AC centrifugal fanforward curved, dual inlet
with housing (flange)
D2E146-HS97-01
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 · D-74673 Mulfingen
Phone +49 7938 81-0
Fax +49 7938 81-110
www.ebmpapst.com
Limited partnership · Headquarters Mulfingen
County court Stuttgart · HRA 590344
General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen
County court Stuttgart · HRB 590142
Nominal data
Type D2E146-HS97-01
Motor M2E068-DF
Phase 1~ 1~
Nominal voltage VAC 230 230
Frequency Hz 50 60
Type of data definition fa ml
Valid for approval / standard CE CE
Speed min-1 1350 1750
Power input W 195 215
Current draw A 0.86 0.94
Motor capacitor µF 5 5
Capacitor voltage VDB 400 400
Capacitor standard P2 (CE) P2 (CE)
Min. back pressure Pa 0 150
Max. ambient temperature °C 45 40ml = max. load · me = max. efficiency · fa = running at free air · cs = customer specs · cu = customer unitSubject to alterations
Data according to ErP directive
Installation category A
Efficiency category Static
Variable speed drive No
Specific ratio* 1.00* Specific ratio = 1 + pfs / 100 000 Pa
Actual Request 2013 Request 2015
Overall efficiency ηes 25.6 25.6 32.6
Efficiency grade N 37 37 44
Power input Pe kW 0.16
Air flow qv m³/h 455
Pressure increase pfs Pa 331
Speed n min-1 2315Data established at point of optimum efficiency
Item no. 10852-5-9980 · Revision 71618 · Release 2010-08-03 · Page 1 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC centrifugal fanforward curved, dual inlet
with housing (flange)
D2E146-HS97-01
Technical features
Mass 2.94 kg
Size 146 mm
Surface of rotor Partially cast in aluminium
Material of terminal box PP plastic, black
Material of impeller PP plastic, fiberglass-reinforced
Housing material PP plastic, black
Motor suspension Motor anti-vibration mounted on both sides
Direction of rotation Counter-clockwise, seen on rotor
Type of protection IP 20
Insulation class "F"
Humidity class F0
Max. permissible ambient motortemp. (transp./ storage)
+ 80 °C
Min. permissible ambient motortemp. (transp./storage)
- 40 °C
Mounting position Shaft horizontal or rotor on bottom; rotor on top on request
Condensate discharge holes None, open rotor
Operation mode S1
Motor bearing Calotte bearing
Speed steps 4
Touch current acc. IEC 60990(measuring network Fig. 4, TNsystem)
< 0.75 mA
Electrical leads With plug; Via terminal box, integrated capacitor connected via terminal box
Motor protection Thermal overload protector (TOP) wired internally
Cable exit Variable
Protection class I (if protective earth is connected by customer)
Product conforming to standard EN 60335-1; CE
Approval GOST; CCC; VDE
Item no. 10852-5-9980 · Revision 71618 · Release 2010-08-03 · Page 2 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC centrifugal fanforward curved, dual inlet
with housing (flange)
D2E146-HS97-01
Product drawing
1 AMP Universal Mate-N-Lok coded plug system; connector shell: AMP 926 682-3; 6x plug pin: AMP 926 886-1
1.1 L = stage 1
1.2 L = step 2
1.3 L = stage 3
1.4 L = stage 4
1.5 N
1.6 Protective earth
2 4 x sheet metal nut for thread EN ISO 1478-ST4.8 (min. screw length 14.5 mm plus thickness of mounting material)
Item no. 10852-5-9980 · Revision 71618 · Release 2010-08-03 · Page 3 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC centrifugal fanforward curved, dual inlet
with housing (flange)
D2E146-HS97-01
Connection screen
When changing speeds, switch must break the circuit
1 Step 1 (min.) 2 Step 2 3 Step 3
4 Step 4 (max.) 5 N 6 PE protective earth
7 Speed increase
Item no. 10852-5-9980 · Revision 71618 · Release 2010-08-03 · Page 4 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC centrifugal fanforward curved, dual inlet
with housing (flange)
D2E146-HS97-01
Charts: Air flow 50 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
qv[m^3/h]800750700650600550500450400350300250200150100500
qv[cfm]450400350300250200150100500
p fs[
Pa]
480
460
440
420
400
380
360
340
320
300
280
260
240
220
200
180
160
140
120
100
80
60
40
20
0
pfs
_E
[IN
H2O
]
1,9
1,851,8
1,75
1,71,65
1,6
1,55
1,51,45
1,4
1,351,3
1,25
1,21,15
1,1
1,051
0,95
0,90,85
0,8
0,750,7
0,65
0,60,55
0,5
0,45
0,40,35
0,3
0,250,2
0,15
0,10,05
Step 4
Step 2
00
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Measurement: LU-72087Measurement: LU-72089Measurement: LU-72091Measurement: LU-72094
Air performance measured as per ISO 5801Installation category A. For detailedinformation on the measuring set-up, pleasecontact ebm-papst. Suction-side noiselevels: LwA measured as per ISO 13347 /LpA measured with 1m distance to fan axis.The values given are valid under themeasuring conditions mentioned above andmay vary according to the actual installationsituation. With any deviation from thestandard set-up, the specific values have tobe checked and reviewed with the unitinstalled.
