Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22
Transcript
Page 1: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

Prince William CountyTypical Residential Deck Design

Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22

AutoCAD SHX Text
CONTENTS
AutoCAD SHX Text
General Notes........................................................2Ledger Fasteners...................................................11 2Ledger Fasteners...................................................11 Ledger Fasteners...................................................11 11 Deck Framing Plan................................................3Rim Joist Attachment............................................11 3Rim Joist Attachment............................................11 Rim Joist Attachment............................................11 11 Cross Section of Deck Connected to House.......4Built-Up Beam......................................................11 4Built-Up Beam......................................................11 Built-Up Beam......................................................11 11 Free Standing Deck Framing Plan........................5Stairway Requirements..........................................12 5Stairway Requirements..........................................12 Stairway Requirements..........................................12 12 Cross Section of Free Standing Deck..................6Tread, Riser, and Stringer Detail.........................12 6Tread, Riser, and Stringer Detail.........................12 Tread, Riser, and Stringer Detail.........................12 12 Lateral Support of Free Standing Deck...............7Stairway Landing Details.......................................13 7Stairway Landing Details.......................................13 Stairway Landing Details.......................................13 13 Framing Plan at Chimney or Bay Window...........8Stairway Connection to Deck................................14 8Stairway Connection to Deck................................14 Stairway Connection to Deck................................14 14 Post-to-Beam Connection....................................8Handrail Details.....................................................14 8Handrail Details.....................................................14 Handrail Details.....................................................14 14 Joist-to-Beam Connection...................................8Do Not Do's...........................................................15 8Do Not Do's...........................................................15 Do Not Do's...........................................................15 Footing Details.......................................................9Stairway Illumination..............................................16 9Stairway Illumination..............................................16 Stairway Illumination..............................................16 16 Guardrail Post Connection.....................................9Clearances.............................................................16 9Clearances.............................................................16 Clearances.............................................................16 16 Ledger Board Connection......................................10Inspection and Scheduling....................................1710Inspection and Scheduling....................................17Inspection and Scheduling....................................1717
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
Department of Development Services Building Development Division 5 County Complex Court Prince William, VA 22192-9201 703-792-6930
AutoCAD SHX Text
SHEET 1 OF 17
Page 2: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

THINGS TO BRING FOR PERMIT

Important!

NOTES ON DESIGN

·

··

·

·

· Setback and Permit Standards for At-Grade Structures

·

·

·

·

·

·

·

··

GENERAL NOTES

AutoCAD SHX Text
Zoning Permit. You must bring a copy of your house location plan that shows the proposed location of the deck, drawn to the same scale as the plan. Show the side yard and rear yard distances (setbacks from property lines) on the plan. No changes shall be made to approved plans without prior approval from the Building Construction Review Branch. Approved deck plans shall not be used for supporting hot-tub installation, without re-submission for review. All metal connections, bolts, joist hangers, etc. shall be galvanized or corrosive resistant. All lumber shall be pressure treated Southern Pine, grade #2 or better. Building permit is not required if all portions of the top of the deck's flooring is within 16.5 inches from all portions of the top of the deck's flooring is within 16.5 inches from portions of the top of the deck's flooring is within 16.5 inches from the finished grade unless it carries structural load, e.g. hot-tub. All decks require zoning permit. Provisions in the Prince William County Zoning Ordinance for at-grade decks and patios differ from those in the Building Code. In the Zoning Ordinance, the standards are as follows: "Patios, decks, walkways, steps and driveways constructed no higher than eight (8) inches above existing grade of the contour of the land where located may encroach within any setback provided that no permanent above-grade affixed structures such as railing, planters, benches, roofs or other appurtenances are installed." Column spacing and joist spans shown are maximum. Smaller decks may be constructed utilizing the same structural members. The typical residential deck design shall be strictly adhered to. All deviations from these drawings shall require an independent set of design documents to be prepared and submitted to the Building Construction Plans Review Branch for review. If a proposed deck does not conform to these typical design details, a custom design can be submitted to the Building Construction Review Branch. Submit two (2) copies of the design, including framing plans, cross sections, and stringer details for review. Material requirements are as follows: Please go to www.treatedwood.com/products/preserve/ for a list of hardware manufacturers that recommend hardware for use with Alkaline Copper Quaternary (ACQ) treated wood. Decking composed of foreign lumber, plastic or manufactured materials may be substituted only when the product has an approved evaluation report from ICC-ES or from an accredited testing laboratory.
AutoCAD SHX Text
Component Nails, screws, lag screws, and bolts shall be Hardware (joist hangers, anchors, clips and angles) shall be Flashing shall be
AutoCAD SHX Text
Requirement hot-dipped zinc galvanized, stainless steel, or approved for use with ACQ, CA, or CA-B hot-dipped galvanized with a 1.85 oz/sf of zinc (G-185 coating) or Stainless Steel (type 304 or better) Examples "Zmax" from Simpson Strong-Tie "Triple Zinc" from USP copper, stainless steel, silicon, bronze, or UV-resistant plastic , and hot-dipped galvanized steel with a G30 zinc coating
AutoCAD SHX Text
Notes: In all cases, electroplated galvanizing is NOT acceptable. ICC Evaluation Report and testing data are required to substantiate decay resistance of plastic.
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
SHEET 2 OF 17
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 3: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

