Quick Start Guide Warning Device LAL-SRW ENG Document No.: 45-3207 Edition: 05/2011 Copyright Pepperl+Fuchs www.pepperl-fuchs.com Pepperl+Fuchs GmbH Lilienthalstrasse 200 68307 Mannheim, Germany Tel. +49 621 776-0 Fax. +49 621 776-1000 Important The manual always takes priority over this quick start guide, which is only intended to provide a brief overview of the warning device functions. Refer to the manual for more detailed information about the warning device. The corresponding safety chapter in this manual is an integral component of this document. Make sure the information in the safety chapter is read and understood. Scope of delivery LAL-SRW SUPPLY ALARM RESET HIGH OIL LEVEL OVERFLOW ALARM SYSTEM OK 68301 Mannheim Germany www.pepperl-fuchs.com OIL SEPARATOR ALARM 1 2 4 3 5 8 6 7 1 Warning device LAL-SRW 2 Overflow sensor NVF-104/34-PF 3 Oil level sensor KVF-104-PF 4 Sludge level sensor SLU-104-PF 5 Cable connector IP68 for one sensor cable LAL-SK2 6 Connection box IP67 NVO5-VD 7 Housing with DIN mounting rail NVO5-KV 8 Mounting set for one sensor NVO5-B Installation and Connection Preparation for Installation Cable Length Number of Cables max. 250 m Connecting 1 sensor 1 x (2 x 1) mm 2 Connecting 2 sensors 2 x (2 x 1) mm 2 or 1 x (4 x 1) mm 2 Mounting Steel Bracket Using Cable Connector Using Connection Box Mounting Oil Level Sensor Mounting Overflow Sensor Mounting Sludge Level Sensor L S X Water Air Oil L S X Water Air Oil L S X Sludge Water Air Oil L Water zero line S Sensor switching point X Alarm limit Always follow operating instructions of the oil/petrol separator manufacturer. Mounting Warning Device Configuring Warning Device Additional Settings LAL-SRW SUPPLY ALARM RESET HIGH OIL LEVEL OVERFLOW ALARM SYSTEM OK 68301 Mannheim Germany www.pepperl-fuchs.com OIL SEPARATOR ALARM LAL-SRW OIL SEPARATOR ALARM Enclosure Electric switchboard 1 0 1 0 13 15 22 23 24 bu bn bu bn OFF ON or or OFF ON 1 2 3 4 5 6 7 8 OFF ON 1 2 3 4 5 6 7 8 / OFF ON 1 2 3 4 5 6 7 8 + YES For connection to external potential free contacts and further adjustments please turn over. Warning Device LAL-SRW / NO Only acoustic and visual alarm, and no external connection 567 230 V AC Warning device is active. Switch on the warning device.
Transcript

Quick Start Guide

Warning DeviceLAL-SRW

ENG

Document No.: 45-3207 Edition: 05/2011

Copyright Pepperl+Fuchswww.pepperl-fuchs.com

Pepperl+Fuchs GmbHLilienthalstrasse 20068307 Mannheim, GermanyTel. +49 621 776-0Fax. +49 621 776-1000

ImportantThe manual always takes priority over this quick start guide, which is only intended to provide a brief overview of the warning device functions. Refer to the manual for more detailed information about the warning device.

The corresponding safety chapter in this manual is an integral component of this document. Make sure the information in the safety chapter is read and understood.

Scope of delivery

LAL-SRW

SUPPLYALARMRESET

HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

1 2 43

5

8

6 7

1 Warning device LAL-SRW 2 OverflowsensorNVF-104/34-PF 3 OillevelsensorKVF-104-PF 4 Sludge level sensor SLU-104-PF 5 Cable connector IP68 for one sensor cable LAL-SK2 6 ConnectionboxIP67NVO5-VD 7 HousingwithDINmountingrailNVO5-KV 8 MountingsetforonesensorNVO5-B

Installation and ConnectionPreparation for Installation Cable Length Number of Cables

max. 250 m

Connecting 1 sensor

1 x (2 x 1) mm2

Connecting 2 sensors

2 x (2 x 1) mm2 or

1 x (4 x 1) mm2

Mounting Steel Bracket Using Cable Connector Using Connection Box Mounting Oil Level Sensor Mounting Overflow Sensor Mounting Sludge Level Sensor

L

SX

Water

Air

Oil L

SX

Water

Air

OilL

S

XSludge

Water

Air

Oil

L Water zero line S Sensor switching point X Alarm limit

Always follow operating instructions of the oil/petrol separator manufacturer.