Measured values
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Stage
4
4
4
4
3
3
3
3
2
2
2
2
1
1
1
1
U
V
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
f
Hz
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
n
min-1
1350
1795
2200
2520
875
1215
1680
2255
660
915
1280
1920
510
715
960
1515
Pe
W
195
185
169
146
128
125
116
94
109
106
102
88
95
94
92
85
I
A
0.86
0.81
0.75
0.65
0.61
0.60
0.58
0.52
0.53
0.52
0.51
0.48
0.47
0.47
0.46
0.44
qv
m3/h
760
645
480
260
480
430
365
235
365
330
280
195
270
245
210
155
pfs
Pa
0
150
300
400
0
67
176
321
0
38
100
230
0
22
55
138
U = Supply voltage · f = Frequency · n = Speed · Pe = Power input · I = Current draw · qv = Air flow · pfs = Pressure increase
Item no. 10852-5-9980 · Revision 71618 · Release 2010-08-03 · Page 5 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
AC centrifugal fanforward curved, dual inlet
with housing (flange)
D2E146-HS97-01
Charts: Air flow 60 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
qv[m^3/h]750700650600550500450400350300250200150100500
qv[cfm]400350300250200150100500
p fs[
Pa]
560
540
520
500
480
460
440
420
400
380
360
340
320
300
280
260
240
220
200
180
160
140
120
100
80
60
40
20
0
pfs
_E
[IN
H2O
]
2,2
2,1
2
1,9
1,8
1,7
1,6
1,5
1,4
1,3
1,2
1,1
1
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0
Step 4
Step 2
00
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Measurement: LU-72088Measurement: LU-72090Measurement: LU-72092Measurement: LU-72095
Air performance measured as per ISO 5801Installation category A. For detailedinformation on the measuring set-up, pleasecontact ebm-papst. Suction-side noiselevels: LwA measured as per ISO 13347 /LpA measured with 1m distance to fan axis.The values given are valid under themeasuring conditions mentioned above andmay vary according to the actual installationsituation. With any deviation from thestandard set-up, the specific values have tobe checked and reviewed with the unitinstalled.
Measured values
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Stage
4
4
4
4
3
3
3
3
2
2
2
2
1
1
1
1
U
V
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
f
Hz
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
n
min-1
1750
2060
2380
2710
1175
1485
1855
2365
890
1100
1365
1835
665
820
1010
1325
Pe
W
215
212
208
201
131
129
125
114
106
105
104
99
92
91
90
88
I
A
0.94
0.93
0.91
0.89
0.67
0.67
0.66
0.65
0.57
0.57
0.57
0.56
0.50
0.50
0.50
0.50
qv
m3/h
580
480
375
230
390
340
290
200
285
250
210
145
220
190
155
110
pfs
Pa
150
260
360
460
68
132
214
350
37
70
110
187
22
41
60
104
U = Supply voltage · f = Frequency · n = Speed · Pe = Power input · I = Current draw · qv = Air flow · pfs = Pressure increase
Item no. 10852-5-9980 · Revision 71618 · Release 2010-08-03 · Page 6 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com