AIR SOURCE HEAT PUMPSPLIT SYSTEM OUTDOORCONDENSING UNITSPAIRED WITH MATCHEDAIR HANDLER
RCH-SERIES
RATED IN ACCORDANCE TO ANSI/AHRI STANDARDS 210/240 - 2008 OR 340 / 360 - 2007
DIMENSION AND SELECTION GUIDE
2
PE
RF
OR
MA
NC
E
DA
TA
NET COOLING
Total Capacity (Btu/h) 42,700Sensible Capacity (Btu/h) 38,592
Electric Power (W) 2,716Leaving Air Temperature (°F db / °F wb) 63.1 / 61.0
Energy Efficiency Ratio (EER) 13.7Integrated Energy Efficiency Ratio (IEER) 16.3
Nominal Airflow (CFM) 2,000
HEATINGTotal Capacity (Btu/h) 39,000
Electric Power (W) 2,716Coefficient of Performance (COP) 4.1
EL
EC
TR
ICA
L D
AT
A
COMPRESSOR(S)
Qty-Nominal Tons-Type 1 - 2.8 - ScrollCapacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 230/1/60 208-230/3/60 460/3/60 575/3/60Run Load Amps (RLA) 16.7 10.4 5.8 3.8
Locked Rotor Amps (LRA) 79 73 38 37
CONDENSER FAN MOTOR(S)
Qty - Horsepower (HP) 1 - 1/2FLA (ea) 6.2 5.4 2.7 1.3
Type PSC
UNITUnit Minimum Circuit Ampacity 27.0 18.4 9.9 6.0
Max. Time Delay Fuse or HACR Breaker 40 25 20 10
ME
CH
AN
ICA
L D
AT
A
CONDENSER FAN(S)Airflow (CFM) 4,000
Diameter (in)-Pitch (deg) 24 - 36
CONDENSER COIL(S)
Quantity 2Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft.) 15.4Rows - Fins per Inch 4 - 12
REFRIGERANT CONNECTION(S)
Suction Line (in OD) 3/4 (Qty 1)Liquid Line (in OD) 3/8 (Qty 1)
Optional Hot Gas Bypass (in OD) 3/8 (Qty 1)Optional Hot Gas Reheat (in OD) 3/8 (Qty 1)
CABINET
Sheet Metal G90 GalvanizedFinish Polyester Coating
Top Pan Thickness (ga) 16Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
REFRIGERANT - R410A Charge based on 25' line set (lbs per circuit) 24
WEIGHTSUnit Weight (lbs) 560
Shipping Weight (lbs) 610
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 22 - 23.
UNIT DATA - RCH044 WITH HCH070 / VCH070RATED IN ACCORDANCE TO ANSI/AHRI 210/240-2008.
CO
OL
ING
CFMENTERING AIR TEMPERATURE (°F)
75 DB 80 DB 85 DB63 WB 67 WB 71 WB 63 WB 67 WB 71 WB 63 WB 67 WB 71 WB
1,600
Total Capacity (Btu/h) 36,605 39,175 41,667 37,653 38,910 41,538 39,997 40,090 41,459Sensible Capacity (Btu/h) 32,326 25,879 19,323 37,653 33,315 26,014 39,997 40,090 33,825
Electric Power (W) 3,060 3,073 3,072 3,040 3,029 3,077 3,064 3,054 3,077Leaving Air Temperature (°F db/°F wb) 56.6/55.3 60.4/59.5 64.1/63.8 58.6/55.0 61.1/59.5 65.3/63.7 62.2/54.5 62.2 / 59.2 65.9/63.7
1,800
Total Capacity (Btu/h) 37,117 39,268 42,019 38,738 39,405 41,753 41,157 41,262 42,500Sensible Capacity (Btu/h) 34,343 26,695 19,961 38,738 35,415 27,004 41,157 41,262 37,172
Electric Power (W) 3,060 3,030 3,081 3,043 3,028 3,081 3,073 3,061 3,087Leaving Air Temperature (°F db/°F wb) 57.7/56.1 61.6/60.4 65.0/64.6 60.4/55.8 62.2/60.3 66.5/64.5 64.1/55.3 64.2/59.9 66.4/64.4
2,000
Total Capacity (Btu/h) 37,566 39,585 42,405 39,654 39,864 42,270 42,172 42,252 43,169Sensible Capacity (Btu/h) 36,039 37,742 20,864 39,654 37,449 28,703 42,172 42,252 39,484
Electric Power (W) 3,054 3,028 3,086 3,047 3,032 3,084 3,075 3,067 3,064Leaving Air Temperature (°F db/°F wb) 58.6/56.4 62.5/61.0 65.6/65.2 61.9/56.4 63.0/60.9 67.1/54.2 65.8/55.9 65.8/60.5 67.2/65.0
NOTES: 1. Above performance assumes 95.0 °F db/75.0 °F wb ambient temperature and reflects gross capacities.