Mounting Warning Device Configuring Warning Device Additional Settings

LAL-SRW

SUPPLYALARMRESET

HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

LAL-SRW

SUPPLYALARMRESET

HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

Enclosure Electric switchboard

AlarmReset

Netz SystemOK

SchichtdickeAlarm

D-68307 Mannheim(0621) 776-0

1

0

1

0

13 15 22 23 24

bubnbubn

OFF

ON

or

or

OFFON

1 2 3 4 5 6 7 8

OFFON

1 2 3 4 5 6 7 8

/

OFFON

1 2 3 4 5 6 7 8

+

YES For connection to external potential free contacts and further adjustments please turn over.

Quick Start Guide

Warning DeviceLAL-SRW

ENG

Document No.: 45-3207 Edition: 05/2011

Copyright Pepperl+Fuchswww.pepperl-fuchs.com

Pepperl+Fuchs GmbHLilienthalstrasse 20068307 Mannheim, GermanyTel. +49 621 776-0Fax. +49 621 776-1000

ImportantThe manual always takes priority over this quick start guide, which is only intended to provide a brief overview of the warning device functions. Refer to the manual for more detailed information about the warning device.

The corresponding safety chapter in this manual is an integral component of this document. Make sure the information in the safety chapter is read and understood.

Scope of delivery

LAL-SRW

SUPPLYALARMRESET

HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

1 2 43

5

8

6 7

1 Warning device LAL-SRW 2 3 4 Sludge level sensor SLU-104-PF 5 Cable connector IP68 for one sensor cable LAL-SK2 6 7 8

Installation and ConnectionPreparation for Installation Cable Length Number of Cables

max. 250 m

Connecting 1 sensor

1 x (2 x 1) mm2

Connecting 2 sensors

2 x (2 x 1) mm2 or

1 x (4 x 1) mm2

Mounting Steel Bracket Using Cable Connector Using Connection Box Mounting Oil Level Sensor Mounting Sludge Level Sensor

L

SX

Water

Air

Oil L

SX

Water

Air

OilL

S

XSludge

Water

Air

Oil

L Water zero line S Sensor switching point X Alarm limit

Always follow operating instructions of the oil/petrol separator manufacturer.

Mounting Warning Device Additional Settings

LAL-SRW

SUPPLYALARMRESET HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

LAL-SRW

SUPPLYALARMRESET HIGH OILLEVELOVERFLOWALARMSYSTEMOK

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

Enclosure Electric switchboard

AlarmReset Netz SystemOK SchichtdickeAlarm

D-68307 Mannheim(0621) 776-0

1

0

1

0

13 15 22 23 24

bubnbubn

OFF

ON

or

or

OFFON

1 2 3 4 5 6 7 8

OFFON

1 2 3 4 5 6 7 8

/

OFFON

1 2 3 4 5 6 7 8

+

YES For connection to external potential free contacts and further adjustments please turn over.

Quick Start Guide

Warning DeviceLAL-SRW

ENG

Document No.: 45-3207 Edition: 05/2011

Copyright Pepperl+Fuchswww.pepperl-fuchs.com

Pepperl+Fuchs GmbHLilienthalstrasse 20068307 Mannheim, GermanyTel. +49 621 776-0Fax. +49 621 776-1000

ImportantThe manual always takes priority over this quick start guide, which is only intended to provide a brief overview of the warning device functions. Refer to the manual for more detailed information about the warning device.The corresponding safety chapter in this manual is an integral component of this document. Make sure the information in the safety chapter is read and understood.

Scope of delivery

LAL-SRWSUPPLYALARMRESET HIGH OILLEVELOVERFLOWALARMSYSTEMOK

68301 Mannheim Germanywww.pepperl-fuchs.comOIL SEPARATOR ALARM

1 2 43

5

8

6 7

1 Warning device LAL-SRW 2 3 4 Sludge level sensor SLU-104-PF 5 Cable connector IP68 for one sensor cable LAL-SK2 6 7 8

Installation and ConnectionPreparation for Installation Cable Length Number of Cables

max. 250 m

Connecting 1 sensor1 x (2 x 1) mm2

Connecting 2 sensors2 x (2 x 1) mm2 or 1 x (4 x 1) mm2

Mounting Steel Bracket Using Cable Connector Using Connection Box Mounting Oil Level Sensor Mounting Sludge Level Sensor

L

SX

Water

Air

Oil L

SX

Water

Air

Oil L

S

XSludge

Water

Air

Oil

L Water zero line S Sensor switching point X Alarm limit

Always follow operating instructions of the oil/petrol separator manufacturer.

