+ All Categories
Home > Documents > proetcc12

proetcc12

Date post: 29-May-2017
Category:
Upload: rjk941
View: 216 times
Download: 2 times
Share this document with a friend
12
Network Protection & Automation Guide 9.4 STANDARD I.D.M.T. OVERCURRENT RELAYS The current/time tripping characteristics of IDMT relays may need to be varied according to the tripping time required and the characteristics of other protection devices used in the network. For these purposes, IEC 60255 defines a number of standard characteristics as follows: Standard Inverse (SI) Very Inverse (VI) Extremely Inverse (EI) Definite Time (DT) 9 Overcurrent Protection for Phase and Earth Faults • 126 Figure 9.3: Relay characteristics for different settings 100 0.10 1.00 Relay A: Current Setting = 100A, TMS = 1.0 1000 10,000 time Relay A operating time 10.00 100. 1000. Relay B: Current Setting = 125A, TMS = 1.3 Current (A) Time (s) Table 9.1: Definitions of standard relay characteristics Figure 9.4 (a): IDMT relay characteristics (a) IEC 60255 characteristics ; TMS=1.0 Operating Time (seconds) Current (multiples of I S ) 0.10 10 1.00 10.00 100.00 1000.00 100 1 I r = (I/I s ), where I s = relay setting current TMS = Time multiplier Setting TD = Time Dial setting (b): North American IDMT relay characteristics Relay Characteristic Equation (IEC 60255) IEEE Moderately Inverse IEEE Very Inverse Extremely Inverse (EI) US CO8 Inverse US CO2 Short Time Inverse t TD I = + 7 0 02394 1 0 01694 0 02 . . . r t TD I r = + 7 5 95 1 0 18 2 . . t TD I r = + 7 28 2 1 0 1217 2 . . t TD I r = + 7 19 61 1 0 491 2 . . t TD I r = + 7 0 0515 1 0 114 0 02 . . . Relay Characteristic Equation (IEC 60255) Standard Inverse (SI) Very Inverse (VI) Extremely Inverse (EI) Long time standard earth fault t TMS I r = × 120 1 t TMS I r = × 80 1 2 t TMS I r = × 13 5 1 . t TMS I r = × 0 14 1 0 02 . . (a): Relay characteristics to IEC 60255
Transcript
Page 1: proetcc12

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

9.4 STANDARD I.D.M.T. OVERCURRENT RELAYS

The current/time tripping characteristics of IDMT relaysmay need to be varied according to the tripping timerequired and the characteristics of other protection devicesused in the network. For these purposes, IEC 60255 definesa number of standard characteristics as follows:

Standard Inverse (SI)Very Inverse (VI)Extremely Inverse (EI)Definite Time (DT)

• 9 •

Ove

rcur

rent

Pro

tect

ion

for

Phas

e an

d E

arth

Fau

lts

• 1 2 6 •

Figure 9.3: Relay characteristics for different settings

1000.10

1.00

Relay A: Current Setting = 100A, TMS = 1.0

1000 10,000

time

Relay A operatingtime

10.00

100.

1000.

Relay B: Current Setting = 125A, TMS = 1.3

Current (A)

Tim

e (s

)

Table 9.1: Definitions of standard relay characteristics

Figure 9.4 (a): IDMT relay characteristics

(a) IEC 60255 characteristics ; TMS=1.0

Ope

ratin

g Ti

me

(sec

onds

)

Current (multiples of ISI )

0.1010

1.00

10.00

100.00

1000.00

1001

Ir = (I/Is), where Is = relay setting currentTMS = Time multiplier Setting

TD = Time Dial setting

(b): North American IDMT relay characteristics

Relay Characteristic Equation (IEC 60255)

IEEE Moderately Inverse

IEEE Very Inverse

Extremely Inverse (EI)

US CO8 Inverse

US CO2 Short Time Inverse t TD

I=

⎝⎜

⎠⎟ +

⎧⎨⎪

⎩⎪

⎫⎬⎪

⎭⎪70 02394

10 01694

0 02

. ..

r

t TDIr

=−

⎛⎝⎜

⎞⎠⎟

+⎧⎨⎩

⎫⎬⎭7

5 951

0 182

. .

t TDIr

=−

⎛⎝⎜

⎞⎠⎟

+⎧⎨⎩

⎫⎬⎭7

28 21

0 12172

. .

t TDIr

=−

⎛⎝⎜

⎞⎠⎟

+⎧⎨⎩

⎫⎬⎭7

19 611

0 4912

. .

t TDIr

=−

⎛⎝⎜

⎞⎠⎟

+⎧⎨⎩

⎫⎬⎭7

0 05151

0 1140 02

. ..

Relay Characteristic Equation (IEC 60255)

Standard Inverse (SI)

Very Inverse (VI)

Extremely Inverse (EI)

Long time standard earth fault t TMSI r

= ×−

1201

t TMSI r

= ×−

8012

t TMSI r

= ×−

13 51

.

t TMSI r

= ×−

0 1410 02

..

