+ All Categories
Home > Documents > r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa...

r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa...

Date post: 13-Mar-2021
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
26
"r e c h n i c a I ii,,,~ ,,., o rn liTl i t t e e II;D~ocu=n'~e ntat ion A Compi:ation of the Documented Action on Comments Rece'iw.~d by the Technical Committees Whose Reports. ,Have Been Publi;~,hed Prior to Consideration at the NFPA Annual Meeting Hyatt Regency Houston Hc, uston, TX May 17-20, 1976 Hotel Please Bring to the Annual IVli~eting] CopyrighP 1975 All Rights Reserved National Fire Protection A.~socmatlon 47{) Atlantic Aw.=nue, Bosto!n, MA 022i£J ~. ,M-3-7 t;.F F ..;M,
Transcript
Page 1: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

"r e c h n i c a I ii,,,~ , , . , o r n liTl i t t e e II;D~ocu= n'~e n t a t i o n

A Compi:ation of the Documented Action on Comments Rece'iw.~d by the Technical Committees Whose Reports. ,Have Been Publi;~,hed

Prior to Consideration at the NFPA Annual Meeting

Hyatt Regency Houston Hc, uston, TX

May 17-20, 1976

Hotel

Please Bring to the Annual IVli~eting ]

CopyrighP 1975 All Rights Reserved

National Fire Protection A.~socmatlon 47{) Atlantic Aw.=nue, Bosto!n, MA 022i£J

~. , M - 3 - 7 t ; .F F ..;M,

Page 2: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14, 26

S u p p l e m e n t a r y

Report of Committee on

Standpipes and Outside Protection

K e n n e t h J . C a r l , C'ha,rman M u n i c i p a l S u r v e y Serv ice , I n s u r a n c e Serv ices Sifter

160 ~ a t e r Street, N e ~ York . N Y 10O38

R i c h a r d H . C h a m b e r l a i n , Ne.re~ary M a n a g e r , F~re P r o t e c t i o n E n g i n e e r i n g , R o ~ e l l a n d A ~ o ( ' m t e 8

642O Fly Road, b,. Sbracuse , N Y 13057

W i l l i s C . B e a r d , N a t i o n a l A ~ n c,l F,r~ E q u i p m e n t Dt~t r l i ,u tors , i n c .

G r a h a m C l a r k e , Fac to ry M u t u a l Resea rch Curp

J o s e p h G . C o u t u , F a c to ry Inxurance A ~ n

AI,~,.L2,7 ~ . . . . . . . . . . . . . . . . . . . . . . . . . . ~ D o u g l a s G. P o o r l y . ( res .k l l l , N'J R o b e r t E l y , ( ' a l d o r n l s FLre t ' h m i a A ~ n H a l b e r t F l n k e l s t e l n , N e ~ Y . r k ~Cate

t ' r b a n D e v e l o p m e n t ( ' o rp E. E. H I n d ~ r e r . ( aterpd~ar t r a c t o r ~'o. T . C . J e s t e r , M a n u f a c t u r e r s ~ a n d a r d l z a -

Lion Society of the V a l v e & b'~l t i n s i n , lus t r~ K e r r y B. K o e n . M e m p h l ~ k i re Department A l l a n R . M a r s h a l l , B a d g e r P o w h a t a n (% R i c h a r d M a r t l n e a u . N a t m n a ] Automatt ,

S p r i n k l e r & F i r e Con t ro l : ~ s n J a m e s W, N o l a n , J a ~ e s ~ N o l a n ( ' u

J o h n ( ) ' H a g a n , Ne~s York ( ' t t y V l ~ D e p t J o h n E, P l a n t i n g s , M e y e r . S t rong & Jones P e t e r K. S c h o n t a g , N F p A I n d u s t r i a l F i r e

P ro t e c t i on S e e t m n R a y &. S i m p s o n . U m v e r m t y of M a r y l a n d

W. H a r r y S m i t h , C a s t i r o n P ipe Resea rch Aggn

W i l l i a m S t a n l e y T h o m p ~ n , F , re E q u i p - m e n t Manulact~irers Assn.

M i l e s S u c h o m e l . U n d e r w r i t e r s L a b o r a - t o rms l n e

W i l l i a m T. T r i n k e t , ~,ldi M u t u a l F i re P ~ - v e n t l o n B u r e a u

Fred S. W i n t e r s , A m e r l ~ n M u t u a l i ~ u r - ~nce A l h a n c e

J . M i l t o n W r i g h t , M a p l e , F L P c ; 2 : Y o r k . . . . . R o . J . . . . • * . . . . . . .

J o t~e ph A. 7 ~ t t , ,Iohnso~ & Hlggt t t s

A l t e r n a t e s

G o r d o n C. A n d e r s o n , Inburance .~ervlce8 A . P . S c l t t i n e , N F I ' A I n d u s t r i a l F i r e P ro Office ~ A I t ~ r n ~ ~. K e n n e t h J Carl t t~eOoa Sec t ion ( A } t e r n a ~ to P K .

R i c h a r d H. Erbe , l n m l r a n c e S e r v h ~ O/flee S e h o n t a g ) of ~ t s r o n m n ( A l t e r n a t e to A l l en S I)lmoff~ E l d o n A. S t e r n , Fa( ' to ry I ~ u r a D c e A ~ n .

R o b e r t J o s e p h M a d d e n , F i r e E q u i p m e n t IA l t e rna t~ to Joseph ( . ( ' d a t a 3 M ~ n u f a c t u r e r s A s s n , I n r ( A l t e r n a t e t,, W d h a m S T h o m p s o n )

Since the publication of the above Committee l i s t in the Technical Committee Reports, the following changes have been made in Committee membership:

Additions:

Murvan M. Maxwell, American Inst i tute of Architects

Guido Moccio,. Fire Marshals Assn. of North America

David O. Rogers, Alexander & Alexander

Stanley W. Muller, American Inst i tute of Architects {Alternate to Murvan M. Maxwell)

Deletion:

Douglas C. Doody

Changes in Representation:

Joseph G. Coutu, Industrial Risk Insurers

Eldon A. Steen, Industrial Risk Insurers (Alternate to Joseph G. Coutu)

Address Correction:

Kenneth J. Carl, Chairman Director, Public Protection Grading Insurance Services Office 160 Water Street New York, NY 10038

The Committee on Standpipes and Outside Protection presents for o f f ic ia l adoption its supplementary report on NFPA 14, Standard for the Insta l la t ion of Standpipe and Hose Systems and NFPA 26, Recommended Practice for the Supervision of Valves Controlling Water Supplies for Fire Protection. This supplementary report contains the documentation of the Committee's action on those public comments and recommendations submitted to i t in response to i ts report as published in the Technical Committee Report on October 7, 1975. In addition to the public comments received, some editor ial changes were made.

179

Page 3: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14~ 26

The supplementary repor t was submitted in two parts to l e t t e r b a l l o t by the Committee.

Part I presents for adoption the documentation of the Committee's action on the public comments and recommendation for NFPA 14.

Part I has been submitted to letter ballot of the Committee which consists of 29 voting members, of whom 19 have voted affirmatively, l has requested to be recorded as not voting (Mr. Schontag) and 9 have not returned their ballots (Messrs. Ely, Finklestein, Maxwell, O'Hagan, Plantinga, Simpson, Smith, Suchomel and Wright).

Part I I presents fo r adoption the documentation of the Committee's act ion on the publ ic comments and recommendations fo r NFPA 26.

Part II has been submitted to letter ballot of the Committee which consists of 29 voting members, of whom 19 have voted affirmatively, l has requested to be recorded as not voting (Mr. Schontag) and 9 have not returned their ballots (Messrs. Ely, Finklestein, Maxwell, O'Hagan, Plantinga, Simpson, Smith, Suchomel and Wright).

180

Page 4: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

1

Submitter:

Donald M. Johnson, Standard Oil Company of Ca l i fo rn ia

Statement of Problem:

The standard does not provide size range of small hose.

Recommendation:

I -5 .1 .2

I -5 .1 .2 Change to read: Class I I : For use p r ima r i l y by the bu i ld ing occupants un t i l a r r i va l of the f i r e department (small hose - 3/4- inch (18mm) through l - I / 2 - i n c h (37mm).

