Part No. CPD-360P Product Information CPD-360P is a passive infrared (PIR) ceiling mountable presence detector for lighng or HVAC automaon control. Presence Detector • High performance presence detector • 360° detecton with lens shield, flush or surface mount • 30m detecon zone • 2 Channel, 5 seconds to 30 minutes and 2 nd channel 10 seconds to 60 minutes • Up to 10 slaves can be aached to extend to range (Part No. CPD-360P-SLAVE) • IP40 but IP54 with included surface mount juncon box • Impulse mode to switch a staircase mer • Oponal IR remote control • Suitable for halogen, Fluro and LED FEATURES AND BENEFITS: Flush mountable Surface mountable with juncon box Lens shield for detecon angle adjustment Master & Slave connecon is for expanding detecon coverage Manual control & Auto/ Semi-auto control are enabled by using external push buon switch Hand-held IR remote control (oponal)
Transcript
Page 1: Product Information - CABAC · }v CPD-360P CPD-360P-Slave RATED VOLTAGE 220 - 240V a 50/60HZ 220 - 240V a 50/60HZ LOAD I FOR LIGHTING V X LOAD II FOR LIGHTING V X LUX SETTING íì>µÆ

Part No. CPD-360P

Product Information

CPD-360P is a passive infrared (PIR) ceiling mountable presence detector for lighting or HVAC automation control.

Presence Detector

• High performance presence detector• 360° detecton with lens shield, flush or surface mount• 30m detection zone• 2 Channel, 5 seconds to 30 minutes and 2nd channel 10 seconds to 60 minutes• Up to 10 slaves can be attached to extend to range (Part No. CPD-360P-SLAVE)• IP40 but IP54 with included surface mount junction box• Impulse mode to switch a staircase timer• Optional IR remote control• Suitable for halogen, Fluro and LED

FEATURES AND BENEFITS:

Flush mountable Surface mountable with junction box

Lens shield for detection angle adjustment

Master & Slave connection is for expanding detection coverage

Manual control & Auto/Semi-auto control are enabled by using external push button switch

Hand-held IR remote control (optional)

Page 2: Product Information - CABAC · }v CPD-360P CPD-360P-Slave RATED VOLTAGE 220 - 240V a 50/60HZ 220 - 240V a 50/60HZ LOAD I FOR LIGHTING V X LOAD II FOR LIGHTING V X LUX SETTING íì>µÆ

Product InformationSPECIFICATIONS:

Feature DescriptionLoad Load I (CH1) for Lighting:

Load II (CH2) for HVAC: (voltage free contact)

Incandescent Lamp: max. 2000WAC Halogen Lamp: max. 1000WLV Halogen Lamp: max. 1000VA/600W (traditional)LV Halogen Lamp: max. 1000VA/900W (electronics)Fluorescent Lamp: max. 900VA/100µFLV Halogen Lamp: 25 x (1 x 18W)LV Halogen Lamp: 12 x (2 x 18W)LV Halogen Lamp: 15 x (1 x 36W)LV Halogen Lamp: 7 x (2 x 36W)LV Halogen Lamp: 10 x (1 x 58W)LV Halogen Lamp: 5 x (2 x 58W)LV Halogen Lamp: max. 1000VA/600W (uncompensated)LED Lamp: max. 500VA/400WEnergy Saving Lamp: max. 600VA/400W (include CFL and PL Lamp)

max. 5A (cos φ = 1) for ≤ 250VACmax. 5A for ≤ 30VDCmax. 1A (cos φ = 0.4) for ≤ 250VAC

Detection Range 360° circular, up to � 30m at height of 2.5m

Lux Adjustment Adjustable from approx. 10 Lux to 2000Lux

Auto Off Time Time 1:(for lighting)

Time 2:(for HVAC)

Adjustable from approx. 10 seconds to 30 minutes and test &

Adjustable from approx. 10 seconds to 60 minutes and

Specifications CPD-360P CPD-360P-SlaveRATED VOLTAGE 220 - 240V ~ 50/60HZ 220 - 240V ~ 50/60HZ

LOAD I FOR LIGHTING V X

LOAD II FOR LIGHTING V X

LUX SETTING 10Lux to 2000Lux X

TIME 1 FOR LIGHTING 5 seconds - 30 minutes Test, X

TIME 2 FOR HVAC 5 seconds - 60 minutes X

OPERATING TEMPERATURE -20°C to +45°C 20°C to +45°C

ENVIRONMENTAL PROTECTION IP40, IP54 (with JB-41) IP40, IP54 (with JB-41)

DETECTION ANGLE 360° 360°

DETECTION RANGE Φ 30m Φ 30m

Page 3: Product Information - CABAC · }v CPD-360P CPD-360P-Slave RATED VOLTAGE 220 - 240V a 50/60HZ 220 - 240V a 50/60HZ LOAD I FOR LIGHTING V X LOAD II FOR LIGHTING V X LUX SETTING íì>µÆ

Product InformationDIMENSIONS (MM):

DETECTION COVERAGE:

· CPD-360P · Detector with junction box (included)

· Remote control (optional purchase) · CDP-P-RC