+ All Categories
Home > Documents > p_sra4_e_ed3

p_sra4_e_ed3

Date post: 08-Aug-2018
Category:
Upload: iqbal-muhammad
View: 213 times
Download: 0 times
Share this document with a friend

of 74

Transcript
  • 8/23/2019 p_sra4_e_ed3

    1/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 1/74-

    Mod. 151-204/66Ed. 02

    SRA 4

    Line-up and Commissioning Procedure

  • 8/23/2019 p_sra4_e_ed3

    2/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 2/74-

    Mod. 151-204/66Ed. 02

    Index:

    1. SCOPE........................................................................................................................... 42. TEST INSTRUMENTS AND DOCUMENTATION ......................................................... 42.1. TOOLS AND TEST INSTRUMENTS.......................................................................... 42.2. SUPPORT DOCUMENTATION.................................................................................. 53. TESTS BENCH FIGURE ............................................................................................... 64. EQUIPMENT AND LINK LINE UP PHASE ................................................................... 74.1. Control before start .................................................................................................. 74.2. Line up Steps ............................................................................................................ 84.3. Verify the properly installation. ............................................................................... 94.4. Verify the insertion of Memory Key on the IDU and Switch ON. ........................ 104.5. PC Connection. ....................................................................................................... 114.6. System type setting ................................................................................................ 134.7. Set the other Hardware Parameter. ....................................................................... 15

    4.8. Set the cable data value. ........................................................................................ 164.9. Set the ODU configuration data value. ................................................................. 174.9.1. Frequency mode and Tx / Rx frequencies............................................................ 174.9.2. Output power level and ATPC setting................................................................... 194.9.3. Command setting and cable compensation......................................................... 204.10. SVR and SW Version Matching. ............................................................................ 214.11. User and other various configurations. ................................................................ 224.11.1. Configuration of the external interface.............................................................. 224.11.2. Configuration of Protection ................................................................................ 264.11.3. Configuration of Co-Channel operation ............................................................ 274.12. Configuration of the network parameters. ........................................................... 28

    4.12.1. IP Address and Net Mask assigned to Radio Network Element......................304.12.2. Routing table........................................................................................................ 314.12.3. NE Parameter....................................................................................................... 324.13. Alarms Check .......................................................................................................... 334.14. Interferences checkand Prx Value ........................................................................ 344.15. Antenna alignment phase ...................................................................................... 35

    4.15.1. Net Builder Application .......................................................................................................36 4.16. Remote station connection.................................................................................... 374.17. Final Check.............................................................................................................. 375. COMMISSIONING PHASE .......................................................................................... 385.1. Field commissioning tests sheets Module ........................................................... 395.1.1. Field commissioning tests sheets Module Common Data ................................. 39

    5.1.1.1. MW Link Acceptance Report .............................................................................. 395.1.1.2. Test Instrument List ............................................................................................ 405.1.1.3. Support Documentation...................................................................................... 405.1.1.4. Basic Equipment & System Configuration........................................................ 415.1.1.5. Outdoor elements and installation info ............................................................. 435.1.1.6. SW User Inventory............................................................................................... 445.1.1.7. System License Fee ............................................................................................ 445.1.1.8. Network Configuration ........................................................................................ 455.1.2. Field commissioning tests sheets Module Add on for 1+1 system ................... 465.1.2.1. System Inventory Report .................................................................................... 465.1.2.2. Equipment SW Inventory .................................................................................... 48

    5.1.2.3. Equipment SW Management .............................................................................. 485.1.2.4. Unit System status .............................................................................................. 495.1.2.5. RF Frequency Settings........................................................................................ 50

  • 8/23/2019 p_sra4_e_ed3

    3/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 3/74-

    Mod. 151-204/66Ed. 02

    5.1.2.6. RF Power Settings ............................................................................................... 515.1.2.7. Command ODUs Setting ..................................................................................... 525.1.2.8. BB Modem Unit configuration ............................................................................ 52

    5.1.2.9. Synchronization Setting for Co-Channel System.............................................535.1.2.10. Settings for Optical BB Modem Unit............................................................... 535.1.3. Local Check............................................................................................................. 545.1.3.1. Power Supply and Alarm unit replacement....................................................... 545.1.3.2. Local Tributary Loop-back check ...................................................................... 565.1.3.3. Optical power Tx Value ....................................................................................... 585.1.3.4. Rx Power Value.................................................................................................... 595.1.4. Hop Check ............................................................................................................... 605.1.4.1. Protection Test .................................................................................................... 605.1.4.2. Radio Site Loop Back.......................................................................................... 625.1.4.3. ATPC Functional Test ......................................................................................... 635.1.4.4. Background BER Test......................................................................................... 646. ADD ON FOR N+1 SYSTEM ....................................................................................... 707. ANNEXES .................................................................................................................... 727.1. Installation view for typical system type .............................................................. 727.1.1. Wide Band system 6-13 Ghz .................................................................................. 727.1.2. Wide Band system 6-13 Ghz .................................................................................. 727.2. IDU Reference Figures Type .................................................................................. 737.3. ODU and Mounting Reference Figures ................................................................. 74

  • 8/23/2019 p_sra4_e_ed3

    4/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 4/74-

    Mod. 151-204/66Ed. 02

    1. Scope

    This document is intended as a helpful guide to put in service the SRA 4 system in field according to the FIELD

    COMMISSIONING TEST SHEETS.The procedure begins with the local switch on and settings of the radio link, it continues with the line-up and itconcludes with the commissioning of both radio stations.Note that this procedure is full applicable for all system type, but some setting and figure must be different relatedto the SVR and ODU type in filed.In any case refer to the properly UMN and OMN manual of system and follow this procedure only for guide line.

    In case of mismatch between the pictures used in th is document and the equipment in f ield (layout andSW LCT Figures) you have to refer to the corresponding manual with the S.V.R. of your system.

    For a properly application of Line-Up and Commissioning activity is suggested the following minimal Test

    2. Test Instruments and documentation

    2.1. Tools and Test Instruments

    Basic Test Instruments suggested for Line-up and commissioning

    Test Instruments Note

    Personal Computer / Laptop

    CPU Pentium III 400 or higher 256 Mbyte RAM minimum (Suggested 512) 3 Gbyte Hard-disk minimum 1.4 Mbyte 3.5 floppy-disk drive CD-ROM drive (40x) RS-232C serial port Ethernet network card (necessary in case of connection on Ethernetinterface only)

    OS Windows XP Prof. / Windows 2K Prof.

    Engine 5.0 for SVR up to 4.4LCT EngineEngine 6.0 for up to SVR 4.5 or higher

    Plug in software Related to the system SVR

    Multimeters Suggested Analogic and Digital Multimeter

    SDH signal AnalyzerSuggested. for STM 1 signal , model Acterna ANT 5Optical option in case of system with optical BB units

    Optical Power meter (only in case ofoptical BB Modem unit)

    Suggested Acterna (WG) OLP Series(eg. Acterna Optical power meter OLP-5, OLP-6 and OLP-8)

    Dynamometric wrench Suggested tool with Siemens code: 323-500/99

    RS232 not modem PC serial cable Pin to Pin (Sub D9 Male / Sub D9 Female)

    Series of coax adaptor

    Suggested for electrical Interface:BNC (m) / 1.6-5.6 (f)1.0-2.3 (m) / 1.6-5.6 (f)1.6-5.6 male/male,1.6-5.6 female / female

    Suggested for optical Interface:

    Check other adaptor in order of BB Modem unit model, DDF / ODF, Testinstrument modelNote that the optical card use a connector type SC

    Tests Cables

    Depend to the DDF interface type and SDH test instrument Interface

    For system with optical BB units type properly optical pig tail, the outputinterface of BB Modem unit use a connector type SC

    Alignment Cable BNC / Banana (to be build in Field)

    Technical Tools bag

    (*) Select the properly test instrument related to the tributary Interface Type, and DDF Interface

  • 8/23/2019 p_sra4_e_ed3

    5/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 5/74-

    Mod. 151-204/66Ed. 02

    2.2. Support Documentation

    Suggested basic support documentation for Line-up and commissioning activities.

    Standard Documentation Note

    LCT OMN Manual Related to the system SVR

    PLUG IN SW OMN Manual Related to the system SVR

    UMN Manual Related to the system SVR

    Installation Instructions Related to the system SVR

    Field Test sheets Related to the system type

    1 Acronyms and general note

    IDU Indoor UnitODU Outdoor UnitBB Base Band Modem Unit

    Note 1

    On LCT SW windows, the name used to identify IDUs units and ODUs depend to the system type (see annexchapter).

