Variable Speed Compressor Technologies Presented By: John Dolan, P.E. President - Thermosystems, Inc. BS in Mechanical Engineering from UIUC 29 years HVAC Equipment Application Experience [email protected] www.thermohvac.com March 14, 2017 Page 1
Transcript
Page 1: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Variable Speed Compressor Technologies

Presented By:

John Dolan, P.E.President - Thermosystems, Inc.

BS in Mechanical Engineering from UIUC

29 years HVAC Equipment Application Experience

[email protected]

www.thermohvac.com

March 14, 2017

Page 1

Page 2: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Variable Speed Compressor Technologies

• Why to Apply

― Energy Savings

― Capacity Control

• Available Technologies & Application

― Motors and Bearings

― Centrifugal Compressors

― Screw Compressor – Positive Displacement

― Scroll Compressor – Positive Displacement

• When to Apply

• When Not to Apply

• Questions

2

Page 3: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Positive Displacement Compressor

3

Page 4: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Basic Refrigeration Cycle

4

LIFT (ΔP)

Page 5: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Water Cooled Flooded Chiller Refrigeration Cycle

5

Page 6: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Basic Direct Expansion (DX) Refrigeration Cycle

6

Page 7: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Refrigeration Cycle

12

34

Page 8: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Reducing Compressor Lift (𝑃𝑐𝑜𝑛𝑑-𝑃𝑒𝑣𝑎𝑝 = ΔP)

8

EXV

EXV

Page 9: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Variable Speed Compressor Technologies

• Why to Apply?

• Energy Savings (Reduce Lift)

• Lower Compressor RPM = Less Work = Less Energy $

• Fan/Pump Laws - RPM ≈ Energy³

• Take Advantage of Lower than Design Condenser Temps

• How Often is Outside Ambient at Design Temp (DB or WB)?

• O'Hare Weather Bin Data – 6 hours/yr ≥ 95°F

• Match Compressor Operation to Actual Condenser Conditions

(Lower Temperatures ≈ Lower Pressures)

• Capacity Control

• How Often is Building or Space at Full Load? (<1%)

• Proportional Control with VFD vs. Staged Control (On/Off)

• Modulate Flow of Refrigerant to Match Load (Screw and Scroll)

• Chiller - More Stable Control of Leaving Water Temperature

• No Return Water Control or LWT Set Point Reset

• DX Air Handler - More Stable Control of Discharge Air

Temperature (DB & WB)9

Page 10: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Variable Speed Compressor Technologies

• Why to Apply?

• Higher Efficiency Motors with Variable Speed Operation

• AC Induction Motor with Variable Frequency Drive

• Permanent Magnet Synchronous Motor (PMSM)

• Motor Speed Operating Range with PMSM

• No longer limited to 1800 & 3600 RPM (AC Induction

Motor Speeds)

• Direct Drive Operation

• Gears to Increase Impeller Speed no Longer Required

• No Transmission Losses (Gears)

• Magnetic Bearing Technology

• Eliminate Oil and Oil Components (Oil Sump, Oil

Pump, Oil Heaters, Oil Separators, Safeties)

• Improve Heat Transfer & Reduce Compressor Wear

• Sustainable Efficiencies for Life of Chiller

Page 11: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Quick Electric Motor Review

• AC Induction Motor

― Most Common Motor in HVAC

― Fixed Speeds Based on 60Hz (1800 & 3600 RPM)

― Max Motor Speed 3600 RPM

― Slip

• Permanent Magnet Synchronous Motor (PMSM, ECM)

― More Efficient than AC Induction Motor - Especially at Part-Load

― Electronically Commutated (ECM)

― Synchronous Motor – Zero Slip

― VFD for Starting Required (Even in Constant Speed Applications)

• VFD Integral to Motor in Some Sizes

― Smaller Size than Comparable Hp AC Induction Motor

― Higher Speeds Allow for Matching Speed to Application

11

Page 12: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Motor Efficiencies (AC Induction vs. PMSM)

NEMA Premium EffAC Induction Motor

PMSM (ECM)

Page 13: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Oil Effects on Heat Transfer

Conclusions and Recommendations:

The heat transfer ratio drops steadily with oil

concentration and reaches a value of 0.65

[from 1.0 normalized] at an oil concentration of

10%.

From ASHRAE Research Project 751-RP,

“Experimental Determination of the Effect of Oil on Heat Transfer

with Refrigerants HCFC-123 and HFC-134a”,

35% heat transfer reduction with 10%

oil concentration in refrigerant

Page 14: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Oil Effects on Chiller Efficiency

Source: The News, 04/15/04, by Jack Sine

Direct Drive PMSM Oil-Free Compressor Design Eliminates

the Performance Degradation Due to Oil Contamination of the

Refrigerant

Page 15: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Traditional Centrifugal Design (Oil Based)

3600 RPM AC

Induction Motor

Thrust Bearings

(Oil)

Impeller Gear Set

(Oil)

Radial

Bearings

(Oil)

Page 16: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Traditional Centrifugal Compressor

(Geared Impeller & Traditional Oiled Bearings)

Traditional Centrifugal Design (Oil Based)

Page 17: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Magnetic Bearing Centrifugal Compressor

High Speed

Permanent Magnet

Synchronous Motor

Axial

Thrust

Bearing

Impeller +

Inlet Vanes Front

Radial

Bearing

Rear

Radial

Bearing

Page 18: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Magnetic Bearing Compressor

