NTPC DOCUMENT NO - 9396-001-PVC-740 BHEL DOCUMENT NO - 4-726-25-33-108 BARAUNI THERMAL POWER STATION - R&M 2x110MW (BIHAR) Bharat Heavy Electricals Limited BHOPAL Scope of this Design Document Covers Design of CABLE TRENCH for Unit No -7 For Barauni Revision R1 Revised as per revise E.S.P. cable trench layout drawing Scope of this Design Document Covers Design of CABLE TRENCH for Unit No -7 For Barauni Thermal Power Station Bihar - (R&M) CONSULTANT STEAG ENERGY SERVICES (INDIA) PVT. LTD. DESCRIPTION OWNER BIHAR STATE ELECTRICITY BOARD OWNER CONSULTANT NTPC LIMITED CLIENT BHARAT HEAVY ELECTRICALS LIMITED, BHOPAL
Transcript
Page 1: (r1) Design Document No - 4-726-25!33!108 e.s.p. Control Room.xls

NTPC DOCUMENT NO - 9396-001-PVC-740

BHEL DOCUMENT NO - 4-726-25-33-108

BARAUNI THERMAL POWER STATION - R&M 2x110MW (BIHAR)

Bharat Heavy Electricals Limited

BHOPAL

Scope of this Design Document Covers Design of CABLE TRENCH for Unit No -7 For Barauni

Revision

R1Revised as per revise E.S.P. cable trench layout

drawing

Scope of this Design Document Covers Design of CABLE TRENCH for Unit No -7 For Barauni

Thermal Power Station Bihar - (R&M)

CONSULTANT STEAG ENERGY SERVICES (INDIA) PVT. LTD.

DESCRIPTION

OWNER BIHAR STATE ELECTRICITY BOARD

OWNER CONSULTANT NTPC LIMITED

CLIENT BHARAT HEAVY ELECTRICALS LIMITED, BHOPAL

Page 2: (r1) Design Document No - 4-726-25!33!108 e.s.p. Control Room.xls

Design of Compressor Foundations and Strengthening Beams for Unit No -6 7For Barauni Thermal Power Station Bihar

1.0.1 Units of Measurement

S.no.

1

S.no.

1

2

3

4

3.0 Loads

Reinforced Concrete 25 kn/m^3

Soil 16 kn/m^3

Geo-technical Investigation Report of M/S Ground Geotechnics Pvt Ltd Submitted by Bhel Bhopal.

3.0.1 Dead Load

Dead load includes the weight of all structural components and other permanently applied external loads. Self-wt. of materials is

calculated on the basis of unit weights given below.

IS : 456 -2000 Plain and Reinforced concret code of practice

SP : 16 - 1980 Design aids for reinforced concrete to IS: 456-1978

IS :800 -1984 Code of Practice for General construction in steel

2.0.2 Codes, Standards and References

Reference Document No Document description

Input Drawing no Input Drawing name

BHEL input drawing no - A3 -726 - 19 - 33 -142 Control room layout for E.S.P.

1.0 INTRODUCTION

Scope of this Design Document Covers Design of E.S.P. CONTROL ROOM Cable trench foundation & structure

Units of measurement used in design shall be of SI or Metric system.

2.0 REFERENCE DRAWING & DOCUMENT

For the arrangement and design of cable trench foundation, following standards and documents have been refered : -

2.0.1 Reference Drawing

Page 1

Soil 16 kn/m^3

The steel reinforcement shall be deformed high yield strength bars of Fy = 415 N/mm2 conforming to IS: 1786

4.0.2 Concrete

Grade M 25 (having concrete cube compressive strength at 28 days of 30 N/mm2) conforming to IS: 456).

4.0 Material

4.0.1 Reinforcement

Page 1

Page 3: (r1) Design Document No - 4-726-25!33!108 e.s.p. Control Room.xls
a.negi
Typewritten Text
INPUT DRAWING
Page 4: (r1) Design Document No - 4-726-25!33!108 e.s.p. Control Room.xls

M 25

Fe 415

25 kn/m^3

25 kn/m^2

18 kn/m^3

9.81 kn/m^3

8.19 kn/m^3

0.5

20 kn/m^2

1.5 m

2 m

0.3 m

1.575 m

(a)