    In case of system up to 1+1, the BB Modem 1 are the unit on the upper position (and related ODU), the BBModem unit 2 are the unit on the lower position (and related ODU)

    For system more than 1+1 (eg 3+1), the reference nomenclatures are:

    ODU 1 / BB Modem 1 => ODU St-by / BB Modem St-by (Sub rack IDU 1 and BB Modem on upper position)

    ODU 2 / BB Modem 2 => ODU 1 / BB Modem 1 (Sub rack IDU 1 and BB Modem on lower position)

    ODU 3 / BB Modem 3 => ODU 2 / BB Modem 2 (Sub rack IDU 2 and BB Modem on upper position)

    ODU 4 / BB Modem 4 => ODU 3 / BB Modem 3 (Sub rack IDU 2 and BB Modem on lower position)

    Note 2

    For system in STI tributary configuration the STM1 connection are only on the BB Modem unit 1For system in DTI tributary configuration the STM1 connections are on the BB Modem unit 1 for WorkerTributaries and on BB Modem 2 for Protection Tributaries

    Note 3

    Note that the commissioning test sheets are divided in different type of documents.

    Common Part, this document is the main document to report all data for system type, inventory etc. Add On Field test for 1+1, this document are the testing report for system with system type up to 1+1

    (1+0, 1+1, 2x1+0) Add On Field test for N+1, this document are the testing report for system with system type up to N+1

    (2+1, 3+1 etc..) Support documentation, document support for Installation Check Lists and Antenna alignment guide line.

    For 2x(1+0) System use the Add On for 1+1 system field commissioning document and consider that system 1 forone direction and system 2 for the secondary direction (in the protection tests mark a N.A. field)

    For 1+0 System use the Add On for 1+1 system field commissioning document and fit only the value refereed onChannel 1 and ODU 1

  • 8/23/2019 p_sra4_e_ed3

    6/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 6/74-

    Mod. 151-204/66Ed. 02

    The test cabling and Series of coax adaptor depend to the DDF type installed in field and to the physical Interfaceof used test Instrument. Remember that the access interfaces for SRA 4 are:

    STM 1 electrical access type 1.0-2.3 (female)

    STM 1 optical access type SC

    Service E1 access type 1.0-2.3 (female)

    Service V11 access type RJ 45 ETH Access Network type RJ45

    AGC Measurement point (on ODU) access type BNC (female)

    3. Tests Bench Figure

    General Layout for Link Test

    The above figure is an example of the general layout of the instruments (BER Test) and portable PC (Local CraftTerminal) in the stations.

    If you need to use an external power supply for the Laptop, it is recommended to connect fi rst the serialcable and then the power supply cable.Doing this the other way round could be dangerous, because the power supply uni t for the laptopnormally contains an autotransformer, and the di fference of ground potential could damage the serial

    port of the PC and (or) the serial interface of the IDU.

  • 8/23/2019 p_sra4_e_ed3

    7/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 7/74-

    Mod. 151-204/66Ed. 02

    4. Equipment and Link Line Up Phase

    4.1. Control before start

    The people responsible for the installation must have the following basic requirements:

    SRA4 radio basic knowledge

    Basic PC knowledge

    Skill to install and use SRA4 software management (LCT and related Plug In SW)

    Mechanical installation knowledge (antenna, kit pole, cabling, etc.)

    Note that if you never saw a SRA4 system before, is recommendable read previously the system manuals.

    Check if:

    The system is properly equipped as per indications in the paragraph "EQUIPMENT COMPOSITION" ofthe UMN manual according to the project specification.

    All the external connections for IDU have been done following the system specifications:

    Primary supply voltage

    IDU-ODU cable

    Tributary cable (STM 1 Signal)

    Alarm cable (if request)

    Networking connection (if request)

    User Channel connection (if request)

    Typical cabling for Co-Channel system (if applicable)

    Typical cabling for N+1 system (if applicable)

    All installation for Outdoor elements has been done following the system specifications:

    IDU-ODU cable

    Mounting Kit (if request)

    Antenna and related polarization

    ODUs and related position on the mounting (for system more than 1+0)

    Grounding connection

    Typical cabling for Co-Channel System (if applicable)

    Al l the uni ts fi tted the equipment are tested and adjusted at the factory in order to optimize thecharacteristics: usually i s not required any check on these units while installed.

  • 8/23/2019 p_sra4_e_ed3

    8/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 8/74-

    Mod. 151-204/66Ed. 02

    4.2. Line up Steps

    In order to operate and configure the SRA4 system is important following the below steps indications.

    Is suggested following this phase order:

    Verify the properly installation (maximum attention to the IDU ODU cable and ODU position on themounting.

    Verify the insertion of Memory Key on the IDU.

    Switch ON IDU PWR

    Switch ON the ODU PWR

    Connect the PC and start the dial up connection and LCT SW (speed at 38400 bps and open theLocalne.map file)

    Set the System Type (1+0,1+1 HS, etc)

    After the system reset, restart the Local connection and LCT SW (open the Localne.map file)

    Set the properly ODU Unit and the other main configuration parameter (modulation, capacity etc...).

    Check if the SVR and SW Version Matching (In case of necessity proceed with the Software Alignment

    Procedure). Verify and set the System Parameter referred to the project specification (System configuration,

    Frequency, Power (ATPC and related value etc.))

    Verify and apply the cable equalization procedure

    After the Frequency setting verify if no interference signal is detected from the ODU (Prx about -99 dBm).

    Check if the RF transmission signal is not squelched (if necessary active the RF transmission signal).

    Set the properly Networking configuration data (refer to the project specification).

    After the system reset, restart the Local connection and LCT SW (open the specified map file with theproperly IP Address).

    Verify that not other alarms are active except the RF Loss (if the remote site is OFF) and the alarmrelated to the no data on tributary interface (Tx and Rx Payload).

    Repeat the entire above step from the opposite station.

    Start with the Alignment phase (for this phase set the ATPC Status Disabled with a maximum power

    selectable and for 1+1 system is suggested precede with alignment on system 1 active on both stations). After the alignment check the Prx Value (from LCT SW) and verify that the value is under the projectspecification.

    Create a new map file (with both extremity IP address), and verify the connection with both NetworkElement (local and remote station).

    Proceed with all Local and Link Line-up test (refer to the field commissioning tests sheets).

    Proceed with all Local and Link Commissioning test (refer to the field commissioning tests sheets).

    For the Help guide line for the above mentioned point refer to the next chapter.

    (Note that the images and related indication are referred to the 3+1 System type and Wideband ODU, forthe properly SW management refers to the OMN manual).

  • 8/23/2019 p_sra4_e_ed3

    9/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 9/74-

    Mod. 151-204/66Ed. 02

    4.3. Verify the properly installation.

    For the properly installation refer to the installation documents and UMN Manual.

    Apply and check the installation with the Check lists document reference

    Note that for 1+1 HS system the properly ODU position referred to the Mounting type (see figure for someexample of 1+1 mounting kit).

    Check the energy breakers and the polarity of the power supply connection (for the polarity of PSUconnector, refer to the UMN manual).

    Note that for the IDU equipped with two BB units is required two separate PSU Inputs.

    Check the electrical continuity for IDU-ODU cable and connectors using a multimeter (verify the properlyPin contact). During the test is suggested move the cable to verify a properly pin connection.

    Check all other installation specification referred to the installation instruction on the UMN Manual.

    Cable to test thecontinuity of IDU-ODU CableCC between groundand central point

  • 8/23/2019 p_sra4_e_ed3

    10/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 10/74-

    Mod. 151-204/66Ed. 02

    Is suggested particularly attention on the connection between ODU and mounting.

    In order to preserver in the time the quality of external O-ring (bigger) is suggested strew a small quantity ofgrease on the O-ring.

    4.4. Verify the insertion of Memory Key on the IDU and Switch ON.

    Check that the Backup Memory Key is properly inserted on the equipment.

    Note that, the HW code of the memory Key, depend to the License fee. Using the UMN Manual to verify that theHW Memory Key is in the properly project specification.

    Switch ON the IDU unit and after the ODUs Units. Wait until controller unit ends the boot phase (about30 / 60 sec.).