Magnitude™ WME Compressor Rotating Group

Magnetic Bearings

and Sensors

Permanent Magnet

Synchronous Motor

Suction Gas

Discharge

Inlet Guide

Vanes

Single Stage

Impeller

VFD in

External Panel

Page 19: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Water Cooled Centrifugal Chiller Efficiencies

0

0.2

0.4

0.6

0.8

1

1.2

0 10 20 30 40 50 60 70 80 90 100 110

Chiller percent load

kW

/ t

on

10% energy

reduction

Fixed Speed Motor

AC Induction w/ VFD

High Speed VFD w/

Magnetic Bearings

30% energy

reduction

Note: Based on 500 ton Chiller with Same Condenser and Evaporator

Page 20: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Operating Cost Comparison – Centrifugal Chillers

0

100

200

300

400

500

600

700

800

900

0 10 20 30 40 50 60 70 80 90 100

Chiller Percent Load

Op

erat

ing

Ho

urs

0

0.2

0.4

0.6

0.8

1

1.2

kW /

to

n

Fixed Speed ~ $243,287/year

Traditional VFD ~ $164,934/year

High Speed VFD w/ Mag Bearing ~ $131,709/year

Cooling Load Profile

10% energy

reduction

Note: Based on 500 ton Chiller with Same Condenser and Evaporator and $0.10/ per kWh

Page 21: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

©2016 Daikin Applied

CONSTANT SPEED & VOLUME SCREW COMPRESSOR

Pd

Ps

Over Compression

or Lost Work

Pc’’

• P

fixed

fixe

d

Discharge

to

Condenser P cond

V displacement

A

B

Page 22: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

©2016 Daikin Applied

VARIABLE SPEED SCREW COMPRESSOR

VFD on Compressor Motor

Varies the Volume of

Refrigerant and Discharge

Pressure is Controlled by

the Slide Valves

Vd

PcA

Point APoint B

Discharge to

Condenser

variable

vari

able

B

Page 23: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Scroll Compressor Technologies

23

Digital ScrollConstant Speed

Variable Capacity

Load/unload 20sec time step

Variable Speed PMSM or

AC Induction Motor w/VFDVariable Speed Compression

and Capacity Control

Fixed Speed ScrollOn/Off

Staged Control

Page 24: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Variable Speed vs. Variable Capacity

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

25

%

35

%

45

%

55

%

65

%

75

%

85

%

95

%

% C

om

pre

sso

r Po

wer

% Cooling Capacity

Digital Scroll

RebelVariable

Speed

24

Digital scrolls are Off/On for Compression with

Constant Speed AC Motor

Page 25: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Scroll Compressor Staging (Variable and Constant Speed)

25

NONINV NONNONINVNON7%

100%

System Capacity

Capacity Control2 Condensing Units

4 Compressors

Co

mp

ress

or

Op

erat

ion

Page 26: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Airside Compressor Cycling Effects

26

Page 27: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

When to Apply

• Significant Hours with Lower than Design Condenser Temperatures

― Take Advantage of Lower ECWT or Ambients

― Reduce Lift Wherever Possible

• Lower Condenser Temps (Water)

• Higher Evaporator Temps (Chilled Water Temp or Discharge Air)

• Significant Hours with Lower than Design Load

― Watch Minimum Loading with Constant Speed Machines

• Excessive Cycling on Large Hp Compressors

• Generator Back-Up

― VFD Compressors will have Lower Inrush at Start-up

• Variable Chilled Water Flow Applications

― Better Control of LWT

― Less Cycling of Compressors (Air Cooled Chillers)

27

Page 28: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

When to Apply

• Meeting or Exceeding ASHRAE 90.1 & IECC Efficiencies

― Water Cooled Compliance (Full Load kW/ton and IPLV)

― Air Cooled Compliance (EER and IEER)

― Path A (Constant Speed) vs. Path B (Variable Speed)

― Must Meet Both Full Load kW/ton and IPLV

• Utility Rebates for Higher Efficiency Equipment

― More Rebate $ for Better IPLV or IEER

― Rebate May Offset or Pay for VFD

• Humid Areas

― Stable Leaving Water Control or Leaving Air Control

― More Latent Cooling & Stable Coil Discharge Temperatures

― Minimize or Eliminate Condensate Re-Evaporation when

Compressor Shuts Off

• Sound Sensitive Applications

― Variable Speed Equipment is Quieter than Constant Speed

28

Page 29: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

When Not to Apply

• Centrifugal Chiller Applications with Minimal Condenser Relief

― Humid Areas with Constant Loads (High WB)

• Very Large Tonnage Plants

― 60,000 ton Plant with 20+ Chillers

• Large Airside Applications with Multiple Scroll Compressors

― 100+ tons with 6 or 8 stages

― Compressor that is Off is Always More Efficient than Operating Compressor

• Airside DX Applications in Dry Climates (Low Latent Loads)

― Sensible Load Applications

― Discharge Air Reset or Leaving Water Reset

• Heat Recovery Chiller Applications – Fixed Lift

• Any Others? Page 29

Page 30: Presented By: John Dolan, P.E. - ASHRAE® Illinois Chapterillinoisashrae.org/.../variable_speed_compressors_dolan.pdf · Presented By: John Dolan, P.E. ... ―Capacity Control ...

Page 30