PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE Edition June 2009
Transcript
Page 1: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

Edition June 2009

Page 2: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

Comments… Suggestions… Corrections…The User Documentation Department would like toknow your opinion of this manual. Your feedback helpsus optimize our documentation to suit your individual needs.

Feel free to send us your comments by e-mail to [email protected].

Certified documentation according to DIN EN ISO 9001:2000To ensure a consistently high quality standard anduser-friendliness, this documentation was created tomeet the regulations of a quality management system which complies with the requirements of the standardDIN EN ISO 9001:2000.

cognitas. Gesellschaft für Technik-Dokumentation mbHwww.cognitas.de

Copyright and TrademarksCopyright © 2009 Fujitsu Technology Solutions GmbH.

All rights reserved.Delivery subject to availability; right of technical modifications reserved.

All hardware and software names used are trademarks of their respective manufacturers.

Page 3: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A

Contents

1 Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

1.1 The PRIMECENTER Rack . . . . . . . . . . . . . . . . . . . . 7

1.2 Target Group . . . . . . . . . . . . . . . . . . . . . . . . . . 12

1.3 Summary of Contents . . . . . . . . . . . . . . . . . . . . . 13

1.4 Notational Conventions . . . . . . . . . . . . . . . . . . . . 13

1.5 Technical Data (excerpt) . . . . . . . . . . . . . . . . . . . . 14

2 Important Notes . . . . . . . . . . . . . . . . . . . . . . . . 17

2.1 Rack Philosophy . . . . . . . . . . . . . . . . . . . . . . . . 17

2.2 Notes on Safety . . . . . . . . . . . . . . . . . . . . . . . . . 19

2.3 Notes on Mounting the Rack Components . . . . . . . . . . 21

2.4 Environmental Protection . . . . . . . . . . . . . . . . . . . 22

3 Preparations . . . . . . . . . . . . . . . . . . . . . . . . . . 25

3.1 Unpacking and Checking the Delivery Unit . . . . . . . . . . 25

3.2 Installation Procedure . . . . . . . . . . . . . . . . . . . . . 26

3.3 Opening the PRIMECENTER Rack . . . . . . . . . . . . . . 273.3.1 Opening the door with the door knob . . . . . . . . . . . . . . 28

3.4 Rolling off the PRIMECENTER Rack from the Transport Palette . . . . . . . . . . . . . . . . . . . 29

3.4.1 Handling and Transportation Instructions until 12/2007 . . . . . 293.4.2 Handling and Transportation Instructions from 01/2008 . . . . . 34

3.5 Setting up the PRIMECENTER Rack . . . . . . . . . . . . . 35

3.6 Mounting the Anti-Tilt Plate until end of 2007 . . . . . . . . 39

3.7 Mounting the Anti-Tilt Plate from 01/2008 . . . . . . . . . . 43

Page 4: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A

Contents

4 Mounting Rack Components . . . . . . . . . . . . . . . . . . 51

4.1 The System Architect . . . . . . . . . . . . . . . . . . . . . . 52

4.2 The Height Unit (HU) . . . . . . . . . . . . . . . . . . . . . . 53

4.3 Inserting Cage and Spring Nuts and Mounting Elements . . 544.3.1 Inserting Cage Nuts . . . . . . . . . . . . . . . . . . . . . . . . 544.3.2 Inserting Spring Nuts . . . . . . . . . . . . . . . . . . . . . . . 554.3.3 Inserting Plugwashers . . . . . . . . . . . . . . . . . . . . . . 56

4.4 Support Systems . . . . . . . . . . . . . . . . . . . . . . . . 574.4.1 Sliding Rails with Linear Alignment . . . . . . . . . . . . . . . . 574.4.2 Telescopic Rails with System Mounts . . . . . . . . . . . . . . . 594.4.3 Telescopic Rails for Standard Direct Mounting . . . . . . . . . . 604.4.4 Direct Mounting via the Front Panel . . . . . . . . . . . . . . . 614.4.5 Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

4.5 Mounting in the Front 19-inch Area . . . . . . . . . . . . . . 63

4.6 Mounting in the Expansion Area . . . . . . . . . . . . . . . . 664.6.1 Mounting Rack Components . . . . . . . . . . . . . . . . . . . 66

4.7 Mounting in the Rear 19-inch Area . . . . . . . . . . . . . . . 67

4.8 Converting the Rack from a Depth of 940 mm to 1000 mm . 68

4.9 Rack Surround Cable Inlets and Outlets with External Cabling . . . . . . . . . . . . . . . . . . . . . . . . . 72

5 Cable Management . . . . . . . . . . . . . . . . . . . . . . . 75

5.1 Mounting Components of the Cable Management . . . . . . 755.1.1 Articulated Cable Guides . . . . . . . . . . . . . . . . . . . . . 765.1.2 Cable Guide with Cable Clips . . . . . . . . . . . . . . . . . . . 77

5.2 Connecting and Disconnecting Cables . . . . . . . . . . . . 785.2.1 Connecting Cables . . . . . . . . . . . . . . . . . . . . . . . . 785.2.2 Disconnecting Cables . . . . . . . . . . . . . . . . . . . . . . . 79

5.3 Routing Cables . . . . . . . . . . . . . . . . . . . . . . . . . 795.3.1 Articulated cable guide . . . . . . . . . . . . . . . . . . . . . . 805.3.2 Cable Routing and Strain Relief for the Built-in Rack Component 815.3.3 Cable Guide with Cable Clips . . . . . . . . . . . . . . . . . . . 845.3.4 Direct Connection . . . . . . . . . . . . . . . . . . . . . . . . . 85

Page 5: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A

Contents

6 Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . 87

6.1 Connecting to the Mains Using a 1-phase Socket Strip . . . 88

6.2 Connecting to the Mains Using a 3-phase Socket Strip . . . 906.2.1 Connection Cable . . . . . . . . . . . . . . . . . . . . . . . . 916.2.2 3-phase Power Distribution . . . . . . . . . . . . . . . . . . . 92

6.3 Power Supply via UPS . . . . . . . . . . . . . . . . . . . . . 93

6.4 Connecting to the Potential Compensating System . . . . . 94

7 Appendix A: Stackability . . . . . . . . . . . . . . . . . . . . 95

8 Appendix B: Accessories . . . . . . . . . . . . . . . . . . . 99

8.1 Mounting the Optional Door Knob . . . . . . . . . . . . . . 99

8.2 Mounting the Grounding Kit . . . . . . . . . . . . . . . . . . 101

Related Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . 105

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107

Page 6: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE
Page 7: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 7

1 Preface

1.1 The PRIMECENTER Rack

Fujitsu Technology Solutions has developed a new PRIMECENTER Rack system to consolidate and extend its existing racks. This new system includes the features and advantages of the previous rack series and offers new, forwarding-looking features and performance characteristics. The extensive experience gained in the installation of 19-inch rack systems from Fujitsu Technology Solutions in office environments and data centers has influenced and been taken into account in the new rack system. The main features include:

● Improved ventilation concept for even higher packing densities,

● Additional vertical slots,

● Further enhanced cabling concept,

● Consistent integration and implementation of new requirements for service friendliness and ease of maintenance.

The proven and well thought-out concept of the previous racks is being continued and enhanced in the new PRIMECENTER Rack system.

Figure 1: Different Variants of the PRIMECENTER Rack

Page 8: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

8 A3C40110888A

The PRIMECENTER Rack Preface

The existing performance characteristics offered include:

● Standard 19-inch technology for Fujitsu Technology Solutions and third-party products

● High standard of security with lockable doors and optional access control

● Forward-looking, reliable cable management

● Extensive rack options such as rack surround cable inlets

● Simple horizontal extensibility

● Additional rack components (console, switch, UPS, ...)

● Ready-to-run or preinstalled delivery

New performance characteristics of the PRIMECENTER Rack system include:

Stack Concept

The PRIMECENTER Rack is available with 12, 24, 38 and 46 height units (HU). The 12, 24 and 38 HU versions are stackable. This means that rack cabinets with up to 50 height units can be created, from the small rack for office environ-ments through to large full size racks for data centers.

This broad configuration offering not only allows users to choose the best rack system to suit their needs, they also have the option of adapting their rack system to match later growth requirements, without needing to invest in unnec-essary rack space from the outset.

In addition, PRIMECENTER Racks can be added on consecutively, even if they are fully assembled. The side panels are retained to ensure uniform ventilation of the rack with internal cabling between the cabinets. Users can themselves decide whether to opt for horizontal or vertical growth in height units as best suits their needs.