    IDU Power ON ODU1 Power ON

    ODU2 Power ON

  • 8/23/2019 p_sra4_e_ed3

    11/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 11/74-

    Mod. 151-204/66Ed. 02

    4.5. PC Connection.

    Switch ON the PC and connect it to the IDU using the serial cable by F interface (RS-232 direct pin to pincable).

    Note for LCT 6.0 or higher:

    On the start up phase of Windows, check if the Services Manager is automatically started

    The starting phase of Services Manager is characterized by a proper window.

    When Services Manager is running, a proper icon is present in the tray area of the desktop.

    Switch ON the PC and connect it to the IDU using the serial cable by F interface (RS-232 direct pin topin cable). Note that the PC connection are available if on the IDU are connected the Memory Key.

    Run the "direct connection" dial up connection and verify that TCP/IP is running before continue (refer tothe OMN manual for setting and configuration of Dial-up connection).(Note that the Dial up connection and modem propriety is at 38400 bps).

    Waiting that the window showing time and speed connection (connection established).

  • 8/23/2019 p_sra4_e_ed3

    12/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 12/74-

    Mod. 151-204/66Ed. 02

    Open the "Radio Management, and run the Local Craft Terminal application (Verify that the properlyPlug-in SW is installed in the PC) and opening the "LocalNe" Map.

    The Security window will appear with a user class and password to be filled out.

    Enter asAdmin Userclass with sysmanagerfor password.

  • 8/23/2019 p_sra4_e_ed3

    13/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 13/74-

    Mod. 151-204/66Ed. 02

    4.6. System type setting

    According to the planning and the equipment, it must be SRA 4 configured with the proper system type

    configuration.From the main operating menu, Status and Config > Equipment > System):

    On the System type field select one of the following parameter.

    (1+0)

    (1+1) Hot Stand-By STI

    (1+1) Frequency Diversity STI

    (1+1) Hot Stand-By DTI

    (1+1) Frequency Diversity DTI

    2x(1+1) Frequency Diversity STI

    2x(1+1) Frequency Diversity DTI

    (2+0)

    (2+1)

    (3+1)

    N.B. After the modification of a system type the IDU disconnects automatically from the PC.Wait until the system reset the configuration, and then restart the connection using the method indicatesin the above paragraph.

    Types of System type field menu depend to the system SVR and Plug In SW used. In any case refer to the

    properly OMN manual and project specification

  • 8/23/2019 p_sra4_e_ed3

    14/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 14/74-

    Mod. 151-204/66Ed. 02

    After this setting, set the properly System Config value.

    On the System Config field select one of the following parameter.

    STM-1 32 Alternate Polarization

    STM-1 32 Co-Channel

    STM-1 128 Alternate Polarization

    STM-1 128 Co-Channel

    2xSTM-1 128 Alternate Polarization

    2xSTM-1 128 Co-Channel

    Note that the System Config type is related to the license constrict.

    Note that for the protection system type STI (single tributary interface) the STM 1 was connected only onthe BB1 modem unit (one STM1 Interface). For protection system type DTI (Double tributary interface) theworker STM 1 was connected on the BB1 modem unit and the protection STM 1 on the BB2 modem unit.

    STM 1 STM 1 Worker STM 1 Protection

    Single Tributary Interface Double Tributary Interface

  • 8/23/2019 p_sra4_e_ed3

    15/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 15/74-

    Mod. 151-204/66Ed. 02

    4.7. Set the other Hardware Parameter.

    Once the proper system type is configured, set and verify all other Hardware configuration elements:

    BB Modem unit type

    Type and composition of Alarm unit, Controller

    Type of ODU Unit

    Note that if the ODU connected to the IDU is not of the type selected via software, the Mismatch wording tappear and the ODU remains Disconnected until the operator does not provide to select the properly type.

    In case of system N+1 the operator must be configure the units present in the IDU #2.

  • 8/23/2019 p_sra4_e_ed3

    16/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 16/74-

    Mod. 151-204/66Ed. 02

    4.8. Set the cable data value.

    Related to the ODU Type and IDU-ODU Cable specification, set the properly BB Modem setting

    Cable Length

    The operator can choose the length of the IF cable between one of the two values: Short and Long.

    The Cable setting is related to the ODU type / Cable type and Cable length.

    For ODU Wideband

    For ODU Narrowband

    For the proper setting of the Cable Length and IF Output Level fields, refer to UMN manual.

    IF Output Level

    In case ofNarrowband ODU, the operator can choose the output level on the IF cable between one of the twovalues: +5dBm and -10dBm (Normally -10 dBm). In case ofWideband ODU, set this value to +5dBm.

  • 8/23/2019 p_sra4_e_ed3

    17/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 17/74-

    Mod. 151-204/66Ed. 02

    Tx Mod Inverted Spectrum (only if BB-Modem is connected to ODU Narrowband)

    This parameter inverts the transmission spectrum of the modem and it must be properly set for the Narrowband

    ODUs, in accordance to what reported in the hardware manual. In case of wrong configuration of the parameter,the traffic is interrupted.The operator can choose one of the two values: Inverted and Not Inverted. (Normally is the Not Invertedselection).

    XPIC Status

    It indicates the status of XPIC canceller: ON or OFF (on in case of Co-channel system)

    XPIC

    This parameter is meaningful only for co-channel systems. It allows cancelling the residual of the orthogonal. Theoperator can choose between one of the two values: ON (canceller running, manual operation) and Forced OFF(canceller disabled).

    Note that the allowing of field for IF power and Tx Spectrum Inversion depend to the system SVR andsystem type.The allowing of Co-Channel is allowing only in case of Co-Channel configuration.

    4.9. Set the ODU configuration data value.

    4.9.1. Frequency mode and Tx / Rx frequencies.

    Once the IF level is adjusted, it is possible to set the Tx / Rx frequency and power settings.

    In order to set the frequency, it is necessary to select in which frequency mode the link will work: Continuous

    mode orFreq Plan mode.

    In the Continuous mode the frequency value are entered directly in KHz.

    In the Freq Plan mode enter the Freq Plan value (Channel ID), preset the values of the first channel IDand last channel ID (see the OMN manual for more info).

    Note that the Frequency Plan modality, allows determining the transmission frequency with the number ID of thechannel.To use this modality, it is necessary to define the frequency plan intended to be used.In particular, it is necessary to specify the identifier (numeric) of the first ID and last ID channel intended to beused, the frequency transmission of the first channel and the spacing among the different channels.

    Note that, for Frequency RF value, set the proper value, in accordance to the RF bandwidth of ODU andsystem Config.

    The RF bandwidth depends to the type of ODU and the Modulation Type (selected from the system config data(32 or 128).For more info see the UMN Manual in the electrical characteristics chapter.

    For the Frequency setting, select from the main Status and configuration menu, the ODU configure field.According with the frequency plan select in which frequency mode will work the link, continuous mode or FreqPlan mode.

  • 8/23/2019 p_sra4_e_ed3

    18/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 18/74-

    Mod. 151-204/66Ed. 02

    On the same menu, select the channel spacing according with the planning. Note that this field applies thespacing filter in the ODU but not all the bandwidth. For a properly values refer to the following reference value(except other condition depending to the frequency planning):

    28000 Khz for system at one STM-1 and 128 TCM modulation value

    55000 Khz for system at one STM-1 and 32 TCM modulation value

    56000 Khz for system at two STM-1 and 128 TCM modulation value.

    All other value depends to the Frequency planning for network.

    In order to execute the properly settings for channel spacing, it is necessary proceed as follows before(in case the frequency mode are in Continuous):

    1. Enable the Freq Plan Activation On;2. Set the parameters of the frequency plan: Freq Ch. #1, First Channel ID and Last Channel ID;3. Disable the Freq Plan Activation Off;

    Note that if any data for Tx Freq. Plan Parameter are set the system dont accept the related data forChannel spacing setting.

    Once described the frequency plan, in order to transmit on a given channel, it is sufficient to write the identifier ofthe chosen channel into the RF Channel ID field.

    Set the Frequency parameter for all ODU

    Note that for Narrowband ODU the frequency setting is not applicable, the ODU is with a fixed frequencyvalue.

  • 8/23/2019 p_sra4_e_ed3

    19/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 19/74-

    Mod. 151-204/66Ed. 02

    4.9.2. Output power level and ATPC setting.

    From the ODU Configure field set all Tx power parameter.

