SLD Series Single Phase Double Insulator Disconnector
Product Brochure
2 | SLD Series brochure
Optional Accesories
— Load break interrupter
— Flicker arc interrupters
— Load break hooks
— Earthing bolts
— Cable connectors
Key Features
— Designed and tested in accordance with AS1306-1985 Standard
— Rated Voltage 24 kV and 36 kV.
— Rated current: 630 and 800 A,
— Porcelain insulators up to 170 kV BIL
— Strength and stability of Double Insulator Design.
— Positive latching to prevent accidental opening due to faults, line vibration, wind or other environmental influences.
— Flexible mounting options
— Straight Fixed Contact Blade to ensure smooth low effort operation and reduce wear on contact plating.
— Hinge end moving blade alignment to ensure that moving contacts align and engages properly.
— Separate contact areas at hinge end to replace the hinge as the current carrying path.
— Range of accessories such as arc horn, cable connector, load break interrupter, earth bolt and earth stirrup available
— Corrosion resistant hot-dip galvanized and Stainless steel 316 ferrous components- durable in harsh environment
— Silver plated copper contacts
— Bright tin plated terminal palms suitable for use with connectors, copper and aluminum compression lugs.
— Locally manufactured and supported
— Short Lead times
SLD Series double insulator disconnector (isolator) is designed to be used on overhead distribution systems in a totally exposed environment and can be used as mechanical switching device which provides an isolating distance in open position. The SLD Series design provides strength and stability of double insulator design, positive latching to prevent accidental opening due to faults, line vibration, wind or other environmental influences. The straight fixed contact blades ensure smooth low effort operation and reduce wear on contact plating. The hinge end moving blade ensures the moving contacts alignment and proper engagement.
SLD Series Single Phase Double Insulator Disconnector
SLD Series brochure | 3
Insulators
Current Carrying Assembly
Terminal Palms
Construction
The standard porcelain insulators are light grey in colour and constructed from a single piece of glazed porcelain.
Porcelain insulators provide high creepage with 150 kV and 170 kV BIL insulation level.
Current carrying parts are manufactured from HD HC copper with 630 amp continuous rating. Moving contacts have ‘lead in’ feature and straight parallel sides to ensure low effort operation, reduce plating wear and ensure contact alignment during closing operation.
The hinge end is designed with separate contacts so that the current path is not through the joint and to provide blade alignment during the closing operation.
Terminal palms are bright tin plated to AS2395-1980 and are suitable for use with connectors, copper and aluminum compression lugs.
Mounting
The SLD series disconnector is designed for Underslung and Vertical mounting.
Underslung Mounting
Vertical Mounting
4 | SLD Series brochure
Configuration
K
ØJ
G I
H
A
H
B C
D
ØF X 4 PL.
E
L
A B C D E F G H I J K L
12/24 Kv ( Porcelain) 640 118 143 168 113.5 13.5 286 440 35 50 344 403
36 Kv ( Porcelain) 751 118 143 168 113.5 13.5 410 563 35 50 434 493
All dimensions are in mm.
SLD Series brochure | 5
Accessories
with Load Break Hook and Cable Connector
with Load Break Interrupter
with Earthing Bolts
with Flicker Arc Interrupters
SLD
ser
ies
bro
chur
e
Technical Data
Rated Voltage KV 12/24 36
Rated Continuous Current Amp 630 / 800 630 / 800
Rated Frequency Hz 50 50
Basic Insulation Level (BIL) kV 150 200
Insulator material Porcelain Porcelain
Creepage mm 380 660
Rated Short-time Withstand Current (1 sec.)
kA25 (630 Amp units)
16 (800 Amp units)
Rated peak withstand current kAp62.5 (630 Amp units)
40 (800 Amp units)
For more information please contact:
Medium Voltage Products1 Baupaume RoadMoorebank, NSW 2170 AustraliaPhone: +61 2 9753 7111Fax: +61 2 9602 2454
www.abbaustralia.com.au
Note
While care has been taken to ensure that the information contained in this document is correct, no responsibility can be accepted for any inaccuracy. We reserve the right to alter or modify the information contained herein at any time in the light of technical or other developments. Technical specifications are valid under normal operating conditions only. We do not accept any responsibility for any misuse of the product and cannot be held liable for indirect or consequential damages. Technical data and design is subject to change and should be confirmed prior to ordering.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction–in whole or in parts–is forbidden without ABB’s prior written consent.
Copyright 2013 ABB.
All rights reserved.