Furanic Compounds in Electrical Insulating Liquids by HPLCASTM D-5837 Report
WEIDMANN DIAGNOSTIC SOLUTIONS8406 SCRANTON STREET + HOUSTON, TX + 77061
(713) 595-1030 + (713) 595-1034WWW.WEIDMANN-DIAGNOSTICS.COM
HOUSTON, TXATTN: PO #:
Location:
Serial #:
Bank/Ph:
Tank:
Breathing:
Fluid:
Mfr:
KV:
KVA:
Imp.(% Z):
Container:
Project ID:
Account:
Order #:
Control #:
Received:
Reported:
Customer ID:Gallons:
LUFKIN
C0725651
3
TRANSFORMER
SEAL
MIN 106350
COOPER
13.2/7.62
15000
R465 3 3 3
67
307210
6035991
08/10/2009
08/20/2009
A Member of the WICOR Group
< 10
< 10
< 10
< 10
< 10
10
10
10
10
10
2-Furaldehyde
5-Hydroxy-methyl-furaldehyde
2-Acetylfuran
5-Methyl-2-furaldehyde
2-Furyl alcohol
Furanic Compound Result (ppb) Reporting Limit (ppb)
* BRL = Below Reporting Limit
The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann Diagnostic Solutions does notimply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relateonly to the sample or samples tested. Any interpretations or opinions expressed represent the best judgement of Weidmann Diagnostic Solutions. Weidmann DiagnosticSolutions assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment orother property for which this report may be used or relied upon for any reason whatsoever.
Results:
Diagnostics:
Notations:
New insulation with a high degree of mechanical strength will typically have a Degree of Polymerization (DP) of 1000-1300. "Middle Aged" paper isapproximately 500 and paper with less than 250 is in its "Old Age". Severely degraded insulation with a DP of 150 or less will have very little mechanicalstrength and may result in a transformer failure. The following estimations are based on current research of GSU transformers filled with mineral oil.
QC Chemist: CN
Estimated Degree of Polymerization (DP): >1003Estimated Operating Age of the Equipment: <1.0
WEIDMANN DIAGNOSTIC SOLUTIONS8406 SCRANTON STREET + HOUSTON, TX + 77061
(713) 595-1030 + (713) 595-1034WWW.WEIDMANN-DIAGNOSTICS.COM
HOUSTON, TXATTN: PO #:
Location:
Serial #:
Bank/Ph:
Tank:
Breathing:
Fluid:
Mfr:
KV:
KVA:
Imp.(% Z):
Container:
Project ID:
Account:
Order #:
Control #:
Received:
Reported:
Customer ID:Gallons:
LUFKIN
C0725651LTC
LTC
SEAL
MIN 190
COOPER
3A 3A 3A
67
307210
6036005
08/10/2009
08/20/2009
Acceptable for equipment > 69 kV for in-service oil - kV not provided (25 ppm max).
Diagnostic not applicable.
Diagnostic not applicable.
Diagnostic not applicable.
Color Number diagnostic not applicable. Visual diagnostic not applicable.
A Member of the WICOR Group
Phys
ical
, Che
mic
al, a
nd E
lect
rical
Tes
tsM
etal
sPC
BDi
agno
stic
s
603600508/07/2009
307210
L.5CLR&SPRK
PARTICULATES
25
35
46.10.003
< 0.5
< 0.5< 0.5< 0.5< 0.5
< 0.5
< 0.5< 0.5
< 1.0 PPM
1N
D-1533B Moisture in Oil (ppm):D-971 Interfacial Tension (dynes/cm):D-974 Acid Number (mg KOH/g):D-1500 Color Number (Relative):D-1524 Visual Exam. (Relative):D-1524 Sediment Exam. (Relative):D-877 Dielectric Breakdown (kV):D-1816 Dielectric Breakdown 1 mm (kV mm-C):D-1816 Dielectric Breakdown 2 mm (kV mm-C):D-924 Power Factor @ 25C (%):D-924 Power Factor @ 100C (%):D-924 Power Factor @spec.C (% C):D-1298 Specific Gravity (Relative):D-445 Viscosity @ 100F (SUS):D-445 Viscosity @ Spec.F (SUS F):D-92 Flash Point (C):D-92 Fire Point (C):D-97 Pour Point (C):WDS Passivator (ppm):D-2668 Oxidation Inhibitor (wt. %):D-1807 Refractive Index (Relative):D-1169 Resistivity (ohm cm):
Aluminum (Al) (ppm):Copper (Cu) (ppm):
Dissolved Iron (Fe) (ppm):Fault, Wear, and Lead (Pb) (ppm):Contamination Silver (Ag) (ppm):Metals Tin (Sn) (ppm):
Zinc (Zn) (ppm):Silicon (Si) (ppm):
Concentration (ppm):EPA-Method 8082 PCB Type (Aroclor):
Reporting Limit:
Lab Control Number:Date Sampled:
Order No.:ASTM Method Oil Temp.(C):
Moisture in Oil:Interfacial Tension:
Acid Number:Color Number and Visual:
Dielectric Breakdown D-877:Dielectric Breakdown D-1816:
Power Factor @ 25C:Power Factor @ 100C:
Oxidation Inhibitor:
The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann-ACTI Inc. does not imply that the contents of the sample received by this laboratory are the same as all suchmaterial in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgement of Weidmann-ACTI. Weidmann-ACTI assumes noresponsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever.
