+ All Categories
Home > Documents > Pumps Fans Blowers

Pumps Fans Blowers

Date post: 06-Apr-2018
Category:
Upload: anant-joshi
View: 235 times
Download: 2 times
Share this document with a friend
39
 PUMPS BLOWERS FANS Selection & Efficiency Improvement Submitted By: Anant Joshi [2011PME5057] Manoj Singh [2011PME Pankaj Verma [2011PME Umardaraj [2011PMM SUBMITTED TO: DR. JYOTIRMAY MATHUR DEPARTMENT OF MECHANICAL ENGINEERING
Transcript

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 1/39

 

PUMPS BLOWERS FANS

Selection & Efficiency Improvement

Submitted By:

Anant Joshi [2011PME5057]

Manoj Singh [2011PME

Pankaj Verma [2011PME

Umardaraj [2011PMM 

SUBMITTED TO:

DR. JYOTIRMAY MATHUR

DEPARTMENT OF

MECHANICAL ENGINEERING

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 2/39

Page 1.1-1 of 39 

Proper pump for the right process is the cornerstone of the process industry, where selection of a pump for smooth functioning of the machinery is vital.

*R.P. Sharma 

Abstract

The heart of most process industry is the rotating equipment. In almost all the

process industry liquid is to be handled to and fro through various vessels, storage

tanks, heights and lengths during the process of operation.  In fact, most 

manufacturing plants, commercial buildings, and municipalities rely on pumping

systems.

Fans and blowers provide air for ventilation and industrial process requirements.

Fans generate a pressure to move air (or gases) against a resistance caused by

ducts, dampers, or other components in a fan system

Pumps Fans and blowers being rotating equipment plays a very important role in

process industries and no plant can be operated successfully without reliable andlow energy efficient pumping, Fan and blower system. The profit of the plant or

company depends upon more reliable and efficient pumping, Fan and blower

system.

This report is devided into two parts, First part include pumps and second part deal

with Fans and blowers.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 3/39

Table of Contents

1.1 Introduction ....................................................................................................................................... 1.1-3

1.2 CLASIFICATION OF PUMPS ................................................................................................................. 1.2-3

1.2.1 POSITIVE DISPLACEMENT PUMPS ............................................................................................... 1.2-3

1.2.1.1 Reciprocating Pumps .............................................................................................................. 1.2-3

1.2.1.2 Rotary Pumps ......................................................................................................................... 1.2-4

1.2.2 CENTRIFUGAL PUMPS ................................................................................................................ 1.2-4

1.3 Pump Selection Considerations .......................................................................................................... 1.3-4

1.3.1 Understanding Pumping System Requirements .......................................................................... 1.3-4

1.3.2 End Use Requirements—System Flow Rate and Head ................................................................. 1.3-5

1.3.3 Environmental Considerations .................................................................................................... 1.3-5

1.3.4 Methods of Selection ................................................................................................................. 1.3-6

1.3.5 System Characteristics ................................................................................................................ 1.3-71.3.6 Pump Curves .............................................................................................................................. 1.3-8

1.3.7 Pump operating point ...................................................................................................................... 9

1.4 Factors Affecting Pump Performance ....................................................................................................... 9

1.4.1 Matching Pump and System Head-flow Characteristics..................................................................... 9

1.4.2 Effect of over sizing the pump ........................................................................................................ 10

1.4.3 Energy loss in throttling .................................................................................................................. 12

1.4.4 Effect of speed variation ................................................................................................................. 13

1.4.5 Effects of impeller diameter change ............................................................................................... 15

1.4.6 Pump suction performance (NPSH)................................................................................................. 16

1.4.7 Flow Control Strategies .................................................................................................................. 17

1.4.7.1 Pumps in parallel switched to meet demand .............................................................................. 17

1.4.7.2 Stop/start control ....................................................................................................................... 18

1.4.7.3 Flow control valve ...................................................................................................................... 19

1.4.7.4 By-pass control ........................................................................................................................... 19

1.4.7.5 Fixed Flow reduction .................................................................................................................. 20

1.4.7.6 Meeting variable flow reduction ................................................................................................. 21

1.5 Energy Conservation Opportunities in Pumping Systems ........................................................................ 22

1.6 Maintain Pumping Systems Effectively ................................................................................................... 23

1.6.1 Basic Maintenance Checklist........................................................................................................... 24

2.1 INTRODUCTION ..................................................................................................................................... 25

2.2 Types of fans .......................................................................................................................................... 25

2.2.1 Centrifugal fans .............................................................................................................................. 25

2.2.2 Axial fans ........................................................................................................................................ 25

2.3 Important terms and definitions ............................................................................................................ 26

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 4/39

Page 1.1-1 of 39 

2.3.1 System characteristics .................................................................................................................... 26

2.3.2 Fan characteristics .......................................................................................................................... 27

2.3.3 System characteristics and fan curves............................................................................................. 28

2.3.4 Fan laws ......................................................................................................................................... 29

2.4 SELECTING A FAN ................................................................................................................................... 30

2.4.1 BASIC REQUIREMENTS ................................................................................................................... 30

2.4.2 DETERMINING NECESSARY AIRFLOW .............................................................................................. 30

2.4.3 CALCULATING NECESSARY STATIC PRESSURE .................................................................................. 31

2.4.4 CHOOSING THE APPROPRIATE FAN OR BLOWER WITH THE WORKING POINT ................................. 32

2.4.5 OPTIMISING FAN SELECTION .......................................................................................................... 32

2.4.6 SAFETY MARGIN ............................................................................................................................. 33

2.5 Fan and Blower Efficient System Operation ............................................................................................ 33

2.5.1 Installation of Fan ........................................................................................................................... 33

2.5.1.1 Impeller Inlet Seal Clearances ..................................................................................................... 33

2.5.1.2 System Resistance Change .......................................................................................................... 33

2.5.2 Flow Control Strategies .................................................................................................................. 33

2.5.2.1 Pulley Change ............................................................................................................................. 34

2.5.2.2 Damper Controls ........................................................................................................................ 34

2.5.2.3 Inlet Guide Vanes ....................................................................................................................... 34

2.5.2.4 Variable Speed Drives ................................................................................................................. 35

2.5.2.5 Series and Parallel Operation ...................................................................................................... 35

