setting the high-pressure control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Setting the low-pressure control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
7/30/2019 Practical Tips Danffos
10/20
134 DKRCC.PF.000.G1.02 / 520H1459 Danoss A/S (AC-DSL/MWA), 10 - 2006
Notes
7/30/2019 Practical Tips Danffos
11/20
Danoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 135
Practicaltips
Fitters notes Practical Tips - The installation process
Process:
Planning o component location andtubing layout
Setting up o main components
Piping and component installation
Evacuation
Flushing
Pressure testing
Leak testing
Charging
Setting saety equipment
Testing saety equipment
Setting controls
Testing the complete system andreadjusting controls, etc.
Ac0_0061
Ac0_0008
Installation must be planned so that
Damage to building sections, includingcold room insulation, is minimal.
Components are located unctionallycorrectly (e.g. adequate air ow tocompressor, condenser, evaporator).
Pipe runs are as short as easibly possible.
Installation process
Planning
Main components (compressor, condenser,evaporator, etc.) must be mounted securely inposition, using the accompanying brackets and inaccordance with the manuacturers instructions.
The compressor must always be secured toa horizontal base. I vibration dampers aresupplied, they must also be tted.
Ac0_0009
Location o main components
Ac0_0004
Installation must be as rapid as possible so thatsignicant quantities o moisture, air or otherimpurities have little chance o collecting in thesystem.
Compressors and lter driers should thereore beinstalled last, immediately beore evacuating andcharging the system.
All openings into the rerigerant system - withabsolutely no exception - must be completely
sealed against air and water vapour or theduration o any pauses that might occur ininstallation work.
Installation o rerigerationsystem
7/30/2019 Practical Tips Danffos
12/20
136 DKRCC.PF.000.G1.02 / 520H1459 Danoss A/S (AC-DSL/MWA), 10 - 2006
Fitters notes Practical Tips - The installation process
Ac0_0002
As ar as possible, piping must be horizontal orvertical. The exceptions are:
Suction lines, which can be given a slight alltowards the compressor.
Discharge lines, which can have a slight all
away rom the compressor.
Pipe xing brackets, clips, etc. must be pitchedto suit the pipe diameter and load rom compo-nents mounted in the lines.
I vibration dampers are tted to the compressor,then suitable vibration eliminators should betted to suction and discharge piping.
Oil locks must be mounted in vertical suctionlines at a pitch o 1.5 to 5 m depending onrunning time per cycle. In systems withlarge load variations it can be necessary to
introduce double risers.Suction lines must also be installed to takeaccount o oil return to the compressor.
In systems with varying loads, the demandsare particularly critical at low loads.
Ac0_0011
All components should be installed so that theyare easily accessible or service and possiblerepair.
Controls and saety equipment must be locatedso that testing and adjustment can easily beperormed using ordinary tools.
Ac0_0012
Piping installation
Location o other components
7/30/2019 Practical Tips Danffos
13/20
Danoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 137
Practicaltips
Fitters notes Practical Tips - The installation process
Ac0_0036
Compressors in parallel must be installed withoil equalization between compressor crankcases,otherwise whichever compressor(s) run mostwill steal oil rom the other compressor(s). Oilequalization can be introduced by installing an
equalizing tube between oil sumps. In systemswith one equalizing tube, the tube must beinstalled between compressor oil sumps andmust be o such a diameter that both oil andrerigerant vapour are able to ow through itunhindered.
With two equalizing tubes (fg. 1)One tube must be installed between compressoroil sumps, the other between compressor vapourchambers (crankcases). When installing oilequalization in either o the orms described, thecompressors must be set up in exactly the samehorizontal plane.
Oil level controls (fg. 2)Oil equalization is also possible using oil levelregulators.I these are used, the compressors can beinstalled at dierent levels. However, levelcontrols are much more expensive thanequalizing pipes.
The ollowing components are necessary with oillevel regulation:
Oil separator (1)
Pressure equalizing valve (2)
Oil reservoir (3)
Oil lter (4)
Oil level regulator (5)
Remember that each compressor must beprotected with a high-pressure control, e.g. KP7.
Compressors in parallelinstallation
Ac0_0013
All components must have a temperature notlower than that o their surroundings - beorethey are opened. This prevents condensation inthe components.
For example, components must not be installedimmediately ater they have been brought rom acold service van into a warm room.
The processes that might give rise tocontamination o rerigerant systemsare:
Component storage
Pipe cutting
Cleaning pipe ends
SolderingFlare connections
Important installation processes
Component storage
7/30/2019 Practical Tips Danffos
14/20
138 DKRCC.PF.000.G1.02 / 520H1459 Danoss A/S (AC-DSL/MWA), 10 - 2006
Fitters notes Practical Tips - The installation process
Ac0_0014
Tubing must be cut with a pipe cutter or be sawn.Never use any kind o lubricant/coolant.