EQPT. LOCATION
PAGE
USER
ADDRESS
CUSTOMER
JOB #
TRANSFORMER MAINTENANCE TEST Electrical Reliability Services Inc.Houston Area Service Center
1455 E. Sam Houston Pkwy SSuite 190
Pasadena, TX 77503Phone 281-241-2800
NA
31001771 of 4
PLANT DATE LAST INSPECTION
DATE
SUBSTATION Transformer Yard C-07256-5-1POSITION
5/13/11 TEMPERATURE HUMIDITY % C-07256-5-131 °C 53
WR C13-061 AND MEGGER C13-057 Vaundrae Ross and Delon WadeEQPT. INVENTORY NO. TESTED BY:
56700, REVISED 4/17/08COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
VISUAL AND MECHANICAL INSPECTION
INSPECT PHYSICAL AND MECHANICAL CONDITION
VERIFY FANS OPERATE
INSPECT ANCHORAGE, ALIGNMENT AND GROUNDING
INSPECTION REPORT
FAIL
FAIL
FAIL
PASS
PASS
PASS
INSPECTION REMARKS
Fans not installed because the Xfmr is going to be painted
N/A
ELECTRICAL TESTS (OPTIONAL FOR L.V. TRANSFORMERS OR BELOW 500 kVA)
5
1.54064
5
1.76446
5
2.01242
MINUTESPRIMARY TO
GROUNDSECONDARY TO
GROUNDPRIMARY TO SECONDARY
INSULATION RESISTANCE IN MEGOHMS
TEST KV
0.50
1.00
10.00
P. I.
P.I. = 10 min/1 min
MAINTENANCE
PHASE A PHASE B PHASE CCALC
TRANSFORMER TURN RATIO TEST
TAP
C CAL
ACCEPTANCE
4.208
4.208
4.210
0.01510
0.1511
0.01509
WINDING RESISTANCE TEST IN OHMS
/15,000 20,000 25,000 110
10 4930
NAMEPLATE DATA
C-07256-5-1SERIAL NO.
%
141,600 136,800 132,000 127,200
A B C D E
132,000 VOLTS
Cooper Power Systems YR MFR 1991
KVA
IMPEDANCE //OA FA FA
122,400
WINDING MATERIAL °CCOPPER
C
CLASSTYPECAPACITY
B.I.L. RATINGTEMPERATURE RISE
PRIMARY KV
TAP POSITION Gas Blanketed
TAP SETTING
TAP VOLTAGES
/ 55
MANUFACTURER
INSULATING MEDIUM
TANK TYPE
Mineral Oil
SECONDARY KV 13,200
DRY TYPE CONSERVATOR
WYE
132,000
7,621/
DELTA
Gallons
WORKING TAP AF
H1-H2
H2-H3
H3-H1
X0-X2
X0-X3
X0-X1
Core Ground megged at 500 volts 1,690 MohmsCOMMENTS:
DEFICIENCIES:
03
3,650
4,060
6,255
2,056
2,420
4,270
3,680
4,510
9,076
EQPT. LOCATION
PAGE
USER
ADDRESS
CUSTOMER
JOB #
INSULATION TESTSTWO-WINDING TRANSFORMERS
Electrical Reliability Services Inc.Houston Area Service Center
1455 E. Sam Houston Pkwy SSuite 190
Pasadena, TX 77503Phone 281-241-2800
NA
31001772 of 4
PLANT DATE LAST INSPECTION
DATE
SUBSTATION Transformer Yard C-07256-5-1POSITION
5/13/11 TEMPERATURE HUMIDITY % C-07256-5-13032.0
°C 46
M4K 0866 Vaundrae Ross and Delon WadeEQPT. INVENTORY NO. TESTED BY:
93500, REVISED 5/21/10COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
OIL TEMP °C
RATED I
1
# TAPS5
NOMINAL33 On Load
CHANGEROff Load
TAP SETTING
YEAR
106350
PRIMARY:SECOND:
1327.621 / 4.400
1091,894
kVA25,00025,000
kV
UG
LB
4930ACCEPTANCE
OA/FA/FA
SUNNY30
110
1991
3CuWDG MATERIAL
PHASESN2 BLANKETED
C-07256-5-1
OIL VOLUMEREASON
CLASSTYPE
WEIGHTSER NO MFR
