P Series UPS DataBook Tower & Rack Mount on-line UPS Single Phase 700VA - 20kVA
Transcript
Page 1: PSeriesDataBook

P Series UPS DataBook

Tower & Rack Mount on-line UPSSingle Phase 700VA - 20kVA

Page 2: PSeriesDataBook

The P Series on-line UPS systems are available in tower and 19” rack formats with in-built batteries and with battery extensions. Versions are available with extra chargers to shorten battery recovery time. This document provides all technical details about our P Series range - providing protection from all ten mains supply problems. The P Series offers maximum versatility in application and long, trouble-free life.

P Series on-line UPS range

2

SPower P Series - technically advanced UPS

Input:Your UPS will provide reliable secure power, but it also should minimise the risk of any disturbance to your critical equipment, whilst having no impact on the incoming mains network. This is achieved by providing a wide input voltage range, typically 160 to 276 volts for a 240volt nominal product. This ensures that the UPS continues to be mains driven with large variations in voltage and that the battery is fully charged at all times. UPS systems can impact on the mains supply. Not only does the P Series provide you with high integrity output but the input mains should see near zero impact. This is achieved as follows:-

Power factor correction• notionally to unity which gives optimum energy consumption from the mains source.A• sine wave input current is generated by the latest rectifiertechnology.Thisensuresthattheharmonicfedback to the mains is negligible.Rectifier• soft start means that there is no inrush current impact on the mains during UPS switch on.

Note the last two points ensure that the UPS does not need you to oversize the mains or any standby diesel generator systems on the input side. Spike and surge protection are provided for in the UPS design by in-built lightning and surge protection devices on the UPS input, additionally the UPS has independent network, fax and modem surge protection.

Output:The P Series is output optimised. Not only do they produce high quality regulated sine wave output with close frequency tolerance, additionally they have:-Output short circuit and overload protection to ensure that the load and the UPS operate correctly and safely in abnormal conditions. Cold start function (start from DC battery power only) - this can be a life saver when restarting a plant or system after a major mains supply shutdown; and UPS Green Mode - energy saving function (active standby operation), the UPS can be parameterised to operate in this mode. This means the mains has priority and the UPS operates in no load standby mode. It will come into action should the mains fail. This mode of operation incurs only a small no load loss of the UPS hence it is more energy efficient.

The UPS has two groups of controllable load output sockets for load segmentation; these can be parameterised using the software included with each UPS. By grouping loads into a high and low priority groups it is possible to switch them off automatically at different times after mains failure. This allowsyoutooptimisetheloadprofileandautonomy;andcan save the cost of additional batteries.

Controls:The P Series has fully digitised microprocessor control providingalltheabovebenefitswithspeedandaccuracy;an Emergency Power Off function to allow the UPS to be completely shutdown at the push of a button in the event severe situations; and automatic fan speed control to ensure that all UPS components are carefully cooled and operate at their optimum temperatures. This ensures continuous correct operation and system longevity.

In the design of the SPower P Series attention has been paid to all areas of UPS technology; detailed comparison will show that the best solution for your single phase applications is the P Series.

Page 3: PSeriesDataBook

3

UPS Technology Protection from: SPower range (single phase)

Passive Standby (Offline)

As long as the mains is present, the load is supplied directly by the mains. In the case of a power problem the inverter starts up and takes over the load supply after a shortinterruption-therectifiercanonlychargethebat-tery. Basic protection.

power failure voltage drop voltage spikes A

Line Interactive (Hybrid)

The mains and the inverter run in parallel, the mains input suppliestheloadandtheinverterrefinesthepowerqual-ity and charges the battery. In the case of power failure the mains switch opens and the load is supplied from the battery via the inverter. Improved protection.

power failure voltage drop voltage spikes low voltage surges

C, H

Double Conversion (On Line)

Theunitrunsconstantlywiththerectifierconvertingthemains to DC which charges the battery and supplies the inverter. The inverter continuously supplies the load with a constant voltage and frequency - the unit prevents surges and mains “noise” from reaching the load. When the mains fails the inverter continues to be supplied from the inverter which is powered by the battery.

power failure voltage drop voltage spikes lightning effects under voltage over voltage voltage surge frequency variation voltage distortion voltage harmonics

P(this Data-

Book)

Battery: The key component of any UPS system is its battery. SPower produce UPS systems that ensure the battery can be operated and maintained properly to allow the system to achieve the very best integrity and reliability. This is achieved by advanced battery management (three-stage charging); allowing carefully controlled battery charging to ensure both battery availability and extended life. If the supply is connected then automatic battery charging is provided even with UPS in off mode

To ensure the battery is not over discharged and damaged, a battery protection cut off is provided when the battery voltage becomes too low; and in order that the battery is in prime condition automatic battery diagnostics are carried out to establish the backup time and calculate replacement information.

