2
˚C Pressure kPa (Gauge) R12 R134a R406A Bub Dew R408A Bub Dew R409A Bub Dew R407F GENETRON® PERFORMAX™ LT Bub Dew R417A ISCEON 59 Bub Dew R404A Bub Dew R407C Bub Dew R410A Bub Dew R22 R507 Bub Dew R744 CO 2 R717 NH 3 R600a ISO BUTANE R290 PROPANE HFO 1234yf HFO 1234ze -50 -62 -72 -75 -57 -25 -23 -72 -54 -43 -18 -57 -42 -20 -17 -51 -28 7 8 -37 -15 -15 581 -61 -92 -31 -64 -81 -48 -58 -68 -72 -52 -17 -15 -68 -48 -36 -9 -52 -36 -12 -8 -45 -19 19 19 -30 -6 -6 638 -55 -90 -23 -60 -78 -46 -53 -64 -68 -48 -9 -7 -64 -43 -28 0 -46 -29 -3 1 -39 -11 31 31 -22 3 3 699 -50 -90 -17 -55 -75 -44 -48 -60 -65 -42 1 3 -60 -37 -20 10 -40 -21 8 11 -32 -2 44 45 -14 14 14 763 -43 -88 -8 -50 -72 -42 -43 -55 -61 -36 10 13 -55 -30 -11 22 -33 -13 18 22 -24 8 58 59 -6 25 25 831 -37 -86 1 -45 -68 -40 -37 -50 -56 -29 21 24 -50 -23 -1 34 -25 -4 30 34 -16 19 74 74 4 37 37 903 -30 -85 10 -39 -65 -38 -31 -45 -51 -22 33 36 -45 -15 9 47 -18 5 42 47 -7 30 90 90 14 50 50 978 -21 -83 20 -32 -61 -36 -24 -39 -45 -14 45 48 -39 -7 20 61 -9 15 55 60 3 43 107 108 25 64 64 1059 -13 -81 30 -26 -56 -34 -17 -32 -40 -6 59 61 -32 2 32 75 1 26 70 74 14 56 126 127 37 79 79 1143 -3 -79 41 -19 -51 -32 -10 -25 -34 2 72 76 -25 12 45 91 10 38 85 90 25 70 147 147 49 94 94 1232 7 -76 54 -11 -46 -30 -1 -17 -27 12 88 91 -17 22 59 108 21 50 101 106 37 85 168 169 63 112 112 1326 18 -73 66 -2 -40 -28 8 -9 -19 21 104 107 -9 32 74 126 33 63 118 124 50 102 191 192 76 130 130 1423 30 -70 80 7 -34 -26 17 0 -12 32 121 125 0 44 90 145 45 78 136 143 65 119 215 216 92 148 149 1527 43 -67 94 17 -28 -24 28 10 -3 43 139 143 9 56 107 165 59 93 156 163 80 138 241 243 108 169 169 1635 57 -63 110 27 -21 -22 38 20 6 56 158 163 19 70 125 187 73 110 177 183 96 158 269 270 125 190 190 1749 72 -60 126 38 -12 -20 50 32 16 69 179 183 30 84 145 211 88 127 198 205 113 178 298 299 144 213 213 1867 89 -56 143 50 -5 -18 61 43 26 83 200 205 42 99 165 235 105 145 222 229 132 200 329 330 163 237 237 1991 106 -52 161 62 4 -16 74 56 37 97 224 228 54 114 188 261 122 164 247 254 152 224 362 363 184 263 263 2121 125 -48 181 75 14 -14 88 70 49 112 248 253 68 132 212 289 141 185 273 280 172 249 396 398 206 289 289 2256 145 -43 200 90 24 -12 102 84 61 129 274 278 82 149 236 318 161 207 300 308 195 276 433 434 229 318 318 2398 166 -37 222 105 34 -10 117 99 74 146 300 306 97 168 263 348 181 229 329 338 218 303 471 473 254 348 348 2546 189 -32 244 121 46 -8 134 116 89 164 329 335 113 187 291 380 203 254 360 369 243 333 512 514 279 379 380 2700 214 -25 267 137 58 -6 150 133 104 183 359 364 130 209 321 414 227 279 392 401 270 363 555 557 306 413 413 2860 240 -19 291 155 71 -4 168 152 120 203 391 397 147 231 352 450 251 306 426 435 298 396 599 601 335 447 448 3027 267 -13 318 174 85 -2 187 171 137 225 424 430 167 254 386 488 278 334 462 471 328 430 646 649 364 484 484 3200 297 -6 345 194 100 0 207 192 155 247 459 465 187 278 420 527 305 364 499 508 359 466 697 699 396 522 523 3382 328 2 373 214 115 2 227 213 174 271 495 502 208 304 457 569 334 395 538 548 392 504 748 751 429 562 563 3570 361 10 402 236 132 4 249 236 194 296 533 540 230 331 497 613 365 429 579 589 427 544 803 806 464 605 605 3765 396 19 433 260 149 6 272 260 215 321 574 581 254 359 537 658 398 463 622 633 464 586 860 863 501 649 650 3968 433 28 466 284 167 8 296 286 237 349 616 623 279 389 581 706 431 499 667 678 502 629 920 923 539 695 696 4179 472 37 500 309 187 10 321 313 260 377 659 667 305 420 626 756 467 537 714 726 543 675 983 987 579 743 744 4398 513 47 535 336 207 12 347 342 285 407 706 713 333 452 673 808 504 577 763 774 586 722 1049 1052 621 794 794 4625 557 58 572 364 228 14 375 371 311 438 753 761 362 486 723 863 544 618 814 826 630 772 1117 1121 665 847 847 4861 603 69 610 393 251 16 404 402 338 471 803 812 392 521 775 921 584 661 868 881 678 825 1189 1193 710 902 903 5106 651 81 650 424 275 18 433 435 367 504 856 864 424 558 830 