6
OXICOM LITIC INDUSTRIAL ı COMPACTO ı PREMONTADO
Transcript
Page 1: Presentación de PowerPointwatersystemsoxicom.com/wp-content/uploads/2017/02/Oxicom-WS_… · •Approvals: (USP, Ph. Eur., JP, ANSI/AMMI, GMP, ISPE, FDA, NEMA, UL) OXICOM LITIC ELECTROLYTIC

OXICOM LITIC

INDUSTRIAL ı COMPACTO ı PREMONTADO

Page 2: Presentación de PowerPointwatersystemsoxicom.com/wp-content/uploads/2017/02/Oxicom-WS_… · •Approvals: (USP, Ph. Eur., JP, ANSI/AMMI, GMP, ISPE, FDA, NEMA, UL) OXICOM LITIC ELECTROLYTIC

Electrolytic ozone generator for

pure and demineralized water,

for continuous disinfection of

water storage and distribution

systems (systemic protection).

Suitable for purified water or

comparable specifications for

Aqua Purificata, WFI (Water for

Injection/Aqua ad Injectabilia) or

comparable specifications in the

pharmaceuticals-, cosmetics-

and semi-conductor industry,

hemodialysis, biotechnology as

well as in medical systems.

• Short-circuit-proof power supply

• Stainless steel housing

• Redundant operation (off ELAP

2800)

• Easy change of components

• Downward compatible to all ELAP

ozone cells (up to 4,0 g O3/h)

• Configurable alarm outputs

• Automatic logging of operating states

and alarms

OXICOM

LITIC

INDUSTRIAL ı COMPACTO ı PREMONTADO

ELECTROLYTIC OZONE

GENERATOR

• Purest ozone (no added substances) Low energy- and operating costs • High safety (work and microbiological protection) Fine and more accurate ozone

dosage

• High ozone concentration in the water

• Approvals: (USP, Ph. Eur., JP, ANSI/AMMI, GMP, ISPE, FDA, NEMA, UL)

Page 3: Presentación de PowerPointwatersystemsoxicom.com/wp-content/uploads/2017/02/Oxicom-WS_… · •Approvals: (USP, Ph. Eur., JP, ANSI/AMMI, GMP, ISPE, FDA, NEMA, UL) OXICOM LITIC ELECTROLYTIC

OXICOM LITIC ELECTROLYTIC OZONE GENERATOR

Modelo

Ozone

Production

g/h

Power

Supply

LITIC – 1,5 1,5 240V-50 Hz

LITIC – 3 3,0 240V-50 Hz

LITIC – 4 4,0 240V-50 Hz

LITIC – 5 5,0 240V-50 Hz

Features of the control unit (execution: Master-SV-S)

Output power: Current controlled 0…6 VDC 0...45 A max. 250 W (at ELAP

5.0)

Display and Control: 10 inch touch display (switchable language)

Emergency control by magnet switch and 7 segment display

Input for REMOTE ON/OFF: (1x per ozone cell) By means of closing contact

Input 4...20 mA for: (1x per ozone cell) Control ozone capacity

Potential free contacts for: (48 VDC / 1A)

(1x per ozone cell)

Common alarm 1

Common alarm 2 Ozone production

Outputs 4...20 mA for:

(1x per ozone cell)

Operating voltage of cell

Operating current of cell

Operating temperature: 0…40°C

Protection class of power supply: IP 65 (DIN 40 050 IEC 529, EN 60 529 / 10.91)

Protection class: Class I, protection grounding (acc. to DIN 57 100 resp. VDE

0100 and 0106 T1)

Emergency supply at mains shut down: (1x per

ozone cell) By means of accumulator 48 h for at least

Mains connections: 110…230 V AC, 50/60 Hz, 400 VA

Power factor: > 0,95

Weight: approx. 25 kg

Page 4: Presentación de PowerPointwatersystemsoxicom.com/wp-content/uploads/2017/02/Oxicom-WS_… · •Approvals: (USP, Ph. Eur., JP, ANSI/AMMI, GMP, ISPE, FDA, NEMA, UL) OXICOM LITIC ELECTROLYTIC

OXICOM LITIC ELECTROLYTIC OZONE GENERATOR

Features of the ozone cell

Material Stainless steel DIN EN 10 027 mat. 1.4571 (AISI 316Ti) PTFE

No. of cells per apparatus: 1

Ozone concentration: (in the water phase) Depends on the actual water flow

Flow during standby:

Periodically a small flow to fill up the ozone cell

continuously a very small flow (the ozone cell must always

be filled with water!)

Flow during production: approx. 100...250 ℓ/h (150 ℓ/h nominal)

Water quality: Demineralized water, conductivity < 10 µS/cm (purified

water or comparable specification)

Water temperature: approx. 15...25 °C

Operating temperature of the cell: < 50 °C, nominal 30...40 °C

Temperature measurement: Sensor integrated

Flow measurement Sensor for short water integrated

Pressure measurement Sensor integrated

Display of parameter Display

Parameter transfer to control unit Data bus

Pressure resistance of the cell: + 16 bar

Operating pressure of the cell: + 0...10 bar

Dimensions of the cell: approx. 305 x 125 mm (without Clamp connector);

installation depth min. 135 mm

Hydraulic connections: R/G 3/8“ or Clamp connector

Connection for hydrogen disposal: R/G 1/8“

Hydrogen gas quantities: approx. 27 Nℓ/h

Seals and el. insulation material: (in contact with

the agents)

PTFE, FEP

(according to FDA)

Protection class of the cell: IP 26 (DIN 40 050 IEC 529, EN 60 529/10.91)

Standard cable length: 5 m

Weight: Approx. 4 kg (at ELAP 5.0)

Page 5: Presentación de PowerPointwatersystemsoxicom.com/wp-content/uploads/2017/02/Oxicom-WS_… · •Approvals: (USP, Ph. Eur., JP, ANSI/AMMI, GMP, ISPE, FDA, NEMA, UL) OXICOM LITIC ELECTROLYTIC