+ All Categories
Home > Documents > Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical...

Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical...

Date post: 15-Feb-2020
Category:
Upload: others
View: 5 times
Download: 0 times
Share this document with a friend
80
Transcript
Page 1: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,
Page 2: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

WBPEEUI110506A0

Preface

This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,and repair of the Type PTSP Platinum Standard Smart Pres-sure Transmitter.

It is important for safety and operating reasons to read andunderstand this instruction. Until doing so, do not install orcomplete any tasks or procedures related to calibration, opera-tion, maintenance, or repair.

Page 3: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

WBPEEUI110506A0

List of Effective Pages

Total number of pages in this instruction is 78, consisting of the following:

Page No. Change Date

Preface OriginalList of Effective Pages Original

iii through viii Original1-1 through 1-13 Original2-1 through 2-7 Original3-1 through 3-8 Original4-1 through 4-6 Original5-1 through 5-8 Original6-1 through 6-8 Original7-1 through 7-3 Original8-1 through 8-7 Original9-1 through 9-6 Original

Index-1 through Index-4 Original

When an update is received, insert the latest changed pages and dispose of the super-seded pages.

NOTE: On an update page, the changed text or table is indicated by a vertical bar in the outer mar-gin of the page adjacent to the changed area. A changed figure is indicated by a vertical bar in theouter margin next to the figure caption. The date the update was prepared will appear beside thepage number.

Page 4: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

Table of Contents

WBPEEUI

Page

SECTION 1 - INTRODUCTION....................................................................................................1-1OVERVIEW ..................................................................................................................1-1INTENDED USER.........................................................................................................1-1EQUIPMENT DESCRIPTION .........................................................................................1-1FEATURES...................................................................................................................1-1EQUIPMENT APPLICATION ..........................................................................................1-3INSTRUCTION CONTENT .............................................................................................1-3HOW TO USE THIS INSTRUCTION ...............................................................................1-4REFERENCE DOCUMENTS..........................................................................................1-4NOMENCLATURE ........................................................................................................1-5SPECIFICATIONS.........................................................................................................1-7

Common Specifications..........................................................................................1-7Type PTSPG Gage Pressure Transmitter Specifications ...........................................1-9Type PTSPA Absolute Pressure Transmitter Specifications....................................1-10

OPTIONS AND ACCESSORIES ...................................................................................1-10

SECTION 2 - DESCRIPTION AND OPERATION........................................................................2-1INTRODUCTION...........................................................................................................2-1FUNCTIONAL OPERATION ...........................................................................................2-1

Cell and Characterization Board Assembly .............................................................2-2Electronics Assembly .............................................................................................2-2EZ CAL Option.......................................................................................................2-3Communications....................................................................................................2-4Temperature Compensation ...................................................................................2-4Diagnostics ............................................................................................................2-6Software Functions ................................................................................................2-6Function Generator................................................................................................2-7

SECTION 3 - INSTALLATION .....................................................................................................3-1INTRODUCTION...........................................................................................................3-1UNPACKING AND INSPECTION ....................................................................................3-1LOCATION CONSIDERATIONS .....................................................................................3-1SETUP AND PHYSICAL INSTALLATION ........................................................................3-1

Mounting ...............................................................................................................3-2Electronics Housing Orientation ......................................................................3-3Indicator Orientation .......................................................................................3-3EZ CAL Option ................................................................................................3-3

Piping ....................................................................................................................3-4Wiring....................................................................................................................3-4

Analog Mode....................................................................................................3-4Digital Mode ....................................................................................................3-7Grounding .......................................................................................................3-8

SELECTING DEFAULTS ...............................................................................................3-8HAZARDOUS LOCATION INSTALLATIONS (FLAMMABLE ATMOSPHERES)...................3-8

SECTION 4 - CALIBRATION.......................................................................................................4-1INTRODUCTION...........................................................................................................4-1CALIBRATION PROCEDURES ......................................................................................4-1

Equipment Required for Calibration.......................................................................4-1Analog Mode Calibration ........................................................................................4-2

Bench Calibration............................................................................................4-2

110506A0 iii

Page 5: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

Table of Contents (continued)

Page

SECTION 4 - CALIBRATION (continued)D/A adjustment (fine tuning the analog loop) .................................................. 4-3

Digital Mode Calibration ........................................................................................ 4-4RERANGING THE ANALOG OUTPUT............................................................................ 4-5REZERO PROCEDURE ................................................................................................ 4-6VERIFYING CALIBRATION WITH THE EZ CAL OPTION................................................ 4-6

SECTION 5 - OPERATING PROCEDURES................................................................................5-1INTRODUCTION .......................................................................................................... 5-1OPERATOR INTERFACE .............................................................................................. 5-1CONFIGURATION PROCEDURE .................................................................................. 5-1

ID Tag ................................................................................................................... 5-1Select Mode ........................................................................................................... 5-1Channel Number ................................................................................................... 5-2Transmitter Type ................................................................................................... 5-2Output Type .......................................................................................................... 5-2Output Action ....................................................................................................... 5-2Damping Adjustment............................................................................................. 5-2Primary Engineering Units..................................................................................... 5-3Primary Upper and Lower Range Values ................................................................ 5-3Startup and Failure Conditions ............................................................................. 5-3Secondary Engineering Units................................................................................. 5-4Secondary Lower and Upper Range Values ............................................................ 5-4Cell Temperature Alarm Limits .............................................................................. 5-4Get Config Key....................................................................................................... 5-4Send Config Key .................................................................................................... 5-5View Config Key..................................................................................................... 5-5

OPERATIONAL FUNCTIONS......................................................................................... 5-5Special Feature Key ............................................................................................... 5-5

Fix Output/Cancel Fix Output ........................................................................ 5-5Local LCD Setup ............................................................................................. 5-5Standard Configuration................................................................................... 5-5

Output Key............................................................................................................ 5-6Monitor Output ............................................................................................... 5-6Monitor Input.................................................................................................. 5-6Monitor Cell Temperature................................................................................ 5-6Monitor Secondary Engineering Units.............................................................. 5-6

Status Key............................................................................................................. 5-6F1 Key................................................................................................................... 5-7

CONFIGURATION LOCKOUT PROCEDURE.................................................................. 5-7

SECTION 6 - TROUBLESHOOTING...........................................................................................6-1INTRODUCTION .......................................................................................................... 6-1ERROR MESSAGES AND CORRECTIVE ACTION ......................................................... 6-1

SECTION 7 - MAINTENANCE.....................................................................................................7-1INTRODUCTION .......................................................................................................... 7-1PREVENTIVE MAINTENANCE SCHEDULE................................................................... 7-1PREVENTIVE MAINTENANCE PROCEDURES .............................................................. 7-2

Checking Connections ........................................................................................... 7-2Indicator Window Cleaning .................................................................................... 7-2

iv WBPEEUI110506A0

Page 6: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

WBPEEUI

Table of Contents (continued)

Page

SECTION 7 - MAINTENANCE (continued)Transmitter Exterior Cleaning................................................................................7-3

SECTION 8 - REPAIR AND REPLACEMENT PROCEDURES ..................................................8-1INTRODUCTION...........................................................................................................8-1COMPONENT REMOVAL AND INSTALLATION PROCEDURES ......................................8-1

Cell and Characterization Board Assembly Removal ...............................................8-3Cell and Characterization Board Assembly Installation...........................................8-4Amplifier Assembly Removal ..................................................................................8-5Amplifier Assembly Installation ..............................................................................8-5Electronics Housing and Housing Cover Replacement ............................................8-5O-Ring Replacement ..............................................................................................8-6

OPTIONAL EQUIPMENT REMOVAL AND INSTALLATION PROCEDURES ......................8-6Indicator Removal ..................................................................................................8-6Indicator Installation..............................................................................................8-6EZ CAL Option Removal.........................................................................................8-7EZ CAL Option Installation ....................................................................................8-7Tagging Replacement (Wired Stainless Steel) ..........................................................8-7

SECTION 9 - SUPPORT SERVICES...........................................................................................9-1INTRODUCTION...........................................................................................................9-1REPLACEMENT PARTS ................................................................................................9-1SPARE PARTS LISTS ....................................................................................................9-1

O-Ring Kits ............................................................................................................9-2Electronics Kits ...................................................................................................9-2Hardware Kits .....................................................................................................9-3Cell with Characterization Board Assembly Replacements ......................................9-5

TRAINING ....................................................................................................................9-6TECHNICAL DOCUMENTATION ...................................................................................9-6

List of Figures

No. Title Page

2-1. Type PTSP Transmitter ..........................................................................................2-12-2. Cell and Characterization Board Assembly .............................................................2-22-3. Electronics Block Diagram.....................................................................................2-32-4. Analog Point-to-Point Wiring ..................................................................................2-52-5. Digital Field Bus Wiring .........................................................................................2-52-6. Communication Noise Rejection .............................................................................2-62-7. Function Generator Example .................................................................................2-73-1. External and Mounting Dimensions .......................................................................3-23-2. Gas Pressure Installation .......................................................................................3-53-3. Vapor Pressure Installation ....................................................................................3-53-4. Liquid Pressure Installation ...................................................................................3-64-1. Calibration Setup (Typical) .....................................................................................4-25-1. Lockout Jumper.....................................................................................................5-86-1. Troubleshooting Flowchart (Sheet 1 of 3) ...............................................................6-6

110506A0 v

Page 7: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

List of Figures (continued)

No. Title Page

6-2. Troubleshooting Flowchart (Sheet 2 of 3) ............................................................... 6-76-3. Troubleshooting Flowchart (Sheet 3 of 3) ............................................................... 6-88-1. Internal Transmitter Components.......................................................................... 8-28-2. External Transmitter Components......................................................................... 8-3

List of Tables

No. Title Page

1-1. Reference Documents ............................................................................................ 1-41-2. Nomenclature........................................................................................................ 1-51-3. Common Specifications ......................................................................................... 1-71-4. Ambient Condition Limits for Certified Applications ............................................... 1-91-5. Type PTSPG Gage Pressure Transmitter Specifications........................................... 1-91-6. Type PTSPA Absolute Pressure Transmitter Specifications ................................... 1-111-7. Options and Accessories...................................................................................... 1-124-1. Analog Mode Calibration Tolerances ...................................................................... 4-34-2. Digital Mode Calibration Tolerances....................................................................... 4-56-1. Error Messages...................................................................................................... 6-26-2. Output Troubleshooting ........................................................................................ 6-57-1. Preventive Maintenance Schedule.......................................................................... 7-29-1. O-Rings, Cell and Cover......................................................................................... 9-29-2. Amplifier Assembly (Compensated) ........................................................................ 9-29-3. Indicator, Add-On.................................................................................................. 9-29-4. Indicator, Spare..................................................................................................... 9-29-5. EZ CAL Option ...................................................................................................... 9-39-6. Process Adapters ................................................................................................... 9-39-7. Electronics Housing............................................................................................... 9-49-8. Cover, Housing...................................................................................................... 9-49-9. Tag, Stainless Steel, Wired..................................................................................... 9-5

vi WBPEEUI110506A0vi WBPEEUI110506A0

Page 8: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

WBPEEUI110506A0 vii

Safety Summary

SPECIFICWARNINGS

Consider the corrosive properties of the measured substance whenselecting piping materials. Degradation of the piping can upset theprocess. Some process upsets can injure personnel and damageequipment. (p. 3-4)

When pressurizing, avoid overloading and pressure hammer. Referto the introduction section for the pressure limits of the cell. Exceed-ing this pressure could result in damage to the cell and cause seri-ous injury to personnel. (p. 3-4)

Explosionproof/dust-ignitionproof installations and intrinsically safeinstallations in Class II or Class III hazardous locations require thatthe assembly be kept tight while circuits are live unless the locationis known to be nonhazardous at the time. (p. 4-1, 8-1)

The outputs of smart devices change to a fixed value during initial-ization and detected failure conditions. These values must beselected by the user to ensure safe operation. (p. 5-3)

System maintenance must be performed only by qualified personneland only after securing equipment controlled by the circuit. Alteringor removing components from an active circuit may upset the pro-cess being controlled. (p. 8-1)

SPECIFIC CAUTIONS

Do not remove the cell lock and rotate the electronics housing aboutthe cell. Doing so can damage the cell cable and will void thewarranty. (p. 3-3)

If the cell and characterization board assembly has been cleanedfor oxygen and chlorine service, do not compromise the integrity ofthis cleaning during these procedures. Impurities will react with oxy-gen and chlorine and damage the transmitter and the process.(p. 7-3, 8-1)

Clean the diaphragms with a soft rag and appropriate solvent. Theuse of metal brushes, blades, or other tools will damage the dia-phragms. (p. 7-3)

Page 9: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

viii WBPEEUI110506A0

Trademarks and Registrations

Registrations and trademarks used in this document include:

™EZ CAL Trademark of Elsag Bailey Process Automation.

™Platinum Standard Trademark of Elsag Bailey Process Automation.

®Hastelloy Registered trademark of Haynes International, Incorporated.

®Teflon Registered trademark of E. I. DuPont de Nemours Company, Incorporated.

®HART Registered trademark of HART Communication Foundation.

®NEVER-SEEZ Registered trademark of USM Corporation.

®Dow Corning Registered trademark of Dow Corning Corporation.

Page 10: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SECTION 1 - INTRODUCTION

WBPEEUI

OVERVIEW

The Type PTSP Platinum Standard Smart Pressure Transmit-ter accurately measures absolute or gage pressure of corrosiveand noncorrosive liquids, vapors, and gases. It may be config-ured to provide a polled digital process variable signal (digitalfield bus mode) or a four to 20-milliampere process variablesignal (analog mode).

It is important for safety and operating reasons to read andunderstand this manual. Until doing so, do not install or com-plete any tasks or procedures related to installation, calibra-tion, operation, maintenance, or repair.

INTENDED USER

The information in this publication is a guide for technical per-sonnel responsible for the installation, calibration, operation,maintenance, and repair of the Type PTSP Platinum StandardSmart Pressure Transmitter.

EQUIPMENT DESCRIPTION

The Type PTSP pressure transmitter consists of a cell andcharacterization board assembly and an electronics assembly.The electronics package uses the latest microprocessor tech-nology, allowing calibration, operation, and troubleshootingfrom a local or remote location.

The Type STT Smart Transmitter Terminal communicates withthe transmitter to configure, calibrate, check transmitter sta-tus, and perform other interactions with the transmitter. TheEZ CAL™ option allows calibration validation without theType STT terminal. An optional LCD (liquid crystal display)shows output in percent and user-defined secondary engineer-ing units, input in primary engineering units, cell tempera-ture, and the transmitter ID tag. An analog meter is alsoavailable for local output indication for those applicationswhere the transmitter operates at temperature extremes (referto Table 1-3 for the temperature limits).

FEATURES

Accurate, Stable, and Reproducible Measurements. Siliconpiezo-resistive cell technology provides precise, stable, andreproducible pressure measurements.

OVERVIEW110506A0 1 - 1

Page 11: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INTRODUCTION

Standard Hastelloy® C-276 Wetted Diaphragm. This corro-sion resistant material is compatible with most substances. Itreduces stock and minimizes purchase variations.

Easy Zero and Span Validation. The nonintrusive EZ CALoption does not violate the transmitter case. It allows zero andspan validation to previously defined pressure values withoutthe use of the Type STT terminal. The EZ CAL option may besupplied at delivery or added in the field, and can be used onany Type PTSP pressure transmitter (except those with stain-less steel housings).

Turndown Ratios from 1:1 to 40:1. Most Type PTSP pres-sure transmitters have a turndown ratio range from 1:1 to40:1.

Enhanced Remote Communications. Communicates withthe Type STT Smart Transmitter Terminal. This hand-heldcommunication device uses a high frequency AC signalingmethod known as FSK (frequency shift keying). This communi-cation method functions in the high noise environment foundin many factories. The Type STT terminal communicates withthe transmitter anywhere there is access to the signal wireswithin 1.6 kilometers (1.0 mile) of the transmitter. This parallelconnection does not disrupt the isolated analog four to20-milliampere process variable signal. The terminal is alsoavailable in French and Spanish language versions.Types STT04 terminals and later have the ability to communi-cate with HART devices.

Optional Two-Line, Seven Character Liquid CrystalDisplay. Displays output in percent and user-defined second-ary engineering units, input in primary engineering units, celltemperature, and transmitter ID tag. An analog meter is alsoavailable for those applications where the transmitter operatesoutside the temperature limits of the LCD. Both are easilyinstalled for convenient local indication.

Advanced Electronics Insures Reliability. The amplifierassembly uses surface mount technology, designed to exceed50 years MTBF (mean time between failure).

Dual Cover Housing. Immune to RFI (radio frequencyinterference).

Reduced Installation and Service Costs. Remote communi-cations, modular plug-in electronics, and long-term stabilityreduce installation and service time.

Direct Replacement of Existing Analog Two-WireTransmitters. Transmitters used in the analog mode replacemost four to 20-milliampere output pressure transmitters thatoperate over a two-wire system.

FEATURES1 - 2 WBPEEUI110506A0

Page 12: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INTRODUCTION

WBPEEUI

Digital Field Bus Compatibility. When used as a high speeddigital communicating device, analog signal processing doesnot occur. This results in an overall accuracy that is improvedby more than three times compared to a traditional analog sys-tem. Such applications are INFI 90® OPEN supported.

Transmitter Diagnostics. The transmitter performs a seriesof self-checks, monitoring such areas as configuration integ-rity and input circuitry. A user-defined cell temperature alarmis available. These diagnostics reduce troubleshooting and ser-vice time.