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 5/39

Page 1.1-2 of 39 

TABLE OF FIGURES

FIGURE 1 STATIC HEAD 1.3-7 

FIGURE 2 FRICTION HEAD LOSS VS. FLOW CURVE 1.3-8 

FIGURE 3 HEAD- FLOW CURVE 1.3-8 

FIGURE 4 PUMP OPERATING POINT 9 

FIGURE 5 TYPICAL CENTRIFUGAL PUMP PERFORMANCE CURVE 10 

FIGURE 6 EFFECT ON SYSTEM CURVE WITH THROTTLING 11 FIGURE 7 PUMP CHARACTERISTIC CURVES 12 

FIGURE 8 EXAMPLE OF SPEED VARIATION EFFECTING CENTRIFUGAL PUMP PERFORMANCE 15 

FIGURE 9 EXAMPLE: IMPELLER DIAMETER REDUCTION ON CENTRIFUGAL PUMP PERFORMANCE 16 

FIGURE 10 TYPICAL HEAD-FLOW CURVES FOR PUMPS IN PARALLEL 17 

FIGURE 11 TYPICAL HEAD-FLOW CURVES FOR PUMPS IN PARALLEL, WITH SYSTEM CURVE ILLUSTRATED. 18 

FIGURE 12 CONTROL OF PUMP FLOW BY CHANGING SYSTEM RESISTANCE USING A VALVE. 19 

FIGURE 13 PUMP CURVE BEFORE & AFTER IMPELLER TRIMMING 20 

FIGURE 14 EFFECT OF VFD 21 

FIGURE 15 SYSTEM CURVE OF A FAN AND EFFECT OF SYSTEM RESISTANCE (US DOE, 1989) 27 

FIGURE 16 TYPICAL FAN EFFICIENCY CURVE (BEE INDIA, 2004) 28 

FIGURE 17 FAN PERFORMANCE CURVE 29 

FIGURE 18 SPEED, PRESSURE AND POWER OF FANS 29 

FIGURE 19 DETERMINING NECESSARY AIRFLOW 31 

FIGURE 20 WORKING POINT 32 

FIGURE 21 PULLEY CHANGE 34 

FIGURE 22 SERIES AND PARALLEL OPERATION 35 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 6/39

Page 1.2-3 of 39 

1 PUMPS

1.1  Introduction

Pumps are the fluid moving machineries which increase the mechanical energy of 

the fluids to be displaced. The energy increase may be used to increase the velocity,

the pressure or the elevation of the fluids. A large number of pumps, differing

widely in principle and mechanical construction, have been developed to meet a

wide variety of operating conditions. For selection of pumps for a specific

application requires the knowledge of operating conditions of the system and

applicability of different available pumps.

1.2  CLASIFICATION OF PUMPS

By far the most common method of adding energy is by Positive displacement or

Centrifugal action, which can be supplied by the outside forces. These methods lead

to the two major classes of fluid moving machinery: 1. Positive Displacement Pumps

2. Centrifugal Pumps

1.2.1 POSITIVE DISPLACEMENT PUMPS

Depending upon the way of force generation, these can be classified asReciprocating (force applied to the fluid by a piston acting in a cylinder) and Rotary

(by rotating pressure members) pumps.

1.2.1.1 Reciprocating Pumps

A definite volume of liquid is trapped in a chamber, which is alternately filled from

the inlet and emptied at a higher pressure through the discharge. The chamber is a

stationary cylinder that contains a piston or plunger. According to the required

operating pressure.The maximum discharge pressure for commercial piston pumps is about 50 atm.

For higher pressure services plunger pumps can be utilized, they can discharge

against a pressure of 1500 atm. or more.

Diaphragm pumps can be used to handle toxic or corrosive liquids. They handle

small to moderate amounts of liquid, up to about 100 gal/min, and can develop

pressures in excess of 100 atm.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 7/39

Page 1.3-4 of 39 

1.2.1.2 Rotary Pumps

Rotary pumps best on clean, moderately viscous fluids, such as light lubricating oil.

Discharge pressures upto 200 atm and discharge a steady stream at moderate to

high pressures. They cannot be used with slurries.

Rotary pumps can be classified as Gear pump, Lobe (a broad rounded segmental

division) pump, Screw pump, Cam (eccentric projection on a revolving shaft, shaped

so as to give some desired linear motion) pump, and Vane (blade of a wind mill,propeller, revolving fan) pump.

1.2.2 CENTRIFUGAL PUMPS

The mechanical energy of the liquid is increased by centrifugal action. Centrifugal

pumps are classified as single suction and double suction pumps depending upon

the suction from either one side or from both sides respectively.

. A so-called high-energy centrifugal pump can develop a head of more than 200 m

in a single stage. But generally when a head greater than about 30 m is needed, 2 or

more impellers can be mounted in series on a single shaft and a multi-stage pump is

obtained. The discharge from the second provides suction for the third, and so forth.

The developed heads of all stages add to give a total head several times that of a

single stage.

Because of environmental considerations, leak proof centrifugal pumps are

increasingly used for handling dangerous liquids.

1.3 Pump Selection Considerations 

1.3.1 Understanding Pumping System Requirements

Pumps transfer liquids from one point to another by converting mechanical energy

from a rotating impeller into pressure energy (head). The pressure applied to the

liquid forces the fluid to flow at the required rate and to overcome friction (or head)

losses in piping, valves, fittings, and process equipment. The pumping system

designer must consider fluid properties, determine end use requirements, and

understand environ-mental conditions.

Fluid Properties: The properties of the fluids being pumped can significantlyaffect the choice of pump. Key considerations include:

  Acidity/alkalinity (pH) and chemical composition: Corrosive and acidic fluids

can degrade pumps, and should be considered when selecting pump materials.

Operating temperature: Pump materials and expansion, mechanical seal

components, and packing materials need to be considered with pumped fluids that 

are hotter than 200°F.

Solids concentrations/particle sizes: When pumping abrasive liquids such as

industrial slurries, selecting a pump that will not clog or fail prematurely depends

on particle size, hardness, and the volumetric percentage of solids.Specific gravity: The fluid specific gravity is the ratio of the fluid density to that of 

water under specified conditions. Specific gravity affects the energy required to lift 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 8/39

Page 1.3-5 of 39 

and move the fluid, and must be considered when determining pump power

requirements.

Vapor pressure: A fluid’s vapor pressure is the force per unit area that a fluid

exerts in an effort to change phase from a liquid to a vapor, and depends on the

fluid’s chemical and physical properties. Proper consideration of the fluid’s vapor

pressure will help to minimize the risk of cavitation.

Viscosity: The viscosity of a fluid is a measure of its resistance to motion. Sincekinematic viscosity normally varies directly with temperature, the pumping system

designer must know the viscosity of the fluid at the lowest anticipated pumping

temperature. High viscosity fluids result in reduced centrifugal pump performance

and increased power requirements. It is particularly important to consider pump

suction-side line losses when pumping viscous fluids.

1.3.2 End Use Requirements—System Flow Rate and Head

The design pump capacity, or desired pump discharge in gallons per minute (gpm)

is needed to accurately size the piping system, determine friction head losses,

construct a system curve, and select a pump and drive motor. Process requirements

may be met by providing a constant flow rate (with on/off control and storage used

to satisfy variable flow rate requirements), or by using a throttling valve or variable

speed drive to supply continuously variable flow rates.The total system head has

three components: static head, elevation (potential energy), and velocity (or

dynamic) head. Static head is the pressure of the fluid in the system, and is the

quantity measured by conventional pressure gauges. The height of the fluid level

can have a substantial impact on system head. The dynamic head is the pressure

required by the system to overcome head losses caused by flow rate resistance in

pipes, valves, fittings, and mechanical equipment. Dynamic head losses are

approximately proportional to the square of the fluid flow velocity, or flow rate. If 

the flow rate doubles, dynamic losses increase fourfold.