    Setting Parameter and Ptx Setting.

    In the Tx Power setting is present all parameter related the operatives data of Power Tx (ATPC and value of Ptxwith ATPC).

    Referred to the Network RF planning set the properly value.

    Note that for the antennas alignment phase, it must be set the maximum transmission power and disablethe ATPC management.

    For ODU Narrowband the ODU Configuration field are referred to the following figure:

  • 8/23/2019 p_sra4_e_ed3

    20/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 20/74-

    Mod. 151-204/66Ed. 02

    4.9.3. Command setting and cable compensation.

    After the all ODU setting verify that all HW setting are OK and start the cable compensation command.

    From the main ODU Configure field, refer to the command group settings.

    To start the Cable compensation phase (in manual mode) select:

    a. from field Comp IF Cable Mode in manualb. from field Start Comp IF Cable select ONc. Waiting until the end of operationd. Repeat the same step for all ODUse. Return to the Cable Mode in Automatic

    Comp IF Cable Mode

    It allows selecting one of the two possible management strategies: Auto (default) orManual.After an ODU setting or replacement, the procedure for cable compensation must be activated to calculate thecorrect value of the attenuation (default value stored in ODU is 31 dB), depending on the length of IF cable and onthe IF TX power level.In Auto mode, the cable compensation is automatically activated when one of these two conditions occurs:

    ODU is switched on The IF TX power level is changed

    In Manual mode, the cable compensation is activated acting on the related activation command.

    Start Compensation IF Cable

    It allows to manually forcing the procedure for the cable compensation. It is visible and can be activated only bySW.

    During the cable compensation procedure, the red indication Comp Cable Running appears. If the compensationprocedure ends successfully, the red indication End Comp Cable appears for some seconds. If the compensationprocedure ends unsuccessfully, the Cable Comp out of Range indication appears.

    The ODU Status & Configuration window displays also the wording ODU Power-up procedure: Completed (atthe end of the ODU initialisation) orODU Power-up Procedure: Running (during the initialisation of ODU).

  • 8/23/2019 p_sra4_e_ed3

    21/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 21/74-

    Mod. 151-204/66Ed. 02

    Squelch SW Activation

    It allows stopping the transmission of the TX RF signal. Possible values are:

    Off, the system transmits the RF Power(normal operation) On, the transmission is interrupted (squelched).

    4.10. SVR and SW Version Matching.

    From the main menu, Status and Config > Software > Software Bank IDU / ODU:

    Check that the Software Release loaded on both memory bank is with the same SVR reference.Check that the Run Version in Modem Unit is with the same SVR reference.

    Other wise refer to the OMN Manual for a properly for Bank Alignment and SW download procedure.

  • 8/23/2019 p_sra4_e_ed3

    22/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 22/74-

    Mod. 151-204/66Ed. 02

    4.11. User and other various configurations.

    For other setting refer to the project specification and properly system type. For more information refer to the OMN

    and UMN Manual.

    The various setting is started from the main configuration menu on the Ext Interface field, Co-Channel field andProtection field.

    4.11.1. Configuration of the external interface

    Pressing the Ext Interface button in the Equipment Status & Configuration window , the External InterfaceSetting window opens, where the user can configure:

    the operation of the laser (in case of optical BB Modem units)

    the Q interface

    the output commands (if applicable) the input station alarms (if applicable)

    the auxiliary channels (if applicable)

    The window layout and the displayed parameters depend on the System Type configured on theequipment.

  • 8/23/2019 p_sra4_e_ed3

    23/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 23/74-

    Mod. 151-204/66Ed. 02

    a) Laser Management

    Pressing the Laser Management push-button (present only for BB-modem with optical interface) in the External

    Interface Setting window, the BB-Modem Payload window opens, where the operator can configure the laseroperation.

    In case of Optical BB Modem unit, for any reference of Optical propriety, refer to the G.957 S1.1 ITU-T Normative.Only for reference see next table:

    STM-1 according to Recommendations G.707 and G.958

    155 520

    Application code (Table 1) S-1.1

    Operating wavelength range nm 1261a)-1360

    Transmitter at reference point S

    Source type MLM

    Spectral characteristics

    maximum RMS width () nm 7.7

    maximum 20 dB width nm

    minimum side mode suppression ratio dB

    Mean launched power

    maximum dBm 8

    minimum dBm 15

    Minimum extinction ratio dB 8.2

    Optical path between S and R

    Attenuation rangeb) dB 0-12

    Maximum dispersion ps/nm 96

    Minimum optical return loss of cable plant at S, including

    any connectors dB NA

    Maximum discrete reflectance between S and R dB NA

    Receiver at reference point R

    Minimum sensitivityb) dBm 28

    Minimum overload dBm 8

    Maximum optical path penalty dB 1

    Maximum reflectance of

    receiver, measured at R

    dB NA

    a) Some Administrations may require a limit of 1270 nm.

    b) See clause 6.

  • 8/23/2019 p_sra4_e_ed3

    24/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 24/74-

    Mod. 151-204/66Ed. 02

    b) Q Interface

    Pressing the Q Interface button in the External Interface Setting window, the Q Interface Parameters window

    opens, for the configuration of the parameters related to the Q communication interface (10/100BaseT). This isused for the transport of the TMN information of the SRA 4 radio network towards a supervision center.The window opens in read only modality (greyed fields). To modify the values reported in the window, press theModify button: the configuration fields switch to write modality.

    c) Output commands

    Selecting Output Commands in the External Interface Setting window, the Output Commands Settingwindow opens, where the user can configure up to 4 output commands.It is possible to assign a name to each output command, clicking twice on the related description field: the FieldEditing window opens for the insertion of the desired string (max. 16 characters).

    d) Input station alarms

    Pressing the Station Alm button in the Equipment Status&Configuration window, the Input Station Alarms

    window opens.It is possible to assign a name to each station alarm (max. 4), clicking twice on the related field: the Field Editingwindow opens for the insertion of the desired string (max16 characters).For each one of the available station alarms, the user can configure the Polarity parameter, to set the electriclevel corresponding to the alarm logic condition. Clicking twice on this field, the Field Editing window opens forthe selection of the parameter configuration.

    Two alarm logics can be configured: Ground = alarm (Gnd=Alarm) (default condition); Floating = alarm (Floating=Alarm).

  • 8/23/2019 p_sra4_e_ed3

    25/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 25/74-

    Mod. 151-204/66Ed. 02

    e) Auxiliary channels

    For system type (1+0), (1+1), (2+0) and 2x(1+1).

    Pressing the AUX Channel button in the External Interface Setting window, the corresponding AUX ChannelBB-Modem window opens, where the user can enable or disable the operation of the auxiliary channels related tothe selected BB-Modem unit.

    For (N+1) System Types.Pressing the AUX Channel button in the External Interface Setting window, the corresponding AUX ChannelBB-Modem window opens, where the operator can enabled or disable the operation of the auxiliary channelsrelated to the selected BB Modem unit.

  • 8/23/2019 p_sra4_e_ed3

    26/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 26/74-

    Mod. 151-204/66Ed. 02

    4.11.2. Configuration of Protection

    The protection scheme which can be used on the SRA 4 equipment are:

    (1+1) Hot Stand-by, for the protection against hardware failures of the reception and transmission failures (RF andIF sections)(1+1) Frequency Diversity, to add a protection also against the unbalancings in the propagation of the radio signalas fading and multipath interferences (the hitless switching is required in the reception section)2x(1+1) Frequency Diversity, it is a protection scheme identical to (1+1), but with two (1+1) independent systemswithin the same Network Element(2+1) and (3+1) Frequency Diversity, with hitless switching in the reception section(1+1) Double Tributary Interface, for the protection against the failures of the tributary line and the base band unit.

    The type of protection is then different for (1+1) or 2x(1+1) systems (par. 6.7.1.3.1) and (N+1) systems.

    a) Protection in (1+1) and 2x(1+1) System Type

    Pressing the Protection button in the Equipment Status & Configuration window, the Protection windowopens, where the user can configure the protection modality for the equipment.

  • 8/23/2019 p_sra4_e_ed3

    27/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 27/74-

    Mod. 151-204/66Ed. 02

    b) Protection in (N+1) System Type

    Pressing the Protection button in the Equipment Status & Configuration window, in case of (N+1) System

    Type, the following Protection opens, where the user can configure the protection modality for the for the localequipment and display the display the status of the remote radio unit.