VOLTAGE (kV)
10IMPEDANCE %
BIL
OILCOOLANT
CPPWEATHER
Dyn1
Diagram # 5 (ANSI)
SERIAL NUM MFR. TYPE/CLASS kV AMPS YEARBUSHING NAMEPLATE
DSG1ZUA3S05786308 CPS 115 80011 2003H11ZUA3S05786304 CPS 115 800 2003H21ZUA3S05786306 CPS 115 800 2003H3
HNS85694 CPS 25 2000 2003L1S85695 CPS 25 2000 2003L2S85693 CPS 25 2000 2003L3S85696 CPS 25 2000 2003LN
CLG
TRANSFORMER OVERALL TESTS
C
C
CHL'
CHL
CHG + CHL
TEST NO
TEST MODE
INSULATION TESTED
1 GST GND H L
20º C %PF
IRAuto/Man
/ CHG GST H L G / 2
10.01
10.00 0.34 0.27 0.800
22.547
10.034
0.6100
0.3410
UST H L 10.00 0.19 0.15 0.800 12.508 0.2390 G / 3
OK4CLG + CHL GST
GND L 5.00 0.800 55.330 2.0910 / 5
GST L H 5.00 0.43 0.34 0.800 42.820 1.8230 G / 6
CHL UST L H 5.00 0.18 0.14 0.800 12.508 0.2290 G / 7
CHL' OK8CHG' / 9 CLG' /
0.269
0.268
0.242
1.514
0.21 0.17 0.800 12.513
0.21 0.17 0.800 12.510
5.944
36.078
ENG GND GAR UST
H
TEST 5 MINUS TEST 6
TEST 1 MINUS TEST 2
MINUS HIGH BUSH.
MINUS LOW BUSH.
HG
LG
TEST LEAD CONFIGURATION
TEST
kV
5,980.60
2,661.60
3,317.80
3,319.00
14,676.4
11,358.3
3,317.90
3,318.10
1,577.03
9,569.90
CAPACITANCE
C (pF)MEASURED
10
WATTSmACORR
FACTOR
0.800
DIRECTPOWER FACTOR %
NO.
H1 360.63 0.24 0.24 1.000 1.360 0.0320 G / 10.01
H2 UST 10.01 362.75 0.31 0.31 1.000 1.368 0.0420 G / 12
H3 UST 10.01 361.19 0.18 0.18 1.000 1.362 0.0250 G / 13
UST14
16
17
18
X1
X2
X3
X0
UST
UST
UST
UST
5.00
5.00
5.00
5.00
612.23
590.54
585.63
522.88
0.46
0.46
0.45
0.45
0.46
0.46
0.45
0.45
1.000
1.000
1.000
1.000
2.308
2.226
2.208
1.971
0.1060
0.1030
0.1000
0.0890
G /
G /
G /
G /
15
19
CAPACITANCE
0.23
0.23
0.23
0.49
0.42
0.46
0.46
365.00
366.00
365.00
620.00
598.00
592.00
529.00
SERIAL #
1ZUA3S05786308
1ZUA3S05786304
1ZUA3S05786306
S85694
S85695
S85693
S85696
OIL TEST
POWER FACTOR
UST11
BUSHING C1 TESTSBUSHING NAMEPLATE TEST
MODETEST
kVCAPACITANCE
C (pF) MEASURED 20º C %PF
CORR FACTOR mA WATTS
TEST NO.
INSULATION TESTSTWO-WINDING TRANSFORMERS
Electrical Reliability Services Inc.Houston Area Service Center
1455 E. Sam Houston Pkwy SSuite 190
Pasadena, TX 77503Phone 281-241-2800
3 of 4PAGE
93500, REVISED 5/21/10COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
21
22
23
24
25
26
27
H1
H2
H3
X1
X2
X3
X0
1ZUA3S05786308
1ZUA3S05786304
1ZUA3S05786306
S85694
S85695
S85693
S85696
GRD
GRD
GRD
GRD
GRD
GRD
GRD
GRD
0.25
0.25
0.25
3,833.00
3,844.00
3,833.00
0.50
0.50
0.50
0.50
0.50
0.50
0.50
3,810.90
3,818.90
3,815.40
234.81
238.68
231.25
248.05
0.36
0.33
0.41
0.52
0.48
0.42
0.48
0.36
0.33
0.41
0.52
0.48
0.42
0.48
1.000
1.000
1.000
1.000
1.000
1.000
1.000
14.367
14.397
14.384
0.885
0.900
0.872
0.935
0.5110
0.4700
0.5920
0.0460
0.0430
0.0370
0.0450
G /
G /
G /
I /
I /
I /
I /
TEST NO.