FIG

UR

E 1: D

EC

K F

RA

MIN

G P

LA

N

AutoCAD SHX Text
GP
AutoCAD SHX Text
TP
AutoCAD SHX Text
TP
AutoCAD SHX Text
TP
AutoCAD SHX Text
GP
AutoCAD SHX Text
GP
AutoCAD SHX Text
GP
AutoCAD SHX Text
GP
AutoCAD SHX Text
Joist: 2x8 @ 16" OC Typical
AutoCAD SHX Text
(2)-2x10 Beam: Figure 16, sheet 11 Typical
AutoCAD SHX Text
TP
AutoCAD SHX Text
Treated Post 6x6
AutoCAD SHX Text
Guardrail Post 4x4 (treated)
AutoCAD SHX Text
Exterior wall of house
AutoCAD SHX Text
Guardrail Post Connection: Figure 10, sheet 9
AutoCAD SHX Text
6x6 Post: Figure 7, sheet 8 Typical
AutoCAD SHX Text
Ledger Connection: Figure 11 or 12, sheet 10 AND Figure 14, sheet 11
AutoCAD SHX Text
Chimney or Bay Window: Figure 6, sheet 8
AutoCAD SHX Text
Intermediate Landing: Figure 19 and 20, sheet 13
AutoCAD SHX Text
Handrail: Figure 22, sheet 14
AutoCAD SHX Text
Rim Joist: Figure 15, sheet 11 Typical
AutoCAD SHX Text
4x4 Rail Post
AutoCAD SHX Text
Decking: Table 1 sheet 8
AutoCAD SHX Text
Stairway: Figure 17, sheet 12
AutoCAD SHX Text
Ground Landing: Figure 20, sheet 13
AutoCAD SHX Text
Double Joist Attachment: Figure 13, Sheet 10
AutoCAD SHX Text
Double Joist: (2)-2x8 Typical
AutoCAD SHX Text
Exterior house condition shall not contain any of the following: prefabricated floor joist system (without at least 1 " solid band board), brick veneer, stone or cultured stone on 14" solid band board), brick veneer, stone or cultured stone on the wall, or cantilever. (refer to sheet 5 for free standing deck)
AutoCAD SHX Text
Max Of Span 14 Of Span For Joist & Beam
AutoCAD SHX Text
SHEET 3 OF 17
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 4: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

FIGURE 2A: CROSS SECTION OF DECK CONNECTED TO HOUSE

FIGURE 2B: CROSS SECTION OF DECK CONNECTED TO HOUSE

AutoCAD SHX Text
2x2 Min. Pickets shall be attached to side rails by one of the following methods: A. (1)-#8 screw top and bottom B. (2)-8d spiral nails top and bottom
AutoCAD SHX Text
(2)-2x10 Beam: Figure 16, sheet 11
AutoCAD SHX Text
Openings shall not allow the passage of a 4" diameter sphere
AutoCAD SHX Text
6x6 Post
AutoCAD SHX Text
Footing: Figure 9, sheet 9
AutoCAD SHX Text
Side Rail 2x4 Min.
AutoCAD SHX Text
Top Rail 2x4 Min. or 54 board
AutoCAD SHX Text
finished grade
AutoCAD SHX Text
rim joist
AutoCAD SHX Text
Ledger Connection: Figure 11 or 12, sheet 10 AND Figure 14, sheet 11
AutoCAD SHX Text
GP
AutoCAD SHX Text
TP
AutoCAD SHX Text
4x4 post shall NOT be notched
AutoCAD SHX Text
finished grade
AutoCAD SHX Text
Joist-To-Beam: Figure 8, sheet 8
AutoCAD SHX Text
Post-To-Beam: Figure 7, sheet 8
AutoCAD SHX Text
Stairway Requirements: Figure 17, sheet 12
AutoCAD SHX Text
Stringer Detail: Figure 18, sheet 12
AutoCAD SHX Text
Stairway Connection: Figure 21, sheet 14
AutoCAD SHX Text
Ledger Connection: Figure 11 or 12, sheet 10 AND Figure 14, sheet 11
AutoCAD SHX Text
Guardrail Post Connection: Figure 10, sheet 9
AutoCAD SHX Text
Intermediate Landing: Figure 19 and 20, sheet 13
AutoCAD SHX Text
SHEET 4 OF 17
AutoCAD SHX Text
(refer to sheet 6 for free standing deck)
AutoCAD SHX Text
(refer to sheet 6 for free standing deck)
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 5: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