For many pumping systems, total system head requirements vary. For example, in

wet well or reservoir applications, suction and static lift requirements may vary as

the water surface elevations fluctuate. For return systems such as HVAC circulating

water pumps, the values for the static and elevation heads equal zero. We also need

to be aware of a pump’s net positive suction head requirements. Centrifugal pumps

require a certain amount of fluid pressure at the inlet to avoid cavitation.

 A rule of thumb is to ensure that the suction head available exceeds that required by 

the pump by at least 25% over the range of expected flow rates.

1.3.3 Environmental Considerations

Important environmental considerations include ambient temperature and

humidity, elevation above sea level, and whether the pump is to be installed indoors

or outdoors.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 9/39

Page 1.3-6 of 39 

1.3.4 Methods of Selection

Pumps are usually selected by any of the following three methods:

(1) The prospective purchaser supplies one or more manufacturers with complete

details of the pumping conditions and requests a recommendation and bid on the

units which appear best suited for the conditions.

(2) The purchaser makes a complete calculation of the pumping system and then

chooses a suitable unit from current catalogs and rating charts.(3) A combination of these two methods is used to arrive at the final selection.

The essential data required by any pump manufacturer before a recommendation

and bid can be prepared are:

1. Number of units required

2. Nature of the liquid to be pumped

a. Fresh or salt water, acid or alkali, oil, gasoline, slurry

b. Cold or hot 

c. Its specific gravityd. Viscous or non-viscous

e. Clear and free from suspended foreign matter or dirty and gritty

3. Capacity: the required capacity as well as the minimum and maximum amount of 

Liquid, the pump will ever be called upon to deliver.

4. Suction Conditions

a. A suction lift 

b. A suction head

c. Length and diameter of the suction pipe

5. Discharge conditionsa. Static head: constant or variable

b. Friction head

c. Maximum discharge pressure against which the pump must deliver the

liquid

6. Total Head Variations

7. is the service continuous or intermittent?

8. Is the pump to be installed in a horizontal or vertical position.

9. What type of power is available to drive the pump and what are the

characteristics of this power10. What space, weight, or transportation limitations are involved

11. Location of installation

a. Geographical location

b. Elevation above sea level

c. Indoor or outdoor installation

d. Range of ambient temperatures

12. Are there any special requirements or marked preferences with respect to the

design, construction, or performance of the pump?

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 10/39

Page 1.3-7 of 39 

In quick estimates, for convenience, below written 5 steps are related to size class,

and best buy.

1. Sketching the pump and piping layout 

2. Determining the capacity

3. Finding the total head

4. Studying the liquid conditions

5. Choosing the class and type

1.3.5 System Characteristics

In a pumping system, the objective, in most cases, is either to transfer a liquid from

a source to a required destination, e.g. filling a high level reservoir, or to circulate

liquid around a system, e.g. as a means of heat transfer in heat exchanger.

A pressure is needed to make the liquid flow at the required rate and this must 

overcome head 'losses' in the system. Losses are of two types: static and friction

head.

Static head is simply the difference in height of the supply and destination

reservoirs, as in Figure 1. In this illustration, flow velocity in the pipe is assumed to

be very small. Another example of a system with only static head is pumping into a

pressurised vessel with short pipe runs. Static head is independent of flow and

graphically would be shown as in Figure 1.

Figure 1 Static Head 

Friction head (sometimes called dynamic head loss) is the friction loss, on the liquid

being moved, in pipes, valves and equipment in the system. Friction tables are

universally available for various pipe fittings and valves. These tables show friction

loss per 100 feet (or metres) of a spe- cific pipe size at various flow rates. In case of 

fittings, friction is stated as an equivalent length of pipe of the same size. The

friction losses are proportional to the square of the flow rate. A closed loop

circulating system without a surface open to atmospheric pressure, would exhibit 

only friction losses and would have a system friction head loss vs. flow curve asFigure 2

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 11/39

Page 1.3-8 of 39 

Figure 2 Friction head loss vs. flow curve 

1.3.6 Pump Curves

The performance of a pump can be expressed graphically as head against flow

rate. The cen- trifugal pump has a curve where the head falls gradually withincreasing flow. This is called the pump characteristic curve (Head - Flow curve) -

see Figure 3

Figure 3 Head- Flow Curve 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 12/39

Page 9 of 39 

1.3.7 Pump operating point 

When a pump is installed in a system the effect can be illustrated graphically by

superimposing pump and system curves. The operating point will always be

where the two curves intersect. Figure 4

Figure 4 Pump Operating Point 

1.4  Factors Affecting Pump Performance

1.4.1 Matching Pump and System Head-flow Characteristics

Centrifugal pumps are characterized by the relationship between the flow rate (Q)

they produce and the pressure (H) at which the flow is delivered. Pump efficiency

varies with flow and pres- sure, and it is highest at one particular flow rate. The

Figure 5 below shows a typical vendor-supplied head-flow curve for a centrifugal

pump. Pump head-flow curves are typically given for clear water. The choice of 

pump for a given application depends largely on how the pump head-flow

characteristics match the requirement of the system downstream of the pump.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 13/39

Page 10 of 39 

Figure 5 Typical Centrifugal Pump Performance Curve 

1.4.2 Effect of over sizing the pump

As mentioned earlier, pressure losses to be overcome by the pumps are function of 

flow – the system characteristics – are also quantified in the form of head-flow

curves. The system curve is basically a plot of system resistance i.e. head to be

overcome by the pump versus various flow rates. The system curves change with

the physical configuration of the system; for example, the system curves depends

upon height or elevation, diameter and length of piping, number and type of fittings and pressure drops across various equipment - say a heat exchanger.

A pump is selected based on how well the pump curve and system head-flow

curves match. The pump operating point is identified as the point, where the

system curve crosses the pump curve when they are superimposed on each other.

The Figure shows the effect on system curve with throttling.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 14/39

Page 11 of 39 

Figure 6 Effect on System Curve with Throttling 

In the system under consideration, water has to be first lifted to a height  – this

represents the static head. Then, we make a system curve, considering the frictionand pressure drops in the system- this is shown as the green curve.

Suppose, we have estimated our operating conditions as 500 m3/hr flow and

50 m head, we will chose a pump curve which intersects the system curve (Point 

A) at the pump's best effi- ciency point (BEP).

But, in actual operation, we find that 300 m3/hr is sufficient. The reduction in

flow rate has to be effected by a throttle valve. In other words, we are introducing

an artificial resistance in the system.

Due to this additional resistance, the frictional part of the system curve

increases and thus the new system curve will shift to the left -this is shown as thered curve.

So the pump has to overcome additional pressure in order to deliver the

reduced flow. Now, the new system curve will intersect the pump curve at point B.