980 628 707 924 936 727 879 1263 1267 759 959 960 5360 702 93 692 456 300 20 465 470 396 539 909 918 457 597 887 1042 672 754 983 995 779 936 1341 1346 808 1019 1020 5624 756 106 734 490 326 22 497 506 427 577 967 975 492 637 947 1107 720 803 1043 1056 832 995 1422 1427 860 1081 1082 5898 812 120 779 525 353 24 531 544 460 615 1025 1034 528 679 1009 1174 769 855 1107 1120 889 1056 1506 1512 914 1146 1147 6182 871 134 826 562 382 26 567 584 495 655 1087 1096 567 722 1075 1244 821 909 1173 1186 948 1121 1594 1600 970 1213 1215 0 933 150 874 600 412 28 604 625 531 697 1151 1160 607 768 1142 1317 874 965 1241 1255 1009 1187 1686 1691 1029 1284 1285 0 997 165 925 640 444 30 642 668 568 740 1217 1226 649 815 1214 1393 930 1022 1312 1326 1074 1257 1781 1787 1090 1357 1358 0 1065 182 977 681 477 32 681 714 606 785 1286 1295 692 864 1288 1472 989 1083 1386 1400 1141 1329 1880 1886 1153 1432 1434 0 1136 199 1031 725 511 34 723 761 647 832 1357 1367 738 915 1365 1554 1049 1146 1463 1477 1211 1404 1983 1989 1219 1511 1512 0 1211 218 1087 770 547 36 766 810 690 881 1431 1441 785 968 1446 1639 1113 1211 1543 1558 1284 1482 2090 2096 1287 1593 1594 0 1288 236 1145 817 585 38 811 861 734 931 1508 1519 834 1023 1530 1727 1179 1279 1626 1641 1360 1563 2201 2208 1358 1678 1679 0 1368 256 1205 866 624 40 857 914 780 983 1588 1598 886 1080 1617 1819 1247 1349 1712 1727 1439 1647 2316 2323 1431 1765 1767 0 1453 277 1267 916 665 42 905 970 828 1038 1671 1682 940 1139 1707 1913 1319 1422 1802 1816 1521 1734 2436 2443 1508 1857 1858 0 1541 298 1331 969 708 44 954 1028 878 1093 1756 1767 995 1200 1802 2012 1393 1498 1894 1909 1607 1824 2559 2567 1586 1951 1953 0 1633 321 1398 1024 752 46 1006 1088 929 1151 1845 1857 1053 1263 1900 2114 1470 1576 1990 2005 1696 1917 2688 2695 1668 2050 2051 0 1729 345 1467 1080 798 48 1060 1151 983 1211 1937 1948 1113 1328 2002 2219 1550 1657 2090 2105 1789 2013 2821 2829 1753 2151 2153 0 1828 369 1538 1139 845 50 1115 1216 1040 1274 2033 2044 1175 1397 2108 2328 1633 1742 2193 2208 1885 2113 2959 2968 1840 2256 2259 0 1931 394 1611 1200 896 52 1171 1283 1098 1338 2131 2143 1240 1466 2219 2441 1719 1829 2300 2314 1985 2217 3103 3111 1931 2365 2367 0 2039 420 1687 1264 947 54 1231 1353 1158 1404 2233 2245 1308 1539 2333 2558 1809 1919 2411 2425 2089 2323 3251 3259 2024 2479 2480 0 2151 448 1765 1329 1001 56 1292 1426 1220 1472 2338 2350 1377 1614 2452 2678 1902 2013 2525 2540 2197 2434 3405 3413 2121 2596 2598 0 2267 476 1845 1397 1057 58 1355 1501 1285 1543 2447 2459 1450 1691 2575 2803 1997 2109 2644 2659 2310 2548 3565 3572 2221 2717 2719 0 2387 506 1929 1467 1115 60 1419 1579 1353 1616 2560 2572 1525 1771 2704 2931 2097 2209 2768 2781 2426 2666 3730 3738 2325 2844 2846 0 2513 537 2014 1539 1175 Pressure Temperature Chart Liquid Temperature Volume Flow cfm x 0.472 = l/s fpm x 0.00508 = m/s imp. gal/min x 0.0758 = l/s U.S. gal/min x 0.0631 = l/s Volume ft 3 x 0.02832 = m 3 Please note: This chart is intended as a guide only. Conversion Factors Velocity fps x 0.3048 = m/s fpm x 0.00508 = m/s Temperature ˚C = (˚F - 32) ÷ 1.8 ˚F = (˚C x 1.8) + 32 Heat Flow Btu/hr x 0.252 – kcal/hr Btu/hr x 0.293 = watts watts x 0.86 = kcal/hr watts x 3.4129 = Btu/hr watts x 0.000284 = ton (refr) Pressure kPa ÷ 6.89 = psi inch Hg x 3.39 = kPa inch H2O x 0.249 = kPa mm Hg (1 torr) x 0.133 = kPa Heat Flow (cont.) watts x 0.00133 = HP kcal/hr x 1.163 = watts kcal/hr x 3.97 = Bru/hr HP x 746 = watts ton (refr) x 3517 = watts Follow us on SA EDITION 01/09/2014 CAPE TOWN T 021 551 8790 F 021 551 8758 [email protected] GAUTENG T 011 392 4791 F 011 392 2296 www.agas.com GUIDE TO REFRIGERANT REPLACEMENTS REFRIGERANT REPLACEMENT (ZERO ODP) There is no single product that can replace R22 in all applicaons. If you need help on any parcular applicaon, please contact us. * Not suitable for systems with capillary tube, expansion