NORTH CAMPUS -
8701 PERRY HIGHWAY, PITTSBURGH PA. 15237
UPS AND GENERATOR UPGRADES
COMMUNITY COLLEGE OF ALLEGHENY COUNTY
ASE PROJ. NUMBER: - 1741037
CCAC PROJ. NO.: - 13-C003n5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
MWM
MWM
DEB
ELECTRICAL DATA SHEET
E001
GENERAL ELECTRICAL NOTES:GENERAL: UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL WORK SHOWN ON THE ELECTRICAL DRAWINGS ISNEW WORK TO BE PROVIDED UNDER THIS CONTRACT.
DEMOLITION: SEE "ELECTRICAL GENERAL DEMOLITION NOTES" SHEET E.001 FOR ADDITIONAL DEMOLITIONREQUIREMENTS.
COORDINATION: COORDINATE AND COOPERATE WITH ALL TRADES ON THE PROJECT.
RECORD DRAWINGS: SECURE AN EXTRA SET OF ELECTRICAL DRAWINGS TO BE KEPT ON SITE AND MARK, DAILY, THEDRAWINGS IN RED AS THE PROJECT PROGRESSES IN ORDER TO KEEP AN ACCURATE RECORD OF ALL DEVIATIONSBETWEEN THE WORK SHOWN ON THE DRAWINGS AND THE WORK WHICH IS ACTUALLY INSTALLED. THESE MARKEDDRAWINGS SHALL REFLECT ANY AND ALL CHANGES AND REVISIONS TO THE ORIGINAL DESIGN WHICH EXISTS INTHE COMPLETED WORK. DELIVER THE MARKED DRAWINGS TO THE <ARCHITECT/ENGINEER> AT PROJECT CLOSE-OUT.
TESTS: TEST ALL WIRING FOR CONTINUITY AND GROUNDS BEFORE CONNECTING ANY FIXTURES OR DEVICES.PERFORM INSULATION RESISTANCE TESTS ON ALL WIRING #8 OR LARGER TO ENSURE THAT ALL PORTIONS ARE FREEFROM SHORT-CIRCUITS AND GROUNDS.
INSPECTIONS: ARRANGE ALL NECESSARY INSPECTIONS. DELIVER ALL REQUIRED INSPECTION CERTIFICATES TO THEOWNER.
GROUNDING: PROVIDE GROUNDING IN ACCORDANCE WITH THE NEC FOR THE ELECTRICAL SYSTEM INCLUDINGEQUIPMENT FRAMES CONDUITS, SWITCHES, CONTROLLERS, WIRE-WAYS, NEUTRAL CONDUCTORS, AND OTHEREQUIPMENT. PROVIDE A GROUNDING CONDUCTOR IN ALL POWER CIRCUITS.
LABELS: PROVIDE LABELS FOR ALL PANELBOARDS, CABINETS, SAFETY SWITCHES, MOTOR-DISCONNECT SWITCHES,AND MOTOR CONTROLLERS. LABELS SHALL BE MACHINE ENGRAVED, LAMINATED PLASTIC, PERMANENTLYATTACHED WITH SELF-TAPPING SCREWS OR RIVETS. DO NOT USE SELF-ADHESIVE LABELS.
J-BOX LABELING: LABEL ALL JUNCTION BOXES WITH PERMANENT MARKER IDENTIFYING CIRCUIT NUMBER ANDPANELBOARD OF CIRCUITS WITHIN.
PANEL DIRECTORY: PROVIDE TYPEWRITTEN PANELBOARD DIRECTORY CARD IN EACH PANELBOARD INCLUDINGEXISTING PANELBOARDS MODIFIED FOR THIS PROJECT WITH CIRCUIT LOAD INFORMATION AND ROOM NUMBERCLEARLY IDENTIFIED. USE ACTUAL ROOM NUMBERS IN THE BUILDING, NOT THE ROOM NUMBERS SHOWN ON THECONTRACT DRAWINGS, AS THEY ARE OFTEN DIFFERENT.
MOTOR COORDINATION: MOTORS, MOTOR STARTERS, CONTROLLERS, INTEGRAL DISCONNECT SWITCHES, ANDCONTACTORS SHALL BE PROVIDED WITH THEIR RESPECTIVE PIECES OF EQUIPMENT BY THE EQUIPMENT SUPPLIER.COMMUNICATE WITH THE TRADES PROVIDING THE EQUIPMENT, VERIFYING ALL REQUIREMENTS, PROVIDE ALLELECTRICAL CONNECTIONS REQUIRED THEREIN, AND INSTALL MOTOR STARTERS.
MOTOR DISCONNECTS: ALL MOTORS SHALL HAVE DISCONNECTING MEANS.
MOTOR FUSE PROTECTION: WHERE FUSE PROTECTION IS SPECIFICALLY REQUIRED BY THE EQUIPMENTMANUFACTURER, PROVIDE FUSE SWITCHES IN LIEU OF NON-FUSE SWITCHES OR IN LIEU OF ENCLOSED CIRCUITBREAKERS, OR OTHER DEVICES INDICATED.
CONNECTION DETAILS: SECURE APPROVED SHOP DRAWINGS SHOWING WIRING DIAGRAMS, ROUGH-IN AND HOOK UPDETAILS FROM OTHER INVOLVED CONTRACTORS FOR EQUIPMENT WHICH MUST BE CONNECTED ELECTRICALLY.
EQUIPMENT DETAILS: MECHANICAL EQUIPMENT WILL BE FURNISHED AND INSTALLED BY THE MECHANICALCONTRACTOR. THE LOCATIONS SHOWN ON THE ELECTRICAL DRAWINGS ARE APPROXIMATE. COORDINATE WITH THEMECHANICAL CONTRACTOR TO DETERMINE THE EXACT LOCATION OF EACH PIECE OF EQUIPMENT AND DETERMINETHE EXACT ROUGH-IN AND CONNECTION REQUIREMENTS.
STARTER MOUNTING: WHERE AN INDIVIDUALLY MOUNTED SAFETY SWITCH, STARTER OR CIRCUIT BREAKER IS SHOWNADJACENT TO ITS RESPECTIVE LOAD AND NOT MOUNTED ON A WALL, PROVIDE ALL SUPPORTS, BRACKETS,ANCHORING, ETC. NECESSARY TO PROPERLY SUPPORT THE DEVICE.
LIGHTING ARRANGEMENT: ARRANGE LIGHTING FIXTURES IN ACCORDANCE WITH THE ARCHITECTURAL REFLECTEDCEILING PLANS.
LIGHTING COORDINATION: COORDINATE LIGHTING FIXTURES WITH GRILLES, DIFFUSERS, SPRINKLER HEADS, ANDACCESS PANELS, ETC.
MATERIAL COORDINATION: VERIFY CEILING AND WALL CONSTRUCTION AND MATERIAL PRIOR TO ORDERING LIGHTFIXTURES OR OTHER DEVICES TO ENSURE PROPER FIXTURES OR DEVICE IS FURNISHED TO MATCH CONSTRUCTION.
MOUNTING HEIGHTS: MOUNTING HEIGHTS INDICATED ARE FROM THE FINISHED FLOOR TO THE CENTERLINE OF THEWIRING DEVICE UNLESS OTHERWISE NOTED. MOUNTING HEIGHTS OF LIGHTING FIXTURES AND FIRE ALARM DEVICESARE TO THE BOTTOM OF THE FIXTURE OR DEVICE UNLESS OTHERWISE NOTED.
DEVICE LOCATIONS: COORDINATE LOCATIONS OF SWITCHES, RECEPTACLES, AND TELE/DATA OUTLETS WITH OTHERWALL MOUNTED DEVICES SUCH AS THERMOSTATS AND CONTROL STATIONS. DO NOT MOUNT WIRING DEVICESBACK TO BACK. PROVIDE MINIMUM OF ONE STUD SEPARATION.
EWC RECEPTACLES: RECEPTACLES FOR ELECTRIC WATER COOLERS (EWC) SHALL BE INSTALLED OUT OF VIEW ANDBEHIND THE EWC ENCLOSURE. VERIFY THE MOUNTING HEIGHT WITH THE EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.
DEVICE COORDINATION: THOROUGHLY REVIEW AND COORDINATE ALL CASEWORK, DOOR SWINGS, AND CABINETDRAWINGS AND ARCHITECTURAL ELEVATIONS WITH DEVICE LOCATIONS PRIOR TO ROUGH-IN OF OUTLET BOXES.
BARRIERS: WHERE A MULTIPLE GANG BOX HAS CIRCUITS OF DIFFERENT VOLTAGES OR SYSTEMS WHICH AREREQUIRED TO BE SEPARATED, PROVIDE THE CODE-REQUIRED SEPARATION USING A FULL HEIGHT AND DEPTHBARRIER PLATE.
FIRE PROOFING: FOR ANY WALL OR FLOOR PENETRATIONS THROUGH FIRE RATED STRUCTURES PROVIDEFIRE-PROOFING TO SEAL ALL THE PENETRATIONS AFTER THE CONDUIT HAS BEEN INSTALLED. FIRE PROOFING FORPENETRATIONS SHALL BE UL APPROVED PER THE THE PENETRATION MADE IN ORDER TO MAINTAIN FIRE RATEDINTEGRITY OF THE STRUCTURE.
ELECTRICAL GENERAL DEMOLITION NOTES:GENERAL: DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND FIELDINVESTIGATION PRIOR TO DEMOLITION. VISIT THE EXISTING BUILDING PRIOR TO BID INORDER TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND IN ORDER TOAVOID CONFLICTS.
DASHED ITEMS: ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS ARE EXISTINGAND SHALL BE REMOVED COMPLETE INCLUDING BOXES, CONDUIT, WIRE, FASTENERS,AND ASSOCIATED APPURTENANCES UON.
SOLID ITEMS: ALL ITEMS SHOWN SOLID ON DEMOLITION PLANS ARE EXISTING TOREMAIN.
CIRCUITING TO REMAIN: EXISTING CIRCUITING TO REMAIN SHALL BE REROUTED ORRECONNECTED, AS REQUIRED, WHERE AFFECTED BY NEW WORK IN ORDER TOMAINTAIN CONTINUITY OF CIRCUIT.
REUSE OF EXISTING CIRCUITRY: EXISTING CIRCUITRY SERVING LIGHTING FIXTURESAND/OR RECEPTACLES FOR A GIVEN AREA SHALL BE REUSED WHERE CONVENIENT TOSERVE THE NEW LAYOUT. PROVIDE CIRCUIT MODIFICATIONS INDICATED OR ASOTHERWISE REQUIRED TO MAINTAIN THE CONTINUITY OF THE EXISTING CIRCUITS THATREMAIN.
EXISTING CONDUIT: ALL EXISTING CONDUITS AND WIRING THAT WILL NOT BE REUSEDSHALL BE REMOVED WHERE THEY WILL BE EXPOSED UPON COMPLETION OF NEWWORK. EXISTING CONDUIT TO REMAIN CONCEALED IN WALLS SHALL BE ABANDONED.EXISTING CONDUIT TO REMAIN BELOW FLOOR SLAB SHALL BE CUT OFF ONE INCHBELOW ROUGH FLOOR AND GROUTED FLUSH. ALL EXISTING WIRING IN CONDUITS TOBE ABANDONED SHALL BE DISCONNECTED FROM POWER SOURCE AND REMOVED.
REPAIR DAMAGE: EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS. REPAIR, AT NOADDITIONAL COST TO OWNER, ANY DAMAGE CAUSED TO EXISTING CONSTRUCTIONAND/OR EQUIPMENT TO REMAIN.
ASSOCIATED APPURTENANCES: REMOVE ALL ELECTRICAL APPURTENANCES(DISCONNECTS, STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED WITH EQUIPMENT TOBE REMOVED BY OTHERS.
KNOCKOUT PLUGS AND COVERS: ALL CONDUIT REMOVED SHALL BE REMOVED IN ITSENTIRETY, INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING HARDWARE, ETC.PROVIDE CONDUIT PLUGS AND BLANKS FOR ALL OPENINGS CREATED BY THEREMOVAL OF CONDUIT. PROVIDE BLANK COVER PLATES FOR ALL OPENED OUTLETBOXES CREATED BY THE REMOVAL OF THE EQUIPMENT AND/OR DEVICES.
DEMOLISHED MATERIALS: ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BERELOCATED OR DESIGNATED TO BE TURNED OVER TO THE OWNER, SHALL BECOMEPROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED COMPLETELY FROM THESITE.
SCHEDULE OUTAGES: ALL WORK AND ALL POWER OUTAGES IN THE EXISTINGBUILDING SHALL BE SCHEDULES AT TIMES CONVENIENT TO THE OWNER.
NOTIFICATION: NOTIFY THE OWNER PRIOR TO TURNING OFF ANY CIRCUITS.
EXISTING CIRCUITS: IF DURING THE COURSE OF CONSTRUCTION, IT IS DETERMINED BYTHE CONTRACTOR THAT AN EXISTING CIRCUIT BECOMES SPARE, THE CONTRACTORSHALL UPDATE THE PANELBOARD DIRECTORY TO INDICATE SUCH, EVEN IF IT IS NOTEXPLICITLY MARKED ON THE ELECTRICAL PLANS.
ELECTRICAL PANELBOARD
JUNCTION BOX - ABOVE CEILINGS OR FLUSH IN WALLS.
POWER
ELECTRICAL CIRCUIT RUN IN CONDUIT AND CIRCUIT HOMERUN TOPANELBOARD (PANEL AND CIRCUIT DESIGNATION AS INDICATED).AS A MINIMUM CONDITION, EACH SINGLE PHASE CIRCUIT SHALLHAVE 1 #12 PHASE CONDUCTOR, 1 #12 NEUTRAL CONDUCTOR, AND 1#12 GROUNDING CONDUCTOR IN 3/4" CONDUIT. PROVIDEADDITIONAL PHASE CONDUCTORS AS REQUIRED FOR "MULTIPLEPHASED" ELECTRICAL LOADS. PROVIDE ADDITIONAL "SWITCH LEG"CONDUCTORS TO PROVIDE THE LIGHT FIXTURE CONTROLINDICATED. MULTIPLE SINGLE PHASE CONDUCTORS SHALL BEGROUPED TOGETHER IN A COMMON CONDUIT IN ACCORDANCEWITH THE NEC AND AT THE CONTRACTOR'S DISCRETION. NEUTRALAND GROUNDING CONDUCTORS SHALL BE SHARED AS ALLOWEDBY THE NEC. CONDUIT LARGER THAN 3/4" AND CONDUCTORSLARGER THAN #12 SHALL BE AS INDICATED.
GENERALKEYED NEW WORK NOTE.
EQUIPMENT CONNECTION.
DRY-TYPE TRANSFORMER
FUSE SIZE (AMPS), N.F. INDICATES NON-FUSED
DISCONNECT SWITCH - SIZE AS INDICATED ON PLANS
SIZE (AMPS)
30/2/20/3R
No. OF POLES
NEMA RATING (IF OTHER THAN 1)
E DUPLEX RECEPTACLE, 20A, 120V, 18"AFF, UON. SUBSCRIPT "E"DENOTES RECEPTACLE ON EMERGENCY POWER. EMERGENCYRECEPTACLE SHALL BE RED.
MOTOR CONNECTION.
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH,MOUNT WITHIN SITE OF MOTOR 5'-0"AFF, MAXIMUM, UON.
SINGLE RECEPTACLE, 20A, 120V, 18"AFF, UON.ABOVE FINISHED FLOORAFF
ABBREVIATIONSAMPEREA
ABOVE FINISHED GRADEAFGAIR HANDLING UNITAHU
AIC AMPERE INTERRUPTING CURRENTATS AUTOMATIC TRANSFER SWITCHAV AUDIO/VISUALBFG BELOW FINISHED GRADEC CONDUITCATV CABLE ANTENNA TELEVISION
CFL COMPACT FLUORESCENTCKT CIRCUITEBU EMERGENCY BATTERY UNITEC EMPTY CONDUIT
ECB ENCLOSED CIRCUIT BREAKEREF EXHAUST FANERU ENERGY RECOVERY UNITEQUIP EQUIPMENTETR EXISTING TO REMAINEWC ELECTRIC WATER COOLEREWH ELECTRIC WATER HEATEREXIST EXISTINGFHP FRACTIONAL HORSE POWERFLA FULL LOAD AMPSGC GENERAL CONTRACTORGFI GROUND FAULT CIRCUIT
GND GROUNDHID HIGH INTENSITY DISCHARGE
KVA KILO-VOLT AMPEREKW KILO-WATTLC LIGHTING CONTACTORLTG LIGHTINGMAU MAKE UP AIR UNITMCA MINIMUM CIRCUIT AMPSMC MECHANICAL CONTACTORMC METAL CLADMCB MAIN CIRCUIT BREAKERMFR MANUFACTURERMLO MAIN LUGS ONLYMTD MOUNTEDNEC NATIONAL ELECTRICAL CODENF NON-FUSEDNIC NOT IN CONTRACTNL NIGHT LIGHTNTS NOT TO SCALEOC ON CENTEROFCI OWNER FURNISHED
CONTRACTOR INSTALLEDP POLE
PCP PUMP CONTROL PANELPF POWER FACTORPL PROPERTY LINEPNL PANELPNLBD PANELBOARDØ PHASEPRI PRIMARYRECPRTU ROOF TOP UNITSE SERVICE ENTRANCESEC SECONDARYTBB TELEPHONE BACKBOARD
TVSS TRANSIENT VOLTAGE
TYP TYPICALUON UNLESS OTHERWISE NOTEDV VOLTSVAC VOLTS ALTERNATING CURRENTVAV VARIABLE AIR VOLUMEVDC VOLTS DIRECT CURRENT
CCTV CLOSED CIRCUIT TELEVISIONCB CIRCUIT BREAKER
EC ELECTRICAL CONTRACTOR
HP HORSE POWER/HEAT PUMPHVAC HEATING, VENTILATING,
IG ISOLATED GROUNDJB JUNCTION BOX
PC PLUMBING CONTRACTOR
AND AIR CONDITIONING
VFD VARIABLE FREQUENCY DRIVEW WATTS/WIREWG WIRE GUARDWP WEATHERPROOFXFMR TRANSFORMER
SURGE SUPPRESSER
TR TAMPER RESISTANT
RECEPTACLE
J
E
1
INTERRUPTER
CLEAN UP: ON PROJECT CLOSE-OUT, CLEAN ALL ELECTRICAL DEVICES, LIGHTING FIXTURES, LAMPS AND LENSES,AND REMOVE ALL PAINT SPATTERS FROM DEVICES, FIXTURES, AND PLATES. REPLACE ALL INOPERATIVE LAMPS.
OWNER FURNISHED EQUIPMENT: CONTRACTOR SHALL OBTAIN CUT SHEETS, INSTALLATION DATA, AND ROUGH-INREQUIREMENTS FOR OWNER FURNISHED, CONTRACTOR INSTALLED EQUIPMENT AND COORDINATE ROUGH-IN ANDPOWER REQUIREMENTS WITH THE OWNER'S REPRESENTATIVE PRIOR TO STARTING ANY ASSOCIATED WORK.
CONDUIT ROUTING: ALL CONDUIT RUN OVERHEAD SHALL BE RUN AT THE BOTTOM OF THE FLOOR, ROOF STRUCTURE,OR LOWEST CHORD OF JOIST SPACE (AS APPLICABLE) ABOVE IN ORDER TO AVOID CONFLICTS WITH OTHER TRADES.
WIRING DEVICES: ALL RECEPTACLES AND SWITCHES SHALL BE LABELED WITH PLASTIC LAMINATED LABEL WITH THEPANELBOARD DESIGNATION AND CIRCUIT NUMBER FROM WHICH IT IS FED.
EQUIPMENT DEMONSTRATION: PROVIDE A DEMONSTRATION OF THE OPERATION OF ALL ELECTRICAL COMPONENTSUPON REQUEST OF THE OWNER.
CEILING PLENUM: ALL WIRING THAT WILL NOT BE RUN IN CONDUIT SHALL BE PLENUM RATED.
DATE
REVISIONS
NO.