Supporting Comment:

This change supports the recommended change fo r Section 4-2.1 of th is standard.

Committee Act ion:

PART I

Recommendation :

14

I -5 .1 .3

Delete "and those t ra ined in handling heavy hose streams"

Paragraph would then read "Class I I ! fo r use by e i the r f i r e deparments or by bu i ld ing occupants"

Supporting Comment:

With the considerat ions the standard has on pressure regu la t ing devices and the fac t that heavy hose streams are not used th is change is considered necessary.

Committee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

This proposal const i tu tes new mater ia l .

Hold fo r fu ture agenda.

Committee Comment:

The Committee feels that 1 I /2 inch hose is read i l y ava i lab le as a l i s t e d item. Hose smal ler than 1 I /2 i~ch is covered in A- I -5 .1 .2 .

The subject of hose smal ler than 1 I /2 inch is under ac t ive study by a subcommittee and w i l l be considered fo r fu ture rev is ions.

3 Submitter:

Rolf Jensen, Rolf Jensen & ~ssoc~ates, Inc.

Statement of Problem:

The sect ion is incomplete.

Recommendation:

2

Submitter:

Gerald Duarte, Asst Chief, Contra Costa County Consolidated Fire D i s t r i c t

Statement of Problem:

Class I I I systems are equipped wi th pre-connect- ed 1 I / 2 " hose equipment which are not "heavy hose streams"

I -5 .2

Revise Section I -5 .2 to read: "Class I service shal l be capable of furn ish ing the e f fec t i ve f i r e streams required during the more advanced stages of f i r e on the ins ide of bu i ld ings or fo r exposure

I f i r e p ro tec t i on . "

Supporting Comment:

Addi t ion of the word "p ro tec t ion" completes the sentence.

Committee Act ion:

Accepted as an e d i t o r i a l rev is ion . 181

Page 5: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14

Committee Comment:

The Committee agrees wi th th i s proposal .

4 Submitter:

Edward J. R e i l l y , Nat ional Automatic Spr ink le r & F i re Control Assn., Inc.

Statement of Problem:

NFPA 13 and 14 should be cons is ten t wi th each other and take in to account Model Bu i ld ing Codes and most municipal codes whose requirements are more r e s t r i c t i v e than e i t h e r NFPA 13 or 14.

A l l CABO Codes fo r bu i ld ings over 75 fee t in height requ i re the f o l l ow ing :

l ) Water suppl ies up to 15,0DO gal lon~ in Seismic Zones two and three

2) A minimum of two r i se rs which must be manifolded together at vary ing bu i ld ing heights

3) Onsite suppl ies requ i re a hose stream discharge of I00 gpm on every f l o o r and every r i s e r .

Sections 3-7.8 and 8-4 of NFPA 13-1975 ca l l f o r 2 I / 2 - i nch hose valves fo r f i r e department use or the minimum of 500 gpm. Section 8-4 .4 , which does not requ i re tha t ca lcu la ted sp r i nk l e r demand be added, i s r e f e r e n c e d to NFPA 14 which ca l l s f o r a minimum of 500 gpm fo r the f i r s t r i s e r and 250 gpm fo r the second r i s e r wi th a maximum of lO00 gpm fo r a l l r i se rs . In view of the splendid record of supervised automatic s p r i n k l e r systems in e x t i n - guishing or c o n t r o l l i n g f i r e s , 500 gpm hose stream requirements are excessive.

A member of the IAFC and a member of FEMA have reported tha t f i r e departments, in actual p rac t i ce , use l I / 2 - i nch hose tha t d e l i v e r only lO0 gpm from the hose streams.

I t the re fo re seems incons is ten t to requ i re such a high volume of hose stream water when f i r e departments are equipped wi th 1 I / 2 - i nch hose l ines to back up a s p r i n k l e r system in a complete ly spr ink le red bu i l d ing .

Recommendation:

I -7.1

I -7 COMBINED SYSTEMS

I-7.1 A combined system is one where the water p ip ing serves both 1 I / 2 - inch (38 mm) ou t l e t s fo r f i r e department use and ou t l e t s fo r automatic sp r i nk le rs . Such combined systems shal l comply wi th the requirements of NFPA 13-1975 in

regard to the automatic sp r i nk l e r por t ions of the system, and wi th NFPA 14 in regard to s iz ing of v e r t i c a l r i se rs and water suppl ies. When the bu i ld ing is complete ly sp r ink le red , the r i se rs may be sized by hydrau l ic ca l cu la t i ons .

Supporting Comment:

None.

Committee Act ion:

Hold fo r fu tu re agenda.

Committee Comment:

This proposal cons t i tu tes new ma te r i a l .

5

S u b m i t t e r :

Stephen J. G i l b e r t , Chairman Fi re Hose Committee

Statement of Problem:

SI un i ts have not been approved by NFPA hose committee nor ANSI.

Recommendation:

I - 7 . 1 , I - 7 . 4 , 3-4.1, 3-4.2, 3-4.3 and A-3-4.1

Delete SI un i ts in Paragraphs I - 7 . 1 , I - 7 . 4 , 3-4.1, 3-4.2 and 3-4.3 and A-3-4.1.

Supporting Comment:

Does not meet NFPA-194-1974 Standard fo r Screw Threads and Gaskets fo r F i re Hose Connections.

Committee Act ion:

Accepted wi th mod i f i ca t i on . New sect ions to be added as fo l lows :

I -5 Units. Metr ic un i ts o f measurement in th i s standard are in accordance wi th the modernized metr ic system known as the I n t e rna t i ona l System of Units (SI ) . Two uni ts ( l i t r e and bar) , outs ide of but recognized by SI, are commonly used in i n t e r - na t iona l f i r e p ro tec t i on . These uni ts are l i s t e d in Table I -5 wi th conversion fac to rs .

I -5 .1 I f a value fo r measurement as given in th i s standard is fo l lowed by an equ iva len t value in

182

Page 6: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

I other un i ts , the f i r s t stated is to be regarded as the requirement. A given equivalent value may be approximate.

Table I -5

Name of Unit Unit Symbol Conversion Factor

metre m m i l l ime t re mm

l i t r e d~d~m 3 cubic decimeter pascal Pa

bar bar

bar bar

1 f t . = 0.305 m 1 in. = 25.4 mm_ 1 gal . = 3.785-I-- 1 gal . = 3.785 dm 3 I psi = 6894.757

Pa 1 psi = 0.0689

bar 1 bar = 105 Pa

For additonal conversions and informat ion see ANSI Z210. I-1973, Metr ic Pract ice Guide.

Renumber Sections I-5 through I - I I .

Committee ConT1ent:

I t was the i n ten t of the Committee to introduce Sl uni ts in th is standard as par t of the eventual United States conversion to SI un i ts . The Com- mi t tee feels that the add i t ion of Section I -5 w i l l c lear up any misunderstanding.

14

Because of th is establ ished record, hose stream requirements in NFPA 13 (Table 2-2.1(B) should provide adequate back-up to sp r ink le r systems to f i g h t i n t e r i o r f i r e s .

W~h his comment, Mr. Reil ly enclosed Automatic Sprinkler Performance Tables by ~ . H. W. M ~ y a t t , A ~ n Fire Pro~ect~on Associalion.

Committee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

This proposal constitutes new material.

7

Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

6

Submitter:

Edward J. Rei l ly, National Automatic Sprinkler & Fire Control Assn., Inc.

Statement of Problem:

See Proposal No. 4.

Recommendation:

I-7.2

I -7 .2 The waLer supply fo r a combined system shal l comply wi th the requirements given in Table 2-2.1(B) of NFPA 13-1975.

Supporting Comment:

HARRY W. MARRYATT'S TEXT "AUTOMATIC SPRINKLER PERFORMANCE IN AUSTRALIA (1886 - 1969) is the most re l iable source of data on supervised automatic sprinkler performance known to us. The record (attached) indicates that 66.56% of f i res were extinguished or controlled by one sprinkler. 92.81% by Five or less sprinklers. This was accomplished with water supplies and densities lower than those in the U.S.