(a): Relay characteristics to IEC 60255

Page 2: proetcc12

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 1 2 7 •

The mathematical descriptions of the curves are given inTable 9.1(a), and the curves based on a common settingcurrent and time multiplier setting of 1 second areshown in Figure 9.4(a). The tripping characteristics fordifferent TMS settings using the SI curve are illustratedin Figure 9.5.

Although the curves are only shown for discrete values ofTMS, continuous adjustment may be possible in anelectromechanical relay. For other relay types, the settingsteps may be so small as to effectively provide continuousadjustment. In addition, almost all overcurrent relays arealso fitted with a high-set instantaneous element.

In most cases, use of the standard SI curve provessatisfactory, but if satisfactory grading cannot beachieved, use of the VI or EI curves may help to resolvethe problem. When digital or numeric relays are used,other characteristics may be provided, including thepossibility of user-definable curves. More details areprovided in the following sections.

Relays for power systems designed to North Americanpractice utilise ANSI/IEEE curves. Table 9.1(b) gives themathematical description of these characteristics andFigure 9.4(b) shows the curves standardised to a timedial setting of 1.0.

9.5 COMBINED I.D.M.T. AND HIGH SET INSTANTANEOUS OVERCURRENT RELAYS

A high-set instantaneous element can be used where thesource impedance is small in comparison with theprotected circuit impedance. This makes a reduction inthe tripping time at high fault levels possible. It alsoimproves the overall system grading by allowing the'discriminating curves' behind the high set instantaneouselements to be lowered.

As shown in Figure 9.6, one of the advantages of the highset instantaneous elements is to reduce the operatingtime of the circuit protection by the shaded area belowthe 'discriminating curves'. If the source impedanceremains constant, it is then possible to achieve high-speed protection over a large section of the protectedcircuit. The rapid fault clearance time achieved helps tominimise damage at the fault location. Figure 9.6 alsoillustrates a further important advantage gained by theuse of high set instantaneous elements. Grading withthe relay immediately behind the relay that has theinstantaneous elements enabled is carried out at thecurrent setting of the instantaneous elements and not at

• 9 •O

verc

urre

nt P

rote

ctio

n fo

r Ph

ase

and

Ear

th F

aults

Figure 9.5: Typical time/current characteristics of standard IDMT relay

Tim

e (s

econ

ds)

Current (multiples of plug settings)

2

3

4

6

8

10

1

2 3 4 6 8 10 20 3010.1

0.2

0.4

0.3

0.6

0.8

1.0TMS

0.90.80.70.60.5

0.4

0.3

0.2

0.1

Figure 9.4 (b): IDMT relay characteristics

(b) North American characteristics; TD=7

0.10101

1.00

10.00

100.00

1000.00

100

Ope

ratin

g Ti

me

(sec

onds

)

Current (multiples of ISI )

Moderately Inverse

Time Inverse

CO 8 Inverse

ExtremelyInverse

Page 3: proetcc12

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

the maximum fault level. For example, in Figure 9.6,relay R2 is graded with relay R3 at 500A and not 1100A,allowing relay R2 to be set with a TMS of 0.15 instead of0.2 while maintaining a grading margin between relaysof 0.4s. Similarly, relay R1 is graded with R2 at 1400Aand not at 2300A.

9.5.1 Transient Overreach

The reach of a relay is that part of the system protectedby the relay if a fault occurs. A relay that operates for afault that lies beyond the intended zone of protection issaid to overreach.When using instantaneous overcurrent elements, caremust be exercised in choosing the settings to preventthem operating for faults beyond the protected section.The initial current due to a d.c. offset in the current wavemay be greater than the relay pick-up value and cause itto operate. This may occur even though the steady stater.m.s. value of the fault current for a fault at a pointbeyond the required reach point may be less than therelay setting. This phenomenon is called transientoverreach, and is defined as:

…Equation 9.1

where:I1 = r.m.s steady-state relay pick-up currentI2 = steady state r.m.s. current which when fully

offset just causes relay pick-up

When applied to power transformers, the high setinstantaneous overcurrent elements must be set abovethe maximum through fault current than the powertransformer can supply for a fault across its LV terminals,in order to maintain discrimination with the relays onthe LV side of the transformer.

% % transient overreach = − ×I II

1 2

2100

9.6 VERY INVERSE (VI) OVERCURRENT RELAYS

Very inverse overcurrent relays are particularly suitable ifthere is a substantial reduction of fault current as thedistance from the power source increases, i.e. there is asubstantial increase in fault impedance. The VI operatingcharacteristic is such that the operating time isapproximately doubled for reduction in current from 7 to4 times the relay current setting. This permits the use ofthe same time multiplier setting for several relays in series.

Figure 9.7 provides a comparison of the SI and VI curvesfor a relay. The VI curve is much steeper and thereforethe operation increases much faster for the samereduction in current compared to the SI curve. Thisenables the requisite grading margin to be obtained witha lower TMS for the same setting current, and hence thetripping time at source can be minimised.