Agency Certifications. Designed to comply with FM (FactoryMutual) and CSA (Canadian Standards Association) certifica-tions as intrinsically safe, explosionproof, and nonincendive.Selected transmitters may be supplied with CENELEC (Euro-pean Committee for Electrotechnical Standardization) or SAA(Standards Association of Australia) certifications on specialorder. A NEMA 4X and IP67 housing makes the transmittersuitable for corrosive environments. The standard electronicshousing is made of a low copper (less than one percent) Alumi-num alloy. A polyurethane coating on the housing providesenvironmental protection.

EQUIPMENT APPLICATION

Uses for the transmitter include process control applicationsin the power generation, gas, water, petroleum, pulp andpaper, and food industries.

INSTRUCTION CONTENT

This instruction is organized into nine sections.

Introduction Describes this instruction and the transmitter. Includes refer-ence documents, nomenclature, specifications, and optionsand accessories.

Description andOperation

Describes the functional operation of the transmitter andassociated equipment. It also includes information about spe-cial applications such as the function generator.

Installation Provides procedures for placing the transmitter into service.

Calibration Identifies the calibration status of the transmitter and providescalibration check procedures. Calibration and validation pro-cedures using both the Type STT terminal and EZ CAL optionappear here.

Operating Procedures(Transmitter

Configuration)

Addresses startup procedures, configuring, and monitoring ofthe Type PTSP pressure transmitter (using the Type STT ter-minal), and the procedures that make the unit operational.

EQUIPMENT APPLICATION110506A0 1 - 3

Page 13: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INTRODUCTION

Troubleshooting Provides steps that aid in solving operating difficulties that canoccur, tables that list corrective action for error messages, anda troubleshooting flowchart.

Maintenance Contains preventive maintenance schedules and procedures.

Repair and ReplacementProcedures

Details procedures involved in replacing transmittercomponents.

Support Services Provides spare parts lists and ordering information for replace-ment parts.

HOW TO USE THIS INSTRUCTION

Read this entire instruction through in sequence beforeattempting to install, calibrate, operate, troubleshoot, service,or repair the transmitter. After becoming completely familiarwith the transmitter and this instruction, it may be used as areference.

Throughout this instruction, the following text conventionsgenerally apply.

Display Item Any item displayed on a screen appears as italic text. Example:

Running

REFERENCE DOCUMENTS

Table 1-1 lists Bailey-Fischer & Porter documents referred toin this instruction.

Table 1-1. Reference Documents

Number Description

B8113038 Board level wiring diagram

C-E21-50 Platinum Standard Series Smart Transmitters for Pressure, Flow and Level Measurements, Type PTS Specification

D3055062 Dimension drawing for Type PTSP pressure transmitters

D3055064 Dimension drawing for optional indicator

D3055065 User field connections

I-E96-302 Field Bus I/O Module (IMFBS01) Instruction

I-G18-1 Instrument Connecting Piping

P-E21-001 Installing a 4 to 20 mA Transmitter in a Hazardous Location

WBPEEUI110502A0 Type STT Smart Transmitter Terminal Instruction

HOW TO USE THIS INSTRUCTION1 - 4 WBPEEUI110506A0

Page 14: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INTRODUCTION

WBPEEUI

NOMENCLATURE

The Type PTSP pressure transmitter has 15 nomenclaturepositions. Positions five through 15 each have customer select-able options. Use Table 1-2 to select or verify transmitter type.

Table 1-2. Nomenclature

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Platinum Standard Smart Pressure TransmitterP Type CellP T S P _ _ _ _ _ _ _ _ _ _ _

Measurement application

A _ _ _ _ _ _ _ _ _ _ Absolute pressure

G _ _ _ _ _ _ _ _ _ _ Gage pressure

Measurement range1

E _ _ _ _ _ _ _ _ _

F _ _ _ _ _ _ _ _ _

G _ _ _ _ _ _ _ _ _

G _ _ _ _ _ _ _ _ _

J _ _ _ _ _ _ _ _ _

Diaphragm material and fill fluid

1 _ _ _ _ _ _ _ _

2 _ _ _ _ _ _ _ _

A _ _ _ _ _ _ _ _

B _ _ _ _ _ _ _ _

E _ _ _ _ _ _ _ _

F _ _ _ _ _ _ _ _

Pressure connection material

1 _ _ _ _ _ _ _ Stainless steel 316 (ordered most)

A _ _ _ _ _ _ _ Hastelloy C-276

M _ _ _ _ _ _ _ For remote seal use (direct mount)

0 0 _ _ _ _ _ Not used - enter zeros

Nominal Range Minimum RangeTypes

kPa psi kPa psi

0 - 200 0 - 30 0 - 5 0 - 0.8 PTSPA

0 - 690 0 - 100 0 - 69 0 - 10 PTSPG

0 - 3,000 0 - 450 0 - 75 0 - 11.3 PTSPA

0 - 3,000 0 - 450 0 - 200 0 - 30 PTSPG

0 - 40,000 0 - 5,800 0 - 1,000 0 - 145 All

Diaphragm Material Fill Fluid Types

Hastelloy C-276 Silicone oil (ordered most)

All

Gold plated Hastelloy C-276 Silicone oil

Hastelloy C-276 Fluorinated oil

Gold plated Hastelloy C-276

Hastelloy C-276 Fluorinated oil - cleaned for O2 and Cl2 serviceGold plated Hastelloy C-276

NOMENCLATURE110506A0 1 - 5

Page 15: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INTRODUCTION

Adapters2 and mounting bracket

0 _ _ _ _

1 _ _ _ _

2 _ _ _ _

A _ _ _ _

B _ _ _ _

C _ _ _ _

M _ _ _ _

N _ _ _ _

P _ _ _ _

Certifications

0 _ _ _ NEMA 4X - Bailey-Fischer & Porter standard

1 _ _ _ NEMA 4X and CENELEC flameproof and intrinsically safe

2 _ _ _ NEMA 4X and FM/CSA explosionproof and intrinsically safe

Housing and electrical connection

1 _ _

A _ _

Indicator, lightning arrestor, and EZ CAL option3

0 _

1 _

3 _

4 _

A _

B _

D _

E _

M _

N _

Q _

R _

Table 1-2. Nomenclature (continued)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Platinum Standard Smart Pressure TransmitterP Type CellP T S P _ _ _ _ _ _ _ _ _ _ _

Adapters2 Mounting Bracket Types

None (ordered most) None All

None Zinc plated chromate dipped Carbon steel

None Stainless steel 316

½ NPT female ss 3162 None

½ NPT female ss 3162 Zinc plated chromate dipped Carbon steel

½ NPT female ss 3162 Stainless steel 316

½ NPT female Hast C-2762 None

½ NPT female Hast C-2762 Zinc plated chromate dipped Carbon steel

½ NPT female Hast C-2762 Stainless steel 316

Housing Electrical Connection Types

Standard - low Cu light alloy Al Two ½ NPT with 1 plug All

Stainless steel 316 Two ½ NPT with 1 plug All3

Indicator Lightning Arrestor EZ CAL Option3 Types

Not included Not included Not included All

Not included Included Not included All

Not included Not included Included All3

Not included Included Included All3

LCD Not included Not included All

LCD Included Not included All

LCD Not included Included All3

LCD Included Included All3

Analog meter Not included Not included All

Analog meter Included Not included All

Analog meter Not included Included All3

Analog meter Included Included All3

NOMENCLATURE1 - 6 WBPEEUI110506A0

Page 16: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INTRODUCTION

WBPEEUI

SPECIFICATIONS

The specifications are organized into separate tables. First is alist of specifications common to all Type PTSP pressure trans-mitters. This is followed by specifications unique to each mea-surement application (gage and absolute pressure).

Common Specifications

Tables 1-3 and 1-4 list the specifications common to allType PTSP pressure transmitters.

Configuration, tagging, and accessories4

0

1

2

3

4

5

6

7

A

B

C

D

E

F

G

HNOTES:1. Units will be set to the nominal range. Customer calibrations are selected in nomenclature position 15. Refer to Table 1-7 for help.

2. Refer to Figure 3-1 for identification of the ½-NPT male to female process adapter (selectable in nomenclature position 11).3. EZ CAL option cannot be used on transmitters with stainless steel housings (A in nomenclature position 13).4. Typical accessories are mounted remote seals, football style process adapters, and manifolds.

Table 1-2. Nomenclature (continued)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Platinum Standard Smart Pressure TransmitterP Type CellP T S P _ _ _ _ _ _ _ _ _ _ _

Configuration Customer Tagging Accessories4 Types

Standard Not included Not included All

Standard Riveted stainless steel Not included

Standard Wired stainless steel Not included

Standard Paper Not included

Standard Not included Included

Standard Riveted stainless steel Included

Standard Wired stainless steel Included

Standard Paper Included

Custom Not included Not included All

Custom Riveted stainless steel Not included

Custom Wired stainless steel Not included

Custom Paper Not included

Custom Not included Included

Custom Riveted stainless steel Included

Custom Wired stainless steel Included

Custom Paper Included

Table 1-3. Common Specifications

Property Characteristic/Value

Reference conditions

Temperature 15.0° to 35.5°C (59.0° to 95.9°F)

Humidity 45% to 75%

Barometric pressure 86.0 to 106.0 kPa (12.5 to 15.4 psi)

Humidity limits 5% to 100% noncondensing continuous when covers are properly installed and conduit is sealed

SPECIFICATIONS110506A0 1 - 7

Page 17: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INTRODUCTION

Temperature limits for electronics, cell, and optional liquid crystal display

Supply voltage 12 to 53 VDC (12 to 42 VDC for CSA certified applications)4,5. Installation category III.

Power supply effect

Analog mode ±0.005% of URL per volt

Digital field bus mode ±0.003% of URL per volt

Output signal

Analog 4 to 20 mA

Digital Bailey FSK communications

Output current limiting

Maximum ≥21.6 mA

Minimum ≤3.7 mA

Loop load limits Refer to Figure 2-4

Damping/response time (one time con-stant - approximately 62% of final reading)

Analog and digital response to a step input change is adjustable from 0.0 to 32.0 secs and is entered during configuration. This value is in addition to:

Cell response time: dependent on cell and fill fluidElectronics response time: approximately 0.3 sec

RFI/EMI effects ≤±0.1% of URL in fields from 4 to 1,000 MHz at 10 V/m

Surge tolerance Complies to IEEE 472 test criteria. 2.5 kV, 1.5 MHz at 10 V/m

Vibration effect ±0.1% of URL for 1 g from 1 to 2,000 Hz in any axis of the transmitter

Enclosure rating NEMA 4X and IP67

FM/CSA certifications6,7

Explosionproof and dust-ignitionproof

Class I, Division 1, Groups B, C and D; Class II, Division 1, Groups E, F and G; Class III

Intrinsically safe Classes I, II and III, Division 1; applicable groups when connected per drawing B222611

Nonincendive Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups E, F and G; Class III

NOTES:1. The normal operating temperature range is that at which the transmitter meets all specifications. The extreme operating temperaturerange is that at which the transmitter remains powered without damage.2. All transmitters with fluorinated oil filled cells can only be operated in temperatures from -10° to +80°C (+14° to +176°F).3. The normal operating temperature range for the LCD is that at which the LCD remains functional. Exceeding those conditions may causethe LCD to go blank. The transmitter remains functional to its operating limits. When the temperature returns to the acceptable range, thedisplay is restored; however, the life of the display may be reduced.4. The minimum supply voltage necessary to support communications is 17.0 VDC.5. Add 0.4 VDC to all minimum supply voltage values if using the lightning arrestor option.

6. Refer to Table 1-4 for the ambient condition limits for certified applications.7. The transmitters are only certified for those agencies and classes indicated on the certification label. Do not install the transmitters inlocations for which they are not suited. Refer to nomenclature position 12.

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.

Table 1-3. Common Specifications (continued)

Property Characteristic/Value

ParameterElectronics1 Cell1,2 LCD3

°C °F °C °F °C °F

Normal operating

-40 to +85 -40 to +185 -40 to +85 -40 to +185 0 to +50 +32 to +122

Extreme operating

-50 to +85 -58 to +185 -50 to +120 -58 to +248 0 to +50 +32 to +122

Storage/transport

-55 to +85 -67 to +185 -55 to +85 -67 to +185 -20 to +70 -4 to +158

SPECIFICATIONS1 - 8 WBPEEUI110506A0

Page 18: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INTRODUCTION

WBPEEUI

Type PTSPG Gage Pressure Transmitter Specifications

Table 1-5 lists the specifications unique to Type PTSPG gagepressure transmitters.

Table 1-4. Ambient Condition Limits for Certified Applications

Agency CategoryTmax Tmin Pmax Pmin O2max

°C °F °C °F kPa psia kPa psia %

FM Explosionproof 80 176 -40 -40 108 15.7 86 12.5 21

Dust-ignitionproof

Intrinsic safety 65 (T4) 149 (T4)

Nonincendive

CSA Explosionproof 60 140

Dust-ignitionproof

Intrinsic safety 40 (T3C)60 (T3A)

104 (T3C)140 (T3A)

Nonincendive 60 (T4A) 140 (T4A)

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.

Table 1-5. Type PTSPG Gage Pressure Transmitter Specifications

Property Characteristic/Value

Measurement range, turndown ratio, zero sup-pression, and zero elevation

Lower range value (zero) and upper range value (100%) can be calibrated at any value of pressure, provided that:

1. Their algebraic difference (the calibrated span) corresponds to an authorized TDR.

2. Both are within the following acceptable limits.

Stability

PTSPGF ±0.2% of URL per 12-month period (at reference conditions)

PTSPGG and PTSPGJ ±0.1% of URL per 12-month period (at reference conditions)

Type

International System Units

Range Limits1 (kPa) Span and Turndown Ratio (TDR)

Upper Lower Nominal (kPa) Minimum (kPa)

PTSPGF 690 -100 690 1:1 TDR 69 10:1 TDR

PTSPGG 3,000 0 3,000 1:1 TDR 200 15:1 TDR

PTSPGJ 40,000 0 40,000 1:1 TDR 1,000 40:1 TDR

Type

American Units

Range Limits1 (psi) Span and Turndown Ratio (TDR)

Upper Lower Nominal (psi) Minimum (psi)

PTSPGF 100 -14 100 1:1 TDR 10 10:1 TDR

PTSPGG 450 0 450 1:1 TDR 30 15:1 TDR

PTSPGJ 5,800 0 5,800 1:1 TDR 145 40:1 TDR

SPECIFICATIONS110506A0 1 - 9

Page 19: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INTRODUCTION

Type PTSPA Absolute Pressure Transmitter Specifications

Table 1-6 lists the specifications unique to the Type PTSPAabsolute pressure transmitter.

OPTIONS AND ACCESSORIES

Table 1-7 lists the options and accessories available with theType PTSP pressure transmitter.

Reference accuracy - per IEC 770 and SAMA PMC 31.1

The reference accuracy includes the effects of linearity, hysteresis, repeatability, and deadband. These values are for transmitters with zero based spans, silicone oil fill, and Hastelloy C-276 isolating diaphragms at a reference temperature of 25°C (77°F). The value listed may vary depending on the URL and calibrated span of the particular transmitter.

PTSPGF ±0.20% of span or ± (% of span), whichever is greater

PTSPGG and PTSPGJ ±0.10% of span or ± (% of span), whichever is greater

Pressure limits The minimum sustained absolute pressure is 3.4 kPa (0.5 psi). The maximum overpressure is listed in the following table.

Overpressure effect This value is for transmitters with zero based spans, silicone oil fill, and Hastelloy C-276 isolating diaphragms at a reference temperature of 25°C (77°F).

±0.05% of URL for line pressures 1.5 times URL.

Ambient temperature effect on zero and span

These values are for transmitters with zero based spans, silicone oil fill, and Hastelloy C-276 isolating diaphragms. The effects listed are for a variation of ±25°C (±45°F) from a calibration done at a temperature between -30° and +80°C (-22° and +176°F), as long as the variation does not take the transmitter out of the temperature specifications listed in Table 1-3.

PTSPGF ±(0.15% URL + 0.10% span)

PTSPGG and PTSPGJ ±(0.08% URL + 0.10% span)

Weight 1.3 kg (2.9 lbs) without options or accessories.NOTE:1. Types PTSPGG and PTSPGJ pressure transmitters are not compensated for barometric pressure. Type PTSPGF pressure transmittersare not linearized or thermally stabilized below atmospheric pressure.

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.

Table 1-5. Type PTSPG Gage Pressure Transmitter Specifications (continued)

Property Characteristic/Value

0.016 URL×Span

--------------------------------

0.008 URL×Span

--------------------------------

TypeURL Overpressure Limit

(kPa) (psi) (kPa) (psi)

PTSPGF 690 100 1,250 180

PTSPGG 3,000 450 6,000 870

PTSPGJ 40,000 5,800 41,368 6,000

OPTIONS AND ACCESSORIES1 - 10 WBPEEUI110506A0

Page 20: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INTRODUCTION

WBPEEUI

Table 1-6. Type PTSPA Absolute Pressure Transmitter Specifications

Property Characteristic/Value

Measurement range, turndown ratio, zero suppression, and zero elevation

Lower range value (zero) and upper range value (100%) can be calibrated at any value of pressure, provided that:

1. Their algebraic difference (the calibrated span) corresponds to an authorized TDR.

2. Both are within the following acceptable limits.

Stability ±0.1% of URL per 12-month period (at reference conditions)

Reference accuracy - per IEC 770 and SAMA PMC 31.1

The reference accuracy includes the effects of linearity, hysteresis, repeatability, and deadband. These values are for transmitters with zero based spans, silicone oil fill, and Hastelloy C-276 isolating diaphragms at a reference temperature of 25°C (77°F). The value listed may vary depending on the URL and calibrated span of the particular transmitter.