FIG

UR

E 3

: F

RE

E S

TA

ND

IN

G D

EC

K F

RA

MIN

G P

LA

N

AutoCAD SHX Text
GP
AutoCAD SHX Text
TP
AutoCAD SHX Text
TP
AutoCAD SHX Text
TP
AutoCAD SHX Text
GP
AutoCAD SHX Text
GP
AutoCAD SHX Text
GP
AutoCAD SHX Text
GP
AutoCAD SHX Text
Joist: 2x8 @ 16" OC Typical
AutoCAD SHX Text
(2)-2x10 Beam: Figure 16, sheet 11 Typical
AutoCAD SHX Text
TP
AutoCAD SHX Text
Treated Post 6x6
AutoCAD SHX Text
Guardrail Post 4x4 (treated)
AutoCAD SHX Text
Guardrail Post Connection: Figure 10, sheet 9
AutoCAD SHX Text
6x6 Post: Figure 7, sheet 8 Typical
AutoCAD SHX Text
Rim Joist: Figure 15, sheet 11 Typical
AutoCAD SHX Text
4x4 Rail Post
AutoCAD SHX Text
Decking: Table 1 sheet 8
AutoCAD SHX Text
Handrail: Figure 22, sheet 14
AutoCAD SHX Text
Stairway: Figure 17, sheet 12
AutoCAD SHX Text
Intermediate Landing: Figure 19 and 20, sheet 13
AutoCAD SHX Text
Ground Landing: Figure 20, sheet 13
AutoCAD SHX Text
(2)-2x10 Beam: Figure 16, sheet 11 Typical
AutoCAD SHX Text
Deck shall be free standing when adjacent house condition contains any of the following: prefabricated floor joist system (without at least 1 " solid band board), brick veneer, stone or cultured stone on the 14" solid band board), brick veneer, stone or cultured stone on the wall, or cantilever.
AutoCAD SHX Text
Required Bridging at each guardrail post
AutoCAD SHX Text
Max Of Span 14 Of Span For Joist & Beam
AutoCAD SHX Text
Max Of Span 14 Of Span For Joist & Beam
AutoCAD SHX Text
SHEET 5 OF 17
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 6: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

FIGURE 4A: CROSS SECTION OF FREE STANDING DECK

FIGURE 4B: CROSS SECTION OF FREE STANDING DECK

AutoCAD SHX Text
finished grade
AutoCAD SHX Text
Joist-To-Beam: Figure 8, sheet 8
AutoCAD SHX Text
Post-To-Beam: Figure 7, sheet 8
AutoCAD SHX Text
Stringer Detail: Figure 18, sheet 12
AutoCAD SHX Text
Stairway Connection: Figure 21, sheet 14
AutoCAD SHX Text
Guardrail Post Connection: Figure 10, sheet 9
AutoCAD SHX Text
Stairway Requirements: Figure 17, sheet 12
AutoCAD SHX Text
Intermediate Landing: Figure 19 and 20, sheet 13
AutoCAD SHX Text
6x6 Post
AutoCAD SHX Text
Footing: Figure 9, sheet 9
AutoCAD SHX Text
finished grade
AutoCAD SHX Text
rim joist
AutoCAD SHX Text
GP
AutoCAD SHX Text
TP
AutoCAD SHX Text
2x2 Min. Pickets shall be attached to rails by one of the following methods: A. (1)-#8 screw top and bottom B. (2)-8d spiral nails top and bottom
AutoCAD SHX Text
Side Rail 2x4 Min.
AutoCAD SHX Text
4x4 post shall NOT be notched
AutoCAD SHX Text
(2)-2x10 Beam: Figure 16, sheet 11
AutoCAD SHX Text
Openings shall not allow the passage of a 4" diameter sphere
AutoCAD SHX Text
Bracing: Figure 5, sheet 7
AutoCAD SHX Text
Top Rail 2x6 or board54 board
AutoCAD SHX Text
Fixed seating adjacent to or within 36 inches of the edge of any open side of the deck shall have guard rails not less than 36 inches high measured vertically above the seat of the fixed seating.
AutoCAD SHX Text
GUARD REQUIREMENTS FOR FIX SEATING ON DECKS
AutoCAD SHX Text
SHEET 6 OF 17
AutoCAD SHX Text
Deck shall not be anchored to face of house
AutoCAD SHX Text
Deck shall not be anchored to face of house
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 7: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