NO. SERIAL #
BUSHING
POWER FACTOR CAPACITANCE
NAMEPLATE TEST kV
CAPACITANCE C (pF) MEASURED 20º C
CORR FACTOR mA WATTS
IRAuto/Man
EQUIV% POWER FACTOR
20
BUSHING C2 TESTS
28
29
30
IRAuto/ManWATTSTEST MODE mATEST kV
/
/
/
31
32
/
/
33
34
/
/
35
36
/
/
RATED
kVSERIAL # MFROVERALL CATALOG
UNIT CATALOG TYPE ORDERLOCATION
SURGE ARRESTERS
38
39
40
41
42
43
44
45
46
SERIAL # DSG TEST MODE SKIRT # TEST kV mA WATTS IRAuto/Man
37
HOT COLLAR TESTS
EXCITING CURRENT TESTS
kVDETC LTC
CONNECTIONS:
kVmAkV WATTS Induct. (H) mA WATTS Induct. (H)
H1 - H2 H2 - H3
mA WATTS Induct. (H)
H3 - H1
IR
A N 7.547.5416.53 39.39 39.773.3510.013 10.013 10.013 3,521.657,923.72 3,522.12 G / 47
B N 8.018.0117.64 41.98 42.413.5510.017 10.017 10.017 3,319.297,484.76 3,317.63 G / 48
C N 8.548.4818.93 44.85 45.173.8110.014 10.014 10.014 3,111.876,977.40 3,131.69 G / 49
D N 9.029.0320.15 48.02 48.453.9810.012 10.012 10.012 2,943.656,672.78 2,942.35 G / 50
E N 9.599.6121.60 51.54 52.034.2110.014 10.014 10.014 2,769.286,309.49 2,763.81 G / 51
NEUTRAL BUSHING
GDIB
HLGN
====
====
INSULATION RATING KEYGOODDETERIORATED
HIGH VOLTAGE WINDING
INVESTIGATE
LOW VOLTAGE WINDING
NOTE: SHORT EACH WINDING ON ITSELF
BAD
EQUIVALENT CIRCUIT
= QUESTIONABLEQ
GROUND
COMMENTS: Test satisfactory.All Test results are good and comparableXfmr has a core ground
EQPT. LOCATION
PAGE
USER
ADDRESS
CUSTOMER
JOB #
INSULATION TESTSTWO-WINDING TRANSFORMERS
Electrical Reliability Services Inc.Houston Area Service Center
1455 E. Sam Houston Pkwy SSuite 190
Pasadena, TX 77503Phone 281-241-2800
NA
31001774 of 4
PLANT DATE LAST INSPECTION
DATE
SUBSTATION Transformer Yard C-07256-5-1POSITION
5/13/11 TEMPERATURE HUMIDITY % C-07256-5-13032.0
°C 46
M4K 0866 Vaundrae Ross and Delon WadeEQPT. INVENTORY NO. TESTED BY:
93500, REVISED 5/21/10COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
OIL TEMP °C
RATED I
1
# TAPS5
NOMINAL33 On Load
CHANGEROff Load
TAP SETTING
YEAR
106350
PRIMARY:SECOND:
1327.621 / 4.400
1091,894
kVA25,00025,000
kV
UG
LB
4930ACCEPTANCE
OA/FA/FA
SUNNY30
110
1991
3CuWDG MATERIAL
PHASESN2 BLANKETED
C-07256-5-1
OIL VOLUMEREASON
CLASSTYPE
WEIGHTSER NO MFR
VOLTAGE (kV)
10IMPEDANCE %
BIL
OILCOOLANT
CPPWEATHER
Dyn1
Diagram # 5 (ANSI)
SERIAL NUM MFR. TYPE/CLASS kV AMPS YEARBUSHING NAMEPLATE
DSG1ZUA3S05786308 CPS 115 80011 2003H11ZUA3S05786304 CPS 115 800 2003H21ZUA3S05786306 CPS 115 800 2003H3
HNS85694 CPS 25 2000 2003L1S85695 CPS 25 2000 2003L2S85693 CPS 25 2000 2003L3S85696 CPS 25 2000 2003LN
CLG
TRANSFORMER OVERALL TESTS
C
C
CHL'
CHL
CHG + CHL
TEST NO
TEST MODE
INSULATION TESTED
1 GST GND H L
20º C %PF
IRAuto/Man
/ CHG GST H L G / 2
10.01
10.00 0.34 0.27 0.800
22.547
10.034
0.6100
0.3410
UST H L 10.00 0.19 0.15 0.800 12.508 0.2390 G / 3
OK4CLG + CHL GST
GND L 5.00 0.800 55.330 2.0910 / 5
GST L H 5.00 0.43 0.34 0.800 42.820 1.8230 G / 6
CHL UST L H 5.00 0.18 0.14 0.800 12.508 0.2290 G / 7
CHL' OK8CHG' / 9 CLG' /
0.269
0.268
0.242
1.514
0.21 0.17 0.800 12.513
0.21 0.17 0.800 12.510
5.944
36.078
ENG GND GAR UST
H
TEST 5 MINUS TEST 6
TEST 1 MINUS TEST 2
MINUS HIGH BUSH.