High Capacity

The capacity of the height units that can be constructed can be adjusted by stacking and can be extended at any time. In addition, up to 3x 2 HU, mounted vertically, are available for installations of up to 290 mm in depth (240 mm + 50 mm cabling). This means, for example, that horizontal height units do not have to be occupied for hubs, modems or switches.

Page 9: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 9

Preface The PRIMECENTER Rack

Universality

The PRIMECENTER Rack can be configured quickly and consistently using a single software tool with all products from Fujitsu Technology Solutions (PRIMERGY, PRIMEPOWER, BS2000 and all associated peripherals, FibreCAT and storage subsystems). This guarantees that the needs and requirements of users can be implemented as required. Even third-party products can be installed in the PRIMECENTER Rack with their original assembly kits plus adapters from Fujitsu Technology Solutions.

Variable Rack Depth

There are two depth variants of the PRIMECENTER Rack, 940 mm and 1100 mm. It is possible to convert from one to the other depth variant at any time.

Optimized Cabling

As with the previous rack series, the new PRIMECENTER Rack system has integrated a cabling area as well as articulated cable guides, which are not only service friendly but also decisively improve operational reliability and service-ability. Cables are not forced below their minimum bending radius and are laid neatly to avoid confusion. Even in the event of maintenance, faster re-avail-ability of the affected systems is guaranteed because no cables in the cabinet can fall or become twisted.

Ventilation

The air duct runs from front to rear. Because of the high extraction rate and the low air resistance, optimum ventilation is achieved for each height unit. A specially designed front door with a perforation rate of more than 60 percent ensures constant ventilation. The PRIMECENTER Rack is therefore also suitable to meet the future installation needs of servers and storage systems that have a high heat dissipation.

Service-friendliness

The 19-inch devices are mounted on sliding and telescopic rails. The doors can be hinged and unhinged easily by one person. The marking and numbering of the height units simplifies the assembly when installing and adding on compo-nents. Together with the cabling, the anti-tilt plate as well as the stable construction, not only is the availability increased, but maintenance and downtimes are also shorter for conversions and upgrades.

Page 10: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

10 A3C40110888A

The PRIMECENTER Rack Preface

Standards

Equipped with an earthquake kit, the 38 height unit PRIMECENTER Rack achieved NEBS Level 3 Bellcore GR63 Core, Earthquake Zone 4 and therefore passed the relevant earthquake test.

Each rack can be equipped with an AC main power connection that complies with European and American standards. At least two socket strips and two AC main power connections can be configured for phase redundancy. Because of the high leakage current of a fully configured rack, CEE-compliant plug connectors are used. Connection sets are available for 1-phase and 3-phase power supply as well as a 3-phase rigid connection.

IEC309 plug connectors ensure reliable grounding in the rack. The power supply components are optimized for these applications and the dimensioning ensures reliable and permanent grounding. IEC320 connectors are used within the rack.

Infrastructure

Compliance with standards means that third-party products or products from third-party suppliers, such as electric door locks, smoke and water level sensors as well as power supply components, can likewise be integrated.

Page 11: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 11

Preface The PRIMECENTER Rack

Patented Device Cabinet

This PRIMECENTER Rack is a patented device cabinet (patent specification: DE 199 62 659 C 2).

The invention deals primarily with a server cabinet. Because the mounting area with the devices and servers contained within is arranged asymmetrically, space is available left at the side for cable routing and for horizontal cable supports. Additional devices, particularly vertically aligned 19-inch modules can be arranged toward the front of this free side space.

Figure 2: Certificate showing granting of the patent

Page 12: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

12 A3C40110888A

Target Group Preface

Additional patents have also been granted or applied for:

● Depth adjustment: Patent No. E2001, 0486

● Rack surround cabling: Patent No. P2001, 0749

● Stack and expansion concept: Patent No. P2001, 0084

● Support systems: Applied for under 10164173.7

1.2 Target Group

This manual is intended for those responsible for installing the hardware and ensuring that the system runs smoothly (service personnel, technicians and technical specialists).

The manual is designed so that you can commission the PRIMECENTER Rack without prior special knowledge. Knowledge of the hardware to be integrated is helpful for understanding the various connection options. The 3-phase power connection is an exception and must only be installed by an authorized electrician approved by the local utility company.

The manual does not include technical descriptions of services that only the service department of Fujitsu Technology Solutions GmbH or appropriately trained specialist staff are allowed to carry out.

Page 13: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 13

Preface Summary of Contents

1.3 Summary of Contents

This manual describes how to set up the PRIMECENTER Rack and how to connect and route the cables. It also provides an introduction to the philosophy behind the PRIMECENTER Rack.

The installation of the actual components, such as the server and storage expansion units, for example, is described in the respective manuals for these devices.

You will find additional information:

● in the “Security, Guarantee and Ergonomics” manual

● in the documentation for the individual components installed in the rack

● in the documentation for the operating systems used

1.4 Notational Conventions

bold type Used for emphasis in the body of the text“quotation marks” Used for references to other chapters, sections or

manualsÊ Identifies an action that you need to takeI Alerts you to important information, notes and tips

V CAUTION! Warning sign indicating that your health, the correct functioning of your system or the security of your data may be at risk if you ignore the information given at this point

Page 14: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

14 A3C40110888A

Technical Data (excerpt) Preface

1.5 Technical Data (excerpt)

Cabinet size: 12 HU 24 HU 38 HU 46 HUExternal Height: 670 mm 1230 mm 1820 mm 2220 mmThe dimensions refer to ISO2768c

Width: 700 mm 700 mm 700 mm 700 mmDepth: 940 mm /

1000 mm1000 mm / 1100 mm

1000 mm / 1100 mm

1000 mm / 1100 mm

External transport dimensions: (cabinet and packaging)External Height: 790 mm 1345 mm 1935 mm 2335 mm

Width: 970 mm 970 mm 970 mm 970 mmDepth: 1100 mm 1280 mm 1280 mm 1280 mm

Cabinet weight:

82 kg (empty)

110 kg (empty)

150 kg (empty)

168 kg (empty)

Total weight 1000 kg 1000 kg 1000 kg 1000 kg19-inch clearance

The 19-inch level clearance is 450.5 mm with atolerance of + 1 mm / - 0 mm

Internal depth Distance front and rear at 19-inch level: 740 mm. Minimum distance between front 19-inch level and door: 60 mm

Side panels Locked from inside, also accessible when rack is assembled19-inch support brace

The size of the holes on the 19-inch supports is 9.5 mm x 9.5 mm

Power ratings Connection to the mains is possible via UPS. The primary circuit UPS connection should be carried out in accordance with the data sheet for the respective UPS. All socket strips must be ordered separately. Please refer to the configurator for information on the configuration. Rated voltage range: 200 - 240 V, Rated frequency: 50 - 60 Hz

Ambient conditions (EN60721)

Transport: Ambient temperature -25°C to 60°CRelative humidity 15% - 98%Mechanical ambient conditions: Operational class 3K3*, 3M2, Transport class 2K2, 2M2, 2S1Storage class 1M3, 1K2, 1S2

* possibly restricted by rack components

Page 15: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 15

Preface Technical Data (excerpt)

Maximum load 1000 kg stationary on roller/leveling feet1000 kg dynamic (only on roller feet)

Security function

Lockable front + rear door, locked side panels, anti-tilt plate

Protection class (acc. to DIN 40050 or IEC 529) IP00

Page 16: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE
Page 17: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 17

2 Important NotesThis chapter provides you with important information on setting up and operating the PRIMECENTER Rack system.

2.1 Rack Philosophy

The PRIMECENTER Rack combines features in such a way as to make it unique in the world of 19-inch rack technology. The PRIMECENTER Rack is designed without compromise to provide the user with the highest possible level of service, offering unparalleled flexibility at an acceptable price. The well-balanced concept is reflected in the following points among others:

Transport Concepts

The height of the 38 HU PRIMECENTER Rack allows it to fit through a normal, 2-meter high door without having to be tipped, even if it is still on the delivery palette. This not only makes the rack easier to transport but also allows it to be delivered with components such as server or storage expansion units already installed and configured as specified by the customer. It also makes it easy to move the PRIMECENTER Rack to a new location on its rollers. The internal cabling is complete.

The same specifications apply to both the 24 HU PRIMECENTER Rack and the 12 HU PRIMECENTER Rack.