Two problems occur in this section:

I. This section imposes additional water supply requirements in a combined sprinkler-standpipe system by requiring that water supplies also comply with Sec. I-7.3 in addition to the normal standpipe system requirements contained in Sec. 5-3.1.

2. Reference is made to water supply require- ments contained in Sec. 2-I.2 and 5-3.1. Section 2-I.2 contains pipe size require- ments, not water supply requirements.

Recommendation:

I-7.2

Revise Sec. I -7 .2 to read: "The water supply fo r a combined system shal l comply wi th the requirements given in 5-3.1. Exception: When the bu i ld ing is completely spr ink le red, the water suppl ies shal l comply wi th I - 7 . 3 . "

Supporting Comment:

Problem No. I :

There is a subtle but very important change in the verbiage of Sec. I-7.2 as compared to Sec. 142 of the former edition of the standard. Insertion of the word "also" would require that the water supply be sized, both in compliance with I-7.3 and 5-3.1. Obviously, this takes away the credit

183

Page 7: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14

which has been given in p r i o r ed i t ions of the standard in s iz ing the water supply fo r a f u l l y spr ink lered bu i ld ing . Bui ld ings designed under Sec. 14 of the previous ed i t ions of the standard have produced exce l len t service records and no j u s t i f i c a t i o n fo r an increase in the water supply requirements fo r these bu i ld ings is seen.

Problem No. 2:

This is a m i s i d e n t i f i c a t i o n of a reference paragraph.

Committee Act ion:

I Accepted in p r i nc i p l e . Delete "2-1.2 and" in second l ine and "also" in t h i r d l i ne of I -7 .2 as published in the Technical Committee Reports.

Committee Comment:

The Committee agrees wi th th is proposal.

Committee Comment:

This proposal constitutes new material.

9 Submitter:

Rolf Jensen, Rolf Jensen& Associates, Inc.

Statement of Problem:

The water supply for a combined system should relate to the actual system requirements irrespective of the size or occupancy of the building.

Recommendation:

8 Submitter:

Edward J. Re i l l y , National Automatic Spr ink le r & Fire Control Assn., Inc.

Statement of Problem:

See Proposal No. 4.

Recommendation:

I -7 .3

DELETE:

REASONS: I . A combination system as defined in I -7.1 can only be i ns ta l l ed in a completely spr ink lered bu i ld ing .

2. Water suppl ies (as proposed) are governed by Table 2-2.1(B), and 8-4.4 of NFPA 13-1975. NAS & FCA intends to submit an amendment to 8-4.4 to make NFPA 13 and 14 conform to water supply requirements of 2-2.1(B).

Supporting Comment:

None.

Committee Action:

Hold for future agenda.

I -7 .3

Revise Paragraph I-7.3 to read: "The minimum water supply for a combined system shall be equal to the sprinkler system design demand plus 250 gpm for inter ior hose use."

Supporting Comment:

Fire wi l l be controlled by the sprinkler systems. Final mop-up wi l l be with hose lines.

The standard contains no definit ion of a l ight hazard or a high rise building. Thus, reference to these types of buildings which are not properly defined by the standard is inappropriate.

Committee Act ion:

See Proposal No. 8.

Committee Comment:

See Proposal No. 8.

10

Submitter:

Stephen J. Gilbert, Chairman Fire Hose Committee

184

Page 8: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

Statement of Problem:

Spec i f i ca t ion of Fire Hose Connection sizes are not in the scope of NFPA-14 but ra ther the scope of NFPA-194.

Recommendation:

DELETE AND SUBSTITUTE When combination systems as defined in I-7.1

are provided class I , I I or I I I shal l not be required.

When combination systems are provided one 1 I /2 inch hose ou t l e t and a cap wi th an attachment chain shal l be provided on every f l o o r on every r i s e r .

14

I -7 .4

Reference I;o non-standard threads should be deleted. Revise I -7 .4 to read:

I -7 .4 In combined systems, when the bu i ld ing is completely spr ink le red, 1 I /2 inch (37 mm) hose fo r use by the bu i ld ing occupants (Class I I serv ice) may be omi t ted, subject to the approval of the au thor i t y having j u r i s d i c t i o n , provided that each standpipe ou t l e t locat ion is equipped wi th a 2 I /2 inch hose valve having a 2.5-7.5 NH male o u t l e t , a 2.5-7.5 NH female x 1.5-9 NH male reducer, and a 1.5-9 NH cap and chain. (Note: For fu r the r de ta i l s see Standard fo r screw threads and gaskets fo r Fire Hose Connections NFPA-194-1974).

Supporting Comment:

NFPA-194-1974 Standard fo r Screw Threads and Gaskets for Fire Hose Connections and ANSI-181.1 do not a l low for threads other than the NH standard.

Committee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

This proposal const i tu tes new mater ia l .

Supporting Comment:

None.

Committee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

This proposal const i tu tes new mater ia l .

12 Submitter:

Gerald Duarte, Asst Chief, Contra Costa County Consolidated Fire D i s t r i c t

Statement of Problem:

El iminat ing Class I I standpipe equipment in some occupancies, because i t is sp r ink le r protected is not a sound f i r e pro tec t ion prac t ice .

Recommendation:

11

Submitter:

Edward J. Re i l l y , National Automatic Spr ink ler & Fire Control Assn., Inc.

Statement of Problem:

See Proposal No. 4.

Recommendation:

I -7 .4

I-7.4

Delete Paragraph I-7.4

Supporting Comment:

I t should be required in Standard 14 and i f local authority wishes to grant an exception i t should be shown in the building code and not an NFPA Standard for the instal lat ion of standpipe and hose systems.

Committee Act ion:

Hold for future agenda.

185

Page 9: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14

Committee Comment: Recommendation:

This proposal cons t i tu tes new ma te r i a l .

13 Submitter'

C. W. Schirmer, Schirmer Engineering Corp.

Statement of Problem:

Omission of hose in combined systems is not clearly indicated but is "subject to the approval of the authority having jur isd ic t ion" . This is contrary to most major model building codes.

Recommendation:

1-7.4

Retain present wordage in 144 of NFPA 14-1974.

Support ing Comment:

Occupant use hose is not needed in bu i ld ings contemplated under th i s Sect ion ( f u l l y spr ink le red high r i se s t ruc tu res ) .

Committee Act ion:

Rejected.

2-I .6

Revise Sec. 2 - I . 6 to read: "Where pumps supply ing two or more zones are located at the same l e v e l , each zone shal l have separate and d i r e c t supply p ip ing of a size not smal ler than the r iser which i t serves. Zones with two or more standpipes shall have at least one direct supply pipe of a size not smaller than the largest r iser which i t serves."

Support ing Comment:

There does not seem to be any reason to cause the s ize of supply pipes to be l a rge r than the s ize of the r i s e r s , because the same f low w i l l occur in both. I f the committee be l ieves tha t excess f r i c t i o n loss may occur in supply p ipes, e i t h e r because they are of excessive length or because mu l t i p l e r i se rs are being f lowed s imul tan- eously, then the sect ion should be rev ised to ref lect the need for increased supply pipe sizes only under those conditions.

In any case i t does not appear tha t there is any j u s t i f i c a t i o n fo r mu l t i p l e supply pipes between a water supply source and the r i se rs in a m u l t i p l e r i s e r system.

Committee Act ion:

Hold for future agenda.

Committee Comment:

This proposal cons t i tu tes new ma te r i a l .

Committee Comment:

The Committee fee ls tha t hose may be needed in some cases and should be subject to the approval of the a u t h o r i t y having j u r i s d i c t i o n . This sec- t i on app l ies to a l l f u l l y sp r ink le red s t ruc tures not on ly to h i gh - r i se s t ruc tu res .

15

Submitter:

Rol f Jensen, Rol f Jensen & Associates, Inc.

Statement o f Problem:

14

Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

Reference is made to a minimum pipe s ize of 8". Two supply l i nes are requi red from a pump discharge to a zone which has two or more standpipes.

The time duration required the stored water supply is not stated.

Recommendation:

2-I .8

Revise Sec. 2-1.8 by adding a statement to the end reading: "The volume of stored water shall be adequate to supply the required flows for a 30- minute period."