The revised parameters are

300 m3/hr at 70 m head. The red double arrow line shows the additional pressure

drop due to throttling. You may note that the best efficiency point has shifted from

82% to 77% efficiency. So what we want is to actually operate at point C which is

300 m3/hr on the original system curve. The head required at this point is only 42

meters.What we now need is a new pump which will operate with its best efficiency

point at C. But there are other simpler options rather than replacing the pump.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 15/39

Page 12 of 39 

The speed of the pump can be reduced or the existing impeller can be trimmed (or

new lower size impeller). The blue pump curve represents either of these options.

1.4.3 Energy loss in throttling

Consider a case (see Figure 7) where we need to pump 68 m3/hr of water at 47 mhead. The pump characteristic curves (A…E) for a range of pumps are given in the

Figure 7.

Figure 7 Pump Characteristic Curves 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 16/39

Page 13 of 39 

1.4.4 Effect of speed variation

As stated above, a centrifugal pump is a dynamic device with the head generated

from a rotat- ing impeller. There is therefore a relationship between impeller

peripheral velocity and gener- ated head. Peripheral velocity is directly related toshaft rotational speed, for a fixed impeller diameter and so varying the rotational

speed has a direct effect on the performance of the pump. All the parameters

shown in fig 6.2 will change if the speed is varied and it is important to have an

appreciation of how these parameters vary in order to safely control a pump at 

different speeds. The equations relating rotodynamic pump performance

parameters of flow, head and power absorbed, to speed are known as the  Affinity 

Laws: 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 17/39

Page 14 of 39 

Where: 

Q = Flow rate 

 H = Head 

P = Power absorbed 

 N = Rotating speed 

Efficiency is essentially independent of speed 

Flow: Flow is proportional to the speed 

Q1 / Q2 = N1 / N2 

Example: 100 / Q2 = 1750/3500 Q2 = 200 m3 /hr 

Head: Head is proportional to the square of speed 

2 2 

H1 /H2 = (N1 ) / (N2 ) Example: 100 /H2 = 17502 / 35002

 

H2 = 400 m 

Power(kW): Power is proportional to the cube of speed 

3 3 

kW1 / kW2 = (N1 ) / (N2 ) Example: 5/kW2 = 17503 / 35003

 

kW2 = 40 

As can be seen from the above laws, doubling the speed of the centrifugal pump will increase

the power consumption by 8 times. Conversely a small reduction in speed will result in drastic

reduction in power consumption. This forms the basis for energy conservation in cen- trifugal

pumps with varying flow requirements. The implication of this can be better understood as

shown in an example of a centrifugal pump in Figure 8 below. 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 18/39

Page 15 of 39 

Figure 8 Example of Speed Variation Effecting Centrifugal Pump Performance 

Points of equal efficiency on the curves for the 3 different speeds are joined to make the iso-

efficiency lines, showing that efficiency remains constant over small changes of speed provid- ing the

pump continues to operate at the same position related to its best efficiency point (BEP). 

The affinity laws give a good approximation of how pump performance curves change with speed

but in order to obtain the actual performance of the pump in a system, the system curve also has to be

taken into account. 

1.4.5 Effects of impeller diameter change

Changing the impeller diameter gives a proportional change in peripheral velocity, so it follows

that there are equations, similar to the affinity laws, for the variation of performance with

impeller diameter D: 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 19/39

Page 16 of 39 

Efficiency varies when the diameter is changed within a particular casing. Note the difference

in iso-efficiency lines in Figure 6.14 compared with Figure 6.13. The relationships shown here

apply to the case for changing only the diameter of an impeller within a fixed casing geometry,

which is a common practice for making small permanent adjustments to the performance of a cen-

trifugal pump. Diameter changes are generally limited to reducing the diameter to about 75% of 

the maximum, i.e. a head reduction to about 50%. Beyond this, efficiency and NPSH are badly

affected. However speed change can be used over a wider range without seriously reducing effi-

ciency. For example reducing the speed by 50% typically results in a reduction of efficiency by 1or 2 percentage points. The reason for the small loss of efficiency with the lower speed is that  

mechanical losses in seals and bearings, which generally represent <5% of total power, are pro-

portional to speed, rather than speed cubed. It should be noted that if the change in diameter is

more than about 5%, the accuracy of the squared and cubic relationships can fall off and for pre-

cise calculations, the pump manufacturer's performance curves should be referred to. 

Figure 9 Example: Impeller Diameter Reduction on Centrifugal Pump Performance 

The illustrated curves are typical of most centrifugal pump types. Certain high flow, low head

pumps have performance curve shapes somewhat different and have a reduced operating region of flows. This requires additional care in matching the pump to the system, when chang- ing speed and

diameter. 

1.4.6 Pump suction performance (NPSH)

Liquid entering the impeller eye turns and is split into separate streams by the leading edges of the

impeller vanes, an action which locally drops the pressure below that in the inlet pipe to the pump. 

If the incoming liquid is at a pressure with insufficient margin above its vapour pressure, then

vapour cavities or bubbles appear along the impeller vanes just behind the inlet edges. Thisphenomenon is known as cavitation and has three undesirable effects: 

1) The collapsing cavitation bubbles can erode the vane surface, especially when pumping

water-based liquids. 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 20/39

Page 17 of 39 

2) Noise and vibration are increased, with possible shortened seal and bearing life. 

3) The cavity areas will initially partially choke the impeller passages and reduce the pump per-

formance. In extreme cases, total loss of pump developed head occurs. 

The value, by which the pressure in the pump suction exceeds the liquid vapour pressure, is expressed as a head

of liquid and referred to as Net Positive Suction Head Available – (NPSHA). This is a charac- teristic of the system

design. The value of NPSH needed at the pump suction to prevent the pump from cavitating is known as NPSH

Required – (NPSHR). This is a characteristic of the pump design. 

The three undesirable effects of cavitation described above begin at different values of NPSHAand generally there will be cavitation erosion before there is a noticeable loss of pump 

head. However for a consistent approach, manufacturers and industry standards, usually define the

onset of cavitation as the value of NPSHR when there is a head drop of 3% compared with the head

with cavitation free performance. At this point cavitation is present and prolonged operation at this

point will usually lead to damage. It is usual therefore to apply a margin bywhich NPSHA should

exceed NPSHR. 

As would be expected, the NPSHR increases as the flow through the pump increases, see fig In addition,

as flow increases in the suction pipework, friction losses also increase, giving a lower NPSHA at the

pump suction, both of which give a greater chance that cavitation will occur. NPSHR also varies

approximately with the square of speed in the same way as pump head and conversion of NPSHR fromone speed to another can be made using the following equations. 

Q ∝ N 

NPSHR ∝ N 2 

It should be noted however that at very low speeds there is a minimum NPSHR plateau, 

NPSHR does not tend to zero at zero speed It is therefore essential to carefully consider NPSH 

in variable speed pumping. 

1.4.7 Flow Control Strategies

1.4.7.1  Pumps in parallel switched to meet demand

Another energy efficient method of flow control, particularly for systems where static head is a high

proportion of the total, is to install two or more pumps to operate in parallel. Variation of flow rate

is achieved by switching on and off additional pumps to meet demand. The combined pump curve is

obtained by adding the flow rates at a specific head. The head/flow rate curves for two and three

pumps are shown in Figure 6.17. 