The 46 HU PRIMECENTER Rack is delivered without the rack components pre-installed. The components are mounted in the rack after it has reached its location. This rack can also be easily moved to a new location on its rollers. The transport concept for the 46 HU PRIMECENTER Rack assumes that the customer does not know about individual local conditions like the height of the door frame or the existence of elevators etc. Therefore, the "empty" rack can also be transported in a "tipped" position.

Page 18: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

18 A3C40110888A

Rack Philosophy Important Notes

Installation Concept

The PRIMECENTER Rack is based on internationally standardized 19-inch rack technology and makes optimum use of the space provided. In addition to mounting rack components horizontally at the front and rear, an optional expansion area is also available. Up to 3x 2 HU, mounted vertically, are available for installations of up to 290 mm in depth, (240 mm + 50 mm cabling). This means, for example, that horizontal height units do not have to be occupied for hubs, modems or switches.

If cable management is not used, the full depth of this mounting location can be used.

Rack components can be mounted horizontally using sliding rails or telescopic rails. Mounting components using telescopic rails and the corresponding cable management system allows maintenance and repair work to be carried out easily and cost-effectively and supports hot-plug solutions.

Cable Management

The PRIMECENTER Rack provides an efficient cable management system. Because the cables are routed along the side of the rack components using articulated cable guides or cable guides with cable clips, the connection side of the rack components remains tidy, making it is easy to see where each cable leads. A distinction is made between two types of connection:

– A connection via an articulated cable guide

– A direct connection

An articulated cable guide is used together with rack components that are mounted in the PRIMECENTER Rack using telescopic rails or sliding rails. This combination allows rack components to be pulled from the rack without having to disconnect the cables first and therefore allows device components to be replaced during operation in hot-plug solutions.

With other rack components, cables are connected directly. This means that the cables can be shorter but hot-plug solutions are not or only partially supported.

Excess lengths of cable can be fastened at certain locations within the PRIMECENTER Rack using one or more cable guides with cable clips.

Page 19: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 19

Important Notes Notes on Safety

Ventilation Concept

If the PRIMECENTER Rack is to function reliably, adequate ventilation of all the rack components must be ensured. To guarantee that this is always the case, the ventilation concept applied to all rack components has been coordinated with the PRIMECENTER Rack to provide a uniform overall solution. The basic ventilation concept is designed so that fresh air is drawn in through the front and warm air is expelled from the rear.

Because of the high extraction rate - the perforation rate in the doors is more than 60 percent causing lower air resistance - optimum ventilation is achieved for each height unit. The PRIMECENTER Rack is therefore already aligned to meet the future installation needs of servers and storage systems that have a high heat dissipation.

2.2 Notes on Safety

V CAUTION!

Observe the safety instructions in the documentation for the individual components mounted in the rack and the following notes on safety.

● The activities described in this manual may only be performed by technicians, service personnel or technical specialists. Ignoring the instructions in this manual can result in personal injury or damage to equipment (risk of tipping over, etc.).

● When the unit is transported, it is only allowed to have a lean angle of max. 30°.

● The unit must remain in the original package till its installation location.

● Make sure the floor at the final place of installation has sufficient load-bearing capacity.

● Always ensure that the anti-tilt plate is mounted when you set up the PRIMECENTER Rack (risk of tipping over).

● When connecting or disconnecting cables, refer to the relevant notes in the section “Connecting and Disconnecting Cables” on page 78.

● Route the cables in such a way that they do not form a potential hazard (make sure no one can trip over them) and that they cannot be damaged.

Page 20: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

20 A3C40110888A

Notes on Safety Important Notes

V CAUTION!

● When mounting a server, pull the telescopic rails out all the way until they click into position.

● For safety reasons, no more than one unit must be pulled out of the rack at a time, otherwise the rack may tip over.

This is illustrated by the following pictogram:

● Before you mount a server in the PRIMECENTER Rack, remove all heavy and easily removed server components such as hot-plug disks and power supply modules for redundant power supplies since this makes the server lighter and easier to mount.

● Before pushing extended telescopic rails back into the rack, pull the ball cage of the telescopic rail forward as far as it will go.

● For safety reasons, no more than one unit may be withdrawn from the rack at any one time during installation and maintenance work. If more than one unit is withdrawn from the rack at any one time, there is a danger that the rack will tilt forward.

● If necessary, have other people help you mount the individual compo-nents in the rack because of the weight involved.

● Install only system expansions that satisfy the requirements and rules governing safety. If you install other expansions, you may damage the system or violate these safety regulations. Information can be obtained from customer service or your local sales office.

● If you cause a defect on the device by installing or exchanging system expansions, the warranty is invalidated.

● The configurations available in the PRIMECENTER Rack can carry a leakage current >3.5 mA. Therefore, a ground connection must be established before connecting to the mains (see chapter “Power Supply” on page 87).

Page 21: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 21

Important Notes Notes on Mounting the Rack Components

V CAUTION!

● The AC main power connection for the PRIMECENTER Rack must be installed by an authorized electrician approved by the local utility company.

2.3 Notes on Mounting the Rack Components

Before you start mounting components in the rack, you should identify the positions of the individual components in the PRIMECENTER Rack according to the configuration generated using the System Architect (see section “The System Architect” on page 52). You should then mark the positions using the relevant assembly aid, if one was supplied with the rack component.

Marking and numbering the height units simplifies the assembly when installing and adding on components.

The maximum mounting height for the PRIMECENTER Rack is 12/24/38/46 height units (HU). One height unit corresponds to 44.45 mm (see section “The Height Unit (HU)” on page 53).

A lift truck is available from Fujitsu Technology Solutions to ensure that heavy components can be fitted precisely into the rack. The address for ordering the lift truck is available from FSC Service.

Observe the following rules when mounting the components:

● Mount the components in the rack from bottom to top.

● Mount heavy parts at the bottom, e.g. the uninterruptible power supply.

● Mount the keyboard or rack console at a height that makes it easy to operate (HU 17 - 21).

● Position the dummy covers so that later planned extensions can be installed without having to rearrange components.

● To accommodate the ventilation concept and ensure proper ventilation of all the components in the rack, any unused areas must be closed using dummy covers.

● Mount the unit in accordance with the technical manual and assembly aid supplied.

Page 22: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

22 A3C40110888A

Environmental Protection Important Notes

2.4 Environmental Protection

Environmentally Friendly Product Design and Development

This product has been designed in accordance with the Fujitsu Technology Solutions standard “Environmentally Friendly Product Design and Devel-opment”. This means that the designers have taken into account crucial criteria such as durability, selection and labeling of materials, emissions, packaging, the ease with which the product can be dismantled and the extent to which it can be recycled. This saves resources and thus reduces the harm done to the environment.

Notes on Saving Energy

Devices that do not have to be on permanently should not be switched on until they are needed and should be switched off during long breaks and when work is finished.

Notes on Packaging

We recommend that you do not throw away the original packaging in case you need it later for transportation. If possible, devices should be transported in their original packaging.

Notes on Dealing with Consumables

Please dispose of printer consumables and batteries in accordance with local regulations.

Notes on Labeling Plastic Housing Parts

Please avoid attaching your own labels to plastic housing parts wherever possible, since this makes it difficult to recycle them.

Page 23: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 23

Important Notes Environmental Protection

Take-back, Recycling and Disposal

For details on take-back and reuse of devices and consumables within Europe, contact your Fujitsu Technology Solutions branch office/subsidiary or our recycling center in Paderborn:

Fujitsu Technology Solutions GmbHRecycling CenterD-33106 Paderborn

Tel. ++49 5251 8180-10

Fax ++49 5251 8180-15

Page 24: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE
Page 25: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 25

3 PreparationsThis chapter describes the preparations for installation and all the tasks involved in setting up and operating the PRIMECENTER Rack.

3.1 Unpacking and Checking the Delivery Unit

Delivery Unit

– PRIMECENTER Rack– Anti-tilt plate– Keys

You will receive two pairs of keys, one for the front and one for the rear door. Keep the keys in a safe place.

– Tools for adjusting the leveling feet– Additional assembly materials in a bag– Technical manual

Depending on the order placed, the PRIMECENTER Rack may be already fully assembled and ready to operate on delivery.

Ê Unpack all the individual parts.

Ê Check the delivery for damage sustained during transport.

Ê Check whether the delivery matches the specifications in the delivery note.

Ê Check whether all the necessary details have been entered on the first page of the guarantee booklet.