valve only. ** 50/50 mix of Mineral/Alkylbenzene preferred. LONG-TERM REPLACEMENT PREVIOUS / PHASING OUT (ODP) GWP 1480 HFO 1234ze HFO OIL Polyol Ester APPLICATION Med Temp Refrig Water Chillers GWP 6 R11 CFC APPLICATION Centrifugal Chillers GWP 4750 CFC BANNED R437A ISCEON® M049PlusHFC OIL Mineral** Alkylbenzene Polyol Ester APPLICATION Auto Air Cond Med Temp Refrig GWP 1805 R134a HFC OIL Polyol Ester Polyalkylene- Glycol APPLICATION Med Temp Refrig Air Condioning Auto Air Cond GWP 1430 R600a ISO Butane HC OIL Mineral Alkylbenzene APPLICATION Domesc Refrig HFO 1234yf HFO OIL Polyol Ester Polyalkylene- Glycol APPLICATION Auto Air Cond GWP 4 GWP 3 HFO 1234ze HFO OIL Polyol Ester APPLICATION Med Temp Refrig Water Chillers GWP 6 R12 CFC APPLICATION Auto Air Cond Med Temp Refrig High Temp Refrig GWP 10900 CFC BANNED R290 Refrigerant Grade Propane OIL Mineral APPLICATION Low Temp Refrig Med Temp Refrig HC GWP 3 HFC OIL Polyol Ester APPLICATION Low Temp Refrig Med Temp Refrig GENETRON® PERFORMAX™ LT R407F GWP 1824 R422A ISCEON® M079 OIL Mineral** Alkylbenzene Polyol Ester APPLICATION Low Temp Refrig Med Temp Refrig HFC GWP 3143 R404A HFC OIL Polyol Ester APPLICATION Low Temp Refrig Med Temp Refrig (FX70/HP62) R125/143a/134a (44/52/4%) R507 HFC OIL Polyol Ester APPLICATION Low Temp Refrig Med Temp Refrig (AZ50) R125/143a (50/50%) GWP 3922 GWP 3985 R1270 Propylene OIL Mineral APPLICATION Low Temp Refrig Med Temp Refrig HC GWP 2 R407A HFC OIL Polyol Ester APPLICATION Med Temp Refrig Klea60 GWP 2107 R502 CFC APPLICATION Low Temp Refrig Med Temp Refrig R22/115 (50/50%) GWP 4657 CFC BANNED R417A ISCEON® M059 HFC OIL Mineral** Alkylbenzene Polyol Ester APPLICATION Med Temp Refrig Air Condioning R422D ISCEON® M029 HFC OIL Mineral Alkylbenzene Polyol Ester APPLICATION Med Temp Refrig Air Condioning Water Chillers R424A RS44 HFC OIL Mineral Alkylbenzene Polyol Ester APPLICATION Med Temp Refrig Air Condioning R434A* RS45 HFC OIL Mineral Alkylbenzene Polyol Ester APPLICATION Low Temp Refrig Med Temp Refrig Water Chillers GWP 2346 GWP 2729 GWP 2440 GWP 3245 R407C HFC OIL Polyol Ester APPLICATION Air Condioning (Klea 66/ Suva 9000) R32/125/134a (23/25/52%) R410A OIL Polyol Ester APPLICATION Air Condioning (AZ20) R32/125 (50/50%) HFC R744 CO2 OIL Mineral APPLICATION Various Carbon Dioxide HFC OIL Polyol Ester APPLICATION Low Temp Refrig Med Temp Refrig GENETRON® PERFORMAX™ LT R407F GWP 1824 GWP 1 GWP 1774 GWP 2088 ISCEON® M089 HFC OIL Mineral Alkylbenzene Polyol Ester APPLICATION Ultra Low Temp Refrigeraon GWP 3698 R23 HFC OIL Polyol Ester APPLICATION Ultra Low Temp Refrigeraon GWP 14800 R508A HFC OIL Polyol Ester APPLICATION Ultra Low Temp Refrigeraon R23/116 (39/61%) GWP 13214 R508B HFC OIL Polyol Ester APPLICATION Ultra Low Temp Refrigeraon Sulva 95 GWP 13396 R13 CFC APPLICATION Ultra Low Temp Refrigeraon OR R503 R23/13 CFC BANNED R123 HCFC APPLICATION Centrifugal Chillers GWP 120 APPLICATION Low Temp Refrig Med Temp Refrig HCFC R409A OR R406A GWP 1943 GWP 1585 APPLICATION Low Temp Refrig Med Temp Refrig HCFC OR R408A R22 HCFC APPLICATION Low Temp Refrig Med Temp Refrig Air Condioning GWP 1810 GWP 3152 R402A GWP 2788 R402B GWP 2416 R403B GWP 4457 OIL Mineral Alkylbenzene Polyol Ester OIL Mineral Alkylbenzene Follow us on ‘Drop in’ is a generic term; refrigerants should never be mixed or dropped in on top of an exisng refrigerant. HFC Drop in replacements in most cases do not require a change of lubricant type, however manufacturers’ guidance as well as good engineering pracce should be followed. All informaon supplied is for guide purposes only. Please note: Not all products are available in all outlets. YOUR SOLUTIONS PROVIDER
Transcript
Page 1: Pressure Temperature Chart GUIDE TO REFRIGERANT ... · ˚C Pressure kPa (Gauge) R12 R134a R406A Bub Dew R408A Bub Dew R409A Bub Dew R407F GENETRON® PERFORMAX™ LT Bub Dew R417A