Figure 10 Typical Head-Flow Curves for Pumps in Parallel  

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 21/39

Page 18 of 39 

The system curve is usually not affected by the number of pumps that are running. For a system

with a combination of static and friction head loss, it can be seen, in Figure 6.18, that 

the operating point of the pumps on their performance curves moves to a higher head and hence lower

flow rate per pump, as more pumps are started. It is also apparent that the flow rate with two pumps

running is not double that of a single pump. If the system head were only static, then flow rate would

be proportional to the number of pumps operating. 

It is possible to run pumps of different sizes in parallel provided their closed valve heads are

similar. By arranging different combinations of pumps running together, a larger number of differentflow rates can be provided into the system. 

Care must be taken when running pumps in parallel to ensure that the operating point of the pump

is controlled within the region deemed as acceptable by the manufacturer. It can be seen in Figure11

that if 1 or 2 pumps were stopped then the remaining pump(s) would operate well out along the curve

where NPSH is higher and vibration level increased, giving an increased risk of operating problems. 

Figure 11 Typical Head-Flow Curves for Pumps in Parallel, With System Curve Illustrated.  

1.4.7.2  Stop/start control

In this control method, the flow is controlled by switching pumps on or off. It is necessary to have a

storage capacity in the system e.g. a wet well, an elevated tank or an accumulator type pressure vessel.

The storage can provide a steady flow to the system with an intermittent oper- ating pump. When the

pump runs, it does so at the chosen (presumably optimum) duty point and when it is off, there is no

energy consumption. If intermittent flow, stop/start operation and the storage facility are acceptable,

this is an effective approach to minimise energy consumption. 

The stop/start operation causes additional loads on the power transmission components andincreased heating in the motor. The frequency of the stop/start cycle should be within the motor design

criteria and checked with the pump manufacturer. 

It may also be used to benefit from "off peak" energy tariffs by arranging the run times dur- ing the

low tariff periods. 

To minimise energy consumption with stop start control it is better to pump at as low flow rate as

the process permits. This minimises friction losses in the pipe and an appropriately small pump can be

installed. For example, pumping at half the flow rate for twice as long can reduce energy consumption

to a quarter. 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 22/39

Page 19 of 39 

1.4.7.3  Flow control valve

With this control method, the pump runs continuously and a valve in the pump discharge line is

opened or closed to adjust the flow to the required value. 

Figure 12 Control of Pump Flow by Changing System Resistance Using a Valve. 

To understand how the flow rate is controlled, see Fig With the valve fully open, the pump

operates at "Flow 1". When the valve is partially closed it introduces an additional friction loss in the

system, which is proportional to flow squared. The new system curve cuts the pump curve at "Flow

2", which is the new operating point. The head difference between the two curves is the pressure

drop across the valve. It is usual practice with valve control to have the valve 10% shut even at maximum flow. Energy is

therefore wasted overcoming the resistance through the valve at all flow conditions. There is some

reduction in pump power absorbed at the lower flow rate (see Figure 6.19), but the flow multiplied

by the head drop across the valve, is wasted energy. It should also be noted that, while the pump will

accommodate changes in its operating point as far as it is able within its performance range, it can

be forced to operate high on the curve, where its efficiency is low, and its reliability is affected. 

Maintenance cost of control valves can be high, particularly on corrosive and solids-con- taining

liquids. Therefore, the lifetime cost could be unnecessarily high. 

1.4.7.4  By-pass control 

With this control approach, the pump runs continuously at the maximum process demand duty, with

a permanent by-pass line attached to the outlet. When a lower flow is required the surplus liquid is

bypassed and returned to the supply source. 

An alternative configuration may have a tank supplying a varying process demand, which is

kept full by a fixed duty pump running at the peak flow rate. Most of the time the tank over- 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 23/39

Page 20 of 39 

flows and recycles back to the pump suction. This is even less energy efficient than a control valve because there

is no reduction in power consumption with reduced process demand.

The small by-pass line sometimes installed to prevent a pump running at zero flow is not a means of flow

control, but required for the safe operation of the pump.

1.4.7.5  Fixed Flow reduction

1.4.7.5.1  Impeller trimming

Impeller trimming refers to the process of machining the diameter of an impeller to reduce the

energy added to the system fluid. 

Impeller trimming offers a useful correction to pumps that, through over- ly conservative design

practices or changes in system loads are oversized for their application. 

Trimming an impeller provides a level of correction below buying a smaller impeller from the

pump manu- facturer. But in many cases, the next smaller size impeller is too small for the pump

load. Also, smaller impellers may not be available for the pump size in question and impeller

trimming is the only practical alternative short of replacing the entire pump/motor assembly.

Figure 13 Pump curve before & after impeller trimming 

Impeller trimming reduces tip speed, which in turn directly lowers the amount of energy

imparted to the sys- tem fluid and lowers both the flow and pressure generated by the pump. 

The Affinity Laws, which describe centrifugal pump performance, provide a theoretical

relationship between impeller sizes and pump output. 

Trimming an impeller changes its operating efficiency, and the non-linearities of the Affinity Laws

with respect to impeller machining complicate the prediction of pump perfor- mance. Consequently,

impeller diameters are rarely reduced below 70 percent of their original size.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 24/39

Page 21 of 39 

1.4.7.6  Meeting variable flow reduction

1.4.7.6.1   Variable Speed Drives (VSDs)

In contrast, pump speed adjustments provide the most efficient means of controlling pump flow. By

reducing pump speed, less energy is imparted to the fluid and less energy needs to be throt- tled or

bypassed. There are two primary methods of reducing pump speed: multiple-speed pump motors and

variable speed drives (VSDs). 

Although both directly control pump output, multiple-speed motors and VSDs serve entirely

separate applications. Multiple-speed motors contain a different set of windings for each motor

speed; consequently, they are more expensive and less efficient than single speed motors. Multiple

speed motors also lack subtle speed changing capabilities within discrete speeds. 

VSDs allow pump speed adjustments over a continuous range, avoiding the need to jump from

speed to speed as with multiple-speed pumps. VSDs control pump speeds using several different

types of mechanical and electrical systems. Mechanical VSDs include hydraulic clutches, fluid

couplings, and adjustable 

belts and pulleys. Electrical VSDs include eddy current clutches, wound- rotor motor controllers, and

variable fre- quency drives (VFDs). VFDs adjust the electrical frequency of the power sup- plied to a

motor to change the motor's rotational speed. VFDs are by far the most popular type of VSD. 

However, pump speed adjustment is not appropriate for all systems. In appli- cations with high

static head, slowing a pump risks inducing vibrations and cre- ating performance problems that are

similar to those found when a pump operates against its shutoff head. For systems in which the

static head repre- sents a large portion of the total head, caution should be used in deciding

whether to use VFDs. Operators should review the performance of VFDs in similar applications and

consult VFD manufacturers to avoid the damage that can result when a pump operates too slowly

against high static head.

