Range Size CF Voltage (V) Charger (A) Battery (Ah) Options
330 445 645
645P
12
5 10 20 30
7 14 24 40 48 80
B C D F J
RC S V
330 445 645
645P
24
5 10 20 30
7 14 24 40 48
445 645
645P
2.5 5
10 15
7 14 24
CF330 300 x 333 x 203**
CF445 450 x 497 x 253**
CF645 600 x 497 x 253**
CF645P 686 x 497 x 253**
** Dimensions HWD
•
•
•
•
•
•
•
•
•
DELTA 600 DELTA 300 Bottom View
L N
230Vac
ALPHA 900 CE-P
0 230
•
•
•
•
•
•
•
AGATE / 1082
Diode de couplage
AGATE
1082
RE1
RE2
RE3
Distribution 4 départs
•
•
•
•
• o o
o
•
• o o o
• o
AGATE
1082
RE1
RE2
RE3
Green
Yellow Red
Reset
•
•
•
•
(1): In case of option V: Display (2): In case of option B: Battery test
•
•
•
•
In In
2*In
In/2 In/2
In
Thermostat Data Hysteresis 7 K (± 4 K tolerance)
Operating Temperature -45 to +80°C
Setting Ranges 0 to +60°C
Feeler Element Bimetal
•
•
•
•
•
o o o o o o o o o
•
•
• ☺
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Charger Type CE-P DELTA 300 DELTA 600 ALPHA 900
Voltage (floating / boost) at 20°C 12V 24V 48V
13.6 / 14.1Vdc 27.3 / 28.3Vdc 54.5 / 56.6Vdc
13.6 / 13.8Vdc 27.3 / 27.6Vdc 54.5 / 55.2Vdc
Current 12V 24V 48V
5A 5A 2.5A
10A 10A 5A
20A 20A 10A
30A 30A 15A
Output voltage tolerance 1% (mains present and battery charged)
RMS ripple ratio < 0.2%
Efficiency (typical) > 85%
Calorific dissipation (w/o option D and RC) 18W 37W 74W 110W
Mains supply Voltage 230 Vac (187Vac to 264Vac)
Frequency 50/60Hz (47Hz to 63Hz)
Power 200VA 470VA 670VA 1000VA
Recommended upstream protection 6A-C
Battery Type Valve regulated lead acid battery : VRLA
Capacity C10 12V 24V 48V
7 to 48Ah 7 to 48Ah 7 to 24Ah
7 to 80Ah 7 to 48ah 7 to 24Ah
14 to 80Ah 14 to 48Ah 7 to 24Ah
24 to 80Ah 24 to 48Ah 14 to 24ah
Backup time at 20°C T = Function (Idc/C) With : Idc = Output current C10 = Battery capacity Example : Max permanent current: I charger = 5A C10 = 7Ah Idc = I charger – I battery recharge Idc = 5 – 7/10 = 4,3A Approximate backup time duration:
Idc/C10 = 4,3/7 0,6 T 30min (for max permanent current)
Protection FB (on AGATE 1082 card) Fuse 6.3x32 – MDA30R – 30A Tempo 250V 10kA
Output Voltage 12 / 24 / 48Vdc
Permanent current Idc max Idc = I charger – I batt. recharge (see example above)
Current peak 1s 50A max
Current peak 15s 2*C10 limited to 50A
Short circuit current 20*C10
Protection FU (on AGATE 1082 card) Fuse 6.3x32 – MDA30R – 30A Tempo 250V 10kA
Protection Insulation resistance 1 M (input/PE ; output/PE)
Dielectric strength input/PE 2300Vdc / 1min
Dielectric strength output/PE 500Vcc / 1min
Environment Storage temperature -5°C à +45°C
Running temperature 0 à +40°C
Assigned temperature 20°C 5°C
Spikes 15 ° C limited to one day to preserve the characteristics and life of the battery.
Altitude 0 - 1000m
Relative humidity < 95% at 20°C
Remote alarms NO/NC contact 1A – 250Vac – AC1
Standards Product standard NF C 58-311 : 03 / 1990
SELV Product NF C 15-100 : 09 / 2005
EMC Directive 2004/108/CE
LV Directive 2006/95/CE