Batterieshaveafinitelifewhichistypically3to5yearsinthe P Series UPS. The UPS will indicate the end of battery life. To minimise the potential disturbance when changing the battery this is housed in a “hot swappable” battery cassette. This makes battery change-out possible with the UPS still in service - eliminating load side downtime.

You may have loads that required to be supported for longer times than those available from the UPS internal battery. SPower provides a range of battery packs to give extended autonomy. The use of battery packs to extend the autonomy may give rise to questions of battery recharge when using the standard internal UPS charger. SPower can help with this problem using its range of external chargers and battery packs with their own charger.

Communications:Provision of high quality power is our byword, however it is equally vital to know what’s going on with your UPS and mains supply; and to communicate this information to users and support staff both locally and remotely.

Each UPS has a multilingual front panel LCD-Display. This has two functions:-

To display accurate measurements of the UPS input •and output parameters. These include voltage, current, power, VA, Crest factor, frequency, remaining autonomy time, and other detailed information.To display, and together with the front panel mounted •push buttons, allow the UPS system parameters to be set and stored.

In addition to local information and control each UPS comes with free SPower communication software included. This allows the use of the UPS communication ports to provide information remotely. The following are provided:-

USB output socket with cable.•RS232 output socket with cable.•Interface slot which can accommodate either an •optional SNMP or relay card.

The software can be installed on a local or remote computer to do the following:-

To display accurate measurements of the UPS input •and output parameters. These include voltage, current, power, VA, Crest Factor, frequency, remaining autonomy time, and other detailed informationThe display and setting of the UPS system parameters.•Scheduling shutdown and reboot of the connected •equipment.Recording of power disturbance and alarm events.•

There are three main UPS technologies, SPower supplies all three, allowing you freedom of choice. All UPS systems have to supply the load, charge the battery and produce mains from the battery when the supply is not present; however the degree of protection they offer differs>>>

Page 4: PSeriesDataBook

P Series Tower700-1000-2000-3000VATower Model SP P700 SP P1000 SP P2000 SP P3000OUTPUT Capacity 700VA / 490W 1000VA / 700W 2000VA / 1400W 3000VA / 2100W

Voltage (selectable) single phase 208V, 220V, 230V, 240V +/-2% Frequency (on battery) 50/60Hz+/-0.5%HighEfficiencyMode >95%(ACtoAC)Efficiency 87% linear load 92% linear loadHarmonicDistortion <3%ofTHDatlinearloadCrest Factor 3:1Output Sockets 4 X IEC 60320

C134 X IEC 60320

C138 X IEC 60320 C13 1 X IEC 60320 C19

INPUT Voltage Single Phase 208V/220V/230V/240VVoltage Range

120 ~ 139V140~159V160 ~ 276V

Load Capacity 0 ~ 40% 0 ~ 70% 0 ~ 100%

Frequency 50/60HzAutoSensingConnector IEC 60320

BATTERY Type Sealed, maintenance-free lead acid batteriesDC Voltage (V) 24V/2x12V7.2AH 36V/3x12V7.2AH 72V/6x12V7.2AH 72V/6x12V9AHTypical Recharge Time 3 hours (to 90%) Back Up Time (Full Load) 7 min. 6 min. 6 min. 5min.BackUpTime(HalfLoad) 15min. 15min. 15min. 14 min.

PROTECTION Surge Protection IEC61000-4-5level3Overload Protection 125%for1min.and150%for10sec.