MINUS LOW BUSH.
HG
LG
TEST LEAD CONFIGURATION
TEST
kV
5,980.60
2,661.60
3,317.80
3,319.00
14,676.4
11,358.3
3,317.90
3,318.10
1,577.03
9,569.90
CAPACITANCE
C (pF)MEASURED
10
WATTSmACORR
FACTOR
0.800
DIRECTPOWER FACTOR %
NO.
H1 360.63 0.24 0.24 1.000 1.360 0.0320 G / 10.01
H2 UST 10.01 362.75 0.31 0.31 1.000 1.368 0.0420 G / 12
H3 UST 10.01 361.19 0.18 0.18 1.000 1.362 0.0250 G / 13
UST14
16
17
18
X1
X2
X3
X0
UST
UST
UST
UST
5.00
5.00
5.00
5.00
612.23
590.54
585.63
522.88
0.46
0.46
0.45
0.45
0.46
0.46
0.45
0.45
1.000
1.000
1.000
1.000
2.308
2.226
2.208
1.971
0.1060
0.1030
0.1000
0.0890
G /
G /
G /
G /
15
19
CAPACITANCE
0.23
0.23
0.23
0.49
0.42
0.46
0.46
365.00
366.00
365.00
620.00
598.00
592.00
529.00
SERIAL #
1ZUA3S05786308
1ZUA3S05786304
1ZUA3S05786306
S85694
S85695
S85693
S85696
OIL TEST
POWER FACTOR
UST11
BUSHING C1 TESTSBUSHING NAMEPLATE TEST
MODETEST
kVCAPACITANCE
C (pF) MEASURED 20º C %PF
CORR FACTOR mA WATTS
TEST NO.
SERIAL NUMBERMANUFACTURER
18.4090
TTR C30-005 Vaundrae Ross and Delon WadeEQPT. INVENTORY NO. TESTED BY:
56400, REVISED 4/17/08COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
USER
ADDRESS
CUSTOMER
JOB #
TRANSFORMER LOAD TAP CHANGERTURNS RATIO TEST3 Phase Test Method
Electrical Reliability Services Inc.Houston Area Service Center
1455 E. Sam Houston Pkwy SSuite 190
Pasadena, TX 77503Phone 281-241-2800
NA
31001774 of 4
PLANT DATE LAST INSPECTION
DATE
SUBSTATION Transformer Yard C-07256-5-1POSITION
5/13/11 TEMPERATURE HUMIDITY % C-07256-5-130 °C 28
NAMEPLATE DATA
C-07256-5-1
15L
14L
13L
12L11L
10L
9L
8L
7L
6L
5L
4L3L
2L
1L
N
1R
2R
3R
4R5R
6R
7R
8R
9R
10R
11R
12R13R
14R
15R
16R
/
/
/
/
//
/
/
/
/
/
/
//
/
/
/
/
/
/
//
/
/
/
/
/
/
//
/
/
/
16L
TAP NO.
CALCULATED RATIO
PRIMARY VOLTAGE
SECONDARY TAP VOLTAGE
MEASURED RATIO
3 H 1H 2 3
Test satisfactory.COMMENTS:
DEFICIENCIES:
03
11,880
11,963
12,045
12,128
12,21012,293
12,375
12,458
12,540
12,623
12,705
12,788
12,87012,953
13,035
13,118
13,200
13,283
13,365
13,448
13,53013,613
13,695
13,778
13,860
13,943
14,025
14,108
14,19014,273
14,355
14,438
14,520
6,858
6,906
6,954
7,002
7,0497,097
7,144
7,192
7,239
7,287
7,335
7,383
7,4307,478
7,526
7,574
7,620
7,669
7,716
7,764
7,8117,859
7,906
7,954
8,002
8,049
8,097
8,145
8,1928,240
8,288
8,336
8,383
132,000
132,000
132,000
132,000
132,000132,000
132,000
132,000
132,000
132,000
132,000
132,000
132,000132,000
132,000
132,000
132,000
132,000
132,000
132,000
132,000132,000
132,000
132,000
132,000
132,000
132,000
132,000
132,000132,000
132,000
132,000
132,000
19.2476
19.1138
18.9819
18.8518
18.726118.5994
18.4770
18.3537
18.2346
18.1145
17.9959
17.8789
17.765817.6518
17.5392
17.4280
17.3228
17.2122
17.1073
17.0015
16.899216.7960
16.6962
16.5954
16.4959
16.3996
16.3023
16.2063
16.113316.0194
15.9266
15.8349
15.7462
19.2610
19.1040
18.9150
18.8330
18.743018.5980
18.4090
18.3350
18.2490
18.1120
17.9330
17.8620
17.778017.6510
17.4850
17.4140
17.3370
17.2700
17.1960
17.0730
16.912016.8490
16.7780
16.6630
16.5140
16.4480
16.3800
16.2700