˚C

Pressure kPa (Gauge)

R12 R134a R406A

Bub Dew

R408A

Bub Dew

R409A

Bub Dew

R407FGENETRON®

PERFORMAX™ LTBub Dew

R417AISCEON 59Bub Dew

R404A

Bub Dew

R407C

Bub Dew

R410A

Bub Dew

R22 R507

Bub Dew

R744CO2

R717NH3

R600aISO

BUTANE

R290 PROPANE

HFO 1234yf

HFO 1234ze

-50 -62 -72 -75 -57 -25 -23 -72 -54 -43 -18 -57 -42 -20 -17 -51 -28 7 8 -37 -15 -15 581 -61 -92 -31 -64 -81-48 -58 -68 -72 -52 -17 -15 -68 -48 -36 -9 -52 -36 -12 -8 -45 -19 19 19 -30 -6 -6 638 -55 -90 -23 -60 -78-46 -53 -64 -68 -48 -9 -7 -64 -43 -28 0 -46 -29 -3 1 -39 -11 31 31 -22 3 3 699 -50 -90 -17 -55 -75-44 -48 -60 -65 -42 1 3 -60 -37 -20 10 -40 -21 8 11 -32 -2 44 45 -14 14 14 763 -43 -88 -8 -50 -72-42 -43 -55 -61 -36 10 13 -55 -30 -11 22 -33 -13 18 22 -24 8 58 59 -6 25 25 831 -37 -86 1 -45 -68-40 -37 -50 -56 -29 21 24 -50 -23 -1 34 -25 -4 30 34 -16 19 74 74 4 37 37 903 -30 -85 10 -39 -65-38 -31 -45 -51 -22 33 36 -45 -15 9 47 -18 5 42 47 -7 30 90 90 14 50 50 978 -21 -83 20 -32 -61-36 -24 -39 -45 -14 45 48 -39 -7 20 61 -9 15 55 60 3 43 107 108 25 64 64 1059 -13 -81 30 -26 -56-34 -17 -32 -40 -6 59 61 -32 2 32 75 1 26 70 74 14 56 126 127 37 79 79 1143 -3 -79 41 -19 -51-32 -10 -25 -34 2 72 76 -25 12 45 91 10 38 85 90 25 70 147 147 49 94 94 1232 7 -76 54 -11 -46-30 -1 -17 -27 12 88 91 -17 22 59 108 21 50 101 106 37 85 168 169 63 112 112 1326 18 -73 66 -2 -40-28 8 -9 -19 21 104 107 -9 32 74 126 33 63 118 124 50 102 191 192 76 130 130 1423 30 -70 80 7 -34-26 17 0 -12 32 121 125 0 44 90 145 45 78 136 143 65 119 215 216 92 148 149 1527 43 -67 94 17 -28-24 28 10 -3 43 139 143 9 56 107 165 59 93 156 163 80 138 241 243 108 169 169 1635 57 -63 110 27 -21-22 38 20 6 56 158 163 19 70 125 187 73 110 177 183 96 158 269 270 125 190 190 1749 72 -60 126 38 -12-20 50 32 16 69 179 183 30 84 145 211 88 127 198 205 113 178 298 299 144 213 213 1867 89 -56 143 50 -5-18 61 43 26 83 200 205 42 99 165 235 105 145 222 229 132 200 329 330 163 237 237 1991 106 -52 161 62 4-16 74 56 37 97 224 228 54 114 188 261 122 164 247 254 152 224 362 363 184 263 263 2121 125 -48 181 75 14-14 88 70 49 112 248 253 68 132 212 289 141 185 273 280 172 249 396 398 206 289 289 2256 145 -43 200 90 24-12 102 84 61 129 274 278 82 149 236 318 161 207 300 308 195 276 433 434 229 318 318 2398 166 -37 222 105 34-10 117 99 74 146 300 306 97 168 263 348 181 229 329 338 218 303 471 473 254 348 348 2546 189 -32 244 121 46-8 134 116 89 164 329 335 113 187 291 380 203 254 360 369 243 333 512 514 279 379 380 2700 214 -25 267 137 58-6 150 133 104 183 359 364 130 209 321 414 227 279 392 401 270 363 555 557 306 413 413 2860 240 -19 291 155 71-4 168 152 120 203 391 397 147 231 352 450 251 306 426 435 298 396 599 601 335 447 448 3027 267 -13 318 174 85-2 187 171 137 225 424 430 167 254 386 488 278 334 462 471 328 430 646 649 364 484 484 3200 297 -6 345 194 1000 207 192 155 247 459 465 187 278 420 527 305 364 499 508 359 466 697 699 396 522 523 3382 328 2 373 214 1152 227 213 174 271 495 502 208 304 457 569 334 395 538 548 392 504 748 751 429 562 563 3570 361 10 402 236 1324 249 236 194 296 533 540 230 331 497 613 365 429 579 589 427 544 803 806 464 605 605 3765 396 19 433 260 1496 272 260 215 321 574 581 254 359 537 658 398 463 622 633 464 586 860 863 501 649 650 3968 433 28 466 284 1678 296 286 237 349 616 623 279 389 581 706 431 499 667 678 502 629 920 923 539 695 696 4179 472 37 500 309 187