1 m

1.5

DESIGN OF CABLE TRENCH R.C.C. WALL

DESIGN DATA

Grade of concrete =

Grade of reinforcement steel =

Unit weight of concrete =

Allowable compressive strength of concrete =

For earth pressure

Clear height of cable trench (h) =

Clear width of cable trench =

Thickness of base slab =

Height of wall from top of bottom slab =

Bending moment Calculation

Case -1 ANALYSIS AND DESIGN OF TRENCH WALL FOR SATURATED CONDITION

Dry density of soil =

Density of water =

Submerged density of soil =

Coefficient of earth pressure at rest Ko =

Surcharge on back fill conisdered Fs =

Detail of cable trench

1

Pe = 10.125 kn

0.5 m

0.3 13.50 kn/m^2

13.50 kn/m^2

10.13 kn

5.06 kn-m

(b)

1.5 m

Ps = 15 kn

0.3 m Ko x Fs = 10 kn/m^2

Ko x γsub soil x h =

Earth Pressure at Rest = (Ko x γsub soil x h) =

Lateral force due to eart pressure ( 0.5 x h x Ko x γsub soil x h) =

Bending moment at base due to earth pressure Mep = Pe x 0.50 =

For surcharge

0.75 m

0.75 m

1

Page 5: (r1) Design Document No - 4-726-25!33!108 e.s.p. Control Room.xls

10 kn/m^2

15 kn

11.25 kn-m

(c )

3.96 Kn-m

3.96 Kn-m

3.97 Kn-m

11.88 Kn-m

28.20

28.20 kn-m (unfactored bending moment)

110.72 mm

165.72 mm

142 mm

0.2 %

284 sqmm

28.195 kn-m (unfactored bending moment)

2.10

0.653

927.26 sqmm

Check for minimum steel requirement

Calculate Area of Steel (Main Steel near soil face)

Pt Required for Ku 2.097 =

Area of steel required =

Minimum pt =

Ast = (0.2 x 1000 x 105)/100 =

Bending moment at bottom of wall =

Ku = (1.5 x B.M)/(b x d2) =

Wall shall be design per m width

Bending moment at bottom of wall =

Teff = SQRT( 1.5 X B.M.X)/(0.138 x Fck x b) =

Total thickness = (110.72 + 50 + 5) =

Provided thickness of wall 200 mm is more then the reqiuired

Provided effective thickness of wall = (200-50-8) =

Bending moment due to cable tray-1 = ((3.5 x 0.820) + (3.5 x 0.310)) =

Bending moment due to cable tray-2 = ((3.5 x 0.820) + (3.5 x 0.310)) =

Bending moment due to cable tray-3 = ((3.5 x 0.820) + (3.5 x 0.310)) =

Total Bending Moment due to cable tray & cable dead load (Mc) =

Check for thickness of wall

Total bending moment at bottom of wall = (Me+Ms+Mc) = (5.86+11.25+11.88) =

Earth Pressure due to surcharge (Ko x Fs) =

Lateral force due to surcharge ( hxKoxFs ) =

Bending moment at base due to surcharge Ms = Ps x 0.75 =

Bending moment due to cable tray load

2

927.26 sqmm

0.2 %

284 sqmm

(a)

1.5 m

Pe = 4.6069 kn

6.14 kn/m^2

6.14 kn/m^2

4.607 kn

2.30 kn-m

Earth Pressure at Rest

Earth Pressure at Rest (Ko x γsub soil x h) =

Bending moment at base due to earth pressure Mep = Pe x 0.50 =

Lateral force due to eart pressure ( 0.5 x h x Ko x γsub soil x h) =

PROVIDED REINF. STEEL AT 10T @ 170 MM C/C (Provided Ast = 462 > 310.0 sqmm )

Case -2 ANALYSIS AND DESIGN OF TRENCH WALL FOR SUBMERGE CONDITION

For earth pressure

1.0 m

0.50 m

0.3 m Ko x γsub soil x h =

Area of steel required =

PROVIDED REINF. STEEL AT 16T @ 170 + 10t @ 170 Upto height 0.8m from top of base

slab MM C/C (Provided Ast =1644 >927.26sqmm )

Distribution steel on wall face away from soil

Minimum pt =

Ast = (0.2 x 1000 x 105)/100 =

2

Page 6: (r1) Design Document No - 4-726-25!33!108 e.s.p. Control Room.xls

(b)

0.75 m

1.5 mPs = 15 kn

0.75

Ko x Fs = 10 kn/m^2Surcharge

10 kn/m^2

15 kn

11.25 kn-m

(C)