    4.11.3. Configuration of Co-Channel operation

    The SRA 4 radio equipment allows setting the co-channel operation for the system, only for System Type (2+0).This functionality is supported only by Co-channel Wideband ODU. It is possible to configure each BB-Modem unitto operate with a given polarization at RF frequency: one of the two ODUs will be configured as master sync(synchronization source), while the other ODU will be configured as slave sync (the synchronization source istaken by the other ODU).

    In case of co-channel configuration, the transmission frequencies of the two ODUs must be the same(F_TX_ODU1=F_TX_ODU2; F_RX_ODU1=F_RX_ODU2).The equipments with (1+1) FD System Type and enabled co-channel functionality do not protect againstthe selective fading.

    The operator must configure one of the two BB-Modem units with a given polarization:the other unit will automatically configured with the orthogonal polarization.A configuration change from alternate polarization to co-channel polarization (in the System Types which supportthis functionality) is refused if:

    at least one of the two ODUs is a Narrowband ODU; at least one of the two ODUs does not support the co-channel operation.

    It is possible to select the IF/RF synchronization between the ODUs among:

    ODU 1 (connected to the upper BB-modem card) master, ODU 2 slave; ODU 2 (connected to the lower BB-modem card) master, ODU 1 slave;

    Pressing the Co-Channel button in the Equipment Status & Configuration window, the following Co-Channelwindow opens, for the configuration of the operating parameters.

  • 8/23/2019 p_sra4_e_ed3

    28/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 28/74-

    Mod. 151-204/66Ed. 02

    Note that in case of Co-Channel system type, is required a properly IDU cabling connection and ODUsinterconnection cable Kit. For more detail refer to UMN Manual.

    4.12. Configuration of the network parameters.

    The new IDU coming from factory doesnt have any project specified IP address. A default address was set fromfactory, this address is 10.10.10.10Independently of the local IP Address of equipment, the local connection using the Localne.map file (using thedial-up modem connection) supply the access in all systems; this access is only a local access.After the activation of system is suitable set a specific IP address, in order to manage the equipment from remotestation (after the alignment).

    In a stand-alone link scenario it is not necessary to define a complete IP planning, but is suitable to set only twovalid IP addresses:

    Use this Net mask on both radios 255.255.255.0 (same value for both stations)

    Use this IP address 150.166.X.Y

    Suggested IP Address for stands alone Link:

    Station A Station B

    IP Address 150.166.16.2 150.166.8.4

    Net Mask 255.255.255.0 255.255.255.0

    The above mentioned rules are only indicative and only for stand alone link, for different rule refer to the IP plan ofproject.In case of stand alone link (without IP network Plan), dont connect any Network cables or other network theequipments (Switch, Hub, Router etc).

    Note that never set these IP addresses:

    0.x.x.x (network address = 0) 127.x.x.x (addresses reserved to loopback) 192.168.255.x (network addresses 192.168.255) Y.x.x.x con 224

  • 8/23/2019 p_sra4_e_ed3

    29/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 29/74-

    Mod. 151-204/66Ed. 02

    After the IP data, is possible check the properly networking connection with the system using a LCT RadioManagement and connect with the equipment trough the Q Lan access (using a cross LAN cable and a properlyIP Address configured on the LAN card in the laptop).

    In this case set the IP Address of laptop with the same area of the equipment IP and use the same address ofequipment for gateway.

    See the following example:

    If the IP address of the equipment are setting with:

    Station A

    IP Address 150.166.16.2

    Net Mask 255.255.255.0

    From the Network proprieties, select the propriety of the LAN card.

    Select the field Internet Protocol (TCP/IP)

    Insert the following data:

    Access from Station A

    IP Address 150.166.16.4

    Subnet Mask 255.255.255.0

    Default gateway 150.166.16.2

  • 8/23/2019 p_sra4_e_ed3

    30/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 30/74-

    Mod. 151-204/66Ed. 02

    Connect the Laptop to the equipment using a ETH Cross Over Cable on the Q-LAN port.Open the LCT Management and the .map file with the NE configured with the properly IP Address.Check the access to the equipment.

    To configure the Networks parameter, from the main menu select Network group.

    4.12.1. IP Address and Net Mask assigned to Radio Network Element

    Open the Status and Config > Network > IP Address window. Click on Modify button to pass to read/writemodality.Set the IP address of the equipment and the related Net-Mask, which must be assigned by the networkadministrator on the basis of the planning of the supervision network (or for stand alone Link). Confirm with OKbutton.

    Be careful in the execution of this operation, because a wrong configuration of the NE parameters canmake the network element unreachable.

    Note: after the insertion of a new IP address the system disconnects automatically from the PC. Wait untilthe system reset the networks configuration data, and then restart the connection using properly addressof NE files (new map file).(To create a new map file see the use of Net Builder SW in the OMN Manual).

  • 8/23/2019 p_sra4_e_ed3

    31/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 31/74-

    Mod. 151-204/66Ed. 02

    4.12.2. Routing table

    Set the routing table according to the Network planning or suggested from the customer. If the Network plan is not

    available dont change the default value configuration.

    Set the entries of the static routing table according to what foreseen by the planning of the supervision network.Confirm with OK. It is possible to set up to 16 entries. For each entry, it is necessary to set the followingparameters:

    Destination AddressIt is the destination IP address of the routing entry, which can be both the IP address of an host and the IPaddress of a different network/subnetwork.

    SubNet-MaskIt is the SubNet-Mask associated to the destination IP address

    Gateway

    It is the IP address of the gateway through which the destination of the routing entry is reached.

    MetricIt is the number of hops which separate the equipment from the destination indicated in the routing entry.

  • 8/23/2019 p_sra4_e_ed3

    32/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 32/74-

    Mod. 151-204/66Ed. 02

    4.12.3. NE Parameter

    This configuration is optional: it is not necessary for the correct operation of the system.

    Open the Status and Config > Network > NE Parameters window.For each network interface present in the system, the operator can enable the following parameters:

    For each Interface entry, it is necessary to set the following parameters:

    RIPv1It allows managing the information for the updating of the routing table.To configure it, double click on the RIPv1 field corresponding to the interested interface: the selection windowopens. Select the wished value and confirm with OK.

    Static Route PropagationIt allows enabling/disabling, clicking on the Enable check-box, the propagation of all the static routing information

    through the interested interface. Select the wished value and press OK.

    Border GatewayIt allows enabling/disabling, clicking on the Enable check-box, the Border Gateway functionality on the interestedfunctionality. Select the wished value and confirm with OK.

    Ingress SummarizationIt allows enabling/disabling, clicking on the Enable check-box, the Ingress Summarization on the interestedinterface. Select the wished value and confirm with OK.

    If the RIPv1 parameter is disabling, the configuration of the Static Route Propagation, Border Gatewayand Ingress Summarization parameters is not meaningful.

    The enabled interfaces are:

    FIt corresponds to the RS-232 serial interface, used for the connection between LCT and equipment

    Q10/100BaseT Ethernet interface, user for the connection between the equipment Controller and the NetViewersupervisory system.

    R1 and R2Channels embedded into the radio frame, reserved for the transmission, via radio, of the supervisory information;for each radio system, it is present a R embedded channel:

    For more information refered the NE Parameter refer to the UMN and OMN Manual.

  • 8/23/2019 p_sra4_e_ed3

    33/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 33/74-

    Mod. 151-204/66Ed. 02

    4.13. Alarms Check

    After all Line-up setting, verify that not other alarms are active except the RF Loss (with related indication) and thealarm related to the tributary interface signal (example LOS).Check that no Physical alarms are active for Faulty of unit or Mismatch configuration. For all alarms indication

    refer to the OMN and UMN manual.

    Selecting the Physical and Functional command in Alarms menu, the Physical and Functional Alarmswindow opens, where the general alarm status on the equipment is displayed.The window is subdivided into three parts: the Functional Alarms section, the Physical Alarms section and theSeverity Alarms section.

  • 8/23/2019 p_sra4_e_ed3

    34/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 34/74-

    Mod. 151-204/66Ed. 02

    4.14. Interferences checkand Prx Value

    After the frequency setting and power setting, before start with the Alignment phase (and with the remote station

    in Power off condition) check if the Prx value dont detect a interference signal from other Links.

    The operator can measure the value of the power received by the ODUs installed in the system by means of thecommands ofMeasurements menu.