FIGURE 5A: LATERAL SUPPORT OF FREE STANDING DECK

FIGURE 5B: LATERAL SUPPORT FOR ALL DECKS

AutoCAD SHX Text
Joist
AutoCAD SHX Text
(2)-2x10 Beam
AutoCAD SHX Text
Rim Joist
AutoCAD SHX Text
4x4 Rail Post
AutoCAD SHX Text
2x6 Diagonal Bracing (or 2x4 minimum for bracing parallel to beam)
AutoCAD SHX Text
6x6 Post
AutoCAD SHX Text
Decking
AutoCAD SHX Text
(when required)
AutoCAD SHX Text
Required bridging at each guardrail post
AutoCAD SHX Text
Beam
AutoCAD SHX Text
use 2x8 blocking when joist and post do not align
AutoCAD SHX Text
(1)- " dia. 12" dia. thru-bolt with washers, Typical
AutoCAD SHX Text
Bracing Parallel to Beam
AutoCAD SHX Text
Bracing Perpendicular to Beam
AutoCAD SHX Text
when joist and post are aligned
AutoCAD SHX Text
2x4, Typical
AutoCAD SHX Text
finished grade
AutoCAD SHX Text
Beam
AutoCAD SHX Text
SHEET 7 OF 17
AutoCAD SHX Text
Deck bracing shall be provided when deck height is greater than 8'-0" above grade.
AutoCAD SHX Text
Knee bracing shall be provided when deck height is greater than 8'-0" above grade.
AutoCAD SHX Text
Free standing decks shall be braced with 2x6 diagonal bracing corner to corner at the underside of floor joists using an 8d nail at each joist, or by installing 2x6 decking diagonally.
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 8: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

®

FIGURE 6: FRAMING PLAN AT CHIMNEY OR BAY WINDOW

FIGURE 7: POST-TO-BEAM CONNECTION

FIGURE 8: JOIST-TO-BEAM CONNECTIONS

AutoCAD SHX Text
12" diameter thru-bolt and washers, Typical
AutoCAD SHX Text
notch post to match beam
AutoCAD SHX Text
(2)-2x10 Beam
AutoCAD SHX Text
6x6 Post
AutoCAD SHX Text
OPTION 1
AutoCAD SHX Text
(3)-8d toe nailed (2 on one side, 1 on the other)
AutoCAD SHX Text
hurricane tie or similar
AutoCAD SHX Text
joist hanger
AutoCAD SHX Text
OPTION 2
AutoCAD SHX Text
OPTION 3
AutoCAD SHX Text
top of joist and beam must be at the same level
AutoCAD SHX Text
(2)-2x10 beam
AutoCAD SHX Text
Chimney or Bay Window
AutoCAD SHX Text
2" Min.
AutoCAD SHX Text
Decking
AutoCAD SHX Text
Ledger Board
AutoCAD SHX Text
Deck Joists
AutoCAD SHX Text
Double Joists and Double Headers
AutoCAD SHX Text
Joist hangers required at intersections
AutoCAD SHX Text
TABLE 1: 507.4
AutoCAD SHX Text
Joist Spacing
AutoCAD SHX Text
Thickness of Diagonal Decking
AutoCAD SHX Text
Composite Material
AutoCAD SHX Text
2x
AutoCAD SHX Text
54x
AutoCAD SHX Text
16" OC
AutoCAD SHX Text
YES
AutoCAD SHX Text
NO
AutoCAD SHX Text
NO
AutoCAD SHX Text
12" OC
AutoCAD SHX Text
YES
AutoCAD SHX Text
YES
AutoCAD SHX Text
YES
AutoCAD SHX Text
Treated Southern Yellow Pine #2 or better Trex or similar, must be rated to support 40 PSF or 200 pound concentrated load
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
Exterior house condition shall not contain any of the following: prefabricated floor joist system (without at least 1 " solid band board), brick veneer, stone or cultured stone on the wall, or cantilever. 14" solid band board), brick veneer, stone or cultured stone on the wall, or cantilever. (refer to sheet 5 for free standing deck)
AutoCAD SHX Text
SHEET 8 OF 17
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 9: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