COMMUNICATION Audible Alarm Battery Back-Up / UPS faultVisual Display Input / output voltage, input / output frequency, on-line mode, back up mode,

battery capacity, loadlevelMonitoring RS-232 Serial Port and USB; optionally SNMP Slot

ENVIRONMENT Operating Temperature 0 - 40 deg. CStorage Temperature -20~50deg.CInstallation Altitude upto3500mAudible Noise < 40 dBA (1 metre from surface)RelativeHumidity 0~95%humidity,non-condensing

CONFORMANCE Safety CE, UL 1778 EMC conformance IEC61000-4,FCCPart15,CISPR22

COLOUR Anthracite (RAL 7016)SOFTWARE SPower Communication SoftwareACCESSORIES Battery expansion, connecting cable, USB, SNMP , Relay CardWEIGHT (kg) 13.5 16.2 31.6 32.5DIMENSION (mm)WxDxH 152x420x237 225x425x360

SP P700 and P1000 SP P2000 and P3000

NEMAsocketandlowvoltageversions(100V/110V/115V/120V/127Vopt)areavailabletospecialorder

4

All P Series units have an external Emergency Power Off circuit - making sure that safe working can be done.

All P Series units have loadconfigurablesegmentation - allowing less critical loads to be switched off after a certain time in battery mode.

Page 5: PSeriesDataBook

P Series Tower6-10-20 kVATower Model SP P6 SP P10 SP P20OUTPUT

Capacity 6000VA / 4200W 10000VA / 7000W 20000VA / 14000WVoltage (on battery) 208, 220V, 230V, 240V +/-2%Frequency (on battery) 50/60Hz+/-0.5%Overload Recovery Auto transfer to UPSHighEfficiencyMode > 98 % (AC to AC)Output Wave Form Sine waveHarmonicDistortion <3%ofTHDatlinearloadCrest Factor 3:1

INPUT Voltage Single Phase

208V/220V/230V/240V Voltage / Range Load Capacity

120 ~ 139V140~159V160 ~ 276V

0 ~ 40%0 ~ 70%0 ~ 100%

Frequency 50/60HzAutoSensingCONNECTION Hardwire

BATTERY

Type Sealed, maintenance-free lead acid batteries DC Voltage (V) Battery 240V/20x12V7.2AH 240V/20x12V9AH 240V/20x12V9AHTypical Recharge Time 4 hours (90% full)Management Self-test, adjustable battery transfer points and alarm settingsBattery Protection Cut off without draining any current when battery is lowBack Up Time 6min.fullload/15min.halfload

PROTECTION Surge Protection IEC61000-4-5Level3Overload Protection 125%for1min.and150%for10sec.Short Circuit Protection UPS output cut off / input fuse/circuit breaker protection

COMMUNICATION

Audible Alarm Battery Back-Up / UPS faultVisual Display Input / output voltage, input / output frequency, on-line mode, back

up mode, battery capacity, load level Monitoring RS-232 Serial Port and USB; optionally SNMP Slot

ENVIRONMENT Operating Temperature 0 - 40 deg. C Storage Temperature -20~50deg.COperating Altitude upto3500mAudible Noise <55dBA(1metrefromsurface)RelativeHumidity 0~95%humidity,non-condensing

CONFORMANCE Safety UL 1778, CE EMC (EMS / EMI) IEC61000-4,FCCPart15,CISPR22

SOFTWARE SPower Communication Software ACCESSORIES Battery expansion, connecting cable, USB, SNMP , Relay CardCOLOUR Anthracite (RAL7016) WEIGHT W/O ISOT (kg) 86 112 175

W ISOT (kg) 123 180 225DIMENSION W/OISOTWxDxH(mm) 257x590x570 257x690x715 342x863x905

WISOTWxDxH(mm) 257x590x700 342x690x715 342x863x905

5

The SP 6-10-20 tower units are also available with several types of battery extension units and various special battery chargers. Allowing you to build the system to meet exact application requirements. The answer to higher power and extended autonomy with the simplicity of single phase supply. Call for further details.

If you need single phase power >3 kVA this can be also supplied from a 3 phase supply by using our 3 phase in / single phase out units.

All P Series > 3kVA are fittedwithamanualbypass - the load can be supplied even if the UPS is switched OFF.

Page 6: PSeriesDataBook

P Series RackMount1000-2000-3000VARack-Mount SP P1000 RM SP P2000RM SP P3000RMOUTPUT

Capacity 1000VA / 700W 2000VA / 1400W 3000VA / 2100WVoltage (selectable) single phase 208V, 220V, 230V, 240V +/-2%Frequency (on battery) 50/60Hz+/-0.5%HighEfficiencyMode >95%(ACtoAC)Efficiency 87% 90%UPS Green Mode Energy saving function (No Load Shutdown)HarmonicDistortion <3%ofTHDatlinearloadCrest Factor 3:1Output Socket Option 4 x IEC 60320 C13 4x IEC 60320 C13 1 x IEC 60320 C19