Mounting Warning Device Additional Settings

LAL-SRWSUPPLYALARMRESET HIGH OILLEVELOVERFLOWALARMSYSTEMOKOIL SEPARATOR ALARM

LAL-SRWOIL SEPARATOR ALARM

Enclosure Electric switchboard

10

10

13 15 22 23 24

bubnbubn

OFF

ON

or

or

OFFON 1 2 3 4 5 6 7 8

OFFON 1 2 3 4 5 6 7 8

/

OFFON 1 2 3 4 5 6 7 8

+

YES For connection to external potential free contacts and further adjustments please turn over.

NO Only acoustic and visual alarm, and no external connection

5 67230 V AC

Warning device is active.

Switch on the warning device.

NO Only acoustic and visual alarm, and no external connection

5 67230 V AC

Warning device is active.

Switch on the warning device.

NO Only acoustic and visual alarm, and no external connection

5 67230 V AC

Warning device is active.

Switch on the warning device.

Troubleshooting

SUPPLYALARMRESET

HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

LAL-SRW

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

The warning device is not in operation.Check whether the voltage supply is connected.

SUPPLYALARMRESET

HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

LAL-SRW

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

System is being put into operation. Overflow sensor in warm-up phase.Waituntiloverflowsensorhasreachedoperating temperature.

SUPPLYALARMRESET

HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

LAL-SRW

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

Warning device in normal state.

SUPPLYALARMRESET

HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

LAL-SRW

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

Alarm state, currently not active.1. Check the separator status.2. Press the Reset key.

SUPPLYALARMRESET

HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

LAL-SRW

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

Excessive liquid levelIt is essential to check the separator status. If necessary, takes measures to stop the alarm situation. The alarm situation can result if:• thecoalescencefilterisblockedor• the drain is defective or blocked.

SUPPLYALARMRESET

HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

LAL-SRW

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

Sensor fault or lead breakageCheck sensor and sensor installation and replace the sensor if necessary.

SUPPLYALARMRESET

HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

LAL-SRW

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

Maximum layer thickness or maximum sludge level reached.It is essential to check the separator status. Empty (disposal) the oil/petrol separator if necessary.

SUPPLYALARMRESET

HIGH OILLEVEL

OVERFLOWALARM

SYSTEMOK

LAL-SRW

68301 Mannheim Germanywww.pepperl-fuchs.com

OIL SEPARATOR ALARM

Sensor fault or lead breakageCheck sensor and sensor installation and replace the sensor if necessary.

LED does not light (OFF).

LED lights up (ON).

LEDflashing.

Relay Setting potential free Contacts

1 2 3 4 5 6 7 8

OFFON

1 2 3 4 5 6 7 8

OFFON

1 2 3 4 5 6 7 8

OFFON

1 2 3 4 5 6 7 8

OFFON

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

1 2 3 10 11 12

No powerNo LED ON

"SYSTEM OK" LED flashing

"SYSTEM OK"LED ON

"OVERFLOW ALARM"LED ON/flashing

"HIGH OIL LEVEL"LED ON/flashing

Warning deviceis not in operation

Alarm statecurrently not active

Warning devicein normal state

Excessive liquid levelor sensor fault

or lead breakage

Max. layer thicknessor max. sludge level

reachedor sensor fault

or lead breakage

No active alarm

**

* switch after 3 min.

ExamplesExternal Warning Light and Central Monitoring System Two External Warning Lights – one for Oil Layer Alarm and one for Overfill Alarm

1 2 3 4 5 6 7 8

OFFON

1 23 5 67 101112

230 V AC

1 2 3 4 5 6 7 8

OFFON

1 23 5 67 101112

230 V AC24V

CommissioningAcoustic Alarm

DIP 3Alarm ON

1 2 3 4 5 6 7 8

OFFON

DIP 3Alarm OFF

1 2 3 4 5 6 7 8

OFFON

24 Hours Repetition

DIP 6Repetition ON

1 2 3 4 5 6 7 8

OFFON

+

DIP 6Repetition OFF

1 2 3 4 5 6 7 8

OFFON

÷

Reset Function

DIP 7Reset key ON

1 2 3 4 5 6 7 8

OFFON

+ Resetfunction

DIP 7Reset key OFF

1 2 3 4 5 6 7 8

OFFON

Resetfunction÷


Recommended