9.7 EXTREMELY INVERSE (EI) OVERCURRENT RELAYS

With this characteristic, the operation time isapproximately inversely proportional to the square of theapplied current. This makes it suitable for the protectionof distribution feeder circuits in which the feeder issubjected to peak currents on switching in, as would bethe case on a power circuit supplying refrigerators,pumps, water heaters and so on, which remainconnected even after a prolonged interruption of supply.The long time operating characteristic of the extremely

• 9 •

Ove

rcur

rent

Pro

tect

ion

for

Phas

e an

d E

arth

Fau

lts

• 1 2 8 •

Ope

ratin

g tim

e (s

econ

ds)

0.10101

1.00

10.00

100.00

100Current ( multiples of Is )

Standard Inverse (SI)

Very Inverse (VI)

Figure 9.7: Comparison of SI and VI relay characteristics

Figure 9.6: Characteristics of combined IDMT and high-set instantaneous overcurrent relays

Tim

e (s

econ

ds)

2

3

1

100001000.1

400/1A

R1 R2 R3Source250 MVA11kV

100/1A 50/1AFault level 13.000A Fault level 2300A Fault level 1100A

Ratio

10,0000

R3

R2 RR1

500A 0.125 TMS

62.5A 0.10 TMS

300A

500A

Page 4: proetcc12

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 1 2 9 •

inverse relay at normal peak load values of current alsomakes this relay particularly suitable for grading withfuses. Figure 9.8 shows typical curves to illustrate this.It can be seen that use of the EI characteristic gives asatisfactory grading margin, but use of the VI or SIcharacteristics at the same settings does not. Anotherapplication of this relay is in conjunction with auto-reclosers in low voltage distribution circuits. Themajority of faults are transient in nature andunnecessary blowing and replacing of the fuses presentin final circuits of such a system can be avoided if theauto-reclosers are set to operate before the fuse blows.If the fault persists, the auto-recloser locks itself in theclosed position after one opening and the fuse blows toisolate the fault.

9.8 OTHER RELAY CHARACTERISTICS

User definable curves may be provided on some types ofdigital or numerical relays. The general principle is that theuser enters a series of current/time co-ordinates that arestored in the memory of the relay. Interpolation betweenpoints is used to provide a smooth trip characteristic. Sucha feature, if available, may be used in special cases if noneof the standard tripping characteristics is suitable.However, grading of upstream protection may becomemore difficult, and it is necessary to ensure that the curve

is properly documented, along with the reasons for use.Since the standard curves provided cover most cases withadequate tripping times, and most equipment is designedwith standard protection curves in mind, the need to utilisethis form of protection is relatively rare.

Digital and numerical relays may also include pre-defined logic schemes utilising digital (relay) I/Oprovided in the relay to implement standard schemessuch as CB failure and trip circuit supervision. This savesthe provision of separate relay or PLC (ProgrammableLogic Controller) hardware to perform these functions.

9.9 INDEPENDENT (DEFINITE) TIMEOVERCURRENT RELAYS

Overcurrent relays are normally also provided withelements having independent or definite timecharacteristics. These characteristics provide a readymeans of co-ordinating several relays in series insituations in which the system fault current varies verywidely due to changes in source impedance, as there isno change in time with the variation of fault current.The time/current characteristics of this curve are shownin Figure 9.9, together with those of the standard I.D.M.T.characteristic, to indicate that lower operating times areachieved by the inverse relay at the higher values of faultcurrent, whereas the definite time relay has loweroperating times at the lower current values.

Vertical lines T1, T2, T3, and T4 indicate the reduction inoperating times achieved by the inverse relay at highfault levels.

9.10 RELAY CURRENT SETTING

An overcurrent relay has a minimum operating current,known as the current setting of the relay. The currentsetting must be chosen so that the relay does notoperate for the maximum load current in the circuitbeing protected, but does operate for a current equal orgreater to the minimum expected fault current.Although by using a current setting that is only justabove the maximum load current in the circuit a certaindegree of protection against overloads as well as faultsmay be provided, the main function of overcurrentprotection is to isolate primary system faults and not toprovide overload protection. In general, the currentsetting will be selected to be above the maximum shorttime rated current of the circuit involved. Since all relayshave hysteresis in their current settings, the setting mustbe sufficiently high to allow the relay to reset when therated current of the circuit is being carried. The amountof hysteresis in the current setting is denoted by thepick-up/drop-off ratio of a relay – the value for a modernrelay is typically 0.95. Thus, a relay minimum current

• 9 •O

verc

urre

nt P

rote

ctio

n fo

r Ph

ase

and

Ear

th F

aults

Figure 9.8: Comparison of relay and fuse characteristics

1000.1

1000

1.0

10.0

100.0

10,000

200.0

Standardinverse (SI)

Current (amps)

Tim

e (s

ecs)

inverse (EI) Es E

200A Fuseus

v

A

Page 5: proetcc12

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

setting of at least 1.05 times the short-time ratedcurrent of the circuit is likely to be required.

9.11 RELAY TIME GRADING MARGIN

The time interval that must be allowed between theoperation of two adjacent relays in order to achievecorrect discrimination between them is called the gradingmargin. If a grading margin is not provided, or isinsufficient, more than one relay will operate for a fault,leading to difficulties in determining the location of thefault and unnecessary loss of supply to some consumers.

