Why Electrify the railway?
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT4
› Nørreport station Monday morning in a very polluted atmosphere due to diesel trains -> solution electric trains
› Ålborg airport a Tuesday morning – the plane is cancelled due to fog -> solution electrification as more efficient system than diesel
› Copenhagen Hamborg in 2 hours and 46 minutes from centre to centre -> electrification
› Reduction of CO₂ -> Electrification
› Efficient use of wind energy -> Electrification
› Urbanisation – Stop getting bad lungs -> Electrification
› Goods on rail in a clean manner -> Electrification
› Diesel train are harder and more expensive to buy as less are made due to more demand for electrical trains
› and many more good reasons
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT5
Urbanization results in many electrical systems that
might interact wrongly
Since 2013 more people lives in cities than in the countryside world wide – this will NEVER change back
Agenda
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT6
› Electrification systems (slide 7-11)
› Earthing and bonding – E&B (slide 12-20)
› Stray currents (Slide 21-24)
› Protection (Slide 25-32)
› Electromagnetic interference – EMI (Slide 33-34)
› Immunization (Slide 35 – 46)
› Return circuit modelling (Slide 47 – 55)
FAR TOO MANY SLIDES -> I will jump in the slides so it fit with the half an hour–Sorry about that
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT7
Electrification Principle -What are the differences in generations?
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT8
Electrification Principle– Generation AReturn circuit via running rails
Stray Currents
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT9
Electrification Principle– Generation BReturn circuit via running rails and return conductor
Stray Currents
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT10
Electrification Principle– Generation CBooster transformer system
Stray Currents
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT11
Electrification Principle– Generation DAuto-transformer system (AT)
Stray Currents
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT12
Why AT system is smart?
Exploiting circular currents at section with train and lower currents from substation to train.
Lower interference with adjacent lines due to low currents and feed from two AT's
400 A to train
200 A delivered
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT13
Earthing and bonding
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT14
Principle - Return circuit and E&B of DC traction systems
Strive to have an isolatedreturn system – "nothing is
connected to rail"
Principle - Return circuit and E&B of AC traction systems
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT15
Strive to have an open returnsystem – "everything is
connected to rail"
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT16
Earthing and bonding on stations – DC railway
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT17
Earthing and bonding of structures – AC railway
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT18
E&B of level crossing – DC railway
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT19
Example of E&B system – VLD not shown
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT20
Why E&B of DC light rail is sometimes connected to E&B for AC heavy rail? Danger to humans
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT21
Stray currents
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT22
DC train systems where return current runs in unplanned path's due to lower impedance than return conductor and return rail.
Corrosion of parallel pipes, reinforcement in tunnels etc.
...or caused by malfunctioning
cathodic protection, high
voltage DC, welding, and
other electrical driven
mechanisms.
2e-+ 2H2O H2 + 2OH
-
Stray currents corrosion principle
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT23
Steel
Cathode 4e-+ 2H2O + O2 4OH
-
Anode
Fe2+ + 2e-
Fe
iCorrosion
VOLTAGE GRADIENT
x Volts y Volts
Incomingcurrent
OUTGOINGCURRENT
i
2Cl-
2e-+ Cl2
4OH-
4e-+ 2H2O + O2
Fe 2e-+ Fe2+
Stray current - example
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT24
Corrosion wherecurrent leaves pipe
Stray current - example
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT25
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT26
Using E&B to protect sensitive structures against straycurrent driven corrosion?
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT27
Using E&B to protect sensitive structures against straycurrent driven corrosion?
Using Cathodic protection to protect against straycurrent – basic principle
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT28
rein
forc
em
ent
concrete
Cl-
Cl-
Cl-
Cl-
refe
ren
ce
ele
ctr
od
e
e-
e-
e-
e-
mV
Cl-
Cl-
anode
e-e-e-
e-
+
Cathodic protection – basic principle
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT29
Pourbaix diagram for iron in water solution (25oC, 1 atm)
Primary effect of cathodicprotection:Change of potential to more negative values
pH
PITTINGCORROSION
PASSIVE
IMMUNE
Pote
ntiale
, V
CORROSION
water separation
2H2O + 2e- H2 + 2OH-
hydrogen development
Cathodic protection - History
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT30
1824 20151900 1973 1987 2003
Sir Humphrey Davy discovers cathodic protectionwith sacrificialanode. The method is used for protection of subsea metal parts on ships.
The method is spread to pipelines in soild. As the electrical impedancein soil is too highthe methoddevelops to chatodicprotection with added current.
Richard Stratfulluses the method for reinfoced concretconstructions. He uses silicium metal anodes covered with a layer of conductiveasphalt.