186

Page 10: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

Supporting Comment:

Addit ion of the 30-minute time requirement makes Sec. 2-1.8 consistent with the Sections 5-3 and 5-4.

Committee Action:

Rejected.

Committee Comment:

Water durations are covered in Sections 5-3 through 5-5.

17

Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

There does not appear to be reasonable j u s t i f i c a t i o n for th is section.

Recommendation :

3-3.3

Delete Sec. 3-3.3.

14

16

Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

The sect ion, as wr i t ten , requires the owner of a bui ld ing to provide hose stream protect ion for neighboring exposing structures.

Recommendation:

Supporting Comment:

None

Committee Action:

Rejected.

Committee Comment:

The Committee feels that the piping should be accessible for inspection and test ing.

3-3.1

I Revise section 3-3.1 to read: "Where bui ldings are wi th in 60 f t . (18.3 M) of exposed bui ld ings, standpipes for' large stream shall be located so as to af ford protect ion to the i n t e r i o r of the bui ld ing from ex te r io r exposures.

Supporting Con~ent:

The in tent of th is section is to provide protect ion to an exposed bui ld ing from an exposing bui ld ing.

Committee Acti on :

Accepted as amended. Revise section 3-3.1 to read: "Where a bui ld ing is wi th in 60 f t . (18.3 M) of exposing bui ld ings, standpipes for large streams shall be located so as to a f ford protect ion to the i n t e r i o r of the bui ld ing from ex te r io r exposures.

Committee Comment:

I8 Submitter:

Rolf densen, Rolf Jensen & Associates, Inc.

Statement of Problem:

This section is redundant. The requirements stated in th is section have been previously stated in Sec. 3-2.1 and Sec. 3-2.2.

Recommendation :

3-3.4

Delete Sec. 3-3.4

Supporting Comment-

None.

The Committee feels the change c l a r i f i e s the in tent of the section. 187

Page 11: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14

Committee Action:

Rejected.

Committee Comment:

The Committee feels that this section is not redundant and i t supplements 3-2.1 and 3-2.2.

19 Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

There does not appear to be reasonable j us t i f i ca t i on for this requirement.

Recommendati on:

3-3.5

Delete Sec. 3-3.5.

Supporting Comment:

None.

Committee Act i on :

Hold for future agenda.

Committee Comment:

This proposal constitutes new material.

20 Submitter:

Stephen J. Gi lbert , Chairman Fire Hose Committee

Statement of Problem:

Following paragraphs are not clear:

3-4.1, .2, and .3 - Are the hose connections valved?

3-4.l - What size connections on the roof outlet?

Recommendat i on :

3-4.1, 3-4.2, 3-4.3

None

Supporting Comment:

None

Committee Action :

I1old for future agenda.

Committee Comment :

This proposal constitutes new material.

188

21 Submitter:

Stephen J. G i l be r t , Chairman Fire Hose Committee

Statement of Problem:

Spec i f i ca t ion of Fire Hose Connection sizes are not in the scope of NFPA-14 but ra ther the scope of NFPA-194.

Recommendation:

3-4.4

Reference to non-standard threads should be deleted. Revise 3-4.4 to read:

3-4.4 Al l hose connection threads in paragraph 3-4 shal l conform to NFPA-194-1974.

Supporting Comment:

NFPA-Ig4-1974 Standard fo r Screw Threads and Gaskets fo r Fire Hose Connections and ANSI-181.1 do not a l low for threads other than the NH standard.

Committee Act ion:

Hold fo r fu ture agenda.

Page 12: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

Committee Comment:

This proposal constitutes new material.

14

Statement of Problem:

There does not appear to be reasonable j u s t i f i - cation for the statement regarding the location of outlets at in ter ior columns.

22 Submitter:

John W. Bisantz, Liberty Mutual Insurance Company

Statement of Problem:

Text of 4 - l . l is not strong enough. A l i f e hazard is involved here for f i re fighers and building occupants. The information contained in "A"4 - l . l , second paragraph, should be included as a part of the standard, rather than kept in the appendix where i t has an information only type of impact.

Recommen da t i on :

Ch 4 para l . l

Add, af ter second sentance, f i r s t paragraph of 4 - l . l , the second paragraph of "A"4 - l . l . Change "should" to "shall" in f i r s t and second sentances of this additional paragraph.

Supporting Con~ment :

I t only makes sense to try to prevent smoke from f i l l i n g stairway towers used for evacuation. Having hose outlets in stairwells only, forces f i re f ighters to par t ia l l y jam open selfclosing f i re doors with f i re hose when operating at a f i re .

Committee Action:

Hold fo r fu ture agenda.

Committee Comment:

This proposal constitutes new material.

Recommendation:

4-I . l

Revise Sec. 4-1.1 by deleting the paragraph: "In buildings having large areas, outlets for Class I and Class I l l service may be located at in ter ior columns (3-3.5)."

Supporting Comment:

None.

Committee Action:

i Accepted in part. The second paragraph of 4-1.1 is added to A-4-1.1.

Committee Comment:

The Committee feels that, in some instances, there is jus t i f i ca t ion for locating standpipes at in ter ior columns. By moving the paragraph to the Appendix (the advisory portion of the standard), the intent of the Committee is accomplished.

24 Submitter:

Stephen J. Gilbert, Chairman Fire Hose Committee

Statement of Problem:

As f i r e hose is mentioned in paragraph 4-2.1, reference should be made to NFPA-196-1974.

Recommendation:

23 Submitter"

Rolf Jensen, Rolf Jensen & Associates, Inc.

4-2.1

None

Supporting Comment:

NFPA-I94-1974 o f fe rs three (3) 1 I / 2 " Single Jacket Hoses.

189

Page 13: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14

Committee Action:

i Accepted. At the end of 4-2.1 add (See NFPA 196-1974, Standard for Fire Hose).

Committee Comment:

The Committee agrees with th is ed i t o r i a l change.

25

Submitter:

Donald M. Johnson, Standard Oil Company of Ca l i fo rn ia

Statement of Problem:

The standard proh ib i ts the use of f i rm wall garden type hose of 3/4-inch (18mm) and l - inch (25mm) size for Class I I standpipe systems.

Recommendation:

4-2.1

4-2.1 Hose. Change to read: Each hose ou t le t provided for the use of bui ld ing occupants (Class I I and I I I services) shall be equipped with not more than I00 feet of approved small (3/4-inch (18mm) thru l - I / 2 - i n c h (37mm) f i r e hose attached and ready for use.

Supporting Comment:

This change w i l l a l low 3/4-inch (18mm) thru l - I / 2 - i n c h (37mm) including f i rm wall garden type hose for use by bu i ld ing occupants (Class I I and I I I services). An inexperienced person can more safely act ivate such a hose, is more l i k e l y to get water on the f i r e sooner in his attempt to ext inguish i t , and create less hazard to himself. Also, small size garden type hose is i n f i n i t e l y more maneuverable in corr idors and of f ices and can e f f ec t i ve l y ext inguish small f i res with less water damage. The hose connection of a standpipe for Class I I I use should be sui tab le for connection of larger hoses by the f i r e department and should be equipped with an eas i ly removed reducing f i t t i n g to adapt to the smaller hose couplings.

This suggested change may require addi t ional re lated changes in the standard.

Committee Action:

See Proposal No. I.

Committee Comment:

See Proposal No. I .

26 Submitter:

Kenneth R. Long, Los Angeles City Fire Department

Statement of Problem:

Hose l i n ing cracks with age.

Recommendation:

4-2. l

Add Exception 2 to Section 4-2.1 as shown:

4-2 Hose.

4-2.1 Each hose ou t le t provided for use of bui ld- ing occupants (Class I I and I I I services) shall be equipped with not more than I00 feet (30.5 m) of approved l ined, 1 I /2 inch (37 mm) f i r e hose attached and ready for use.

Exception Number I : Unlined hose may be used on ex is t ing standpipe i ns ta l l a t i ons made pr io r to June 1976.

Exception Number 2: Unlined Hose may be used when approva.l, from the author i ty havin 9 j u r i sd i c t i on is obtained.