Figure 14 Effect of VFD 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 25/39

Page 22 of 39 

For many systems, VFDs offer a means to improve pump operating efficiency despite changes in

operating conditions. The effect of slowing pump speed on pump operation is illus- trated by the

three curves in Fig. When a VFD slows a pump, its head/flow and brake horsepower (BHP) curves

drop down and to the left and its efficiency curve shifts to the left. This efficiency response provides

an essential cost advantage; by keeping the operating effi- ciency as high as possible across

variations in the system's flow demand, the energy and main- tenance costs of the pump can be

significantly reduced. 

VFDs may offer operating cost reductions by allowing higher pump operating efficiency, but theprincipal savings derive from the reduction in frictional or bypass flow losses. Using a system

perspective to identify areas in which fluid energy is dissipated in non-useful work often reveals

opportunities for operating cost reductions. 

For example, in many systems, increasing flow through bypass lines does not noticeably impact

the backpressure on a pump. Consequently, in these applications pump efficiency does not

necessarily decline during periods of low flow demand. By analyzing the entire system, however, the

energy lost in pushing fluid through bypass lines and across throttle valves can be identified. 

Another system benefit of VFDs is a soft start capability. During startup, most motors expe- rience

in-rush currents that are 5 – 6 times higher than normal operating currents. This high cur- rent fades

when the motor spins up to normal speed. VFDs allow the motor to be started with a lower startupcurrent (usually only about 1.5 times the normal operating current). This reduces wear on the motor

and its controller. 

1.5  Energy Conservation Opportunities in Pumping Systems

  Ensure adequate NPSH at site of installation 

  Ensure availability of basic instruments at pumps like pressure gauges, flow meters. 

  Operate pumps near best efficiency point.   Modify pumping system and pumps losses to minimize throttling. 

  Adapt to wide load variation with variable speed drives or sequenced control of multiple

units. 

  Stop running multiple pumps - add an auto-start for an on-line spare or add a booster pump in

the problem area. 

  Use booster pumps for small loads requiring higher pressures. 

  Increase fluid temperature differentials to reduce pumping rates in case of heat

exchangers. 

  Repair seals and packing to minimize water loss by dripping. 

  Balance the system to minimize flows and reduce pump power requirements.   Avoid pumping head with a free-fall return (gravity); Use siphon effect to advantage: 

  Conduct water balance to minimize water consumption 

  Avoid cooling water re-circulation in DG sets, air compressors, refrigeration systems,

cooling towers feed water pumps, condenser pumps and process pumps. 

  In multiple pump operations, carefully combine the operation of pumps to avoid throttling

  Provide booster pump for few areas of higher head

  Replace old pumps by energy efficient pumps

  In the case of over designed pump, provide variable speed drive, or downsize / replace

impeller or replace with correct sized pump for efficient operation.

  Optimise number of stages in multi-stage pump in case of head margins  Reduce system resistance by pressure drop assessment and pipe size optimization

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 26/39

Page 23 of 39 

1.6  Maintain Pumping Systems Effectively

Effective pump maintenance allows industrial plants to keep pumps operating well, to detect

problems in time to schedule repairs, and to avoid early pump failures. Regular maintenance also

reveals deteriorations in efficiency and capacity, which can occur long before a pump fails.

The amount of attention given to maintenance depends on how important a system is to a plant’s

operations. Downtime can be expensive when it affects critical processes. Most maintenance activities

can be classified as either preventive or predictive. Preventive maintenance addresses routine system

needs such as lubrication, periodic adjustments, and removal of contaminants. Predictive maintenance

focuses on tests and inspections that detect deteriorating conditions.

Preventive Actions 

Preventive maintenance activities include coupling alignment, lubrication, and seal maintenance and

replacement. Mechanical seals must be inspected periodically to ensure that either there is no leakage

or that leakage is within specifications. Mechanical seals that leak excessively usually must be

replaced. A certain amount of leakage is required, however, to lubricate and cool the packing seals.

But the packing gland needs to be adjusted if the leakage exceeds the manufacturer’s specifications.

The packing gland must be replaced if it has to be tightened excessively to control leakage. Over

tightening causes unnecessary wear on the shaft or its wear sleeve and increases electric power use.

Routine maintenance of pump motors, such as proper lubrication and cleaning, is also vital.

Predictive Actions 

Predictive maintenance helps minimize unplanned equipment outages. Sometimes called “condition

assessment” or “condition monitoring,” it has become easier with modern testing methods and

equipment. The following methods apply to pumping systems:

Vibration analysis.

Trending vibration amplitude and frequency can detect an impending bearing failure. It can also reveal

voltage and mechanical imbalances that could be caused by impeller erosion or coupling problems.

Changes in vibration over time are more meaningful than a single “snapshot” of the vibration

spectrum. 

Motor current signature analysis.

Sometimes called “dynamic analysis,” this reveals deteriorating insulation, rotor bar damage, electrical

system unbalance, and harmonics. It can also pick up system problems such as malfunctioning controlvalves that cause flow rate disturbances. Tracking the signature over time is more valuable than a

single snapshot.

Lubrication oil analysis.

This applies only to large, oil-lubricated pumps, and is an expensive procedure. Oil analysis can detect

bearing problems caused by metal particles or chemical changes that result from overheating, and seal

problems caused by pumped fluid in the oil. It also provides guidance on proper oil-change intervals. 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 27/39

Page 24 of 39 

Periodic efficiency testing.

Testing the wire-to-water efficiency and keeping records to spot trends is useful. Finally, see the

checklist of maintenance items below, which can be tailored for many kinds of systems, applications,

and facilities.

1.6.1  Basic Maintenance Checklist 

Packing. 

Check for leakage and adjust according to the instructions of the pump and packing manufacturers.

Allowable leakage is usually 2 to 60 drops per minute. Add packing rings or, if necessary, replace all the

packing.

Mechanical Seals. Check for leakage. If leakage exceeds the manufacturer’s specifications, replace

the seal.

Bearings. 

Determine the condition of the bearing by listening for noises that indicate excessive wear, measuring

the bearing’s operating temperature, and using a predictive maintenance technique such as vibration

analysis or oil analysis. Lubricate bearings according to the pump manufacturer’s instructions; replace

them if necessary.

Motor/Pump Alignment.

Determine if motor/pump alignment is within the service limits of the pump.

Motor Condition. 

Check the integrity of motor winding insulation. These tests usually measure insulation resistance at a

certain voltage or the rate at which an applied voltage decays across the insulation. A vibration

analysis can also indicate certain conditions within motor windings and lead to early detection of 

developing problems.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 28/39

Page 25 of 39 

2 FANS AND BLOWERS

2.1  INTRODUCTION

Most manufacturing plants use fans and blowers for ventilation and for industrial processes that need

an air flow. Fan systems are essential to keep manufacturing processes working, and consist of a fan,

an electric motor, a drive system, ducts or piping, flow control devices, and air conditioning equipment

(filters, cooling coils, heat exchangers, etc.). An example system is illustrated in Figure 1. The US

Department of Energy estimates that 15 percent of electricity in the US manufacturing industry is used

by motors. Similarly, in the commercial sector, electricity needed to operate fan motors composes a

large portion of the energy costs for space conditioning (US DOE, 1989). Fans, blowers and

compressors are differentiated by the method used to move the air, and by the system pressure they

must operate against. The American Society of Mechanical Engineers (ASME) uses the specific ratio,

which is the ratio of the discharge pressure over the suction pressure, to define fans, blowers and

compressors (see Table 1)

2.2  Types of fans

There exist two main fan types. Centrifugal fans used a rotating impeller to move the air stream. Axial

fans move the air stream along the axis of the fan.