PTSPAE ±0.20% of span or ± (% of span), whichever is greater

PTSPAG and PTSPAJ

±0.10% of span or ± (% of span), whichever is greater

Pressure limits The minimum sustained absolute pressure is 3.4 kPa (0.5 psi). The maximum overpressure is listed in the following table.

Overpressure effect This value is for transmitters with zero based spans, silicone oil fill, and Hastelloy C-276 isolating diaphragms at a reference temperature of 25°C (77°F).

±0.05% of URL for line pressures 1.5 times URL.

Ambient temperature effect on zero and span

These values are for transmitters with zero based spans, silicone oil fill, and Has-telloy C-276 isolating diaphragms. The effects listed are for a variation of ±25°C (±45°F) from a calibration done at a temperature between -30° and +80°C (-22° and +176°F), as long as the variation does not take the transmitter out of the tem-perature specifications listed in Table 1-3.

PTSPAE ±(0.10% URL + 0.10% span)

PTSPAG and PTSPAJ ±(0.08% URL + 0.10% span)

Weight 1.3 kg (2.9 lbs) without options or accessories.

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.

Type

International System Units

Range Limits (kPa) Span and Turndown Ratio (TDR)

Upper Lower Nominal (kPa) Minimum (kPa)

PTSPAE 200 0 200 1:1 TDR 5 40:1 TDR

PTSPAG 3,000 0 3,000 1:1 TDR 75 40:1 TDR

PTSPAJ 40,000 0 40,000 1:1 TDR 1,000 40:1 TDR

Type

American Units

Range Limits (psi) Span and Turndown Ratio (TDR)

Upper Lower Nominal (psi) Minimum (psi)

PTSPAE 30 0 30 1:1 TDR 0.8 40:1 TDR

PTSPAG 450 0 450 1:1 TDR 11 40:1 TDR

PTSPAJ 5,800 0 5,800 1:1 TDR 145 40:1 TDR

0.016 URL×Span

--------------------------------

0.013 URL×Span

--------------------------------

TypeURL Overpressure Limit

(kPa) (psi) (kPa) (psi)

PTSPAE 200 30 600 87

PTSPAG 3,000 450 6,000 870

PTSPAJ 40,000 5,800 41,368 6,000

OPTIONS AND ACCESSORIES110506A0 1 - 11

Page 21: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INTRODUCTION

Table 1-7. Options and Accessories

Item Description

Type STT Smart Transmit-ter Terminal

Hand-held device for calibration, configuration, monitoring, and troubleshooting. Also communicates with HART devices.

EZ CAL option1 External nonintrusive device for zero and span validation. Add on kit no. 258562_1.

Liquid crystal display option1

Two-line, seven-character display for local output indication. Displays output in percent and user-defined secondary engineering units, input in primary engi-neering units, cell temperature, and transmitter ID tag. Mounts in four orienta-tions for easy viewing. Refer to Table 1-3 for the temperature limitations. Add on kit no. 258550_1 (aluminum cover) or 258550_5 (stainless steel cover).

Analog meter option1 Provides local output indication for those applications where the transmitter operates outside the temperature limits of the LCD. Linear 0 to 100 and square root 0 to 10 graduations on same scale. Add on kit no. 258550_2 (aluminum cover) or 258550_6 (stainless steel cover).

Process adapter option1

(straight)½ NPT male to female stainless steel 316 or Hastelloy C-276. Part no. 1951753_ _.

Process adapter (football style)

½ NPT stainless steel 316 for connection to flanged manifold. Part no. 1948994_1.

Mounting bracket option1 Universal support for mounting on panel or 1.5 in. to 2.0-in. pipe. Available in Zinc-plated, chromate-dipped carbon steel, or stainless steel 316.

Degreasing option1 For use in oxygen or chlorine service.

Gold plated Hastelloy C-276 diaphragm option1

For use in hydrogen service.

Tantalum diaphragm For use with highly corrosive fluids.

Remote diaphragm seals For use with high temperature and corrosive fluids or where impulse line clogging may be a problem.

Lightning arrestor option1 Mounts internally to suppress lightning induced transients. Tested to suppress 10 successive 8 by 20 µsec pulses with a peak value of 20 kA (reference IEEE C62.41).

Antistatic kit Contains static-dissipative work surface (mat), ground cord assembly, wrist bands, and alligator clip for personnel working on devices containing semicon-ductor components. Kit no. 1948385_1.

Available drawings

B8113038 Board level wiring diagram.

D3055062 Dimension drawing for Type PTSP pressure transmitters.

D3055064 Dimension drawing for optional indicator.

D3055065 User field connections.

OPTIONS AND ACCESSORIES1 - 12 WBPEEUI110506A0

Page 22: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INTRODUCTION

WBPEEUI

Configuration option1 The transmitters are delivered with a standard configuration. Custom configura-tions can be ordered by selecting that option in nomenclature position 15. The factory programmed configuration is listed below, as well as a column to aid in ordering custom configurations.

NOTE:1. These items are selected via nomenclature in Table 1-2.

Table 1-7. Options and Accessories (continued)

Item Description

Parameter Standard Configuration Custom Configuration

ID tag PTS

Operating mode Analog

Output function Linear - normal acting

Damping 0.5 sec

Engineering units (EU) in. H2O/psi

Lower range value (LRV) 0.0

Upper range value (URV) URL of transmitter

Initialize output Low

Fail output Low

Secondary EU ..MA

Secondary LRL 4.00

Secondary URL 20.00

Cell temp. low alarm -40°C

Cell temp. high alarm 85°C

OPTIONS AND ACCESSORIES110506A0 1 - 13

Page 23: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SECTION 2 - DESCRIPTION AND OPERATION

WBPEEUI

INTRODUCTION

This section describes the Type PTSP Platinum StandardSmart Pressure Transmitter. It also includes informationabout special functions such as the function generator. Referto Figure 2-1 for an illustration of the transmitter.

Type PTSP pressure transmitters measure absolute and gagepressures of corrosive or noncorrosive liquids, vapors, andgases. The transmitter can be configured to provide a polleddigital process variable signal (digital field bus mode) or a fourto 20-milliampere process variable signal (analog mode). Usesfor the transmitter include process control applications in theelectric, gas, water, chemical, petroleum, pulp and paper, andfood industries.

FUNCTIONAL OPERATION

The Type PTSP pressure transmitter has two major sections: acell and characterization board assembly, and an electronicsassembly. The Type STT Smart Transmitter Terminal commu-nicates with the Type PTSP pressure transmitter. The EZ CALoption provides a way to validate the zero and span of thetransmitter without using the Type STT terminal.

Figure 2-1. Type PTSP Transmitter

R IG H T H O U S IN G C OVE R(P R OTE C TS TE R M IN ALS )

E Z C A L O P TIO N

P IPE P LU G(1 /2 -14 N P T FO RE LEC T R IC AL C O ND U IT)

C E LL LO C K IN G S CR E W(O N OT H ER S ID E )

E LEC T RO N IC SA SS E M BLY

C E LLA SS E M BLY

C E LL LO C K

O -R IN G S E AL (2)

LE FT H O U SIN GC OV E R (P RO TE C TSE LEC T RO N IC S A NDO P TIO N A L LC D O R

A N ALO G M E TE R )

C E LL

O P TIO N A L1/2 -N P T M A LE

TO FE M A LEP RO C ES SA DAP TE R

O P TIO N A L 1 /2 -N PTFO OTB A LL-S TY LE

P RO C ES SA DAP TE R T 02 1 97 A

INTRODUCTION110506A0 2 - 1

Page 24: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

DESCRIPTION AND OPERATION

Cell and Characterization Board Assembly

Type PTSP pressure transmitters use an electrically isolatedpiezo-resistive monocrystal silicon chip as the sensing device.A Wheatstone bridge is implanted on the silicon chip in thedeflecting areas of the sensor.

The pressure transfers through the fill fluid (silicone oil or flu-orinated oil) that is between the isolating diaphragm and thesilicon chip (Fig. 2-2). The resistance of the bridge varies as afunction of the pressure. A regulated current, applied to thebridge, results in an unbalanced voltage across the bridge.This voltage is proportional to the applied pressure.

The cell and characterization board are a matched set and maynot be separated. For more information on the characteriza-tion board, refer to Electronics Assembly.

Electronics Assembly

Figure 2-3 shows the Type PTSP pressure transmitter elec-tronics in block diagram form. All calibration, configuration,and compensation data are stored in both the main and char-acterization boards. The output of the cell goes into a customanalog to digital converter on the LSI smart chip via the char-acterization board. The microcontroller requests the digitaloutputs of the custom analog to digital converter. It uses these

Figure 2-2. Cell and Characterization Board Assembly

C H A R AC TE R IZATIO NB O AR D

P R ES S U R E

S IL IC O NC H IP

IS O LATIN GD IA PH R AG M

FILL FLU ID

T 02 19 8 A

FUNCTIONAL OPERATION2 - 2 WBPEEUI110506A0

Page 25: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

DESCRIPTION AND OPERATION

WBPEEUI

digital outputs and the memory stored on the characterizationboard to calculate an output for the transmitter. This output isthen available as a four to 20-milliampere output or a polleddigital process variable signal.

The transmitters include a lockout jumper that when acti-vated, prevents any alterations to the calibration orconfiguration (Fig. 5-1).

EZ CAL Option

NOTE: The EZ CAL option is for zero and span validation only. Donot use it to change the calibrated span of the transmitter. TheEZ CAL option provides no means to indicate if an error is made.

After mounting the EZ CAL option, one of two magneticallycoupled components responds to the moving of a magnet inthe EZ CAL option. When validating the zero, adjust the inputpressure to the configured zero value and turn and hold theadjustment screw on the EZ CAL option in the zero directionfor at least three seconds. This causes the electronics to auto-matically adjust the output to zero percent. To validate thespan, set the input pressure to the configured span value,depress the span lock and turn and hold the adjustment screwon the EZ CAL option in the span direction for at least three

Figure 2-3. Electronics Block Diagram

S EE P RO M

LS IS M AR T C H IP

A N ALO G TO D IG ITA LC O N VE RT ER

LC DO P TIO N

32KE PR O M

E EP R O M

H C 11M IC RO C O N T RO LLER

IN TE R N A LP OW E R SU P P LY

FS KC O M M U N IC ATIO N

C IR C U ITRY

IS O LATIO N FILT ER

C U R R E N TC O N TRO L

VO LTAG ER E G U LATIO N

LIG H T N IN GA R R ES TO R

O P TIO N

D IG ITAL FS KC O M M U N IC ATIO N S

O RD IG ITAL FS K

C O M M U N IC ATIO N SW ITH

4 TO 20-m A O U T PU T

IS O LATIO N

IS O LATIO N

A N ALO G M E TE RO P TIO N

1) P R E SS U R E

2) C E LL T EM P E R AT U R E

3) DY N AM IC TE M PE R ATU R E (TY P E P TS D P R ES S U R E TR A N SM ITT ER O N LY )

C H A R AC T E R IZ ATIO NBO AR D

M A IN B OAR D

T 02 19 9 A

FUNCTIONAL OPERATION110506A0 2 - 3

Page 26: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

DESCRIPTION AND OPERATION

seconds. This causes the electronics to automatically adjustthe output to 100 percent. Span or zero or both may beadjusted.

Communications

A high frequency AC voltage signal imposed on the signalwires, known as FSK (frequency shift keying), allows commu-nications between the Type PTSP pressure transmitter and theType STT terminal. The location of the Type PTSP pressuretransmitter may be up to 1.6 kilometers (1.0 mile) from theType STT terminal. The FSK method provides excellent noiseimmunity for remote communications. A minimum of250-ohms loop resistance is necessary to support communica-tions (Fig. 2-4). This is true whether the transmitter is config-ured in the analog (four to 20 milliampere) point-to-point modeor the digital field bus mode. The Type STT terminal connectsto the target transmitter anywhere there is access to the signalleads of the transmitter (for point-to-point wiring, the TypeSTT terminal must be connected between the device and the250-ohm resistance). The clip leads connect across the signalleads independent of signal direction or polarity. Since thecommunication signal, a high frequency AC, has a zero DCaverage, it has no effect on the output. Two different frequencylevels transmit a logic zero or a logic one.

Configuring the transmitter in the digital mode (refer toSection 5) causes the microcontroller to set the output of thetransmitter to less than four milliamperes for low power con-sumption. The transmitter then provides a digital process vari-able signal. The transmitter reports its output (in percent) upto ten times per second for control purposes (Fig. 2-5).

NOTE: Refer to the Field Bus I/O Module (IMFBS01) Instructionfor wiring practices and output update times.

The FSK communication technique makes it possible to com-municate in the presence of electrical noise. Figure 2-6 showshow the ability to communicate varies with the amplitude andfrequency of the noise. This graph represents a typical instal-lation and applies only when one noise frequency is present.The graph indicates that the FSK communication techniquetolerates up to two volts of noise amplitude at 60 hertz. Thistolerance decreases as the noise frequency approaches theFSK communication frequencies of 19.0 kilohertz and30.5 kilohertz.

Temperature Compensation

The transmitter electronics monitor the temperature of the cellassembly. This is accomplished by monitoring the resistanceof one of the legs of the Wheatstone bridge within the cell. Thistechnique provides a true cell temperature measurement, and

FUNCTIONAL OPERATION2 - 4 WBPEEUI110506A0

Page 27: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

DESCRIPTION AND OPERATION

WBPEEUI

the transmitter uses it to calculate an advanced correction forthe cell output based on the programmed cell temperaturecharacteristics. The transmitter also compensates the four to20-milliampere output for temperature changes within the

Figure 2-4. Analog Point-to-Point Wiring

Figure 2-5. Digital Field Bus Wiring

N OTE S:

1 . D O N OT C O N N EC T T YPE STT TER M IN AL D IR EC T LY AC RO SS P OW E R SU PP LY.

2 . G R APH SH OW N IS F O R 20-m A M A XIM U M O U T PU T.

3 . AD D 0 .4 VD C TO ALL M IN IM U M SU PP LY VO LTAG E VA LU E S IF U S IN G LIG H T N IN G AR R ES TO R O PT IO N .12 16 .6 25 35 45 53

0

230

600

1200

1800

2050

C O M M U N IC ATIO N SO PE R AT IN G

R AN G E

T0 2608ASU P PLY VO LTAG E (V D C )

LO ADR ES ISTAN C E

( )Ω

250 (TY P)

ΩH IG H IM P EDAN C E

C O N T RO LLER ,R EC O R D ER O R

C O N T RO L S YST EM

SY ST EMPO W ER S U PPLY

SIG N A L W IR E S

+

+

–ST T T B1

+ +

–TE S T

P W R /O U T P U T

T 02609A

T ER M IN AT IO NU N IT

IN FI 90 O P E N SY S T EM

F IE LD BU SI/O M O D U LE

M U LT IF U N C T IO NP RO C E S S O R /

M U LT IF U N C T IO NC O N TRO LLE R

S IG N A L W IR ES

T RA N S M IT TE R 1 T RA N S M IT TE R 8

+

S TT T B1 T B1

+ ++ +

– –

– –TE ST TE ST

PW R/O UTP UT

PW R/O UTP UT

FUNCTIONAL OPERATION110506A0 2 - 5

Page 28: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

DESCRIPTION AND OPERATION

electronics housing. The cell temperature can be monitored onthe Type STT terminal.

Diagnostics

Continuous self-diagnostics are accessible on demand throughthe Type STT terminal. Areas monitored include: cell; cell tem-perature; electronics temperature; calibration; configuredpressure limits; input circuits; analog to digital converter;microcontroller ROM, SEEPROM, EEPROM; and referencevoltages. Diagnostics identify the malfunctioning section of thetransmitter. The diagnostics may indicate if a calibration erroroccurs.

Software Functions

Configuration and operational commands allow the input of anID tag for the transmitter configuration, selection of engineer-ing units (primary and secondary), and definition of the out-put. The output can be a linear representation of the input or afunction generator that follows a curve consisting of sixstraight line segments. The output can be set for normal orreverse acting and fixed to a specific value for plant startupand troubleshooting purposes. Other commands allow the out-put to be set to default values upon transmitter power up andfailure. The Type STT terminal also supports configuration,input, output, and transmitter status monitoring. A dampingcommand is also available.

Figure 2-6. Communication Noise Rejection

N O ISE FR E Q U E N C Y (H Z)

N O ISE A M P LITU D E(VO LTS )

10 100 1 ,000 10 ,000 100 ,00010

1

2

3

4

T02200A

60 H Z

19 .0 kH Z 30 .5 kH Z

FUNCTIONAL OPERATION2 - 6 WBPEEUI110506A0

Page 29: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

DESCRIPTION AND OPERATION

WBPEEUI

Function Generator

The function generator is a curve consisting of six straight linesegments programmed into the transmitter via the Type STTterminal. This makes it possible to program the output to fol-low the input in a way that is specific to a certain application.

The first and last points of the curve (P0 and P6) are pre-defined at zero-percent input and output, and 100-percentinput and output respectively. The other five points (P1, P2,P3, P4, and P5) are user defined. Refer to Section 5 and theType STT Smart Transmitter Terminal Instruction formore information on the function generator.

Figure 2-7 shows a function generator used to control the out-put of a transmitter. This transmitter is connected to a tankwith a varying shape. The function generator makes it possibleto approximate the changes in shape of the tank, and thus totrack the volume of the liquid in the tank.

Figure 2-7. Function Generator Example

N OTE: P0 A N D P 6 AR E PR ED E FIN ED.P 1 TH RO U GH P 5 AR E E N TE RE DD UR IN G C O N FIG UR AT IO N .