The grading margin depends on a number of factors:

i. the fault current interrupting time of the circuitbreaker

ii. relay timing errors

iii. the overshoot time of the relay

iv. CT errors

v. final margin on completion of operation

Factors (ii) and (iii) above depend to a certain extent onthe relay technology used – an electromechanical relay,for instance, will have a larger overshoot time than anumerical relay.

Grading is initially carried out for the maximum faultlevel at the relaying point under consideration, but acheck is also made that the required grading marginexists for all current levels between relay pick-up currentand maximum fault level.

• 9 •

Ove

rcur

rent

Pro

tect

ion

for

Phas

e an

d E

arth

Fau

lts

• 1 3 0 •

Tim

e (s

econ

ds)

Fault current (amps)

10

1

100100.1

6000A 3500A

10001

Settings of independent (definite) time relay Settings of I.D.M.T. relay with standard inverse characteristic

Fault level 2000A 1200A

10.000

Grading margin between relays: 0.4s

R1

R1A

R4

R4A

R2

R2A

R2R

3 R

4

R4A

R3A

R2A

R1A

R1

T1

T2

T3TT

T4TT

R3

R3A

R1A

300A 0.2TMSR 175A 0.3TMSR 100A 0.37TMSR4A

set at 57.5A 0.42TMS

R1A

300A 1.8sR 175A 1.4sR 100A 1.0sR4A

set at 57.5A 0.6s

Figure 9.9: Comparison of definite time and standard I.D.M.T. relay

Page 6: proetcc12

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 1 3 1 •

9.11.1 Circuit Breaker Interrupting Time

The circuit breaker interrupting the fault must havecompletely interrupted the current before thediscriminating relay ceases to be energised. The timetaken is dependent on the type of circuit breaker usedand the fault current to be interrupted. Manufacturersnormally provide the fault interrupting time at ratedinterrupting capacity and this value is invariably used inthe calculation of grading margin.

9.11.2 Relay Timing Error

All relays have errors in their timing compared to theideal characteristic as defined in IEC 60255. For a relayspecified to IEC 60255, a relay error index is quoted thatdetermines the maximum timing error of the relay. Thetiming error must be taken into account whendetermining the grading margin.

9.11.3 Overshoot

When the relay is de-energised, operation may continuefor a little longer until any stored energy has beendissipated. For example, an induction disc relay will havestored kinetic energy in the motion of the disc; staticrelay circuits may have energy stored in capacitors.Relay design is directed to minimising and absorbingthese energies, but some allowance is usually necessary.

The overshoot time is defined as the difference betweenthe operating time of a relay at a specified value of inputcurrent and the maximum duration of input current,which when suddenly reduced below the relay operatinglevel, is insufficient to cause relay operation.

9.11.4 CT Errors

Current transformers have phase and ratio errors due tothe exciting current required to magnetise their cores.The result is that the CT secondary current is not anidentical scaled replica of the primary current. This leadsto errors in the operation of relays, especially in the timeof operation. CT errors are not relevant whenindependent definite-time delay overcurrent relays arebeing considered.

9.11.5 Final Margin

After the above allowances have been made, thediscriminating relay must just fail to complete itsoperation. Some extra allowance, or safety margin, isrequired to ensure that relay operation does not occur.

9.11.6 Overall Accuracy

The overall limits of accuracy according to IEC 60255-4for an IDMT relay with standard inverse characteristicare shown in Figure 9.10.

9.12 RECOMMENDED GRADING INTERVALS

The following sections give the recommended overallgrading margins for between different protection devices.

9.12.1 Grading: Relay to Relay

The total interval required to cover the above itemsdepends on the operating speed of the circuit breakersand the relay performance. At one time 0.5s was anormal grading margin. With faster modern circuitbreakers and a lower relay overshoot time, 0.4s isreasonable, while under the best conditions even lowerintervals may be practical.

The use of a fixed grading margin is popular, but it maybe better to calculate the required value for each relaylocation. This more precise margin comprises a fixedtime, covering circuit breaker fault interrupting time,relay overshoot time and a safety margin, plus a variabletime that allows for relay and CT errors. Table 9.2 givestypical relay errors according to the technology used.

It should be noted that use of a fixed grading margin isonly appropriate at high fault levels that lead to shortrelay operating times. At lower fault current levels, withlonger operating times, the permitted error specified inIEC 60255 (7.5% of operating time) may exceed the fixedgrading margin, resulting in the possibility that the relayfails to grade correctly while remaining within

• 9 •O

verc

urre

nt P

rote

ctio

n fo

r Ph

ase

and

Ear

th F

aults

Figure 9.10: Typical limits of accuracy from IEC 60255-4 for an inverse definite minimum time overcurrent relay

Tim

e (s

econ

ds)

2

3

4

6

8

10

1

20

3

40

50

2 3 4 5 6 8 10 20 301

Time/Current characteristic allowable limit

At 2 times settingAt 5 times settingAt 10 times settingAt 20 times setting

2.5 x Declared error1.5 x Declared error1.0 x Declared error1.0 x Declared error

Page 7: proetcc12

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

matter as the procedure adopted for phase relays in Table 9.3. Either the above factors must be taken intoaccount with the errors calculated for each current level,making the process much more tedious, or longergrading margins must be allowed. However, for othertypes of relay, the procedure adopted for phase faultrelays can be used.