16.129016.0680
16.0020
15.9000
15.7610
19.2640
19.1090
18.9140
18.8360
18.745018.6050
18.4120
18.3340
18.2490
18.1160
17.9340
17.8660
17.782017.6560
17.4850
17.4150
17.3400
17.2700
17.1970
17.0730
16.914016.8570
16.7800
16.6650
16.5100
16.4530
16.3850
16.2780
16.127016.0700
16.0030
15.9020
15.7600
19.2650
19.1120
18.9120
18.8350
18.745018.6000
18.3360
18.2500
18.1160
17.9340
17.8660
17.781017.6570
17.4830
17.4160
17.3380
17.2720
17.1960
17.0780
16.912016.8560
16.7790
16.6680
16.5120
16.4530
16.3830
16.2770
16.127016.0710
16.0030
15.9060
15.7630
1X0/X 2X0/XH1H 3X0/XH2H
Cooper Power Systems
M4K 0866 Vaundrae Ross and Delon WadeEQPT. INVENTORY NO. TESTED BY:
56365, REVISED 3/4/09COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
USER
ADDRESS
CUSTOMER
JOB #
TRANSFORMERTURNS RATIO TEST
Electrical Reliability Services Inc.Houston Area Service Center
1455 E. Sam Houston Pkwy SSuite 190
Pasadena, TX 77503Phone 281-241-2800
NA
3100177
PLANT DATE LAST INSPECTION
DATE
SUBSTATION Transformer Yard C-07256-5-1POSITION
5/13/11 TEMPERATURE HUMIDITY % C-07256-5-13232.0
°C 30
NAMEPLATE DATA
OIL TEMP °C
RATED I
1
# TAPS5
NOMINAL33 On Load
CHANGEROff Load
TAP SETTING
YEAR
106350
PRIMARY:SECOND:
13213.2 / 7.621
66656
kVA15,00015,000
kV
UG
LB
4930Acceptance
OA/FA/FA
Sunny32
110
6/1991
3Cu
0.5ALLOWED ERR %
WDG MATERIALPHASES
N2 BLANKETED
C-07256-5-1
OIL VOLUMEREASON
CLASSTYPE
WEIGHTSER NO MFR
VOLTAGE (kV)
10IMPEDANCE %
BIL
OILCOOLANT
CPPWEATHER
Dyn1
SERIAL NUM MFR. TYPE/CLASS kV AMPS YEARBUSHING NAMEPLATE
DSGH1H2H3HNL1L2L3LN
H1 - H3 / X1 - X01 3 1 0 H2 - H1 / X2 - X02 1 2 0 H3 - H2 / X3 - X03 2 3 0
Ph(min)Error Error IexcPh(min)Ratio RatioRatio Error Iexc Ph(min)
HIGH SIDE TAPS TO LOW SIDE NOMINAL TURNS RATIO TESTS
# IexcPRIMARY
TAPSEC. TAP
CALC RATIO
HIGH SIDE VOLTAGE
LOW SIDE VOLTAGE
Test Volt.
R2 (1) Nominal 141,600 13,200 18.5990 18.5970 18.58000.09 0.001 18.5802 0.10
R1 (2) Nominal 136,800 13,200 17.9580 17.9560 17.95000.03 0.002 17.9504 0.04
Nominal Nominal 132,000 13,200 17.3370 17.3400 17.32000.11 0.003 17.3205 0.10
L1 (4) Nominal 127,200 13,200 16.7010 16.7080 16.69000.10 0.004 16.6907 0.06
L2 (5) Nominal 122,400 13,200 16.0810 16.0790 16.06000.11 0.015 16.0608 0.13
COMMENTS: Test Satisfactory
DEFICIENCIES:
A Member of the WICOR Group
Diss
olve
d G
as A
naly
sis
Oil
Scre
enDi
agno
stic
sWEIDMANN DIAGNOSTIC SOLUTIONS
8406 SCRANTON STREET + HOUSTON, TX + 77061(713) 595-1030 + (713) 595-1034
WWW.WEIDMANN-DIAGNOSTICS.COM
HOUSTON, TXATTN: PO #:
Location:
Serial #:
Bank/Ph:
Tank:
Breathing:
Fluid:
Mfr:
KV:
KVA:
Imp.(% Z):
Container:
Project ID:
Account:
Order #:
Control #:
Received:
Reported:
Customer ID:Gallons:
LUFKIN
C0725651
3
TRANSFORMER
SEAL
MIN 106350
COOPER
13.2/7.62
15000
R465 3 3 3
67
307210
6035991
08/10/2009
08/20/2009
Acceptable for in-service oil (35 ppm max).
Acceptable for in-service oil (26 kV min).
Acceptable for in-service oil (0.5% max).
Acceptable for in-service oil (5% max).
Acceptable for in-service oil (25 dynes/cm min).