DESIGNED:
DRAWN:
DATE:
CHECKED:
SCALE:
07-21-17
AS NOTED
800 Allegheny Avenue Pittsburgh, Pennsylvania 15233
DRAWING NUMBER:
NORTH CAMPUS -
8701 PERRY HIGHWAY, PITTSBURGH PA. 15237
UPS AND GENERATOR UPGRADES
COMMUNITY COLLEGE OF ALLEGHENY COUNTY
ASE PROJ. NUMBER: - 1741037
CCAC PROJ. NO.: - 13-C003n5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
MWM
MWM
DEB
ELECTRICAL SPECIFICATIONS
E002
ELECTRICAL SPECIFICATIONS
A. GENERAL PROVISIONS
1. REQUIREMENTS SPECIFIED IN DIVISION 1, INSTRUCTIONS TO BIDDERS, SUPPLEMENTAL GENERALCONDITIONS, SPECIAL CONDITIONS, ADDENDA, ALTERNATES, CONTRACT AND PROPOSAL, ALONGWITH DIVISION 16 AND ALL IT'S SECTIONS, COMPRISE THE CONTRACT DOCUMENTS FOR THEELECTRICAL CONTRACT. DRAWINGS AND ALL THEIR REVISIONS UP TO THE BID SUBMITTAL DATEBECOME A BINDING PART OF THE CONTRACT, ALONG WITH THESE SPECIFICATIONS AS THOUGH THEYWERE ONE, AND ANYTHING IMPLIED BY THE SPECIFICATIONS AS THOUGH SHALL BE INTERPRETED ASALSO IMPLIED BY THE DRAWINGS AND VICE VERSA. PROVIDE NECESSARY ITEMS FOR A COMPLETEINSTALLATION OF ALL ELECTRICALLY OPERATED EQUIPMENT LISTED IN THE SPECIFICATIONS ORSHOWN ON THE DRAWINGS.
2. THE ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING AND EQUIPMENT DRAWINGS ANDSPECIFICATIONS ARE INCORPORATED INTO, AND BECOME A PART OF THIS DIVISION. THISCONTRACTOR SHALL EXAMINE ALL SUCH DRAWINGS AND SPECIFICATIONS AND BECOMETHOROUGHLY FAMILIAR WITH THE PROVISIONS CONTAINED THEREIN. THE SUBMISSION OF THE BIDSHALL INDICATE SUCH KNOWLEDGE.
3. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. THEY ARE INTENDED TO SHOW THE APPROXIMATELOCATIONS OF EQUIPMENT AND CONDUIT. DIMENSIONS GIVEN ON THE PLANS, IN FIGURES, SHALLTAKE PRECEDENCE OVER SCALED DIMENSIONS AND SHALL BE VERIFIED IN THE FIELD. THEELECTRICAL CONTRACTOR SHALL LAYOUT ALL EQUIPMENT ROOMS TO MAKE SURE THE EQUIPMENT,AS PURCHASED, FITS IN THE ROOM OR SPACE SHOWN AND HAS ALL CLEARANCES REQUIRED BY THENEC. EXACT LOCATION OF ALL EQUIPMENT SHALL BE VERIFIED IN THE FIELD AND ROUTING OFCONDUITS SHALL SUIT FIELD CONDITIONS.
4. UNTIL TIME OF INSTALLATION, THE ARCHITECT RESERVES THE RIGHT TO MAKE MINOR CHANGES IN THELOCATION OF CONDUIT AND EQUIPMENT WITHOUT ADDITIONAL COST TO THE CONTRACT.
5. THE ELECTRICAL DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER.MATERIAL AND LABOR NECESSARY TO THE PROJECT SHALL BE FURNISHED AND INSTALLED EVENTHOUGH NOT SPECIFICALLY MENTIONED IN BOTH. LABOR AND/OR MATERIALS NEITHER SHOWN NORSPECIFIED, BUT OBVIOUSLY NECESSARY FOR THE COMPLETION AND PROPER FUNCTIONING OF THESYSTEM, SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
6. ARRANGE ALL EQUIPMENT SUBSTANTIALLY AS SHOWN ON THE DRAWINGS. MAKE DEVIATIONS ONLYWHERE NECESSARY TO AVOID INTERFERENCE. CHECK ALL EQUIPMENT SIZES AGAINST AVAILABLESPACE PRIOR TO SHIPMENT TO AVOID INTERFERENCE.
7. EXAMINE THE WORK OF OTHER TRADES INSOFAR AS THEIR WORK COMES IN CONTACT WITH OR ISCOVERED BY THIS WORK. IN NO CASE ATTACH TO, OR FINISH AGAINST ANY DEFECTIVE WORK ORINSTALL WORK IN A MANNER WHICH WILL PREVENT PROPER INSTALLATION OF THE WORK OF OTHERTRADES.
8. ELECTRICAL CONTRACTOR SHALL VERIFY WITH OTHER TRADES ALL ELECTRICAL CONNECTIONS.CONTRACTOR SHALL VERIFY VOLTAGE, PHASE AND HORSEPOWER AND SHALL NOTIFY ENGINEER OFDISCREPANCIES PRIOR TO START OF WORK. ELECTRICAL CONTRACTOR SHALL PROVIDEDISCONNECTING MEANS AND OVERLOAD PROTECTION FOR ALL EQUIPMENT UNLESS FURNISHEDINTEGRAL WITH EQUIPMENT PACKAGE.
9. IT IS THE INTENT OF THESE DRAWINGS THAT THIS BE A COMPLETE ELECTRICAL JOB, ANY ERRORS OROMISSIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO BIDDING THE JOB.
B. VISIT TO THE SITE
1. THIS CONTRACTOR SHALL VISIT THE SITE OF THE WORK AND FAMILIARIZE THEMSELVES WITH ALLCONDITIONS AFFECTING THIS CONTRACTORS WORK. THE SUBMISSION OF THE PROPOSAL SHALLINDICATE SUCH KNOWLEDGE. NO ADDITIONAL PAYMENT SHALL BE MADE ON CLAIMS THAT ARISEFROM A LACK OF KNOWLEDGE OF THE EXISTING CONDITIONS.
C. CODE AND PERMITS
1. INSTALLATION SHALL BE IN FULL ACCORDANCE WITH ALL CODES, RULES AND REGULATIONS OFMUNICIPAL, CITY, COUNTY, STATE AND PUBLIC UTILITIES AND ALL OTHER AUTHORITIES HAVINGJURISDICTION OVER THE PREMISES.
2. COMPLY WITH ANY SPECIFICATION REQUIREMENTS THAT ARE IN EXCESS, BUT NOT IN CONFLICT WITHCODE REQUIREMENTS.
3. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, PLAN REVIEWS, AND CERTIFICATES OFINSPECTION IN CONNECTION WITH THE WORK REQUIRED BY THE FOREGOING AUTHORITIES. BEFOREFINAL PAYMENT OF THE CONTRACT IS ALLOWED, ALL CERTIFICATES SHALL BE DELIVERED TO THEARCHITECT IN DUPLICATE.
4. ELECTRICAL MATERIAL AND EQUIPMENT SHALL BEAR THE UL LABEL EXCEPT WHERE UL DOES NOTLABEL SUCH TYPES OF MATERIAL AND EQUIPMENT.
D. SHOP DRAWING SUBMITTALS
1. THE ELECTRICAL CONTRACTOR SHALL SUBMIT FIVE (5) SETS OF SHOP DRAWINGS. THE SHOPDRAWINGS OF THE FOLLOWING EQUIPMENT USING THE INDICATED NUMBERING SYSTEM AND TITLES,SHALL BE SUBMITTED THROUGH THE ARCHITECT TO THE ENGINEER AND THEN RESUBMITTED FOR FINALAPPROVAL IF NECESSARY. SHOP DRAWINGS SHALL BE SUBMITTED FOR THE FOLLOWING ITEMS:
a. WIRING DEVICESb. PANEL BOARDS, STARTERS, SAFETY SWITCHES
2. ALL SUBMITTED SHOP DRAWINGS (MANUFACTURERS' EQUIPMENT DESCRIPTIVE SHEETS OR VENDORS'PREPARED DRAWINGS) SHALL HAVE THE GENERAL CONTRACTOR'S OR SUBCONTRACTOR'S STAMP OFAPPROVAL INDICATING THAT THE ITEM SUBMITTED IS AS CALLED FOR ON THE PLANS ANDSPECIFICATION, IS APPROVED BY THE GENERAL CONTRACTOR OR SUBCONTRACTOR, THE DATE OFAPPROVAL AND INITIALED BY THE PERSON APPROVING THE SUBMITTAL AND THE NAME OF THECOMPANY SUBMITTING SAID EQUIPMENT FOR APPROVAL.
3. SUBMIT BOUND BROCHURES COMPLETE WITH A TABLE OF CONTENTS. LOOSE OR STAPLED TOGETHERSHEETS ARE NOT ACCEPTABLE. ANY SUBMITTALS NOT IN BROCHURE FORM OR NOT AS SPECIFIEDSHALL BE RETURNED AT THE CONTRACTORS EXPENSE FOR RESUBMITTAL.
4. ALL DESCRIPTIVE LITERATURE SHALL BE SUBMITTED IN A THREE (3) HOLE BROCHURE WITH A COVERIDENTIFYING THE FOLLOWING:
a. NAME OF THE JOB.b. LOCATION OF THE JOB, ADDRESS, CITY AND STATEc. NAME AND ADDRESS OF THE COMPANY SUBMITTING THE BROCHURES.d. DATE OF THE SUBMITTAL.
5. EVERY EFFORT SHALL BE MADE, IN CHECKING THE SHOP DRAWINGS, TO DETECT AND CORRECT ALLERRORS, OMISSIONS AND INACCURACIES. FAILURE TO DO THIS WILL NOT RELIEVE THE ELECTRICALCONTRACTOR OF THE RESPONSIBILITY FOR THE PROPER AND COMPLETE INSTALLATION INACCORDANCE WITH THE CONTRACT DOCUMENTS.
E. AS-BUILT DRAWINGS
1. SUBMIT TO THE ARCHITECT ON SET OF REPRODUCIBLE ELECTRICAL DRAWINGS SHOWING THE AS BUILTCONDITIONS.
F. STANDARDS AND SUBSTITUTIONS
1. WHEREVER THE WORDS "APPROVED BY", "APPROVED EQUAL", "AS DIRECTED" OR SIMILARPHRASES ARE USED IN THE FOLLOWING SPECIFICATIONS, THEY SHALL BE UNDERSTOOD TOREFER TO THE OWNER AS THE APPROVING AGENCY. THE NAME OR MAKE OF ANY EQUIPMENTOR MATERIALS NAMED IN THIS SPECIFICATION (WHETHER OR NOT THE WORDS "OR APPROVEDEQUAL" ARE USED) SHALL BE KNOWN AS THE "STANDARD".
2. THESE SPECIFICATIONS ESTABLISH QUALITY STANDARDS OF MATERIALS AND EQUIPMENT TO BEPROVIDED. SPECIFIC ITEMS ARE IDENTIFIED BY MANUFACTURER, TRADE NAME OR CATALOGDESIGNATION. THE CONTRACTOR SHALL SUBMIT THE BASE BID PRICE BASED UPON STANDARDSPECIFIED EQUIPMENT DESCRIBED HEREIN AND AS DETAILED ON DRAWINGS AND ASSOCIATEDCONTRACT DOCUMENTS. THESE SPECIFICATIONS ARE NOT TO BE CONSIDERED PROPRIETARY.THE CONTRACTOR MAY SUBMIT INFORMATION ON MATERIALS AND MANUFACTURERS (OTHERTHAN THOSE LISTED) FOR REVIEW BY THE OWNER, ARCHITECT AND ENGINEER NO LATER THANTEN (10) DAYS BEFORE BIDS ARE SUBMITTED. IN ADDITION, SAMPLES OF THE PROPOSEDEQUIPMENT MAY BE REQUIRED TO BE SUBMITTED TO THE ENGINEER FOR REVIEW NO LATER THANTEN (10) DAYS BEFORE BIDS ARE SUBMITTED. MANUFACTURERS OF PRODUCTS ACCEPTED BYTHE OWNER, ARCHITECT, AND ENGINEER WILL BE LISTED IN AN ADDENDUM TO THESPECIFICATIONS AS AN ACCEPTABLE SUBSTITUTION. EQUIPMENT ACCEPTED AS DETAILEDBELOW AND SHALL BE SHOWN AS A SEPARATE ADD OR DEDUCT PRICE TO BE FACTORED INTOTHE BASE PRICE BY THE ARCHITECT AND OWNER IF ACCEPTED.
3. SHOULD THE CONTRACTOR PROPOSE TO FURNISH MATERIALS AND EQUIPMENT OTHER THANTHOSE SPECIFIED OR APPROVED BY ADDENDUM, SUBMIT A WRITTEN REQUEST FORSUBSTITUTION TO THE OWNER, ARCHITECT, AND ENGINEER AT BID OPENING. THE REQUESTSHALL BE AN ALTERNATE TO THE ORIGINAL BID; BE ACCOMPANIED WITH COMPLETE DESCRIPTIVE(MANUFACTURER, BRAND NAME, CATALOG NUMBER, ETC.) AND TECHNICAL DATA FOR ALLITEMS. FAILURE BY THIS CONTRACTOR TO SUBMIT THE REQUISITE DOCUMENTATION DETAILEDABOVE SHALE BE UNDERSTOOD BY THE OWNER, ARCHITECT AND ENGINEER TO INDICATE THATSUBSTITUTE EQUIPMENT WILL NOT BE PRESENTED BY THE CONTRACTOR FOR CONSIDERATION.SUCH SUBSTITUTIONS WILL NOT BE CONSIDERED AFTER THE BID OPENING DATE AND DELAY OFTHE PROJECT WILL NOT BE PERMITTED FOR FURTHER INSPECTION AND EVALUATION AFTER THISDATE.
4. WHERE SUCH SUBSTITUTIONS ALTER THE DESIGN OR SPACE REQUIREMENTS INDICATED ON THEDRAWINGS, INCLUDE ALL ITEMS OF COST FOR THE REVISED DESIGN AND CONSTRUCTIONINCLUDING COST OF ALL ALLIED TRADES INVOLVED.
5. ACCEPTANCE OR REJECTION OF THE PROPOSED SUBSTITUTIONS SHALL BE SUBJECT TOAPPROVAL OF THE OWNER, ARCHITECT, AND ENGINEER. IF REQUESTED, THE CONTRACTORSHALL SUBMIT (AT THEIR COST) INSPECTION SAMPLES OF BOTH THE SPECIFIED AND PROPOSEDSUBSTITUTE ITEMS.
6. IN ALL CASES WHERE SUBSTITUTIONS ARE PERMITTED, THE CONTRACTOR SHALL BEAR ANY EXTRACOST OF EVALUATING THE QUALITY OF THE MATERIAL AND EQUIPMENT TO BE PROVIDED.
G. TESTING AND PLACING IN SERVICE
1. ANY MATERIAL OR EQUIPMENT FAILING A TEST SHALL BE REPAIRED OR REPLACED AT THECONTRACTOR'S EXPENSE.
2. TESTS SHALL INCLUDE THE FOLLOWING:
a. MEASURE THE LOAD ON EACH PHASE OF THE MAIN SERVICE AND EACH PHASE OF EVERY FEEDERUNDER FULL LOAD CONDITIONS
b. MEASURE THE NO-LOAD AND FULL-LOAD VOLTAGES (PHASE TO PHASE, PHASE TO NEUTRAL ANDPHASE TO GROUND FOR EACH PHASE OF EACH SERVICE, OF EACH SEPARATELY DERIVED SYSTEM,AND AT EACH PANELBOARD OR TRANSFORMER).
c. MEASURE THE GROUND RESISTANCE OF THE MAIN SERVICE GROUNDING ELECTRODE AND THEGROUND RESISTANCE OF EACH SEPARATELY DERIVED SYSTEM'S GROUNDING ELECTRODE.
d. MAKE INSULATION RESISTANCE TESTS ON ALL DRY TYPE TRANSFORMERS AND MOTORS.
H. INTERFERENCES
1. BEFORE THE INSTALLATION OF ANY ITEM BEGINS, THE ELECTRICAL CONTRACTOR SHALL CAREFULLYASCERTAIN THAT IT DOES NOT INTERFERE WITH CLEARANCES FOR THE ERECTION OF FINISH BEAMS,COLUMNS, PILASTERS, WALLS OR OTHER STRUCTURAL OR ARCHITECTURAL MEMBERS AS SHOWN ONTHE ARCHITECTURAL DRAWINGS. IF ANY WORK IS INSTALLED AND THE ARCHITECTURAL DESIGNCANNOT BE FOLLOWED, THIS CONTRACTOR SHALL, AT THEIR OWN EXPENSE, MAKE CHANGES IN THEWORK AS DIRECTED BY THE ARCHITECT TO PERMIT THE COMPLETION OF THE ARCHITECTURAL WORK INACCORDANCE WITH DRAWINGS AND SPECIFICATIONS.
2. IT SHALL BE THE DUTY OF THIS CONTRACTOR TO REPORT ANY INTERFERENCES BETWEEN THISCONTRACTORS WORK AND THAT OF ANY OF THE OTHER CONTRACTORS AS SOON AS THEY AREDISCOVERED. THE ARCHITECT SHALL DETERMINE WHICH EQUIPMENT WILL BE RELOCATED,REGARDLESS OR WHICH WAS INSTALLED FIRST. THE DECISION WILL BE FINAL.
I. QUALITY ASSURANCE
1. ALL PRODUCTS SHALL BE NEW AND OF THE TYPE AND QUALITY SPECIFIED. WHERE MATERIAL,EQUIPMENT, APPARATUS OR OTHER PRODUCTS ARE SPECIFIED BY MANUFACTURER, BRAND NAME,TYPE OF CATALOG NUMBER, SUCH DESIGNATION SHALL ESTABLISH THE STANDARDS OF THE DESIREDQUALITY AND STYLE. IT IS THE INTENT OF THESE SPECIFICATIONS TO ESTABLISH A STANDARD OFQUALITY OF MATERIALS AND EQUIPMENT INSTALLED.
J. NAMEPLATES
1. CENTRAL: FURNISH AND MOUNT ON EACH PANELBOARD, SWITCHBOARD (INCLUDING BRANCHSWITCHES), LARGE JUNCTION BOX, SAFETY SWITCH, STARTER, REMOTE CONTROL, PUSH BUTTONSTATION, AND ALL SIMILAR CONTROLS, A NAMEPLATE DESCRIPTIVE OF THE EQUIPMENT OREQUIPMENT CONTROLLED.
2. PROVIDE BLACK AND WHITE NAMEPLATES CONSTRUCTED FROM LAMINATED PHENOLIC WITH A WHITECENTER CORE. LETTERS SHALL BE ENGRAVED IN THE PHENOLIC TO FORM WHITE LETTERS 3/8" HIGH.FASTEN THE NAMEPLATES WITH SCREWS AND AN ADHESIVE TYPE FASTENER.
K. MOUNTING ACCESSORIES
1. THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL ANGLE IRON, CHANNEL IRON, RODS, SUPPORTS,HANGERS, CONCRETE OR PLYWOOD REQUIRED TO INSTALL, MOUNT AND SUPPORT ANY ELECTRICALEQUIPMENT OR DEVICE CALLED FOR ON THE PLANS.
2. SUPPORTING MATERIAL SHALL BE COMPLETE WITH HANGARS, CONNECTORS, BOLTS, CLAMPS ANDNECESSARY ACCESSORIES TO MAKE A COMPLETE INSTALLATION. SUPPORTING MATERIAL SHALL BEGALVANIZED, PAINTED OR OTHERWISE SUITABLY FINISHED. PRODUCTS BY BINKLEY, STEEL CITY ORRACO WILL BE ACCEPTABLE.
3. ALL SURFACE-MOUNTED EQUIPMENT ON BLOCK WALLS SHALL BE MOUNTED ON 3/4" PLYWOODBACKBOARD. ALL FLOOR MOUNTED EQUIPMENT SHALL BE INSTALLED ON A 4" HIGH CONCRETEHOUSEKEEPING PAD.
L. EXECUTION
1. THE ELECTRICAL WORK FOR CONSTRUCTION PURPOSES SHALL CONFORM TO ALL FEDERAL (OSHA),STATE, ALL SPECIFIC SAFETY REQUIREMENTS AND THE REQUIREMENTS OF THE CURRENT EDITION OFTHE NEC.