2.2.1 Centrifugal fans

Centrifugal fans (Figure 6) increase the speed of an air stream with a rotating impeller. The speed

increases as the reaches the ends of the blades and is then converted to pressure. These fans are able

to produce high pressures, which makes them suitable for harsh operating conditions, such as systems

with high temperatures, moist or dirty air streams, and material handling

2.2.2  Axial fans

Axial fans (Figure 10) move an air stream along the axis of the fan. The way these fans work can be

compared to a propeller on an airplane: the fan blades generate an aerodynamic lift that pressurizesthe air. They are popular with industry because they are inexpensive, compact and light.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 29/39

Page 26 of 39 

2.3  Important terms and definitions

2.3.1 System characteristics

The term “system resistance” is used when referring to the static pressure. The system resistance is

the sum of static pressure losses in the system. The system resistance is a function of the configurationof ducts, pickups, elbows and the pressure drops across equipment, for example bag filter or cyclone.

The system resistance varies with the square of the volume of air flowing through the system. For a

given volume of air, the fan in a system with narrow ducts and multiple short radius elbows is going to

have to work harder to overcome a greater system resistance than it would in a system with larger

ducts and a minimum number of long radius turns.

Long narrow ducts with many bends and twists will require more energy to pull the air through them.

Consequently, for a given fan speed, the fan will be able to pull less air through this system than

through a short system with no elbows. Thus, the system resistance increases substantially as the

volume of air flowing through the system increases; square of air flow.

Typically a system resistance curve (Figure 15) is generated with for various flow rates on the x-axisand the associated resistance on the y-axis.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 30/39

Page 27 of 39 

Figure 15 System Curve of a Fan and Effect of System Resistance (US DOE, 1989)  

2.3.2 Fan characteristics

Fan characteristics can be represented in form of fan curve(s). The fan curve is a performance curve

for the particular fan under a specific set of conditions. The fan curve is a graphical representation of a

number of inter-related parameters. Typically a curve will be developed for a given set of conditionsusually including: fan volume, system static pressure, fan speed, and brake horsepower required to

drive the fan under the stated conditions. Some fan curves will also include an efficiency curve so that

a system designer will know where on that curve the fan will be operating under the chosen conditions

(see Figure 16). Of the many curves shown in the figure, the curve static pressure (SP) versus flow is

especially important. The intersection of the system curve and the static pressure curve defines the

operating point. When the system resistance changes, the operating point also changes. Once the

operating point is fixed, the power required can be determined by following a vertical line that passes

through the operating point to an intersection with the power (BHP) curve. A horizontal line drawn

through the intersection with the power curve will lead to the required power on the right vertical

axis. In the depicted curves, the fan efficiency curve is also presented.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 31/39

Page 28 of 39 

Figure 16 Typical Fan Efficiency Curve (BEE India, 2004) 

2.3.3 System characteristics and fan curves

In any fan system, the resistance to air flow (pressure) increases when the flow of air is increased. As

mentioned before, it varies as the square of the flow. The pressure required by a system over a range

of flows can be determined and a "system performance curve" can be developed (shown as SC) (see

Figure 17).

This system curve can then be plotted on the fan curve to show the fan's actual operating point at "A"

where the two curves (N1 and SC1) intersect. This operating point is at air flow Q1 delivered against

pressure P1. A fan operates at a performance given by the manufacturer for a particular fan speed.

(The fan performance chart shows performance curves for a series of fan speeds.) At fan speed N1, the

fan will operate along the N1 performance curve as shown in Figure 17.

The fan's actual operating point on this curve will depend on the system resistance; fan’s operating

point at “A” is flow (Q1) against pressure (P1). 

Two methods can be used to reduce air flow from Q1 to Q2:

  The first method is to restrict the air flow by partially closing a damper in the system. This action

causes a new system performance curve (SC2) where the required pressure is greater for any given

air flow. The fan will now operate at "B" to provide the reduced air flow Q2 against higher pressure

P2.

  The second method to reduce air flow is by reducing the speed from N1 to N2, keeping the damper

fully open. The fan would operate at "C" to provide the same Q2 air flow, but at a lower pressure

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 32/39

Page 29 of 39 

P3. Thus, reducing the fan speed is a much more efficient method to decrease airflow since less

power is required and less energy is consumed.

Figure 17 Fan performance curve

2.3.4 Fan lawsThe fans operate under a predictable set of laws concerning speed, power and pressure. A change in

speed (revolutions per minute or RPM) of any fan will predictably change the pressure rise and power

necessary to operate it at the new RPM. This is shown in Figure 18.

Figure 18 Speed, pressure and power of fans 

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 33/39

Page 30 of 39 

2.4  SELECTING A FAN

2.4.1 BASIC REQUIREMENTS

VOLTAGE: The first step is to determine the nominal voltage; this can be AC or DC.

DIMENSIONS: Optimizing performance within the available space envelope is the most important

criteria

2.4.2 DETERMINING NECESSARY AIRFLOW

Dissipated power has to be determined first. If this value is unknown, the estimation can be done by

taking the power consumed by the equipment and the efficiency (which is approximately 75 % for

electronics equipment).

The graph below (fig19) shows how to calculate the airflow according to the dissipated power, using

the formula:

This calculation does not take into consideration pressure drop, which has a direct impact on the

airflow.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 34/39

Page 31 of 39 

Figure 19 Determining necessary airflow

2.4.3 CALCULATING NECESSARY STATIC PRESSURE

Each component mounted in the equipment opposes a resistance to air circulation. These

accumulated resistances are called “pressure drop”. The pressure drop is balanced by the fan static

pressure which is expressed in mmH2O or in Pa. The necessary airflow of the fan must be specified at

a certain static pressure. Pressure drop is not easily calculable, especially in complex equipment. In

cooling applications, pressure drop can be calculated according to duct diameter, length, bends or

other deviations.

Here is one basic principle to calculate pressure drop: A specified fan, which air performance is known,

is mounted on the equipment. The air speed can be measured at the outlet of the equipment with an

anemometer. The airflow is calculated as follows:

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 35/39

Page 32 of 39 

The static pressure, corresponding to the measured airflow, can therefore be read on the fan

performance curve. The value of this static pressure is the second parameter to consider when

selecting a fan.

2.4.4  CHOOSING THE APPROPRIATE FAN OR BLOWER WITH THE WORKING POINT

The combination of necessary airflow and static pressure gives a value which is called working point. It

is now very easy to choose the appropriate fan or blower, by selecting a model in the catalogue, which

curve meets the working point (see fig 20).