Acceptable for in-service oil (0.2 mg KOH/g max).
Diagnostic not applicable for Type I. Exceeds limit for in-service oil Type II (0.09% min).
Color Number diagnostic not applicable. Visual diagnostic not applicable.
Hydrogen within condition 1 limits (100 ppm).Acetylene within condition 1 limits (2 ppm).Ethylene within condition 1 limits (50 ppm).Carbon Monoxide within condition 1 limits (350 ppm).Overall equipment condition code: 1.
Analyzed gases do not exceed warning thresholds. Rogers Ratios do not apply.
CO2/CO Ratio not applicable - neither gas exceeds its limit.
No previous sample available.
DGA Key Gas / Interpretive Method:
DGA Rogers Ratio Method:DGA Cellulose (Paper) Insulation:
DGA IEEE/ANSI (C57.104-1991):
Moisture in Oil:Interfacial Tension:
Acid Number:Color Number and Visual:
Dielectric Breakdown D-877:Dielectric Breakdown D-1816:
Power Factor @ 25C:Power Factor @ 100C:
Oxidation Inhibitor:
IEEE (C57.104)(Most recent sample)
(Two most recent samples)
603599108/07/2009
30721038
0.885
L.5CLR&SPRK
ND
4
0.0721
1267
7
72577292
79349
9
022
22
5
65
48
0.0130.524
40.40.006
< 0.020
Hydrogen (H2):Methane (CH4):Ethane (C2H6):
Ethylene (C2H4):Acetylene (C2H2):
Carbon Monoxide (CO):Carbon Dioxide (CO2):
Nitrogen (N2):Oxygen (O2):
Total Dissolved Gas:Total Dissolved Combustible Gas:
Equivalent TCG Percent:
D-1533B Moisture in Oil (ppm):D-971 Interfacial Tension (dynes/cm):D-974 Acid Number (mg KOH/g):D-1500 Color Number (Relative):D-1524 Visual Exam. (Relative):D-1524 Sediment Exam. (Relative):D-877 Dielectric Breakdown (kV):D-1816 Dielectric Breakdown 1 mm (kV mm-C):D-1816 Dielectric Breakdown 2 mm (kV mm-C):D-924 Power Factor @ 25C (%):D-924 Power Factor @ 100C (%):D-1298 Specific Gravity (Relative):WDS Passivator (ppm):D-2668 Oxidation Inhibitor (wt. %):
ASTM D-3612 Lab Control Number:Report Units: PPM Date Sampled:
Order Number:Oil Temp.(C):
The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann Diagnostic Solutions does not imply that the contents of the sample received by this laboratory are the same asall such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgement of Weidmann Diagnostic Solutions. WeidmannDiagnostic Solutions assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon forany reason whatsoever.
A Member of the WICOR Group
Diss
olve
d G
as A
naly
sis
Oil
Scre
enDi
agno
stic
sWEIDMANN DIAGNOSTIC SOLUTIONS
8406 SCRANTON STREET + HOUSTON, TX + 77061(713) 595-1030 + (713) 595-1034
WWW.WEIDMANN-DIAGNOSTICS.COM
��
HOUSTON, TXATTN: PO #:
Location:
Serial #:
Bank/Ph:
Tank:
Breathing:
Fluid:
Mfr:
KV:
KVA:
Imp.(% Z):
Container:
Project ID:
Account:
Order #:
Control #:
Received:
Reported:
Customer ID:Gallons:
LUFKIN
C0725651LTC
LTC
SEAL
MIN 190
COOPER
3A 3A 3A
67
307210
6036005
08/10/2009
08/20/2009
Acceptable for equipment > 69 kV for in-service oil - kV not provided (25 ppm max).
Diagnostic not applicable.
Diagnostic not applicable.
Diagnostic not applicable.
Color Number diagnostic not applicable. Visual diagnostic not applicable.
DGA Key Gas / Interpretive Method:
Moisture in Oil:Interfacial Tension:
Acid Number:Color Number and Visual:
Dielectric Breakdown D-877:Dielectric Breakdown D-1816:
Power Factor @ 25C:Power Factor @ 100C:
Oxidation Inhibitor:
IEEE (C57.104)(Most recent sample)
603600508/07/2009
307210
L.5CLR&SPRK
PARTICULATES
25
35
46.10.003
Hydrogen (H2):Methane (CH4):Ethane (C2H6):
Ethylene (C2H4):Acetylene (C2H2):
Carbon Monoxide (CO):Carbon Dioxide (CO2):
Nitrogen (N2):Oxygen (O2):
Total Dissolved Gas:Total Dissolved Combustible Gas:
Equivalent TCG Percent:
D-1533B Moisture in Oil (ppm):D-971 Interfacial Tension (dynes/cm):D-974 Acid Number (mg KOH/g):D-1500 Color Number (Relative):D-1524 Visual Exam. (Relative):D-1524 Sediment Exam. (Relative):D-877 Dielectric Breakdown (kV):D-1816 Dielectric Breakdown 1 mm (kV mm-C):D-1816 Dielectric Breakdown 2 mm (kV mm-C):D-924 Power Factor @ 25C (%):D-924 Power Factor @ 100C (%):D-1298 Specific Gravity (Relative):WDS Passivator (ppm):D-2668 Oxidation Inhibitor (wt. %):
ASTM D-3612 Lab Control Number:Report Units: PPM Date Sampled:
Order Number:Oil Temp.(C):
The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann Diagnostic Solutions does not imply that the contents of the sample received by this laboratory are the same asall such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgement of Weidmann Diagnostic Solutions. WeidmannDiagnostic Solutions assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon forany reason whatsoever.