A LL VALUE S S H OW N A R EP ER C EN TAG E IN P UT AN DO U TP U T Px (% IN , % O U T)

IN P U T F T H 0 (% )2

O U T P U T m A (% )

P 3, P 4, P5 , P 6 (100 , 100)

P 2 (50, 40)

P 1 (30, 10)P 0 (0 , 0 )

20(100 )

20(100 .00)

16(75.00)

12(50.00)

8(25.00)

4(0.00 )

18(90)

16(80)

14(70)

12(60)

10(50)

8(40)

6(30)

4(20)

2(10)

0(0)

1 00 % F U L L P 3

P 2

P 1

P 0

P 1

P 2

P 3

T R A N S M IT T E R

T02201A

FUNCTIONAL OPERATION110506A0 2 - 7

Page 30: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SECTION 3 - INSTALLATION

WBPEEUI

INTRODUCTION

This section aids in all levels of the installation process. Thegoal is to provide clear procedures for placing the transmitterinto service.

NOTE: Refer to Installing a 4 to 20 mA Transmitter in a Hazard-ous Location and ANSI/ISA RP12.6, Installation of IntrinsicallySafe Systems for Hazardous (Classified) Locations whenapplicable.

UNPACKING AND INSPECTION

1. Check for any obvious damage to the carton or its con-tents. If damage is evident, notify the carrier and a salesrepresentative.

2. Remove any loose packing from the carton.

3. Carefully remove the transmitter from the carton.

4. Inspect the nameplate to verify the unit received matchesthe desired function.

5. If the transmitter is to be stored prior to installation, packit in the original container, if possible. Store in an area freefrom corrosive vapors and extremes in temperature andhumidity. Install the covers and seal all wiring inlets.

NOTE: Storage temperatures must not exceed the limits listed inTable 1-3.

LOCATION CONSIDERATIONS

Because of process and economic considerations, pressuretransmitters must often be installed in harsh environments.The transmitter should, however, be located so as to minimizethe effects of temperature gradients and fluctuations, and toavoid shock and vibration.

When mounting the unit, be sure to leave ample clearance toopen the cover of the electronics (Fig. 3-1). Wire the transmit-ter with twisted, shielded pairs for best results. Avoid sourcesof RFI (radio frequency interference).

SETUP AND PHYSICAL INSTALLATION

The quality of the measurement depends on the correct instal-lation of the transmitter. This includes the orientation, pipe

INTRODUCTION110506A0 3 - 1

Page 31: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INSTALLATION

connections, and wiring. Refer to the Instrument ConnectingPiping instruction and ASME/ANSI Code for Pressure Piping(ANSI B31.1) when applicable.

Mounting

Since the transmitter weighs only 1.3 kilograms (2.9 pounds),and the end of the measuring cell is ½-NPT male threaded,direct connection to the process is possible. Figure 3-1 showsthe external and mounting dimensions. There is an optional½-NPT female process adapter available when required. Referto Tables 1-2 and 1-7 for more information on the processadapter.

If needed, there is a universal support to mount the transmit-ter to a panel or 1.5 to 2.0-inch pipe. Refer to Tables 1-2 and

Figure 3-1. External and Mounting Dimensions

SETUP AND PHYSICAL INSTALLATION3 - 2 WBPEEUI110506A0

Page 32: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INSTALLATION

WBPEEUI

1-7 for more information on the mounting bracket. Figure 3-1also shows this mounting scheme.

ELECTRONICS HOUSING ORIENTATION

The electronics housing in not designed to rotate about thecell. The cell lock has a flat on it that matches with a flat onthe cell. Do not remove the cell lock unless performing therepair and replacement procedures in Section 8.

Make orientation adjustments to the electronics housing byusing the process connection or the process adapters.

INDICATOR ORIENTATION

The transmitter is shipped with the indicator in the upright(zero-degree) position. If desired, rotate the indicator270 degrees in increments of 90 degrees.

1. Remove the left housing cover from the electronics housing(Fig. 2-1).

2. Remove the four screws that secure the indicator to theamplifier assembly (Fig. 8-1).

3. Gently pull on the indicator to unplug it from the amplifierassembly.

4. Align the connector on the back of the indicator with one ofthe four meter openings in the amplifier assembly (Fig. 8-1).The alignment of the connector depends on the desired viewingorientation. Gently press the indicator down to seat the matingconnectors.

5. Install the four screws that secure the indicator to theamplifier assembly.

6. Coat the threads of the housing cover with a light coatingof DRI-GLIDE graphite sealant (Man-Gill Chemical Corpora-tion).

7. Replace the left housing cover.

CAUTIONDo not remove the cell lock and rotate the electronics housingabout the cell. Doing so can damage the cell cable and will voidthe warranty.

SETUP AND PHYSICAL INSTALLATION110506A0 3 - 3

Page 33: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INSTALLATION

EZ CAL OPTION

1. The transmitter is delivered with a logo nameplate in placeof the EZ CAL option. Lift up on the logo nameplate to snap itstab out of the EZ CAL option mounting hole.

2. Position the EZ CAL option on the top of the transmitter asshown in Figure 3-1 and install the mounting screw.

Piping

Piping should be in accordance with ANSI Code B31.1 for pres-sure piping.

The nameplate indicates the maximum allowable pressure. Donot exceed this value when pressurizing the cell.

The piping between the primary element and the transmittermust transfer the process pressure at the pipe taps to thetransmitter. Possible sources of error in this pressure transferare:

• Leaks.• Friction loss, if continuous purging is used.• Trapped gas in a liquid line.• Trapped condensates in a gas line.

Figures 3-2, 3-3, and 3-4 show several installation examples.These are typical piping arrangements only. They are intendedas generalized guides, and may not necessarily reflect theexact configuration required for the particular service.

Wiring

There are two possible wiring configurations for the Type PTSPpressure transmitter.

NOTE: Never connect the loop wiring to the test terminals.

WARNING

Consider the corrosive properties of the measured substancewhen selecting piping materials. Degradation of the piping canupset the process. Some process upsets can injure personneland damage equipment.

WARNING

When pressurizing, avoid overloading and pressure hammer.Refer to the introduction section for the pressure limits of thecell. Exceeding this pressure could result in damage to the celland cause serious injury to personnel.

SETUP AND PHYSICAL INSTALLATION3 - 4 WBPEEUI110506A0

Page 34: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INSTALLATION

WBPEEUI

ANALOG MODE

In the analog mode of operation, the electrical connections aremade in the typical two-wire, four to 20-milliampereconfiguration as shown in Figure 2-4. There is a + (positive)and - (negative) terminal provided at the transmitter to identifythe signal leads (Fig. 2-4).

NOTE: Insure that the temperature rating of the wire is suitable forthe environment.

Figure 3-2. Gas Pressure Installation

Figure 3-3. Vapor Pressure Installation

T0 2204A

IS O LATIN GVA LV E

F ILL LIQU IDTA N K

D R A IN

SETUP AND PHYSICAL INSTALLATION110506A0 3 - 5

Page 35: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INSTALLATION

The signal terminals located in the electronics housing acceptwire sizes up to 14 AWG. The signal wiring supplies all powerto the transmitter. The power supply limits are 12 to 53 VDC(12 to 42 VDC for certified applications) across the transmitterinputs. Refer to Figure 2-4 for the load resistance limits, or usethe equation:

NOTES:1. The equation for load resistance is based on a maximum outputof 20 milliamperes with the - (negative) TEST terminal jumper screwtightened. In some cases (initialize high, fail high, overpressure con-ditions, etc.) the output may be higher. If this value is known, it canbe used in the denominator of the equation instead of 0.02.

2. If the - (negative) TEST terminal jumper screw is loosened½-turn, the minimum supply voltage is 12.7 VDC.

3. If using the optional lightning arrestor, add 0.4 VDC to all mini-mum supply voltage values.

The power supply and load resistance are variable over theentire operating region shown in Figure 2-4.

The TEST terminals have the same four to 20-milliampere sig-nal as the PWR/OUTPUT terminals. Loosen the - (negative)TEST terminal jumper screw ½-turn for calibration or testing.

Signal wiring should be shielded. Use twisted pairs for bestresults. Connect the shield at the ground terminal inside theelectronics housing (Fig. 2-4) or at the receiver.

NOTE: Connect the shield at one end only. Connecting the shield atboth ends may result in a ground loop condition.

Figure 3-4. Liquid Pressure Installation

T0 2205AD R A IN

IS O LATIN GVA LV E

RmaxV 12.00–

0.02-----------------------=

SETUP AND PHYSICAL INSTALLATION3 - 6 WBPEEUI110506A0

Page 36: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INSTALLATION

WBPEEUI

DIGITAL MODE

In the digital mode of operation there is no four to20-milliampere signal. The transmitter draws less thanfour milliamperes to maintain operation (Fig. 2-5).

NOTE: Refer to the Field Bus I/O Module (IMFBS01) Instructionfor wiring practices and output update times.

In the digital mode, the process variable signal of each trans-mitter is a digitally polled variable. The field bus modulesequentially polls each transmitter output on the bus. Eachtransmitter on the bus has its own unique address that isassigned during configuration. Refer to Channel Number inSection 5 for information on configuring the transmitteraddress. The address allows the field bus module to distin-guish between transmitters on the loop.

Each transmitter present on the bus is wired from the controlsystem to the + (positive) and - (negative) terminals of thetransmitter. Connect all transmitters on the bus in parallel.

The minimum power supply voltage required for the loop isdetermined by:

The load resistance must include the system input resistanceand the resistance of the wire. No meters or measuring devicesare to be included in the field bus loop since the transmittersare not delivering an analog process variable. Power supplyregulation is not critical as long as the voltage remains abovethe minimum calculated value.

The Type STT terminal can be connected anywhere there isaccess to the signal leads. Since the Type STT terminal alsohas its own bus address, it can be connected to the bus whilethe system is online. Only one Type STT terminal can be con-nected to the bus at any one time. While the field bus I/Omodule is online, the Type STT terminal can monitor anytransmitter on the bus.

In order to change any calibration or configuration parametersof transmitters using the Type STT terminal, the field bus I/Omodule must be instructed to bring the desired transmitteroffline.

Signal wiring should not be run in conduit or open trays withwiring used to power other devices and should not be run nearheavy electrical equipment. Twisted shielded pairs are recom-mended for best results. Reverse polarity protection is builtinto the transmitter to protect it against accidental reversal ofthe field wiring connections.

minumum supply voltage =12 volts 0.004 no. of transmitters on bus× load resistance×( )+

SETUP AND PHYSICAL INSTALLATION110506A0 3 - 7

Page 37: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

INSTALLATION

GROUNDING

Signal wiring may be either ungrounded (floating) or groundedat any one point in the signal loop. If more than one transmit-ter is connected to a single power supply, grounding should beat the supply. The transmitter housing must also be grounded.A ground terminal is provided inside the electronics housing(Figs. 2-4 and 2-5).

SELECTING DEFAULTS

The configuration of process control equipment within a par-ticular system dictates the response to the controlled processof that system. Configuration may include such items ascross-limits, interlocks and alarms dealing with bad quality,and safety control equipment. Modern electronic process con-trol equipment based on semiconductor technology is highlyreliable and can be expected to provide long trouble-free ser-vice. However, component failures that disrupt process controlare still possible. In addition, power line induced failures, fail-ures caused by human error, static discharge, conducted andradiated EMI, acts of nature such as lightning strikes, andaccidents can cause disruption of process control.

Refer to Section 5 to select defaults for failure conditions.

HAZARDOUS LOCATION INSTALLATIONS (FLAMMABLE ATMOSPHERES)

The Type PTSP Platinum Standard Smart Pressure Transmit-ter must not be located in a hazardous (classified) locationunless factory marked as suitable for that location. This equip-ment must be installed and operated according to Installing a4 to 20 mA Transmitter in a Hazardous Location.

SELECTING DEFAULTS3 - 8 WBPEEUI110506A0

Page 38: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SECTION 4 - CALIBRATION

WBPEEUI

INTRODUCTION

This section identifies the calibration status of the unit andprovides the calibration check procedures. Calibration andvalidation procedures using both the Type STT terminal andthe EZ CAL option appear here.

CALIBRATION PROCEDURES

If the standard configuration is ordered, the Type PTSP pres-sure transmitter will be set close to a zero based full scalespan. A custom calibration can be factory supplied or imple-mented in the field.

The Type PTSP pressure transmitter operates in either theanalog mode or the digital mode. Calibration procedures differdepending on the selected mode of operation.

The analog mode of operation allows both a complete benchcalibration and a D/A adjustment. The D/A adjustment com-pensates for slight inaccuracies in the four to 20-milliamperecurrent loop (or in receiving devices such as recorders). Usethis procedure only when the system has first been installed orif something in the four to 20-milliampere current loop haschanged. The digital mode of operation allows only a benchcalibration.

NOTE: This section is meant as a generalized guide and does notgo through the step-by-step procedures required of the Type STTterminal. Although the menus that appear on the Type STT terminaldisplay are easy to follow, consult the Type STT Smart TransmitterTerminal Instruction while performing these procedures.

Equipment Required for Calibration

• DC power supply, 24, ±1 VDC (recommended).

• Digital multimeter (DMM) - 4-½ digit display minimumwith an accuracy at least four times greater than that ofthe transmitter (Tables 1-5 and 1-6).

• 250-ohm (±0.01-percent) resistor, ½-watt minimum.

WARNING

Explosionproof/dust-ignitionproof installations and intrinsi-cally safe installations in Class II or Class III hazardous loca-tions require that the assembly be kept tight while circuits arelive unless the location is known to be nonhazardous at thetime.

INTRODUCTION110506A0 4 - 1

Page 39: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

CALIBRATION

• Pressure source with an accuracy at least four timesgreater than that of the transmitter (Tables 1-5 and 1-6).

• Type STT Smart Transmitter Terminal.

Analog Mode Calibration

Use these procedures for validation of transmitter calibrationbefore installation, after an inadvertent overpressure condi-tion, or after the replacement of components. If the checkoutindicates an incorrect calibration, continue with the procedureto calibrate the transmitter.

BENCH CALIBRATION

1. Mount and connect the transmitter in a calibration setupsuch as the one shown in Figure 4-1.

NOTE: Turn the - (negative) test terminal jumper screw ½-turncounterclockwise.

2. Orient the transmitter in the same position as the finalinstallation.

3. Allow the transmitter to stabilize for 15 minutes afterpower up.

4. Connect the pressure source to the cell.

5. Apply a pressure to the cell equal to the configured ordesired lower range value.

6. The milliammeter should read 4.000 mA plus or minus thetolerance for the particular transmitter listed in Table 4-1.

Figure 4-1. Calibration Setup (Typical)

T02610 A

D C P OW ERS U PP LY

+

+

A M M E TE R

S TT

JU M P ERS C R EW

C A SEG RO U N D IN GTER M IN A L

250 ±0.01%0.5 WM IN

Ω

TB1

+ +

–TE S T

P W R /O U TP U T

CALIBRATION PROCEDURES4 - 2 WBPEEUI110506A0

Page 40: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

CALIBRATION

WBPEEUI

7. Apply a pressure to the cell equal to the configured ordesired upper range value.

8. The milliammeter should read 20.000 mA plus or minusthe tolerance for the particular transmitter listed in Table 4-1.

9. If the output is not within the limits specified in Steps 6and 8, calibrate the unit. To do so, press the CALIBRATE keyon the Type STT terminal and follow the procedure in the TypeSTT Smart Transmitter Terminal Instruction.

10. Turn the - (negative) test terminal jumper screw clockwiseuntil tight.

D/A ADJUSTMENT (FINE TUNING THE ANALOG LOOP)

This procedure does not require removal of the covers from theelectronics housing. Compensation for slight inaccuracies inthe four to 20-milliampere current loop (or in receiving devicessuch as recorders) is accomplished by accessing the calibra-tion menu on the Type STT terminal while it is connected tothe target Type PTSP pressure transmitter. This proceduredoes not adjust the zero or span of the transmitter and onlyapplies when first installing the system or if something in thefour to 20-milliampere current loop has changed. To adjustthe zero of the transmitter, refer to REZERO PROCEDURE.

Either connect the DMM, set to measure DC milliamperes, inseries with the four to 20-milliampere current loop, or make aparallel connection across the precision 250-ohm resistorshown in Figure 2-4, with the DMM set to measure VDC. Withthe latter setup, the four to 20-milliampere output corre-sponds to one to five VDC.

NOTES:1. These notes only apply when measuring VDC across the250-ohm resistor shown in Figure 2-4.

Table 4-1. Analog ModeCalibration Tolerances

TypeTolerance

mAVDC (across

precision resistor)

PTSPAG 0.016 0.004

PTSPAJ

PTSPGG

PTSPGJ

PTSPAE 0.032 0.008

PTSPGF

CALIBRATION PROCEDURES110506A0 4 - 3

Page 41: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

CALIBRATION

2. The loop resistor must have a tolerance of 0.01 percent or bet-ter in order for this procedure to be valid.

3. If a resistor value other than a 250 ohms is used, the voltageoutput will be different according to Ohms law:

4. Throughout this procedure, the voltage values, based on a250-ohm resistor, will be shown in parentheses following the milliam-pere values.

1. Press the CALIBRATE key on the Type STT terminal.

2. Use the up arrow and down arrow keys to scroll throughthe menu and select D-A ADJUSTMENT.

3. Press the ENTER key.

4. The instruction, ADJUST TO 4 mA THEN HIT ENTERappears on the display. Use the up arrow and down arrow keysto adjust the output to 4.000 mA (1.000 VDC) plus or minusthe tolerance for the particular transmitter listed in Table 4-1.If using a receiving device (e.g. recorder), adjust for azero-percent indication.