    Selecting the View command in the Measurements menu, the Unit Measurements window opens, where themeasures of the transmission and reception power related to the ODU units installed in the system are displayed.

    Check that the Rx power value are minor to 95 dBm.

  • 8/23/2019 p_sra4_e_ed3

    35/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 35/74-

    Mod. 151-204/66Ed. 02

    4.15. Antenna alignment phase

    In order to start the alignment phase, check that the ATPC status is disabled and set the power with the maximum

    output power. The values of the Nominal setting value depend to the ODU type and frequency range. Apply thissetting in both stations.

    Connect the Multimeter on the main ODU (typically the ODU connected to the BB1) to the BNC connector (issuggested an analogic multimeter type ICE).

    Start with the antenna adjustment following the indication reported in to the installation information on the antennasupplier (Andrew, Comelit etc)

    After the alignment verify with the Prx Value check (from LCT SW) and verify that the system is under the projectspecification.

    Remember this consideration:

    a. The VAGC range is between -3.4 V and 1.2 V (typical values) for PRX values between -30 dBm and -75dBm, according to a linear law with rate of about 0.5 V for 10 dB.b. Consider the difference between the nominal value and guaranteed for Transmission Power (See UMN

    Manual).c. The accuracy of Prx value depends to the ODU type, referrer to the UMN Manual for the Prx value

    accuracy.

    Wide Band ODU

    6-13 Ghz AP 6-13 Ghz AP / CC 15-38 Ghz AP 15-38 Ghz AP / CC

    Narrowband ODU

    15-26 Ghz AP

  • 8/23/2019 p_sra4_e_ed3

    36/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 36/74-

    Mod. 151-204/66Ed. 02

    4.15.1. Net Builder Application

    When the link (station A and station B) is properly configured and aligned, in order to verify if from the local station

    are enabled the access to the remote station, is necessary create a new map files.

    To build a new map use the SW Net Builder included in the Radio Management applications.

    Run Net Builderapplication from the Radio Management applications.

    Go to File > New to create a new map and insert the New Net-Element.

    Insert the proper NE Name and (with the Settings field) the related IP addresses (for Station A and Station B with

    max 3 elements), note that for SRA 4 and SRAL XD system check that the Protocol as TNMP EXT value.

    Save the file in map directory.

    Dont overwrite the Localne.map file, but create a new file (example Radio.map)

  • 8/23/2019 p_sra4_e_ed3

    37/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 37/74-

    Mod. 151-204/66Ed. 02

    4.16. Remote station connection

    When the link (station A and station B) is properly configured and aligned verify from the local station the access

    to the remote station.

    Connect the PC with the dial up connection and run the Local Craft Terminal application.Load the new map (example "radio.Map") created with Net builder and check if the remote/local elementconnection is available (the related icon of remote/local station appear colored) or unavailable (the icons appeargrey).

    Station A Station B

    150.166.16.2 150.166.8.4

    4.17. Final Check

    After all setting and configuration system parameters, verify that no abnormal alarm status is present on theequipment except the Tributary alarms (in case no STM 1 channel is connected).

    Note that:

    Dont insert a HW loop on the same tributary in both terminal stations.

    MW Link

  • 8/23/2019 p_sra4_e_ed3

    38/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 38/74-

    Mod. 151-204/66Ed. 02

    5. Commissioning Phase

    The Lineup test is a system control in order to verify if all configuration and functionality of equipment working

    properly. Is important check all suggested test before the commissioning.

    We divide this test in local check and hop check.The local check is fundamentally the control of all setting and local functionality of system (ex. Local Loop). Thehop check is the control of the Link functionality.

    For Line up test use the same testing reported in the Field commissioning Test Sheets.

    This chapter is refers to the properly mode to fill and apply the commissioning report model.

    Note that from the release 5 of the above mentioned document, the documents are divided in 3 parts:

    Common Part; this document report all common specification independently of the system type (System Setup,HW Outdoor inventory, Network Parameter etc).

    Add for system up to 1+1; this document report the configuration data, Local test and hop test for system up to1+1 (1+0, 2x(1+0), 1+1).

    Add for system up to N+1; this document report the configuration data, Local test and hop test for system up toN+1 (2+1, 3+1)

    All documents are in word format with field form to fit them.

    Separate support documents are produced to guide the operator for Lineup and commissioning (installation checklist and Antenna alignment procedure guideline).

  • 8/23/2019 p_sra4_e_ed3

    39/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 39/74-

    Mod. 151-204/66Ed. 02

    5.1. Field commissioning tests sheets Module

    5.1.1. Field commissioning tests sheets Module Common Data

    5.1.1.1. MW Link Acceptance Report

    Customer: Insert the customer nameLink: radio link name or site names (i.e. LondonIpswich)Equipment: unit name, frequency and system type (i.e. SRA 4 15 GHz 1+0)Country: customer countryWork Order: radio linkorder number referenceIdentification Station A / B: Station ID or Name location for station A and B.

  • 8/23/2019 p_sra4_e_ed3

    40/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 40/74-

    Mod. 151-204/66Ed. 02

    5.1.1.2. Test Instrument List

    Refer to this list of suggested test equipment to verify that the Line up and commissioning team is equipped with

    all necessary tools and test instrument for a properly job.Note that is only a suggested list. In any case the applicability of same accessory (cable and adaptors) depends tothe type of access interface connector on the Digital Distribution Frame and the model of Test Instrument used forthe SDH tests.

    5.1.1.3. Support Documentation

    Insert (from the basic form menu) the support and available document used for system setup and relatedconfiguration

    Normally the supporting documentation is:

    Network IP Planning Report Survey Project installation Manual Microwave Link Form MW Link Installation Check List

  • 8/23/2019 p_sra4_e_ed3

    41/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 41/74-

    Mod. 151-204/66Ed. 02

    5.1.1.4. Basic Equipment & System Configuration

    Mark in all field related to the system under test.

    For more specification related to the HW and related specification, refer to the UMN Manual and Annex figuresreported in this document.

    System release:

    To verify the System Version Release refer to chapter SVR and SW Version Matching and note the SVR versionof IDUs.

    Other configuration system data:

    Insert (from the basic form menu) all the basic data related System type configuration.

  • 8/23/2019 p_sra4_e_ed3

    42/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 42/74-

    Mod. 151-204/66Ed. 02

    IDU Type:

    Note the related IDU model, case of the IDU type are not marked select other from the menu and write a new

    data.

    BB Modem unit Type and ODUs Type

    From the System menu, note the related System type and System Configuration configured.

    Radio Channel destination

    In case of 2x(1+0) (or co-channel) system, note if the destination of both direction are the same or not (refer to thesystem configuration data).

  • 8/23/2019 p_sra4_e_ed3

    43/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 43/74-

    Mod. 151-204/66Ed. 02

    Co Channel system

    In the system are in Co Channel, note the HW configuration and related SW indication in the Co Channel setting

    menu.

    For HW Configuration note for each BB Modem Unit the related ODUs and Pair (or coupled) connected with eachcouple of ODUs.

    For the related SW menu, refer to the above chapter Configuration of Co-Channel operation

    5.1.1.5. Outdoor elements and installation info

    For a properly management of Link information, is suitable note the related element for same HW element notacquire from the SW management of system.

    The information is:

    Type of mounting FrameAntenna Protection SystemType of IDU-ODU cableLength of cablesData of Antennas

    Data of Mounting KitData of Flex wave guide Kits.

    Read all the above indicate information from the different Label directly on the different Item.

  • 8/23/2019 p_sra4_e_ed3

    44/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 44/74-

    Mod. 151-204/66Ed. 02

    5.1.1.6. SW User Inventory

    Compile the data related to the type of SW used for manage the equipment under test. From the Inventory > LCT

    (or Net Viewer) field fit the properly data.Note on this field all the related SW information Used for the Lineup and commissioning operations.This info are related to the Engine type used (LCT or Netviewer), P/N and Release of Plug-In SW installed on thePC.

    5.1.1.7. System License Fee

    Report the data reported in the main menu, Status and Config > Equipment > System > License upgrade.Note that this data depend to the type of Memory Key inserted in to the system.

  • 8/23/2019 p_sra4_e_ed3

    45/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 45/74-

    Mod. 151-204/66Ed. 02

    5.1.1.8. Network Configuration

    Note the entire relevant Network configuration Data (IP Address, Routing Table, and NE Parameter).