·

·

·

FIGURE 9: FOOTING DETAILS

FIGURE 10: GUARDRAIL POST CONNECTION DETAIL

AutoCAD SHX Text
frost depth
AutoCAD SHX Text
undisturbed soil
AutoCAD SHX Text
finished grade
AutoCAD SHX Text
pre-manufactured cast-in-place post anchor
AutoCAD SHX Text
post anchor
AutoCAD SHX Text
post anchor
AutoCAD SHX Text
provide seal to prevent seapage of water
AutoCAD SHX Text
Option 1
AutoCAD SHX Text
Option 2
AutoCAD SHX Text
Option 3
AutoCAD SHX Text
guardrail post
AutoCAD SHX Text
12" dia. thru-bolt and washers, Typical
AutoCAD SHX Text
2x8 blocking End nail w/10d nails top and bottom, each side (if hold-down is not used)
AutoCAD SHX Text
outside joist
AutoCAD SHX Text
hold-down anchor (optional) w/ " dia. 12" dia. thru-bolts and washers
AutoCAD SHX Text
outside joist
AutoCAD SHX Text
guard post
AutoCAD SHX Text
12" dia. thru-bolt and washers, Typical
AutoCAD SHX Text
rim joist
AutoCAD SHX Text
hold-down anchor (optional) w/ " dia. 12" dia. thru-bolts and washers
AutoCAD SHX Text
joist
AutoCAD SHX Text
joist
AutoCAD SHX Text
rim joist
AutoCAD SHX Text
hold-down anchor (optional)
AutoCAD SHX Text
hold-down anchor (optional)
AutoCAD SHX Text
rim joist
AutoCAD SHX Text
joist
AutoCAD SHX Text
Guardrail Post to Outside Joist
AutoCAD SHX Text
Guardrail Post to Rim Joist
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
PLAN
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
PLAN (at joist)
AutoCAD SHX Text
PLAN (between joists)
AutoCAD SHX Text
attach per rim joist details (if hold-down is not used)
AutoCAD SHX Text
All footings shall bear on solid ground; bearing conditions shall be verified in the field by an approved Third Party Inspector or by County Inspectors prior to placement of concrete. The bottom of all footings closer than 5'-0" to the exterior wall of the existing house must be extended down to undisturbed soil. Pre-manufactured post anchors shall be galvanized with 1.85 oz/sf of zinc (G-185 coating) or shall be stainless steel. All concrete must be properly mixed per specifications.
AutoCAD SHX Text
SHEET 9 OF 17
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 10: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

FIGURE 11: LEDGER BOARD CONNECTION TO DIMENSIONAL BAND BOARD

FIGURE 12: LEDGER BOARD CONNECTION TO FOUNDATION WALL FIGURE 13: DOUBLE JOIST ATTACHMENT

TO LEDGER BOARD

AutoCAD SHX Text
Exterior wood framed house wall
AutoCAD SHX Text
Flashing to protect ledger board
AutoCAD SHX Text
Decking
AutoCAD SHX Text
2x8 Deck Joist @ 16" OC, Typical
AutoCAD SHX Text
If concrete wall, use " diameter expansion 12" diameter expansion anchors, embeded 3" into wall. If hollow masonry wall, use " diameter epoxy 12" diameter epoxy anchors or equal, embedded 3 " into wall.12" into wall.
AutoCAD SHX Text
2x8 Ledger board shall be pressure treated No. 2 Southern Pine or better
AutoCAD SHX Text
Foundation Wall
AutoCAD SHX Text
Floor Joist
AutoCAD SHX Text
Existing band board minimum 1 " width14" width
AutoCAD SHX Text
Gap between ledger board and face of house band joist shall not exceed ".12".
AutoCAD SHX Text
Decking
AutoCAD SHX Text
Flashing 1. Flashing is requred at any ledger board connection to a wall or floor assembly of frame construction. 2. Flashing shall be corrosion resistant. 3. Install flashing per manufacturer's recommendations.
AutoCAD SHX Text
2x8 Deck Joist @ 16" OC, Typical
AutoCAD SHX Text
2x8 ledger board shall be pressure treated No. 2 Southern Pine or better
AutoCAD SHX Text
12" diameter bolts and washers, OR " 12" diameter lag screws where the tip of the lag screws shall fully extend beyond the inside face of the band joist.
AutoCAD SHX Text
Floor Joist
AutoCAD SHX Text
Foundation Wall
AutoCAD SHX Text
Existing band board minimum 1 " width14" width
AutoCAD SHX Text
When using lag screws, gap between ledger board and face of house band joist shall not exceed ".12".
AutoCAD SHX Text
(2)- " dia. lag screws, 12" dia. lag screws, bolts, or anchors
AutoCAD SHX Text
Double joists hanger
AutoCAD SHX Text
Ledger board
AutoCAD SHX Text
SHEET 10 OF 17
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 11: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