Supporting Comment:

In the past the l i n i ng in hose has cracked in the folds as i t is seldom reposit ioned. We have found no problems with a good grade of unlined hose.

Committee Action:

Rejected.

Committee Comment:

The Committee feels that l i s ted l ined hose is ava i lab le and should provide sat is fac tory service.

The three major model bui ld ing codes, Uniform Bui lding Code, Southern Standard Bui lding Code and BOCA Basic Bui lding Code require l ined hose on wet standpipe systems.

190

Page 14: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

27

Submitter:

Donald M. Johnson, Standard Oil Company of Cal i fornia

Statement of Problem:

Provision must be made for storage of 3/4-inch (18mm) and l- inch (25mm) firm wall garden type hose suggested for Section 4-2.1.

Recommendation:

4-3, 4-3.1, 4-3.2

a) 4-3 Hose Racks. Revise the t i t l e to, "Hose Racks and Reels."

b) 4-3.1 Change to read: Each station provided with small hose shall be equipped with a l is ted rack or other approved storage f a c i l i t y .

c) 4-3.2 Change to read: Each hose rack or other approved storage f a c i l i t y for small hose shall be provided with a label aff ixed to include "Fire Hose for Use by Occupants" and operating instructions.

Supporting Comment:

None.

Committee Action:

See Proposal No. I.

Committee CoBnent:

See Proposal No. I.

28 Submitter:

Loren L. Keltner, National Fire Sprinkler Corp.

Statement of Problem:

Error in wording. The words "Prior to" should be replaced with the word "after".

Recommendation:

4-4.3

On installations made after June, 1976, each hose valve having linen hose shall be provided with a l isted automatic drip connection so installed that any slight leakage past the valve seat wi l l be prevented from entering the hose.

Supporting Comment:

Same reaspning as exception to paragraph 4-2.1.

Committee Action:

14

Accepted as amended. Delete "On installations made prior to June 1976" and change the word

I "linen" to "unlined" and at the end of the section add (see Exception - 4-2.1).

Committee Comment:

The Committee feels the change clar i f ies the intent of the section.

29

Submitter-"

Stephen J. Gilbert, Chairman Fire Hose Committee

Statement of Problem:

Specification of Fire Hose Connection sizes are not in the scope of NFPA-14 but rather the scope of NFPA-194.

Recommendation:

4-4.4

Reference to non-standard threads should be deleted. Revise 4-4.4 to read:

4-4.4 The hose outlet of each hose valve shall have threads conforming to NFPA-194-1974 Standard for Screw Threads and gaskets for f i re hose connections.

Supporting Comment:

NFPA-194-1974 Standard for Screw Threads and Gaskets for Fire Hose Connections and ANSI-181.1 do not allow for threads other than the NH standard.

191

Committee Comment:

Hold for future agenda. An editorial change is made in the second sentence to read as follows:

Page 15: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14

"American National Fire Hose Connection Screw Threads shal l be used whenever they w i l l f i t ex i s t i ng equipment." The word "Connections" in the note is changed to "Couplings".

Committee Comment:

This proposal const i tu tes new mater ia l .

30 Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

I t is i l l o g i c a l to place a "K" fac to r l i m i t a - t i on on a nozzle which w i l l l i m i t the disc_s~h~ge from a standpipe to 75 gpm (75 = 7.5 x ~ 0 0 ) when the design c r i t e r i a fo r that standpipe ca l l s fo r the c a p a b i l i t y of de l i ve r ing I00 gpm or 500 gpm.

Recommendation:

4-5.1

Revise Sec. 4-5.1 to read: "Nozzle shal l be of an approved type. The discharge c o e f f i c i e n t shal l be such that I00 gpm may be discharged from a Class I I standpipe and hose system and 250 gpm from a Class I I I standpipe and hose system."

Supporting Comment:

A wide var ie ty of nozzles that are UL l i s t e d and FM approved are ava i lab le on standpipe and hose systems wi th "K" factors in excess of the 7.5 l i m i t a t i o n .

Statement of Problem:

A minimum water supply should also be included fo r combined systems.

Recommendation:

Include a new section e n t i l e "Minimum Supply fo r Combined Systems". The minimum supply fo r a combined spr ink le r /s tandp ipe system shal l be 250 gpm (hose stream requirement) plus the hydrau l i - ca l l y ca lcu lated sp r ink le r demand for a 30-minute per iod . "

Supporting Comment:

Inclusion of these minimum requirements completes the format fo r water supply requirements presented in Chapter 5.

Committee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

This proposal const i tu tes new mater ia l .

32 Submitter:

R.E. Hughey, Chief Engineer, Insurance Services Of f ice

Statement of Problem:

Con=nittee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

This proposal const i tu tes new mater ia l .

31 Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

As present ly w r i t t e n , the standard spec i f ies water pressure and quant i ty requirements only at the top of ve r t i ca l r i se rs . No informat ion is provided fo r the s iz ing of hor izontal runs of p ip ing.

Recommendation:

192

Chapter 5

Add the fo l low ing three paragraphs:

5-3.2 The minimum water supply at the hydrau l i - ca l l y most remote hose connection shal l be s u f f i c i e n t to provide a residual pressure of 65 pounds per square inch (448 kPa) at the ou t l e t w i th 500 gal lons per minute (1893 L/min) f lowing from the ou t l e t .

Page 16: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

5-4.2 The minimum water supply at the hydrau l i - ca l l y most remote hose connection shal l be s u f f i c i e n t to provide a residual pressure of 65 pounds per square inch (448 kPa) at the ou t l e t w i th I00 gal lons per minute (379 L/min) f lowing from the ou t l e t .

5-5.2 The minimum supply fo r the hyd rau l i ca l l y most remote hose connection on Class I I I service shal l be the same as fo r Class I service.

Supporting Comment:

The proposed addition would fac i l i t a te hydraulic design for horizontal runs of pipe as well as for vert ical risers.

Committee Action:

Accepted as a c l a r i f i c a t i o n of 5-3.1.

Committee Comment:

The Committee agrees wi th th is proposal.

33 Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

Sec. 5-2.4 should reference Sec. 5-3 and 5-5 which establish water supply requirements.

Recommendation:

5-2.4

Revise Sec 5-2.4 to read: "Supply for Class I and Class I l l services shall be capable of furnish- ing the number of streams in durations required by Sec. 5-3 and Sec. 5-5."

Supporting Comment:

None.

Committee Act ion:

Accepted as amended. Revise 5-2.4 to read: "Supply for Class I and Class I l l services shall be capable of furnishing the number of streams and durations required in 5-3 and 5-5. These minimums may be increased by the authority having jur isd ic- t i on." 193

Committee Comment:

14

The Committee agrees with this proposal.

34 Submit ter :

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

A f i re department connection is required for each standpipe zone within a high rise building.

Recommendation:

5-6.2

Revise Sec. 5-6.2 to read: "In high rise buildings having two or more zones, a f i re department connection shall be provided for each zone. (See Figures A-2-1b and A-2-1c)

Exceptions:

I . Fire department connections are not required for standpipe zones which have the lowest hose outlet more than 400 f t . above the f i re department connection in le t elevation.

2. Where the local f i re department has special- ized apparatus for pumping to elevations in excess of 400 f t . , f i re department connec- tions shall be provided so as to take advantage of the pumping capabil i ty of the specialized apparatus."

Supporting Comment:

When the e levat ion grad ient between the pump ou t l e t and the standpipe ou t l e t exceeds 400 f t . , the pump cannot be expected to provide a reasonable source of supply to the standpipe o u t l e t .

Committee Action:

Hold fo r fu ture agenda.

Committee Comment:

This proposal const i tu tes new mater ia l .

Page 17: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14

35 Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

There appears no reasonable just i f icat ion for including this section.

Recommendation:

5-6.3

Delete Sec. 5-6.3 and provide appropriate appendix material detailing f i re department connections support recommendations.

Supporting Comment:

None.

Supporting Comment:

NFPA-194-1974 Standard for Screw Threads and Gaskets for Fire Hose Connections and ANSI 181.1 do not allow for threads other than the NH standard.