    For more info refer to the above Chapter Configuration of the network parameter.

    Note that the default data of NE parameter is the data showed in the following figure.

    ETH MTU: 1362RIPv1: EnableStatic Route, Border Gateway and Ingress Summarization Desabled

  • 8/23/2019 p_sra4_e_ed3

    46/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 46/74-

    Mod. 151-204/66Ed. 02

    5.1.2. Field commissioning tests sheets Module Add on for 1+1 system

    This Field test is considering an Add module to the above mentioned module (Common Data).

    This module is the suggested module for all the system types where the in the system type is sufficient only oneIDU (1+0, 1+1, 2x1+0).

    5.1.2.1. System Inventory Report

    For both stations (A and B) insert the reference data from the Inventory menu.Verify if the HW code of the unit is according to the project specification.

    To insert the inventory data on the commissioning document, run, from the NE plug-in, the Inventory Report tool.

    The Inventory Data window is displayed.

    If the file displayed by default into the Inventory file line already exists, the Show push-button results activated.Click on Browse and specify the file name and the relevant path, where the inventory data have to be stored.

  • 8/23/2019 p_sra4_e_ed3

    47/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 47/74-

    Mod. 151-204/66Ed. 02

    Click on Start, if a file with the same name already exists in this folder, the system asks for the confirmation tooverwrite the existing file. The push-button switches from Start to Stop and the storing phase starts with thedisplaying of the relevant messages.

    At the end of the storing phase: the message displaying stops on Finished, the Stop software push-button isdeactivated, the Show push-button is activated, if it was deactivated.Click on Show to display the report on units inventory data with the system base editor (WordPad or Notepad).

    Using the Menu > Edit, Select all data, copy and past them on the Inventory data File Module.

    At the end, Click on Close to close the window Inventory Data and exit.

  • 8/23/2019 p_sra4_e_ed3

    48/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 48/74-

    Mod. 151-204/66Ed. 02

    5.1.2.2. Equipment SW Inventory

    Pressing the Equipment button in the Inventory window, the Equipment Software window opens, where theSoftware Code and the Software Release of the units present in the system are displayed.

    On the same time, check that the Software Release loaded on all ODUs (for system with 2 ODUs) is with thesame SVR reference.

    5.1.2.3. Equipment SW Management

    Selecting Software Bank IDU in the Software menu, the IDU Software Banks (and ODU Software) window

    opens, allowing managing the memory banks of the IDU and ODUs units.Note the embedded software and/or firmware running on the equipment unit.Write on the Field tests sheets the data for both relevant to the memory banks.

  • 8/23/2019 p_sra4_e_ed3

    49/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 49/74-

    Mod. 151-204/66Ed. 02

    5.1.2.4. Unit System status

    On the System Status verify that not abnormal alarm are detect from system. In case same alarms are activeinsert the properly note.

  • 8/23/2019 p_sra4_e_ed3

    50/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 50/74-

    Mod. 151-204/66Ed. 02

    5.1.2.5. RF Frequency Settings

    Compile all data related to specified configuration of Frequency setting.

    Verify that all data inserted are matched with the project specification.

  • 8/23/2019 p_sra4_e_ed3

    51/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 51/74-

    Mod. 151-204/66Ed. 02

    5.1.2.6. RF Power Settings

    Compile all data related to specified configuration of Power setting.

    Verify that all data inserted are matched with the project specification.

    Tx Power Setting with Narrow Band ODUs

  • 8/23/2019 p_sra4_e_ed3

    52/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 52/74-

    Mod. 151-204/66Ed. 02

    5.1.2.7. Command ODUs Setting

    Verify and compile the related data, in according with the project specification.

    Note the status of ODUs parameter at the commissioning time.

    5.1.2.8. BB Modem Unit configuration

    In order to fit the BB Modem Configuration, refer to the referred chapter Set the cable data value.Note all relevant data.In case of Co-Channel system type, mark also the relevant Co-Channel data configuration Parameter, from thesame windows in the above figure.

  • 8/23/2019 p_sra4_e_ed3

    53/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 53/74-

    Mod. 151-204/66Ed. 02

    5.1.2.9. Synchronization Setting for Co-Channel System

    If is applied the Co-Channel system, mark the relevant configuration for the Synchronisation of the ODUs

    Coupled.For more information refer to the UMN and OMN Manual and to the chapter Configuration of Co-Channeloperation.

    Note that for 2x(1+0) Co-Channel system, mark only the available field.

    5.1.2.10. Settings for Optical BB Modem Unit

    In case of Optical BB Modem Unit, note the relevant configuration of the Laser status of them.Refer to the Customer / Project requirement.

  • 8/23/2019 p_sra4_e_ed3

    54/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 54/74-

    Mod. 151-204/66Ed. 02

    5.1.3. Local Check

    5.1.3.1. Power Supply and Alarm unit replacement

    This test is applicable only for system 1+1.Connect the remote HW loop on the STM 1 signal under test (Station B).On station A connect the STM 1 BER test Instrument and check that the STM 1 signal working properly.Switch OFF the related DC power (from PDB) and verify that the system working normally.On the Alarm menu check that the related BB Modem unit are in alarm for PSU problem.Check on the BER Instrument that the STM1 signal working properly.Repeat the test for the other BB Modem Unit.

    Station A MW Link Station B

  • 8/23/2019 p_sra4_e_ed3

    55/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 55/74-

    Mod. 151-204/66Ed. 02

    For the Alarm unit replacement procedure, verify before to start this measure, if the system is in the SVR 4.5 orhigher, if the related Plug In SW are matching with the system SVR and if the Alarm controller unit support this

    feature.

    If the system support this functionality operate with the following procedure:

    Pressing the Maintenance push-button in the Equipment Status & Configuration window, the Maintenancewindow opens, where the operator can execute the procedure for the replacing of the alarm unit without trafficloss.

    In order that this functionality is supported, it is necessary that at least a BB-modem unit is of the HWversion that supports this procedure and that this BB-modem unit is supplied (Vpow connectorconnected to power supply). Other wise, the Start push-button will remain inactive and the extraction ofthe alarm unit will cause the switching off of the whole IDU and of the ODUs.

    Ifthis functionality is supported, push-buttons Key in Plug-in Windows

    Press the Start push-button and verify that Switch Status changes from Open to Closed. Extract the hardware key from the alarm unit Extract the front panel from the unit Re-Insert the alarm unit Install the front panel Insert the hardware key.

    All the steps must be completed within 3 minutes. Otherwise, the IDU unit, after 3 minutes, switches off.

    Check on the BER Instrument that after the simulation of Alarm unit management, the STM1 signal workingproperly.

  • 8/23/2019 p_sra4_e_ed3

    56/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 56/74-

    Mod. 151-204/66Ed. 02

    5.1.3.2. Local Tributary Loop-back check

    Purpose of this test is checking the local Loop back feature of system. Apply the test bend in figure. Connect the

    SDH signal analyzer on the first STM 1 (and after on trib. 2 in case of 2xSTM 1 configuration system). Apply thedifferent loop back feature (by SW) and verify in the STM 1 signal is properly received to the test instruments.

    Apply the Local test in Station A and Station B

    Station A MW Link Station B

  • 8/23/2019 p_sra4_e_ed3

    57/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 57/74-

    Mod. 151-204/66Ed. 02

    With a STM 1 BER Test instrument check the correct insertion of STM 1 signal (from DDF if present) and verifythat no errors occur with the Loop operation.Check in the same time if the related Tx Payload alarm is OFF (Green indication) when the STM 1 signal is

    present and it is ON (Red indication) when the STM 1 signal is disconnected.To see the alarm status select from main menu Alarms > Physical and Functional > Tx payload.

    To perform the test remember that:

    Configuration of Loop-back Trib SideThe tributary local loop-back is executed at the physical input/output interface level. The user can enable ordisable the local loop-back function.

    Configuration of Loop-Back Trib Side INTThe internal tributary loop back is executed at BB unit level (the signal closed in loop before the modem section).

    Configuration of Loop-Back Radio SideThe local loop-back on radio side is executed up to the level of RSOH tributary interface.Remember the in order to check the Radio Side loop back, the loop is in your local station forward remote site.This loop is applied in the Hop test chapter.

  • 8/23/2019 p_sra4_e_ed3

    58/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 58/74-

    Mod. 151-204/66Ed. 02

    5.1.3.3. Optical power Tx Value

    In case of Optical BB Modem Units, is suggested a test to verify the Optical Power.