FIGURE 14: FASTENER SPACING AND CLEARANCES AT LEDGER BOARD

FIGURE 16: BUILT-UP BEAM DETAIL

FIGURE 15: RIM JOIST ATTACHMENT DETAIL

AutoCAD SHX Text
TABLE 2: FASTENER SPACING (S) FOR A RESIDENTIAL SOUTHERN PINE DECK LEDGER AND A 2-INCH NOMINAL SOLID-SAWN BAND JOIST [50 PSF TOTAL LOAD]
AutoCAD SHX Text
Joist Span (ft)
AutoCAD SHX Text
6' and less
AutoCAD SHX Text
6'-1" to 8'
AutoCAD SHX Text
8'-1" to 10'
AutoCAD SHX Text
10'-1" to 12'
AutoCAD SHX Text
On-Center Spacing of Fasteners
AutoCAD SHX Text
12"x4" Lag Screw
AutoCAD SHX Text
30
AutoCAD SHX Text
23
AutoCAD SHX Text
18
AutoCAD SHX Text
15
AutoCAD SHX Text
12" Bolt with washers
AutoCAD SHX Text
36
AutoCAD SHX Text
36
AutoCAD SHX Text
34
AutoCAD SHX Text
29
AutoCAD SHX Text
The maximum gap between the face of the ledger board and face of the house band joist shall be ". 12". The tip of the lag screw shall be fully extended beyond the inside face of the band joist. Ledgers shall be flashed to prevent water from contacting the house band joist. Lag screws and bolts shall be staggered as shown. Deck ledger shall be 2x8 No. 2 Southern Pine (minimum), or other approved method and material as established by standard engineering practice.
AutoCAD SHX Text
a
AutoCAD SHX Text
b
AutoCAD SHX Text
c
AutoCAD SHX Text
d
AutoCAD SHX Text
e
AutoCAD SHX Text
a,b
AutoCAD SHX Text
c
AutoCAD SHX Text
d,e
AutoCAD SHX Text
rim joist
AutoCAD SHX Text
attach rim joist to end of each joist with (5)-#10x3" Min. wood screws
AutoCAD SHX Text
joists
AutoCAD SHX Text
10d nails or #10 wood screws, staggered in 2 rows
AutoCAD SHX Text
2 nails or screws, each end
AutoCAD SHX Text
lag screws, bolts, or anchors, with washers, Typical
AutoCAD SHX Text
(4)- " lag screws, bolts, or anchors with washers at each end12" lag screws, bolts, or anchors with washers at each end
AutoCAD SHX Text
2"
AutoCAD SHX Text
2"
AutoCAD SHX Text
Provide additional lag screws, bolts, or anchors with washers on each side of exterior terminations that penetrate the band board such as dryer vent caps and fresh air intakes.
AutoCAD SHX Text
Exterior penetration (typical)
AutoCAD SHX Text
SHEET 11 OF 17
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 12: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

FIGURE 17: STAIRWAY REQUIREMENTS

FIGURE 18: TREAD, RISER, AND STRINGER DETAIL

AutoCAD SHX Text
34"-1 " nosing which shall 14" nosing which shall not deviate from one another by more than "38"
AutoCAD SHX Text
riser heights shall not deviate from one another by more than "38"
AutoCAD SHX Text
treads: 2x material
AutoCAD SHX Text
risers: 1x material, Min.
AutoCAD SHX Text
risers may be open, but shall not allow the passage of a 4" diameter sphere
AutoCAD SHX Text
stringer: cut 2x12
AutoCAD SHX Text
tread depths shall not deviate from one another by more than "38"
AutoCAD SHX Text
stringer: solid 2x12
AutoCAD SHX Text
tread ledger: 2x4 attached to stringer on each side with (4)-10d nails or (4)-#8 wood screws
AutoCAD SHX Text
risers may be open, but shall not allow the passage of a 4" diameter sphere
AutoCAD SHX Text
grade
AutoCAD SHX Text
2x12 stair stringer
AutoCAD SHX Text
4x4 post
AutoCAD SHX Text
12" diameter thru-bolt and washers, Typical
AutoCAD SHX Text
stair guardrail height measured from nosing of step
AutoCAD SHX Text
triangular opening shall not permit the passage of a 6" dia. sphere
AutoCAD SHX Text
handrail shall return to post at each end
AutoCAD SHX Text
frost depth
AutoCAD SHX Text
10"x10"x8" thick stair footing
AutoCAD SHX Text
Opening shall not permit the passage of a 4 " diameter 38" diameter sphere
AutoCAD SHX Text
4x4 post
AutoCAD SHX Text
2x12 stringer @ 24" OC Max.
AutoCAD SHX Text
SHEET 12 OF 17
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 13: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