9.16.3 Sensitive Earth-Fault Protection

LV systems are not normally earthed through animpedance, due to the resulting overvoltages that mayoccur and consequential safety implications. HV systemsmay be designed to accommodate such overvoltages, butnot the majority of LV systems.

However, it is quite common to earth HV systems throughan impedance that limits the earth-fault current. Further,in some countries, the resistivity of the earth path may bevery high due to the nature of the ground itself (e.g.desert or rock). A fault to earth not involving earthconductors may result in the flow of only a small current,insufficient to operate a normal protection system. Asimilar difficulty also arises in the case of broken lineconductors, which, after falling on to hedges or drymetalled roads, remain energised because of the lowleakage current, and therefore present a danger to life.

To overcome the problem, it is necessary to provide anearth-fault protection system with a setting that isconsiderably lower than the normal line protection. Thispresents no difficulty to a modern digital or numericalrelay. However, older electromechanical or static relaysmay present difficulties due to the high effective burdenthey may present to the CT.

The required sensitivity cannot normally be provided bymeans of conventional CT’s. A core balance currenttransformer (CBCT) will normally be used. The CBCT is acurrent transformer mounted around all three phase (andneutral if present) conductors so that the CT secondarycurrent is proportional to the residual (i.e. earth) current.Such a CT can be made to have any convenient ratiosuitable for operating a sensitive earth-fault relayelement. By use of such techniques, earth fault settingsdown to 10% of the current rating of the circuit to beprotected can be obtained.

Care must be taken to position a CBCT correctly in acable circuit. If the cable sheath is earthed, the earthconnection from the cable gland/sheath junction mustbe taken through the CBCT primary to ensure that phase-sheath faults are detected. Figure 9.17 shows the correctand incorrect methods. With the incorrect method, thefault current in the sheath is not seen as an unbalancecurrent and hence relay operation does not occur.

The normal residual current that may flow during healthy

conditions limits the application of non-directional sensitiveearth-fault protection. Such residual effects can occur dueto unbalanced leakage or capacitance in the system.

9.17 DIRECTIONAL EARTH-FAULT OVERCURRENTPROTECTION

Directional earth-fault overcurrent may need to beapplied in the following situations:

i. for earth-fault protection where the overcurrentprotection is by directional relays

ii. in insulated-earth networks

iii. in Petersen coil earthed networks

iv. where the sensitivity of sensitive earth-faultprotection is insufficient – use of a directionalearth-fault relay may provide greater sensitivity

• 9 •

Ove

rcur

rent

Pro

tect

ion

for

Phas

e an

d E

arth

Fau

lts

• 1 3 8 •

Cable gland /sheathground connection

(a) Physical connections

(b) Incorrect positioning

Cable gland

Cablebox

No operation

Operation

I >

I >

I >

Figure 9.17: Positioning of core balance current transformers

Page 8: proetcc12

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 1 3 9 •

The relay elements previously described as phase faultelements respond to the flow of earth fault current, andit is important that their directional response be correctfor this condition. If a special earth fault element isprovided as described in Section 9.16 (which will normallybe the case), a related directional element is needed.

9.17.1 Relay Connections

The residual current is extracted as shown in Figure 9.15.Since this current may be derived from any phase, inorder to obtain a directional response it is necessary toobtain an appropriate quantity to polarise the relay. Indigital or numerical relays there are usually two choicesprovided.

9.17.1.1 Residual voltage

A suitable quantity is the residual voltage of the system.This is the vector sum of the individual phase voltages. Ifthe secondary windings of a three-phase, five limbvoltage transformer or three single-phase units areconnected in broken delta, the voltage developed acrossits terminals will be the vector sum of the phase toground voltages and hence the residual voltage of thesystem, as illustrated in Figure 9.18.

The primary star point of the VT must be earthed.However, a three-phase, three limb VT is not suitable, asthere is no path for the residual magnetic flux.

When the main voltage transformer associated with thehigh voltage system is not provided with a broken deltasecondary winding to polarise the directional earth faultrelay, it is permissible to use three single-phaseinterposing voltage transformers. Their primary windingsare connected in star and their secondary windings areconnected in broken delta. For satisfactory operation,however, it is necessary to ensure that the main voltagetransformers are of a suitable construction to reproducethe residual voltage and that the star point of theprimary winding is solidly earthed. In addition, the starpoint of the primary windings of the interposing voltagetransformers must be connected to the star point of thesecondary windings of the main voltage transformers.