Remove internal and external burrs with a specialdeburring tool.
Avoid copper swar entering the pipe.Use calibration tools to ensure the correctdiameter and roundness.
Blow through the pipe using a blast o drycompressed air or dry nitrogen.
Never use ordinary compressed air; it containstoo much moisture. Never blow through pipingby mouth.
Piping which has been prepared or later usemust be laid ready, with sealed ends, togetherwith the other components.
Ac0_0015
Ac0_0016
Silver solder consists o 30% silver, copper, zincand tin. The melting range is just over 655C toabout 755C.
Silver solder will bind only with clean, non-oxidized metal suraces.
Clean the pipe ends with a special brush andapply ux at once, immediately beore soldering.
Silver soldering ux must be suspended in spirit,never water.
Ac0_0017
Smear a thin layer o ux around the solderingpoint ater the parts have been joined.
Silver solder can then be used to permanently
join dierent materials, e.g. brass/copper andiron/copper.
Pipe cutting
Pipe cleaning
Silver soldering (brazing)
7/30/2019 Practical Tips Danffos
15/20
Danoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 139
Practicaltips
Fitters notes Practical Tips - The installation process
Phosphor solder consists o 2-15% silver withcopper and phosphor. The melting range is about640C to 740C.
Flux must not be used when making phosphorsolder connections.
Phosphor solder can only be used to join copperto copper.
Ac0_0018
Ac0_0019
At the high temperatures used in soldering,oxidation products (scale) orm immediately ithe pipe comes into contact with atmospheric airwhile soldering is taking place.
An inert gas must thereore be blown through
the system during soldering. Send a slight ow odry nitrogen or another kind o inert gas throughthe tubing.
Do not begin soldering until there is no more airin the component(s) concerned.
Start the operation with a strong ow o inertgas.
Closely observe that no air ow goes into thepipe with inert gas ow.
Reduce the ow to a minimum when soldering isstarted.
Maintain this slight ow o shielding gas duringthe whole soldering process.
Soldering must be perormed with oxygen andgas, with a slight oxygen decit and a relativelylarge burner jet.
The solder must not be applied until the meltingtemperature is reached on the parts beingconnected.
Never use more solder than necessary, otherwisethere is a risk o blocking the pipe partially orcompletely.
Solder quickly so that the oxygen absorptionproperty o the ux is not impaired, i.e. or nolonger than about 15 seconds.
Ac0_0020
Phosphor solder
Use o inert gas when soldering
Economic soldering
7/30/2019 Practical Tips Danffos
16/20
140 DKRCC.PF.000.G1.02 / 520H1459 Danoss A/S (AC-DSL/MWA), 10 - 2006
Fitters notes Practical Tips - The installation process
Ac0_0021
The temperature must not be higher thannecessary.
Thereore draw the ame back slowly when themelting temperature is reached.
External ux residue must be removed bybrushing with hot water.
Alloys based on tin or lead are not recommendedas solders or rerigerant systems.
Ac0_0022
Use only approved rerigeration copper piping.
Cut ends at right angles to the piping.
Remove all internal and external burrs.
Make the are the right size, neither too small nortoo large.
Do not compress the are so severely that itbecomes hard.
Leave nal tightening up until actual installation.
Be careul with the temperature
Flare connections(copper piping)
Ac0_0023
Vacuum pump
Vacuum gauge
Charging bottle (or service cylindercontaining rerigerant)(Vacuum pump, vacuum gauge andcharging bottle can be obtainedassembled as an evacuation andcharging board.)
Charging hoses
Leak detector
Remove moisture, atmospheric air and inert gasrom the system when evacuating.
Steps to ollow:
On completing installation work, the next stepsare:
Evacuation and rerigerant charging
Leak testing
Starting up and adjustment.
Faults, which occur ater the system has beenstarted, can necessitate:
Repair o the system.
Evacuation, fushing and
charging
Necessary equipment
7/30/2019 Practical Tips Danffos
17/20
Danoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 141
Practicaltips
Fitters notes Practical Tips - The installation process
Ac0_0024
The vacuum pump should be capable o quicklybringing the system pressure down to about 0.05mbar.
Pump capacity, e.g. 20 l/minute. Eectiveevacuation requires large pipe diameters.
Thereore evacuation through Schraedervalves is not advisable. Use a Quick Connectoror compressors with process tube or use theprocess connectors on the compressor suctionand perhaps the discharge stop valve.
The valve spindle must be in its mid position.
Vacuum hoses and tubes must be as short aspossible and the diameter sufciently large.
Normally, an ordinary 1/4" charging hose notmore than 1 m in length can be used.
Evacuate in two stages with rerigerant ushingbetween.
The process o evacuation, ushing and chargingis described below.