10 321 313 260 377 659 667 305 420 626 756 467 537 714 726 543 675 983 987 579 743 744 4398 513 47 535 336 20712 347 342 285 407 706 713 333 452 673 808 504 577 763 774 586 722 1049 1052 621 794 794 4625 557 58 572 364 22814 375 371 311 438 753 761 362 486 723 863 544 618 814 826 630 772 1117 1121 665 847 847 4861 603 69 610 393 25116 404 402 338 471 803 812 392 521 775 921 584 661 868 881 678 825 1189 1193 710 902 903 5106 651 81 650 424 27518 433 435 367 504 856 864 424 558 830 980 628 707 924 936 727 879 1263 1267 759 959 960 5360 702 93 692 456 30020 465 470 396 539 909 918 457 597 887 1042 672 754 983 995 779 936 1341 1346 808 1019 1020 5624 756 106 734 490 32622 497 506 427 577 967 975 492 637 947 1107 720 803 1043 1056 832 995 1422 1427 860 1081 1082 5898 812 120 779 525 35324 531 544 460 615 1025 1034 528 679 1009 1174 769 855 1107 1120 889 1056 1506 1512 914 1146 1147 6182 871 134 826 562 38226 567 584 495 655 1087 1096 567 722 1075 1244 821 909 1173 1186 948 1121 1594 1600 970 1213 1215 0 933 150 874 600 41228 604 625 531 697 1151 1160 607 768 1142 1317 874 965 1241 1255 1009 1187 1686 1691 1029 1284 1285 0 997 165 925 640 44430 642 668 568 740 1217 1226 649 815 1214 1393 930 1022 1312 1326 1074 1257 1781 1787 1090 1357 1358 0 1065 182 977 681 47732 681 714 606 785 1286 1295 692 864 1288 1472 989 1083 1386 1400 1141 1329 1880 1886 1153 1432 1434 0 1136 199 1031 725 51134 723 761 647 832 1357 1367 738 915 1365 1554 1049 1146 1463 1477 1211 1404 1983 1989 1219 1511 1512 0 1211 218 1087 770 54736 766 810 690 881 1431 1441 785 968 1446 1639 1113 1211 1543 1558 1284 1482 2090 2096 1287 1593 1594 0 1288 236 1145 817 58538 811 861 734 931 1508 1519 834 1023 1530 1727 1179 1279 1626 1641 1360 1563 2201 2208 1358 1678 1679 0 1368 256 1205 866 62440 857 914 780 983 1588 1598 886 1080 1617 1819 1247 1349 1712 1727 1439 1647 2316 2323 1431 1765 1767 0 1453 277 1267 916 66542 905 970 828 1038 1671 1682 940 1139 1707 1913 1319 1422 1802 1816 1521 1734 2436 2443 1508 1857 1858 0 1541 298 1331 969 70844 954 1028 878 1093 1756 1767 995 1200 1802 2012 1393 1498 1894 1909 1607 1824 2559 2567 1586 1951 1953 0 1633 321 1398 1024 75246 1006 1088 929 1151 1845 1857 1053 1263 1900 2114 1470 1576 1990 2005 1696 1917 2688 2695 1668 2050 2051 0 1729 345 1467 1080 79848 1060 1151 983 1211 1937 1948 1113 1328 2002 2219 1550 1657 2090 2105 1789 2013 2821 2829 1753 2151 2153 0 1828 369 1538 1139 84550 1115 1216 1040 1274 2033 2044 1175 1397 2108 2328 1633 1742 2193 2208 1885 2113 2959 2968 1840 2256 2259 0 1931 394 1611 1200 89652 1171 1283 1098 1338 2131 2143 1240 1466 2219 2441 1719 1829 2300 2314 1985 2217 3103 3111 1931 2365 2367 0 2039 420 1687 1264 94754 1231 1353 1158 1404 2233 2245 1308 1539 2333 2558 1809 1919 2411 2425 2089 2323 3251 3259 2024 2479 2480 0 2151 448 1765 1329 100156 1292 1426 1220 1472 2338 2350 1377 1614 2452 2678 1902 2013 2525 2540 2197 2434 3405 3413 2121 2596 2598 0 2267 476 1845 1397 105758 1355 1501 1285 1543 2447 2459 1450 1691 2575 2803 1997 2109 2644 2659 2310 2548 3565 3572 2221 2717 2719 0 2387 506 1929 1467 111560 1419 1579 1353 1616 2560 2572 1525 1771 2704 2931 2097 2209 2768 2781 2426 2666 3730 3738 2325 2844 2846 0 2513 537 2014 1539 1175