HE
AT
ING
CFM AMBIENT TEMPERATURE (°F)10 17 20 30 40 47 50 60
1,600Total Capacity (Btu/h) 20,463 22,754 24,248 29,642 36,687 36,927 38,459 44,865
Electric Power (W) 2,242 2,280 2,299 2,362 2,494 2,501 2,537 2,631
1,800Total Capacity (Btu/h) 20,532 22,917 24,393 29,835 36,982 37,199 39,619 45,225
Electric Power (W) 2,219 2,255 2,273 2,331 2,453 2,459 2,493 2,582
2,000Total Capacity (Btu/h) 20,630 23,046 24,512 29,992 37,219 37,422 39,741 45,754
Electric Power (W) 2,201 2,235 2,252 2,306 2,420 2,426 2,459 2,540
NOTES: 1. Above performance assumes 70.0 °F db/ 60.0 °F wb entering air temperature.
3
PE
RF
OR
MA
NC
E
DA
TA
NET COOLING
Total Capacity (Btu/h) 54,800Sensible Capacity (Btu/h) 45,352
Electric Power (W) 3,590Leaving Air Temperature (°F db / °F wb) 61.8 / 59.8
Energy Efficiency Ratio (EER) 13.3Integrated Energy Efficiency Ratio (IEER) 13.6
Nominal Airflow (CFM) 2,200
HEATINGTotal Capacity (Btu/h) 49,300
Electric Power (W) 3,717Coefficient of Performance (COP) 3.8
EL
EC
TR
ICA
L D
AT
A
COMPRESSOR(S)
Qty-Nominal Tons-Type 1 - 3.8 - ScrollCapacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 230/1/60 208-230/3/60 460/3/60 575/3/60Run Load Amps (RLA) 21.8 13.7 6.2 4.8
Locked Rotor Amps (LRA) 117 83 41 33
CONDENSER FAN MOTOR(S)
Qty - Horsepower (HP) 1 - 1/2FLA (ea) 6.2 5.4 2.7 1.3
Type PSC
UNITUnit Minimum Circuit Ampacity 33.5 22.5 10.5 7.3
Max. Time Delay Fuse or HACR Breaker 50 35 15 10
ME
CH
AN
ICA
L D
AT
A
CONDENSER FAN(S)Airflow (CFM) 4,000
Diameter (in)-Pitch (deg) 24 - 36
CONDENSER COIL(S)
Quantity 2Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft.) 15.4Rows - Fins per Inch 4 - 12
REFRIGERANT CONNECTION(S)
Suction Line (in OD) 7/8 (Qty 1)Liquid Line (in OD) 1/2 (Qty 1)
Optional Hot Gas Bypass (in OD) 3/8 (Qty 1)Optional Hot Gas Reheat (in OD) 3/8 (Qty 1)
CABINET
Sheet Metal G90 GalvanizedFinish Polyester Coating
Top Pan Thickness (ga) 16Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
REFRIGERANT - R410A Charge based on 25' line set (lbs per circuit) 24
WEIGHTSUnit Weight (lbs) 585
Shipping Weight (lbs) 635
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 22 - 23.
UNIT DATA - RCH054 WITH HCH070 / VCH070RATED IN ACCORDANCE TO ANSI/AHRI 210/240-2008.
CO
OL
ING
CFMENTERING AIR TEMPERATURE (°F)
75 DB 80 DB 85 DB63 WB 67 WB 71 WB 63 WB 67 WB 71 WB 63 WB 67 WB 71 WB
2,000
Total Capacity (Btu/h) 47,453 50,913 54,081 48,391 51,037 54,447 51,383 51,616 54,717Sensible Capacity (Btu/h) 39,794 32,163 24,645 48,391 41,910 33,626 51,383 51,086 43,696
Electric Power (W) 4,065 4,077 4,082 4,071 4,076 4,082 4,076 4,078 4,085Leaving Air Temperature (°F db/°F wb) 56.9/55.0 60.5/59.2 63.9/63.5 58.0/54.8 61.0/59.1 64.8/63.4 61.6/54.3 61.8/59.0 65.3/63.3
2,200
Total Capacity (Btu/h) 48,117 51,478 54,639 49,516 51,634 55,090 52,597 52,651 55,257Sensible Capacity (Btu/h) 42,082 33,456 25,584 49,516 44,029 33,309 52,597 52,651 45,948
Electric Power (W) 4,073 4,077 4,083 4,072 4,078 4,085 4,079 4,079 4,086Leaving Air Temperature (°F db/°F wb) 57.6/55.7 61.2/59.9 64.5/64.1 59.5/55.4 61.8/59.8 65.5/64.0 63.2/54.9 63.3/59.6 66.1/63.9
2,400
Total Capacity (Btu/h) 48,584 51,392 55,097 50,496 52,130 55,559 53,656 53,707 55,656Sensible Capacity (Btu/h) 43,934 34,703 26,491 50,496 46,102 36,697 53,656 53,707 47,880
Electric Power (W) 4,074 4,073 4,077 4,084 4,074 4,074 4,079 4,086 4,081Leaving Air Temperature (°F db/°F wb) 57.0/51.8 58.4/56.3 61.9/60.4 65.1/64.7 60.8/51.3 60.8/55.9 62.6/60.4 66.2/64.6 64.5/50.7
NOTES: 1. Above performance assumes 95.0 °F db/75.0 °F wb ambient temperature and reflects gross capacities.