Furanic Compounds in Electrical Insulating Liquids by HPLCASTM D-5837 Report
WEIDMANN DIAGNOSTIC SOLUTIONS8406 SCRANTON STREET + HOUSTON, TX + 77061
(713) 595-1030 + (713) 595-1034WWW.WEIDMANN-DIAGNOSTICS.COM
��
HOUSTON, TXATTN: PO #:
Location:
Serial #:
Bank/Ph:
Tank:
Breathing:
Fluid:
Mfr:
KV:
KVA:
Imp.(% Z):
Container:
Project ID:
Account:
Order #:
Control #:
Received:
Reported:
Customer ID:Gallons:
LUFKIN
C0725651
3
TRANSFORMER
SEAL
MIN 106350
COOPER
13.2/7.62
15000
R465 3 3 3
67
307210
6035991
08/10/2009
08/20/2009
A Member of the WICOR Group
< 10
< 10
< 10
< 10
< 10
10
10
10
10
10
2-Furaldehyde
5-Hydroxy-methyl-furaldehyde
2-Acetylfuran
5-Methyl-2-furaldehyde
2-Furyl alcohol
Furanic Compound Result (ppb) Reporting Limit (ppb)
* BRL = Below Reporting Limit
The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann Diagnostic Solutions does notimply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relateonly to the sample or samples tested. Any interpretations or opinions expressed represent the best judgement of Weidmann Diagnostic Solutions. Weidmann DiagnosticSolutions assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment orother property for which this report may be used or relied upon for any reason whatsoever.
Results:
Diagnostics:
Notations:
New insulation with a high degree of mechanical strength will typically have a Degree of Polymerization (DP) of 1000-1300. "Middle Aged" paper isapproximately 500 and paper with less than 250 is in its "Old Age". Severely degraded insulation with a DP of 150 or less will have very little mechanicalstrength and may result in a transformer failure. The following estimations are based on current research of GSU transformers filled with mineral oil.
QC Chemist: CN
Estimated Degree of Polymerization (DP): >1003Estimated Operating Age of the Equipment: <1.0
Name Tap Changer
H1 H2 3
H2 H3 3
H3 H1 3
x0 x1 3
x0 x2 3
x0 x3 37/20/2011 09:31:02 AM x0 x3 closed shorted +
shorted +
7/20/2011 09:25:22 AM x0 x1 closed shorted +
7/20/2011 09:28:53 AM x0 x2 closed
shorted +
7/20/2011 09:08:17 AM H2 H3 closed shorted +
7/20/2011 09:14:01 AM H3 H1 closed
shorted +
Test Traces
Date/Time Red Blue Tertiary Other
7/20/2011 09:01:46 AM H1 H2 closed
Vector Group: Dyn0
MVA Rating: 1.7E-05MVA
High Voltage: 132kV
Low Voltage: 7.62kV
Tertiary Voltage: 0kV
Phases: 3
Number:
Transformer
Serial Number: C-07258-5-1
Manufacturer: Cooper
Type Code:
Year: 1991
Location: Canonsburg PA
Comment:
OMICRON FRAnalyzer 2.0
Tester: jboney
Date / Time: 7/20/2011 09:31:02 AM
Location: 2217 Aldine Bender Rd
Oil Temperature: 35 °C / 95 °F
7/20/2011 9:49:35 AM 1 / 4
OMICRON FRAnalyzer 2.0
1 MHz 2 MHz logarithmic 110
100 kHz 1 MHz logarithmic 210
100 Hz 1 kHz logarithmic 210
20 Hz 100 Hz logarithmic 50
10 kHz 100 kHz logarithmic 210
1 kHz 10 kHz logarithmic 210
Customized Frequency Ranges:
From Frequency To Frequency Sweep Mode Points
Attenuator: <adapt automatically>
Input Impedance: 50 ȍ
Receiver Bandwidth: <adapt automatically>
Sweep Settings
Start Frequency: 20 Hz
Stop Frequency: 2 MHz
Sweep Mode: see customized frequency ranges
Points / Sweep: 1000
7/20/2011 9:49:35 AM 2 / 4