5. Press the ENTER key.

6. The message, ADJUST TO 20 mA THEN HIT ENTER appearson the display. Use the up arrow and down arrow keys toadjust the output to 20.000 mA (5.000 VDC) plus or minus thetolerance for the particular transmitter listed in Table 4-1. Ifusing a receiving device, adjust for a 100-percent indication.

7. Press the ENTER key.

Digital Mode Calibration

1. Mount and connect the transmitter in a calibration setupsuch as the one shown in Figure 4-1.

NOTE: Turn the - (negative) test terminal jumper screw ½-turncounterclockwise.

2. Orient the transmitter in the same position as the finalinstallation.

3. Connect the pressure source to the cell.

4. Apply a pressure to the cell equal to the configured ordesired lower range value.

5. Since the transmitter configuration is for digital operation,the milliammeter should read below four milliamperes.

V I R×=( )

CALIBRATION PROCEDURES4 - 4 WBPEEUI110506A0

Page 42: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

CALIBRATION

WBPEEUI

6. Press the OUTPUT key on the Type STT terminal, thenselect MONITOR OUTPUT.

7. The Type STT terminal should display 0.00% plus orminus the tolerance for the particular transmitter listed inTable 4-2.

8. Apply a pressure to the cell equal to the configured ordesired upper range value.

9. Since the transmitter is configured for digital operation,the milliammeter should read below four milliamperes.

NOTE: If the four to 20-milliampere output changes with respect topressure, then the unit is not in the digital mode. To enter this mode,press the CONFIGURE key on the Type STT terminal and follow thestep-by-step procedures in the Type STT Smart Transmitter Ter-minal Instruction. Use the SEND CONFIG key to download thenew configuration to the transmitter (refer to Section 5).

10. Press the OUTPUT key on the Type STT terminal and selectMONITOR OUTPUT.

11. The Type STT terminal should display 100.00% (±0.15%).

12. If the digital output is not within the limits stated inSteps 7 and 11, calibrate the transmitter. To do so, press theCALIBRATE key on the Type STT terminal and follow the pro-cedures in the Type STT Smart Transmitter TerminalInstruction.

13. Turn the - (negative) test terminal jumper screw clockwiseuntil tight.

RERANGING THE ANALOG OUTPUT

By pressing the RERANGE key on the Type STT terminal, thecurrent (four to 20-milliampere) output can be quicklyreranged to represent a different portion of the input span.This procedure bypasses the need to completely configure theType PTSP pressure transmitter. Damping, engineering units,

Table 4-2. Digital ModeCalibration Tolerances

Type Tolerance (%)

PTSPAG 0.10

PTSPAJ

PTSPGG

PTSPGJ

PTSPAE 0.20

PTSPGF

RERANGING THE ANALOG OUTPUT110506A0 4 - 5

Page 43: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

CALIBRATION

and the temperature alarm can also be adjusted duringrerange.

NOTE: The transmitter output is based on the values entered in thisprocedure. The terminal will not reject invalid ranges; therefore, it isimperative that the operator know the range limits specified for thetransmitter. Refer to Table 1-2 for the proper ranges.

REZERO PROCEDURE

This procedure zeroes the transmitter only and does not com-pensate for slight inaccuracies in the four to 20-milliamperecurrent loop. To adjust for these inaccuracies, refer to D/AADJUSTMENT (FINE TUNING THE ANALOG LOOP).

By pressing the REZERO key on the Type STT terminal, thetransmitter can be zeroed without performing a completebench calibration. There is no effect on the span of thetransmitter.

VERIFYING CALIBRATION WITH THE EZ CAL OPTION

NOTE: The EZ CAL option is for zero and span validation only. Donot use it to make large adjustments to the zero or span of the trans-mitter. The EZ CAL option provides no means to indicate if an erroris made.

1. If not installed, refer to the Section 3 for installationprocedures.

2. Open the dust cover on the EZ CAL option.

3. Connect the pressure source to the cell.

4. Apply a pressure to the cell equal to the configured lowerrange value.

5. Turn and hold the adjustment screw on the EZ CAL optionin the zero direction (indicated on the EZ CAL option) for atleast three seconds. The transmitter automatically adjusts theoutput to zero percent.

6. Apply a pressure to the cell equal to the configured upperrange value.

7. Depress the span lock and turn and hold the adjustmentscrew on the EZ CAL option in the span direction (indicated onthe EZ CAL option) for at least three seconds. The transmitterautomatically adjusts the output to 100 percent.

REZERO PROCEDURE4 - 6 WBPEEUI110506A0

Page 44: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SECTION 5 - OPERATING PROCEDURES

WBPEEUI

INTRODUCTION

This section addresses start-up procedures, configuration, andmonitoring of the Type PTSP Platinum Standard Smart Pres-sure Transmitter and the procedures that make it operational.

OPERATOR INTERFACE

The Type PTSP pressure transmitter can be monitored andcontrolled using the Type STT terminal. Connect the Type STTterminal across the signal wires in a parallel connection(Figs. 2-4 and 2-5) wherever there is convenient access. (Forpoint-to-point wiring, the Type STT terminal must be con-nected between the transmitter and the 250-ohm resistor.)Refer to the Type STT Smart Transmitter TerminalInstruction for detailed information and data entryprocedures.

NOTE: All of the menu items that appear on the Type STT terminalmay not apply to the Type PTSP pressure transmitter.

CONFIGURATION PROCEDURE

Configuration of the transmitter includes defining an identifi-cation tag, primary lower and upper range values, digital oranalog mode of operation, primary engineering units, second-ary engineering units and secondary lower and upper rangevalues, output parameters, cell temperature alarm limits, anda damping constant. Use the CONFIGURE key and follow thestep-by-step procedures in the Type STT Smart TransmitterTerminal Instruction. Once a configuration has been savedin the Type STT terminal, download it to a connected transmit-ter using the SEND CONFIG key. The remainder of this sectionexplains the configuration parameters.

ID Tag

The transmitter ID tag is a 14-character alphanumeric tag thatcan be programmed into the transmitter. It is different thanthe transmitter address. The ID tag is entered during configu-ration for identification purposes. To display the ID tag on theterminal screen, press the STATUS key.

Select Mode

Select either the analog mode or the digital mode. If the digitalmode is selected, the transmitter does not output a four to20-milliampere signal in proportion to the input. The output

INTRODUCTION110506A0 5 - 1

Page 45: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

OPERATING PROCEDURES

will be locked below four milliamperes. If the analog mode isspecified instead, the transmitter will provide a four to20-milliampere output signal.

Although there are no harmful effects to the transmitter or theloop, do not connect a transmitter configured for the analogmode to a field bus. The field bus will not support analog out-put devices.

Channel Number

The transmitter address (displayed as CHANNEL # on the TypeSTT terminal display) is used for field bus transmitters. Eachtransmitter on the field bus must have a separate address. Theaddress range is one through 15.

Transmitter Type

This menu displays types of Bailey-Fischer & Porter smarttransmitters. Choose the PTS selection by using the up arrowand down arrow keys and then pressing the ENTER key.

Output Type

The output of the transmitter must be specified as linear withrespect to the input. Also, the output can be specified as thevolume of a spherical or flat ended horizontal tank, or as afunction generator that follows a six-segment linear function.If a function generator is chosen, five input and output pointsmust also be specified as a percent of input. Note that the firstand the last point on the curve are assumed to be zero and100 percent respectively. Program five other points betweenthese two values (refer to Function Generator in Section 2).

Output Action

A transmitter in the normal-acting mode has an output thatincreases with increasing input. The output of a transmitter inthe reverse acting mode decreases with increasing input.

Damping Adjustment

Damping adjustments have no effect on the calibration oraccuracy of the transmitter; however, damping can be used tosmooth out a fluctuating process signal. Damping is adjust-able and provides single (1τ) time constant values from 0.00 to32.00 seconds. A damping adjustment of 32.00 seconds wouldbe used for a very noisy signal and a damping adjustment of0.00 seconds would be used for an extremely quiet signal.

CONFIGURATION PROCEDURE5 - 2 WBPEEUI110506A0

Page 46: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

OPERATING PROCEDURES

WBPEEUI

Primary Engineering Units

Primary engineering units are programmable. The selectionsappearing on the Type STT terminal display are:

• iH20 — inches of water.• mmHG — millimeters of mercury.• cmH20 — centimeters of water.• PSI — pounds per square inch.• MPA — megapascals.• kPA — kilopascals.• BARS — bars.• mBARS — millibars.• Kgcm2 — kilograms per square centimeter.

Primary Upper and Lower Range Values

The range of the transmitter may be set electronically to anyvalue from zero to 100 percent (-100 kPa (-14 psi) to 100 per-cent for Type PTSPGF pressure transmitters) of the upperrange limit to suit a specific application, provided the valuesare acceptable to the transmitter (refer to Table 1-2 for thenominal and minimum ranges of the transmitters).

Startup and Failure Conditions

On power up, there is a four-second initialization period dur-ing which the output of the transmitter is in transition fromnonpowered (no current output) and an output of either above100 percent or below zero percent as defined duringconfiguration.

If in the analog mode, INITIALIZE LOW sets the output to belowzero percent (approximately 3.7 milliamperes) while INITIALIZEHIGH sets the output to above 100 percent (approximately22 milliamperes).

If in the digital mode, INITIALIZE LOW sets the output to belowzero percent (approximately 3.7 milliamperes) while INITIALIZEHIGH sets the output to above 100 percent. However, the cur-rent stays at approximately 3.7 milliamperes. The default ini-tialization value is low (below zero percent). After initialization,the output ramps up or down to the correct value.

If during its continual diagnostics the microcomputer detectsan error that is fatal to the transmitter or system, the trans-mitter output goes to a predetermined fail level. This level

WARNINGThe outputs of smart devices change to a fixed value duringinitialization and detected failure conditions. These valuesmust be selected by the user to ensure safe operation.

CONFIGURATION PROCEDURE110506A0 5 - 3

Page 47: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

OPERATING PROCEDURES

must be selected during configuration. The default value is low(below zero percent). Table 6-1 shows what types of errorscause the transmitter to enter the fail mode.

NOTE: For a transmitter in the normal acting mode, output corre-sponding to zero-percent input would be four milliamperes and out-put corresponding to 100-percent input would be 20 milliamperes.For a transmitter in the reverse acting mode, output correspondingto zero-percent input would be 20 milliamperes and output corre-sponding to 100-percent input would be four milliamperes.

Secondary Engineering Units

Secondary engineering units are programmable. These unitsare in a free form format of seven characters. Program anyseven characters into the transmitter, such as MA or GAL/HR.These units are used in conjunction with the secondary lowerand upper range numeric values.

Use the up arrow and down arrow keys or the decimal numberkeys to select the secondary units.

NOTE: The secondary engineering units are left justified when dis-played on the local LCD. If desired, enter dummy characters to cen-ter or right justify the display.

Secondary Lower and Upper Range Values

The secondary lower and upper range values of the transmittercan be set to any range within ±99999. These ranges can bemonitored by the Type STT terminal or displayed on theoptional LCD of the transmitter. The ranges are a function ofthe output of the device. The output can be polled from thedevice or displayed on the optional LCD. These ranges have noeffect on the calibration of the transmitter and are used toreport the output of the transmitter in user-defined units.

Cell Temperature Alarm Limits

This sets the alarm limits for the cell temperature. The defaultvalues are -50.00-degrees Celsius and +120.00-degrees Cel-sius. Program the alarm limits anywhere between these twovalues.

Get Config Key

Once a Type PTSP pressure transmitter has been configured,the configuration that has been loaded into the transmittermemory may be reviewed by pressing the GET CONFIG key onthe Type STT terminal (refer to the Type STT Smart Trans-mitter Terminal Instruction). The configuration is not storedin the Type STT terminal memory unless YES is chosen when

CONFIGURATION PROCEDURE5 - 4 WBPEEUI110506A0

Page 48: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

OPERATING PROCEDURES

WBPEEUI

STORE THIS CONFIGURATION? appears on the Type STT ter-minal display.

Send Config Key

The SEND CONFIG key allows selection of a configuration fromthe terminal memory to be sent to the transmitter (refer to theType STT Smart Transmitter Terminal Instruction).

View Config Key

Pressing the VIEW CONFIG key allows the parameters of theworking configuration to be viewed, but not changed (refer tothe Type STT Smart Transmitter Terminal Instruction).

OPERATIONAL FUNCTIONS

Operational functions for the Type PTSP pressure transmitterare performed by using the SPECIAL FEATURE, OUTPUT,STATUS, and F1 keys on the Type STT terminal.

Special Feature Key

Press the SPECIAL FEATURE key on the Type STT terminaland follow the procedures in the Type STT Smart Transmit-ter Terminal Instruction.

FIX OUTPUT/CANCEL FIX OUTPUT

For system troubleshooting purposes, the Type PTSP pressuretransmitter output can be set to a constant, specified as a per-cent of the four to 20-milliampere signal. Press the SPECIALFEATURE key and select FIX OUTPUT from the menu of theType STT terminal (refer to the Type STT Smart TransmitterTerminal Instruction). To cancel FIX OUTPUT, press the SPE-CIAL FEATURE key, then select CANCEL FIX OUTPUT.

LOCAL LCD SETUP

The local LCD can be programmed to display output in percentand user-defined secondary engineering units, input in pri-mary engineering units, cell temperature, and transmitter IDtag.

STANDARD CONFIGURATION

This function allows the configuration of the transmitter to bechanged back to the original configuration entered at thefactory.

OPERATIONAL FUNCTIONS110506A0 5 - 5

Page 49: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

OPERATING PROCEDURES

Output Key

Press the OUTPUT key on the Type STT terminal and followthe procedures in the Type STT Smart Transmitter Termi-nal Instruction.

MONITOR OUTPUT

The Type PTSP pressure transmitter output can be monitoredby pressing the OUTPUT key on the Type STT terminal, andchoosing MONITOR OUTPUT from the display menu (refer tothe Type STT Smart Transmitter Terminal Instruction).The output displays as a percent, rather than in milliamperes,and updates once per second.

MONITOR INPUT

The input to the Type PTSP pressure transmitter can be moni-tored by using the OUTPUT key on the Type STT terminal andselecting MONITOR INPUT from the displayed menu (refer tothe Type STT Smart Transmitter Terminal Instruction).The input displays in engineering units and updates once persecond.

MONITOR CELL TEMPERATURE

By pressing the OUTPUT key on the Type STT terminal andselecting TEMPERATURE, the Type STT terminal displays theambient temperature of the cell in degrees Celsius.

MONITOR SECONDARY ENGINEERING UNITS

The secondary engineering units variable can be monitored bythe Type STT terminal by pressing the OUTPUT key and select-ing SECONDARY UNITS. The output reflects the output of thetransmitter, but it is a percentage of the secondary lower andupper range values and displays in secondary engineeringunits.

Example: If the secondary lower range value is 10.0 gal/hr, the secondary upper rangevalue is 100.0 gal/hr and the output of the transmitter is at 75 percent, the dis-play reads 75-percent range or 77.5 GAL/HR.

Status Key

The status of the transmitter, determined from results of thecontinuous self-diagnostics, can be checked using the STATUSkey on the Type STT terminal. Refer to Section 6 for the correc-tive action necessary.

OPERATIONAL FUNCTIONS5 - 6 WBPEEUI110506A0

Page 50: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

OPERATING PROCEDURES

WBPEEUI

F1 Key

The Type STT terminal allows configurations to be copied toand from Type STC cartridges. Multiple configuration copiesoverwrite existing configurations on the terminal or cartridge,regardless of the amount of memory space available. Performthis function by pressing the F1 key on the Type STT terminal.Refer to the Type STT Smart Transmitter TerminalInstruction for more information.

CONFIGURATION LOCKOUT PROCEDURE

The Type PTSP pressure transmitter has a lockout feature.When engaged, configuration and calibration information isunalterable. This has no effect on the monitoring of transmit-ter functions. Refer to Figure 5-1 for the location of the jumperon the amplifier assembly.

1. Remove power from the transmitter.

2. Remove the left housing cover (Fig. 2-1) from thetransmitter.

3. If there is an optional meter, remove the four indicatorscrews (Fig. 8-1) and unplug it from the amplifier assembly. Ifthere is no optional meter, skip to Step 4.

4. Use needle nose pliers to change the jumper position. Posi-tion B locks the configuration and Position A enablesconfiguration.

5. Reverse this procedure to put the transmitter back intoservice.

CONFIGURATION LOCKOUT PROCEDURE110506A0 5 - 7

Page 51: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

OPERATING PROCEDURES

Figure 5-1. Lockout Jumper

LOC KO U T

A | B

J1

J1EN A BLE

C O N FIG U R ATIO N

J1

J1

LOC KC O N FIG U R ATIO N

C U STO M ERSET TIN G

T0189 0B

A | B

A | B

A | B

CONFIGURATION LOCKOUT PROCEDURE5 - 8 WBPEEUI110506A0

Page 52: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SECTION 6 - TROUBLESHOOTING

WBPEEUI

INTRODUCTION

If the Type PTSP Platinum Standard Smart Pressure Transmit-ter cannot implement a command, the Type STT terminal isprompted. Pressing the STATUS key on the Type STT terminalcauses it to display an error message relating to the existingproblem. If an error occurs, but is corrected before theType STT terminal is connected (such as a temporary over-pressure condition), the error is stored and is indicated oncethe terminal is connected and the STATUS key is pressed.Table 6-1 shows these error messages, the probable cause ofthe malfunction and the recommended corrective action.Table 6-2 lists possible output problems and the recom-mended corrective action. A troubleshooting flowchart appearsin Figures 6-1, 6-2, and 6-3.