    Connect the PC to the equipment and on the Laser Management windows set the Laser Restart Field in Manualfor Test Mode.Set the Laser Forcing in OFF status.Connect the test instrument to the Out port of STM 1 signal.Set the Laser Forcing field in ON status and check the Optical power measure.Verify that the value of Optical Laser is under the system specification.After the test, set the Laser Forcing in OFF status.Disconnect the Test Instrument.Set the Laser Restart Field in Auto Mode.Set the Laser Forcing field in ON status.

    Repeat the measure for all available STM1 optical Interfaces.

    Note that the Optical Output interfaces for STM 1 signal are in SC type, related to the type and model of Opticalpower meter use a properly Pig Tail cable or Optical Adaptor.

  • 8/23/2019 p_sra4_e_ed3

    59/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 59/74-

    Mod. 151-204/66Ed. 02

    5.1.3.4. Rx Power Value

    At the end of alignment phase, check the received power level from main menu Measurements > View field.

    Remember that:

    Theoretical Nominal Received Signal: insert the value calculated from the Path calculation (ifavailable).

    Readed Received Power: insert the value showed from the LCT SW.

    The values of Prx are applicable only in case of normal propagation condition, without interference /fading and with the MW link in complete path clearance.

    The value showed on PC has a accuracy at about 3 dB, but is necessary considering same a tolerancefor Ptx Value. Refer to the UMN manual for more indication.

    For system 1+1 FD the Rx value must be the same (within the equipment tolerance, indicate in the fieldtest sheets).

    For system 1+1 HSTBY with unbalanced Mounting Kit the PRx value for ODU 2 (Stand-By Channel)must be 10 12 dB lower than the ODU 1 (Main) (refer to the mounting frame data sheet).

    To optimize the AGC response and detection from the system set a properly value of Channel SpacingData on the ODU configuration.

  • 8/23/2019 p_sra4_e_ed3

    60/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 60/74-

    Mod. 151-204/66Ed. 02

    5.1.4. Hop Check

    5.1.4.1. Protection Test

    Purpose of this test is checking the switching functionality of system.Apply the Local test in Station A and Station B

    Prepare the test bend in figure.

    Station A MW Link Station B

    Note that, for HSBY system and system up to 1+1, you have three basic choices:

    Note thet the protection scheme which can be used on the SRA 4 equipment are:

    (1+1) Hot Stand-by, for the protection against hardware failures of the reception and transmission failures(RF and IF sections)

    (1+1) Frequency Diversity, to add a protection also against the unbalancing in the propagation of theradio signal as fading and multipath interferences (the hitless switching is required in the receptionsection)

    2x(1+1) Frequency Diversity, it is a protection scheme identical to (1+1), but with two (1+1) independentsystems within the same Network Element.

    The window layout and the displayed parameters depend on the System Type configured on theequipment.

    For all system up to 1+1 the basic displayed menu are showed in the following figure:

  • 8/23/2019 p_sra4_e_ed3

    61/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 63/74-

    Mod. 151-204/66Ed. 02

    5.1.4.3. ATPC Functional Test

    Purpose of this test is checking the functionality of ATPC Feature.

    Being a system split, the measure it is feasible with some limitations, it is possible only a functional test.In order to perform a properly ATPC function the link must be installed in laboratory.

    SRA 4 equipment supports the ATPC (Automatic Transmit Power Control) function both in HSBY systems and inFD systems.All the processing is executed by the FPGA present on the BB-Modem. The ATPC information is exchangedbetween the far ends via byte S(2,2).Note that the ATPC function has a different implementation between Narrowband ODU and Wideband ODU.Refer to the UMN and OMN manual for more specification.

    Pmin and ATPC Range values are set in such a way to respect the hardware range of the transmissionpower values for ODU. The control on these values is executed by ODU that refuses the settings if theyare not correct.The limitations that must be respected are:

    Pmin + ATPC_Range less or equal to TX Power max Pmin TX Power min

    In order to verify the ATPC feature set in the Tx Power Setting field the ATPC Management value in Enabledstatus. Verify (with a properly value of ATPC Threshold and P-min Start value) if the value of Prx signal changerelated to the threshold value.Return to the value of P-min Start with the nominal Tx power and set the ATPC Management in Disabled status.Verify that the Prx value return with a nominal value.

    Note that the Prx value is related to Local Station but the Ptx setting must be change in the remotestation. For more information related the ATPC function refer to the UNM and OMN Manual.

    At the end of test set the ATPC status related to the project specification.

  • 8/23/2019 p_sra4_e_ed3

    62/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 64/74-

    Mod. 151-204/66Ed. 02

    5.1.4.4. Background BER Test

    For background BER test is possible a choice with three different options:

    With the test instrument.

    With the LCT SW application.

    With the Netviewer system.

    It suggests you of to use one of the 3 methods only.

    Al l measurements mode must be done in normal propagation condit ions

  • 8/23/2019 p_sra4_e_ed3

    63/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 65/74-

    Mod. 151-204/66Ed. 02

    Test Instrument mode.

    Use the test bench showed in above figure. Set the SDH BER Test instrument with the basic setting parameter for

    a STM 1 frame BER Test.

    Connect a BER meter on the main radio channel under test.

    The test should be done with no errors during a recording time of 2 or 3 hours (suggested short term time forreserve or stand-by channel) and minimal 12 hours (suggested long term time for working or main channel) for thelong term evaluation, the result should be better than 10

    -10.

    LCT or Netviewer mode.

    With the LCT engine 6.0 or Higher (using the properly plug in SW for SRA 4 SVR 4.5 or higher), is possible start ameasure of performance for long period time and showing the related result in a txt format files.

    The Commissioning Report application allows displaying and saving to file the report of the measures of the longperiod performances.The measures of the long period performances are generally enabled and collected for maintenance purposesduring the execution of commissioning tests.The long period performances are made by a set of 192 consecutive quarter intervals of performance monitoring(performance G.821/G.826 like, RSPI, RPS).The measures of the long period performances are stored in the non volatile memory of the Controller of the NE.The measures of the long period performances are collected using a XML file incompressed format, which is transferred via FTP when the request arrives from LCT.

    To start the test following this two step:

    a. Start the Long PM Recording from the specified test menu from the SW applicationb. At the end of the PM Recording apply the Functionality of Commissioning report of system.

    Long PM Recording

    Pressing the Testing push-buttons in the Equipment Status & Configuration window, the Testing windowopens. Pressing the Long PM Recording field.

    On SRA4 there is a command that allows enabling/disabling the recording of the long period performances (bydefault, this recording is disabled).

    To define the time window for the recording, it is necessary to configure: Recording Type,defines the the relevant position of the time window: From Start Time o Continuous Mode:

    Note that the NE Controller resets the content of the long period performance records:

    at start-up;

    after a manual reset command;

    in correspondence ofStart Time (start of the data recording)

    The window displays a counter that shows how many 15 minutes intervals have been already recorded (ExpiredQuarters field).

  • 8/23/2019 p_sra4_e_ed3

    64/74

    Rep. 1740 Data 16/02/04 Ed. 3 Em./Var. 06/2005 Firma Escudero

    Esec. Elifani Contr Escudero

    909-030/12SIEMENS SRA4Line-Up & Commissioning Procedure - 66/74-

    Mod. 151-204/66Ed. 02

    If the Long PM Recording Start setting is From Start Time, the NE writes a file as soon as it ends to record thelast 15 minutes interval.IfLong PM Recording Start is set to Continuous Mode, the file of the recordings is created on-fly when the FTPrequest is made.

    The operator, after the configuration of all the recording parameters, can enable it clicking twice on the LongPeriod PM Recording field: the following Field Editing window opens.

    The Get PM Recorded File push-button opens the PMCommReport window for the recording of the long periodperformance file.

    Commissioning report

    The procedure for the execution of the Commissioning Report is the following one:Run from the plug-in of NE the Commissioning Report tool.

    The PmCommReport window opens.

    Click on Browse and specify the name of the file and the relevant path where save the report.

    Click on Start to transfer via FTP the measures of the long period performances stored into the NE; if a file withthe same name already exists in the folder, a confirmation for overwriting the existing file is required.It is always possible anytime to stop the transfer of the long period performance measures and close the

    Commissioning Report tool clicking on Close.During the transfer, the Start and Show push