Committee Comment:

Hold for future agenda. An editorial change is made in the second sentence to read as follows: "American National Fire Hose Connection Screw Threads shall be used whenever they wi l l f i t the local f i re department hose threads." The word "Connections" in the note is changed to "Couplings".

Committee Comment:

This proposal constitutes new material.

Committee Action:

Hold for future agenda.

Committee Comment:

This proposal constitutes new material.

37

Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

This section should be written in a positive manner.

36 Submitter:

Stephen J. Gilbert, Chairman Fire Hose Committee

Statement of Problem:

Specification of Fire Hose Connection sizes are not in the scope of NFPA-14 but rather the scope of NFPA-194.

Recommendation :

5-6.8

Reference to non-standard threads should be deleted. Revise 5-6.8 to read:

5-6.8 The threads of the Fire Department Connections shall conform to NFPA-194-1974, Standard for Screw Threads and Gaskets for Fire Hose Connections.

Recommendation:

5-6.9c

I Revise Sec. 5-6.9c to read: "Where a hose connection serves only a portion of a building, an appropriate and durable sign shall be attached indicating the portions of the building served."

Supporting Comment:

The committee may also wish to include appendix material regarding this section.

Committee Action:

Accepted as an editorial revision.

Committee Comment:

The Committee agrees with this proposal.

194

Page 18: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

38 Submitter:

Roll Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

This sect ion is not consistent wi th Sec. 2-1.6 regarding the s ize of hor izonta l p ip ing connecting the base of a standpipe system.

Recommendation:

6-I . I

Revise Sec. 6-1.1 to read: "Connections from gravity tanks (on buildings) and pressure tanks (on top f loor or roof) shall be made to the top of the standpipe system except where tanks are used as a supply to standpipes in several buildings or sections of a building, in which cases they shall be made at the base of the standpipes. Such connections to standpipes shall be as large as the standpipes which they serve."

Supporting Comment:

None.

Committee Action:

Hold for future agenda.

Committee Comment:

This proposal const i tu tes new mater ia l .

39 Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

This sect ion is redundant wi th Sec. 2-1.6.

Recommendation:

6-1.3

Delete Sec 6 - I .3 .

Supporting Comment:

None.

14

Committee Action:

Hold fo r fu ture agenda.

Committee Comment:

This proposal const i tu tes new mater ia l .

40 Submitter: C. V. Lovet t , Webster, New York

Statement of Problem:

I t should not be necessary to have the connec- t ion from a f i r e pump(s) made at the base of standpipes i f adequate check valves, dra ins, etc. are i ns ta l l ed . A pump should be able to be located in the standpipe system at any point i f properly designed for a multi-story building and not restricted to on__n]_y_at base of the standpipe.

Recommendation:

TCR p. 275, 6-1.3

None.

Supporting Comment:

A f i r e pump only at the base of standpipe can be very r e s t r i c t i v e to a high r i se bu i ld ing . Please expla in why i t is required to have the pump only at the base i f not acceptable to locate pump any place in standpipe system. See the attached sketch of a pump located ha l f way up a mu l t i - s t o r y bu i ld ing .

With hW~s comment, Mr. Covert enclosed a ske tch of his proposal.

Committee Act ion:

Accepted in principle. Section 6-1.3 to read as follows: "'6-1.3 Connections from f i re pumps and sources outside the building shall be large enough to deliver their fu l l rated capacity without excessive f r ic t ion losses."

New: A-6- I .3 Connections from f i r e pumps and sources outside the bu i ld ing should be made at the base of the standpipes.

195

Page 19: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14

Committee Comment: Statement of Problem:

The Committee agrees wi th the in ten t of the proposal. The f i r s t sentence is moved to the appendix as a recommendation ra ther than a requirement.

The verbiage of th is sect ion v io la tes the Style Manual.

Recommendation:

41 Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

This sect ion requires standpipes suppl ied by tanks to be interconnected at the top but not standpipes suppl ied by other water supply sources.

Recommendation:

6-I .4

Revise Sec. 6-1.4 to read: "Where two or more standpipes are i ns ta l l ed in the same bu i ld ing or same sect ion of a bu i l d ing , they shal l be i n t e r - connected at the top and bottom. Check valves may be i n s t a l l e d at the base of each r i s e r to prevent c i r c u l a t i o n .

Exception: In bu i ld ing sect ions which are not continuous at the top f l o o r , the top loop may be omi t ted . "

Supporting Comment:

None.

Committee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

This proposal const i tu tes new mate r ia l .

42 Submitter"

Rolf Jensen, Rolf Jensen & Associates, Inc.

6-2.3

Revise Sec. 6-2.3 to read: "Connections to publ ic water systems shal l be con t ro l l ed by ind ica to r post valves of an approved type located not less than 40 f t . (12.2 m) from the bu i ld ing protected. Al l valves shal l be p l a i n l y marked to ind icate the service which they cont ro l .

Exceptions:

I . When the valve cannot be located more than 40 f t . from the bu i ld ing , i t should be placed where i t w i l l be read i l y accessible in case of f i r e and not subject to in ju ry .

2. Where ind ica to r post valves cannot be used, underground valves which are p l a i n l y marked and which have the d i rec t i on to turn to open p l a i n l y marked may be used.

Supporting Comment:

None.

Committee Act ion:

Accepted in p r i nc ip l e as an e d i t o r i a l change. New Section 6-2.3 to read as fo l lows:

"Connections to publ ic water systems shal l be cont ro l led by ind ica to r post valves of an approved type located at leas t 40 f t . (12.2 m) from the bu i ld ing protected. Al l valves shall be p l a i n l y marked to ind icate the service which they con t ro l . "

Exceptions:

I . When the valve cannot be located at least 40 f t . {12.2 m) from the bu i ld ing , i t shal l be placed where i t w i l l be read i l y accessible in case of f i r e and not be subject to i n ju ry .

2. When ind ica to r post valves cannot be used, underground valves may be used. The valve loca- t ions and d i rec t ions to open and services which they contro l shal l be p l a i n l y marked on the bu i l d ings . "

Committee Comment:

The Committee agrees wi th th is proposal.

196

Page 20: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

43 Submitter:

Robert Steiner, Berger Industries, Inc.

Statement of Problem:

6-3.1 is inaccurate, does not conform with work done in NFPA-13 Omitted .188 and .120 Wall E.R. W. pipe as specified in NFPA-13.

Recommendation:

6-3.1, Material & Dimensions

Pipe should be l isted in table as specified in NFPA-I 3.

Supporting Com~ent:

E.R.W. pipe in .120 & .188 wall have working pressures far in access of 300 Ibs.

Committee Action:

Rejected.

Committee Comment :

No technical data on E,R.W. has been submitted to the Committee.

Supporting Comment:

Adequate pipe strength can be obtained by specifying required design working pressures,

A system w i l l not have increased strength by merely increasing the strength of one component. In th is case, increasing the strength of the ver t i ca l piping whi le ignoring the hor izontal piping at the base of the system w i l l not increase the strength of the system behond that of the hor izontal piping, The weak l ink w i l l be the bulk feed piping at the base of the system,

Committee Action:

Accepted.

Committee Comment:

The Committee agrees with th is proposal.

The subject of piping is under act ive study by a subcommittee.

45

Submitter:

William L. Testa, National Automatic Sprinkler and Fire Control Assn.

14

Statement of Problem:

44 Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

The requirement for a minimum 0.250" wall th ick- ness for ver t i ca l piping in Class I and Class I I I systems does not appear to be j u s t i f i e d . This requiremnt precludes the use of Schedule 40 pipe in pipe sizes 4" and smaller. In addi t ion, the hor izontal bulk feed piping for a standpipe system located at the base of the standpipe r isers may have a thinner wall thickness than the ver t i ca l standpipes.

Recomendation:

6-3.1

l Revise Sec. 6-3.1 by delet ing the statement: "Vert ica l pipe in Class I and I I I systems shal l not be less than 0,250 (6.4mm)" thickness," 197

Table 6-3.1 (Page 14-20) should not be l im i ted to: Welded Seamless Pipe, ASTM A 120-73. Asterick references "Standard Wall" Schedule 40 Pipe permitted for pressures up to 300 P.S.I. Schedule 30 Pipe acceptable in sizes 8 inch and larger.