FIGURE 19: INTERMEDIATE STAIRWAY LANDING FRAMING DETAILS

FIGURE 20: STAIRWAY LANDING DIMENSION DETAILS

AutoCAD SHX Text
Framing Plan
AutoCAD SHX Text
upper stringer
AutoCAD SHX Text
lower stringer: bears on ground landing
AutoCAD SHX Text
2x8 joist @ 16" OC, Max.
AutoCAD SHX Text
rim joist
AutoCAD SHX Text
guardrail post
AutoCAD SHX Text
double joist
AutoCAD SHX Text
joist secured with joist hanger
AutoCAD SHX Text
down
AutoCAD SHX Text
down
AutoCAD SHX Text
rim joist and outside joist secured with (2)- " dia. thru-bolts 12" dia. thru-bolts and washers, Typical
AutoCAD SHX Text
stairway
AutoCAD SHX Text
stairway landing
AutoCAD SHX Text
direction of travel
AutoCAD SHX Text
upper stairway: connected to deck (Figure 21, sheet 14)
AutoCAD SHX Text
guardrail post
AutoCAD SHX Text
landing outside joist
AutoCAD SHX Text
12" diameter thru-bolt and washers, Typical
AutoCAD SHX Text
landing decking
AutoCAD SHX Text
cut stringer to bear on double rim joist and landing decking, secure to post with 12" dia. thru-bolt and washers
AutoCAD SHX Text
lower stringer
AutoCAD SHX Text
Framing Cross Section
AutoCAD SHX Text
landing decking
AutoCAD SHX Text
lower stairway
AutoCAD SHX Text
upper stairway
AutoCAD SHX Text
guardrail post
AutoCAD SHX Text
12" dia. thru- bolt and washers, Typical
AutoCAD SHX Text
landing joist
AutoCAD SHX Text
Framing Cross Section
AutoCAD SHX Text
SHEET 13 OF 17
AutoCAD SHX Text
Dimensions shown are for both intermediate, and ground level landings.
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 14: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

FIGURE 21: STAIRWAY CONNECTION TO DECK DETAILS

FIGURE 22: HANDRAIL DETAILS

AutoCAD SHX Text
4x4 guardrail post
AutoCAD SHX Text
rim joist or outside joist
AutoCAD SHX Text
stringer
AutoCAD SHX Text
(2)- " diameter 12" diameter thru-bolts and washers each way, Typical
AutoCAD SHX Text
sloped joist hanger
AutoCAD SHX Text
stringer
AutoCAD SHX Text
rim joist or outside joist
AutoCAD SHX Text
Option 1: Stringer Connection with Thru-Bolts
AutoCAD SHX Text
Option 2: Stringer Connection with Joist Hanger
AutoCAD SHX Text
riser heights shall not deviate from one another by more than "38"
AutoCAD SHX Text
tread depths shall not deviate from one another by more than "38"
AutoCAD SHX Text
Type I, Option 1 For circular handrails only
AutoCAD SHX Text
1 "-2" outside 14"-2" outside diameter
AutoCAD SHX Text
Type I, Option 2 Non-circular handrails must have a perimeter of 4" min. and 6 " max. with a 14" max. with a maximum cross-section dimension of 2 " 14"
AutoCAD SHX Text
Guardrail Post
AutoCAD SHX Text
1 "x1 " spacer 12"x1 " spacer 12" spacer at 24" OC, Max.
AutoCAD SHX Text
handrail with perimeter of 4"-6 "14"
AutoCAD SHX Text
1 "x1 " spacer 12"x1 " spacer 12" spacer at 24" OC, Max.
AutoCAD SHX Text
handrail with perimeter greater than 6 "14"
AutoCAD SHX Text
Type II, Option 1 Handrails with a perimeter greater than 6 " shall provide 14" shall provide a graspable finger recess area on both sides of the profile
AutoCAD SHX Text
finger recess detail
AutoCAD SHX Text
(2)-8d nails, Typical
AutoCAD SHX Text
Side Rail
AutoCAD SHX Text
Corrosion-resistant handrail bracket 4'-0" OC Max.
AutoCAD SHX Text
SHEET 14 OF 17
AutoCAD SHX Text
Handrails should be continuous from top riser to bottom riser.
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 15: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

DO NOT DO'S

AutoCAD SHX Text
SHEET 15 OF 17
AutoCAD SHX Text
Prohibited Post-to-Beam Connection
AutoCAD SHX Text
Prohibited Ledger Attachment: to open web trusses
AutoCAD SHX Text
Prohibited Ledger Attachment: to or thru brick veneer
AutoCAD SHX Text
Prohibited Ledger Attachment: to house overhang
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 16: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

” ”