INPUT Voltage Single Phase ALL MODELS

208V/220V/230V/240VVoltage Range

120 ~ 139V140~159V160 ~ 276V

Load Capacity0 ~ 40%0 ~ 70%0 ~ 100%

Frequency 50/60HzAutoSensingInput lnlet IEC 60320

BATTERY Type Sealed, maintenance-free lead acid batteries DC Voltage (V) 36V/12V7.2AHX3 72V/12V7.2AHx6 72V/12V9AHx6Typical Recharge Time 3 hours (to 90%)Battery Protection Cut off without draining any current when battery is lowBack Up Time (Full Load) 6 min. 6 min. 5min.BackUpTime(HalfLoad) 15min. 15min. 14 min.

PROTECTION Surge Protection IEC61000-4-5level3Overload Protection 125%for1minuteand150%for10sec.Short Circuit Protection UPS output cut off / input fuse/circuit breaker protection

COMMUNICATION Audible Alarm Battery Back-Up / UPS fault Display Input / output voltage, input / output frequency, on-line mode, back up

mode, battery capacity, load levelMonitoring RS-232 Serial Port and USB; optionally SNMP Slot

ENVIRONMENT Operating Temperature 0 - 40 deg. C Storage Temperature -20~50deg.CInstallation Altitude upto3500mAudible Noise < 40 dBA (1 metre from surface)RelativeHumidity 0~95%humidity,non-condensing

CONFORMANCE Safety UL 1778, CEEMC (EMS / EMI) IEC61000-4,FCCPart15,CISPR22

SOFTWARE SPower Communication Software ACCESSORIES Battery expansion, connecting cable, USB, SNMP , Relay Card COLOUR Anthracite (RAL 7016) WEIGHT (kg) 17.3 31.6 33DIMENSIONS WxDxH(mm) 428x425x842U 428x610x84 2USP P1000 RM

SP P2000RM and P3000RM

NEMAsocketandlowvoltageversions(100V/110V/115V/120V/127Vopt)areavailabletospecialorder6

The 3000VA rackmount is also available with no batteries and with no batteries + special battery charger. Allowing you to build the system to meet exact application requirements.

Page 7: PSeriesDataBook

P Series RackMount6000VARack-Mount SP P6RMOUTPUT Capacity 6000VA / 4200W

Voltage (selectable) 208V, 220V, 230V, 240V +/-2%Frequency (on battery) 50/60Hz+/-0.5%Overload Recovery Auto transfer to UPSHighEfficiencyMode >95%(ACtoAC)Output Wave Form Sine waveHarmonicDistortion <3%ofTHDatlinearloadCrest Factor 3:1

INPUT VoltageSingle Phase

208V/220V/230V/240V Voltage / Range

120 ~ 139V140~159V180 ~ 276V

Load Capacity0 ~ 40%0 ~ 70%0 ~ 100%

Frequency 50/60HzAutoSensingCONNECTION Hardwire

BATTERY Type Sealed, maintenance-free lead acid batteriesDC Voltage (V) Battery 240V/20x12V7.2AHTypical Recharge Time 4 hours (to 90% full)Management Self-test, adjustable battery transfer points and alarm set-

tingsBattery Protection Cut off without draining any current when battery is lowBack Up Time 7min full load / 20min half load

PROTECTION Surge Protection IEC61000-4-5level3Overload Protection 125%for1min.and150%for10sec.Short Circuit Protection UPS output cut off / input fuse / circuit breaker protection

COMMUNICA-TION

Audible Alarm Battery Back-Up / UPS faultVisual Display Input / output voltage, input / output frequency, on-line mode,

back up mode, battery capacity, load levelMonitoring RS-232 Serial Port and USB; optionally SNMP Slot

ENVIRONMENT Operating Temperature 0 - 40 deg. CStorage Temperature -20~50deg.COperating Altitude upto3500mAudible Noise <55dBA(1metrefromsurface)RelativeHumidity 0~95%humidity,non-condensing

CONFORMANCE Safety UL 1778, CEEMC (EMS / EMI) IEC61000-4,FCCPart15,CISPR22

SOFTWARE SPower Communication Software ACCESSORIES Battery expansion, connecting cable, USB, SNMP ,

Relay CardCOLOUR Anthracite (RAL7016)WEIGHT UPS (kg) 20

Battery Pack (kg) 24DIMENSIONS UPSWxDxH(mm) 428x597x130(3U)

BatteryPackWxDxH(mm) 428x597x130(3U)

7

The P6000RM does not have internal batteries, so at least one battery pack is required - the ideal solution for multi-bay, multi-server and networking equipment power.