2. CHECK THE HVAC AND PLUMBING SPECIFICATIONS FOR ELECTRICAL REQUIREMENTS AND INCLUDE THESAME IN THE CONTRACT COST.
3. EQUIPMENT CONNECTIONS, STARTERS, DISCONNECT SWITCHES, CONTROL TRANSFORMERS ANDPUSHBUTTON STATIONS FOR THE EQUIPMENT FURNISHED BY THE OWNER OR UNDER A SEPARATECONTRACT SHALL BE INSTALLED AND CONNECTED UNDER THIS DIVISION, AS INDICATED ON THECONTRACT DRAWINGS.
4. ALL CUTTING, PATCHING, EXCAVATING, BACKFILLING AND CONCRETE WORK RELATED TO THISCONTRACT WILL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. THIS CONTRACTORSHALL ASSUME THE RESPONSIBILITY OF PROVIDING THE SLEEVES, CHASES AND OPENINGSNECESSARY FOR THE ELECTRICAL INSTALLATION AND FOR THEIR REPAIR IN AN ACCEPTABLE MANNER,AS DETERMINED BY THE ARCHITECT. ALL HOLES SHALL BE CORE DRILLED. PROVIDE FIRE STOP IN ALLOPENINGS CREATED THROUGH FIRE-RATED WALLS, FLOORS OR CEILINGS.
5. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL REQUIRED ACCESS PANELSNECESSARY FOR THIS WORK. COORDINATE WITH ARCHITECT PRIOR TO INSTALLATION.
M. MATERIALS AND QUALITY OF WORK
1. ALL WORK SHALL BE INSTALLED IN A PRACTICAL AND PROFESSIONAL MANNER, BY MECHANICSSKILLED IN THE SEVERAL TRADES NECESSARY.
2. ALL MATERIALS SHALL BE NEW AND FREE FROM DEFECTS AND SHALL BE THE BEST OF THEIRSEVERAL KINDS UNLESS SPECIFIED OR INDICATED ON THE DRAWINGS TO THE CONTRARY.
3. DURING EACH PHASE AND AT THE COMPLETION OF THE CONSTRUCTION, THIS CONTRACTOR SHALLREMOVE ALL DEBRIS AND EXCESS MATERIALS CAUSED BY THIS WORK. THIS CONTRACTOR SHALLLEAVE THE AREA OF OPERATION BROOM CLEAN.
4. ALL ELECTRICAL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OR ETL LABEL.
5. THIS CONTRACTOR SHALL GUARANTEE THE QUALITY OF WORK AND MATERIALS (EXCEPT LAMPS) FORA PERIOD OF ONE YEAR FROM THE DATE OF THE BUILDING OPENING AND LEAVE THE WORK INPERFECT ORDER AT THE COMPLETION. SHOULD DEFECTS DEVELOP WITHIN THE GUARANTEE PERIOD,THE CONTRACTOR SHALL, UPON NOTICE OF THE SAME, REMEDY THE DEFECTS AND HAVE ALLDAMAGES TO OTHER WORK OR FURNISHINGS CAUSED BY THE REPAIRS CORRECTED AT THISCONTRACTORS EXPENSE TO THE CONDITION BEFORE SUCH DAMAGE.
N. SCOPE OF WORK
1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL, STORAGE, UNPACKING ANDPLACEMENT; TO INCLUDE BUT NOT LIMITED TO, THE FOLLOWING ITEMS:
a. EMERGENCY POWER.b. COMPLETE POWER DISTRIBUTION SYSTEM INCLUDING ALL PANELS, TRANSFORMERS, AND FEEDERSc. COMPLETE BRANCH CIRCUIT WIRING SYSTEM.d. COMPLETE POWER WIRING FOR ALL MECHANICAL AND PLUMBING EQUIPMENT.e. TEMPORARY ELECTRICAL POWER AND LIGHTING AS REQUIRED FOR CONSTRUCTION.f. TESTING OF ALL CABLES AND CIRCUIT WIRING AFTER INSTALLATION.g. WIRING DEVICES AND FLOOR BOXES.h. GROUNDING OF THE ELECTRICAL SYSTEM.
O. TEMPORARY SERVICE
1. THE ELECTRICAL CONTRACTOR SHALL FURNISH, INSTALL AND REMOVE AS REQUIRED ALL TEMPORARYPOWER AND TEMPORARY LIGHTING IN ALL AREAS AND INDIVIDUAL ROOMS WHEN NEEDED BY THEINDIVIDUAL TRADES IN THE PERFORMANCE OF THEIR WORK. THIS CONTRACTOR SHALL PROVIDE AMINIMUM OF TWENTY (20) FOOTCANDLES OF ILLUMINATION FOR TEMPORARY LIGHTING. ANYADDITIONAL LIGHTING REQUIRED BY INDIVIDUAL TRADES SHALL BE PROVIDED BY THE INDIVIDUALTRADES INCLUDING POWER FOR THE LIGHTING. THE ELECTRICAL WORK FOR CONSTRUCTIONPURPOSES SHALL CONFORM TO ALL FEDERAL (OSHA), STATE, SPECIFIC SAFETY REQUIREMENTS, ASWELL AS, THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE AND NATIONAL ELECTRICAL SAFETYCODE. THE ELECTRICAL CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED APPLICATIONS,PERMITS AND INSPECTIONS PERTAINING TO THIS WORK. THIS COST SHALL BE INCLUDED IN THECONTRACTOR'S PRICE.
DATE
REVISIONS
NO.
DESIGNED:
DRAWN:
DATE:
CHECKED:
SCALE:
07-21-17
AS NOTED
800 Allegheny Avenue Pittsburgh, Pennsylvania 15233
DRAWING NUMBER:
NORTH CAMPUS -
8701 PERRY HIGHWAY, PITTSBURGH PA. 15237
UPS AND GENERATOR UPGRADES
COMMUNITY COLLEGE OF ALLEGHENY COUNTY
ASE PROJ. NUMBER: - 1741037
CCAC PROJ. NO.: - 13-C003n5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
MWM
MWM
DEB
ELECTRICAL SPECIFICATIONS
E003
ELECTRICAL SPECIFICATIONS
P. RACEWAYS
1. ALL WIRE SHALL BE RUN IN ACCORDANCE WITH CODE IN CORROSION RESISTANT, RIGID, THREADED,METAL CONDUIT OR ELECTRICAL METALLIC TUBING (EMT) OR METAL CLAD (MC) CABLING UNLESSOTHERWISE SPECIFICALLY STATED HEREIN.
a. CONDUIT IN EXTERIOR WALLS, BELOW FLOOR SLAB, OR UNDERGROUND SHALL BE RIGID,THREADED, GALVANIZED, HEAVY WALL TYPE.
b. CARLON PVC TYPE 40 HEAVY WALL CONDUIT WITH GROUND WIRE MAY BE USED BELOW FLOORSLAB OR UNDERGROUND IN LIEU OF RIGID, THREADED, GALVANIZED CONDUIT. PVC 40 CONDUITSHALL NOT BE RUN IN OR ABOVE FLOOR SLAB. PVC CONDUIT SHALL TERMINATE BELOW FLOORSLAB WITH RIGID, THREADED METAL CONDUIT ADAPTER. CONDUIT ABOVE SLAB SHALL BE METAL.
c. CONDUIT RUN EXPOSED TO THE WEATHER SHALL BE HEAVY WALL, METAL THREADED TYPE.
2. CONDUIT SIZE SHALL BE 3/4" MINIMUM UNLESS NOTED OTHERWISE.
3. CONDUIT SHALL BE SECURELY FASTENED IN PLACE.
4. ALL CONDUIT SHALL BE CONCEALED IN WALLS, FLOORS AND CEILINGS WHEREVER POSSIBLE.EXPOSED CONDUIT IN FINISHED AREAS WILL NOT BE PERMITTED. EXPOSED CONDUIT WILL BEPERMITTED IN UNFINISHED AREAS WITH THE SPECIFIC APPROVAL OF THE ARCHITECT.
5. USE FLEXIBLE CONDUIT FOR THE CONNECTION TO THE RECESSED OR SEMI-RECESSED LIGHTINGFIXTURES (6' LENGTH MAXIMUM). USE LIQUID TIGHT METAL CONDUIT FOR ALL CONNECTIONS TOMOTORS AND OTHER EQUIPMENT SUBJECT TO VIBRATION AND IN AREAS SUBJECT TO MOISTURE.
6. USE WATERTIGHT JOINTS WITH BURIED AND CONCRETE ENCASED CONDUIT. ALL BURIED CONDUITSOUTSIDE OF BUILDINGS SHALL HAVE A MINIMUM OF 24" OF COVER. METAL CONDUITS BURIED INEARTH SHALL BE PAINTED WITH TWO COATS OF HEAVY ASPHALTUM PAINT.
7. SUPPORT RUNS OF CONDUIT AS DETAILED IN THE APPROPRIATE TABLE OF THE NATIONAL ELECTRICALCODE.
8. INSTALL EXPOSED RUNS OF CONDUIT AND CONDUIT ABOVE LAY-IN CEILINGS PARALLEL ORPERPENDICULAR TO THE WALLS, STRUCTURAL MEMBERS OF INTERSECTIONS OF VERTICAL PLANESAND CEILINGS. PROVIDE RIGHT ANGLE TURNS USING FITTINGS OR SYMMETRICAL BENDS. SUPPORTCONDUITS WITHIN 1' OF ALL CHANGES INDIRECTION.
9. IF A CONDUIT IS SUSPENDED, IT SHALL BE SUPPORTED ON TRAPEZE HANGERS WHICH USE"ALL-THREAD" RODS FROM THE STRUCTURAL STEEL. THE USE OF CEILING SUPPORT WIRE OR SIMILARMATERIAL WILL NOT BE ACCEPTED.
10. INSTALL EMPTY CONDUIT FOR FUTURE USE AS INDICATED ON THE DRAWINGS. CONDUIT SHALL BECOMPLETE WITH JETLINE OR PULL ROPE, JUNCTION/OUTLET BOXES, TILE RINGS AND APPROPRIATECOVER PLATES.
11. PROVIDE PITCHPOCKETS WHERE CONDUITS PENETRATE THE ROOF.
12. THREAD LUBRICATION/SEALANT IS REQUIRED ON OUTDOOR AND UNDERGROUND THREADED METALJOINTS.
13. INSTALL FIRE SEAL FITTINGS WHERE CONDUITS PENETRATE CONCRETE FLOOR SLABS, MASONRYWALLS, OR CEILINGS REQUIRED TO BE FIRE RATED.
14. HORIZONTAL PORTION OF CONDUIT EXPOSED ON THE ROOF AND FEEDING EQUIPMENT SHALL NOT BEMORE THAN 5'-0" UNLESS THE WRITTEN APPROVAL FROM ARCHITECT OR ENGINEER IS OBTAINED.
Q. PULL AND JUNCTION BOXES
1. INSTALL PULL AND JUNCTION BOXES WHERE SHOWN ON THE DRAWINGS, AND WHERE REQUIRED FORCHANGES IN DIRECTION, AT JUNCTION POINTS AND TO FACILITATE WIRE PULLING. FURNISH BOX SIZESIN ACCORDANCE WITH NEC UNLESS LARGER BOXES ARE INDICATED ON THE DRAWINGS.
2. PROVIDE STEEL BOXES AND REMOVABLE COVERS OF CODE GAUGE, HOT ROLLED SHEET STEEL, HOTDIPPED GALVANIZED INSIDE AND OUTSIDE, FOR ABOVE GROUND WORK. FURNISH WEATHERPROOFBOXES WHEN INSTALLED ABOVE GROUND OUTSIDE.
3. PROVIDE CAST IRON BOXES, HOT DIPPED GALVANIZED INSIDE AND OUTSIDE WHERE SHOWN ON THEDRAWINGS. FURNISH REMOVABLE COVERS WITH GASKETS AND STAINLESS STEEL, BRASS, OR BRONZESCREWS.
4. PROVIDE CONCRETE BOXES FOR UNDERGROUND WORK UNLESS OTHERWISE INDICATED ON THEDRAWINGS. FURNISH STEEL FRAMES AND COVERS WITH THE COVER ATTACHED TO THE FRAME WITHHEXAGON HEAD, BRASS OR BRONZE CAP SCREWS, 3/8" IN DIAMETER. PROVIDE A RUBBER GASKET FORSEALING BETWEEN THE COVER AND THE FRAME. PAINT THE COVER WITH TWO COATS OF HEAVYASPHALTUM.
R. OUTLET BOXES
1. USE SHEET STEEL BOXES, ZINC COATED OR CADMIUM PLATED, FOR CONCEAL INTERIOR WORK.
2. USE CAST BOXES, ZINC-CADMIUM FINISH MALLEABLE IRON, FOR EXPOSED INTERIOR WORK, AND FOREXPOSED OR CONCEALED WORK IN WET, DAMP OR EXTERIOR LOCATIONS. CAST BOXES SHALL BESERIES FD BY CROUSE HINDS OR APPLETON.
3. WALL BOX SIZES (MINIMUM) SHALL BE 4" SQUARE X 2-1/2" DEEP WHERE WALL CONSTRUCTION PERMITS.WHERE WALL CONSTRUCTION DICTATES, THE WIDTH MAY BE REDUCED TO 2-1/8" OR 1-1/2" UNDERSPECIAL CONDITIONS.
4. FIXTURE OUTLETS IN CEILING (MINIMUM) SHALL BE 4" OCTAGONAL X 1-1/2" DEEP (4-11/16 OCTAGONAL X2-1/2" DEEP WHERE REQUIRED TO ACCOMMODATE LARGER CONDUIT OR LARGER NUMBER OF WIRES).
5. GANG BOXES SHALL BE ONE PIECE (MINIMUM), 2-1/8" DEEP.
6. PROVIDE CAST IRON, CONCRETE-TITE FLOOR BOXES WITH ADJUSTABLE COVERS SET FLUSH AND LEVELWITH THE FINISHED FLOOR, WITH OUTLETS AS INDICATED ON THE DRAWINGS. PROVIDE HUBBELL#8-2400, 4200, OR 4300 SERIES BOXES WITH LEVELING SCREWS. FLUSH TYPE COVERS ANDOPENINGS TO SERVE OUTLETS USED. FURNISH FLUSH CAPS FOR CLOSING OFF BOX WHEN NOT IN USE.
7. FLUSH MOUNT BOXES IN ALL FINISHED WALLS, INSTALL THE PLASTER RINGS IN DRYWALLEDPLASTERED WALLS AND RAISED COVERS AS REQUIRED IN WALLS WITH OTHER FINISHES SO THAT THECOVER PLATES FIT TIGHTLY AGAINST BOXES OR RINGS. 3/16" MAXIMUM GAPS ARE ALLOWED FORNONCOMBUSTIBLE WALLS.
8. ADJUST LOCATIONS OF OUTLETS IN MASONRY OR TILE CONSTRUCTION TO OCCUR IN THE NEARESTJOINT TO THE HEIGHT SPECIFIED. HEIGHTS SHALL MEET ADA REQUIREMENTS.
9. SUPPORT ALL BOXES TO MAINTAIN PROPER ALIGNMENT AND RIGIDITY.
10. CLEAN BOXES OF ALL FOREIGN MATTER PRIOR TO THE INSTALLATION OR WIRING OR DEVICES.
11. MOUNTING HEIGHTS ON THE DRAWING ARE TO THE CENTERLINE OF THE BOXES UNLESS OTHERWISENOTED.
S. WIRE AND CABLE UNITS
1. COLOR CODE CONDUCTORS (EXCEPT CONTROL AND INSTRUMENTATION CONDUCTORS) AS FOLLOWS: 208/120 VOLT SYSTEM 480/277 SYSTEM PHASE A BLACK BROWN PHASE B RED ORANGE PHASE C BLUE YELLOW NEUTRAL WHITE GRAY GROUND GREEN GREEN
a. #12 AND #10 CONDUCTORS SHALL HAVE CONTINUOUS INSULATION COLOR, AS LISTED ABOVE.b. COLOR CODE CONDUCTORS LARGER THAN ABOVE, WHICH DO NOT HAVE CONTINUOUS INSULATION
COLOR BY APPLICATION OF AT LEAST TWO LAPS OF COLORED TAPE ON EACH CONDUCTOR AT ALLPOINTS OF ACCESS INCLUDING JUNCTION BOXES. COLOR TAPE SHALL BE THE EQUAL OF 3MPRODUCTS SCOTCH #35.
c. CONDUCTORS SHALL BE SOFT ANNEALED COOPER INSULATED FOR 600 VOLTS UNLESSSPECIFICALLY INDICATED OTHERWISE. ALUMINUM CONDUCTORS ARE NOT ALLOWED ON THISPROJECT.
2. INSULATION TYPE SHALL BE TYPE THW FOR WIRE SIZES #8 AWG AND LARGER AND THWN FOR #10 AWGAND SMALLER. THHN SHALL NOT BE USED IN WET OR DAMP LOCATIONS.
3. FLEXIBLE CORD SHALL BE HEAVY DUTY TYPE SO WITH AN EQUIPMENT GROUND CONDUCTOR INADDITION TO THE CURRENT CARRYING CONDUCTORS.
4. PROVIDE #12 CONDUCTORS, UNLESS OTHERWISE INDICATED.
a. CONTROL CONDUCTORS SHALL BE #14 MINIMUM FOR NEC CLASS 1 AND #16 FOR NEC CLASS 11.
5. CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED.
6. CONDUCTORS #10 AWG AND SMALLER SHALL BE SOLID.
7. INSTALL WIRING IN CONDUIT.
8. CONNECT #10 AND SMALLER WIRES WITH CONSTANT PRESSURE EXPANDABLE SPRING TYPECONNECTORS, "SCOTCHLOK" BY 3M OR B-CAP BY BUCHANAN.
9. CONNECT #8 AND LARGER WIRES WITH COMPRESSION CONNECTORS OR SPLICES ASMANUFACTURERED BY BURNDY OR T&B.
10. INSULATE SPLICING CONNECTORS TO AT LEAST 200% OF THE WIRE INSULATION. USE PRE-STRETCHEDTUBING CONNECTOR INSULATORS, 3M PST FOR #2 AND LARGER CONDUCTORS.
11. PULL CONDUCTORS USING RECOGNIZED METHODS AND EQUIPMENT LEAVING AT LEAST 6" WIRE AT ALLJUNCTION BOXES FOR CONNECTIONS.
a. CLEANOUT EACH CONDUIT SYSTEM BEFORE PULLING WIRE.
12. FORM AND TIE ALL WIRING IN PANELBOARDS.
13. THERE SHALL BE NO WIRENUT JOINTS OR SPLICES MADE INSIDE SWITCHBOARDS/PANELBOARDS.
14. BRANCH CIRCUIT WIRE SIZES (AND CONDUITS) SHALL BE INCREASED FROM THOSE INDICATED ON THEPLANS TO PREVENT EXCESSIVE VOLTAGE DROP. BRANCH CIRCUITS SHALL BE INSTALLED WITH WIRESOF SUFFICIENT SIZE SO THAT VOLTAGE DROP BETWEEN THE PANEL AND THE LOADS DOES NOT EXCEEDLIMIT OF 2%.
15. WIRE SIZES SHALL BE BASED ON THE 60°C. AMPACITIES FOR WIRE SIZES #14-1 AWG AND 75°CAMPACITIES FOR WIRE SIZES #1/0 AWG AND LARGER.
16. CIRCUITS MAY BE MULTI-PLEXED IN CONDUIT PROVIDED WIRE IS PROPERLY DERATED AND CONDUITSIZED PER NEC. UNDER NO CIRCUMSTANCES SHALL MORE THAN NINE (9) CURRENT CARRYINGCONDUCTORS BE RUN IN A SINGLE CONDUIT. WIREMOLD SERVED BY MULTIPLE CIRCUITS SHALL BEWIRED WITH INDIVIDUAL SEPARATE NEUTRALS FOR EACH CIRCUIT.
T. WIRING DEVICES
1. WIRING DEVICE COLOR SHALL BE SELECTED BY ARCHITECT, UNLESS OTHERWISE INDICATED.
2. PROVIDE TOTALLY ENCLOSED, 20 AMPERE, 120/277 VOLT QUIET A/C GENERAL USE SNAP SWITCHES.
3. SWITCHES SHALL BE SPECIFICATION GRADE AS MANUFACTURED BY HUBBELL, P&S OR LEVITON.
4. PROVIDE NEMA CONFIGURATION 5-20R DUPLEX 125 VOLT GROUNDING TYPE RECEPTACLES RATED FOR20 AMPERES UNLESS OTHERWISE NOTED ON THE DRAWINGS.