Paragraph 6-3.1 states wall thickness not less .250. This excludes 4" Schedule 40, which has a nominal wall thickness of .237 (Sch. 80 is .337).

Recommendation:

Section 6-3.1

Refer to NFPA 13, I ns ta l l a t i on of Spr inkler Systems 1975, Paragraph 3-1.1.2 and 3 - I .1 .3 , al lowing usage of E.R.W. pipe having wall thickness of .188 for sizes 4 through 8 inches and .120 for sizes 2 I /2" through 6". Such wall thickness is permitted for pressures up to 300 P.S.I.

Supporting Comment:

NFPA 14 should also al low option to use more ecomonical .188 and .120 wall thickness pipe.

Page 21: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14

Schedule 30 and 40 Pipe was chosen many years ago, because of thread and cut groove j o in ing features which are now augmented in favor E.R.W. or continuous welded pipe that can be jo ined by r o l l groove or welded p r i nc ip les .

Commiteee Act ion:

See Proposal Nos. 43 and 44.

Committee Comment:

See Proposal Nos. 43 and 44.

46 Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

The requirements fo r p ip ing in th is sect ion should be consistent wi th the requirements wi th Sec. 3-12.1.3 of NFPA 13, 1975 ed i t i on .

Recommendation:

6-4.1

Revise Sec. 6-4.1 to read: " I f f i t t i n g s are of cast i ron, extra heavy patterns shal l be used in sizes la rger than 2" where the normal pressure in the p ip ing system exceeds 175 psi . I f f i t t i n g s are of mal leable i ron, standard weight pat terns shal l be acceptable in sizes up to 6" inc lus ive when the normal pressure in the pipe system does not exceed 300 ps i . F i t t i ngs made of mater ia l other than cast i ron and mal leable iron and s p e c i f i c a l l y approved fo r use in f i r e pro tec t ion systems may be used at p ip ing system pressures up to the working pressure l i m i t s spec i f ied in t h e i r l i s t i n g . "

Supporting Comment:

The two standards should be consistent in t h e i r requirements fo r p ip ing.

Committee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

47

Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

This sect ion impl ies that f l e x i b l e gasketed couplings may be used. This point should be c l a r i f i e d .

Recommendation:

6-4.2

Revise Sec. 6-4.2 so that the f i r s t sentence reads: "A l l p ip ing shal l be i n s t a l l e d by means of threaded or f langed f i t t i n g s , f l e x i b l e gasketed coupl ings, or other approved means."

Supporting Comment:

This w i l l c l a r i f y the question regarding th is type of coupl ing.

Committee Action:

Hold fo r fu ture agenda.

Committee Comment:

The Committee feels that l i s t e d f l e x i b l e gas- keted couplings are covered under other approved means. Further c l a r i f i c a t i o n w i l l be made in fu ture rev is ions.

48 Submitter:

C. V. Lovett , Webster, New York

Statement of Problem:

The statement does not requi re any type of performance tes t or c e r t i f i c a t i o n of the welder.

Recommendation:

TCR p. 276, Par. 6-4.2

Use statement from NFPA No. 13 - 3-12.4.6.

This proposal const i tu tes new mater ia l . 198

Page 22: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

Supporting Comment:

The system is under high pressure and required of a sp r ink le r system and a standpipe system should be s im i l a r .

Committee Act ion:

Hold fo r fu ture act ion.

Committee Comment:

The Committee plans to study the en t i re subject of welding as appl ied to standpipe systems.

49 Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

This sect ion should c l ea r l y s tate where water f low alarm devices are required.

Recommen da t i on :

6-7.1

Revise Sec. 6-7.1 to read: "A water f low alarm device shal l be provided at the base of each standpipe r i s e r and on combined systems at each sp r ink le r system connection to the standpipe."

Supporting Comment:

The committee may also wish to include appendix mater ia l regarding th is sect ion.

Committee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

This proposal const i tu tes new mater ia l , . The por t ion of the proposal wi th respect to 'a water f low alarm device" being provided "at each sp r i nk le r system connection to the standpipe" is a matter tha t f a l l s w i th in the scope of the Committee on Automatic Spr ink lers .

50 Submitter:

Tom L. Lyon, Wilmette, I l l i n o i s

Statement of Problem:

The sect ion is not par t of the scope of the standard.

Recommendation:

7-1.3.1, 7-1.3.2

Delete 7-1.3.1 & 7 - I .3 .2 & inser t

7- I .3 .1 "For new pipe tes t in accordance wi th NFPA #24 Paragraph 99.

Renumber as necessary.

Supporting Comment:

The standard fo r tes t ing of underground pipe should be r es t r i c t ed to one standard & a l l other standards refered to i t . This requirement as wr i t t en does not coincide wi th NFPA #24 1973.

Committee Act ion:

Rejected.

Committee Comment:

Sections 7- I .3 .1 and 7-1.3.2 re fe r to under- ground port ions of the standpipe system.

The Committee points out that the requirements of these two sections have been approved by the Committee fo r inc lus ion in NFPA 24, Standard fo r Outside Protect ion.

51 Submitter:

C. V. Lovet t , Webster, New York

Statement of Problem:

a) & b) No tes t descr ip t ion is provided. This pressure tes t is very vage and incomplete.

b) What is a " s u f f i c i e n t " volume of water - 5 gpm?

14

199

Page 23: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14

Recommendation:

a) TCR p. 277, 7-1.5 b) TCR p. 277, 7-1.4.1

Out l ine i f the tes t is to be a i r - h y d r o s t a t i c , minimum amount of pressure, durat ion, amount of leakage, i f any, etc.

Supporting Comment:

Committee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

This proposal const i tu tes new mater ia l .

None.

Committee Act ion:

a) & b) Hold fo r fu ture agenda.

Committee Comment:

a) This proposal const i tu tes new mate r ia l .

b) The en t i re subject of tes t ing and mainte- nance of standpipe systems is under ac t ive study by a subcommittee.

53 Submitter:

Robert J. Madden, F i re Equipment Manufacturers Assn., Inc.

Statement of Problem:

Present tex t does not include tes t procedure fo r ex is t ing systems. 7-2.5 ex is t ing paragraph to be renumbered 7-2.6.

Recommendation:

52 Submitter:

C. V. Lovet t , Webster, New York

Statement of Problem:

An a i r pressure tes t of only 25 psi is not adequate fo r a wet standpipe, espec ia l l y i f the system is going to have in excess of 150 psi normal s t a t i c pressure.

Recommendation:

TCR p. 277, 7-1.6

None.

Supporting Comment:

This is an inadequate pressure tes t fo r an unused standpipe i f i t is to be replaced in service. I f a f i r e department pumper connects in to such a standpipe you could expect minimum pressures of at least 150 psi . Therefore the system must be capable of wi thstanding at leas t 150 psi wi thout damage or breakage. Refer to N.F.P.A. No. 13-I-11.

7-2.5

At i n te rva ls not greater than 3 years for bu i ld ings or s t ructures 75 feet or greater in height and at i n te rva ls not greater" than 5 years f o r a l l other bu i ld ings or st ructures a l l stand- pipe systems inc luding yard piping shal l be tested hyd ros ta t i ca l l y at not less than 200 pounds psi pressure fo r 15 minutes or at 50 pounds psi in excess of the normal pressure when the normal pressure is in excess of 150 pounds psi . Water f low tes t ing w i l l be completed on each system wi th a minimum f low of 500 gal lons per minute f lowing at the topmost ou t l e t fo r Class I and Class 3 standpipe systems and wi th a minimum f low of I00 gal lons per minute at the topmost ou t l e t fo r Class 2 standpipe systems. Al l f a i l u r e s , excessive leakage, and obstruct ions shal l be reported immediately and the necessary repai rs made to place the system back in service.

Supporting Comment:

During recent years standpipe fa i l u res have been occurr ing at an alarming rate resu l t ing in substant ia l f i r e losses and excessive operat ional delays. Decreased f i r e department manning necessitates a high degree of standpipe r e l i a b i l i t y .

Committee Act ion:

Hold fo r fu ture agenda.