Figure 20 Working point

2.4.5 OPTIMISING FAN SELECTION

If the air requirement is high, and available space limited, it is possible to double the airflow at free

delivery by putting two fans in parallel or to increase the pressure by putting two fans in series. The

noise level will then increase by approximately 3dBA depending on the fan model. The next chapter

shows the benefits of the different fan designs.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 36/39

Page 33 of 39 

2.4.6 SAFETY MARGIN

The choice of safety margin affects the efficient operation of the fan. In all cases where the fan

requirement is linked to the process/other equipment, the safety margin is to be decided.

Based on the discussions with the process equipment supplier, In general, the safety margin can be 5

% over the maximum requirement on flow rate

2.5  Fan and Blower Efficient System Operation

2.5.1 Installation of FanThe installation of fan and mechanical maintenance of the fan also plays a critical role in the efficiency of the

fan. The following clearances (typical values) should be maintained for the efficient operation of the impeller 

2.5.1.1  Impeller Inlet Seal Clearances

• Axial overlap – 5 to 10 mm for 1 metre plus dia impeller

• Radial clearance – 1 to 2 mm for 1 metre plus dia impeller

• Back plate clearance – 20 to 30 mm for 1 metre plus dia impeller

• Labyrinth seal clearance – 0.5 to 1.5 mm

The inlet damper positioning is also to be checked regularly so that the "full open" and "full close"

conditions are satisfied. The fan user should get all the details of the mechanical clearances from the

supplier at the time of installation. As these should be strictly adhered to, for efficient operation of thefan, and a checklist should be prepared on these clearances. A check on these clearances should be

done after every maintenance, so that efficient operation of the fan is ensured on a continuous basis.

2.5.1.2  System Resistance Change

The system resistance has a major role in determining the performance and efficiency of a fan. The

system resistance also changes depending on the process. For example, the formation of the coatings

/ erosion of the lining in the ducts, changes the system resistance marginally. In some cases, the

change of equipment (e.g. Replacement of Multi-cyclones with ESP / Installation of low pressure drop

cyclones in cement industry) duct modifications, drastically shift the operating point, resulting in lower

efficiency. In such cases, to maintain the efficiency as before, the fan has to be changed.

Hence, the system resistance has to be periodically checked, more so when modifications are

introduced and action taken accordingly, for efficient operation of the fan.

2.5.2 Flow Control Strategies

Typically, once a fan system is designed and installed, the fan operates at a constant speed. There may

be occasions when a speed change is desirable, i.e., when adding a new run of duct that requires an

increase in air flow (volume) through the fan. There are also instances when the fan is oversized and

flow reductions are required.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 37/39

Page 34 of 39 

Various ways to achieve change in flow are: pulley change, damper control, inlet guide vane control,

variable speed drive and series and parallel operation of fans. 

2.5.2.1  Pulley Change

When a fan volume change is required on a permanent basis, and the existing fan can handle the

change in capacity, the volume change can be achieved with a speed change. The simplest way to

change the speed is with a pulley change. For this, the fan must be driven by a motor through a v-belt

system. The fan speed can be increased or decreased with a change in the drive pulley or the driven

pulley or in some cases, both pulleys. As shown in the Figure 21

Figure 21 pulley change 

2.5.2.2  Damper Controls

Dampers can be located at inlet or outlet. Dampers provide a means of changing air volume by adding

or removing system resistance. This resistance forces the fan to move up or down along its

characteristic curve, generating more or less air without changing fan speed. However, dampers provide

a limited amount of adjustment, and they are not particularly energy efficient.

2.5.2.3  Inlet Guide Vanes

Inlet guide vanes are another mechanism that can be used to meet variable air demand Guide vanes are

curved sections that lay against the inlet of the fan when they are open. When they are closed, theyextend out into the air stream. As they are closed, guide vanes pre-swirl the air entering the fan housing.

This changes the angle at which the air is presented to the fan blades, which, in turn, changes thecharacteristics of the fan curve. Guide vanes are energy efficient for modest flow reductions  – from 100

percent flow to about 80 percent. Below 80 percent flow, energy efficiency drops sharply.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 38/39

Page 35 of 39 

2.5.2.4  Variable Speed Drives

Variable speed drives provide almost infinite variability in speed control. Variable speed operation

involves reducing the speed of the fan to meet reduced flow requirements. Fan performance can bepredicted at different speeds using the fan laws. Since power input to the fan changes as the cube of the

flow, this will usually be the most efficient form of capacity control. However, variable speed controlmay not be economical for systems, which have infrequent flow variations. When considering variable

speed drive, the efficiency of the control system (fluid coupling, eddy-current, VFD, etc.) should be

accounted for, in the analysis of power consumption.

2.5.2.5  Series and Parallel Operation

Parallel operation of fans is another useful form of capacity control. Fans in parallel can be additionally

equipped with dampers, variable inlet vanes, variable-pitch blades, or speed controls to provide a highdegree of flexibility and reliability.

Combining fans in series or parallel can achieve the desired airflow without greatly increasing thesystem package size or fan diameter. Parallel operation is defined as having two or more fans blowing

together side by side.The performance of two fans in parallel will result in doubling the volume flow, but only at free

delivery.  Series operation can be defined as using multiple fans in a push-pull arrangement. By stagingtwo fans in series, the static pressure capability at a given airflow can be increased.

Figure 22 Series and Parallel Operation 

Both series and parallel operation, particularly with multiple fans certain areas of the combined

performance curve will be unstable and should be avoided. This instability is unpredictable and is a

function of the fan and motor construction and the operating point.

8/3/2019 Pumps Fans Blowers

http://slidepdf.com/reader/full/pumps-fans-blowers 39/39

3 REFRENCES

PUMPS AND PUMPING SYSTEM: Bureau of Energy Efficiency 

PUMPS: SELECTION & TROUBLE SHOOTING Prof B V Babu Assistant Dean – ESD & GroupLeader (Head) - Chemical Engineering Birla Institute of Technology and Science

  Improving Pumping System Performance: A Sourcebook for Industry: U.S. Department of Energy’s

Industrial Technologies Program (ITP) and the Hydraulic Institute (HI)

Application guide - Using variable speed drives (VSDs) in pump applications: ABB Drives 

PUMP SELECTION CRITERIA : Armstrong Pumps Limited

PUMPS AND PUMPING SYSTEM: ENERGY CONSERVATION OPPORTUNITIES:

SHITANSHU PANDEY, MUSANGO LUNGU [ DEPARTMENT OF MECHANICAL ENGINEERING

 MNIT, Jaipur]

FANS AND BLOWERS: Bureau of Energy Efficiency

Technical guide- SELECTING A FAN : ETRI Fans www.etrinet.com 

Electrical Energy Equipment: Fans and Blowers- Energy Efficiency Guide for Industry in Aisa – 

 www.energyefficiencyasia.org 

Fluidic and Microfluidic Pumps, Micropumps, Compressors, Fans and Blowers an Overview:

Craig E. Nelson - Consultant Engineer


Recommended