The residual voltage will be zero for balanced phasevoltages. For simple earth-fault conditions, it will beequal to the depression of the faulted phase voltage. Inall cases the residual voltage is equal to three times thezero sequence voltage drop on the source impedance andis therefore displaced from the residual current by thecharacteristic angle of the source impedance. Theresidual quantities are applied to the directional elementof the earth-fault relay.

The residual current is phase offset from the residualvoltage and hence angle adjustment is required.Typically, the current will lag the polarising voltage. Themethod of system earthing also affects the RelayCharacteristic Angle (RCA), and the following settingsare usual:

i. resistance-earthed system: 0° RCA

ii. distribution system, solidly-earthed: -45° RCA

iii. transmission system, solidly-earthed: -60° RCA

The different settings for distribution and transmissionsystems arise from the different X/R ratios found in thesesystems.

9.17.1.2 Negative sequence current

The residual voltage at any point in the system may beinsufficient to polarise a directional relay, or the voltagetransformers available may not satisfy the conditions forproviding residual voltage. In these circumstances,negative sequence current can be used as the polarisingquantity. The fault direction is determined by comparisonof the negative sequence voltage with the negativesequence current. The RCA must be set based on theangle of the negative phase sequence source voltage.

9.18 EARTH-FAULT PROTECTION ON INSULATEDNETWORKS

Occasionally, a power system is run completely insulatedfrom earth. The advantage of this is that a single phase-earth fault on the system does not cause any earth fault

• 9 •O

verc

urre

nt P

rote

ctio

n fo

r Ph

ase

and

Ear

th F

aults

Figure 9.18: Voltage polarised directional earth fault relay

(a) Relay connections

C

B

A

VaVV

VcVV VbVV VcVV VbVV

Va2VV

3IOII

3VOVV

VaVV

(b) Balanced system (zero residual volts)

(c) Unbalanced system

fault (3Vo residual volts)

3

>I

Page 9: proetcc12

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

current to flow, and so the whole system remainsoperational. The system must be designed to withstand hightransient and steady-state overvoltages however, so its useis generally restricted to low and medium voltage systems.

It is vital that detection of a single phase-earth fault isachieved, so that the fault can be traced and rectified.While system operation is unaffected for this condition,the occurrence of a second earth fault allows substantialcurrents to flow.

The absence of earth-fault current for a single phase-earthfault clearly presents some difficulties in fault detection.Two methods are available using modern relays.

9.18.1 Residual Voltage

When a single phase-earth fault occurs, the healthyphase voltages rise by a factor of √3 and the three phasevoltages no longer have a phasor sum of zero. Hence, aresidual voltage element can be used to detect the fault.However, the method does not provide anydiscrimination, as the unbalanced voltage occurs on thewhole of the affected section of the system. Oneadvantage of this method is that no CT’s are required, asvoltage is being measured. However, the requirementsfor the VT’s as given in Section 9.17.1.1 apply.

Grading is a problem with this method, since all relays inthe affected section will see the fault. It may be possibleto use definite-time grading, but in general, it is notpossible to provide fully discriminative protection usingthis technique.

9.18.2 Sensitive Earth Fault

This method is principally applied to MV systems, as itrelies on detection of the imbalance in the per-phasecharging currents that occurs.

Figure 9.19 illustrates the situation that occurs when asingle phase-earth fault is present. The relays on thehealthy feeders see the unbalance in charging currentsfor their own feeders. The relay in the faulted feeder seesthe charging currents in the rest of the system, with thecurrent of its’ own feeders cancelled out. Figure 9.20shows the phasor diagram.

Use of Core Balance CT’s is essential. With reference toFigure 9.20, the unbalance current on the healthyfeeders lags the residual voltage by 90°. The chargingcurrents on these feeders will be √3 times the normalvalue, as the phase-earth voltages have risen by thisamount. The magnitude of the residual current istherefore three times the steady-state charging currentper phase. As the residual currents on the healthy andfaulted feeders are in antiphase, use of a directionalearth fault relay can provide the discrimination required.

The polarising quantity used is the residual voltage. Byshifting this by 90°, the residual current seen by the relayon the faulted feeder lies within the ‘operate’ region ofthe directional characteristic, while the residual currentson the healthy feeders lie within the ‘restrain’ region.Thus, the RCA required is 90°. The relay setting has to liebetween one and three times the per-phase chargingcurrent.

This may be calculated at the design stage, butconfirmation by means of tests on-site is usual. A singlephase-earth fault is deliberately applied and theresulting currents noted, a process made easier in amodern digital or numeric relay by the measurementfacilities provided. As noted earlier, application of sucha fault for a short period does not involve any disruption

• 9 •

Ove

rcur

rent

Pro

tect

ion

for

Phas

e an

d E

arth

Fau

lts

• 1 4 0 •

Ia3II

IH1I + H3

I +IH2II

IR3I

IR2I

IR1I

IH2I

I

Ia2IIIb2II

Ia1IIIb1II

jXc3XX

jXc2XX

IH1I

jXc1XX

=I +IH2I +IH3I -IH3I=IH1I IH2I

IR3I

Figure 9.19: Current distribution in an insulated system with a C phase –earth fault

Figure 9.20: Phasor diagram for insulated system with C phase-earth fault

An RCA setting of +90° shiftsthe "center of the characteristic" to here

VcpfVVVbpfVV

VbfVV

IR3I = -(IH1I IH2II )

VafVV

VapfVVIR1I

Ia1II

Ib1II

Restrain

Operate

VresVV (= -3Vo)

Page 10: proetcc12

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 1 4 1 •

to the network, or fault currents, but the duration shouldbe as short as possible to guard against a second suchfault occurring.