5. RECEPTACLES SHALL BE SPECIFICATION GRADE AS MANUFACTURED BY HUBBELL, P&S OR LEVITON.
6. RECEPTACLES REQUIRING AMPERAGES, VOLTAGES OR CONFIGURATIONS DIFFERENT FROM THE DUPLEXCONVENIENCE RECEPTACLES ABOVE SHALL BE AS INDICATED ON THE DRAWINGS.
7. PROVIDE OTHER RECEPTACLES OF A QUALITY, MATERIAL AND CONSTRUCTION EQUAL TO THATSPECIFIED FOR DUPLEX CONVENIENCE RECEPTACLES.
8. PROVIDE COVER OR DEVICE PLATES FOR OUTLET BOXES AS FOLLOWS UNLESS OTHERWISE NOTED:
a. FINISHED AREAS: THERMOPLASTIC- COLOR TO MATCH DEVICEb. UNFINISHED AREAS: ZINC COATED SHEET METAL, ALUMINUM, OR CAST METAL AS APPROPRIATE FOR
THE TYPE OF BOX.c. EXTERIOR AREAS: COPPER FREE ALUMINUM WITH GRAY, POWDER EPOXY FINISH, GASKET,
WEATHERPROOF, CROUSE-HINDS 'WLRD' FOR DUPLEX RECEPTACLES AND WLRS FOR SINGLERECEPTACLES OR EQUAL.
d. TELEPHONE, COMMUNICATION, AND SIGNAL OUTLET PLATES, SHALL MATCH THOSE USED FORRECEPTACLES AND SWITCHES. ALL OUTLET AND/OR JUNCTION BOXES SHALL BE COMPLETE WITH ACOVER PLATE BY THIS CONTRACTOR.
e. WHERE DEVICES ARE GANGED, THEY SHALL BE INSTALLED UNDER A COMMON COVERPLATE.f. LOCATE THE SWITCHES APPROXIMATELY 4'-0" ABOVE THE FINISHED FLOOR ELEVATION OR NEAREST
BLOCK COURSE (WITH IN ADA REQUIREMENTS) UNLESS OTHERWISE NOTED. THE LONG DIMENSIONOF THE SWITCHES SHALL BE VERTICAL.
g. BRASS PLATE/RING FOR CARPET INSTALLATION
9. LOCATE RECEPTACLES APPROXIMATELY 1'-6" ABOVE THE FINISHED FLOOR ELEVATION OR NEARESTBLOCK COURSE (WITH IN ADA REQUIREMENTS), UNLESS OTHERWISE NOTED. THE LONG DIMENSION OFTHE RECEPTACLE SHALL BE VERTICAL.
U. SAFETY SWITCHES
1. SAFETY SWITCHES SHALL BE THE ENCLOSED HEAVY-DUTY TYPE (TYPE HD) WITH QUICK-MAKE,QUICK-BREAK MECHANISM AND EXTERNAL PAD LOCKABLE OPERATING HANDLE.
2. SAFETY SWITCHES SHALL BE RATED FOR 240 OR 600 VOLTS AS APPLICABLE. THEY SHALL BEHORSEPOWER RATED WHEN USED IN MOTOR CIRCUITS.
3. SAFETY SWITCHES SHALL BE FUSIBLE OR NONFUSIBLE 2, 3 OR 4 POLE AS INDICATED ON THEDRAWINGS.
4. SAFETY SWITCHES SHALL BE SINGLE THROW UNLESS OTHERWISE INDICATED ON DRAWINGS.
5. ENCLOSURES SHALL BE NEMA 1 INDOORS AND NEMA 3R OUTDOORS UNLESS OTHERWISE INDICATED ONTHE DRAWINGS.
6. MANUFACTURER SHALL BE SQUARE D, SIEMENS, OR EATON CUTLER-HAMMER. ALL SAFETY SWITCHES
SHALL BE BY ONE MANUFACTURER.
7. MOUNT THE SAFETY SWITCHES SECURELY BETWEEN 3' X 6' LEVELS ABOVE THE FLOOR UNLESSOTHERWISE NOTED IN THE DRAWINGS.
8. SWITCHES ON BLOCK WALLS SHALL BE MOUNTED ON A 3/4" PLYWOOD BACKBOARD, WHERE LOCATEDINDOORS.
V. MOTOR STARTERS
1. STARTERS SHALL BE SQUARE D, SIEMENS, OR EATON CUTLER-HAMMER.
2. COORDINATE ALL EQUIPMENT INDICATED ON THE ELECTRICAL DRAWINGS WITH MECHANICAL EQUIPMENTSCHEDULES AND SPECIFICATIONS.
3. STARTERS AND DISCONNECTS SUPPLIED AS AN INTEGRAL PART OF EQUIPMENT SHALL BE FURNISHEDUNDER THE DIVISION PROVIDING THE EQUIPMENT. WIRING AND EQUIPMENT CONNECTIONS SHALL BE BYTHIS CONTRACTOR.
4. MANUAL MOTOR STARTERS SHALL BE CUTLER HAMMER B100/B101 TYPE OR EQUAL.
W. MECHANICAL EQUIPMENT ELECTRICAL CONNECTIONS
1. THE ELECTRICAL CONTRACTOR SHALL FURNISH, INSTALL AND CONNECT ALL POWER WIRING TO ALLMECHANICAL CONTRACTOR FURNISHED EQUIPMENT. THE MECHANICAL CONTRACTOR SHALL FURNISH,INSTALL AND CONNECT ALL CONTROL WIRING TO ALL FURNISHED EQUIPMENT, INCLUDING CONTROLDEVICES, STARTER, AND INTEGRAL DISCONNECT SWITCHES OF MECHANICAL CONTRACTOR FURNISHEDEQUIPMENT.
X. GROUNDING
1. GROUND ALL EQUIPMENT PER N.E.C.
2. GROUND EACH OUTSIDE LIGHTING STANDARD SEPARATELY WITH ONE GROUND ROD AND A #6 GROUNDWIRE.
3. GROUND ALL DRY TYPE TRANSFORMERS AS PER DRAWINGS AND NEC #450-9.
4. ALL CONDUITS SHALL CONTAIN A CODE SIZED GROUND WIRE SIZE PER NEC IN ADDITION TO THECONDUCTORS SHOWN ON THE PLANS. WHERE CIRCUIT CONDUCTORS ARE INCREASED IN SIZE FORVOLTAGE DROP, THE GROUND WIRE SIZE SHALL BE INCREASED PROPORTIONATELY.
5. WHERE AN ISOLATED, INSULATED GROUND IS REQUIRED A SEPARATE GREEN GROUND SHALL BE RUNFROM THE PANEL GROUND BUS TO THE ISOLATED GROUND CONNECTION OF THE DEVICE SERVED. INNO CASE SHALL THE SYSTEM GROUND (WIRE AND ASSOCIATED OUTLET BOXES, CONDUIT ANDBUILDING STEEL) BE ALLOWED TO CONTACT THE ISOLATED GROUND (GREEN WIRE AND DEVICEGROUND).
Y. DRY TYPE TRANSFORMERS
1. TRANSFORMERS SHALL BE CONTINUOUSLY RATED ISOLATING TYPE FOR 60 HERTZ SERVICE UNLESSOTHERWISE INDICATED.
2. INSULATION SYSTEMS SHALL BE 220° C. (150°C RISE).
3. ENCLOSURES FOR TRANSFORMERS SHALL BE METALLIC, SUITABLE FOR INDOOR AND OUTDOORINSULATION AS APPLICABLE AND RODENT PROOF.
4. MANUFACTURER SHALL BE SQUARE D, SIEMENS, OR EATON CUTLER-HAMMER. FRACTIONAL KVATRANSFORMERS SHALL BE MANUFACTURED BY EDWARDS OR THE SPECIAL EQUIPMENT MANUFACTURERIN WHICH THE TRANSFORMERS ARE USED.
5. FOUR APPROVED VIBRATION DAMPENERS PER TRANSFORMER SHALL BE EMPLOYED AS NECESSARY TOAVOID TRANSMITTING ANY VIBRATION TO THE BUILDING STRUCTURE. SIZES OF THE MOUNTINGS SHALLBE SELECTED ON THE BASIS OF THE WEIGHT OF THE TRANSFORMER, USING:
a. A MINIMUM 1" THICK RUBBER-CORK-RUBBER SANDWICH TYPE FOR FLOOR MOUNTING.b. A SPRING TYPE FOR SUSPENSION MOUNTING.c. TWO (2) SPRING TYPE AT THE TOP (WITH TWO (2) STEEL BRACKETS) AND TWO (2) RUBBER-IN
COMPRESSION TYPE AT THE BOTTOM (STAND-OFF) FOR WALL MOUNTING.
6. NO CONDUIT SHALL BE ATTACHED DIRECTLY TO THE TRANSFORMER. AT EACH ATTACHMENT, PROVIDEA VIBRATION DAMPENING ASSEMBLY CONSISTING OF:
a. AT&B #5721, 2, 3 ETC., OR EQUIVALENT FEMALE HUB TYPE LIQUID-TIGHT CONNECTOR BY STEEL CITY,EFCOR OR APPROVED EQUAL.
b. T&B #5331, 2, 3 ETC., OR EQUIVALENT MALE HUB TYPE LIQUID-TIGHT CONNECTOR WITH AN INSULATEDTHROAT BY STEEL CITY, EFCOR OR APPROVED EQUAL.
c. SHORT LENGTH (24" PLUS OR MINUS) OF LIQUID-TIGHT FLEXIBLE CONDUIT.d. A BONDING JUMPER OF NEC SIZE OUTSIDE OF THE ASSEMBLY.
7. FLOOR MOUNTING: ALL FLOOR MOUNTED TRANSFORMERS SHALL BE INSTALLED ON A 4" HIGHCONCRETE PAD. THIS CONTRACTOR SHALL FURNISH AND INSTALL CONCRETE PAD.
Z. PANELBOARDS
1. PANELBOARDS SHALL BE ENCLOSED DEAD FRONT SAFETY TYPE WITH FEATURES AND RATINGS ASSCHEDULED ON DRAWINGS.
2. PANELS KNOWN AS "LOAD CENTERS" ARE UNACCEPTABLE.
3. MOLDED CASE CIRCUIT BREAKERS SHALL BE AS SCHEDULED ON THE DRAWINGS AND SPECIFIED IN THISDIVISION.
4. ALL BUS BARS SHALL BE RECTANGULAR SOLID COPPER.
5. SPACE, WHERE SHOWN IN PANEL SCHEDULES, DESIGNATES SPACE FOR FUTURE PROTECTIVE DEVICESAND SHALL INCLUDE BUS AND SUPPORT.
6. INSTALL CABINETS SO THAT CENTER OF THE TOP BREAKER DOES NOT EXCEED 6'-6" ABOVE THEFINISHED FLOOR.
7. ENTRIES ON DIRECTORY CARDS SHALL BE TYPED, COMPLETE AND ACCURATE.
8. ALL BOLTED CONNECTIONS SHALL BE TORQUED IN ACCORDANCE WITH MANUFACTURERS STANDARDS.
9. ELECTRICAL CONTRACTOR SHALL ARRANGE CIRCUITS AS NEAR AS POSSIBLE TO CIRCUIT NUMBERS ONTHE DRAWINGS. AT COMPLETION OF JOB, ELECTRICAL CONTRACTOR SHALL TAKE CURRENT READINGCHECKS OF RESPECTIVE PHASES. A MINIMUM OF CIRCUIT CONNECTIONS SHALL BE REARRANGED TOBALANCE, AS CLOSELY AS POSSIBLE, THE LOAD IN THE PANEL.
10. ALL BREAKERS SHALL BE BOLT ON TYPE.
11. PROVIDE (3) SPARE 1" CONDUITS INTO ACCESSIBLE CEILING WHERE PANELS ARE FLUSH MOUNTED.
12. MANUFACTURER SHALL BE SQUARE D, SIEMENS, OR EATON CUTLER-HAMMER.
AA.FUSES
1. THE CONTRACTOR SHALL FURNISH A COMPLETE SET OF FUSES FOR ALL SWITCHES, PLUS FUSIBLEEQUIPMENT FURNISHED BY OTHER TRADES. UNLESS OTHERWISE INDICATED ON THE DRAWINGS, THEFUSES SHALL BE OF THE FOLLOWING TYPE:
a. FUSES 601 TO 600 AMPS SHALL BE UL CLASS. TRADE TYPE SHALL BE KRP-C AS MANUFACTUREDBY THE BUSSMAN COMPANY.
b. FUSES 1/10 TO 600 AMPS SHALL BE UL CLASS RK1. TRADE TYPE SHALL BE LOW PEAK LPS-RK(600V) AND LPN-RK (250C) AS LET BOXE MANUFACTURED BY BUSSMAN COMPANY.
c. ALL OTHER FUSES SHALL BE DUAL ELEMENT CURRENT LIMITING TYPE WITH 200,000 AMPERESSYMMETRICAL INTERRUPTING CAPACITY.
2. FUSES SHALL BE MANUFACTURED BY BUSSMANN, FERRAZ-SHAWMUT OR RELIANCE.
3. SPARE FUSES AMOUNTING TO A DUPLICATE SET OF EACH SIZE INSTALLED SHALL BE TURNED OVER TOTHE OWNER UPON COMPLETION OF THE PROJECT. PROVIDE AND PLACE IN A SPARE FUSE CABINETSIMILAR TO BUSSMAN #SFC.
4. THIS CONTRACTOR SHALL REPLACE ALL FUSES BLOWN DURING CONSTRUCTION.
11171119112111231125112711291131113311351137113911411143
1100I
1145
1140
1100G
1136 1116
1112A
1116A
1100G
1112 11151100E
1100D
11101110A1111
1113
1109
1107
1100
1108A1120B
1108
11181142 1134
1138
1138
1100J
1100R
1147A 1145A 1100K
1147
1172
1170 1149
11671168A1168
11661100Q
11641165B
1153
1155
1157
1165A1165
1161
1159
1166
1150C
1148
1144B
1144
1144D
1150
1100P
1011A1152
1000F
10111159
1007B
1007A
1007C
1007
1124B
1000E 1000I1000E
1007A
1026E 1026D 1026A1026C
1026B
1026G 1026
1026H 1026I
1000G1022
1022A
1022B
1020A
1020B
1020
C
1020
1026
1024
1214
1024A1200E 1016
1000H 1200D
1214B
1214A120C
1211 1213
1209
1207
1200B1200A
1121B 1212A
1212
1210
1210
1208 1206
1210
C12
10B
1205
1215
1200
1000V
1000K
1012
1014 1006D
1006C1006
1006E 1004G
1004
1004F 1004E
1010 1008
1004D
1004B
1000L1004A
1000A
1150A
1126C
1126B
1124A 1124
1126A1005H
1005I
1005J
1005A
1005
1005
1005K
11261146
1144C
1144A1130 1128 1100H
1128A1128B
1120
1100C
1120A
1122
1005G1005F
1005E1005D
1122A1122A
1122D
1122C
1005C
1100L
1105
11031106
1104
1102
1003F 1003E 1003D1101
1003J 1003C
1003G
1100B
1100A
1003G
1003G 1003A
1003B1001
1100J 1001D
1000B
1000
1003
1003
L10
03R
1000P
1002
1002C
1002A
1000R 12021203
1204A
1201
1204
EX. PANEL 'NE1'120/208V., 3Ø, 4W.
EX. PANEL 'NE1A'120/208V., 3Ø, 4W.
PANEL 'MDF1A'120/208V., 3Ø, 4W.
EX. PANEL 'TR1'120/208V., 3Ø, 4W.
PANEL 'TR1A'120/208V., 3Ø, 4W.
T
APPROXIMATE LOCATION OF 275 KWDIESEL GENERATOR IN ENCLOSURE.FINAL LOCATION SHALL BE VERIFIEDWITH COLLEGE.
400 AMP, 3-POLEGENERATOR BREAKER
PROVIDE PROTECTIVE BOLLARDS. REFERTO DETAIL 3/E601 FOR FURTHERINFORMATION. PAINT BOLLARDSYELLOW.
PANEL 'TR1B'120/208V., 3Ø, 4W.VERIFY LOCATION OFPANEL WITH CCACNORTH, PRIOR TOROUGH-IN.
A
A
CONCRETE ENCASED DUCTBANKUNDER ENTIRE ROADWAY. REFERTO DETAIL 2/E601.
ELECTRICAL CONTRACTOR SHALL PROVIDETRENCHING/EXCAVATION FOR 4" CONDUIT ANDREPAIR. BACKFILL AND PAVE TO MATCH EXISTINGASPHALT CONDITIONS. DO NOT DISTURB ANYEXISTING UTILITIES. COORDINATE ROUTING WITHCCAC NORTH CAMPUSADMINISTRATION/FACILITIES AND EXISTING UTILITYROUTINGS.
CONDUIT STUBBED UP OUT OF THE GROUND ANDRAN UP SIDE OF BUILDING TO 90° LB FITTING.
RUN CONDUIT ABOVE ACCESSIBLE CEILING SPACEIN EMT CONDUIT TO ROOM 1138.
1
E201
APPROXIMATE LOCATION OF GENERATORANNUNCIATOR PANEL. ELECTRICALCONTRACTOR SHALL VERIFY FINALLOCATION IN THIS ROOM WITH CCACNORTH REPRESENTATIVE PRIOR TOROUGH-IN.
3
E201
2
E201
EXIS
TING
PARK
ING
LOT
DATE
REVISIONS
NO.
DESIGNED:
DRAWN:
DATE:
CHECKED:
SCALE:
07-21-17
AS NOTED
800 Allegheny Avenue Pittsburgh, Pennsylvania 15233
DRAWING NUMBER:
NORTH CAMPUS -
8701 PERRY HIGHWAY, PITTSBURGH PA. 15237
UPS AND GENERATOR UPGRADES
COMMUNITY COLLEGE OF ALLEGHENY COUNTY
ASE PROJ. NUMBER: - 1741037
CCAC PROJ. NO.: - 13-C003n5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
MWM
MWM
DEB
GROUND FLOOR POWER PLAN
E101
1
E101GROUND FLOOR POWER PLAN1/16" = 1'-0"
STOP - CALL USBEFORE YOU DIG
PENNSYLVANIA ONE CALL SYSTEMS, INC.3 BUSINESS DAYS NOTICE IS THE LAW!
8-1-1 OR 1-800-242-1776WWW.PAONECALL.ORG
THE LOCATION OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATEWAY ONLY AND HAVE NOT BEEN INDEPENDENTLY VERIFIED BY THE USING AGENCY. THECONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIESBEFORE COMMENCING WORK, AND AGREES TO BE FULLY RESPONSIBLE FOR ANY ANDALL DAMAGES WHICH MAY OCCUR BY THE CONTRACTOR'S FAILURE TO EXACTLYLOCATED AND PRESERVE ANY AND ALL UTILITIES.
CONTRACTOR SHALL NOTIFY THE PA ONE CALL SYSTEM NOT LESS THAN THREE (3) DAYSPRIOR TO CONSTRUCTION. THE CONTRACTOR SHALL PLACE THE CALL AND PROVIDE ANAPPROXIMATE DATE AND TIME THAT DIGGING WILL OCCUR. THE ONE CALL SYSTEM WILLTHEN NOTIFY THE PUBLIC AND PRIVATE UTILITIES IN THE AREA. PUBLIC AND PRIVATEUTILITIES WILL THEN COORDINATE DIRECTLY WITH THE CONTRACTOR FOR ACTUAL FIELDLOCATIONS.
PA ONE CALL SYSTEM PHONE: 8-1-1 OR 1-800-242-1776.
GENERAL UTILITY & ONE CALL INFORMATION:
2050 2048 2046 2044 2042 2040 2038 2036 2034 2032 2030 2028 2026 2024 2022 2020 2018 2016 2014 2012 2010 2008
2043 2041 2039204520472052
2000
K
2025 2023 2021 2019 2017 2007
2004A
2000
G
2000P 2006
2000
D
2002
2037 2035 2033 2031 2029 2027
20832000M
2049 2100C
2000F
2202
2204
2206
22082210
2100 2100B
2100A
2101
2000B
2004
2003 2000 2001
2000
A
2102
2000L EX. PANEL 'TR2'120/208V., 3Ø, 4W.