V CAUTION!

Check that the bag attached to the rear door contains the keys for the rack.

Should you discover that damage has occurred during transport or that the delivery does not match the delivery note, notify your supplier immediately!

The PRIMECENTER Rack is shipped on a palette to which it is secured.

Page 26: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

26 A3C40110888A

Installation Procedure Preparations

3.2 Installation Procedure

V CAUTION!

Observe the safety and installation notes in the chapter “Important Notes” on page 17.

Work through the installation steps in the specified order. The individual steps are described in detail in the next chapters.

● Setting up and adjusting the PRIMECENTER Rack.

The palette has an integrated ramp function that allows you to remove the PRIMECENTER Rack from the palette without any additional aids.

V CAUTION!

Make sure that the floor at the final place of installation has sufficient load-bearing capacity!

● Mounting the anti-tilt plate (see page 39 resp. page 43).

Page 27: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 27

Preparations Opening the PRIMECENTER Rack

3.3 Opening the PRIMECENTER Rack

The PRIMECENTER Rack has a split door at the front. The left door contains a lock system. The doors can be opened with a key.

Optionally, a door knob can be mounted so that the doors can be opened and closed without a key (see section “Opening the door with the door knob” on page 28).

Opening the door with the key

Figure 3: Opening the PRIMECENTER Rack with a key

Ê Turn the key 180 degrees anti-clockwise.

Ê Open the left door first, then the right door.

Page 28: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

28 A3C40110888A

Opening the PRIMECENTER Rack Preparations

3.3.1 Opening the door with the door knob

Figure 4: Opening the rack with the door knob

Ê Turn the door knob 180 degrees anti-clockwise.

Ê Open the left door first, then the right door.

I How to mount the door knob is described in the section “Mounting the Optional Door Knob” on page 99.

Page 29: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 29

Preparations Rolling off the PRIMECENTER Rack

3.4 Rolling off the PRIMECENTER Rack from the Transport Palette

The palette has an integrated ramp function that allows you to remove the PRIMECENTER Rack from the palette without any additional aids.

V CAUTION!

Pay attention to the load carrying capacity of the floor at the final place of installation!

V CAUTION!

If necessary, ask other people for help.

3.4.1 Handling and Transportation Instructions until 12/2007

The instructions from 01/2008 you will find in the chapter after next. Work through the following steps in order to remove the PRIMECENTER Rack from the palette:

Page 30: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

30 A3C40110888A

Rolling off the PRIMECENTER Rack Preparations

Figure 5: Assembling the roll-off ramps

Ê Assemble the roll-off ramps as shown in the figure (steps 1, 2, 3).

The roll-off ramps are secured to the palette using two preconditioned screws each. Make sure that the roll-off ramps are form-fit with the front and side of the palette to ensure the proper track span.

Page 31: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 31

Preparations Rolling off the PRIMECENTER Rack

Figure 6: Removing the shipping braces

Ê Using a (battery powered) screwdriver, carefully remove the shipping brace (three on each side) from the transport palette.

Figure 7: Removing the transport blocks

Ê Carefully remove the two transport blocks by undoing the screws (two on each side).

3x

3x

Page 32: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

32 A3C40110888A

Rolling off the PRIMECENTER Rack Preparations

Figure 8: Tilting and stabilizing the palette

Ê Tilt the palette forwards from the rear and stabilize the position of the palette by placing the transport blocks underneath.

V CAUTION!

The rack can weigh up to 1000 kg. Please be very careful when moving the rack. Call on assistance from other people if necessary.Avoid heavy shocks.

The rack tilts forwards with the palette so that the roll-off ramps are at a level with the surface of the palette.

The transport blocks are placed underneath the rear of the palette and prevent the palette and the rack tilting back into their rest position.

Page 33: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 33

Preparations Rolling off the PRIMECENTER Rack

Figure 9: Rolling off the rack

Ê Roll the rack carefully off the transport palette.

Ê Roll the PRIMECENTER Rack into its final position at the place of instal-lation.

V CAUTION!

The rack can weigh up to 1000 kg. Please be very careful when moving the rack. Call on assistance from other people if necessary.

Page 34: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

34 A3C40110888A

Rolling off the PRIMECENTER Rack Preparations

3.4.2 Handling and Transportation Instructions from 01/2008

V CAUTION!

The rack can weigh up to 1000 kg. Please be very careful when moving the rack. Call on assistance from other people if necessary.

Detaching from the wooden pallet

Ê The unit is seated on the pallet and is secured with 6 metal clamps, which must be unscrewed from the pallet.

Ê For removing the screws a Phillips screwdriver is required.

Ê After removal of the packing foil the unit must be slipped from the pallet as shown below.

Page 35: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 35

Preparations Setting up the PRIMECENTER Rack

3.5 Setting up the PRIMECENTER Rack

When you have rolled the PRIMECENTER Rack off the transport palette, read this section to help you set up the PRIMECENTER Rack.

4x

2xright and left

>90°

3x

3x

4x

1

2x

23

1 2

3

Page 36: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

36 A3C40110888A

Setting up the PRIMECENTER Rack Preparations

Required areas for the rack

Figure 10: Installation and service areas required for the rack

Page 37: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 37

Preparations Setting up the PRIMECENTER Rack

Figure 11: Undoing the screws of the cover plate

Ê Undo the two screws of the front cover plate.

Ê Remove the cover plate.

Figure 12: Removing the cover plate

1 Front joint element 2 Screw for leveling foot

2

1

Page 38: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

38 A3C40110888A

Setting up the PRIMECENTER Rack Preparations

Figure 13: Adjusting the PRIMECENTER Rack

Ê Make sure that the four installation plates have been fixed to the leveling feet.

Ê Adjust the PRIMECENTER Rack using the supplied Allen key.The leveling feet are easy to adjust when not carrying the full weight of the rack. If necessary, please ask another person to tilt the rack slightly in order to relieve the leveling foot in question.

Ê Raise the leveling feet such that the anti-tilt plate can be easily pushed in underneath.

I The horizontal orientation of the rack is required to ensure the pull-out functions of the components mounted to the rack.

I The Rack is set up properly, as a rule, when the front panels of the mounted components add up to form a continuous vertical line!

Page 39: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 39

Preparations Mounting the Anti-Tilt Plate

3.6 Mounting the Anti-Tilt Plate until end of 2007

This chapter describes how to mount the anti-tilt plate on the PRIMECENTER Rack.

V CAUTION!

Make sure that the floor at the final place of installation has sufficient load-bearing capacity!

Figure 14: Anti-tilt plate

Ê Push the anti-tilt plate under the rack from the front.

V CAUTION!

The anti-tilt plate must make firm contact with the ground at the front.

The anti-tilt plate is fastened to the rear joint elements with two Allen screws (M8xM40).

11

Page 40: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

40 A3C40110888A

Mounting the Anti-Tilt Plate Preparations

Figure 15: Inserting a screw in the rear joint element

Ê Insert a screw into the right rear joint element and fasten it.

Ê Then insert a screw into the left rear joint element and fasten it.

I If you cannot access the left rear joint element because of any installed support systems, proceed as described in the following section: “Special case: Support systems installed in the bottom level”.

Page 41: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 41

Preparations Mounting the Anti-Tilt Plate

Special case: Support systems installed in the bottom level

Figure 16: Pulling out systems in the bottom level

Ê Pull out toward the front any systems installed in the bottom level.

Figure 17: Pushing the support system outward

1

Page 42: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

42 A3C40110888A

Mounting the Anti-Tilt Plate Preparations

Figure 18: Pushing the support system to the center of the rack

Ê Loosen the bottom support system (1) at the rear left and push it in the direction of the outer cover plate (see figure 17) or of the center of the rack (see figure 18) to provide access to the joint element.

Ê Insert a screw in the rear left joint element and fasten it.

Ê Refasten the support system.

Ê Push the bottom-level systems back in.

1

Page 43: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 43

Preparations Mounting the Anti-Tilt Plate

Figure 19: Tightening the front stud screw for the anti-tilt plate

Ê Fasten one stud screw (M12x40) into each of the two front joint elements. This presses the anti-tilt plate against the floor.

V CAUTION!

The anti-tilt plate must make firm contact with the ground at the front.

Ê Reinsert the cover plate and fasten it.

3.7 Mounting the Anti-Tilt Plate from 01/2008

To improve the access when mounting the anti-tilt plate, the srewing was brought to a horizontal position. Support systems on the bottom level need not be demounted any more.