It is also possible to dispense with the directional elementif the relay can be set at a current value that lies betweenthe charging current on the feeder to be protected andthe charging current of the rest of the system.

9.19 EARTH FAULT PROTECTION ON PETERSEN COILEARTHED NETWORKS

Petersen Coil earthing is a special case of highimpedance earthing. The network is earthed via areactor, whose reactance is made nominally equal to thetotal system capacitance to earth. Under this condition,a single phase-earth fault does not result in any earthfault current in steady-state conditions. The effect istherefore similar to having an insulated system. Theeffectiveness of the method is dependent on theaccuracy of tuning of the reactance value – changes insystem capacitance (due to system configurationchanges for instance) require changes to the coilreactance. In practice, perfect matching of the coilreactance to the system capacitance is difficult toachieve, so that a small earth fault current will flow.Petersen Coil earthed systems are commonly found inareas where the system consists mainly of rural overheadlines, and are particularly beneficial in locations subjectto a high incidence of transient faults.

To understand how to correctly apply earth faultprotection to such systems, system behaviour under earthfault conditions must first be understood.

Figure 9.21 illustrates a simple network earthed througha Petersen Coil. The equations clearly show that, if thereactor is correctly tuned, no earth fault current will flow.

Figure 9.22 shows a radial distribution system earthedusing a Petersen Coil. One feeder has a phase-earth faulton phase C. Figure 9.23 shows the resulting phasordiagrams, assuming that no resistance is present.

• 9 •O

verc

urre

nt P

rote

ctio

n fo

r Ph

ase

and

Ear

th F

aults

C B

A ILI

-IBI

-ICII

VabVVVacVV

-----

N

Current vectors for A phase fault

Source

Petersencoil

-ICII

-jX- CXX-jX- X

jXLXX

(=ILII )

VanVV

L

-jX- CXX

(=-IbII

VabVV

jXC

XIcII )

VacVV

CIfII

-IBI

IfIIf IBI - C+VanVV

jXLXX

=O if =IBI +ICIIan

jXLX

Figure 9.21: Earth fault in Petersen Coil earthed system

A

N

C B

3VO

VVIL

IH3

IH2

IH1

b1

Ia1

Ib1II

IL

IR3

Ia1

IR1

=IH1

Vres

=-3VO

V Vres

=-3VO

V

a) Capacitive et inductive currents

b) Unfaulted line c) Faulted line

-IH1

IR3

=-I +I=- -I

H2

-I

Figure 9.23: C phase-earth fault in Petersen Coil earthed network: theoretical case –no resistance present in XL or XC

ILI =IFII IH1I IH2I -IH3IH1+IH2I

ILI

IFII

IH2IIa3II

II =IFIIb3II

Ia2IIb2II

IR3

IR2I

-jX- C3XX

-jX- C2XXjXLXX

ILIIH1I

Ia1IIb1II

IR1I-jX- C1XX

Figure 9.22: Distribution of currents during a C phase-earth fault – radial distribution system

Page 11: proetcc12

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e

In Figure 9.23(a), it can be seen that the fault causes thehealthy phase voltages to rise by a factor of √3 and thecharging currents lead the voltages by 90°.

Using a CBCT, the unbalance currents seen on thehealthy feeders can be seen to be a simple vectoraddition of Ia1 and Ib1, and this lies at exactly 90° laggingto the residual voltage (Figure 9.23(b)). The magnitudeof the residual current IR1 is equal to three times thesteady-state charging current per phase. On the faultedfeeder, the residual current is equal to IL-IH1-IH2, asshown in Figure 9.23(c) and more clearly by the zerosequence network of Figure 9.24.

However, in practical cases, resistance is present andFigure 9.25 shows the resulting phasor diagrams. If theresidual voltage Vres is used as the polarising voltage, theresidual current is phase shifted by an angle less than90° on the faulted feeder and greater than 90° on thehealthy feeders.

Hence a directional relay can be used, and with an RCAof 0°, the healthy feeder residual current will fall in the‘restrain’ area of the relay characteristic while thefaulted feeder residual current falls in the ‘operate’ area.

Often, a resistance is deliberately inserted in parallelwith the Petersen Coil to ensure a measurable earth faultcurrent and increase the angular difference between theresidual signals to aid relay application.

Having established that a directional relay can be used,two possibilities exist for the type of protection elementthat can be applied – sensitive earth fault and zerosequence wattmetric.