The P 6000 RM series is capableofveryflexibleapplication - please call us.

TheP6000RMisfittedwith a manual bypass - the load can be supplied even if the UPS is switched OFF.

Page 8: PSeriesDataBook

The P Series line up

Series P Double Conversion UPS; 700VA -20 kVA TOWERItem Code Product Description Autonomy Net

weight Unit dimensions

Popular listings (also shown in BOLD) notes100% load width depth height

(mins) kg mm mm mm11019 SP P700 online UPS 700 VA 7 13.5 152 420 23711020 SP P1000 online UPS 1000 VA 6 16.2 152 420 23711021 SP P2000 online UPS 2000 VA 6 31.6 225 425 36011022 SP P3000 online UPS 3000 VA 5 32.5 225 425 36011125 SP P3000 online UPS 3000 VA no battery 0 15.7 225 425 36011126 SP P3000 online UPS 3000 VA 5Acharger 0 17 225 425 36011023 SP PBP1 Battery extension for

P 700table 21 152 420 238

11024 SP PBP2 Battery extension for P 1000

table 21 152 420 238

11025 SP PBP3 Battery extension for P 2000/3000

table 42 225 425 360

11026 SP P6 online UPS 6 kVA 6 86 257 590 57011027 SP P10 online UPS 10 kVA 6 112 257 690 71511028 SP P20 online UPS 20 kVA 6 175 342 863 90511029 SP P10-31 online UPS 10 kVA 3 phase i/p 6 80 257 690 71511030 SPP15-31 onlineUPS15kVA 3 phase i/p 6 175 342 863 90511031 SP P20-31 online UPS 20 kVA 3 phase i/p 6 175 342 863 90511032 SP PBP4 Battery extension for

P 5-20 kVA40 x 12V / 7,2 Ah

table 129 257 590 570

11033 SPPBP5 Battery extension for P5-20kVA

40 x 12V / 7,2 Ah with 4A charger

table 131 257 590 570

11034 SP PBP6 Battery extension for P5-20kVA

60 x 12V / 9 Ah

table 129 257 590 570

11035 SP PBP7 Battery extension for P5-20kVA

20 x 12V / 17 Ah

table 158 257 690 715

11036 SP PBP8 Battery extension for P5-20kVA

20 x 12V / 17 Ah with 4A charger

table 160 257 690 715

11037 SP PBP9 Battery extension for P5-20kVA

20 x 12V / 26 Ah with 4A charger

table 255.5 398 649 1010

Series P Double Conversion UPS; 700-6000 VA RACK MOUNT11038 SP P1000 RM online UPS 1000 VA 2U 6 17.1 428 425 8411039 SP P2000 RM online UPS 2000 VA 2U 6 31.6 428 635 8411040 SP P3000 RM online UPS 3000 VA 2U 5 32.5 428 635 8411041 SP PBP2 RM Battery extension for

P 1000 RM2U table 22 428 425 84

11043 SP PBP4 RM Battery extension for P 3000 RM

2U table 43.5 428 635 84

11044 SP P6 RM online UPS 6 kVA 3U 0 20 428 597 13011045 SP PBP5 RM Battery extension for

P 6 RM 3U table 66 428 597 130

8

The SPower P Series is a comprehensive UPS range. Tower and rackmount versions are available, with internal batteries and battery extensions. The popular listings are shown in BOLD-otherproductsintherangeallowaperfectsolutiontobeconfiguredfornonstandardand other demanding applications such as extended autonomies and fast battery charging.

Please contact SPowerUK for all application questions - especially when extended autonomy and fast charging are required - we wish to provide you with the very best solution.

If you need single phase power >3 kVA this can be also supplied from a 3 phase supply by using our 3 phase in / single phase out units.

