MFG. #5401502 - REV F 05/12 PRINTED IN USA PAGE 1 OF 8 PS10-2A (CCCF) PRESSURE SWITCH Installation The Potter PS10 Series Pressure Actuated Switches are designed for the detection of a waterflow condition in automatic fire sprinkler systems of particular designs such as wet pipe systems with alarm check valves, dry pipe, preaction, or deluge systems. The PS10 is also suitable to provide a low pressure supervisory signal; adjustable between 4 and 20 psi (0,27 and 1,37 BAR). 1. Apply Teflon tape to the threaded male connection on the device. (Do not use pipe dope) 2. Device should be mounted in the upright position (threaded connection down). 3. Tighten the device using a wrench on the flats on the device. Wiring Instructions 1. Remove the tamper resistant screws with the special key provided. 2. Run wires through an approved conduit connector and affix the connector to the device. 3. Connect the wires to the appropriate terminal connections for the service intended. See Figures 2, 4, and 5. Testing The operation of the pressure alarm switch shall be tested upon completion of installation and periodically thereafter in accordance with the applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). Wet System Method 1: When using PS10 and control unit with retard - connect PS10 into alarm port piping on the input side of retard chamber and electrically connect PS10 to control unit that provides a retard to compensate for surges. Insure that no unsupervised shut-off valves are present between the alarm check valve and PS10. CCCF and FM Approved Dimensions: 4 3/4" (12,1cm)W x 2 1/4" (5,7cm)D x 4 3/8" (11,1cm)H Conduit Entrance: One knockout provided for 1/2" conduit. Enclosure: Cover - Die-cast with textured red powdercoat finish Base - Steel/Zinc plated Pressure Connection: Nylon 1/2" NPT Male Factory Adjustment: 5 - 7 PSI (0,34 - 0,48 BAR) Differential: 1 PSI (0,06 BAR) typical Maximum System Pressure: 250 PSI (17,2 BAR) Switch Contacts: Two SPDT (Form C) 15.0 Amps at 125/250VAC, 2.5 Amps at 30VDC Environmental Specifications: NEMA 4/IP66 Rated Enclosure - indoor or outdoor when used with NEMA 4 conduit fittings. Temperature range: -40°F to 140°F (-40°C to 60°C) Tamper: Cover incorporates tamper resistant fasteners that requires a special key for removal. One key is supplied with each device. For optional cover tamper switch kit, order Stock No. 0090134. See bulletin #5400984. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential Occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Potter Electric Signal Company • St. Louis, MO • Customer Service: 866-572-3005 • Tech Support: 866-956-0988 • Canada 888-882-1833 • www.pottersignal.com Method 2: When using the PS10 for local bell application or with a control that does not provide a retard feature - the PS10 must be installed on the alarm outlet side of the retard chamber of the sprinkler system. Testing: Accomplished by opening the inspector's end-of-line test valve. Allow time to compensate for system or control retard. Note: Method 2 is not applicable for remote station service use, if there is an unsupervised shut-off valve between the alarm check valve and the PS10. Wet System With Excess Pressure Connect PS10 into alarm port piping extending from alarm check valve. Retard provisions are not required. Insure that no unsupervised shut-off valves are present between the alarm check valve and the PS10. Testing: Accomplished by opening the water by-pass test valve or the inspector's end-of-line test valve. When using end-of-line test, allow time for excess pressure to bleed off. Dry System Connect PS10 into alarm port piping that extends from the intermediate chamber of the alarm check valve. Install on the outlet side of the in-line check valve of the alarm port piping. Insure that no unsupervised shut-off valves are present between the alarm check valve and the PS10. Testing: Accomplished by opening the water by-pass test valve. Note: The above tests may also activate any other circuit closer or water motor gongs that are present on the system. Ordering Information Model Description Stock No. PS10-2A (CCCF) Pressure switch with two sets 1340410 SPDT contacts Hex Key 5250062 Cover Tamper Switch Kit 0090134
Transcript
Page 1: PS10-2A (CCCF)

MFG. #5401502 - Rev F05/12

PRINTeD IN USA PAGe 1 OF 8

PS10-2A (CCCF)PRESSURE SWITCH

InstallationThe Potter PS10 Series Pressure Actuated Switches are designed for the detection of a waterflow condition in automatic fire sprinkler systems of particular designs such as wet pipe systems with alarm check valves, dry pipe, preaction, or deluge systems. The PS10 is also suitable to provide a low pressure supervisory signal; adjustable between 4 and 20 psi (0,27 and 1,37 BAR). 1. Apply Teflon tape to the threaded male connection on the device. (Do not use pipe dope)2. Device should be mounted in the upright position (threaded connection down).3. Tighten the device using a wrench on the flats on the device.