Page 44: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

44 A3C40110888A

Mounting the Anti-Tilt Plate Preparations

Figure 20: Anti-tilt plate with appropriate screws

Figure 21: Anti-tilt plate from 01/2008

Ê Push the anti-tilt plate under the rack from the front.

V CAUTION!

The anti-tilt plate must make firm contact with the ground at the front.

M8x12mm

M8x12mm

M5x8mm

M5x8mm

Page 45: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 45

Preparations Mounting the Anti-Tilt Plate

Figure 22: Move central grounding point to the right if required

Figure 23: 1 Clamping nut M52 Mounting bracket3 Allen screw M5x8mm4 Allen screw M8x12mm

Page 46: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

46 A3C40110888A

Mounting the Anti-Tilt Plate Preparations

Figure 24: Insert Clamping nut M5 in the rack profile

Figure 25: Position of right mounting bracket

Page 47: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 47

Preparations Mounting the Anti-Tilt Plate

Figure 26: Allen screw M5x8mm (right hand side of the rack)Tool: Allen key M4

Figure 27: Bracket mounted in the right corner at the rear of the rack. Insert bracket in the rear left corner of the rack, tighten the screw M5x8 and move it to the right into position. Align screw thread M8 in the anti-tilt plate with the drill hole of the mounting bracket and tighten the screw M8x12mm . Afterwards please mount the left bracket.

Page 48: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

48 A3C40110888A

Mounting the Anti-Tilt Plate Preparations

Figure 28: Tighten the screws

Figure 29: Bracket mounted at the left rear corner of the rack. Take out the leveling foot, raise the rolls, adjust the rack

Page 49: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 49

Preparations Mounting the Anti-Tilt Plate

Figure 30: Tighten the screws

Figure 31: Short and extended anti-tilt plate

Page 50: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE
Page 51: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 51

4 Mounting Rack ComponentsThis chapter describes how to prepare the PRIMECENTER Rack for the instal-lation of rack components. Refer to the appropriate operating manuals for infor-mation on how to mount the components themselves.

The rack has three areas in which components can be mounted:

– the 19-inch area with 12/24/38/46 HU, which is accessible from the front and is used for mounting the rack components horizontally.

– the optional expansion area with 1 x 2 HU, 2 x 2 HU and 3 x 2 HU, which is accessible from the front and is used for mounting the rack components vertically.

– the 19-inch area, which is accessible from the rear and is used for mounting the rack components horizontally if not already occupied by other compo-nents.

Before you prepare the PRIMECENTER Rack and start mounting components, you should use the System Architect to help you determine the mounting position and the mounting height of the relevant components. Also observe the information in the section “Notes on Mounting the Rack Components” on page 21.

V CAUTION!

Make sure the floor at the final place of installation has sufficient load-bearing capacity!

Page 52: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

52 A3C40110888A

The System Architect Mounting Rack Components

4.1 The System Architect

The System Architect configuration tool is used as an aid for configuring the PRIMECENTER Rack.

Before you start mounting components in the PRIMECENTER Rack, you should identify the positions for mounting the individual components in the PRIMECENTER Rack according to the configuration generated using the System Architect and, if available, the assembly aid supplied with the component.

Figure 32: Configuration example

3 x PRIMERGY N200

Dummy cover 1HU PRIMERGY S30Console Switch

PRIMERGY S30

PRIMERGY N400

PRIMERGY N400

Rack consoleConsole SwitchConsole Switch

PRIMERGY N800/4HDD

Dummy cover 2HU PRIMERGY N800/4HDD

UPS APCUPS APC

Page 53: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 53

Mounting Rack Components The Height Unit (HU)

4.2 The Height Unit (HU)

The unit of measurement used in the PRIMECENTER Rack is the height unit (HU). One height unit comprises a 3-hole section in the front area and mounting area (starts and ends with a narrow metal bar) and corresponds to 44.45 mm or 1 ¾ inches.

The height units are numbered consecutively in ascending order from 1 upwards, above and below the center of the vertical support uprights.

A PRIMECENTER Rack with 38 height units therefore has 19 height units above and 19 height units below the center of the support uprights.

Figure 33: Height unit (HU)

1 HE1 HE

Page 54: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

54 A3C40110888A

Inserting mounting elements Mounting Rack Components

4.3 Inserting Cage and Spring Nuts and Mounting Elements

When mounting rack components you often have to insert cage and spring nuts and/or mounting elements in the support uprights. Proceed as follows:

Ê Mark the position of the components to be fitted on the four support uprights.

I In order to facilitate the positioning, assembly aids are shipped with the rack components.

4.3.1 Inserting Cage Nuts

Figure 34: Inserting cage nuts

Ê Insert the cage nut as shown in the figure with the bottom part of the cage in the appropriate mounting hole of the support upright (1).

Ê Use the tool supplied to lever the upper part of the cage nut into the mounting hole as shown (2).

The cage nut should lock into the mounting hole as shown (3).

Page 55: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 55

Mounting Rack Components Inserting mounting elements

4.3.2 Inserting Spring Nuts

You need spring nuts for mounting socket strips for the power supply of the rack components.

Figure 35: Inserting spring nuts

Ê Insert the spring nut into the appropriate groove on the support upright at the marked location (1) - (4).

Ê If necessary, slide the spring nut within the groove until it locks in the correct position (5).

1

2

3

4

5

5

ca. 45°

Page 56: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

56 A3C40110888A

Inserting mounting elements Mounting Rack Components

4.3.3 Inserting Plugwashers

You need plugwashers and M5 screws for mounting telescopic rails, sliding rails and support brackets. Together with the screw head of the M5 screw, the plugwasher forms a keyed connection in the square 9.5 x 9.5 mm 19-inch grid.

Figure 36: Inserting plugwashers

Ê Insert the plugwashers (1) into the relevant opening on the support upright or support bracket.

Page 57: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 57

Mounting Rack Components Support systems

4.4 Support Systems

Support systems are needed in order to be able to integrate system compo-nents effortlessly into the rack. There are different types of support systems, which are introduced below:

● Sliding rails with linear alignment

● Telescopic rails with system mounts

● Telescopic rails for standard direct mounting (screw fastening)

● Direct mounting via the front panel

● Adapter for integrating older support systems (Classic Rack and Datacenter Rack).

4.4.1 Sliding Rails with Linear Alignment

Figure 37: Sliding rails with linear alignment

1

2

Page 58: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

58 A3C40110888A

Support systems Mounting Rack Components

Figure 38: Sliding rails with linear alignment and different hold-down clamps

Sliding rails are used for installing system components that do not have hot-plug functions or service-related functions.

1

2

Page 59: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 59

Mounting Rack Components Support systems

4.4.2 Telescopic Rails with System Mounts

Figure 39: Telescopic rails with system mounts

Telescopic rails with system mounts offer the best functional solution for installing systems. The installation is not assembly-intensive because only two screws are generally needed to fix the system in place.

1

2

Page 60: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

60 A3C40110888A

Support systems Mounting Rack Components

4.4.3 Telescopic Rails for Standard Direct Mounting

Figure 40: Telescopic rails for standard direct mounting (screw fastening)

Telescopic rails for standard direct mounting can be assembly intensive. 8 to 10 screws are generally needed to secure the system. The installation depth and height should be fixed and secured with the assistance of others.

1

2

Page 61: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 61

Mounting Rack Components Support systems

4.4.4 Direct Mounting via the Front Panel

Figure 41: Direct mounting via the front panel

This generally involves switch boxes or signal distributers that are light weight and have a small installation depth.

1

2

Page 62: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

62 A3C40110888A

Support systems Mounting Rack Components

4.4.5 Adapters

Figure 42: Adapter for integrating older support systems

This adapter bracket forms the lateral Knürr-specific fixing grid (Classic Rack and Datacenter Rack). It allows older support systems to be integrated in the new PRIMECENTER Rack. Thanks to both the bracket and the variable instal-lation depth, compliance with the installation standard of many other rack manufacturers is guaranteed automatically.

1

2

Page 63: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 63

Mounting Rack Components Mounting in the front 19-inch area

4.5 Mounting in the Front 19-inch Area

Components are mounted in the front 19-inch area of the PRIMECENTER Rack using either telescopic or sliding rails. Light components can also be mounted via the front panel.

If components are mounted using telescopic rails, all the cables leading to the components are routed via an articulated cable guide. If service work needs to be performed, the cables can remain connected when the components are removed from the PRIMECENTER Rack. This makes servicing much easier and also allows device components in hot-plug slots to be replaced during operation.