PANEL 'TR2A'120/208V., 3Ø, 4W.
T
T T
EX. PANEL 'TR'120/208V., 3Ø, 4W.
EX. PANEL 'ML'277/480V., 3Ø, 4W.
EX. PANEL 'NEL'277/480V., 3Ø, 4W.
EX. PANEL 'NEL2'277/480V., 3Ø, 4W.
EX. PANEL 'NER'120/208V., 3Ø, 4W.
EXISTINGGENERATOR277/480V., 3Ø, 4W.
EXISTING ATS277/480V., 3Ø, 4W.
EXISTING 4000 AMPMAIN SWITCHBOARD277/480V., 3Ø, 4W.
CU1
CU2
J J
1SBA-16,181SBA-20,22
ELECTRICAL CONTRACTORSHALL INSTALLDISCONNECT SWITCHESAND MAKE FINALCONNECTIONS TOCONDENSING UNITSLOCATED ON ROOF.NOTE: COORDINATE ROOFING PENETRATIONS WITH THE ROOFINGWARRANTY HOLDER, RICH KOSUDA, TREMCO, PRIOR TO ANY ACTIONS.
2
E201
DATE
REVISIONS
NO.
DESIGNED:
DRAWN:
DATE:
CHECKED:
SCALE:
07-21-17
AS NOTED
800 Allegheny Avenue Pittsburgh, Pennsylvania 15233
DRAWING NUMBER:
NORTH CAMPUS -
8701 PERRY HIGHWAY, PITTSBURGH PA. 15237
UPS AND GENERATOR UPGRADES
COMMUNITY COLLEGE OF ALLEGHENY COUNTY
ASE PROJ. NUMBER: - 1741037
CCAC PROJ. NO.: - 13-C003n5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
MWM
MWM
DEB
SECOND FLOOR POWER PLAN
E102
1
E102SECOND FLOOR POWER PLAN1/16" = 1'-0"
3000S
3032
3030
3028
3000R 3000Q
3000
M
3021C3021D 3021
3021A 3021B 3019A 3019B
3019 3017 3015F 3015C
3017A 3017B 3015E 3015D 3015
3000N
3015B 3015A 3009
3015
3007 3007A 3007A
3000A
3002
3002A
3000B
30003004
3006
3008
3003
3003
3010
3003A
300F3006
301230143016
3000J
3018
3003
3020
3022
3024
3000L
3026A3026B
OPEN TO FIRST FLOORPANEL 'TR3A'120/208V., 3Ø, 4W.
DATE
REVISIONS
NO.
DESIGNED:
DRAWN:
DATE:
CHECKED:
SCALE:
07-21-17
AS NOTED
800 Allegheny Avenue Pittsburgh, Pennsylvania 15233
DRAWING NUMBER:
NORTH CAMPUS -
8701 PERRY HIGHWAY, PITTSBURGH PA. 15237
UPS AND GENERATOR UPGRADES
COMMUNITY COLLEGE OF ALLEGHENY COUNTY
ASE PROJ. NUMBER: - 1741037
CCAC PROJ. NO.: - 13-C003n5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
MWM
MWM
DEB
THIRD FLOOR POWER PLAN
E103
1
E103THIRD FLOOR POWER PLAN1/16" = 1'-0"
1138
T
DISCONNECT SWITCH
75 KVA TRANSFORMER
PANEL '1SBA'
UPS
PANEL 'UPS1A'
225 AMP, 480 VOLT AUTOMATICTRANSFER SWITCH
150 AMP, 480 VOLT AUTOMATICTRANSFER SWITCH
ELECTRICAL WIREWAYW/DISCONNECTSON WALL
ELECTRICAL CONTRACTOR SHALLREMOVE EXISTING CARPETING ANDADHESIVE IN THIS ROOM. THOROUGHLYCLEAN AND REMOVE ALL ADHESIVESAND FOREIGN MATERIAL THAT WILLINTERFERE WITH INSTALLATION OFANTI-STATIC FLOOR SYSTEM. PROVIDEANTI-STATIC INTERLOCKING FLOOR TILESYSTEM IN ENTIRE ROOM. CCAC SHALLPROVIDE SPECIFICATION.
AC2
AC1
ELECTRICAL CONTRACTOR SHALLINSTALL DISCONNECT SWITCHES ANDPROVIDE INTERCONNECTION WIRINGBETWEEN ROOF MOUNTED CONDENSINGUNITS AND AC UNITS PERMANUFACTURER'S REQUIREMENTS.DISCONNECTS BY MECHANICALCONTRACTOR'S EQUIPMENT SUPPLIER.
I.T. ROOM1138
EX. PANEL 'NE1'120/208V., 3Ø, 4W.
EX. PANEL 'NE1A'120/208V., 3Ø, 4W.
PANEL 'MDF1A'120/208V., 3Ø, 4W.
I.T. ROOM1213
EX. PANEL 'TR1'120/208V., 3Ø, 4W.
PANEL 'TR1A'120/208V., 3Ø, 4W.
I.T. ROOM2000M
EX. PANEL 'TR2'120/208V., 3Ø, 4W.
PANEL 'TR2A'120/208V., 3Ø, 4W.
DATE
REVISIONS
NO.
DESIGNED:
DRAWN:
DATE:
CHECKED:
SCALE:
07-21-17
AS NOTED
800 Allegheny Avenue Pittsburgh, Pennsylvania 15233
DRAWING NUMBER:
NORTH CAMPUS -
8701 PERRY HIGHWAY, PITTSBURGH PA. 15237
UPS AND GENERATOR UPGRADES
COMMUNITY COLLEGE OF ALLEGHENY COUNTY
ASE PROJ. NUMBER: - 1741037
CCAC PROJ. NO.: - 13-C003n5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
MWM
MWM
DEB
ENLARGED POWER PLANS
E201
1
E201ENLARGED POWER PLAN - IT ROOM 11381/4" = 1'-0"
2
E201ENLARGED POWER PLAN - IT ROOM 11381/4" = 1'-0"
3
E201ENLARGED POWER PLAN - IT ROOM 12131/4" = 1'-0"
4
E201ENLARGED POWER PLAN - IT ROOM 200M1/4" = 1'-0"
DATE
REVISIONS
NO.
DESIGNED:
DRAWN:
DATE:
CHECKED:
SCALE:
07-21-17
AS NOTED
800 Allegheny Avenue Pittsburgh, Pennsylvania 15233
DRAWING NUMBER:
NORTH CAMPUS -
8701 PERRY HIGHWAY, PITTSBURGH PA. 15237
UPS AND GENERATOR UPGRADES
COMMUNITY COLLEGE OF ALLEGHENY COUNTY
ASE PROJ. NUMBER: - 1741037
CCAC PROJ. NO.: - 13-C003n5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
MWM
MWM
DEB
ELECTRICAL RISER DIAGRAM
E501
UPSCABINET480V IN208V
OUTPUT
UPSCABINET
UPSCABINET
GROUND FLOOR - ROOM 1138
275 KW DIESELEMERGENCY GENERATOR
480V, 3Ø, 3W.600A
F40
0AT
EXISTING MAIN SWITCHBOARD277/480V., 3Ø, 4W.
DISTRIBUTIONPANELUPS1A
350 AMP MCB120/208V., 3Ø, 4W.
65KAIC
PANELTR2
XXA MCB
EXISTING
208/120V3Ø 4WXX KAICXXX A
ROOM 2000M
FINISHED GRADEAT PARKING LOT
ELEC RM 2210
400 AMPENCLOSEDCIRCUITBREAKER
(3) 600KCMIL + (1) #3 - 4"CSCHEDULE 40 PVC
225 AMP, 480 VOLT, 3-POLE AUTOMATICTRANSFER SWITCH. THE 'ATS' SHALL BEPROVIDED BY CCAC AND INSTALLED ANDWIRED BY ELECTRICAL CONTRACTOR.ELECTRICAL CONTRACTOR SHALL ALSOTAKE DELIVERY AND PROVIDE STORAGEPRIOR TO INSTALLATION.
PANELTR2A
50A MCB208/120V
3Ø 4W10 KAIC
ROOM 2000M
(3) #2/0 +(1) #6 - 2"C.
(4) 500KCMIL +(1) #1/0 - 4"C.
ROOM 1138
(4) #1 +(1) #6 - 1 1/2"C.
(3) 600KCMIL + (1) #3 - 4"C
PROVIDE (1) 175 AMP/3-POLEAND (1) 125 AMP/3-POLE FUSIBLESWITCHES IN EXISTINGSWITCHBOARD TO SERVENORMAL SIDE OF ATS SWITCHESIN ROOM 1138.
175A/3P.
EN
PANEL1SBA
250A MCB208/120V
3Ø 4W14 KAIC
75 KVATRANSFORMER
T
(480 PORTS)
(4) #1/0 + (1) #6 - 2"C.
ELECTRICAL CONTRACTORSHALL PROVIDE CONCRETEGENERATOR PAD
PROVIDE A 1 1/4" CONDUITWITH BELDEN 9729 @#18WIRES FOR GENERATORCONTROLS TO REMOTEANNUNCIATOR LOCATED INSECURITY ROOM 1001.
PROVIDE BRANCH CIRCUITS FOR GENERATOR CONTROL,BATTERY CHARGER AND JACKET HEATER. CIRCUITS SHALL BEDEDICATED 120V., 20 AMP/1P. CIRCUITS. PROVIDE (3) 1" PVCCONDUITS UNDERGROUND AND TRANSITION TO RIGIDGALVANIZED CONDUITS AS THEY STUB UP OUT OF GROUND.ROUTE CONDUITS UP SIDE OF BUILDING ADJACENT TO THE400 AMP FEEDER AND PROVIDE 90° LB FITTING TO INSIDEBUILDING. ONCE INSIDE BUILDING TRANSITION TO EMTCONDUIT.
1SBA-11SBA-31SBA-5
POWER RISER CODED NOTES:P1. ELECTRICAL CONTRACTOR SHALL DISCONNECT EXISTING BRANCHCIRCUITING SERVING EXISTING AC UNIT AND REMOVE BACK TO POINT OFORIGIN. PROVIDE NEW BRANCH CIRCUIT FROM PANEL '1SBA' ANDTERMINATE AT AC UNIT DISCONNECTING MEANS. ELECTRICALCONTRACTOR SHALL VERIFY ROUTINGS FOR BRANCH CIRCUITING ANDPROVIDE THE COLLEGE WITH A PLAN FOR REVIEW AND SCHEDULING TORUN THE BRANCH CIRCUITS. PROVIDE CORE DRILLS WHERE REQUIREDFOR TRAVELING VERTICALLY THROUGH FLOORS. FIRE SEAL ALLPENETRATIONS THROUGH FLOORS AND FIRE RATED WALLS. ELECTRICALCONTRACTOR SHALL VERIFY LOCATIONS OF ALL CONDENSING AND ACUNITS. REFER TO PANEL SCHEDULE FOR BREAKER AND WIRE SIZE.
P2. ELECTRICAL CONTRACTOR SHALL DISCONNECT EXISTING BRANCHCIRCUITING SERVING EXISTING CONDENSING UNIT AND REMOVE BACKTO POINT OF ORIGIN. PROVIDE NEW BRANCH CIRCUIT FROM PANEL '1SBA'AND TERMINATE AT CONDENSING UNIT DISCONNECTING MEANS.ELECTRICAL CONTRACTOR SHALL VERIFY ROUTINGS FOR ALL BRANCHCIRCUITING AND PROVIDE THE COLLEGE WITH A PLAN FOR REVIEW ANDSCHEDULING TO RUN THE BRANCH CIRCUITS. PROVIDE CORE DRILLSWHERE REQUIRED FOR TRAVELING VERTICALLY THROUGH FLOORS. FIRESEAL ALL PENETRATIONS THROUGH FLOORS AND FIRE RATED WALLS.ELECTRICAL CONTRACTOR SHALL VERIFY LOCATIONS OF ALLCONDENSING AND AC UNITS. REFER TO PANEL SCHEDULE FOR BREAKERAND WIRE SIZE.
P#
P1
EXIST. AC-9
EXIST. CU-9
P2
CLOSET
PANELNE1
EXISTING
208/120V3Ø 4W
J
P3. ELECTRICAL CONTRACTOR SHALL DISCONNECT EXISTING FEEDERSERVING EXISTING PANEL 'NE-1' AND REMOVE BACK 10' OR SO ANDTERMINATE INSIDE OF JUNCTION BOX. TAG JUNCTION BOX TO INDICATEFEEDER SERVING EXISTING PANEL 'NE-1'. TURN FEEDER BREAKER OFF INPANEL 'NE' AND MARK "SPARE"
P4. ELECTRICAL CONTRACTOR SHALL DISCONNECT EXISTING FEEDERSERVING EXISTING PANEL 'NE-1A'' AND REMOVE BACK 10' OR SO ANDTERMINATE INSIDE OF JUNCTION BOX. TAG JUNCTION BOX TO INDICATEFEEDER SERVING EXISTING PANEL 'NE-1A'. TURN DISCONNECT SWITCHOFF AND MARK "SPARE".
P5. PROVIDE PLACARD ON PANEL 'NE1' AFTER FEEDER HAS BEENDISCONNECTED AND REMOVED FROM PANEL 'NE' TO INDICATE"PANEL 'NE-1' HAS BEEN DE-ENERGIZED FROM ORIGINAL SOURCE"
P6. PROVIDE PLACARD ON PANEL 'NE1A' AFTER FEEDER HAS BEENDISCONNECTED AND REMOVED TO INDICATE"PANEL 'NE-1A' HAS BEEN DE-ENERGIZED FROM ORIGINAL SOURCE"
P3
UPS PURCHASED BY CCAC. THEELECTRICAL CONTRACTOR SHALL TAKEDELIVERY, PROVIDE STORAGE, INSTALLAND MAKE ALL FINAL TERMINATIONS FORUPS. COMMISSIONING, START-UP, TESTINGAND TRAINING SHALL BE PROVIDED BY UPSMANUFACTURER.
DIESEL GENERATOR AND DAY TANK SHALLBE PURCHASED BY CCAC. THE ELECTRICALCONTRACTOR SHALL TAKE DELIVERY,PROVIDE STORAGE, INSTALL AND MAKE ALLFINAL TERMINATIONS. THE ELECTRICALCONTRACTOR SHALL PROVIDE IN THEIR BID,FIRST FUEL FILL UP OF DIESEL FUEL DAYTANK AND FOR REQUIRED AMOUNT OF FUELFOR TESTING. DAY TANK IS SIZED FOR 24HOURS OF RUNTIME. COMMISSIONING,START-UP, TESTING AND TRAINING SHALL BEPROVIDED BY GENERATOR MANUFACTURER.
125A/3P.
EN
150 AMP, 480 VOLT , 3-POLEAUTOMATIC TRANSFER SWITCH. THE'ATS' SHALL BE PROVIDED BY CCAC ANDINSTALLED AND WIRED BY ELECTRICALCONTRACTOR. ELECTRICALCONTRACTOR SHALL ALSO TAKEDELIVERY AND PROVIDE STORAGEPRIOR TO INSTALLATION.
(3) #2/0 + (1) #6 - 2"C.
(3) #1/0 + (1) #6 - 2"C.(3) #2/0 + (1) #6 - 2"C.
(3) #1/0 + (1) #6 - 2"C.
(3) #2/0 +(1) #6 - 2"C.
(3) #1/0 + (1) #6 - 2"C.
(4) 600KCMIL +(1) #3 - 4"C
WIREWAY(4) 250KCMIL +(1) #2 - 3"C.
PROVIDE A 200 AMP, 3-POLE,480 VOLT FUSED DISCONNECTSWITCH FUSED AT 125 AMPS
PROVIDE A 200 AMP3-POLE, 480 VOLTFUSED DISCONNECTSWITCH FUSED AT175 AMPS
90° LBFITTING -RGS
PROVIDE A 1" CONDUITBETWEEN ATS UNITS ANDPROVIDE (5) #12 CONTROLWIRES
PROVIDE A 1" CONDUIT FROMATS UNIT AND PROVIDE (5)#12 CONTROL WIRES BACKTO GENERATOR. TRANSITIONTO PVC ONCE CONDUIT HASEXITED THE BUILDING.
200 AMP FUSEDDISCONNECT SWITCHFUSED AT 125 AMPS.
200 AMP FUSEDDISCONNECT SWITCHFUSED AT 175 AMPS.
AIC RATINGS SHALL MATCH EXISTINGRATINGS AT MAIN SWITCHBOARD INWHICH THE FUSIBLE DISCONNECTSWITCHES ARE BEING SERVED FROM.
SECOND FLOOR
THIRD FLOOR
P5
PANELNE1A
EXISTING
208/120V3Ø 4W
J
P4
P6
PANELTR1
XXA MCB
EXISTING
208/120V3Ø 4W
ROOM 1213
PANELTR1A
50A MCB208/120V
3Ø 4W10 KAIC
PANELMDF1A
100A MCB208/120V
3Ø 4W22 KAIC
ROOM 1138(920 PORTS)
ROOM 1213(480 PORTS)
TRANSITION TO 4" RIGIDGALVANIZED STEEL
P1
EXIST. AC-3
EXIST. CU-3
P2
(3) #1 +(1) #6 - 1 1/2"C.
PANELTR1B
50A MCB208/120V
3Ø 4W10 KAIC
ROOM 1002(480 PORTS)
PANELTR3A
70A MCB208/120V
3Ø 4W10 KAIC
ROOM 3000b(650 PORTS)
ROOM 1138
(4) #2 + (1) #6 - 11/2"C.
(4) #2 + (1) #6 -1 1/2"C.
P1
EXIST. AC-5
EXIST. CU-5
P2
FUTURE AC-UNIT
FUTURE CU UNIT
1SBA-39,41
60/2
ROOM 1002
30/2
BRANCH CIRCUITING SHALLTERMINATE AT DISCONNECTSWITCH IN ROOM WHEREFUTURE IT EQUIPMENT SHALLBE LOCATED. COORDINATEWITH CCAC PRIOR TOROUGH-IN.
ROOM 1213
ROOM 2000M
DATE
REVISIONS
NO.
DESIGNED:
DRAWN:
DATE:
CHECKED:
SCALE:
07-21-17
AS NOTED
800 Allegheny Avenue Pittsburgh, Pennsylvania 15233
DRAWING NUMBER:
NORTH CAMPUS -
8701 PERRY HIGHWAY, PITTSBURGH PA. 15237
UPS AND GENERATOR UPGRADES
COMMUNITY COLLEGE OF ALLEGHENY COUNTY
ASE PROJ. NUMBER: - 1741037
CCAC PROJ. NO.: - 13-C003n5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
MWM
MWM
DEB
ELECTRICAL RISER DIAGRAM
E601
12" HIGH, 4000 PSI CONCRETEPAD WITH #5 REBAR. COORDINATEOPENINGS FOR CONDUITS, ETC WITHGENERATOR REP - MATT PETERS
275 KW DIESEL GENERATORBY CCAC
12" 12"
8" COMPACTED FILL BASE.
TOTAL LENGTH OF GENERATOR SHALL BE VERIFIEDWITH CUMMINS REP - MATT PETERS 412-820-8410
275 KW DIESELGENERATOR
BY CCAC
12" HIGH, 4000 PSI CONCRETEPAD WITH
12"
12"
12" 12"
TOTAL WIDTH OFGENERATOR
SHALL BE VERIFIED WITHCUMMINS REP -MATT PETERS412-820-8410
TOTAL LENGTH OFGENERATOR SHALLBE VERIFIED WITHCUMMINS REP -MATT PETERS412-820-8410
1
E601GENERATOR PAD DETAILNTS
NO SCALE
DUCTBANK SECTION 'A-A'2E601
4" SCHEDULE 40 PVCCONDUIT WITH PULLWIRE (TYPICAL U.N.O.)
DUCT BANK CONCRETEENCASEMENT (TYPICAL)
3"
MINIMUM DEPTH FOR TOP OF DUCT BANK SHALL BE 36"BELOW GRADE. COORDINATE DEPTHS OF CROSSINGDUCTBANKS, AND WITH .2 & .3 CONTRACTOR'S. (TYPICAL)
3" WIDE "ELECTRICAL LINES BELOW" RED MARKER TAPE.PLACE 12" BELOW SURFACE. (TYPICAL)
DRIVEWAY OR GRADE
3"
7 1/2"
P
3'-0"
XX X X4"3'-
2"6"
3'-6"
6" DIA. BOLLARDS, CONCRETEFILLED SCHEDULE 40 STEEL PIPE,CONCRETE WASH TOP.