Page 9: PSeriesDataBook

P Series Autonomy table

SP P700 - SP P1000 - SP P2000 - SP P3000

LoadAutonomy (mins) Autonomy (mins)

P700 P1000W VA Base +1BP +2BP Base +1BP +2BP70 100 90 440 660 140 540 700

140 200 39 190 365 62 240 410 Autonomy (mins)210 300 22 121 235 35 150 260 P2000280 400 14 89 170 23 105 180 Base +1BP +2BP Autonomy (mins)350 500 10 67 135 16.5 77 140 44 180 340 P3000420 600 7.5 52 110 13 60 115 35.5 150 275 Base +1BP +2BP490 700 6 42 91 10.5 48 97 29.5 125 230 38 131 250560 800 8.8 40 82 25 105 197 33 115 210630 900 7.5 35 71 21 90 170 29 100 180

700 1000 6.5 31 62 18.1 78 150 25.5 87 160

770 1100 16 68 133 22.5 75 143840 1200 14 60 119 20 66 128910 1300 12.3 53 108 17.8 59.5 115980 1400 11 48 98 16 54 1051050 1500 10 44 89 14.4 49.5 961120 1600 9 41 81 13 46 881190 1700 8.2 38 75 12 43 801260 1800 7.5 35 69 11 40 741330 1900 7 33 64 10 37.5 691400 2000 6.5 31 60 9.3 35 651470 2100 8.5 32.5 611540 2200 8 30 57.51610 2300 7.5 28 541680 2400 7 26.5 511750 2500 6.5 24.7 481820 2600 6.2 23.5 45.51890 2700 5.95 22 431960 2800 5.7 21 412030 2900 5.4 20 39.52100 3000 5.1 19 38

SP P6 - SP P10 - SP P20Load P6000 P6000 RM P10000

W VA Base +1BP +2 BP +1BP +2BP +3BP Base +1BP +2BP700 1000 90 300 600 90 200 310 120 380 720

1400 2000 37 145 250 35 90 150 47 168 3272100 3000 21 89 155 21 50 90 28 102 199 P200002800 4000 14 60 115 14 35 61 19 70 140 Base +1BP +2BP3500 5000 10 45 90 10 26 45 14 52 109 35 93 1854200 6000 7.5 36 72 7.5 21 35 11 40 86 29 74 1444900 7000 8.7 32.7 68.7 24 61 1145600 8000 7.2 27 57.2 20 50 976300 9000 6 22.5 49 17 43 837000 10000 5.1 19 43 14.5 37 727700 11000 12.5 32.5 62.58400 12000 11 29 569100 13000 10 25.5 509800 14000 9 22.5 4510500 15000 8 20.5 4111200 16000 7.3 18.5 3811900 17000 6.6 17 34.812600 18000 6 15.4 32.513300 19000 5.5 14 30.514000 20000 5 12.8 29

9

To select the UPS for your application based upon Autonomy then look up the load (in watts or VA) in the left hand column and then follow the row across to see the corresponding Autonomy for each applicable UPS model (with or without battery extension unit).

Thiswouldbefor100%load-toseeforexample50%loadAutonomiesthenchoosehalf the watts or VA in the left column.

The Autonomy of a UPS can be greatly extended by the use of battery packs - but remember that the batteries have to be recharged to provide full protection following a power outage - for demanding applications it is often better to use a larger UPS or utilise an SPower system with an additional charger option.

The autonomy of UPS systems can be increased through our various battery pack types - including enhanced recovery through extra chargers.Thefiguresshown here are based on typicalconfigurations.

Page 10: PSeriesDataBook

Battery Extensions

SPower Battery packs are available for both tower and rack-mount units. The DC connector is coded so that connection can be made only to the correct matching unit.

10

Settings LCD display Explanation Selection Factory default RemarksOutput Volt. Setting O/P V Setting Select Nominal

Voltage 208/220/230/240 V 230V Allows optimum voltage setting to provide highest load

equipment life .

Input/Frequency I/P F Setting Select input frequency range when UPS goes into free run mode

±2%±5%±7% ±5% Set UPS output frequency tolerance

Input/Bypass Voltage

I/P Bypass Set Select Input Voltage range when bypass is available

±10%+10/-15%+15/-20%

+10/-15% Set UPS output voltage tolerance to allow bypass transfer

Free Run Mode Free Run Set Select if UPS can run in Free run mode (unsynchronised)

ON/OFF ON Set operation with output in synchronisation with mains supply

Bypass Enable/Disable at Free run mode

Bypass disable If Enable is chosen, the UPS can go to bypass when unsynchronised.

Disable/Enable Disable -

HEmodeSetting HEModeSet Select to run UPS in highefficiencymode

ON/OFF OFF Operate the UPS with bypass as priority - the UPS is then an active standby.