1 m

Lateral force due to surcharge ( hxKoxFs ) =

Bending moment at base due to surcharge Ms = Ps x 0.75 =

For water pressure

For surcharge

0.3 m

Earth Pressure due to surcharge (Ko x Fs) =

3

1 m

1.5 m

Pw = 11.036 kn

0.5 m

h x γw0.3 m

14.72 kn/m^2

11.04 kn

5.79 kn-m

(c )

3.96 Kn-m

3.96 Kn-m

3.96 Kn-m

11.87 Kn-m

31.212

31.21 kn-m (unfactored bending moment)

116.49 mm

174.49 mm

142 mm

Provided thickness of wall 200 mm is more then the reqiuired

Provided effective thickness of wall = (200-50-8) =

Check for thickness of wall

Total bending moment at bottom of wall=(Mep+Msp+Msw+Mc)= (2.30+11.25+ 5.79+11.87) =

Wall shall be design per m width

Bending moment at bottom of wall =

Teff = SQRT( 1.5 X B.M.X)/(0.138 x Fck x b) =

Total thickness = (116.49 + 50 + 8) =

Bending moment at base due to water pressure Mw = Pw x 0.50 =

Bending moment due to cable tray load

Bending moment due to cable tray-1 = ((3.5 x 0.820) + (3.5 x 0.310)) =

Bending moment due to cable tray-2 = ((3.5 x 0.820) + (3.5 x 0.310)) =

Bending moment due to cable tray-1 = ((3.5 x 0.820) + (3.5 x 0.310)) =

Total Bending Moment due to cable tray & cable dead load (Mc) =

Water pressure

Water Pressure (h x γw) =

Lateral force due to water ( 0.5 x Ko x γw x h) =

3

Page 7: (r1) Design Document No - 4-726-25!33!108 e.s.p. Control Room.xls

Minimum pt = 0.20 %

Ast = (0.2 x 1000 x 105)/100 =284.00 sqmm

31.21 kn-m (unfactored bending moment)

2.32

0.743

1055.06 sqmm

Minimum pt = 0.20 %

Ast = (0.2 x 1000 x 105)/100 =284.00 sqmm

82.50 Kn

75.00 Kn

81.00 Kn

70.00 Kn

21.00 Kn

329.50 Kn

29.95 Kn/sqm

Distribution steel on wall face away from soil

(b) For 1700 mm wide cable

Bending moment at bottom of wall =

Ku = (1.5 x B.M)/(b x d2) =

Pt Required for Ku 2.32 =

Area of steel required =

PROVIDED REINF. STEEL AT 16T @ 170 + 10t @ 170 Upto height 0.8m from top of base

slab MM C/C (Provided Ast =1644 > 601.4 sqmm )

Calculate Area of Steel

Check for minimum steel requirement

BEARING PRESSURE CHECK

(a) For 1200 mm wide cable

(i) Self weight of base slab = (25 x 2.2 x 5 x 0.3) =

(ii) Self weight of wall = (25 x 0.2 x 1.5 x 5 x 2) =

(iii) Back fill weight = (18 x 0.3 x1.5 x 5 x 2) =

(iv) cable tray weight = (3.5 x 5 x 4) =

(v) EC Panel load = (7 x 3) =

Total Weight =

Bearing Pressure = (329.50/(2.2 x 5) =

PROVIDED REINF. STEEL AT 10T @ 170 MM C/C (Provided Ast =461.95 sqmm > 310.0 sqmm )