Pressure Temperature ChartLiq

uid

Tem

pera

ture

Volume Flowcfm x 0.472 = l/sfpm x 0.00508 = m/simp. gal/min x 0.0758 = l/sU.S. gal/min x 0.0631 = l/s

Volumeft3 x 0.02832 = m3Please note: This chart is intended as a guide only.Co

nver

sion

Fa

ctor

s Velocityfps x 0.3048 = m/sfpm x 0.00508 = m/s

Temperature˚C = (˚F - 32) ÷ 1.8˚F = (˚C x 1.8) + 32

Heat FlowBtu/hr x 0.252 – kcal/hrBtu/hr x 0.293 = wattswatts x 0.86 = kcal/hrwatts x 3.4129 = Btu/hrwatts x 0.000284 = ton (refr)

PressurekPa ÷ 6.89 = psiinch Hg x 3.39 = kPainch H2O x 0.249 = kPamm Hg (1 torr) x 0.133 = kPa

Heat Flow (cont.)watts x 0.00133 = HPkcal/hr x 1.163 = wattskcal/hr x 3.97 = Bru/hrHP x 746 = wattston (refr) x 3517 = watts

Follow us on

SA E

DITI

ON

01/

09/2

014

CAPE TOWNT 021 551 8790 F 021 551 8758

[email protected]

GAUTENGT 011 392 4791 F 011 392 2296www.agas.com

GUIDE TO REFRIGERANT REPLACEMENTSREFRIGERANT REPLACEMENT (ZERO ODP)

There is no single product that can replace R22 in all applications.

If you need help on any particular application, please contact us.

* Not suitable for systems with capillary tube, expansion valve only.

** 50/50 mix of Mineral/Alkylbenzene preferred.

LONG-TERM REPLACEMENTPREVIOUS / PHASING OUT (ODP)

GWP 1480

HFO 1234ze

HFO

OILPolyol Ester

APPLICATIONMed Temp RefrigWater Chillers

GWP 6

R11

CFC

APPLICATIONCentrifugal Chillers

GWP 4750

CFC BANNED

R437AISCEON®

M049Plus™

HFC

OILMineral**AlkylbenzenePolyol EsterAPPLICATIONAuto Air CondMed Temp Refrig

GWP 1805

R134a

HFC

OILPolyol EsterPolyalkylene- GlycolAPPLICATIONMed Temp RefrigAir ConditioningAuto Air Cond

GWP 1430

R600aISO Butane

HC

OILMineralAlkylbenzene

APPLICATIONDomestic Refrig

HFO 1234yf

HFO

OILPolyol EsterPolyalkylene-GlycolAPPLICATIONAuto Air Cond

GWP 4 GWP 3

HFO 1234ze

HFO

OILPolyol Ester

APPLICATIONMed Temp RefrigWater Chillers

GWP 6

R12

CFC

APPLICATIONAuto Air CondMed Temp RefrigHigh Temp Refrig

GWP 10900

CFC BANNED

R290Refrigerant

Grade Propane

OILMineral

APPLICATIONLow Temp RefrigMed Temp Refrig

HCGWP 3

HFC

OILPolyol Ester

APPLICATIONLow Temp RefrigMed Temp Refrig

GENETRON® PERFORMAX™ LT

R407F

GWP 1824

R422AISCEON® M079

OILMineral**AlkylbenzenePolyol EsterAPPLICATIONLow Temp RefrigMed Temp Refrig

HFCGWP 3143

R404A

HFC

OILPolyol Ester

APPLICATIONLow Temp RefrigMed Temp Refrig

(FX70/HP62)R125/143a/134a

(44/52/4%)

R507

HFC

OILPolyol Ester

APPLICATIONLow Temp RefrigMed Temp Refrig

(AZ50)R125/143a(50/50%)

GWP 3922 GWP 3985

R1270Propylene

OILMineral

APPLICATIONLow Temp RefrigMed Temp Refrig

HCGWP 2

R407A

HFC

OILPolyol Ester

APPLICATIONMed Temp Refrig

Klea60

GWP 2107

R502

CFC

APPLICATIONLow Temp RefrigMed Temp Refrig

R22/115(50/50%)

GWP 4657

CFC BANNED

R417AISCEON® M059

HFC

OILMineral**AlkylbenzenePolyol EsterAPPLICATIONMed Temp RefrigAir Conditioning

R422DISCEON® M029

HFC

OILMineralAlkylbenzenePolyol EsterAPPLICATIONMed Temp RefrigAir ConditioningWater Chillers