Wiring Instructions 1. Remove the tamper resistant screws with the special key provided. 2. Run wires through an approved conduit connector and affix the connector to the device. 3. Connect the wires to the appropriate terminal connections for the service intended. See Figures 2, 4, and 5.Testing The operation of the pressure alarm switch shall be tested upon completion of installation and periodically thereafter in accordance with the applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).Wet System Method 1: When using PS10 and control unit with retard - connect PS10 into alarm port piping on the input side of retard chamber and electrically connect PS10 to control unit that provides a retard to compensate for surges. Insure that no unsupervised shut-off valves are present between the alarm check valve and PS10.

CCCF and FM ApprovedDimensions: 4 3/4" (12,1cm)W x 2 1/4" (5,7cm)D x 4 3/8" (11,1cm)HConduit Entrance: One knockout provided for 1/2" conduit. Enclosure: Cover - Die-cast with textured red powdercoat finish Base - Steel/Zinc plated Pressure Connection: Nylon 1/2" NPT MaleFactory Adjustment: 5 - 7 PSI (0,34 - 0,48 BAR)Differential: 1 PSI (0,06 BAR) typicalMaximum System Pressure: 250 PSI (17,2 BAR)Switch Contacts: Two SPDT (Form C) 15.0 Amps at 125/250VAC, 2.5 Amps at 30VDCEnvironmental Specifications: NEMA 4/IP66 Rated Enclosure - indoor or outdoor when used with NEMA 4 conduit fittings. Temperature range: -40°F to 140°F (-40°C to 60°C) Tamper: Cover incorporates tamper resistant fasteners that requires a

special key for removal. One key is supplied with each device. For optional cover tamper switch kit, order Stock No. 0090134. See bulletin #5400984.

Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential Occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72

Potter Electric Signal Company • St. Louis, MO • Customer Service: 866-572-3005 • Tech Support: 866-956-0988 • Canada 888-882-1833 • www.pottersignal.com

Method 2: When using the PS10 for local bell application or with a control that does not provide a retard feature - the PS10 must be installed on the alarm outlet side of the retard chamber of the sprinkler system.Testing: Accomplished by opening the inspector's end-of-line test valve. Allow time to compensate for system or control retard. Note: Method 2 is not applicable for remote station service use, if there is an unsupervised shut-off valve between the alarm check valve and the PS10.

Wet System With Excess Pressure Connect PS10 into alarm port piping extending from alarm check valve. Retard provisions are not required. Insure that no unsupervised shut-off valves are present between the alarm check valve and the PS10. Testing: Accomplished by opening the water by-pass test valve or the inspector's end-of-line test valve. When using end-of-line test, allow time for excess pressure to bleed off.

Dry System Connect PS10 into alarm port piping that extends from the intermediate chamber of the alarm check valve. Install on the outlet side of the in-line check valve of the alarm port piping. Insure that no unsupervised shut-off valves are present between the alarm check valve and the PS10. Testing: Accomplished by opening the water by-pass test valve.Note: The above tests may also activate any other circuit closer or water motor gongs that are present on the system.