NOTE: More than one error can be present on one transmitter; how-ever, only one error at a time can be displayed on theType STT terminal. As such, error messages on the Type STT termi-nal are based on a priority structure. The error holding the most sig-nificance to the system will be displayed first and any others thatfollow will appear according to their rank on the priority structure.

ERROR MESSAGES AND CORRECTIVE ACTION

This section contains all of the possible error messages per-taining to the Type PTSP pressure transmitter that can displayon the Type STT terminal. Table 6-1 lists the messages inalphabetical order and has four columns:

1. The Message column lists the errors (alphabetically)exactly as they appear on the smart terminal.

2. The Fail Mode column indicates if the error causes theType PTSP pressure transmitter to enter the fail mode. Refer toStartup and Failure Conditions in Section 5 for moreinformation.

3. The Probable Cause column provides a brief explanationof the cause of the error.

4. The Corrective Action column lists corrective actions totake for each error.

INTRODUCTION110506A0 6 - 1

Page 53: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

TROUBLESHOOTING

Table 6-1. Error Messages

MessageFail

ModeProbable Cause Corrective Action

Calibration required No Cell not calibrated with present amplifier board.

Calibrate transmitter.

Cannot save, configura-tion too large

No Transmitter type not sup-ported by Type STT terminal firmware revision level.

Consult Bailey Controls Company regarding latest Type STT terminal firmware revision.

Cell characterization board EEPROM failure

Yes Damage to cell characteriza-tion board.

Turn Type STT terminal off and then on. If error still exists after reset, replace cell and characterization board assembly (Section 8).

Cell temperature over alarm

No Cell temperature under/over alarm limit.

Correct temperature problem.

Cell temperature under alarm

Change alarm value. Refer to Type STT Smart Transmitter Terminal Instruction.

Cell temperature over limit

No Cell temperature input exceeds upper factory limit.

Remove source of temperature extreme.

Cell temperature under limit

No Cell temperature input exceeds lower factory limit.

Remove source of temperature extreme.

Config “tagname” already exists

No Attempted to copy configura-tion to cartridge or transmitter where it already exists.

Erase old configuration before copying new one. Refer to Type STT Smart Transmitter Terminal Instruction.

Damaged cell or charac-terization board

Yes Cell or characterization board disconnected.

Make sure cell, characterization board, and amplifier assembly are mounted properly.

Cell or characterization board damaged.

Replace cell and characterization board assembly (Section 8).

Electronics temperature measurement failure

No Hardware failure of on-board temperature sensor.

Replace amplifier assembly (Section 8).

Electronic temperature out of range

No Temperature inside electron-ics housing exceeds limit set at factory.

Remove source of temperature extreme.

Error! Attempt to config-ure duplicate address

No Attempt was made to assign analog mode transmitter address on FBM.

Be sure transmitter is in correct mode (analog or digital). Use VIEW key on Type STT terminal to verify mode. Refer to Type STT Smart Transmitter Terminal Instruction for details.

Attempt was made to assign digital mode transmitter to occupied FBM address.

Assign transmitter to unoccupied address or channel number of FBM.

ERROR MESSAGES AND CORRECTIVE ACTION6 - 2 WBPEEUI110506A0

Page 54: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

TROUBLESHOOTING

WBPEEUI

Field device can't execute command: FBM on-line

No The Type STT terminal cannot change any transmitter parameters while the field bus is active.

Transmitter must be brought off-line. This can be done from the MFC/MFP module by tuning the function code.

NOTE: To bring transmitter offline, the FBM can be unplugged from the rack. Be aware that by doing this, communi-cation is lost for all other transmitters on the bus. When FBM is unplugged, there is a two-minute time-out period until the Type STT terminal will be allowed to change parameters. After the two-minute period, the transmitter allows the Type STT terminal access.

Field device can't execute command: Invalid com-mand

No Incorrect syntax. Wrong transmitter type selected in configuration.

Excessive line noise. Check line noise. Use oscilloscope to determine if line noise is excessive.

Type STT terminal failure. Verify Type STT terminal operation. Verify by using another Type STT ter-minal known to be operational.

Field device can't execute command: Lockout engaged

No Unable to configure or calibrate.

Hardware lock active. Refer to CON-FIGURATION LOCKOUT PROCE-DURE in Section 5.

Field device can't exe-cute: Data out of range

Yes Transmitter sent data that is out of acceptable range.

Press VIEW key on Type STT terminal to verify parameters of configuration and consult appropriate device instruc-tion for correct parameters.

Field device configuration does not match STT's

No Configuration of transmitter does not exactly match corre-sponding configuration in Type STT terminal.

Rerange was executed without updat-ing Type STT terminal configuration. Perform GET CONFIG (Section 5).

Field device main elec-tronics EEPROM failure

Yes Memory problem. Remove power from transmitter and reapply. If error still exists after reset, replace amplifier assembly (Section 8).

Field device input over range

No Input exceeds cell specification.

Correct process input.

Field device input under range

Table 6-1. Error Messages (continued)

MessageFail

ModeProbable Cause Corrective Action

ERROR MESSAGES AND CORRECTIVE ACTION110506A0 6 - 3

Page 55: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

TROUBLESHOOTING

Field device not responding

No Type STT terminal not con-nected properly.

Check Type STT terminal wiring con-nections. Refer to Figure 2-4 or 2-5 for correct wiring arrangements.

Short in communication wire. Perform a continuity check to deter-mine if a short exists.

Transmitter does not have minimum of 17 VDC across inputs.

Correct power problem.

Not using correct communica-tion method.

Turn off Type STT terminal. Turn on and select FSK/BUS and press ENTER again. ID tags appear on screen. Select ID tag of transmitter, or select one appearing within brackets if unsure of ID tag. Press ENTER. Press STA-TUS key. If this error message is still present, go to next step.

Transmitter or Type STT ter-minal defective.

If available, verify that Type STT termi-nal is functional by connecting to another transmitter. Replace Type STT terminal if not functional.

If Type STT terminal is functional, replace amplifier assembly in transmit-ter (Section 8).

Field device not sup-ported by cartridge or handheld

No Field device type not sup-ported by release of Type STT terminal firmware and cartridge.

Check to see if correct cartridge is inserted into Type STT terminal.

Field device output is fixed or in adj. mode

No Type STT terminal turned off while 4 to 20-mA output was being calibrated.

Power down transmitter and power up transmitter.

Transmitter cannot execute command because of fix output.

Take transmitter out of fix output. Refer to Type STT Smart Transmitter Ter-minal Instruction.

Field device RAM failure Yes Memory problem. Replace amplifier assembly (Section 8).

Input applied incorrectly, calibration failure

No Calibrated input outside fac-tory allowable limits.

Correct signal and calibrate (Section 8).

Span & zero key misoper-ation

No Misoperation of EZ CAL option.

Try again.

Damaged EZ CAL option. Replace EZ CAL option (Section 8).

Damaged amplifier assembly. Replace amplifier assembly (Section 8).

Sorry, that routine not implemented in ROM D10

No Cartridge not compatible. Purchase latest Type STT terminal firmware. Refer to spare parts lists in Type STT Smart Transmitter Termi-nal Instruction.

Unknown error No Transmitter reported an error not understood by Type STT terminal.

Contact Bailey Technical Support.

Table 6-1. Error Messages (continued)

MessageFail

ModeProbable Cause Corrective Action

ERROR MESSAGES AND CORRECTIVE ACTION6 - 4 WBPEEUI110506A0

Page 56: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

TROUBLESHOOTING

WBPEEUI

Table 6-2. Output Troubleshooting

Fault Probable Cause Corrective Action

High output Transmitter electronics connections.

Make sure all pins and receptacles are clean.

Check cell connections.

Transmitter electronics failure. Press STATUS key and refer to Table 6-1 and Figure 6-1.

Erratic output Cell. Press STATUS key and refer to Table 6-1 and Figure 6-1.

Loop wiring. Check for intermittent shorts, open circuits, and multiple grounds.

Process fluid pulsation. Increase damping.

Install dampers in pressure piping.

Pressure piping. Check for entrapped gas in liquid lines and for liquid in dry lines.

Transmitter electronics connections.

Make sure pins and receptacles are clean.

Check cell connections.

Transmitter electronics failure. Press STATUS key and refer to Table 6-1 and Figure 6-1.

Low output or no output Power supply. Check output of power supply.

Loop wiring. Check for shorts, open circuits, and multiple grounds.

Check polarity of connections.

Check loop impedance.

Process connection. Check installation and condition of process connection.

Note any changes in process prop-erties that may affect output.

Pressure piping. Check that pressure connection is correct.

Check for leaks or blockage.

Check that blocking valves are fully open and bypass valves are tightly closed.

Check for entrapped gas in liquid lines and for liquid in dry lines.

Check that density of fluid in pres-sure piping is unchanged.

Check for sediment at transmitter process connection.

Device in digital mode. If analog output is desired, config-ure the transmitter using CONFIG-URE key, then press SEND CONFIG.

ERROR MESSAGES AND CORRECTIVE ACTION110506A0 6 - 5

Page 57: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

TROUBLESHOOTING

Low output or no output (continued) Transmitter electronics connections.

Check for shorts in cell leads.

Make sure pins and receptacles are clean.

Check cell connections.

Transmitter electronics failure. Press STATUS key and refer to Table 6-1 and Figure 6-1.

Cell. Press STATUS key and refer to Table 6-1 and Figure 6-1.

Figure 6-1. Troubleshooting Flowchart (Sheet 1 of 3)

Table 6-2. Output Troubleshooting

Fault Probable Cause Corrective Action

C O M PA R EF U N C T IO N C O D E

C O N F IG . W IT HT R A N S M IT TE R

C O N F IG .

R E T R IEV E I/OS TATU S R E P O R T

O F C O R R E C T FB M

Y E S

Y E S

Y E S

Y E S

Y E S

Y E S

Y E SY E S

Y E S

Y E S

Y E S

Y E S

Y E S

Y E SN O

N O

N O

N O

N O

N O

N O

N O

N O

N O

N O

N O

N O

N O

D E T E R M IN E W H YP R OT E C TIO N

W A S IN S TA L LE D

D E T E R M IN E IFA P P LIC ATIO N

R E Q U IR E SF IXE D O U T P U T

P E R F O R MC A L IB R ATIO N

C H E C K

E R R O R S TIL LE X IS T?

W RO N GT R A N S M IT TE R

T Y P E?

X M T T RC O N N E C T E DTO F B M O R

A S I?

C O N F IG U R ATIO NL O C KO U T JU M P E R

S E T ?

R E S P O N D IN G ? IN P U TFA ILU R E ?

C H A N N E LFA ILU R E /O U TO F R A N G E ?

T E M P E R AT U R ER A N G E

E X C E E D E D ?

C A L IB R ATIO NE R R O R ?

OV E R -P R E S S U R E ?

N OTD O W N L O A D E D ?

O U T P U TF IXE D ?

F B MH AV E S TATU S

E R R O R S ?

N O F B MR E S P O N S E /

W RO N G M O D U L ER E S P O N S E ?

T 02 2 37 A

A

A

B

B

C O M M U N IC AT IO NM AY PA S S TH RO U G H

H IG H N O IS EE N V IRO N M E N T

C H E C K TU /T MC A B LIN G .

R E P LA C E F B M IFC A B LIN G IS G O O D

C H E C K FB MIN P U T

C A L IB R ATIO N

C H E C K FB M JU M P E RA N D S W IT C H

S E T TIN G S . R E P L AC EF B M IF J U M P E R AN DS W IT C H S E T TIN G S

C H E C K G O O D.

R E F E R TOE R R O R M E S S AG E

TA B L E

C O R R E C T O U T-O F -R A N G E C O N D IT IO N

O R IN S TA L L N E WR A N G E X M T T R

C O R R E C TE N V IRO N M E N T

TO W ITH INS P E C IFIC ATIO N

C O N TAC T B A IL E YT E C H N IC A LS U P P O RT

S TA RT

ERROR MESSAGES AND CORRECTIVE ACTION6 - 6 WBPEEUI110506A0

Page 58: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

TROUBLESHOOTING

WBPEEUI

Figure 6-2. Troubleshooting Flowchart (Sheet 2 of 3)

Y E S

Y E S

Y E S

Y E S

Y E S

Y E S Y E S

Y E S

N O

N O

N O

N O

N O

N O

N O

N O

T 02 2 38 A

D O N E

D O N E

1 2-V D CM IN . SU PP LY

AC R O S SIN P U T S?

2 50 INC U R R E N T LO O P ?

(E X C E P T INF IEL D B U S

M O D E )

ΩX M T T R

C O M M U N IC AT E SW IT H S T T?

C O M M U N IC AT IO NIN T ER M ITT E N T ?

S T TC O N N E C T E D

AC R O S S S IG N A LW IR ES ?

P OW E R S U P P LYP O L A R IT Y C O R R E C T

TO X M T T R ?

P R O B LE M S T ILLE X IS T?

P R O B LE M S T ILLE X IS T?

A

BC O R R E C T P OW E R

S U P P LY F O R1 2-V D C M IN IM U M

C H A R G E S T TB AT T E R IES

R E P LA C EA M P L IFIE RA S S E M B LY

A D D R E Q U IR E DL O O P R E S IS TAN C E

F O RC O M M U N IC AT IO N

C O N N E C TS T T

P R O P E R LYC O N N E C T

P OW E R S U P P LY

C O N TAC T B A IL E YT E C H N IC A LS U P P O RT

C

ERROR MESSAGES AND CORRECTIVE ACTION110506A0 6 - 7

Page 59: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

TROUBLESHOOTING

Figure 6-3. Troubleshooting Flowchart (Sheet 3 of 3)

R E P LA C E L C DB O A R D. IF LC D B O A R D

N OT D E F E C TIV E ,R E P LA C E A M P LIF IER

A S S E M B LY

C O R R E C TT E M P E R AT U R E

P R O B LE M

P R E S S S P E C IA LF E AT U R E KE Y O NS T T A N D S E LE C TF IX O U T P U T. S E T

O U T P U T TO D R IF TVA L U E

B R IN G C O M P L E T EU N IT TO T E M P. W H ER E

P E R F O R M A N C E ISP O O R . P R E SS O U T P U T

K E Y O N ST T A N DR E P O RT IN P U T

R E P LA C E C EL L A N DC H A R AC T E R IZ AT IO N

B O A R D A S S E M B LY

R E P LA C EA M P L IFIE RA S S E M B LY

C O N TAC T B A IL EYT E C H N IC A LS U P P O RT

R E P LA C EA M P L IFIE RA S S E M B LY

R E P LA C E C EL L A N DC H A R AC T E R IZ AT IO N

B O A R D A S S E M B LY

C O N TAC T B A IL EYT E C H N IC A LS U P P O RT

R E P LA C EA M P L IFIE RA S S E M B LY

Y E S

Y E S Y E S Y E S

Y E S

Y E SY E S

Y E S

Y E S

Y E S

Y E SN O

N O N O N O

N ON O

N O

N O

N O

N O

N OL C DF U N C T IO N IN G

P R O P E R LY ?

A M B IE N T T E M P.W IT H INS P E C S ?

P R O B LE M S T ILLE X IST ?

P R O B LE M S T ILLE X IST ?

P R O B LE M S T ILLE X IST ?

P R O B LE M S T ILLE X IST ?

O U T P U T D R IF T IN GO R E R R AT IC ?

R E P O RT E D IN P U TC O R R E C T ?

4 -20 m A O U T PU TC O R R E C T AT TH IS

T E M P ?

P R O B LE M S T ILLE X IST ?

O U T P U TS TA B L E?

T 02 23 9 A

B

C C

D O N E

ERROR MESSAGES AND CORRECTIVE ACTION6 - 8 WBPEEUI110506A0

Page 60: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SECTION 7 - MAINTENANCE

WBPEEUI

INTRODUCTION

The reliability of any stand-alone product or control system isaffected by the maintenance of the equipment. Bailey-Fischer& Porter recommends that all equipment users practice a pre-ventive maintenance program that will keep the equipmentoperating at an optimum level.

NOTE: Refer to the IInstalling a 4 to 20 mA Transmitter in a Haz-ardous Location application guide when applicable.

Personnel performing preventive maintenance should meet thefollowing qualifications:

• Be qualified electrical technicians or engineers that knowthe proper use of test equipment.

• Be familiar with the Type PTSP Platinum Standard SmartPressure Transmitter and associated equipment and haveexperience working with process control systems.

PREVENTIVE MAINTENANCE SCHEDULE

The Type PTSP Transmitter has no moving parts and requireslimited maintenance when operated under normal conditions.

Table 7-1 is the preventive maintenance schedule for theType PTSP transmitter. The table lists the tasks in groupsaccording to their specified maintenance interval. Some tasksin Table 7-1 are self-explanatory. Instructions for tasks thatrequire further explanation are covered under PREVENTIVEMAINTENANCE PROCEDURES.

If the transmitter is inoperative, or if operation is faulty, referto Section 6.

WARNING

System maintenance must be performed only by qualified per-sonnel and only after securing the equipment controlled by thecircuit. Altering or removing components from an active circuitmay upset the controlled process leading to personnel injuryand equipment damage.

Explosionproof/dust-ignitionproof installations and intrinsi-cally safe installations in Class II or Class III hazardous loca-tions require that the assembly be kept tight while circuits arelive unless the location is known to be nonhazardous at thetime. Failure to follow this warning can lead to unsafe condi-tions that can injure personnel and damage equipment.

INTRODUCTION110506A0 7 - 1

Page 61: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

MAINTENANCE

PREVENTIVE MAINTENANCE PROCEDURES

This section covers tasks from Table 7-1 that require specificinstructions or further explanation:

• Checking and tightening all wiring connections.• Cleaning the indicator window (if supplied).• Cleaning the exterior of the transmitter.