FIGURE 23: CLEARANCE FROM MECHANICAL AND ELECTRICAL INSTALLATION

·

·

·

·

AutoCAD SHX Text
STAIRWAY ILLUMINATION FOR DECKS
AutoCAD SHX Text
The International Residential code (IRC) establishes the requirements for stairway illumination. This section
AutoCAD SHX Text
includes stairways associated with decks. The following are a few of the ways to comply with the stairway
AutoCAD SHX Text
illumination requirements:
AutoCAD SHX Text
Install an exterior light fixture within 5 feet of horizontal distance from the top landing of the stairway.
AutoCAD SHX Text
The light fixture must be positioned to illuminate both the top landing and the stairway.
AutoCAD SHX Text
Install an exterior 150 watt flood light fixture within 30 feet of horizontal distance from the top landing
AutoCAD SHX Text
of the stairway. The light fixture must be positioned to illuminate both the top landing and the stairway.
AutoCAD SHX Text
Install low voltage light fixtures that are approved for exterior use. A low voltage fixture must be
AutoCAD SHX Text
installed at each step. Also, one fixture must be installed on the walkway within 3 feet of the bottom
AutoCAD SHX Text
step. Any wiring must be installed and secured in a safe manner. The low voltage lights may be
AutoCAD SHX Text
plugged into an exterior GFI electrical outlet with an In-Use Weatherproof Cover (NEMA 3R Rated) or hard
AutoCAD SHX Text
wired into the electrical panel box in the house.
AutoCAD SHX Text
Other methods of complying with the illumination requirements, including justification and analysis shall be
AutoCAD SHX Text
submitted to the Building Construction Review Branch for approval prior to installation.
AutoCAD SHX Text
An electrical permit and inspection is required for the installation of the required illumination of the stairway.
AutoCAD SHX Text
During the final inspection of the deck, the inspector will verify that the required stairway illumination has been
AutoCAD SHX Text
provided.
AutoCAD SHX Text
GLAZING ADJACENT TO STAIRWAYS
AutoCAD SHX Text
Glazing adjacent to the landing at the bottom of a stairway where the glazing is less than 36
AutoCAD SHX Text
above the landing and
AutoCAD SHX Text
within 60
AutoCAD SHX Text
horizontally and glazing where the bottom edge of the glazing is less than 36
AutoCAD SHX Text
above the plane of the adjacent
AutoCAD SHX Text
walking surface and within 36
AutoCAD SHX Text
horizontally for stairways, landings between flights of stairs and ramps shall be considered
AutoCAD SHX Text
hazardous locations and shall meet safety glazing requirements of the IRC Code.
AutoCAD SHX Text
M
AutoCAD SHX Text
SHEET 16 OF 17
AutoCAD SHX Text
Contact the gas company for a courtesy inspection if: the distance from finished grade to bottom of joist is less than 5'-0", a roof will be above the deck, or the deck will have a floor covering. Normally the power company will not approve a meter location on or under a balcony, porch, carport, deck catwalk, or stairs. Contact power company for more information. Gas fireplace terminations shall be 18" from the top of the outside termination to combustible materials and overhangs or per manufacturer's specifications. Clearances for furnace and water heater (PVC) terminations shall comply with manufactures specifications.
AutoCAD SHX Text
Gas Meter
AutoCAD SHX Text
deck joist
AutoCAD SHX Text
Air Conditioning condensing unit
AutoCAD SHX Text
finished grade
AutoCAD SHX Text
Meter
AutoCAD SHX Text
Front View
AutoCAD SHX Text
Top View
AutoCAD SHX Text
Clear/Unobstructed space around meter
AutoCAD SHX Text
PRINCE WILLIAM COUNTY, VIRGINIA
AutoCAD SHX Text
TYPICAL RESIDENTIAL DECK DESIGN
Page 17: Prince William County€¦ · Prince William County Typical Residential Deck Design Based on Virginia Uniform Statewide Building Code ~ Version 2016-09-22. CONTENTS. General Notes

REQUIRED INSPECTION AND SCHEDULING

·

·

IMPORTANT PHONE NUMBERS:

Hours

OTHER NOTES:·

·

·

·

OUTDOOR RECEPTACLE REQUIREMENTS FOR DECKS

AutoCAD SHX Text
1.Before you dig, call Miss Utility at 1-800-552-7001. Before you dig, call Miss Utility at 1-800-552-7001. 2.Call for a footing inspection before placing concrete. Call for a footing inspection before placing concrete. 3.Call for a final inspection when the deck is complete. Call for a final inspection when the deck is complete. 4.If required, call for electrical permit and inspection. If required, call for electrical permit and inspection. 5.If required, call for electrical permit and inspection. If required, call for electrical permit and inspection. To schedule inspections, go online to www.pwcgov.org/eportal or call the Automated Phone System at 1-866-457-5280. No inspections shall be made unless an approved set of drawings are on site. Residential Plan Review 703-792-6939 Construction Services (Plan Intake) 703-792-4040 Construction Services (Plan Review) 703-792-6930 Construction Services (Permits and Records) 703-792-6924 Construction Inspections 703-792-7006 Zoning Office 703-792-6830 To Schedule Inspection call 1-866-457-5280 or visit: www.pwcgov.org/eportal The Building Development Division reviews Deck plans, Mon. Thru Fri. from 8:00 A.M to 11:00 A.M, on a walk through basis. Emergency windows under decks and porches shall be fully opened and provide a path not less than 36 inches in height to a yard or court. For final inspection, provide access to the top of the deck for decks without stairs. All decks requiring guard rails shall maintain 36 inches height above all walking surfaces and fixed seating. Decks that are accessible from the inside of the dwelling shall have at least one receptacle outlet installed within the perimeter of the deck. Balconies, decks, and porches that are accessible from inside of the dwelling unit shall have at least one Receptacle outlet installed within the perimeter of the balcony, deck, or porch. The receptacle shall be located not more than 6 feet, 6 inches above the balcony, deck, or porch surface.
AutoCAD SHX Text
SHEET 17 OF 17