Ordering Information Model Description Stock No.PS10-2A (CCCF) Pressure switch with two sets 1340410 SPDT contacts Hex Key 5250062 Cover Tamper Switch Kit 0090134

Page 2: PS10-2A (CCCF)

MFG. #5401502 - Rev F05/12

PRINTeD IN USA PAGe 2 OF 8

PS10-2A (CCCF)PRESSURE SWITCH

Typical Sprinkler Applications

Switch Clamping Plate TerminalDimensions

OUTGOING

INCOMING

DWG# 923-3

WET SYSTEM WITH EXCESS PRESSURE

WATER MOTOR GONG

PS10

RBVSWET SYSTEM ALARM CHECK VALVE

OS & Y VALVE

WATER BY-PASS VALVE

WET SYSTEM WITHOUT EXCESS PRESSURE

WATER MOTOR GONG

WET SYSTEM ALARM CHECK VALVE

OS & Y VALVE

RBVS

WATER BY-PASS VALVE

RETARD

PS10

DRY SYSTEM ALARM CHECK VALVE

OS & Y VALVE

WATER BY-PASS VALVE

CHECK VALVE RBVS

DRY SYSTEM

PS10 WATER MOTOR GONG

DWG. #923-2AA

Fig. 2

Fig. 3

Fig. 1

An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

Closing of any shutoff valves between the alarm check valve and the PS10 will render the PS10inoperative. To comply with NFPA-72 any such valve shall be electrically supervised with asupervisory switch such as Potter Model RBVS.

NOTE: To prevent leakage, apply Teflon tape sealant to male threads only. Do not use Pipe Dope.

Use of Pipe Joint Cement may result in obstruction of the aperture and loss of signal.

FOR LOW PRESSURE SIGNALUSED ON DRY OR PRE-ACTION SYSTEMS WITH LESS THAN 20 PSI ONLY

EOLR

COMM NO NC

TO FIRE ALARM PANEL

POSITIVE DC OR HOT AC

NEGATIVE DC OR NEUTRAL AC

TO RING A LOCAL BELL FOR WATERFLOW

COMM NO NC

BELL

FOR WATERFLOW SIGNAL

EOLR

COMM NO NC

DWG# 5924-3TO FIRE ALARM PANEL

Typical Electrical ConnectionsFig. 4

Page 3: PS10-2A (CCCF)

MFG. #5401502 - Rev F05/12

PRINTeD IN USA PAgE 3 OF 8

PS10-2A (CCCF)PRESSURE SWITCH

•Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. •Shock hazard. Disconnect power source before servicing. Serious injury or death could result. •Read all instructions carefully and understand them before starting installation. Save instructions for future use. Failure to read and understand instructions could result in improper operation of device resulting in serious injury or death.•Risk of explosion. Not for use is hazardous locations. Serious injury or death could result.

•Do not tighten by grasping the switch enclosure. Use wrenching flats on the bushing only. Failure to install properly could damage the switch and cause improper operation resulting in damage to equipment and property. •To seal threads, apply Teflon tape to male threads only. Using joint compounds or cement can obstruct the pressure port inlet and result in improper device operation and damage to equipment. •Do not over tighten the device, standard piping practices apply.

Engineer/Architect Specifications Pressure Type Waterflow Switch Pressure type waterflow switches; shall be a Model PS10 as manufactured by Potter Electric Signal Company, St Louis MO., and shall be installed on the fire sprinkler system as shown and or specified herein.Switches shall be provided with a ½” NPT male pressure connection and shall be connected to the alarm port outlet of; Wet Pipe Alarm Valves, Dry Pipe Valves, Pre-Action Valves, or Deluge Valves. The pressure switch shall be actuated when the alarm line pressure reaches 5 - 7 PSI (0,34 - 0,48 BAR).Pressure type waterflow switches shall have a maximum service pressure rating of 250 PSI (17,2 BAR) and shall be factory adjusted to operate on a pressure increase of 5 - 7 PSI (0,34 - 0,48 BAR).

Pressure switch shall have two form C contacts, switch contact rating 15.0 Amps at 125/250 VAC, 2.5 Amps at 30 VDC.The cover of the pressure type waterflow switch shall be die-cast and shall attach with tamper resistant screws. The Pressure type waterflow switch shall be suitable for indoor or outdoor service with a NEMA 4/IP66 rating.The pressure type waterflow switch shall be CCCF and FM approved.

W/ PRESSURE APPLIED

W/O PRESSURE APPLIED

COM

DWG#1505-1

COM

Switch OperationFig. 5

TerminalNO: Closed when installed under normal

system pressure.NC: Open when installed under normal

system pressure. Closes on pressure drop. Use for low pressure supervision.

TerminalNO: Open with no pressure supplied.