Checking Connections

The equipment needed to perform this procedure is aflat-blade screwdriver.

Check all signal wiring, power, and ground connections withinthe transmitter to verify their integrity. When checking con-nections, always turn the screw in the direction to tightenonly. If the connection is loose, it will be tightened. If the con-nection is tight, the tightening action will verify that it issecure. There must not be any motion done to loosen the con-nection.

Indicator Window Cleaning

The equipment required to perform this procedure is:

• Window cleaning solution.• Soft, lint-free cloth.

1. Spray the window cleaning solution on the soft, lint-freecloth. Do not spray directly on the indicator window.

Table 7-1. Preventive Maintenance Schedule1

Task Frequency

Clean indicator window (if supplied). See procedure. 3 months

Clean transmitter exterior. See procedure.

Check and tighten all wiring connections, including power and ground connections. See procedure.

Clean sediment and deposits from connecting piping (proce-dure depends on the installation and the process).

Check and tighten piping connections (procedure depends on the installation and the process).

Check and tighten all conduit connections (procedure depends on the installation and the process).

6 months

Calibrate the unit. Refer to Section 4. 12 months

Change O-rings. Refer to Section 8.

Complete all applicable tasks in this table. Shutdown2

NOTES:1. Environmental conditions might warrant more frequent attention.2. Shutdown is usually defined as an occurrence that happens on a frequency level of greater thanone year.

PREVENTIVE MAINTENANCE PROCEDURES7 - 2 WBPEEUI110506A0

Page 62: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

MAINTENANCE

WBPEEUI

2. Wipe the indicator window with the soft, lint-free clothuntil all deposits are removed and the indicator can be easilyviewed.

Transmitter Exterior Cleaning

The equipment needed to perform this procedure is dependentupon the standard cleaning procedures employed by thecustomer.

When cleaning the exterior of the transmitter, it is common tohose the unit down to free it of dust and process deposits.When this is done, the temperature of the medium (water,steam, or air) should not exceed the specifications of the trans-mitter and associated components (Table 1-3).

CAUTION

If the cell with characterization board assembly has beencleaned for oxygen and chlorine service, do not compromisethe integrity of this cleaning during these procedures. Impuri-ties will react with oxygen and chlorine and damage the trans-mitter and the process.

Clean the diaphragms with a soft rag and appropriate solvent.The use of metal brushes, blades, or other tools will damagethe diaphragms.

PREVENTIVE MAINTENANCE PROCEDURES110506A0 7 - 3

Page 63: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SECTION 8 - REPAIR AND REPLACEMENT PROCEDURES

WBPEEUI

INTRODUCTION

This section contains procedures for replacement of transmit-ter components in the field.

The design of the Type PTSP pressure transmitter allowsreplacement of components in as little as five minutes. All cali-bration and configuration data are stored on both the amplifierassembly and characterization board.

Replacement of the amplifier assembly requires no configura-tion, as the characterization board automatically downloadsthis information into the amplifier assembly. Replacement celland characterization board assemblies come with the standardfactory configuration (refer to Table 1-7) and that data trans-fers to the original amplifier assembly. If a configuration otherthan the standard is required, the transmitter must gothrough either a step-by-step configuration or must have aconfiguration downloaded from the Type STT terminal asdescribed in Section 5. In either case, calibrate the transmitteraccording to the procedures in Section 4-1.

COMPONENT REMOVAL AND INSTALLATION PROCEDURES

Use Figures 8-1 and 8-2 as visual aids when performing theseprocedures.

All procedures assume replacement of the O-rings whenever acomponent sealed by the O-ring is removed.

WARNING

Explosionproof/dust-ignitionproof installations and intrinsi-cally safe installations in Class II or Class III hazardous loca-tions require that the assembly be kept tight while circuits arelive unless the location is known to be nonhazardous at thetime.

System maintenance must be performed only by qualified per-sonnel and only after securing equipment controlled by the cir-cuit. Altering or removing components from an active circuitmay upset the process being controlled.

CAUTION

If the cell and characterization board assembly has beencleaned for oxygen and chlorine service, do not compromisethe integrity of this cleaning during these procedures. Impuri-ties will react with oxygen and chlorine and damage the trans-mitter and the process.

INTRODUCTION110506A0 8 - 1

Page 64: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

REPAIR AND REPLACEMENT PROCEDURES

The items needed to perform these procedures are:

• Spare parts kit identified in Section 9 for the particularcomponent to be replaced.

• O-ring kits identified in Section 9 for the particularapplication.

• 4-mm Allen wrench.

• Phillips screwdriver.

• Flat-blade screwdriver.

• DRI-GLIDE graphite sealant (Man-Gill Chemical Company)or equivalent.

• Dow Corning® No. 4 compound.

Figure 8-1. Internal Transmitter Components

T 02 2 07 A

IN D IC ATO R

LO C KO U TA /B

J1

IN D IC ATO RSC R EW S (4)

C H A R AC T E R IZ ATIONBO AR D S C R EW S (2) C H A R AC T E R IZ ATION

BO AR D C O N N E C TO R

AM PLIFIERAS SE M B LYSC R EW S (3)

Ba iley

Ba iley

COMPONENT REMOVAL AND INSTALLATION PROCEDURES8 - 2 WBPEEUI110506A0

Page 65: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

REPAIR AND REPLACEMENT PROCEDURES

WBPEEUI

• Needle nose pliers or similar tool to remove the O-rings.

Cell and Characterization Board Assembly Removal

NOTE: The cell and characterization board are a matched set. Ifperforming this procedure to remove and install the same cell (forinstance, to change the O-rings or clean the cell), the characteriza-tion board does not need replacing. If performing this procedure toreplace the cell with a new cell, replace the entire cell and character-ization board assembly.

1. Remove the transmitter from the process.

2. Remove the left housing cover from the electronics housing(Fig. 8-2).

3. Use the Phillips screwdriver to remove the three screwsthat secure the amplifier assembly to the electronics housing(Fig. 8-1).

4. Gently pull the amplifier assembly out of the electronicshousing to unplug it from the characterization board connec-tor (Fig. 8-1).

5. Remove the two screws securing the characterizationboard to the electronics housing (Fig. 8-1).

6. Use the 4-mm Allen wrench to remove the cell lockingscrew (Fig. 8-2).

7. Remove the cell lock (Fig. 8-2).

Figure 8-2. External Transmitter Components

R IG H T H O U S IN G C OVE R(P R OTE C TS TE R M IN ALS )

E Z C A L O P TIO N

P IPE P LU G(1 /2 -14 N P T FO RE LEC T R IC AL C O ND U IT)

C E LL LO C K IN G S CR E W(O N OT H ER S ID E )

E LEC T RO N IC SA SS E M BLY

C E LLA SS E M BLY

C E LL LO C K

O -R IN G S E AL (2)

LE FT H O U SIN GC OV E R (P RO TE C TSE LEC T RO N IC S A NDO P TIO N A L LC D O R

A N ALO G M E TE R )

C E LL

O P TIO N A L1/2 -N P T M A LE

TO FE M A LEP RO C ES SA DAP TE R

O P TIO N A L 1 /2 -N PTFO OTB A LL-S TY LE

P RO C ES SA DAP TE R T 02 1 97 A

COMPONENT REMOVAL AND INSTALLATION PROCEDURES110506A0 8 - 3

Page 66: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

REPAIR AND REPLACEMENT PROCEDURES

8. Carefully remove the cell and characterization boardassembly, feeding the cell cable and characterization boardthrough the opening left in the electronics housing by the cell.

9. Remove the cell and cover O-rings (Fig. 8-2).

Cell and Characterization Board Assembly Installation

1. Refer to Section 9 and determine the proper replacementcell and cover O-rings for the application.

2. Coat the O-rings with a film of Dow Corning No. 4 com-pound and install.

3. Coat the upper portion of the cell with a light coating of theDRI-GLIDE sealant.

4. Feed the characterization board and cell cable through theopening in the bottom of the electronics housing, being carefulnot to damage the cell cable.

5. Mount the cell into the electronics housing so that the flaton the cell faces the hole for the cell lock.

6. Install the cell lock and tighten the cell locking screw(Fig. 8-2).

7. Mount the characterization board to the electronics hous-ing and install the two screws (Fig. 8-1).

8. Align the rectangular opening on the bottom of the ampli-fier assembly with the characterization board connector andinstall the amplifier assembly into the electronics housing.Gently press it down to seat the mating connectors.

9. Install the three screws to secure the amplifier assembly tothe electronics housing.

10. Grease the threads of the housing cover with a light film ofthe DRI-GLIDE sealant.

11. Install the housing cover.

NOTE: There will be a delay after initial power up when a new celland characterization board assembly and amplifier assembly aremated.

12. If this is a new cell and characterization board assembly,and a configuration other than the standard factory configura-tion is desired (Table 1-7), perform the configuration proce-dures in Section 5.

13. Perform the calibration procedures in Section 4.

COMPONENT REMOVAL AND INSTALLATION PROCEDURES8 - 4 WBPEEUI110506A0

Page 67: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

REPAIR AND REPLACEMENT PROCEDURES

WBPEEUI

14. Install the transmitter on the process.

Amplifier Assembly Removal

Perform Steps 1 through 4 in the Cell and CharacterizationBoard Assembly Removal section.

Amplifier Assembly Installation

1. Refer to Section 9 and determine the proper replacementcover O-rings.

2. Coat the O-rings with a film of Dow Corning No. 4 com-pound and install.

3. Perform Steps 8 through 11 in the Cell and Character-ization Board Assembly Installation section.

4. Perform the calibration procedures in Section 4.

NOTE: This procedure assumes replacement of the amplifierassembly only. This means that the original configuration is stillpresent in the characterization board memory and will be automati-cally downloaded to the amplifier assembly.

5. Install the transmitter on the process.

Electronics Housing and Housing Cover Replacement

Use this procedure if the electronics housing sustains damage,but the internal components and cell are unaffected.

1. Remove the transmitter from the process.

2. Remove the housing covers from the electronics housing(Fig. 8-2). If the housing covers do not require replacing, go toStep 3. If the housing covers do require replacing, go to Step 6.

3. Remove the housing cover O-rings (Fig. 8-2).

4. Refer to Section 9 and determine the proper cover O-rings.

5. Coat the cover O-rings with a film of Dow Corning No. 4compound and install.

6. Perform Steps 3 through 8 in the Cell and Characteriza-tion Board Assembly Removal section.

7. Discard the old electronics housing and housing covers (ifrequired).

8. Refer to Section 9 and determine the proper cell O-ring(Fig. 8-2).

COMPONENT REMOVAL AND INSTALLATION PROCEDURES110506A0 8 - 5

Page 68: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

REPAIR AND REPLACEMENT PROCEDURES

9. Coat the cell O-ring with a film of Dow Corning No. 4 com-pound and install.

10. Perform Steps 3 through 11 in the Cell and Character-ization Board Assembly Installation section.

11. Perform the calibration checks in Section 4 to verify thecalibration has not changed.

12. Install the transmitter on the process.

O-Ring Replacement

All O-ring replacement procedures are incorporated in thesteps for the replacement of various transmitter components.

OPTIONAL EQUIPMENT REMOVAL AND INSTALLATION PROCEDURES

Use Figures 8-1 and 8-2 as visual aids when performing theseprocedures.

Indicator Removal

1. Remove the transmitter from the process.

2. Remove the left housing cover from the electronics housing(Fig. 8-2).

3. Remove the four screws that secure the indicator to theamplifier assembly (Fig. 8-1).

4. Gently pull on the indicator to unplug it from the amplifierassembly.

5. Remove the housing cover O-ring.

Indicator Installation

1. Align the connector on the back of the indicator with one ofthe four meter openings in the amplifier assembly (Fig. 8-1).The alignment of the connector depends on the desired viewingorientation. Gently press the indicator down to seat the matingconnectors.

2. Install the four screws that secure the indicator to theamplifier assembly.

3. Refer to Section 9 and identify the housing cover O-rings.

4. Coat the O-rings with a film of Dow Corning No. 4 com-pound and install.

OPTIONAL EQUIPMENT REMOVAL AND INSTALLATION PROCEDURES8 - 6 WBPEEUI110506A0

Page 69: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

REPAIR AND REPLACEMENT PROCEDURES

WBPEEUI

5. Coat the threads of the housing cover with a light coatingof DRI-GLIDE sealant.

6. Install the housing cover.

7. Install the transmitter on the process.

EZ CAL Option Removal

1. Use the flat-blade screwdriver to remove the mountingscrew that secures the EZ CAL option to the electronicshousing.

2. Remove the EZ CAL option.

EZ CAL Option Installation

1. Position the EZ CAL option on the electronics housing asshown in Figure 3-1.

2. Use the flat-blade screwdriver to install and tighten themounting screw.

Tagging Replacement (Wired Stainless Steel)

1. Remove the old tag from the transmitter.

2. Run the wire through the tagging hole in the electronicshousing and twist the ends together.

OPTIONAL EQUIPMENT REMOVAL AND INSTALLATION PROCEDURES110506A0 8 - 7

Page 70: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SECTION 9 - SUPPORT SERVICES

WBPEEUI

INTRODUCTION

Bailey Controls Company is ready to help in the use, applica-tion, and repair of its products. Contact your nearest salesoffice to make requests for sales, applications, installation,repair, overhaul, and maintenance contract services.

REPLACEMENT PARTS

When making repairs, order replacement parts from an autho-rized Bailey Controls Company sales representative. Providethe following information:

1. Part description, part number, and quantity.

2. Nomenclature and serial numbers (if applicable).

3. Bailey Controls Company instruction number, page num-ber, and reference figure that identifies the part.

When ordering standard parts from Bailey Controls Company,use the part numbers and descriptions from the spare partslists. Order parts without commercial descriptions from thenearest Bailey Controls Company sales office.

SPARE PARTS LISTS

Tables 9-1 through 9-9 list spare parts and kits. All kits aredelivered with a copy of the kit drawing. This drawing lists theindividual parts contained in the kit and their part numbers.To order compensated spare or replacement cell with charac-terization board assemblies, refer to Cell with Characteriza-tion Board Assembly Replacements.

The Applicable Types column is included to indicate thenomenclature of the transmitter as originally supplied. Dashesin any of the 15 nomenclature positions indicate that any pos-sible selection for that position can apply.

INTRODUCTION110506A0 9 - 1

Page 71: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SUPPORT SERVICES

O-Ring Kits

Electronics Kits

Table 9-1. O-Rings, Cell and Cover

O-Ring1 Kit Number Material Applicable Types

Cell 258556_7 Buna-N All

Cover 258556_8NOTE:1. Each kit contains 10 O-rings.

Table 9-2. Amplifier Assembly (Compensated)

Kit Number1 Applicable Types

258546_1 AllNOTE:1. Each kit contains one amplifier assembly.

Table 9-3. Indicator, Add-On

Kit Number1

Indicator Type

Cover Material

Applicable Types

Position

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

258550_1 LCD Aluminum P T S P - - - - - - - - 1 0 -

258550_2 Analog meter P T S P - - - - - - - - 1 1 -

P T S P - - - - - - - - 1 3 -

P T S P - - - - - - - - 1 4 -

258550_5 LCD Stainless steel P T S P - - - - - - - - A 0 -

258550_6 Analog meter P T S P - - - - - - - - A 1 -

P T S P - - - - - - - - A 3 -

P T S P - - - - - - - - A 4 -NOTE:1. Each kit contains one indicator, one cover with window, and 0.25 oz. of NEVER-SEEZ lubricant.

Table 9-4. Indicator, Spare

Kit Number1

Indicator Type

Applicable Types

Position

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

258550_3 LCD P T S P - - - - - - - - - A -

P T S P - - - - - - - - - B -

P T S P - - - - - - - - - D -

P T S P - - - - - - - - - E -

SPARE PARTS LISTS9 - 2 WBPEEUI110506A0

Page 72: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SUPPORT SERVICES

WBPEEUI

Hardware Kits

258550_4 Analog meter

P T S P - - - - - - - - - M -

P T S P - - - - - - - - - N -

P T S P - - - - - - - - - Q -

P T S P - - - - - - - - - R -NOTE:1. Each kit contains one indicator; one O-ring, cover; and 0.25 oz. of NEVER-SEEZ lubricant.

Table 9-5. EZ CAL Option

Kit Number1

Applicable Types

Position

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

258562_1 P T S P - - - - - - - - 1 3 -

P T S P - - - - - - - - 1 4 -

P T S P - - - - - - - - 1 D -

P T S P - - - - - - - - 1 E -

P T S P - - - - - - - - 1 Q -

P T S P - - - - - - - - 1 R -NOTE:1. Each kit contains one complete EZ CAL module.