1/2" COMPRESSIBLE FILLERAT PIPE PERIMETER.
CONCRETE PAVING.
18" DIA. CONCRETE FOOTING.
AGGREGATE FILL.
3
E601GENERATOR BOLLARD DETAILNOT TO SCALE
EARTH/BACKFILL.
DATE
REVISIONS
NO.
DESIGNED:
DRAWN:
DATE:
CHECKED:
SCALE:
07-21-17
AS NOTED
800 Allegheny Avenue Pittsburgh, Pennsylvania 15233
DRAWING NUMBER:
NORTH CAMPUS -
8701 PERRY HIGHWAY, PITTSBURGH PA. 15237
UPS AND GENERATOR UPGRADES
COMMUNITY COLLEGE OF ALLEGHENY COUNTY
ASE PROJ. NUMBER: - 1741037
CCAC PROJ. NO.: - 13-C003n5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
RJP
RJP
DCP
MECHANICAL DATA SHEET
M001
GENERAL MECHANICAL NOTES (ALL DRAWINGS):
1. MECHANICAL CONTRACTOR SHALL PROVIDE ALL MATERIALS AND EQUIPMENTAND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLEHVAC SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED ANDREQUIRED BY CODE.
2. THE CONTRACT DOCUMENT DRAWINGS ARE DIAGRAMMATIC ONLY, AND AREINTENDED TO CONVEY THE SCOPE AND GENERAL ARRANGEMENT OF WORK.
3. ALL DIMENSIONS AND EXISTING CONDITIONS SHALL BE VERIFIED BY THECONTRACTOR BY FIELD INSPECTION PRIOR TO BIDDING. ANY INTERFERENCESTO INSTALLATION SHALL BE NOTED AND THE CONTRACTOR SHALL INCLUDE INHIS BID PRICE THE COST TO AVOID OR RELOCATE ALL ITEMS, INCLUDINGITEMS OF OTHER TRADES, THAT INTERFERE. ALL WORK SHALL BECOORDINATED WITH ALL TRADES INVOLVED. ALL OFFSETS, RISES,TRANSITIONS AND DROPS IN DUCTS AND PIPING AROUND OBSTRUCTIONSSHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
4. VERIFY ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIEDDRAWINGS. VERIFY AND PROVIDE DUCT TRANSITIONS OR PIPE ADAPTERS TOFURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DIMENSIONSBEFORE FABRICATION.
5. PROVIDE ACCESS IN WALLS & CEILINGS TO ACCESS ALL EQUIPMENT,VALVES, CONTROL DEVICES, VOLUME DAMPERS, AND FIRE/SMOKEDAMPERS.
6. FOLLOW MANUFACTURE'S RECOMMENDATIONS FOR INSTALLATION OFEQUIPMENT. ALSO REFER TO TYPICAL DETAILS FOR INSTALLATION OFEQUIPMENT.
7. ALL MATERIALS FURNISHED, AND ALL WORK PERFORMED BY THEMECHANICAL CONTRACTOR SHALL BE IN ACCORDANCE WITH ALLAPPLICABLE CODES AND REGULATIONS, INCLUDING BUT NOT LIMITED TO THELATEST APPLICABLE EDITIONS OF NFPA, IEEE, OSHA, SMACNA,INTERNATIONAL MECHANICAL CODE, INTERNATIONAL BUILDING CODE, ANDANY STATE, COUNTY, AND LOCAL CODES.
8. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED SUFFICIENTLY ANDANY ADDITIONAL SUPPORT SHALL BE PROVIDED AS REQUIRED TO PROVIDEVIBRATION FREE AND SAFE INSTALLATION. ALL MISCELLANEOUS STEELREQUIRED AND/OR AS SHOWN IN DETAILS FOR DUCTWORK, AND EQUIPMENT(UNLESS OTHERWISE NOTED) SHALL BE FURNISHED AND INSTALLED BY THEMECHANICAL CONTRACTOR. SUPPORT ALL DUCTWORK, PIPING ANDEQUIPMENT MOUNTED ABOVE THE CEILING DIRECTLY FROM THE STRUCTURE.ALL ATTACHMENTS TO BEAMS, TRUSSES, OR JOIST SHALL BE MADE ATPANEL POINTS WITH BEAM CLAMPS MEETING MSS STANDARDS.
9. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH NEC ANDELECTRICAL SPECIFICATIONS FOR THIS PROJECT.
MECHANICAL PIPING GENERAL NOTES (ALL DRAWINGS):
1. ALL PIPING SHOWN HAS BEEN DRAWN SCHEMATICALLY FOR CLARITY ANDSHOW ONLY RELATIVE POSITIONS. PROVIDE OFFSETS AND ELBOWS ASNEEDED TO INSTALL PROPERLY AND TO AVOID INTERFERENCES.
2. ALL NEW OR REPLACED HYDRONIC PIPING SHALL BE INSTALLED SO THAT ITCAN BE COMPLETELY VENTED AT HIGH POINTS AND DRAINED AT LOWPOINTS. PROVIDE AIR VENTS AT HIGH POINTS, TYPE PER SPECIFICATIONS.PROVIDE 1/2" BALL VALVES WITH HOSE END CONNECTIONS AND CAPS ATLOW POINT. ALL WATER MAINS SHALL BE INSTALLED LEVEL, UNLESSOTHERWISE NOTES.
3. PROVIDE SERVICE VALVES AT EACH BRANCH CONNECTION FROM MAINSAND AT EACH TERMINAL DEVICE OR EQUIPMENT CONNECTION.
4. CONTRACTOR SHALL PROVIDE NEW VALVES ON EXISTING PIPING WHERETHE PIPES ARE TO BE REMOVED SO THAT THE SYSTEM DOES NOT HAVE TOBE DRAINED WHILE REMOVING EXISTING UNITS, INSTALLING NEW UNITSAND MAKING CONNECTIONS TO NEW EQUIPMENT.
ENTERING WATER TEMPERATURELEAVING WATER TEMPERATURE
ENTERING AIR TEMPERATURE
TRANSFER GRILLETOP REGISTER
FEET WATER GAUGE (HYDRONIC)FT. W.G.
TGTR
TOTAL STATIC PRESSURET.S.P.
E.W.T.L.W.T.
E.A.T.
EXTERNAL STATIC PRESSURE
REMOVE EXISTING ITEM & RELOCATE TO NEW LOCATION
UNLESS NOTED OTHERWISE
DB/WB DRY BULB / WET BULB
1000-WATT (1 KW = 3,412 BTUH)
INCHES WATER GAUGE (AIR)
E.S.P.
IN. W.G.
KW
UNO
R / R
HEATING, VENTILATION AND AIR CONDITIONING1000 - BRITISH THERMAL UNITS
PHASE
SENS. SENSIBLE
HVACMBH
EXISTING(E)
Ø OR PH
NOTES:1. NOT ALL SYMBOLS AND ABBREVIATIONS ARE IN USE FOR THIS PROJECT.
DIAMETERØ
HEATING WATER RETURN PIPING
HEATING WATER SUPPLY PIPING
CONDENSER WATER RETURN PIPING
CONDENSER WATER SUPPLY PIPING
CHILLED WATER RETURN PIPING
CHILLED WATER SUPPLY PIPING
CONDENSATE DRAIN PIPING
REFRIGERANT PIPING
FUEL OIL SUPPLY PIPING
FUEL OIL RETURN PIPING
BALL VALVE
GATE VALVE
CHECK VALVE
2-WAY CONTROL VALVE
3-WAY CONTROL VALVE
STRAINER (W/ BALL VALVE AND CAP)
BACKFLOW PREVENTER
CIRCUIT SETTER (BALANCING VALVE)
GLOBE VALVE
ELBOW TURNED UP
ELBOW TURNED DOWN
UNION
NATURAL GAS PIPING
BUTTERFLY VALVE
PLUG VALVE
PRESSURE REGULATING VALVE
PRESSURE RELIEF VALVE
PIPE ANCHOR
PIPE GUIDE
FLEXIBLE CONNECTOR
AUTOMATIC AIR VENT
BOTTOM PIPE CONNECTION
D
DUCT SMOKE DETECTOR
THERMOSTAT
VOLUME CONTROL DAMPER
COMBINATION VERTICAL FIRE & SMOKE DAMPER
MOTORIZED DAMPER
VERTICAL FIRE DAMPER (WALL)
BACKDRAFT DAMPER
CONNECTION POINT, NEW TO EXISTING
DISCONNECTION POINT WITH CAP
DRAWING KEYNOTE
EXISTING EQUIPMENT OR DUCTWORK TO BE REMOVED
EXISTING EQUIPMENT OR DUCTWORK TO REMAIN
NEW EQUIPMENT OR DUCTWORK
SYMBOL
MECHANICAL DUCTWORK & GENERAL SYMBOLS LEGEND
DESCRIPTIONABRV.
EQUIPMENT UNIT DESIGNATION
DIFFUSER, REGISTER & GRILLE UNIT DESIGNATION W/ CFM
HORIZONTAL FIRE DAMPER (FLOOR)
COMBINATION HORIZONTAL FIRE & SMOKE DAMPER
VERTICAL SMOKE DAMPER (WALL)
HORIZONTAL SMOKE DAMPER (FLOOR)
LINED DUCTWORK
SUPPLY DUCT UP
SUPPLY DUCT DOWN
RETURN / EXHAUST DUCT UP
RETURN / EXHAUST DUCT DOWN
DUCT OFFSET UP
DUCT OFFSET DOWN
R
CEILING DIFFUSER. - ROUND NECK - # THROW DIRECTIONS
LINEAR DIFFUSER. SEE SCHEDULE FOR INFORMATION.
RETURN or EXHAUST GRILLE - (R = REGISTER)
FLEXIBLE DUCT
SPIN TAP WITH VOLUME CONTROL DAMPER
HUMIDISTAT
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
DUCT ACCESS DOOR
SQUARE / RECTANGULAR DUCT TRANSITION
SQUARE/RECTANGULAR TO ROUND DUCT TRANSITION
UNDER CUT DOOR
SYMBOL
MECHANICAL PIPING SYMBOLS LEGEND
DESCRIPTIONABRV.
TOP PIPE CONNECTION
PIPING CAP
STATIC PRESSURE SENSOR
ROUND DUCT ELBOW UP
ROUND DUCT ELBOW DOWN
FLEXIBLE DUCT CONNECTION (TO EQUIPMENT)
TRIPLE DUTY VALVE WITH MEASURING CONNECTIONS
HOSE BIB
PRESSURE GAGE W/ SHUT-OFF
SUPPLY DIFFUSER - RECTANGULAR - MULTI-DIRECT.
SIDEWALL SUPPLY or RETURN GRILLE - (R = REGISTER)
ELBOW WITH TURNING VANES
FLOW ARROW
BDD
M
DD
T
H
SP
2CO
CO
#TAG
TAGCFM
U
1
HWS
CWS
HWR
CWR
CHWS
CHWR
G
D
R
LPS
MPS
HPS
LPR
FOS
FOR
LOUVERED DOORL
REVISION NUMBER
RETURN OR EXHAUST AIR
SUPPLY OR OUTSIDE AIR
LAT. LATENT
1
1 DEMOLITION DRAWING KEYNOTE
XTR
RX
CD
SD
SG/EG
LD
RG/EG
AD
VD
BDD
MD
FD
HFD
SD
HSD
DD
FD/SD
HFD/SD
RA or EA
SA or OA
HWS
CWS
HWR
CWR
CHWS
CHWR
LEAVING AIR TEMPERATUREL.A.T.
LOW PRESSURE STEAM SUPPLY PIPING (0-15 PSIG)
MEDIUM PRESSURE STEAM SUPPLY PIPING (16-60 PSIG)
HIGH PRESSURE STEAM SUPPLY PIPING (61 TO 200 PSIG)
LOW PRESSURE STEAM CONDENSATE RETURN
HIGH PRESSURE STEAM CONDENSATE RETURNHPR
PUMPED STEAM CONDENSATEPC
VENT PIPINGV
MECHANICAL ABBREVIATIONS
STEAM TRAPT
FLEX
G
D
R
LPS
MPS
HPS
LPR
FOS
FOR
HPR
PC
V
DESCRIPTIONABRV.
ABOVE FINISHED FLOORAFFELEVATION FROM DATUMELEV.
NOT TO SCALENTSNOT IN CONTRACTNIC
FLANGED CONNECTION
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
BV
BFV
PV
GV
GBV
CV
CW CITY (DOMESTIC) WATERCW
CEILING RADIATION FIRE DAMPERRD
T'STAT
H
PRESSURE/TEMPERATUIRE (P/T) PLUG
HB
P/T
8" M
IN.
PIPE OR ELECTRICAL CONDUIT
STAINLESS STEEL CLAMP
PORTAL BOOT TRIMTO SIZE
MULTIPLE PIPEPORTAL CURB CAPROOFING1 1/2" THICK INSULATION
PRE-FAB CURB
ROOFING
INSULATION
ROOF DECK
COVER UNUSED PORTS
CUT OPENINGS IN DECK ONLYAS LARGE AS REQUIRED TOPASS PIPE THROUGH
ROOF DECKFASTENERS 6" O.C.MAX (TYPICAL)
STAINLESS STEELCLAMPS
N28 CAP FOR USEWITH 3/8" TO 2" PIPE
CURB COVER
MOUNTED ON 14"HIGHPREFABRICATEDINSULATED METALCURB
1
M001PIPE PORTAL DETAILNOT TO SCALE
NAILER STRIP
INSULATION
EQUIPMENT RAIL SUPPORT MODELER-4B AS MFR'D BY R.P.S. CORP.OR EQUIV. MAX. BEARING WEIGHT
BY OTHERS
150#/FT BY PATE
COUNTERFLASHING
INSULATION
ROOFING
12"MIN.
ROOF
2
M001EQUIPMENT RAIL SUPPORT DETAILNOT TO SCALE
FASTEN TO ROOF DECK
SUPPLIER TO SIZE REFRIGERANT LINES PERMANUFACTURER'S RECOMMENDATIONS BASED ONFIELD CONDITIONS OF LENGTH AND OFFSETS. PAINTINSULATION AND CLAMP PIPE TO WALL.
FLOOR
CEILING MOUNTEDAC FAN COIL
CEILING
3
M001CEILING MOUNTED AC UNITNOT TO SCALE
CEILING MOUNTEDAC FAN COIL
1 1/4 CONDENSATE DRAIN
NOTE: COORDINATE ROOFING PENETRATIONS WITH THE ROOFINGWARRANTY HOLDER, RICH KOSUDA, TREMCO, PRIOR TO ANY ACTIONS.
MECHANICAL SPECIFICATIONS
MECHANICAL GENERAL CONDITIONS (230010)
A. GENERAL1. CONFORM TO ALL GENERAL AND SPECIAL CONDITIONS OF CONTRACT AS SPECIFIED BY ARCHITECT AND/OR OWNER.
2. PRODUCTS AND INSTALLATION SHALL COMPLY WITH ALL APPLICABLE LAWS, CODES, GOVERNMENT REGULATIONS, UTILITYCOMPANY REQUIREMENTS, ETC. OF ALL AUTHORITIES HAVING JURISDICTION. WORK SHALL COMPLY WITH THE FOLLOWING CODES,STANDARDS AND ORGANIZATIONS: INTERNATIONAL MECHANICAL CODE (IMC), INTERNATIONAL PLUMBING CODE (IPC),INTERNATIONAL ENERGY CODE, NATIONAL ELECTRIC CODE, NFPA, UNDERWRITERS LABORATORY (UL), IRI, FM, SMACNA “HVAC DUCTCONSTRUCTION STANDARDS” GUIDELINES, DETAILS, & MODEL SPECIFICATION, ASHRAE. WHERE CONFLICTS EXIST BETWEENCODES, STANDARDS OR THIS SPECIFICATION THE HIGHER REQUIREMENT SHALL APPLY. DEVIATIONS FROM THE CONTRACTDOCUMENTS REQUIRED BY THE ABOVE AUTHORITIES SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW. OBTAIN PERMITS ANDPAY ALL FEES. ARRANGE FOR ALL REQUIRED INSPECTIONS AND APPROVALS. CONFIRM ALL UTILITY COMPANY REQUIREMENTSAND CONNECTION POINTS IN FIELD, PRIOR TO STARTING WORK.
3. ALL SPECIFICATIONS AND DRAWINGS, I.E., ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL ARE COMPLIMENTARY ANDMUST BE USED IN COMBINATION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION. ANY INFORMATION CONFLICTS WITHIN THESPECIFICATIONS AND DRAWINGS SHALL BE BROUGHT TO THE ENGINEER'S ATTENTION. DRAWINGS ARE DIAGRAMMATIC. CONFIRMALL DIMENSIONS BY FIELD MEASUREMENT. THE EXACT LOCATIONS FOR APPARATUS, FIXTURES, EQUIPMENT AND PIPING WHICH ISNOT COVERED BY DRAWINGS, SHALL BE OBTAINED FROM THE ARCHITECT OR HIS REPRESENTATIVE IN THE FIELD, AND THE WORKSHALL BE LAID OUT ACCORDINGLY.
4. VISIT SITE, CHECK FACILITIES AND CONDITIONS MAKE ALL NECESSARY OBSERVATIONS, MEASUREMENTS, NOTE CONDITIONSUNDER WHICH WORK IS TO BE PERFORMED, AND TAKE ALL ITEMS INTO CONSIDERATION IN BID.
5. EACH CONTRACTOR SHALL PROVIDE FOR HIS OWN CLEAN-UP, REMOVAL AND LEGAL DISPOSAL OF ALL RUBBISH DAILY.CONTRACTOR SHALL PROTECT THEIR WORK AND EXISTING OR ADJACENT PROPERTY AGAINST WEATHER, TO MAINTAIN THEIR WORK,MATERIALS, APPARATUS AND FIXTURES FREE FROM INJURY OR DAMAGE. ANY WORK DAMAGED BY FAILURE TO PROVIDEPROTECTION REQUIRED, SHALL BE REMOVED AND REPLACED WITH NEW WORK AT THE CONTRACTOR'S EXPENSE.
6. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, SEQUENCES OF CONSTRUCTION ANDTHE SAFETY OF WORKMEN.
7. NO PIPING, DUCTWORK, CONTROLS, ETC., SHALL BE INSTALLED OR ROUTED ABOVE ELECTRICAL PANELS AND EQUIPMENT ORTHROUGH ELEVATOR ROOMS.
8. THE CONTRACTOR SHALL COORDINATE AND OBTAIN A WRITTEN LISTING OF ELECTRICAL CHARACTERISTICS OF ALL MECHANICALEQUIPMENT FROM ELECTRICAL CONTRACTOR PRIOR TO ORDERING OF EQUIPMENT. NO ADDITIONAL PAYMENT WILL BE MADE FORLACK OF CONTRACTOR COORDINATION OF ELECTRICAL CHARACTERISTICS.
9. DURING THE BUILDING CONSTRUCTION SOME EXISTING INSTALLATION MAY BE EXPOSED THAT WILL HAVE TO BE CHANGED,ALTERED, REROUTED AND/OR ABANDONED. ANY SUCH WORK WHICH COMES UNDER THE JURISDICTION OF THIS CONTRACTORSHALL BE DONE BY THIS CONTRACTOR WITHOUT EXTRA COST TO THE OWNER, AS THOUGH FULLY DETAILED ON PLANS AND/ORDESCRIBED IN THE SPECIFICATIONS.
10. WORK RELATED TO THE EXISTING BUILDING SHALL BE COORDINATED TO MINIMIZE INTERFERENCE OR INTERRUPTION OF NORMALBUILDING USE BY OWNER. REFER TO ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS.