Closes upon detection of pressure. Use for waterflow indication.

NC: Closed with no pressure applied.

Page 4: PS10-2A (CCCF)

MFG. #5401502 - Rev F05/12

PRINTeD IN USA PAGe 4 OF 8

PS10-2A (CCCF)PRESSURE SWITCH

This page intentionally left blank

Page 5: PS10-2A (CCCF)

MFG. #5401502 - Rev F05/12

85

PS10-2A (CCCF)压力开关

美国印制

安装Potter PS10系列压力开关适用于监测采用了特殊设计的自动喷水灭火系统的水流状况,所谓的特殊设计即指配备了警报单向阀、干管、预作用或雨淋灭火系统的湿管系统。PS10还适用于提供低压监控信号,调节范围为4至20psi(0,27 至1,37 BAR)。1. 将特氟隆带用到设备上的螺纹凸模连接上(不要使用管外壁涂料)。 2. 设备应以垂直方向进行安装(螺纹连接位于下方)。3. 用平面扳手固定设备。

配线使用说明 1. 使用配备的专用钥匙移除防篡改螺丝。2. 将线绕过合格的导管连接器,将连接器附在设备上。3. 针对想要应用的服务,将线连在适当的终端连接上。见图2、4、5。

测试完成安装后,应对压力警报开关的操作情况进行测试,并且按照相关的NFPA条例以及有关部门的相关规定进行周期性的测试(制造商建议至少每季度测试一次)。

湿系统 方法1:当使用PS10及延迟控制组件时,将PS10连接到延迟器输入侧的警报端口管系,并将PS10与提供延迟的控制组件进行电气连接,该延迟用来抵消电涌。请确保在警报单向阀和PS10之间没有不受监控的关闭阀。.

通过CCCF及FM认证尺寸: 长4 3/4" (12,1cm)x 宽2 1/4" (5,7cm)x 高4 3/8" (11,1cm)管道进口: 为1/2"的管道提供一个导管. 外壳: 外盖 - 印模压铸,红色喷粉抛光 底座 - 钢/锌板 压力连接: 尼龙1/2" NPT凸模工厂调整: 5 - 7 PSI (0,34 - 0,48 BAR)压差: 一般1 PSI (0,06 BAR) 系统最大压力: 250 PSI (17,2 BAR)开关触点:双SPDT (C形) 125/250 VAC时15.0 Amps , 30 VDC时2.5 Amps环境规格: NEMA 4/IP66额定外壳 - 当在室内或室外与NEMA 4导管配件一同使用时 温度范围:-40°F至140°F (-40°C至60°C) 防篡改: 外盖包含防篡改紧固件,需要专门钥匙才能移除。每台装置各配备一把钥匙。对于可选的外盖防篡改开关组件,请订购0090134号货品。具体内容请见5400984号文件。服务应用: 自动洒水机 NFPA-13 一到两个家庭的家居使用 NFPA-13D 不超过4层的住宅 NFPA-13R 国家火警法 NFPA-72

Potter Electric Signal Co., LLC • St. Louis, MO • 客服热线: 866-240-1870 • 技术支持:866-956-1211• 加拿大 888-882-1833 • www.pottersignal.com

方法2:当针对局部警铃应用系统使用PS10或与不配备延迟功能的控制器一同使用时 - PS10应安装在喷水灭火系统延迟器的警报输出侧。

测试:打开检测工具的行尾测试阀。匀出时间以抵偿系统或控制延迟。

注意:如果在警报单向阀和PS10之间存在一个不受监控的关闭阀,那么方法2则不适用于遥控站的服务应用。

超压湿系统

将PS10连接到从警报单向阀伸出的警报端口管系。这里不需要提供延迟。请确保在警报单向阀和PS10之间没有不受监控的关闭阀。

测试:打开分流测试阀或检测工具的行尾测试阀。应用行尾测试时,请匀出取消超压的时间。

干系统

将PS10连接到从警报单向阀的中间室伸出的警报端口管系 。 安 装 在警报端口管系的内部单向阀的输出侧。请确保在警报单向阀和PS10之间没有不受监控的关闭阀。

测试:打开分流测试阀。

注意:上述测试还有可能激活系统内其他闭路器或水动机报警铃。

订购信息 型号 描述 货号PS10-2A(CCCF) 双组压力开关 1340410 SPDT触点 六角键 5250062 外盖防篡改开关 0090134

Page 6: PS10-2A (CCCF)