If components are mounted using sliding rails, all the cables are routed directly to the components and are connected without any special aids, i.e. without using an articulated cable guide. If service work needs to be performed, all connected cables must be disconnected before the components can be removed from the PRIMECENTER Rack.

A support bracket is required for mounting components regardless of whether telescopic rails or sliding rails are used.

Figure 43: Support brackets with a load capacity of 150 kg and 50 kg respectively

Support brackets with a load capacity of 50 kg (1 HU) and for support systems with a load capacity of 150 kg (2 HU) are available. A cable clip can be mounted on each support bracket for vertical cabling.

Page 64: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

64 A3C40110888A

Mounting in the front 19-inch area Mounting Rack Components

Special Bracket for PRIMEPOWER Systems (3HU)

Figure 44: Special bracket for PRIMEPOWER systems

Mounting the Support Bracket

The support bracket is mounted at the appropriate height on the rear left support upright and is used to fasten the left sliding or telescopic rail at the rear.

Page 65: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 65

Mounting Rack Components Mounting in the front 19-inch area

Figure 45: Mounting a support bracket with a load capacity of 50 kg and 150 kg (2 U)

Ê Mount the support bracket as shown and screw it to the rear left support upright at the appropriate height using two screws and cage nuts or mounting springs, depending on which variant you are mounting.

Ê If necessary, you can mount one additional cable clip to each support bracket for vertical cabling.

Page 66: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

66 A3C40110888A

Mounting in the expansion area Mounting Rack Components

4.6 Mounting in the Expansion Area

19-inch rack components with a maximum of 2 HU each can be mounted verti-cally in the optional expansion area of the PRIMECENTER Rack to the left of the 19-inch area. The cable management restricts the depth of the components to 290 mm. Gaps that occur when you mount 1 HU components must be covered.

4.6.1 Mounting Rack Components

Figure 46: Mounting a rack component in the expansion area

Ê Remove the cover from the appropriate slot (1).

Ê Insert the cage nuts as required for the component to be installed (2).

Ê Install the rack component (3) and cover any resulting gap with an appro-priate cover.

Page 67: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 67

Mounting Rack Components Mounting in the rear 19-inch area

4.7 Mounting in the Rear 19-inch Area

You can mount additional rack components in the rear 19-inch area if:

– the front area is not occupied with rack components

– the rack components mounted in the front area leave enough space for additional components to be mounted at the rear (in the rear area)

An appropriate support bracket is again required for mounting rack components on the lefthand side. If you cannot use an existing bracket, you will have to mount a new support bracket at the appropriate position.

Figure 47: Example of how to mount a rack component in the 19-inch area at the back

Ê If there is no support bracket at the appropriate position on the left rear support upright, mount a support bracket with the appropriate load capacity (1) (see section “Mounting the Support Bracket” on page 64).

Ê Use the support upright (2) for mounting rack components on the righthand side.

V CAUTION!

Please pay heed to the ventilation concept. The cooling of the built-in rack components must be ensured.

2

1

Page 68: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

68 A3C40110888A

Converting the Rack Mounting Rack Components

4.8 Converting the Rack from a Depth of 940 mm to 1000 mm

The PRIMECENTER Racks are shipped in two depths (940 mm and 1000 mm). The basic frame is the same for all PRIMECENTER Racks.

If the depth of the rack is to be upgraded in the field from 940 mm to 1000 mm, this can be done using a rebuild set. This rebuild set includes adapter pieces for mounting hinges and door stops as well as a rack surround set of panels, comprising top, right and left panel.

Proceed as follows to convert the rack:

Ê First remove the door at the back of the rack.

Figure 48: Installing the adapter pieces for mounting hinges and door stops

Ê Insert the relevant number of cage nuts into the uprights to secure the adapter pieces for mounting the hinges and the door stops.

Ê Tightly fasten the fastening screws for the hinges and the door stops.

12

Page 69: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 69

Mounting Rack Components Converting the Rack

Figure 49: Screws for the right side panel for the door stops

Ê Tightly screw on the fastening screws in the door stop to secure the right side panel.

12

Page 70: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

70 A3C40110888A

Converting the Rack Mounting Rack Components

Figure 50: Screws for the left side panel for the hinges

Ê Tightly screw down the fastening screws in the hinge mounting to secure the left side panel.

Page 71: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 71

Mounting Rack Components Converting the Rack

Figure 51: Screws for the upper panel

Ê Tightly screw down the three fastening screws for the upper panel.

V CAUTION!

With a pencil, mark exactly where the adapter pieces for the hinge mounts and door stops are to be inserted to ensure that they can still be inserted at the same position again after any subsequent upgrade.

Ê Adjust the door on the rear of the rack again and tightly screw down the fastening bolts.

The rack is converted to the old rack depth of 940 mm in the reverse sequence.

12

Page 72: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

72 A3C40110888A

Cable Inlets and Outlets Mounting Rack Components

4.9 Rack Surround Cable Inlets and Outlets with External Cabling

A surrounding slit forms between the basic frame and the rear door as a result of inserting the adapter pieces for the hinge mounts and the door stops. This slit is used for feeding in and out cables.

The width of the slit depends on the depth of the rack. If the rack has a depth of 940 mm, the slit is 50 mm wide and if the rack has a depth of 1000 mm, the slit is 110 mm wide.

This surrounding slit is covered by a set of panels (1 x above und 2 x at the sides). In the case of external cabling or add-on racks, the panels can be removed to feed in and out the cables (figure 52 on page 73).

Page 73: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 73

Mounting Rack Components Cable Inlets and Outlets

Figure 52: Rack surround cable entry and exit points with external cabling

12

Page 74: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE
Page 75: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 75

5 Cable ManagementThis chapter describes how to mount the components of the cable management and how to connect cables and route them in the PRIMECENTER Rack.

1. Mounting components of the cable management

2. Connecting cables

3. Routing cables

5.1 Mounting Components of the Cable Management

The cable management comprises the following parts:

– articulated cable guides

– cable guides with cable clips

Page 76: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

76 A3C40110888A

Mounting the Cable Management Cable Management

5.1.1 Articulated Cable Guides

Articulated cable guides are used for rack components that are mounted in the rack using telescopic rails.

The mounting height of the articulated cable guide depends on the rack component to be installed and must not interfere with the telescopic rails.

Figure 53: Mounting an articulated cable guide

Ê Insert the articulated cable guide into the rear support upright for the cable guide at the appropriate height as shown.

Ê Fasten the articulated cable guide to the rear support upright using two plugwashers and two screws.

The cable managements for some rack components can be installed completely in the free height units. A distance should be left to the next cable management to facilitate cable upgrades.

1 2

Page 77: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 77

Cable Management Mounting the Cable Management

5.1.2 Cable Guide with Cable Clips

You can use one or more cable guides with cable clips to store excess lengths of cable in an orderly fashion at appropriate locations in the rack.

The other cable clips supplied can be distributed over the rack and mounted on the support brackets as needed.

Figure 54: Mounting cable guides with cable clips

Ê Insert the cable guide with cable clips (1) into the support upright for the cable guide at the appropriate height as shown for the articulated cable guide in figure 53 on page 76.

Ê Fasten the cable guide with cable clips to the rear support upright using two plugwashers and two screws.

1

Page 78: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

78 A3C40110888A

Connecting and Disconnecting Cables Cable Management

5.2 Connecting and Disconnecting Cables

V CAUTION!

● The power plug must be pulled out!

● Read the documentation for the device before you connect it.

● Make sure that all signal cables are free of electrostatic charge before they are plugged.

● Never connect or disconnect cables during thunderstorms.

● When disconnecting a cable, always grasp the plug. Never pull on the cable.

● Connect or disconnect cables in the sequence shown below.

5.2.1 Connecting Cables

Ê Switch off all affected devices.

Ê The power plug of all affected devices must be pulled out of the sockets on the socket strip in the PRIMECENTER Rack.

Ê Attach all cables to the devices. Mark the cables and note what function each cable serves.

I Above all, observe the safety notes in the chapter “Important Notes” on page 17.

Ê Plug all data transmission cables into the sockets provided for the data transmission or telephone networks.

Ê Plug the mains power plugs of all devices into the sockets on the socket strip(s) in the rack.

I Make sure that the power cables of the devices are plugged in so that there is an even distribution of power to the three phases (L1, L2, L3) (see chapter “Power Supply” on page 87).