9.19.1 Sensitive Earth Fault Protection

To apply this form of protection, the relay must meet tworequirements:

a. current measurement setting capable of being setto very low values

b. an RCA of 0°, and capable of fine adjustmentaround this value

The sensitive current element is required because of thevery low current that may flow – so settings of less than0.5% of rated current may be required. However, ascompensation by the Petersen Coil may not be perfect,low levels of steady-state earth-fault current will flowand increase the residual current seen by the relay. Anoften used setting value is the per phase chargingcurrent of the circuit being protected.

Fine tuning of the RCA is also required about the 0°setting, to compensate for coil and feeder resistancesand the performance of the CT used. In practice, theseadjustments are best carried out on site throughdeliberate application of faults and recording of theresulting currents.

9.19.2 Sensitive Wattmetric Protection

It can be seen in Figure 9.25 that a small angulardifference exists between the spill current on the healthyand faulted feeders. Figure 9.26 illustrates how thisangular difference gives rise to active components ofcurrent which are in antiphase to each other.

Consequently, the active components of zero sequencepower will also lie in similar planes and a relay capableof detecting active power can make a discriminatory

• 9 •

Ove

rcur

rent

Pro

tect

ion

for

Phas

e an

d E

arth

Fau

lts

• 1 4 2 •

IL

IH3

IROFIOF

IROH

IROH

Xco

IH2 IH13XL

Faulted feeder

Healthy feeders

Key:IROF=residual current on faulted feederIROH=residual current on healthy feederIt can therefore be seen that:-IOF=IL-IH1-IH2-IH3IROF=IH3+IOFSo:-IROF=IL=IH1-IH2

-VO

Figure 9.24: Zero sequence network showing residual currents

A

N

C B

I'L

(I 1+IH2+IH3)'

IR1=IH1

Vres=-3VO

Vres=-3VO

-IH1-IH2

3VO

IL

IR3=IF+IH3

=IL-IH1-IH2

IR3

b) Unfaulted line

Resistive component in feederResistive componentin grounding coil

Restrain

Zero torque line for 0° RCA

c) Faulted line

Operate

Operate

Restrain

Zero torque linefor O° RCA

a) Capacitive and inductive currents with resistive components

Figure 9.25: C phase-earth fault in Petersen Coil earthed network: practical case with resistance present in XL or XC

Page 12: proetcc12

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 1 4 3 •

decision. If the wattmetric component of zero sequencepower is detected in the forward direction, it indicates afault on that feeder, while a power in the reversedirection indicates a fault elsewhere on the system. Thismethod of protection is more popular than the sensitiveearth fault method, and can provide greater securityagainst false operation due to spurious CBCT outputunder non-earth fault conditions.

Wattmetric power is calculated in practice using residualquantities instead of zero sequence ones. The resultingvalues are therefore nine times the zero sequencequantities as the residual values of current and voltageare each three times the corresponding zero sequencevalues. The equation used is:

…Equation 9.5

where:

Vres = residual voltage

Ires = residual current

Vo = zero sequence voltage

Io = zero sequence current

φ = angle between Vres and Ires

φc = relay characteristic angle setting

The current and RCA settings are as for a sensitive earthfault relay.

9.20 EXAMPLES OF TIME AND CURRENT GRADING

This section provides details of the time/current gradingof some example networks, to illustrate the process ofrelay setting calculations and relay grading. They arebased on the use of a modern numerical overcurrentrelay illustrated in Figure 9.27, with setting data takenfrom this relay.

V I

V I

res res c

O O c

× × −( )= × × × −( )

cos

cos

ϕ ϕ

ϕ ϕ 9

9.20.1 Relay Phase Fault Setting Example – IDMT Relays/Fuses

Consider the system shown in Figure 9.28.

The problem is to calculate appropriate relay settings forrelays 1-5 inclusive. Because the example is concernedwith grading, considerations such as bus-zone

• 9 •O

verc

urre

nt P

rote

ctio

n fo

r Ph

ase

and

Ear

th F

aults

Active componentof residual current:faulted feeder

Zero torque linefor O° RCA

Operate

RestrainIR1I

ILII

IR3I IH1II -IH2I

VresVV =-3VOVV

of residual current:healthy feeder

Figure 9.26: Resistive components of spill current

I>>

I>>

I>

I>

I>

I>

I

I

I

500 MVA 11kVUtility source

11kV

Max load 2800A

Utility client

Cable C1 : 5 x 3 x1c x 630mm2 XLPEZ = 0.042 + j 0.086Ω/km/cableL = 2km

3000/5

Bus A 11kV

Bus B 11kV

Bus C 11kV

150/5 200/5

C3C2

4

5

3000/1

Cables C2,C3: 1 x 3c x 185mm2XLPEZ = 0.128 + j 0.093Ω/kmL = Ikm

>

>

>I>

I>I>

I >

Max load 400A/feeder

1

500/1500/1

1000/1

3

Max load 1000A

Reactor R1 : Z=4% on 20MVA

2

Max load 190AMax load 130A Max load 90A

IS = 120%TMS = 0.25

IS = 110%TMS = 0.1

FS2160A

FS1125A

F2 F1

Figure 9.28: IDMT relay grading example

Figure 9.27: MiCOM P140