11. IN CASES OF DOUBT AS TO THE WORK INTENDED, OR IN THE EVENT OF NEED FOR EXPLANATION THEREOF, THE CONTRACTOR SHALLREQUEST SUPPLEMENTARY INSTRUCTIONS FROM THE ENGINEER. NO CHANGES ARE TO BE MADE TO THE WORK OF THIS CONTRACTWITHOUT PRIOR KNOWLEDGE AND APPROVAL OF THE ENGINEER. THE CONTRACTOR SHALL HOLD THE OWNER AND ITSCONSULTANTS HARMLESS AGAINST ALL CLAIMS AND JUDGMENTS ARISING OUT OF THE CONTRACTORS PERFORMANCE OF THEWORK OF THIS CONTRACT. THE CONTRACTOR SHALL NOT PROCEED WITH ANY WORK, WHICH HE EXPECTS ADDITIONALCOMPENSATION BEYOND THE CONTRACT AMOUNT, WITHOUT WRITTEN AUTHORIZATION FROM THE APPROPRIATE AUTHORITY. FAILURE TO OBTAIN SUCH AUTHORIZATION SHALL INVALIDATE ANY CLAIM FOR EXTRA COMPENSATION.
12. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO INSTALL THE HEATING, VENTILATION AND AIR CONDITIONING SYSTEMSO AS TO INSURE QUIET OPERATION. NO VIBRATION OR SOUND SHALL BE TRANSMITTED TO THE BUILDING, STRUCTURE OROCCUPIED AREAS. THE DECISION OF THE ENGINEER AS TO THE QUIETNESS OF THE SYSTEM AND EQUIPMENT SHALL BE FINAL. ITSHALL BE THIS CONTRACTORS RESPONSIBILITY TO CORRECT OR REPLACE ANY NOISY SYSTEM OR EQUIPMENT AS REQUIRED.
13. OBTAIN PERMITS AND PAY ALL FEES. ARRANGE FOR ALL REQUIRED INSPECTIONS AND APPROVALS.
B. DEMOLITION1. DISCONNECT, DISASSEMBLE, CAP, PLUG AND REMOVE ALL MEP ELEMENTS (PIPING, DUCTS, ELECTRICAL DEVICES, WIRING,
CONDUIT, EQUIPMENT, HANGERS, SUPPORTS, ETC) INDICATED ON THE DRAWINGS OR NOT OTHERWISE REQUIRED FOR COMPLETEDPRODUCT. NO MEP ELEMENTS ARE TO BE ABANDONED IN PLACE UNLESS SPECIFICALLY NOTED. NOT ALL ITEMS TO BE REMOVEDARE INDICATED ON DRAWING.
2. ALL OPENINGS ON PIPING AND DUCTS THAT REMAIN SHALL BE CAPPED AND PROPERLY SECURED. WIRING SHALL BEDISCONNECTED AT CIRCUIT BREAKERS AND REMOVED AND BREAKERS MARKED "SPARE." REMOVE AND RECLAIM ANY REFRIGERANTIN EXISTING SYSTEMS PRIOR TO DEMOLITION OF ANY EQUIPMENT ACCORDING TO FEDERAL REQUIREMENT.
3. ANY EQUIPMENT DESIGNATED BY OWNER TO BE SALVAGED SHALL BE PROTECTED AND DELIVERED TO AN OWNER DESIGNATEDAREA ON SITE.
4. ALL ASBESTOS REMOVAL (IF REQUIRED) WILL BE HANDLED BY THE OWNER AND IS NOT A PART OF THIS WORK. IF MATERIALSSUSPECTED OF CONTAINING HAZARDOUS MATERIALS ARE ENCOUNTERED, DO NOT DISTURB; NOTIFY ARCHITECT AND OWNERIMMEDIATELY.
C. BASIS OF DESIGN AND SUBSTITUTIONS1. MANUFACTURERS LISTED ARE BASIS OF DESIGN. SUBSTITUTIONS ARE SUBJECT TO THE APPROVAL OF THE OWNER, ARCHITECT &
ENGINEER. IF SUBSTITUTION IS SUBMITTED, IT IS THE CONTRACTOR'S RESPONSIBILITY TO EVALUATE IT AND CERTIFY THAT THESUBSTITUTION IS EQUIVALENT IN ALL RESPECTS TO THE BASIS OF DESIGN. WHERE SUBMITTALS VARY FROM THE CONTRACTREQUIREMENTS, THE CONTRACTOR SHALL CLEARLY INDICATE ON SUBMITTAL OR ACCOMPANYING DOCUMENTS THE NATURE ANDREASON FOR VARIATIONS. IF SUBSTITUTIONS ARE APPROVED, NOTIFY ALL OTHER CONTRACTORS, SUBCONTRACTORS OR TRADESAFFECTED BY SUBSTITUTION AND FULLY COORDINATE. ANY COSTS RESULTING FROM SUBSTITUTION, WHETHER BY CONTRACTOROR OTHERS, SHALL BE RESPONSIBILITY OF AND PAID FOR BY SUBSTITUTING CONTRACTOR. APPROVED SHOP DRAWINGS DOES NOTABSOLVE THIS CONTRACTOR FROM THIS RESPONSIBILITY. APPROVAL OF SUBSTITUTIONS IS AT THE DISCRETION OF THE ARCHITECT& ENGINEER AND IF SUBMITTED AFTER THE BID, AT THE RISK OF THE CONTRACTOR.
2. ALL EQUIPMENT AND MATERIALS SHALL BE NEW, FREE OF DEFECTS AND U.L. LABELED.
D. CUTTING, PATCHING AND DRILLING
1. ALL CUTTING AND PATCHING OF THE BUILDING CONSTRUCTION REQUIRED FOR THIS WORK SHALL BE BY THIS CONTRACTOR UNLESSSHOWN ON ARCHITECTURAL DRAWINGS AND CONFIRMED AS TO SIZE AND LOCATION PRIOR TO NEW CONSTRUCTION. CUTTINGSHALL BE IN A NEAT AND WORKMANLIKE MANNER. NEATLY SAW CUT ALL RECTANGULAR OPENINGS, SET SLEEVE THROUGHOPENING, AND FINISH PATCH OR PROVIDE TRIM FLANGE AROUND OPENING. CORE DRILL AND SLEEVE ALL ROUND OPENINGS. DONOT CUT ANY STRUCTURAL COMPONENTS WITHOUT ARCHITECT'S APPROVAL.
2. PATCH AND FINISH TO MATCH ADJACENT AREAS THAT HAVE BEEN CUT, DAMAGED OR MODIFIED AS A RESULT OF THEINSTALLATION OF THE MECHANICAL OR ELECTRICAL EQUIPMENT. FIRE STOP ALL PENETRATIONS OF FIRE RATED CONSTRUCTION INA CODE APPROVED MANNER.
3. ALL CONTRACTORS SHALL CONFIRM WITH OWNER, PRIOR TO BID, TIMES AVAILABLE FOR NOISE PRODUCING WORK SUCH ASCUTTING AND CORE DRILLING OF FLOORS, WALLS, ETC., AS WELL AS TIMES FOR WORK WHICH REQUIRE ACCESS INTO ADJOININGTENANT SPACES. INCLUDE ANY PREMIUM TIME IN BID.
4. EXACT LOCATION OF ROOFTOP EQUIPMENT SHALL BE APPROVED BY OWNER'S STRUCTURAL ENGINEER.
5. INFORMATION REGARDING REQUIRED PIPE OPENINGS IN WALLS, FLOORS, CHASES, ETC., AND CONCRETE EQUIPMENT PADS ORFOUNDATIONS SHALL BE GIVEN TO THE GENERAL CONTRACTOR BY THIS CONTRACTOR PRIOR TO THE CONSTRUCTION PERIOD. IFTHIS CONTRACTOR FAILS TO COMPLY WITH THIS REQUEST, OR IF INCORRECT INFORMATION IS GIVEN, THE NECESSARY CUTTINGAND PATCHING WILL BE PERFORMED BY THE GENERAL CONTRACTOR, AT THIS CONTRACTOR'S EXPENSE.
E. WARRANTY
1. FULLY WARRANT ALL MATERIALS, EQUIPMENT AND WORKMANSHIP FOR ONE (1) YEAR FROM DATE OF ACCEPTANCE.EXTEND ALLMANUFACTURER'S WARRANTIES TO OWNER, INCLUDING ALL EXTENDED WARRANTIES ON HVAC EQUIPMENT.
2. REPAIR OR REPLACE WITHOUT CHARGE TO THE OWNER ALL ITEMS FOUND DEFECTIVE DURING THE WARRANTY PERIOD. IN THE CASEOF REPLACEMENT OR REPAIR DUE TO FAILURE WITHIN THE WARRANTY PERIOD, THE WARRANTY ON THAT PORTION OF THE WORKSHALL BE EXTENDED FOR A MINIMUM PERIOD OF ONE (1) YEAR FROM THE DATE OF SUCH REPLACEMENT OR REPAIR.
F. SHOP DRAWING SUBMITTALS
1. SUBMIT SHOP DRAWINGS FOR MECHANICAL EQUIPMENT, FIRE PROTECTION SYSTEMS, DUCTWORK, AND PLUMBING FIXTURES ANDEQUIPMENT WITH ADEQUATE DETAILS AND SCALES TO CLEARLY SHOW CONSTRUCTION. INDICATE THE OPERATINGCHARACTERISTICS FOR EACH REQUIRED ITEM. CLEARLY IDENTIFY EACH ITEM ON THE SUBMITTAL AS TO MARK, LOCATION AND USE,USING SAME IDENTIFICATION AS PROVIDED ON DESIGN DRAWINGS.
2. DUCTWORK AND FIRE PROTECTION DRAWINGS SHALL BE FULLY DIMENSIONED BASED ON FIELD VERIFIED BUILDING CLEARANCESAND ARCHITECTURAL CEILING LAYOUTS, AND INDICATE STRUCTURAL, LIGHTING, DUCTWORK AND PIPING AT ALL CRITICALLOCATIONS.
3. CONTRACTOR SHALL REVIEW AND INDICATE HIS APPROVAL OF EACH SHOP DRAWING PRIOR TO SUBMITTAL FOR REVIEW. DO NOTSTART WORK OR FABRICATION UNTIL SHOP DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND RETURNED TO THECONTRACTOR.
4. SUBMITTALS WILL BE REVIEWED ONLY FOR GENERAL COMPLIANCE WITH THE CONTRACT DOCUMENTS AND NOT FOR DIMENSIONSOR QUANTITIES. THE SUBMITTAL REVIEW SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR PURCHASE OF ANY ITEMIN FULL COMPLIANCE WITH THE CONTRACT DOCUMENTS OR ITS COMPLETE AND PROPER INSTALLATION.
5. WHERE SUBMITTALS VARY FROM THE CONTRACT REQUIREMENTS, THE CONTRACTOR SHALL CLEARLY INDICATE ON SUBMITTAL ORACCOMPANYING DOCUMENTS THE NATURE AND REASON FOR VARIATIONS.
6. REFER TO VARIOUS SECTIONS FOR LISTING OF SHOP DRAWINGS REQUIRED ON THIS PROJECT.
7. EACH MANUFACTURER OR HIS REPRESENTATIVE MUST CHECK THE APPLICATION OF HIS EQUIPMENT AND CERTIFY AT TIME OF SHOPDRAWING SUBMITTAL THAT EQUIPMENT HAS BEEN PROPERLY APPLIED AND CAN BE INSTALLED, SERVICED AND MAINTAINEDWHERE INDICATED ON DRAWINGS. ADVISE ENGINEER IN WRITING WITH SUBMITTAL DRAWINGS OF ANY POTENTIAL PROBLEMS.THE MANUFACTURER SHALL BE RESPONSIBLE FOR ANY CHANGES THAT MIGHT BE NECESSARY BECAUSE OF PHYSICALCHARACTERISTICS OF EQUIPMENT THAT HAVE NOT BEEN CALLED TO THE ENGINEER'S ATTENTION AT THE TIME OF SUBMITTAL.
G. RECORD DRAWINGS
1. EACH CONTRACTOR OR SUBCONTRACTOR SHALL KEEP ONE (1) COMPLETE SET OF THE CONTRACT WORKING DRAWINGS ON THE JOBSITE ON WHICH HE SHALL REGULARLY RECORD ANY DEVIATIONS OR CHANGES FROM SUCH CONTRACT DRAWINGS MADE DURINGCONSTRUCTION.
2. THESE DRAWINGS SHALL RECORD THE LOCATION OF ALL CONCEALED EQUIPMENT, PIPING, ELECTRIC SERVICE, SEWERS, WASTES,VENTS, DUCTS, CONDUIT AND OTHER PIPING, BY MEASURED DIMENSIONS TO EACH SUCH ITEM FROM READILY IDENTIFIABLE ANDACCESSIBLE WALLS OR CORNERS OF THE BUILDING. PLANS ALSO SHALL SHOW INVERT ELEVATION OF SEWERS AND TOPELEVATION OF ALL OTHER BELOW-GRADE LINES.
3. RECORD DRAWINGS SHALL BE KEPT CLEAN AND UNDAMAGED AND SHALL NOT BE USED FOR ANY PURPOSE OTHER THANRECORDING DEVIATIONS FROM WORKING DRAWINGS AND EXACT LOCATIONS OF CONCEALED WORK.
4. AFTER THE PROJECT IS COMPLETED, THESE SETS OF DRAWINGS SHALL BE DELIVERED TO THE ARCHITECT IN GOOD CONDITION, ASA PERMANENT RECORD OF THE INSTALLATION AS ACTUALLY CONSTRUCTED.
H. FIRESTOPPING
1. ALL SERVICES THAT PASS THRU FIRE OR SMOKE RATED PARTITIONS, WALLS, FLOORS, SHALL BE FIRESTOPPED. FIRE STOPPINGRATING SHALL MATCH PARTITION RATING. ALL FIRE STOPPING SYSTEM SHALL MEET THE REQUIREMENTS OF ASTM E 814,UL 1479,AND BE FACTORY MUTUAL APPROVED.
2. ALL FIRESTOPING AND/OR SMOKE STOPPING MATERIAL AND INSTALLATION SHALL BE AS MANUFACTURED BY HILTI OR APPROVEDEQUAL.
I. ACCESS DOORS & PANELS
1. ACCESS DOORS SHALL BE PROVIDED IN WALLS AND CEILINGS WHERE REQUIRED TO PERMIT PROPER ACCESS TO VALVES ANDANY OTHER SUCH DEVICES WHICH REQUIRE MAINTENANCE OR SERVICE. DOORS PLACED IN WALLS, PARTITIONS OR OTHERFIRE-RATED CONSTRUCTION SHALL HAVE A LABEL SIGNIFYING THAT THE DOOR HAS THE SAME FIRE RATING AS THE FIRE-RATEDCONSTRUCTION.
2. THIS CONTRACTOR SHALL FURNISH ACCESS PANELS TO THE GENERAL CONTRACTOR FOR INSTALLATION.
3. ACCESS PANELS SHALL BE CONSTRUCTED OF 14 GAUGE STEEL, WITH 16 GAUGE STEEL FRAMES. DOORS SHALL FINISH FLUSHWITH THE SURROUNDING SURFACE. FRAMES SHALL HAVE 3 INCH WIDE EXPANDED METAL FOR PLASTERED SURFACES AND PLAINFLANGED TYPE FRAME FOR TILE, MASONRY OR GYPSUM BOARD SURFACES. DOORS AND FRAMES SHALL BE FURNISHED PRIMECOATED. DOORS INSTALLED IN CERAMIC TILE OR OTHER NON-PAINTED SURFACES SHALL BE STAINLESS STEEL. HINGES SHALL BECONCEALED SPRING TYPE, TO ALLOW DOORS TO BE OPENED 175 DEGREES. LOCKS SHALL BE FLUSH SCREWDRIVER TYPE WITHSTEEL CAMS. ACCESS PANELS SHALL BE 16 INCHES BY 16 INCHES OR LARGER AS MAY BE REQUIRED FOR PROPER ACCESS TO THEDEVICE BEING SERVED.
4. ACCESS PANELS ARE NOT REQUIRED IN COMPLETELY ACCESSIBLE LIFT OUT TILE CEILINGS. CONTRACTOR SHALL REVIEW THEROOM FINISH SCHEDULE ON THE ARCHITECTURAL DRAWINGS IN ORDER TO VERIFY THE NEED FOR ACCESS PANELS.
REFRIGERANT PIPING (232300)
1. INSTALL REFRIGERANT PIPING BETWEEN CONDENSING UNIT AND DX COIL. PIPING SHALL BE REFRIGERANT GRADE TYPE "L" OR ACRCOPPER WITH BRAZED JOINTS. PIPE PER MANUFACTURER'S PIPING DIAGRAMS AND RECOMMENDATIONS.
2. AFTER COMPLETION, PRESSURE TEST PIPING, PURGE AND EVACUATE SYSTEM TWICE AND CHARGE SYSTEM WITH REFRIGERANTAND OIL.
3. INSTALL PIPING IN AS SHORT AND DIRECT ARRANGEMENT AS POSSIBLE TO MINIMIZE PRESSURE DROP. PROVIDE OIL TRAP ASRECOMMENDED BY THE EQUIPMENT MANUFACTURER.
4. INSTALL UNIONS TO ALLOW REMOVAL OF SOLENOID VALVES, PRESSURE REDUCING VALVES, EXPANSION VALVES, AND AT
CONNECTIONS TO COMPRESSORS AND EVAPORATORS.
5. FILL THE PIPE AND FITTINGS DURING BRAZING, WITH NITROGEN TO PREVENT FORMATION OF SCALE.
DUCTWORK & PIPE INSULATION (230713, 230719)
1. INSULATE REFRIGERANT PIPING LINES WITH 1-1/2" THICK CLOSED CELL ELASTOMERIC FOAM INSULATION WITH SELF-SEALING SEAM.ARMACELL - AP ARMAFLEX SS INSULATION. PAINT CLOSED CELL INSULATION OUTDOORS WITH TWO COATS OF UV RESISTANTPAINT PER MANUFACTURER'S RECOMMENDATIONS. USE PRE-MOLDED COVERS OVER FITTINGS, VALVES, ELBOWS AND CONTROLDEVICES SEALED VAPOR TIGHT.
2. INSULATION SHALL BE OMITTED FROM HOT SYSTEM VALVE BODIES STRAINERS AND UNIONS. SYSTEMS OPERATING BELOWAMBIENT TEMPERATURE SHALL HAVE ALL VALVE BODIES AND PIPING SPECIALTIES FULLY INSULATED. ALL GLYCOL AND CITYWATER PIPING SHALL BE COVERED SAME AS HOT WATER PIPING. ALL VALVE BODIES, STRAINERS, UNIONS, PUMP CASING, WATERSEPARATORS, ETC. IN COLD PIPING SHALL BE COVERED SAME AS PIPING SYSTEM. PIPE HANGERS ON INSULATED PIPE SHALL BEOUTSIDE OF THE INSULATION, SIZED ACCORDINGLY AND WITH SADDLE INSERT SUFFICIENT TO PROTECT INSULATION FROMCRUSHING.
3. ALL INSULATION TO BE APPLIED IN FULL ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ALL INSULATION SHALLCOMPLY WITH 25/50 FLAME AND SMOKE HAZARD RATINGS PER ASTM E-84, NFPA 255 AND UL 723.
4. PROVIDE REMOVABLE INSULATION SECTIONS TO COVER PARTS OF EQUIPMENT WHICH MUST BE OPENED PERIODICALLY FORMAINTENANCE; INCLUDE METAL VESSEL COVERS, FASTENERS, FLANGES, CHILLED WATER PUMPS, FRAMES AND ACCESSORIES.
5. REPLACE DAMAGED INSULATION WHICH CANNOT BE REPAIRED SATISFACTORILY, INCLUDING UNITS WITH VAPOR BARRIER DAMAGEAND MOISTURE SATURATED UNITS.
EQUIPMENT (235000)
1. MAKE ALL FINAL EQUIPMENT CONNECTIONS AND PROVIDE THE NECESSARY ADAPTORS, FITTINGS, VALVES, DEVICES, ETC. FOR ACOMPLETE AND OPERABLE SYSTEM. PROVIDE COMPLETE WITH BASES, ISOLATORS, SUPPORTS AND OTHER REQUIREDACCESSORIES.
2. EQUIPMENT SHALL BE INSTALLED IN FULL ACCORDANCE WITH THE MANUFACTURER'S DATA AND INSTALLATION INSTRUCTIONS,INCLUDING CLEARANCES; LUBRICATE AND ADJUST AS REQUIRED. IT IS THIS CONTRACTOR'S RESPONSIBILITY TO CHECK ANDCONFORM TO THESE REQUIREMENTS PRIOR TO STARTING WORK. FURNISH AND INSTALL CLEAN SET OF FILTERS PRIOR TOBALANCING.