Force Manual Bypass

Manual bypass Permanently force UPS to bypass. For service only.

ON/OFF OFF Allows safe working procedure for battery replacement (hot swappable).

Management of Load groups

Outlet Setting You can put the two load groups on and off form front panel

1 ON & 2 ON - 1 OFF & 2 ON -1 OFF & 2 OFF - 1 ON & 2 OFF

Both load segments ON

Allows loads to be fully protected by UPS during mains failure - or to be shed to increase autonomy for critical areas.

Do Battery Test Battery Test Detect battery is faulty or not.

Make sure that your UPS will provide protection!

Silence Function Silence Set Enable or disable silence function

ON/OFF OFF UPS runs with alarms silenced.

Number of External battery Packs

Bat Cabinet Set This setting is needed for UPS to predict Backup time

0 (only internal batteries) 1(one external pack) 2 (two external pack)

0 Allows the UPS to “know” its full autonomy if battery extensions are used.

Site wiring alarm Site Fault Set You can enable or disable the site wiring

Enable /Disable Disable Enables the detection of voltage between Neutral and Earth

Select Language Language Select load language

English, German, French, Spanish, Italian.

English localisation

Set Generator Mode Generator Set unit in generator mode

ON/OFF OFF optimises UPS input when connected to a generator

Set RS232 communication

RS232 Control Set RS232 communication enable or disable

Enable/Disable Enable -

UPS Settings

Page 11: PSeriesDataBook

Software Accessories

All our UPS Systems can be integrated into networks and alarm systems. We provide the 3 key features either locally at the UPS or remotely:

UPS Monitoring of the mains/UPS actual status• mainsinputvoltage• outputvoltage• i/ofrequency• statusandalarms

In addition, comprehensive historical data logging is also pro-vided for use with various software platforms.

Messaging via e-mail, Pager and SMS is included as part of the standard features of our UPS software (extra equipment required).

Shutdown can be provided for virtually all operating systems and can be managed after a consideration various of events.

Different hardware interfaces including environmental monitor-ing, relay contacts, SNMP and J-Bus meet all possible require-

ments for advanced power protection.

11

SPower control, monitoring and shutdown software is provided with every P Series UPS.

In addition to the Serial ports there is an optional interface slot that allows you to install different communications cards. It can be used in parallel with either the RS232 or USB ports.

Currently there are two cards available for the optional interface slot. An SNMP/WEB card allows management and monitoring over a network or internet, and the AS/400 card provides volt free relay contacts.

Other electrical and mechanical accessories can be provided for your complete project requirements.

SNMP card

Relay card

SPowerUK is here to help you - by supplying quality products backed up by experience, expertise and proven “know-how”. We want you to be able to purchase your UPS knowing exactly what you will be buying and for the UPS to represent a good investment - by protecting your data, your hardware, your up-time, your operational compliance and by minimising many other risks that are attributable and vulnerable to mains supply disturbance.

Please visit our web site and also discuss your applications with us - professional UPS solutions from SPowerUK.www.spoweruk.co.uk [email protected]

The relay card provides status and control communication with non-PC loads - such as PLCs.

The SNMP card provides status and control communication for network and web access.

Page 12: PSeriesDataBook

Telephone +44(0)1942608265Fax +44(0)1942674558Email [email protected] www.spoweruk.co.uk

Ensuring secure power is increasingly a challenge. This challenge occurs more and more often with the extended use of IT, computers, automation and health & safety issues inthehome,offices,industry,telecommunicationsanddatacentres. SPower products meet these challenges.

We provide high quality dependable power both reliably and safely. SPower products cover the range from 300 VA to 3.2 MVA. From securing PC’s and home entertainment systems withinprivatehomesanddataintheofficeuptodemandingduty in industry, hospitals, airports, telecommunications and data processing centres.

Discuss your requirements with SPowerUK and access both experience and world beating technology.

Contact :SPowerUK LtdLowton Business ParkNewton RoadLowton St MarysWarrington WA3 2APUnited Kingdom

Tower 700-3000 VA

Tower5-20kVA

Rack 700-3000 VA

Rack 6000 VA

Pub

licat

ion

SP

UK

P D

ataB

ook

2009

-01

technical details subject to changeE&OE© 2009 SPowerUK Ltd

Other publications in this series: HSeriesUPSDataBook(LineInteractive)M Series UPS DataBook (Three phase modular)please request