PR electronics A/S Lerbakken 10 . DK-8410 Rønde Tlf. 8637 2677 . Fax. 8637 3085 www.prelectronics.dk . [email protected] PRetop 5350B PROFIBUS ® PA/FOUNDATION™ FIELDBUS TRANSMITTER + - + - + - 1 + 2 + - + - 2 1 2 1 - RTD to bus communication Resistance to bus communication mV to bus communication TC to bus communication Difference, redundancy or average; RTD, TC or mV or Application: • Linearised temperature measurement with RTD or TC sensor. • Difference, average or redundancy temperature measurement with RTD or TC sensor. • Linear resistance, potentiometer and bipolar mV measurement. Technical characteristics: • Bus transmitter with both PRofiBus ® PA and FounDaTion™ fieldbus communication. a unique switch function ensures automatic shift between the two protocols. • set-up for PRofiBus ® Pa can be done via siemens simatic ® PDM ® , aBB Melody / Harmony and Metso Dna software and for FounDaTionfieldbus via Emerson DeltaV, Yokogawa Cs 1000 / Cs 3000, aBB Melody / Harmony and Honeywell Experion software. • The simulation mode function can be activated by way of a magnet. • Polarity-independent bus connection. • 24 bit a/D converter ensures high resolution. • PRofiBus ® Pa function blocks: 2 analogue. FounDaTion™ fieldbus function blocks: 2 analogue and 1 PiD. FounDaTion™ fieldbus capability: Basic or Las. Mounting / installation: • for Din form B sensor head mounting. PROFIBUS ® PA ver. 3.0 FISCO-certified Basic or LAS capability with F.F. FOUNDATION™ Fieldbus ver. ITK 4.6 Automatic switch between protocols
Transcript
Page 1: PRetop5350B - OneTemp

PR electronics A/S Lerbakken 10 . DK-8410 Rønde

Tl f . 8637 2677 . Fax. 8637 3085www.prelectronics.dk . [email protected]

PRetop 5350B

PROFIBUS® PA/FOUNDATION™ FIELDBUS TRANSMITTER

+

-

+

-

+- 1

+2

+-

+-

2

12

1

-

RTD tobus communication

Resistance tobus communication

mV tobus communication

TC tobus communication

Difference, redundancy oraverage; RTD, TC or mV

or

Application:•Linearisedtemperaturemeasurementwith

RTD or TC sensor.

•Difference,averageorredundancytemperaturemeasurementwithRTDorTCsensor.

•Linearresistance,potentiometerandbipolarmVmeasurement.

Technical characteristics:

•BustransmitterwithbothPRofiBus® PA and FounDaTion™fieldbuscommunication.auniqueswitchfunctionensuresautomaticshiftbetweenthetwoprotocols.

•set-upforPRofiBus® Pacanbedoneviasiemenssimatic® PDM®,aBBMelody/HarmonyandMetsoDnasoftwareandforFounDaTion™fieldbusviaEmersonDeltaV,YokogawaCs1000/Cs3000,aBBMelody/HarmonyandHoneywellExperionsoftware.

•Thesimulationmodefunctioncanbeactivatedbywayofamagnet.

•Polarity-independentbusconnection.

•24bita/Dconverterensureshighresolution.

•PRofiBus®Pafunctionblocks: 2analogue.

•FounDaTion™fieldbusfunctionblocks: 2analogueand1PiD.

•FounDaTion™fieldbuscapability: BasicorLas.

Mounting / installation:

•forDinformBsensorheadmounting.

PROFIBUS® PA ver. 3.0

FISCO-certified

Basic or LAS capability with F.F.

FOUNDATION™ Fieldbus ver. ITK 4.6

Automatic switch between protocols

Page 2: PRetop5350B - OneTemp

Electrical specifications:Specifications range:-40°C to +85°CCommon specifications:supplyvoltage ................................... 9...30VDC In FISCO installations .................. 9...17.5VDC Consumption ..................................... <11ma Max.currentincreasein theeventofanerror .................... <7ma isolationvoltage,test ........................ 1.5kVaCfor60s isolationvoltage,operation ............... 50VRMs/75VDC Warm-uptime .................................... 30 s signal/noiseratio ............................. Min.60dB Responsetime(programmable) ........ 1...60 s updatingtime .................................... <400ms Executiontime,analogueinput ......... <50ms signaldynamics,input ...................... 24 bit Calibrationtemperature ..................... 20...28°C accuracy,thegreaterofgeneralandbasicvalues:

Vibration(DinclassB) ....................... iEC60068-2-6and iEC60068-2-64 4g/2...100HzHumidity ............................................ <95%RH(non-cond.) Dimensions ........................................ Ø44x20.2mm Protectiondegree(encl./terminal) ... IP68 / IP00Electrical specifications, input:RTD and linear resistance input:

Cable resistance per wire. ................. 50 Ω sensorcurrent ................................... nom.0.2ma

Effectofsensorcableresistance (3-/4-wire) .................................... < 0.002 Ω/Ω Sensor error detection ....................... Yesshortcircuitdetection ....................... < 15 ΩTC input:

Coldjunctioncompensation(CJC) ... <±0,5°CSensor error detection ....................... Yessensorerrorcurrent: whendetecting .............................. nom.4µa else ................................................ 0µashortcircuitdetection ....................... <3mVVoltage input:Measurementrange .......................... -800...+800mVinputresistance ................................. 10 MΩOutput:PROFIBUS® PA connection:PRofiBus® PA protocol ................... Profilea&B,ver.3.0 PRofiBus® PA protocol standard .... En50170vol.2 PRofiBus® PA address (atdelivery) .................................... 126 PRofiBus®Pafunctionblocks ....... 2analogueFOUNDATION™ Fieldbus connection:founDaTion™fieldbusprotocol ... FF protocol founDaTion™fieldbus protocol standard .......................... ffdesignspecifications founDaTion™fieldbuscapability . BasicorLas founDaTion™fieldbusversion ..... ITK 4.6 founDaTion™fieldbus functionblocks .............................. 2analogueand1PiDApprovals:EMC2004/108/EC ............................ En61326-1GOST RI.S. / Ex:aTEX94/9/EC .................................... KEMa02aTEX1318iECEx ................................................. iECExBVs12.0035XFM ..................................................... FM-3015609cCsaus ............................................ CSA-1418937inMETRo .......................................... 08/uL-BRCo-0019nEPsi ................................................ GYJ091290XGosTEx

5350BY112-uK(1232)

Generalvalues

inputtype

absolute accuracy

Temperature coefficient

All ≤±0.05%ofreading ≤±0.002%ofreading/°C

Basicvalues

inputtype

Basic accuracy

Temperature coefficient

Pt100 and Pt1000 ≤ ±0.1°C ≤ ±0.002°C / °C

ni100 ≤ ±0.15°C ≤ ±0.002°C / °C

Cu10 ≤ ±1.3°C ≤ ±0.02°C / °C

Lin. R ≤ ±0.05 Ω ≤ ±0.002 Ω / °C

Volt ≤±10µV ≤±0.2µV/°C

TCtype: E,J,K,L,n,T,u

≤ ±0.5°C

≤ ±0.010°C / °C

TCtype: B,R,s,W3,W5

≤ ±1°C

≤ ±0.025°C / °C

EMCimmunityinfluence ................................< ±0.1% of readingExtendedEMCimmunity: naMuRnE21,acriterion,burst ...................< ±1% of reading

RTD type

Min. value

Max. value

Standard

Pt25...Pt1000 ni25...ni1000 Cu10...Cu1000 Lin. resistance Potentiometer

-200°C -60°C -50°C 0 Ω 0 Ω

+850°C +250°C +200°C 10 kΩ

100 kΩ

iEC60751/JisC1604 Din43760 α = 0.00427

- -

3 54 6 3 54 6 1 23 4 5 6 54 63

+-

54 63

+-+-

54 63 54 633 4 65 54 63

54 63

1

2

54 63

+-+-

12

3 4 65

Output:

Connections:

Input:

Bus installation2 x RTD,2-wireRTD, 2-wire RTD, 3-wire RTD, 4-wire

mV

2 xTC,2-wire, CJCTC, internal CJC

TC, external CJC Potmeter, 3-wireResistance, 2-wire Resistance, 3-wire Resistance, 4-wire

All connection optionsare shown in the user manual.

Connections with two sensorscan be configured for 2 measurements,difference, average or redundancy.

5350B

Type

Order: 5350B

*NB!PleaseremembertoorderPRsimpintype8422ifthesimulationmodefunctionistobeused.

Type

Min. value

Max. value

Standard

B E J K L n R S T u

W3 W5

Ext.CJC

+400°C -100°C -100°C -180°C -200°C -180°C

-50°C -50°C

-200°C -200°C

0°C 0°C

-40°C

+1820°C +1000°C +1200°C +1372°C

+900°C +1300°C +1760°C +1760°C

+400°C +600°C

+2300°C +2300°C

+135°C

iEC60584-1 iEC60584-1 iEC60584-1 iEC60584-1 Din43710 iEC60584-1 iEC60584-1 iEC60584-1 iEC60584-1 Din43710

asTME988-90 asTME988-90

iEC60751