200

Page 24: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

Committee Comment: Recommendation:

14

The entire subject of testing and maintenance of standpipe systems is under active study by a subcommittee.

54

Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

Reference to a "Siamese" f i r e department connection should be e l iminated.

Recommendation:

8-1.1.1

Revise Sec. 8-1.1.1 to read: "The standpipes shal l be provided wi th conspicuously marked f i r e department connections on the outside of the bu i ld ing at s t ree t level and shal l have at leas t one standard hose ou t l e t at each f l o o r .

Supporting Comment:

None.

Committee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

8-I .l .2

Revise Sec. 8-I. I .2 to read: "The pipe sizes, hose valves, hose, water supply and other details for temporary standpipes in buildings under construction shall be in accordance with the requirements for standpipes in new buildings in accordance with this standard.

Exceptions:

I. Only one operational standpipe need be provided on each floor in a building under construction.

2. In periods of freezing weather when the building is not heated, the standpipes shall be dry with the f i re pumps placed in manual operation.

3. Fire pumps may be temporar i ly melted and wi red. "

Supporting Comment:

Clarification is needed regarding the instal- lation of standpipes in buildings under construc- tion. The committee may want to consider revision of the entire Chapter 8 to more clearly express the intent of Chapter 8 regarding temporary stand- pipe protection for buildings under construction.

Committee Action:

Hold for future agenda.

Committee Comment:

This proposal constitutes new material.

This proposal constitutes new material.

55

Submitter:

Rolf Jensen, Rolf Jensen & Associates, Inc.

Statement of Problem:

While this section is intended to establish requirements for temporary standpipe protection in a building under construction, the intent is not clear.

56 Submitter:

Stephen J. G i l be r t , Chairman Fire Hose Committee

Statement of Problem:

Specification of Fire Hose Connection sizes are not in the scope of NFPA-14 but rather the scope of NFPA-194.

Recommendation:

8-I. I .5

Reference to non-standard threads should be deleted. Revise 8-1.l.5 to read:

201

Page 25: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

14

8-1.1.5 All threads on hose connections shall conform to NFPA 194-1974 Standard for Screw Threads and Gaskets for Fire Hose Connections.

Supporting Comment:

NFPA-194-1974 Standard fo r Screw Threads and Gaskets fo r Fire Hose Connections and ANSI-181.1 do not a l low for threads other than the NH standard.

Committee Act ion:

Rejected.

Committee Comment:

Section A- I -5 .1 .2 is advisory only. The subject of hose smal ler than 1 I /2 in. is under ac t ive study by a subcommittee.

Committee Action:

Hold for future agenda.

Committee Comment:

This proposal constitutes new material.

58 Submitter:

Stephen J. Gi lbert, Chairman Fire Hose Committee

Statement of Problem:

57

Submitter:

John Wolfanger, Captain, Shasta Lake Fire Department

Statement of Problem:

Hose smaller than 1 I/2" (37MM) is not designed for use in a hose reel, pack, or other approved devices as indicated in Standard 14 and since such equipment is not l is ted for f i re f ighting use by a nationally recognized testing agency this appendix section should be dropped from this standard.

Recommendation:

A- I -5 ,1 .2

Delete Appendix sect ion A- I -5 .1 .2 in i t ' s en t i r e t y .

Supporting Comment:

Fire hose placed in service on hose reels and semi automatic hose racks are designed by the manufacturer fo r long term service. This hose is tested and approved in accordance wi th the standards of na t i ona l l y recognized tes t ing agencies. These manufacturers have inp lan t inspect ion agencies to insure the performance in an emergency s i t ua t i on . This standard covers the i n s t a l l a t i o n of standpipe and hose systems fo r bu i ld ings and st ructures based upon sound engineering p r i nc i p l es , t es t data and f i e l d experience.

Spec i f i ca t ion of Fire Hose Connection sizes are not in the scope of NFPA-14 but ra ther the scope of NFPA-194.

Recommendation:

A-3-4.1

Reference to non-standard threads should be deleted. Revise A-3-4,1 to read:

A-3-4.1 Where a standpipe system is supplied by f i r e pump, one 2,5-7.5 NH male ou t l e t fo r each 250 gal lons per minute (946 I /min) pump capaci ty may be provided in the form of a wall ou t l e t at the ground level from which the f i r e department may take water fo r use on exposing f i r e s . Each o u t l e t should be con t ro l led by a seperate valve and should be proper ly capped when not in use.

Supporting Comment:

NFPA-194-1974 Standard fo r Screw Threads and Gaskets fo r Fire Hose Connections and ANSI-181.1 do not a l low for threads other than the NH standard.

Committee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

This proposal const i tu tes new mater ia l .

202

Page 26: r e c h n i c a I - NFPA...1 gal. = 3.785 dm 3 I psi = 6894.757 Pa 1 psi = 0.0689 bar 1 bar = 105 Pa For additonal conversions and information see ANSI Z210. I-1973, Metric Practice

Ed i to r i a l Correct ions - NFPA 14

Delete "7 - I . 3 New Underground Pipe".

Change 7-1.3.1 to 7-1.3 and add "underground" a f t e r "new" in f i r s t l i ne .

Change 7-1.3.2 to 7-1.3.1 and change " in" to " i s o l a t i n g " in t h i rd l i ne .

14

I S u b m i t t e r :

Patrick E. Phillips, Signaling Systems Correlating & Detection Devices

Statement of Problem:

The t i t l e is "Propr ie ta ry Supervisory Service Systems" but the word "Propr ie tary" is not def ined w i th in the standard. A d e f i n i t i o n is shown in NFPA 72D "Propr ie tary Protect ive Signal ing Systems" but fo r your purpose, i t is not cor rect . Also you do not c i t e NFPA 71. I bel ieve you wish to describe e l e c t r i c a l devices fo r Gate Valve Posi t ion Supervision (See NFPA 71 para 3-4.3.2, or 72A 3611 of the 1974 vers ions. )

Recommendation:

6-6

Delete the word "Proprietary" in the t i t l e and f i rs t sentance. Correct closing citation to read

NFPA 71 Central Stat ion Protect ive Signal ing Systems 1974

NFPA 72A Local Protect ive Signal ing Systems 1975

NFPA 72B, Aux i l i a r y Protect ive Signal ing Systems 1975

NFPA 72C Remote Stat ion Protect ive Signal ing Systems 1975

NFPA 72D Proprietary Protective Signaling Systems 1975

Supporting Comment:

Para 6-6 is technically not correct and is incomplete as presently written.

Committee Act ion:

Accepted in part. An editorial change has been I made in 6-6 by adding "(See standards listed in

6-4)" and deleting "(NFPA 72A through D)" and the balance is held for future agenda.

Committee Comment:

The mater ia l other than the e d i t o r i a l par t const i tu tes new mater ia l .

26 PART II

2 Submitter: Bob Straley, Public Servant

Statement of Problem:

Sprinkler Systems can be rendered in effective by incidents of vandalism, accidents, or small fires which only affect one or two sprinklers out of a complete system.

Recommendation:

7-3

7-3 Whenever possible emergency individual sprinkler shutoffs should be available for tempor- ary use in case. of accidents, vandalism, or small f i re situations. This allows the sprinkler system to remain primed and effective while arrangements can be made to replace expended sprinkler heads. This also has the additional advantage of limiting the necessary access to locked sprinkler shut off valves to only those in charge of f i re protection and allows anyone else to correct an errant sprinkler without significantly reducing the effectiveness of the sprinkler system.

Supporting Comment:

My 15 years experience with the Alhambra Fire Department has convinced me of the need to pay more attention to situations which can disable a sprinkler system. In public places i t is often impossible to immediately replace an errant sprinkler head, therefore, the whole sprinkler system is disabled and i t ' s protection lost until repairs can be conviently accomplished. This Situation must be avoided i f sprinkler systems are to be relied upon for public safety.

Committee Act ion:

Hold fo r fu ture agenda.

Committee Comment:

This proposal const i tu tes new mater ia l . The Committee feels that th is mater ia l is more app l ica- ble in NFPA 13E, Recommendations fo r Fire Depart- ment Operations in Properties Protected by Sprinkler Systems, and wil l be considered at the time of the next revision.

203


Recommended