Make sure that the cabling of devices with a "dual power feed" fulfils the of the high availability requirements of the system.

Page 79: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 79

Cable Management Routing Cables

5.2.2 Disconnecting Cables

Ê Switch off all affected devices.

Ê Pull the power plugs of all affected devices out of the sockets on the socket strip in the PRIMECENTER Rack.

Ê Pull all data transmission cables out of the sockets provided for the data transmission or telephone networks.

Ê Disconnect all cables on the devices.

5.3 Routing Cables

Only internal cables are routed at the factory. All other cables must be routed during rack installation.

If one or more articulated cable guides are mounted with an installed device, all external cables must be routed in these guides.

If the installed articulated cable guides are not sufficient for the number of cables, you must install additional ones.

The articulated cable guides must be installed 1 HU apart. If this is not possible, the cables must be routed in the rack before installing the device.

For easier access to the articulated cable guides you can pull out the systems above and below the guides toward the front.

This section contains several examples of how to route cables in the PRIMECENTER Rack.

Page 80: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

80 A3C40110888A

Routing Cables Cable Management

5.3.1 Articulated cable guide

Figure 55: Routing cables using an articulated cable guide

Ê Route the cables as shown in the figure.

Page 81: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 81

Cable Management Routing Cables

5.3.2 Cable Routing and Strain Relief for the Built-in Rack Component

The rack component is inserted in the PRIMECENTER Rack and secured. The cables are attached to the relevant plug connectors and should be routed in the cable management system with a reserve length by making a loop over the center axis of the rack component (see figure 56).

Figure 56: Rack top view: rack component inserted and secured

� � � � � � � � � �

� � � � � � �

� � � � � � � � � � � � �

� � � � � � � � �

�����������������

Page 82: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

82 A3C40110888A

Routing Cables Cable Management

When the rack components are extracted, the cables fixed in the articulated guide are also pulled out. The articulated guide stabilizes the cables at the appropriate rack component height and thus ensure a trouble-free insertion and removal (see figure 57 below and figure 58 on page 83). The mechanical attachment is performed using the strain relief fitting on the connectors.

Figure 57: Rack top view: rack component pulled out half way

50%articulatedcable guide

loom of cables

connectors

fron

t of t

he R

ack

Page 83: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 83

Cable Management Routing Cables

Figure 58: Rack top view: rack component pulled out fully

105

% fr

ont o

f the

Rac

k

conn

ecto

rs

artic

ulat

edca

ble

guid

e

loom

of c

able

s

Page 84: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

84 A3C40110888A

Routing Cables Cable Management

5.3.3 Cable Guide with Cable Clips

The example below shows you how to route excess lengths of cable in the PRIMECENTER Rack using a cable guide with cable clips.

V Caution!

In the case of fiber-optic cables, a minimum bending radius must be adhered to.

Figure 59: Routing cables using a cable guide with cable clips

Ê Route the cables as shown in the figure.

Page 85: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 85

Cable Management Routing Cables

5.3.4 Direct Connection

The example below shows how to connect a cable directly to a rack component installed on sliding rails.

Figure 60: Routing cables of a rack component with direct connection

Ê Route the cables in the side area of the rack as shown in the figure.

V Caution!

The ventilation slots of the devices installed underneath must not be covered by the cables.

Page 86: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE
Page 87: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 87

6 Power SupplyThe PRIMECENTER Rack offers various possibilities for supplying power to the integrated rack components. The connection conditions described in the relevant manuals for the integrated rack components should be complied with in all cases.

The power supply to the PRIMECENTER Rack can be included optionally as part of a redundancy concept. In the simplest scenario, redundancy is achieved with the 3-phase mains connection by distributing redundant power supplies to the phases. Ever higher redundancy is achieved by duplicating the current distribution components so that the PRIMECENTER Rack can be connected to two independent inhouse power distribution networks via a dual power feed. This option is offered both in 1-phase and 3-phase socket strips.

V CAUTION!

Remember in configurations with several mains supply cables that all cables must be disconnected so that there is no current flowing to the rack!

The power supply complies with the requirements of the EN60950 regulations. This allows a PRIMECENTER Rack to be connected with a flexible 3 or 5-wire cable to a rated current of up to 16 A per phase. The respective line cross-sections should be noted.

Because of the high number of current distribution components within the PRIMECENTER Rack, the configuration can carry leakage currents > 3.5 mA. For this reason, the PRIMECENTER Rack may generally only be connected to internal power distribution networks via rigid connections or via industrial connections in accordance with IEC309.

Note the requirements outlined in the data sheets when installing the power distributor.

Page 88: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

88 A3C40110888A

Connecting to the Mains Power Supply

6.1 Connecting to the Mains Using a 1-phase Socket Strip

A socket strip with ten insulated sockets and a connection cable is available for a 1-phase AC mains power connection. The cable should not be routed over sharp edges or pinched.

Power is supplied to the individual rack components via the socket strip. The load should be distributed equally to the two 5-pin elements of the 10-way socket strip.

In the case of a dual power feed to the PRIMECENTER Rack, ensure that redundant power supplies are distributed to socket strips that are disconnected from the mains.

The following socket strips are available:

● With 16 A IEC309-compliant connector

● With 32 A IEC309-compliant connector

● With 30 A Twist Lock connector, NEMA L6-30P

● With 16 A IEC320-compliant connector

● With 10 A IEC320-compliant connector

● Socket strip with three 10 A power outlets and 1.5 m connection cable and right-angle insulated plug (max. 10 A)

Page 89: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 89

Power Supply Connecting to the Mains

Figure 61: 1-phase mains connection

Ê Screw the socket strip to the right or left rear support upright of the PRIMECENTER Rack using the screw-down bracket (see also figure 63 on page 91).

Up to three socket strips can be mounted below one another on an upright.

with IEC309 connector (16A)

with Twist Lock connector

with IEC320 connector

1-phase mains connection

connection to mains via UPS

L1

UPS

with IEC309 connector (32A)

Page 90: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

90 A3C40110888A

Connecting to the Mains Power Supply

6.2 Connecting to the Mains Using a 3-phase Socket Strip

The PRIMECENTER Rack provides a 3-phase AC mains power connection and thus offers a uniform power distribution to the power distribution network.

A socket strip with 3 socket blocks (one block per phase, each with one protective contact socket and four insulated sockets ) is available (figure 62).

V CAUTION!

Make sure that the current load of the individual insulated socket blocks do not exceed 10 A.

Servers with redundant power supply units can then be connected to different phases and are thus given additional phase redundancy for high availability configurations. If only one phase fails, the systems that are connected to another phase remain operational.

Figure 62: 3-phase mains connection

3-phase mains connection

terminal strip

L1

L2

L3

Page 91: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 91

Power Supply Connecting to the Mains

Figure 63: Socket strip in rear of PRIMECENTER Rack

Ê Screw the socket strip to the right or left rear support upright of the PRIMECENTER Rack using the screw-down bracket.

6.2.1 Connection Cable

Depending on the device configuration, the socket strip can be connected to the inhouse supply network via a 5-lead power cord with a length of 7 m via a fixed connection or an IEC309-compliant connector.

A 5-pin terminal strip for connecting the individual leads (L1, L2, L3, N and PE) is available in the socket strip (see figure 64 on page 92).

V CAUTION!

The connection may only be performed by an authorized electrician approved by the local utility company. The power connection cable must be voltage free.

Page 92: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

92 A3C40110888A

Connecting to the Mains Power Supply

Figure 64: Mains power connection

Ê Route the external 5-lead connection cable into the rack (1).

Ê Connect the 5-lead connection cable to the 5-pin terminal strip (2) in the PRIMECENTER Rack.

6.2.2 3-phase Power Distribution

Power is supplied to the individual rack components within the PRIMECENTER Rack via the socket strip. If the number of sockets available on the socket strip is not enough, you can use a supplementary socket strip as an extension. (see figure 62 on page 90).

The following supplementary socket strips are available:

● Socket strip with 5 sockets (one 16 A protective contact socket and four 10 A insulated sockets) and 3 m connection cable with protective contact utility connector.

● Socket strip with 3 sockets (three 10 A protective contact sockets) and 1.5 m connection cable with insulated connector (max. 10 A).

Ê If necessary, screw additional socket strips to the (left or right) rear support upright of the PRIMECENTER Rack. Only one supplementary socket strip per phase is permitted.