R424ARS44

HFC

OILMineralAlkylbenzenePolyol EsterAPPLICATIONMed Temp RefrigAir Conditioning

R434A*RS45

HFC

OILMineralAlkylbenzenePolyol EsterAPPLICATIONLow Temp RefrigMed Temp RefrigWater Chillers

GWP 2346 GWP 2729 GWP 2440 GWP 3245

R407C

HFC

OILPolyol Ester

APPLICATIONAir Conditioning

(Klea 66/ Suva 9000)

R32/125/134a(23/25/52%)

R410A

OILPolyol Ester

APPLICATIONAir Conditioning

(AZ20)R32/125(50/50%)

HFC

R744

CO2

OILMineral

APPLICATIONVarious

Carbon Dioxide

HFC

OILPolyol Ester

APPLICATIONLow Temp RefrigMed Temp Refrig

GENETRON® PERFORMAX™ LT

R407F

GWP 1824 GWP 1 GWP 1774 GWP 2088

ISCEON® M089

HFC

OILMineralAlkylbenzenePolyol EsterAPPLICATIONUltra Low Temp Refrigeration

GWP 3698

R23

HFC

OILPolyol Ester

APPLICATIONUltra Low Temp Refrigeration

GWP 14800

R508A

HFC

OILPolyol Ester

APPLICATIONUltra Low Temp Refrigeration

R23/116(39/61%)

GWP 13214

R508B

HFC

OILPolyol Ester

APPLICATIONUltra Low Temp Refrigeration

Sulva 95

GWP 13396

R13

CFC

APPLICATIONUltra Low TempRefrigeration

ORR503R23/13

CFC BANNED

R123

HCFC

APPLICATIONCentrifugal Chillers

GWP 120

APPLICATIONLow Temp RefrigMed Temp Refrig

HCFC

R409AOR

R406A

GWP 1943

GWP 1585

APPLICATIONLow Temp RefrigMed Temp Refrig

HCFC

OR

R408A

R22

HCFC

APPLICATIONLow Temp RefrigMed Temp RefrigAir Conditioning

GWP 1810

GWP 3152

R402AGWP 2788R402BGWP 2416R403BGWP 4457

OILMineralAlkylbenzenePolyol Ester

OILMineralAlkylbenzene

Follow us on

‘Drop in’ is a generic term; refrigerants should never be mixed or dropped in on top of an existing refrigerant.

HFC Drop in replacements in most cases do not require a change of lubricant type, however manufacturers’ guidance as well as good engineering practice should be followed.

All information supplied is for guide purposes only.

Please note: Not all products are available in all outlets.

YOUR SOLUTIONS PROVIDER

Page 2: Pressure Temperature Chart GUIDE TO REFRIGERANT ... · ˚C Pressure kPa (Gauge) R12 R134a R406A Bub Dew R408A Bub Dew R409A Bub Dew R407F GENETRON® PERFORMAX™ LT Bub Dew R417A

PaperworkMETRACLARK will provide their customers with an Environmental Services Request Form which is to be completed by the customer.

One copy is kept by the customer and another copy is returned to METRACLARK with the pump down or recovery cylinder.

CustomersCustomers must ensure that the cylinder number is clearly stated on their ES Request Form. This is in order to ensure full traceability of the cylinder.

The form and the cylinder must be returned to METRACLARK at the same time.

PackagingA-GAS provides a fleet of dedicated recovery and pump down cylinders with specialised valve technology.

This allows engineers to retrieve waste refrigerant in a safe and environmentally responsible manner.

We have 8kg and 45kg cylinders as well as 850kg drums. The cylinders are available on a rental basis.

METRACLARK provides dedicated recovery and pump down cylinders to customers as requested.

LaboratoryReturned cylinders are sent to the laboratory at A-GAS.

The A-GAS laboratory is fully equipped to check refrigerants for moisture, residues, non-condensables and acidity to ensure refrigerant, after cleaning, complies with AHRI 700 standards and therefore can be classified under SANS 10147:2009 as ‘reclaimed’.

Refrigerant Buyback Program

Contact A-GAS for further details. Terms and conditions apply.

CertificationA-GAS will issue a certificate to the customer which ensures traceability of the returned refrigerant.

A-GAS provides customers with the necessary means to be able to meet the requirements of SANS 10147:2009 standards pertaining to refrigerant reclamation and recycling. As stated in the National Environmental Management: Air Quality Act (39/2004): Regulations regarding the phasing-out and management of ozone-depleting substances 37621, it is ILLEGAL to release refrigerant into the atmosphere. Our services include the supply of recovery and pump down cylinders/drums, purity testing of refrigerant as well as a waste management program.