3. THE CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS OF ALL MECHANICAL EQUIPMENT PRIOR TO ORDERING OFEQUIPMENT. COORDINATE REQUIREMENT FOR PROVISION OF MOTOR STARTERS, DISCONNECTS, CONTACTORS, CONTROL WIRING,ETC. AS REQUIRED FOR PROPER FUNCTIONING SYSTEM WITH ELECTRICAL CONTRACTOR. NO ADDITIONAL PAYMENT WILL BE MADEFOR LACK OF CONTRACTOR COORDINATION OF ELECTRICAL CHARACTERISTICS.
4. ALL FLOOR MOUNTED EQUIPMENT SHALL BE INSTALLED ON CONCRETE HOUSEKEEPING PADS. MINIMUM PAD THICKNESS SHALL BENOMINAL 4”. PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 4” ON EACH SIDE. CONCRETE PADS SHALL BE PROVIDEDBY THIS CONTRACTOR. IT SHALL BE THE RESPONSIBILITY OF THE THIS CONTRACTOR TO COORDINATE THE SIZE AND LOCATION OFTHE CONCRETE HOUSEKEEPING PADS WITH THE GENERAL CONTRACTOR.
5. ALL EQUIPMENT SHALL BE MOUNTED ON VIBRATION ISOLATORS TO PREVENT THE TRANSMISSION OF VIBRATION ANDMECHANICALLY TRANSMITTED SOUND TO THE BUILDING STRUCTURE.
6. ISOLATION EQUIPMENT SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER, AND SHALL BE DESIGNED SPECIFICALLY FOR THEAPPLICATION REQUIRED. THIS INCLUDES, BUT IS NOT LIMITED TO, PIPING DUCTWORK, PUMPS, COMPRESSORS. VIBRATIONISOLATORS SHALL BE RATED FOR THE WEIGHT AND SPACING REQUIRED FOR THE EQUIPMENT REQUIRING ISOLATION.
7. PROVIDE CURBS FOR ALL ROOF OPENINGS FOR DUCTS, FLUES, PIPING AND EQUIPMENT. CURBS SHALL BE FURNISHED ASACCESSORIES TO THE EQUIPMENT OR 8" HIGH PATE OR EQUAL EQUIPMENT SUPPORTS SPANNING STRUCTURE AND FLASHED INTOROOFING. ALL CUTTING, FLASHING, AND PATCHING OF ROOF SHALL BE BY OWNER'S ROOFING CONTRACTOR AND PAID FOR BYMECHANICAL CONTRACTOR.
CONTROLS (230910)
1. CONTROL SEQUENCE SHALL BE AS FOLLOWS:
· AC UNIT (AC-1, CU-1) -- REMOTE WALL MOUNTED THERMOSTAT SHALL CYCLE UNIT TO MAINTAIN A ROOM TEMPERATURE OF 72°F(ADJ).
HANGERS AND SUPPORTS (230529)
1. SUPPORT ALL PIPING FROM STRUCTURE WITH UL LISTED HANGERS AND SUPPORTS SUITABLE FOR THE INTENDED INSTALLATION. DESIGN, SELECTION, SPACING, AND APPLICATION OF HANGERS AND SUPPORTS SHALL COMPLY WITH ANSI B31.1 AND MSS SP-69.HANGERS SHALL BE MANUFACTURED BY PENTAIR., OR APPROVED EQUAL. BLACK OR GALVANIZED STEEL PIPE = MODEL NO. 100,CAST IRON PIPE = MODEL NO. 400, COPPER TUBING = MODEL NO. 102-A.
2. CONTRACTOR SHALL PROVIDE INSULATION HANGER WITH PROTECTIVE SHIELDS, SUCH AS PENTAIR, MODEL NO. 125, OR APPROVEDEQUAL FOR ALL INSULATED PIPING.
3. CONTRACTOR SHALL PROVIDE RISER CLAMPS FOR VERTICAL PIPING AT EACH LEVEL. RISER CLAPS SHALL BE PENTAIR MODEL NO.510 FOR STEEL PIPING AND MODEL NO. 511 FOR COPPER TUBING OR APPROVED EQUAL. USE "SHORT-END" RISER CLAMPS WHERESPACE IS LIMITED.
4. CONTRACTOR SHALL PROVIDE SIDE BEAM CLAMPS FOR SUPPORTING PIPING FROM STRUCTURAL STEEL MEMBERS. BEAM CLAMPSSHALL BE MANUFACTURED BY PENTAIR, MODEL 300 OR APPROVED EQUAL.
5. WHERE OTHER MEANS OF SUPPORT PIPING ARE REQUIRED OR DESIRED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAININGTHE ENGINEER'S APPROVAL PRIOR TO INSTALLING THOSE SUPPORTS.
6. HANGERS AND SUPPORTS SHALL BE SPACED AT INTERVALS WHICH WILL PREVENT SAGGING AND REDUCE STRAIN ON VALVESAND SPECIALTIES. HANGER SPACING SHALL BE NO GREATER AND ROD SIZE SHALL BE NO SMALLER THAN THAT SHOWN IN THEFOLLOWING TABLE. HANGERS SHALL ALLOW FOR EXPANSION AND CONTRACTION. HANGER SHALL BE PROVIDED AT EACHCHANGE OF DIRECTION.
7. RISER CLAMPS SHALL BE INSTALLED ABOVE THE FLOOR AT EACH LEVEL. RISER CLAMPS MAY BE SUSPENDED BELOW FLOORLEVEL, WITH HANGER RODS AND INSERTS, WHERE THE INSTALLATION OF ESCUTCHEON PLATES IS REQUIRED.
PIPE WALL SEALS (230517)
1. WALL PIPE SEALS WITH RUBBER LINKS SHALL BE THUNDERLINE LINK SEAL, OR APPROVED EQUAL. WALL PIPE SEALS WITHINORGANIC MATERIAL LINKS THE PENETRATIONS OF FIRE RATED WALLS SHALL BE THUNDERLINE PYRO-PAC, OR APPROVED EQUAL.
2. SEALS SHALL BE MODULAR MECHANICAL TYPE CONSISTING OF INTERLOCKING SYNTHETIC RUBBER OR INORGANIC MATERIAL LINKSSHAPED TO CONTINUOUSLY FILL THE ANNULAR SPACE BETWEEN THE PIPE AND WALL OPENING. LINKS SHALL BE LOOSELYASSEMBLED WITH BOLTS TO FORM A CONTINUOUS BELT AROUND THE PIPE. A PRESSURE PLATE SHALL BE PROVIDED UNDER THEBOLT HEAD AND NUT OF EACH LINK. SEALS SHALL BE CONSTRUCTED TO PROVIDE ELECTRICAL INSULATION BETWEEN THE PIPEAND SLEEVE, THUS REDUCING CHANCES OF CATHODIC REACTION BETWEEN THESE TWO MEMBERS.
3. AFTER THE SEAL ASSEMBLY IS POSITIONED IN THE SLEEVE, THE TIGHTENING OF THE BOLTS SHALL CAUSE THE SEALING ELEMENTSTO EXPAND AND PROVIDE AN ABSOLUTELY WATER-TIGHT SEAL BETWEEN THE PIPE AND SLEEVE.
4. SLEEVES SHALL BE MANUFACTURED FROM HEAVY-WALL, WELDED OR SEAMLESS STEEL PIPE. A FULL CIRCLE CONTINUOUSLYWELDED WATER STOP PLATE SHALL BE PROVIDED TO ASSURE POSITIVE WATER SEALING OF THE SLEEVE. SLEEVE SHALL BEPROTECTED BY A COATING OF ENRICHED RED PRIMER.
IDENTIFICATION (230593)
1. CONTRACTOR SHALL PROVIDE IDENTIFICATION LABELS, TAGS, ETC. AS INDICATED ON THE DRAWINGS AND AS SPECIFIEDHEREIN.THE IDENTIFICATION SHALL BE IN ACCORDANCE WITH ANSI STANDARD A13.1. PRESSURE SENSITIVE MARKERS SHALL BEMANUFACTURED BY THE BRADY CO., OR APPROVED EQUAL. MARKERS SHALL BE MANUFACTURER'S STANDARD PRODUCT.PRESSURE SENSITIVE PIPE MARKERS SHALL BE MANUFACTURED BY THE BRADY CO., OR APPROVED EQUAL. PIPE MARKERS SHALLBE MANUFACTURER'S STANDARD PRODUCT.
DISCONNECT SWITCHES (230514)
1. THIS CONTRACTOR SHALL FURNISH ALL SAFETY DISCONNECT SWITCHES (FUSED AND NON-FUSED) REQUIRED FOR EQUIPMENTFURNISHED UNDER THIS CONTRACT. IN ADDITION, THIS CONTRACTOR SHALL FURNISH A SAFETY DISCONNECT SWITCH FOR ALLMOTORS AND EQUIPMENT WHICH DO NOT HAVE COMBINATION STARTERS OR INTEGRAL DISCONNECTING MEANS. FUSIBLEDISCONNECT SWITCHES SHALL BE PROVIDED FOR ALL EQUIPMENT RATED FOR USE ONLY WITH FUSES (SUCH AS CONDENSINGUNITS, COMPRESSORS, ETC.). SUCH SWITCHES SHALL BE ONE, TWO OR THREE POLE TYPE, WITH SOLID NEUTRAL FOR 4 WIRESERVICE, AND SHALL HAVE THE PROPER CURRENT AND VOLTAGE RATING AS REQUIRED. INSTALLATION OF ALL DISCONNECTSWITCHES SHALL BE BY THE ELECTRICAL CONTRACTOR.
2. ALL SAFETY SWITCHES SHALL BE NEMA HEAVY DUTY TYPE AND SHALL CARRY THE UNDERWRITERS' LABORATORIES LABEL.FUSIBLE SWITCHES SHALL INCORPORATE CLASS "R" FUSE REJECTION FEATURE AND SHALL BE BRACED TO WITHSTAND 200,000AMPERE RMS SYMMETRICAL FAULT CURRENT. SAFETY SWITCHES SHALL CONFORM TO FEDERAL SPECIFICATION W-S-865.
3. PROVIDE HEAVY-DUTY TYPE, SHEET ENCLOSED, SAFETY SWITCHES. THE TYPE, SIZE, AND RATING SHALL BE AS INDICATED ON THEDRAWINGS OR AS REQUIRED BY THE MOTOR OR EQUIPMENT SERVED. THE ENCLOSURE FOR DISCONNECT SWITCHES SHALL BENEMA TYPE 1 FOR INDOOR USE, NEMA TYPE 4X FOR OUTDOOR USE AND NEMA TYPE 7 FOR EXPLOSION PROOF USE. DISCONNECTSSHALL BE MANUFACTURED BY ALLEN-BRADLEY, GENERAL ELECTRIC, CUTLER-HAMMER APPROVED EQUAL.
4. SWITCHES SHALL INCORPORATE QUICK-MAKE, QUICK-BREAK OPERATING HANDLES. THE MECHANISM SHALL BE AN INTEGRAL PARTOF THE BOX, NOT THE COVER, AND SWITCHES SHALL HAVE A COVER INTERLOCK TO PREVENT UNAUTHORIZED OPENING OF THESWITCH DOOR IN THE ON POSITION OR CLOSING OF THE SWITCH MECHANISM WITH THE DOOR OPEN. CURRENT CARRYING PARTSSHALL BE CONSTRUCTED OF HIGH-CONDUCTIVITY COPPER WITH SILVER-TUNGSTEN TYPE SWITCH CONTACT.
5. FUSE CLIPS SHALL BE POSITIVE PRESSURE TYPE REINFORCED FUSE CLIPS.
6. THE ELECTRICAL CONTRACTOR SHALL FURNISH, INSTALL AND CONNECT ALL POWER WIRING TO ALL MECHANICAL CONTRACTORFURNISHED EQUIPMENT. THE MECHANICAL CONTRACTOR SHALL FURNISH, INSTALL AND CONNECT ALL CONTROL WIRING TO ALLFURNISHED EQUIPMENT, INCLUDING CONTROL DEVICES, STARTERS AND INTEGRAL DISCONNECT SWITCHES OF CONTRACTORFURNISHED EQUIPMENT.
CHECK, TEST, START, ADJUST, BALANCE AND INSTRUCTIONS (230593)
1. AFTER INSTALLATION, CHECK ALL EQUIPMENT, AND PERFORM START UP IN ACCORDANCE WITH THE MANUFACTURER'SINSTRUCTIONS.
2. ALL PIPING SHALL BE TESTED AND FREE OF LEAKS.
3. BALANCE ALL SYSTEMS, CALIBRATE CONTROLS, CHECK FOR PROPER OPERATION AND SEQUENCE UNDER ALL CONDITIONS ANDMAKE ALL NECESSARY ADJUSTMENTS.
4. AFTER INSTALLATION AND EQUIPMENT IS PLACED IN OPERATION, HVAC CONTRACTOR IS RESPONSIBLE FOR BALANCING SYSTEMS.BALANCING SHALL BE PERFORMED BY AN INDEPENDENT AABC CERTIFIED CONTRACTOR.
5. ADJUST AND BALANCE THE AIR SYSTEMS BEFORE HYDRONIC, STEAM, AND REFRIGERANT SYSTEMS. TESTING AND BALANCINGSHALL BE DONE IN ACCORDANCE WITH THE MOST RECENT AABC NATIONAL STANDARDS FOR TOTAL SYSTEM BALANCE. GPM'SSHALL BE BALANCED WITHIN 10% OF DESIGN. AFTER ALL AIR SYSTEMS ARE INSTALLED, EACH SUPPLY AIR OUTLET SHALL BE AIRBALANCED TO WITHIN 10% OF THE CFM SHOWN WITH AIR PATTERNS SET AS INDICATED ON DRAWINGS (OR WITHIN 10 CFM WHENBELOW 100 CFM). FAN RPMS AND ZONE DAMPERS SHALL BE ADJUSTED AND SHEAVES SHALL BE REPLACED AS REQUIRED TOACHIEVE AIR BALANCE. ALL ZONES OR PORTIONS THEREOF SERVING OTHER SPACES AND WHICH MAY BE AFFECTED BY THEPROJECT SHALL BE TRAVERSED PRIOR TO CONSTRUCTION. THE FINAL AIR BALANCE SHALL RESTORE THESE AIR QUANTITIES. BEFORE AND AFTER AIR QUANTITIES SHALL BE LISTED IN THE AIR BALANCE REPORT
6. START UP AND PLACE ALL SYSTEMS IN OPERATION AND TAG ALL SWITCHES AND CONTROLS WITH PERMANENT LABELS.
5. INSTRUCT OWNER IN OPERATION OF SYSTEMS AND SUBMIT OPERATING AND MAINTENANCE MANUAL ON ALL EQUIPMENT ANDSYSTEMS.
DATE
REVISIONS
NO.
DESIGNED:
DRAWN:
DATE:
CHECKED:
SCALE:
07-21-17
AS NOTED
800 Allegheny Avenue Pittsburgh, Pennsylvania 15233
DRAWING NUMBER:
NORTH CAMPUS -
8701 PERRY HIGHWAY, PITTSBURGH PA. 15237
UPS AND GENERATOR UPGRADES
COMMUNITY COLLEGE OF ALLEGHENY COUNTY
ASE PROJ. NUMBER: - 1741037
CCAC PROJ. NO.: - 13-C003n5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
RJP
RJP
DCP
MECHANICAL SPECIFICATIONS
M002
11171119112111231125112711291131113311351137113911411143
1100I
1145
1140
1100G
1136 1116
1112A
1116A
1100G
1112 11151100E
1100D
11101110A1111
1113
1109
1107
1100
1108A1120B
1108
11181142 1134
1138
1138
1100J
1100R
1147A 1145A 1100K
1147
1172
1170 1149
11671168A1168
11661100Q
11641165B
1153
1155
1157
1165A1165
1161
1159
1166
1150C
1148
1144B
1144
1144D
1150
1100P
1011A11521011
1159
1007B
1007A
1007
1124B
1007A
1150A
1126C
1126B
1124A 1124
1126A1005H
1005I
1005J
1005A
1005
1005
1005K
11261146
1144C
1144A1130 1128 1100H
1128A1128B
1120
1100C
1120A
1122
1005G1005F
1005E1005D
1122A1122A
1122D
1122C
1005C
1100L
1105
11031106
1104
1102
1003F 1003E 1003D1101
1003J 1003C
1003G
1100B
1100A
1003G
1003G 1003A
1003B1001
1100J1001D
1000B
1003
1003
L10
03R
EXISTING FLOORDRAIN
AC2
1-1/4" D
AC1
23
1
UP TO SECONDFLOOR ROOF
4
MECHANICAL KEYED NOTES:
1. TERMINATE CONDENSATE AT FLOORDRAIN.
2. TWO CEILING SUSPENDED UNITSSTACKED.
3. REFRIGERANT PIPING SIZED PERMANUFACTURER'S RECOMMENDATION.COORDINATE EXACT ROUTING OF PIPINGIN FIELD.
4. NEW SPRINKLER HEAD IN CLOSET. TIEINTO EXISTING SPRINKLER SYSTEM.
#
CU1
CU2
MECHANICAL KEYED NOTES:
1. REFRIGERANT PIPING DOWN TO FIRST FLOOR. SIZEPIPING ACCORDINDING TO MANUFACTURER'SRECOMMENDATION. COORDINATE EXACT ROUTINGOF PIPE IN FIELD
2. CONDENSERS MOUNTED ON ROOF RAILS ONSECOND STORY ROOF.
#
1
2
PIPE PORTAL
DATE
REVISIONS
NO.
DESIGNED:
DRAWN:
DATE:
CHECKED:
SCALE:
07-21-17
AS NOTED
800 Allegheny Avenue Pittsburgh, Pennsylvania 15233
DRAWING NUMBER:
NORTH CAMPUS -
8701 PERRY HIGHWAY, PITTSBURGH PA. 15237
UPS AND GENERATOR UPGRADES
COMMUNITY COLLEGE OF ALLEGHENY COUNTY
ASE PROJ. NUMBER: - 1741037
CCAC PROJ. NO.: - 13-C003n5
NA
HT
PROFESSIONAL
DAVID C. PRICE
N
P
NE
L
No. PE081572
YS V
ENGINEER
NOM
MO
C
L
REGISTERED
EW A
AI
FO
SPLIT SYSTEM AIR-COOLED A/C UNIT SCHEDULE
EVAPORATOR CONDENSER
TAGTOTAL
CAPACITYMBH
SENSIBLECAPACITY
MBH
CFM(DRYCOIL)
E.S.P.IN.
W.G.
NOMINALTONS MCA/MFS ELECTRICAL
VOLTS/PHASEMITSUBISHI
MODEL TAG CFME.S.P.
IN. W.G.
MCA/MOCP ELECTRICALVOLTS/PHASE
UNITED COOLAIRMODEL REMARKS
AC-1 36 26.3 920 0.0 3.02.0A/SERVED
FROMCONDENSER
208 V/1Ø PCA-A36KA7 CU-1 3,880 0.00 25/31 208 V/1Ø PUY-A36NKA7 1,2,3,4.5
AC-2 36 26.3 920 0.0 3.02.0A/SERVED
FROMCONDENSER
208 V/1Ø PCA-A36KA7 CU-2 3,880 0.00 25/31 208 V/1Ø PUY-A36NKA7 1,2,3,4.5
NOTES:1. CAPACITY BASED ON 85 DEG. F. DB/65 DEG. F. WB EAT ON EVAPORATOR AND 95 DEGREES F. AIR ENTERING THE CONDENSER, MID.HIGH FAN SPEED2. UNIT SHALL BE EQUIPPED FOR OPERATION DOWN TO 0° F.3. PROVIDE THE FOLLOWING ACCESSORIES: INTEGRAL CONDENSATE PUMP MITSUBISHI MODEL SI1730-230.4. PROVIDE DISCONNECT FOR OUTDOOR AND INDOOR UNIT BOTH.5. PROVIDE INTEGRAL UNIT CONTROLS AND A HARD WIRED WALL MOUNTED THERMOSTAT/CONTROLLER.
1
M101GROUND FLOOR MECHANICAL PLAN1/16" = 1' -0"
2
M101PARTIAL ROOF MECHANICAL PLAN1/16" = 1' -0"
RJP
RJP
DCP
MECHANICAL PLANS
M101