Ac0_0025
Checking the vacuum pump and hosesa) Mount the charging hoses between
charging board and compressor. Shut o theconnections between charging hoses and
compressor.b) Start the pump and allow it to suck thepressure down as ar as possible.
c) Shut o the pump rom the rest o the system.d) Stop the pump.e) Read o and register the pressure on the
vacuum gauge. The pressure must not bemore than 0.05 mbar.
) Check to ensure that the vacuum can bemaintained. I not, replace charging hosesand/or leaking valves and/or vacuum oil in thevacuum pump.
Ac0_0026
Vacuum pump
Vacuum hoses
7/30/2019 Practical Tips Danffos
18/20
142 DKRCC.PF.000.G1.02 / 520H1459 Danoss A/S (AC-DSL/MWA), 10 - 2006
Fitters notes Practical Tips - The installation process
Evacuation rom suction side o compressor andpossibly also the discharge side.
Charging hose(s) mounted between chargingboard and compressor.
All valves, incl. solenoid valves, open.
Automatic regulating valves at maximumopening.
Evacuate system, i possible down to thepressure previously indicated by the vacuumgauge.
Ac0_0028
To be perormed as described under Checkingthe vacuum pump and hoses.I any leakage is detected:
Approximately localize the leakage byshutting o sections o the system.Retighten are and/or ange connections.Repeat evacuation.
Repeat the test until vacuum is maintained orcontinue with the next point.
Ac0_0030
Apply rerigerant pressure to the system(approx. 2 bar overpressure).
Leak-test all connections.
I leakage is detected:
Use a recycling unit and vacuum pump to
remove rerigerant rom the system.
Repair the leakage.
Repeat the process until no system leakageremains.
I overpressure remains on the system,use the recycling unit to empty it orerigerant.
Then evacuate again as described under
First evacuation.This will urther remove any air and moistureremaining in the rerigerant system.
Ac0_0029
First evacuation
System vacuum test
Flushing and provisional leaktesting
Second evacuation
7/30/2019 Practical Tips Danffos
19/20
Danoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 143
Practicaltips
Fitters notes Practical Tips - The installation process
Ac0_0031
Check and set high-pressure control and anyother saety equipment, incl. motor protector(setting in accordance with scale values).
Ac0_0032
Check all wiring.
Test the control system with compressormotor disconnected.
Check the direction o rotation o the motor.Swap two phases i necessary.
Ater nal evacuation, the system can be chargedwith rerigerant.
A charging board can be used or the purposeand will, with sufcient accuracy, dose the correctquantity o rerigerant or the system. High
accuracy is needed in systems without receiver.I the system has a charging valve, rerigerantcan be supplied in the orm o liquid to the liquidline. Otherwise the rerigerant can be supplied asvapour to the compressor suction stop valve withthe compressor running.
Caution:Too little superheating during the chargingprocess can cause liquid hammer in thecompressor.
Charging must be continued until no vapourormation appears in the sight glass - unlessvapour ormation is due to other aults, see thesection Trouble shooting - Fault location.I the necessary quantity o rerigerant is notknown, use the method last described.
Here however, it is necessary the whole timeto check that the condensing pressure andsuction pressure remain normal and that the
Thermostatic expansion valve superheat is nottoo low.
Ac0_0033
Ac0_0034
Provisional setting o saetyequipment
Checking the electrics
Rerigerant charging
7/30/2019 Practical Tips Danffos
20/20
Fitters notes Practical Tips - The installation process
Ac0_0035
Too high a condensing pressure during thecharging process can mean that the system hasbeen overcharged with rerigerant and must bepartly drained.
Always use the recycling unit i it becomes
necessary to drain o rerigerant.
Ac0_0039
Final setting and testing o saety equipmentmust be perormed with all mechanical andelectrical equipment installed and the system
running.
The unctions must be checked with accurateinstruments. See also the chapter TroubleShooting , section Measuring Instrumentswith reerence to the instructions or the equip-ment concerned.
I a constant-pressure valve is installed, make acoarse setting.
Set the expansion valve superheat.
Using a pressure gauge, set the constantpressure valve.
Set the capacity regulator, i installed.
Set the thermostats (using a thermometer).
Ac0_0062
Ac0_0045
Increase the condensing pressure to
permissible maximum and use a pressuregauge to set the high-pressure control.
Reduce the suction pressure to thepermissible minimum and use a pressuregauge to set the low-pressure control.
Condensing pressure too high
Setting and testing saetyequipment
Conditions
Setting and testingregulation equipment
Procedure
Setting the high-pressure control
Setting the low-pressure control
Attention:When making the above settings,constantly check whether the systemis operating normally (pressure, etc.).
Finally - ensure that correct rerigerant identi-cation labels are afxed to the system in orderthat correct uture servicing is ensured.