4

101.25 Kn

75.00 Kn

81.00 Kn

105.00 Kn

50.50 Kn

412.75 Kn

30.57 Kn/sqm

112.50 Kn

75.00 Kn

81.00 Kn

105.00 Kn

373.50 Kn

24.90 Kn/sqm

(a) 16.5 KN

(b) 15 KN

(d) 16.2 KN

(e) 6 KN

53.7 KN

39.60 KN

1.36 < 1.2

Cable tray load = ( 2 x 3 ) =

Factor of safety against uplift = (down ward load)/(upward load) =

Uplift Check for 1200 m width cable trench

Weight of base slab = (25 x 2.2 x 0.3 x 1) =

Weight of Trench r.c.c. wall (25x1.50x0.2x1x2) =

Weight of soil back fill = (18x0.3x1.50x1x2) =

Total downward pressure =

Total Upward pressure (10x2.2x1.80x1) =

CHECK FOR UPLIFT

TOTAL UPWARD LOAD / M WIDTH

Total Weight =

Bearing Pressure = (373.50/(3.0 x 5) =

(i) Self weight of base slab = (25 x 3.0x 5 x 0.3) =

(ii) Self weight of wall = (25 x 0.2 x 1.5 x 5 x 2) =

(iii) Back fill weight = (18 x 0.3 x1.5 x 5 x 2) =

(iv) cable tray weight = (3.5 x 5 x 6) =

(b) For 1700 mm wide cable

(i) Self weight of base slab = (25 x 2.7 x 5 x 0.3) =

(ii) Self weight of wall = (25 x 0.2 x 1.5 x 5 x 2) =

(iii) Back fill weight = (18 x 0.3 x1.5 x 5 x 2) =

(iv) cable tray weight = (3.5 x 5 x 6) =

(v) LTMSB Panel load = (50.5 kn as per E.S.P. trench

layout drawing) =

Total Weight =

Bearing Pressure = (412.75/(2.7 x 5) =

(c) For 2000 mm wide cable

4

Page 8: (r1) Design Document No - 4-726-25!33!108 e.s.p. Control Room.xls

(a) 20.25 KN

(b) 15 KN

(d) 16.20 KN

(e) 8.00 KN

59.45 KN

48.60 KN

1.22 < 1.2

22.5 KN

15 KN

16.20 KN

12.00 KN

65.70 KN

54.00 KN

1.22 < 1.2

300 mm

50 mm

5 mm

245 mm

Rb Rd

Cable tray load = (2 x 4) =

Weight of Trench r.c.c. wall (25x1.50x0.2x1x2) =

Weight of soil back fill = (18x0.3x1.5x1x2) =

Total downward pressure =

Total Upward pressure (10x3.0x1.80x1) =

Factor of safety against uplift = (down ward load)/(upward load) =

Cable tray Load = (2.0 x 6) =

Total downward pressure =

Total Upward pressure (10x2.7x1.80x1) =

Factor of safety against uplift = (down ward load)/(upward load) =

Weight of base slab = (25 x 3.0 x 0.3 x 1) =

Uplift Check for 2000 m width cable trench

Uplift Check for 1700 m width cable trench

Weight of base slab = (25 x 2.7 x 0.3 x 1) =

Weight of Trench r.c.c. wall (25x1.50x0.2x1x2) =

Weight of soil back fill = (18x0.3x1.50x1x2) =

Overall depth of base slab =

Clear cover =

Dia of bar =

Effective depth of base slab =

Design of base slab

5

B D E

A

C

50 kn/m

0.4 2.2 0.4

150.00 Kn

75 Kn

4 Kn-m

-26.25 Kn-m

At support

4.00 kn-m

0.10

0.08 % < Minimum pt 0.12%

0.12 %

294.00 sqmm

26.25 kn-m

0.66

0.186% < Minimum pt 0.12%

0.186 %

455.7 sqmm

0.19 %

Reinforcement calculation

Bending moment at support =

Pt required for Ku (0.84) =

Reaction calculation

Bending moment at span =

Ku = (Mu/bd^2) =

Pt Provided =

Ast required =

Ast Provided 10 @170c/c both way at top (Provided ast = 461.95 sqmm > 294 sqmm)

Ku = (Mu/bd^2) =

Pt required for Ku (0.06) =

Ast Provided 10 @170c/c both way at bottom (Provided ast = 461.95 sqmm > 455.7 sqmm)

Provided Pt =

Rb = Rd = ( 50 x 3.0)/2 =

Bending moment calculation

B.M. at B = (50 x 0.4 x 0.4 x 0.5) =

B.M. at C = (50x1.5x1.5x0.5)-(75x1.1) =

Pt Provided =

Ast required =

Rb + Rd = ( 50 x 3.0) =

At Mid span

5

Page 9: (r1) Design Document No - 4-726-25!33!108 e.s.p. Control Room.xls

(A.3) Check for shear

(A.3.1)

15.00 kn

15.00 kn

0.09 N/sqmm

0.29 N/sqmm

τv < τc (Hence provided depth is ok in shear)

(A.3.2)

-37.75 kn

0.23 N/sqmm

0.29 N/sqmm

At cantilever face

τv < τc (Hence provided depth is ok in shear)

τc (Permissable shear stress of concrete for Pt (0.09%)

At a distance 0.3381 m from point A

(Unfactored shear force at support)Shear force at A = (50 x 0.30) =

Maximum design shear force at Support A (V) =

τv (Design shear stress) = (V/bd) =

Maximum design shear force at distance of (0.3+0.2+0.245) = 0.745 m from point A (V) =

τv (Design shear stress) = (V/bd) =

τc (Permissable shear stress of concrete for Pt (0.19%) =

66


Recommended