Ê Connect the socket strips as shown.

Page 93: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 93

Power Supply Power Supply via UPS

6.3 Power Supply via UPS

If uninterruptible power supply (UPS) units are involved in supplying energy to the rack and its components, the connection conditions described in the relevant manuals for the integrated rack components should be complied with in all cases. There are many possible combinations:

● The rack is supplied completely via the UPS:

In this case the UPS should be connected directly to the mains. In the rack the rack components are connected directly or optionally via a socket strip to the UPS.

● The rack is partly supplied via a UPS:

This gives a choice of connecting the UPS via the socket strip in the rack or directly to the power supply network. This process also applies if a number of UPSs are used in the rack.

● High-power UPSs above 3000 VA:

UPSs above 3000 VA need their own mains connection because of the large amount of current that they draw. Both fixed connections and connections using IEC 309-complaint connectors can be used here. The technical requirements can be taken from EN60950 and from the specifications of the local utility company.

Online UPSs and line-interactive UPSs are available in different performance classes. Different UPS types are used preferentially by the various server lines for the PRIMECENTER Rack. Please refer here to the configuration information for the individual severs.

The power supply can be configured freely depending on the UPSs used. The input power connector of the respective UPS can be connected either directly to the mains or to the protective contact socket of the main socket strip in the rack by using the connection cable supplied with the respective UPS. The rack components or additional socket strips should be connected to the power outlets of the respective UPS.

Note that the increased leakage currents >3.5mA can also flow over UPS connection cables. The connection cables therefore have to be assigned uniquely to the device and the strain on the UPS relieved, either using appro-priate strain relief facilities or by routing with suitable cabling, which requires the assistance of tools to change the cabling.

Page 94: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

94 A3C40110888A

Potential Compensating System Power Supply

6.4 Connecting to the Potential Compensating System

If required by local regulations, the PRIMECENTER Rack can be connected to the indoor potential-compensating system via the grounding screw located at the rear of the rack chassis. This grounding only protects from external parasitic voltages and does not replace the protective conductor in the mains feeders.

Figure 65: Grounding screw

Page 95: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 95

7 Appendix A: StackabilityThe new PRIMECENTER Racks are available with 12, 24, 38 or 46 height units. The 12, 24 and 38 height unit versions are stackable and allow a vertical rack growth of up to 50 height units.

To mount two racks vertically, proceed as follows:

Figure 66: Removing the top cover

Ê Remove the top cover of the bottom rack by unscrewing the screws on the left and the right of the cover from inside the rack, and take the cover off.

Ê Remove the leveling feet from the rack to be stacked (the rack that is mounted on top). The rollers may remain on the rack.

Page 96: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

96 A3C40110888A

Appendix A: Stackability

Figure 67: Removing the covering panels

Ê To bolt both racks together, first remove the lower covering panel of the upper rack from inside this rack, then remove the upper covering panel from inside the lower rack.

V CAUTION!

If necessary, ask someone else for help when stacking the racks.

Page 97: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 97

Appendix A: Stackability

Ê Now put one rack on top of the other.

Figure 68: Bolting the PRIMECENTER Racks together

Ê Bolt both racks together at the four joining points in the four courners of the racks using an M8 x 70 mm screw and the appropriate nuts for each joining point.

Page 98: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

98 A3C40110888A

Appendix A: Stackability

Figure 69: Bolting the PRIMECENTER Racks together

Ê Now screw the covering panels back on.

Ê Make sure again that all screws have been fixed properly and that both racks are stable.

Page 99: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 99

8 Appendix B: AccessoriesVarious accessories are optionally available with the PRIMECENTER Rack, including:

– Door knob

– Grounding kit (see page 101)

8.1 Mounting the Optional Door Knob

You can mount a door knob instead of the lock.

Figure 70: Door knob

Replacing the Lock with a Door Knob

Proceed as follows:

Ê Remove the lock (see figure 71 on page 100).

Page 100: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

100 A3C40110888A

Mounting the Optional Door Knob Appendix B: Accessories

Figure 71: Mounting/removing the cylinder of the cylinder lock

Ê Mount the door knob (see figure 72).

Figure 72: Mounting the cylinder for the door knob

Mounted core 339-051W-2

Removal key

Mounting/removal instructions for cylinder 430-011W-1

Function key

Mounting:Insert core in the open position (rod guides retracted) as shown above.

Function:Turn 180° to the right using the function key. Lock position. Key can be withdrawn in both positions.

Removal:Bring cylinder into open position. Core can then be removed using the removal key.

Removal key

Mounting:Insert door knob in the open position (rod guides retracted) as shown above.

Function:Turn door knob 180° to the right. Lock position.

Removal:Bring cylinder into open position. Door knob can then be removed using the removal key.

Mounting/removal instructions for cylinder 430-011W-1

Door knob4003-06-1

Page 101: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 101

Appendix B: Accessories Mounting the Grounding Kit

8.2 Mounting the Grounding Kit

I To avoid ESD problems it is recommended to mount the grounding kit.

Conductive parts of the rack must be connected with each other using the grounding kit as follows:

● Right front door

● Left front door (see figure 74)

● Rear door (see figure 75)

● Cover plate (see figure 76)

● Side covers (see figure 77)

Figure 73: Grounding of right front door

Page 102: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

102 A3C40110888A

Mounting the Grounding Kit Appendix B: Accessories

Figure 74: Grounding of left front door

Figure 75: Grounding of rear door

Page 103: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 103

Appendix B: Accessories Mounting the Grounding Kit

Figure 76: Grounding of cover plate

Figure 77: Grounding of side covers

Figure 78: Mounting a tooth washer

I If a cable lug makes contact with a varnished surface, a tooth washer must be used between the cable lug and the surface (see photo).

Page 104: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE
Page 105: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 105

Related PublicationsThe manual for the PRIMECENTER Rack is also available as a PDF file on the DVD supplied with every PRIMERGY server system.

The PDF files for some manuals are also available free of charge for downloading from the Internet. You can find the start page for the online documentation available on the Internet at the following URL:http://manuals.ts.fujitsu.com

Page 106: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE
Page 107: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

A3C40110888A 107

Index

19-inch areamounting horizontally 51

19-inch rack technology 7

Aanti-tilt plate 25area required by the rack 36articulated cable guide 18, 63

mounting 76routing cables 80

assembly aid 52

Ccable clip 63, 65cable guide

with cable clips 18cable guide with cable clips

mounting 77routing cables 84

cable management 18, 75components 75mounting 75

cablesconnecting 78disconnecting 79routing 79, 84, 85

cage nuts 54configuration 52connecting

cables 78consumables 22conversion

in the rear 19-inch area 68

Ddelivery unit 25direct connection 18

routing cables 85disconnecting

cables 79

disposal 23door knob, mounting 99

Eenvironmental protection 22ergonomics 12, 13expansion area 66

mounting vertically 51

Ggrounding kit

mounting 101guarantee 12, 13

Hheight unit (HU) 53hot-plug disks 20hot-replace 18HU (height unit) 53

Iimportant notes 17installation

planning 21preparing 25

installation concept 18installation instructions

cage nuts 54installation procedure 26

Kkeys 25, 27

Llabels

on plastic housing parts 22load capacity 63

Mmains

devices 78, 79mounting

Page 108: PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000 ...manuals.ts.fujitsu.com/file/3574/rack-primecenter-en.pdf · PRIMECENTER Rack System for PRIMERGY, PRIMEPOWER, BS2000, STORAGE

108 A3C40110888A

Index

articulated cable guide 76cable guide with cable clips 77door knob 99grounding kit 101in the expansion area 66in the rear 19-inch area 67, 72tooth washer 103

mounting area 5119-inch front area 51expansion area 51

Nnotational conventions 13notes on safety 19

Ppackaging 22palette 25philosophy 13plastic housing parts

labels 22power supply 87power supply module 20PRIMECENTER Rack 7

Rrack

19-inch technology 7, 17opening 27, 35philosophy 17unpacking 25

rack components 51mounting 51

rack transport, tipped 17recycling 23replacing lock 99routing

cables 79, 80rules for mounting components 21

Ssecurity 12, 13sliding rails 18, 63stackability 95

support bracket 63mounting 64

System Architect 52configuration example 52

Ttake-back

devices and consumables 23technical data 14telescopic rails 18, 63tooth washer

mounting 103transport concept 17

Uunpacking

from beginning of 2008 34untile end of 2007 29

utility company 12, 91

Vventilation concept 19