Environmental Services:Complete Refrigerant Lifecycle Stewardship

offerand

ReturnsMETRACLARK returns customer recovery and pump down cylinders to A-GAS together with the relevant completed ES Request Forms:

Pump down cylinder

Recovery cylinder

IT IS ILLEGAL TO RELEASE REFRIGERANT INTO THE ATMOSPHERE

 *

GENETRON® PERFORMAX™ LT IS THE REPLACEMENT FOR R22Features and Benefits• HFC refrigerant is a zero Ozone

Depletion Potential refrigerant• Lower Global Warming

Potential (GWP) (1824) of all commonly used blends (R404A, R407A, R507, R427A and R422D

• Best capacity match to R22 in low and medium temperature applications

• Suitable for both retrofits and new equipment

• Most efficient R22 retrofit option in the marketplace

• No thermal expansion valve change or adjustment, eliminating retrofit costs

• Requires polyolester• Minimises KWH cost of system

operation• A1 safety classification – non-

toxic and non-flammable• Lower discharge temperature

than R22• Approval from all well-known

compressor manufacturers• Best combination of capacity,

efficiency, GWP and mass flow• Low investment, maximum

performance, lower carbon footprint

IntroductionHoneywell Genetron® Performax™ LT (R407F), a ternary blend of HFC refrigerants R32/R125/R134a serves as a zero Ozone Depleting Potential (ODP) replacement for HCFC refrigerant R22, in various commercial refrigeration applications, particularly in low temperature applications.

Since Genetron® Performax™ LT is a close match to R22, it also serves as a retrofit fluid in applications where R22 is used. Genetron® Performax™ LT is the best performing lower global-warming-potential refrigerant for new supermarket installations with improved energy efficiency compared to other HFCs. It is a better alternative to R404A in both low- and medum-temperature supermarket applications since it has a higher capacity and efficiency than R404A.

Genetron® Performax™ LT is not a “drop-in” replacement and lubricants such as mineral oil and alkylbenzene that have traditionally been used with R22 are immiscible with Genetron® Performax™ LT. Miscible synthetic lubricants such as polyolester should be used to ensure adequate oil return.

TIMELINE AND ACTION PLAN FOR THE PHASE-OUT OF HCFCs

* evaporating -32˚C; condensing 35˚C

Refrigerant Capacity* kJ/m3

Mass Flow Rate* kg/s ODP GWP

R22 1052 6,64 0.05 1810

R407A 1012 7,02 0 2107

R404A 1044 9,58 0 3922

R422D 858 8,20 0 2729

R427A 915 6,26 0 2138

Genetron® Performax™ LT 1093 6,76 0 1825

Action DateQuota system for the assignment of import licences for all HCFCs 1/01/2013

Ban on import of any new or used air conditioning systems or equipment fitted with a compressor and pre-charged or partially charged with HCFC-22 or any refrigerant or refrigerant blend containing any HCFC

1/07/2014

Mandatory recovery and recycling of HCFCs and other ODS refrigerant 1/09/2014

Action DateBan on the use of HCFC-22 (or any other refrigerant containing HCFCs) either in pure form or as a component of blended refrigerants; in the construction, assembly or installation of any new refrigeration or air conditioning system or equipment which requires a compressor to be fitted in South Africa

1/01/2015

Licence/certification required for anyone purchasing refrigerant 1/01/2015Ban on import of HCFC-141b either in pure form or as a component of blended chemicals; for the purpose of placing on the market or use in the production of polyurethane foams or as solvents or any other application

1/01/2016

201420152016201720182019202020212022202320242025

2026 - 20302031 - 2040

2041

Perio

d

0% 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100%Reduction

* 2.5% annual consumption allowed for servicing

BAN / COMPLETE PHASE-OUT

We are pleased to introduce NEW packaging into the A-Gas South Africa offering. The market has been calling for smaller charges than our usual packaging which would assist clients in the DIY and Domestic industries.

The Rapid-Charge Packs allow for a simple, quick and easy way to charge equipment in an efficient manner.

Benefits:• These packs are commonly used as a refrigerant in the Air Conditioning,

Domestic and Commercial sectors.

• A-Flush+ and R134a can also be used in the Automotive sector.

• Valves are supplied separately and can be used on all other Rapid-Charge products.

• Special technology allows the valve to be removed safely without product loss.

• Rapid-Charge packaging and labelling complies with local legislation.

Rapid-Charge Packs are now available in the following sizes as shown here alongside:

• A-Flush+ Cleaning Solution – 640g can

• R134a Refrigerant – 675g can

• R290 Propane – 430g can

• R600a Isobutane – 420g can

REFRIGERANT GRADE CO2 (R744)

• Used for: – pressure testing – leak testing – purging

• 2.2kg cylinder

OXYGEN FREE NITROGEN (OFN)

MUST-HAVES FOR ANY TECHNICIAN!Ideal product for system flushing:

• when carrying out a full retrofit

• when changing oil

• when replacing a refrigerant

• after a compressor burn-out

A-FLUSH

• CO2 can be used as a refrigerant and is becoming increasingly popular due to its excellent properties and low Global Warming Potential (GWP).

• 13.3kg cylinder

Safety Data Sheets are available upon request

ZERO EMISSIONS

Small returnable cylinders

offer an alternative to disposable cylinders.

Having more environmentally

friendly sustainable packaging, they are a safer and

cheaper option than environmentally

unfriendly disposable cylinders.

Small Easy to Use

Compact

Small Easy to Use

Compact

Small Easy to Use

Compact

RECOVERY AND PUMP DOWN CYLINDERS

Rapid-Charge Packs – an A-Gas Initiative

Small Easy to Use

Compact


Recommended