Table 9-6. Process Adapters

Adapter Number

Adapter Type

Applicable Types

Position

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

1951753_1 Male to female stain-less steel 316

P T S P - - - - - - A - - - -

P T S P - - - - - - B - - - -

P T S P - - - - - - C - - - -

1951753_2 Male to female Hastelloy C-276

P T S P - - - - - - M - - - -

P T S P - - - - - - N - - - -

P T S P - - - - - - P - - - -

Table 9-4. Indicator, Spare (continued)

Kit Number1

Indicator Type

Applicable Types

Position

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

SPARE PARTS LISTS110506A0 9 - 3

Page 73: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SUPPORT SERVICES

Table 9-7. Electronics Housing

Kit Number1 Cover Type

Applicable Types

Position

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

258554_1 Aluminum housing with standard terminal block

P T S P - - - - - - - - 1 0 -

P T S P - - - - - - - - 1 3 -

P T S P - - - - - - - - 1 A -

P T S P - - - - - - - - 1 D -

P T S P - - - - - - - - 1 M -

P T S P - - - - - - - - 1 Q -

258554_2 Stainless steel housing with standard terminal block

P T S P - - - - - - - - A 0 -

P T S P - - - - - - - - A A -

P T S P - - - - - - - - A M -

258554_3 Aluminum housing with terminal block/lightning arrestor assembly

P T S P - - - - - - - - 1 1 -

P T S P - - - - - - - - 1 4 -

P T S P - - - - - - - - 1 B -

P T S P - - - - - - - - 1 E -

P T S P - - - - - - - - 1 N -

P T S P - - - - - - - - 1 R -

258554_4 Stainless steel housing with terminal block/lightning arrestor assembly

P T S P - - - - - - - - A 1 -

P T S P - - - - - - - - A B -

P T S P - - - - - - - - A N -

NOTE:1. Each kit contains one electronics housing; two O-rings, cover; one O-ring, cell; and 0.25 oz. ofNEVER-SEEZ® lubricant. The electronics housing is supplied with all components installed, exceptcell with characterization board assembly, amplifier assembly, and housing covers.

Table 9-8. Cover, Housing

Kit Number1 Cover TypeCover

Material

Applicable Types

Position

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

258555_1 Standard Aluminum P T S P - - - - - - - - 1 0 -

P T S P - - - - - - - - 1 1 -

P T S P - - - - - - - - 1 3 -

P T S P - - - - - - - - 1 4 -

SPARE PARTS LISTS9 - 4 WBPEEUI110506A0

Page 74: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SUPPORT SERVICES

WBPEEUI

Cell with Characterization Board Assembly Replacements

To order compensated spare or replacement cell with charac-terization board assemblies:

1. Obtain the first eight characters of the transmitter nomen-clature from the nameplate.

2. If position 5 contains a G, replace it with a 5. If position 5contains an A, replace it with a 6.

3. Add an A1 to the end to complete the 10-position nomen-clature of the compensated cell with characterization boardassembly.

258555_2 Cover with window

Aluminum P T S P - - - - - - - - 1 A -

P T S P - - - - - - - - 1 B -

P T S P - - - - - - - - 1 D -

P T S P - - - - - - - - 1 E -

P T S P - - - - - - - - 1 M -

P T S P - - - - - - - - 1 N -

P T S P - - - - - - - - 1 Q -

P T S P - - - - - - - - 1 R -

258555_3 Standard Stainless steel

P T S P - - - - - - - - A 0 -

P T S P - - - - - - - - A 1 -

258555_4 Cover with window

Stainless steel

P T S P - - - - - - - - A A -

P T S P - - - - - - - - A B -

P T S P - - - - - - - - A M -

P T S P - - - - - - - - A N -NOTE:1. Each kit contains one housing cover with O-ring installed and 0.25 oz. NEVER-SEEZ lubricant.

Table 9-9. Tag, Stainless Steel, Wired

Kit Number1

Applicable Types

Position

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

258557_1 P T S P - - - - - - - - - - 2

P T S P - - - - - - - - - - 6

P T S P - - - - - - - - - - C

P T S P - - - - - - - - - - GNOTE:1. Each kit contains 10 stainless steel tags with 6-in. wires attached.

Table 9-8. Cover, Housing (continued)

Kit Number1 Cover TypeCover

Material

Applicable Types

Position

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

SPARE PARTS LISTS110506A0 9 - 5

Page 75: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

SUPPORT SERVICES

Example 1: A replacement cell with characterization board assembly is required for aType PTSPGF1100021E2 pressure transmitter. Following the procedure:

1. The first eight characters of the transmitter nomenclatureare PTSPGF11.

2. Since position 5 contains a G, it is replaced with a 5, yield-ing PTSP5F11.

3. Adding an A1 to the end results in the 10-position nomen-clature for the compensated spare or replacement cell withcharacterization board assembly, PTSP5F11A1.

Example 2: A replacement cell with characterization board assembly is required for aType PTSPAGAA00M01M0 pressure transmitter. Following the procedure:

1. The first eight characters of the transmitter nomenclatureare PTSPAGAA.

2. Since position 5 contains an A, it is replaced with a 6,yielding PTSP6GAA.

3. Adding an A1 to the end results in the 10-position nomen-clature for the compensated spare or replacement cell withcharacterization board assembly, PTSP6GAAA1.

TRAINING

Bailey Controls Company has a modern training facility avail-able for training personnel. On-site training is also available.Contact a Bailey Controls Company sales office for specificinformation and scheduling.

TECHNICAL DOCUMENTATION

Additional copies of this instruction, or other Bailey ControlsCompany instructions, can be obtained from the nearestBailey Controls Company sales office at a reasonable charge.

TRAINING9 - 6 WBPEEUI110506A0

Page 76: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

WBPEEUI110506A0 Index - 1

Index

A

Accessories .............................................................. 1-12Accuracy.......................................................... 1-10, 1-11Address ...................................................................... 5-2Alarm .......................................................................... 5-4Amplifier assembly

Installation............................................................. 8-5Removal................................................................ 8-5

Analog meter ............................................................ 1-12Analog mode

Calibration...................................................... 4-1, 4-2Bench calibration ............................................ 4-2D/A adjustment ............................................... 4-3

Analog output rerange................................................ 4-5Analog point-to-point wiring

Installation............................................................. 3-4Load resistance limits ........................................... 3-5Power supply ........................................................ 3-5

B

Bench calibration........................................................ 4-2

C

CalibrationAnalog mode.................................................. 4-1, 4-2

Bench calibration ............................................ 4-2D/A adjustment ............................................... 4-3

Digital mode.......................................................... 4-4Equipment required .............................................. 4-1EZ CAL option ...................................................... 4-6Procedures ........................................................... 4-1Rerange................................................................ 4-5Rezero .................................................................. 4-6Tolerances..................................................... 4-3, 4-5

Cell and characterization board assemblyDescription............................................................ 2-2Installation............................................................. 8-4Removal................................................................ 8-3

Cell temperature......................................................... 5-6Cell temperature alarm limits...................................... 5-4Channel number ......................................................... 5-2Cleaning ..................................................................... 7-3

Indicator window................................................... 7-2Transmitter exterior............................................... 7-3

Common specifications .............................................. 1-7Communications

Functional description........................................... 2-4Configuration

Cell temperature alarm limits ................................ 5-4Channel number ................................................... 5-2

Damping adjustment .............................................5-2GET CONFIG key .................................................5-4ID tag.....................................................................5-1Local LCD setup....................................................5-5Lockout..................................................................5-7Option..................................................................1-13Output action.........................................................5-2Output type............................................................5-2Primary engineering units .....................................5-3Primary upper and lower range values .................5-3Secondary engineering units.................................5-4Secondary lower and upper range values.............5-4Select mode ..........................................................5-1SEND CONFIG key...............................................5-5Standard................................................................5-5Startup and failure conditions................................5-3Transmitter type ....................................................5-2VIEW CONFIG key ...............................................5-5

Configuration lockout ..................................................5-7Configuration procedure .............................................5-1

D

D/A adjustment ...........................................................4-3Damping......................................................................1-8Damping adjustment ...................................................5-2Defaults.......................................................................3-8Degreasing................................................................1-12Diagnostics .................................................................2-6Digital field bus wiring

Installation .............................................................3-7Load resistance limits............................................3-7Power supply.........................................................3-7

Digital modeCalibration .............................................................4-4

E

Electronics assemblyFunctional description ...........................................2-2

Electronics housing and cover replacement ...............8-5Electronics housing orientation ...................................3-3Enclosure rating ..........................................................1-8Equipment description ................................................1-1Equipment required for calibration ..............................4-1Error messages...........................................................6-1EZ CAL option...........................................................1-12

Functional description ...........................................2-3Installation ......................................................3-3, 8-7Removal ................................................................8-7Validation procedure .............................................4-6

Page 77: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

Index - 2 WBPEEUI110506A0

Index (continued)

F

F1 key .........................................................................5-7Failure conditions........................................................3-8Features......................................................................1-1Field bus I/O module...................................................3-7Fix output/cancel fix output .........................................5-5Frequency shift keying (FSK)......................................2-4

Noise immunity......................................................2-4Function generator ...............................................2-6, 2-7Functional operation....................................................2-1

G

Gas pressure installation.............................................3-5GET CONFIG key .......................................................5-4Gold plated diaphragm..............................................1-12Grounding ...................................................................3-8

H

Hazardous location installations..................................3-8How to use this instruction ..........................................1-4Humidity limits .............................................................1-7

I

ID tag ..........................................................................5-1Indicator

Analog meter .......................................................1-12Installation .............................................................8-6LCD .....................................................................1-12Removal ................................................................8-6

Indicator window cleaning...........................................7-2Installation

EZ CAL option .......................................................3-3Mounting................................................................3-2Piping ....................................................................3-4Wiring ....................................................................3-4

Analog point-to-point mode .............................3-4Digital field bus mode ......................................3-7Grounding........................................................3-8

Instruction content.......................................................1-3Intended user ..............................................................1-1

L

LCD...........................................................................1-12Lightning arrestor ......................................................1-12Liquid pressure installation..........................................3-6Load resistance limits..................................................3-5Local LCD setup..........................................................5-5Location considerations ..............................................3-1

Lockout jumper ........................................................... 2-3Loop load limits........................................................... 1-8Loop resistance .......................................................... 2-4

M

Maintenance ............................................................... 7-1Cleaning................................................................ 7-3

Indicator window ............................................. 7-2Transmitter exterior ......................................... 7-3

Procedures ........................................................... 7-2Schedule............................................................... 7-1

Measurement range .......................................... 1-9, 1-11Monitor cell temperature............................................. 5-6Monitor input............................................................... 5-6Monitor output............................................................. 5-6Monitor secondary engineering units.......................... 5-6Mounting..................................................................... 3-2Mounting bracket ...................................................... 1-12

N

Nomenclature ............................................................. 1-5

O

OperationConfiguration ........................................................ 5-1

Cell temperature alarm.................................... 5-4Channel number.............................................. 5-2Damping adjustment ....................................... 5-2GET CONFIG key ........................................... 5-4ID tag............................................................... 5-1Local LCD setup.............................................. 5-5Output action................................................... 5-2Output type...................................................... 5-2Primary engineering units ............................... 5-3Primary upper and lower range values ........... 5-3Secondary engineering units........................... 5-4Secondary lower and upper range values....... 5-4Select mode .................................................... 5-1SEND CONFIG key......................................... 5-5Standard.......................................................... 5-5Startup and failure conditions.......................... 5-3Transmitter type .............................................. 5-2VIEW CONFIG key ......................................... 5-5

Configuration lockout ............................................ 5-7F1 key ................................................................... 5-7Fix output/cancel fix output ................................... 5-5Monitor cell temperature ....................................... 5-6Monitor input ......................................................... 5-6Monitor output ....................................................... 5-6Monitor secondary engineering units.................... 5-6

Page 78: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

WBPEEUI110506A0 Index - 3

Index (continued)

OUTPUT key ........................................................ 5-6SPECIAL FEATURE key ...................................... 5-5STATUS key ......................................................... 5-6

Operator interface ...................................................... 5-1Options ..................................................................... 1-12O-ring replacement..................................................... 8-6Output

Current limiting...................................................... 1-8Signal.................................................................... 1-8

Output action .............................................................. 5-2OUTPUT key .............................................................. 5-6Output type................................................................. 5-2Overpressure

Effect................................................................... 1-10Limit .................................................................... 1-11

P

PipingInstallation............................................................. 3-4

Power supply ....................................................... 3-5, 3-7Power supply effect .................................................... 1-8Pressure

Limits ......................................................... 1-10, 1-11Preventive maintenance............................................. 7-1

Indicator window................................................... 7-2Procedures ........................................................... 7-2Schedule............................................................... 7-1Transmitter exterior............................................... 7-3

Primary engineering units........................................... 5-3Primary upper and lower range values....................... 5-3PTHPA

SpecificationsMeasurement range...................................... 1-11Overpressure limit......................................... 1-11Pressure limits .............................................. 1-11Reference accuracy ...................................... 1-11Stability ......................................................... 1-11Temperature effect........................................ 1-11Turndown ratio .............................................. 1-11Weight........................................................... 1-11Zero elevation ............................................... 1-11Zero suppression .......................................... 1-11

PTHPGSpecifications............................................... 1-9, 1-11

Measurement range........................................ 1-9Overpressure effect ...................................... 1-10Pressure limits .............................................. 1-10Reference accuracy ...................................... 1-10Temperature effect........................................ 1-10Turndown ratio ................................................ 1-9Weight........................................................... 1-10

Zero elevation..................................................1-9Zero suppression.............................................1-9

R

Reference accuracy .........................................1-10, 1-11Reference conditions ..................................................1-7Remote diaphragm seals ..........................................1-12Repair and replacement

Amplifier assemblyInstallation .......................................................8-5Removal ..........................................................8-5

Cell and characterization board ............................8-4Cell and characterization board assembly ............8-3Electronics housing and cover ..............................8-5Equipment required...............................................8-1EZ CAL option

Installation .......................................................8-7Removal ..........................................................8-7

IndicatorInstallation .......................................................8-6Removal ..........................................................8-6

Optional equipment ...............................................8-6O-rings ..................................................................8-6Tagging .................................................................8-7

Replacement parts......................................................9-1Rerange ......................................................................4-5Reranging the analog output.......................................4-5Resistance, load limits ................................................3-5Rezero ........................................................................4-6RFI/EMI effects ...........................................................1-8

S

Secondary engineering units ...............................5-4, 5-6Secondary lower and upper range values ..................5-4Select mode ................................................................5-1SEND CONFIG key ....................................................5-5Setup and physical installation....................................3-1Software functions ......................................................2-6Spare parts lists ..........................................................9-1SPECIAL FEATURE key ............................................5-5Specifications............................................. 1-7, 1-9, 1-11

Common................................................................1-7Damping ..........................................................1-8Enclosure rating ..............................................1-8Humidity limits .................................................1-7Loop load limits ...............................................1-8Output current limiting .....................................1-8Output signal ...................................................1-8Power supply effect .........................................1-8Reference conditions.......................................1-7

Page 79: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

Index - 4 WBPEEUI110506A0

Index (continued)

RFI/EMI effects................................................1-8Supply voltage .................................................1-8Surge tolerance ...............................................1-8Temperature limits...........................................1-8Vibration effect.................................................1-8

PTHPAMeasurement range ......................................1-11Overpressure limit .........................................1-11Pressure limits ...............................................1-11Reference accuracy.......................................1-11Stability ..........................................................1-11Temperature effect ........................................1-11Turndown ratio...............................................1-11Weight ...........................................................1-11Zero elevation................................................1-11Zero suppression...........................................1-11

PTHPG.........................................................1-9, 1-11Measurement range ........................................1-9Overpressure effect .......................................1-10Pressure limits ...............................................1-10Reference accuracy.......................................1-10Temperature effect ........................................1-10Turndown ratio.................................................1-9Weight ...........................................................1-10Zero elevation..................................................1-9Zero suppression.............................................1-9

Stability .....................................................................1-11Standard configuration................................................5-5Startup and failure conditions......................................5-3STATUS key ...............................................................5-6STT .............................................................................3-7

Configuration procedure........................................5-1Error messages .....................................................6-1Functional description ...........................................2-4Operator interface .................................................5-1

Supply voltage ............................................................1-8Surge tolerance...........................................................1-8

T

Tagging replacement ..................................................8-7

Tantalum diaphragm................................................. 1-12Technical documentation............................................ 9-6Temperature

Effect.......................................................... 1-10, 1-11Limits .................................................................... 1-8

Temperature compensationFunctional description........................................... 2-4

Tolerances for calibration .................................... 4-3, 4-5Training....................................................................... 9-6Transmitter

Exterior cleaning ................................................... 7-3Transmitter type.......................................................... 5-2Troubleshooting

Error messages .................................................... 6-1Turndown ratio................................................... 1-9, 1-11

U

Unpacking and inspection .......................................... 3-1

V

Vapor pressure installation ......................................... 3-5Vibration effect............................................................ 1-8VIEW CONFIG key..................................................... 5-5

W

Weight ............................................................. 1-10, 1-11Wiring

Installation............................................................. 3-4Analog point-to-point mode............................. 3-4Digital field bus mode...................................... 3-7Grounding ....................................................... 3-8

Z

ZeroElevation ...................................................... 1-9, 1-11Suppression................................................. 1-9, 1-11

Page 80: Preface - Infi 90 Infi90 Documentation/PTSP.pdfPreface This publication is for the use of technical personnel responsi-ble for the installation, calibration, operation, maintenance,

Visit Elsag Bailey on the World Wide Web at http://www.ebpa.com/bfp

Our worldwide staff of professionals is ready to meet your needs for process automation. For the location nearest you, please contact the appropriate regional office.

Elsag BaileyProcess Automation

Europe, Africa, Middle EastVia Puccini 216154 Genoa, ItalyTelephone 39-10-6584-943Telefax 39-10-6584-941

GermanyBorsigstrasse 263755 AlzenauGermanyTelephone 49-6023-943-0Telefax 49-6023-943-300

Asia/Pacific539 Yishun Industrial Park ASingapore 768740Telephone 65-756-7655Telefax 65-753-6549

Americas125 East County Line RoadWarminster, PA USA 18974Telephone 1-215-674-6000Telefax 1-215-674-7183

Form WBPEEUI110506A0 Litho in U.S.A. 798Copyright © 1998 by Elsag Bailey Process Automation, As An Unpublished Work® Registered Trademark of Elsag Bailey Process Automation™ Trademark of Elsag Bailey Process Automation


Recommended