MFG. #5401502 - Rev F05/12

86

PS10-2A (CCCF)压力开关

美国印制

一般灭火器应用

开关夹板端子尺寸 图2

图3

图1

一般电气连接

图4

超压湿系统

水动机警铃

PS10

RBVS湿系统报警止回阀

非超压湿系统

水动机警铃

湿系统报警止回阀

OS & Y 阀

RBVS

延时器

PS10

干系统报警止回阀

水中通测试阀

止回阀RBVS

干系统

PS10

水动机警铃

DWG. #923-2AA

水中通测试阀OS & Y 阀

水中通测试阀OS & Y 阀

低压信号仅限低于20 PSI的干系统或预作用系统

EOLR

COMM NO NC

正直流或热交流

负支流或中性交流

水流信号控制警铃

COMM NO NC

警铃

水流信号

EOLR

COMM NO NC

DWG# 5924-3

接火灾报警控制板

接火灾报警控制板

出口

入口

DWG# 923-3

单导线的绝缘段不用环绕在端子周围,而应作为两个单独的连接。线必须是隔断的,以便在将线从端子底下强行去除时,监控连接情况。

警告

使用管缝胶泥可能导致孔径阻塞及信号丢失。

警告

注意关闭警报单向阀和PS10之间的任何一个关闭阀门都将导致PS10不起作用。按照NFPA-72的规定,此类阀门应该受到监控开关(如Potter Model RBVS)的电子监控。

Page 7: PS10-2A (CCCF)

MFG. #5401502 - Rev F05/12

87

PS10-2A (CCCF)压力开关

美国印制

警告●必须由具备资质的人员按照全国及当地的有关法律规定进行安装。●存在电击危险。检修前切断电源。否则可能引发严重伤亡事故。 ●开始安装前请仔细阅读全部相关信息,并确保完全理解。请保留说明书以备未来之用。不阅读或不理解本说明书可能导致误操作,从而引发严重伤亡事故。●存在爆炸风险。不适于在危险场所使用。否则可能引发严重伤亡事故。

注意

●不要用手来拧紧开关。只能用衬套上的扳手压板。安装不当有可能损坏开关,引起误操作,从而对设备和财产造成损害。 ●在密封螺纹时,只能将特氟隆带用到凸模螺纹上。使用结合剂或胶结剂的话可能阻塞压力端口入口,引发误操作,损坏设备。●不要把设备拧的过紧,遵照标准管系操作惯例即可。

工程师/建筑师规格 压力型水流开关

压力类型水流开关,应为PS10型号,由密苏里州圣路易斯市Potter电气信号公司制造,应按照本说明的指示或规定安装在喷水灭火系统上。

开关应配备1/2”NPT凸模压力连接装置,而且应连接在湿管警报阀、干管阀、预作用阀或雨淋阀的警报端口输出侧、当警报线压力达到 5 - 7 PSI (0,34 - 0,48 BAR) 时,压力开关将被激活。压力型水流开关拥有额定250 PSI (17,2 BAR)的最大工作压力,而且在工厂内调节后可以应对5 - 7 PSI (0,34 - 0,48 BAR)的压力增幅。

压力开关拥有两个C型触点,触点额定电流在125/250 VAC时为15.0 Amps,在30VDC时为2.5 Amps。

压力型水流开关外盖为印模压铸,并附加防篡改螺丝。压力型水流开关应适于额定NEMA 4/IP66下的室内或室外工作。压力型水流开关应通过CCCF和FM认证。

开关操作图5

端子NO: 在系统正常压力下安装时闭合。NC: 系统正常压力下安装时打开。随着压力

的下降闭合。用于低压监控。

端子NO: 无压力时打开。探测到压力后闭

合。用于水流用于显示水流。NC: 无压力时闭合。

带压

无压

COM

DWG#1505-1

COM

Page 8: PS10-2A (CCCF)

MFG. #5401502 - Rev F05/12

88

PS10-2A (CCCF)压力开关

美国印制

本页特意空白。