The firstinstallations in Denmark.
The Vejdirektoratet accepts cathodicprotection as a repair and operations method.
Cathodic protectionof reinforcedconcreteconstrcution is common practise.
Today we have more than 25 years experience with cathodic protection in Denmark.
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT31
Cathodic protection - background
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT32
3
1
5
rein
forc
em
ent
co
ncre
te
6
2
7
3
3 +4
transformer/inverter
board
1. Reinforcement steel
2. Anode system
3. Cabels
4. Transformer/inverter
5. Reference electrode
6. Control system and datalogger
7. Remote control
Catodic protection is an electric repairmethod, where corrosion of the reinforcement steel is stopped by adding an electric current between the reinforcementand an anode system via a transformer/inverter connected to public supply.
Cathodic protetction as a repair strategy
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT33
Initialization Propagation
CO2, Cl-
Time
Expected life/time to repair Increase of lifetime
Accept
Lífe time for cathodic protection
1 2
3
EMI – Electromagnetic interference
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT34
Victims can be:- People living i houses nearby- Hospitals (sensitive equipment)- Laboratory equipment- Dentists and specialist doctors
EMI – Electromagnetic interference
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT35
Immunization of systems along the track
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT36
Example of study:Will immunisation of Banedanmarksignalling equipmentbe necessary due to establishment of Århus lightrail?
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT37
Stray Currents and immunization study usingsimulation – ABACUS tool
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT38
Two trains accelarating
Stray Currents / Immunisation – Electrical properties of soil
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT39
Soil resistivity
Stray Currents / Immunisation
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT40
FE model
Stray Currents / Immunisation
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT41
FE model
Stray Currents / Immunisation
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT42
Two VLD open – local isolation fault
Stray Currents / Immunisation
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT43
Two VLD open – local isolation fault
Stray Currents / Immunisation
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT44
Two VLD open – local isolation fault
+ 2.94e +01+ 5.00e +00+ 4.58e +00+ 4.17e +00+ 3.75e +00+ 3.33e +00+ 2.92e +00+ 2.50e +00+ 2.08e +00+ 1.67e +00+ 1.25e +00+ 8.33e -01+ 4.17e -01+ 0.00e +00- 1.06e -01
Stray Currents / Immunisation
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT45
Two VLD open – local isolation fault
Stray Currents / Immunisation
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT46
Overall result
Stray Currents / Immunisation
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT47
OPERATIONAL SITUATION PMAX DPMAX DPMAX
500
DPMAX
1000
1 Two VLD open (normal
operation)
1,4 V 0,26 V 1,1 V 1,3 V
2 Aarhus VLD closed 1,2 V 0,2 V 0,9 V 1,2 V
3 Two VLD closed, local
isolation fault
2,9 V 0,74 V 2,54 V 2,82 V
4 Aarhus VLD closed,
local isolation fault
2,5 V 0,6 V 2,2 V 2,5 V
5 Two VLD open rail
conductivity 600 S/km
0,1 V 0,2 V 0,2 V 0,2 V
6 Aarhus VLD closed, rail
conductivity 600 S/km
0,9 V 0,1 V 0,2 V 0,2 V
WORST CASE –
classical track joint based
signalling will malfunction
around 1 V and higher.
I.e. immunisation
is necessary.
Overall result
Modelling used for return circuit issues – OPN tool
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT48
Establishing the model
Slice modelling including EMI coupling effects
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT49
Sequence of slides
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT50
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT51
Magnetic flux densityExample using OPN
Maximum return cable current
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT52
0
200
400
600
800
1000
1200
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
SP WU dir.
ATS WU dir.
ATS GUA dir.
SP GUA dir.
MAX.
CU
RREN
T [
A]
SECTION NO.
Short circuit current study
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT53
0
2000
4000
6000
8000
10000
12000
14000
16000
18000
20000
1961 1971 1981 1991 2001 2011
ISOLATOR AT INFEED SHORT CIRCUIT CURRENT
SHORT CIRCUIT POSITION (KM)
MAX.
CU
RREN
T [
A]
Maximum rail earth potential study
17 MAJ 2016
ELECTRIFICATION – RETURN CIRCUIT54
0
20
40
60
80
100
120
140
160
180
1961 1971 1981 1991 2001 2011
ISOLATOR
LR U LEBC Up
RR U LEBC Up 2
AT
LR U LEBC Up 2
RR U LEBC Up 3
Infeed
LR U LEBC Up 3
URE max
RR U LEBC Up
VO
LTAG
E [
V]
POSITION (KM)
78 V
Example of simulation of AT system