HE
AT
ING
CFM AMBIENT TEMPERATURE (°F)10 17 20 30 40 47 50 60
2,000Total Capacity (Btu/h) 27,779 30,743 33,740 39,630 43,790 48,275 51,061 59,129
Electric Power (W) 2,941 3,006 3,041 3,157 3,282 3,351 3,380 3,491
2,200Total Capacity (Btu/h) 27,901 30,883 32,784 39,843 44,030 48,521 51,351 59,511
Electric Power (W) 2,918 2,979 3,011 3,121 3,237 3,304 3,330 3,429
2,400Total Capacity (Btu/h) 28,017 30,999 33,907 40,020 44,232 48,724 51,592 59,556
Electric Power (W) 2,898 2,956 2,984 3,090 3,200 3,266 3,288 3,382
NOTES: 1. Above performance assumes 70.0 °F db/ 60.0 °F wb entering air temperature.
4
UNIT DATA - RCH064 WITH HCH070 / VCH070RATED IN ACCORDANCE TO ANSI/AHRI 210/240-2008.
PE
RF
OR
MA
NC
E
DA
TA
NET COOLING
Total Capacity (Btu/h) 65,700Sensible Capacity (Btu/h) 53,294
Electric Power (W) 4,421Leaving Air Temperature (°F db / °F wb) 60.0 / 58.5
Energy Efficiency Ratio (EER) 13.0Integrated Energy Efficiency Ratio (IEER) 13.2
Nominal Airflow (CFM) 2,400
HEATINGTotal Capacity (Btu/h) 60,700
Electric Power (W) 4,382Coefficient of Performance (COP) 4.1
EL
EC
TR
ICA
L D
AT
A
COMPRESSOR(S)
Qty-Nominal Tons-Type 1 - 4.8 - ScrollCapacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 230/1/60 208-230/3/60 460/3/60 575/3/60Run Load Amps (RLA) 26.3 15.6 7.8 5.8
Locked Rotor Amps (LRA) 134 110 52 39
CONDENSER FAN MOTOR(S)
Qty - Horsepower (HP) 1 - 1/2FLA (ea) 6.2 5.4 2.7 1.3
Type PSC
UNITUnit Minimum Circuit Ampacity 39.1 24.9 26.3 8.5
Max. Time Delay Fuse or HACR Breaker 60 40 20 10
ME
CH
AN
ICA
L D
AT
A
CONDENSER FAN(S)Airflow (CFM) 4,000
Diameter (in)-Pitch (deg) 24 - 36
CONDENSER COIL(S)
Quantity 2Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft.) 15.4Rows - Fins per Inch 4 - 12
REFRIGERANT CONNECTION(S)
Suction Line (in OD) 7/8 (Qty 1)Liquid Line (in OD) 1/2 (Qty 1)
Optional Hot Gas Bypass (in OD) 3/8 (Qty 1)Optional Hot Gas Reheat (in OD) 3/8 (Qty 1)
CABINET
Sheet Metal G90 GalvanizedFinish Polyester Coating
Top Pan Thickness (ga) 16Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
REFRIGERANT - R410A Charge based on 25' line set (lbs per circuit) 26
WEIGHTSUnit Weight (lbs) 605
Shipping Weight (lbs) 655
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 22 - 23.
CO
OL
ING
CFMENTERING AIR TEMPERATURE (°F)
75 DB 80 DB 85 DB63 WB 67 WB 71 WB 63 WB 67 WB 71 WB 63 WB 67 WB 71 WB
2,200
Total Capacity (Btu/h) 57,517 61,349 65,198 58,216 61,648 65,684 61,595 62,158 65,933Sensible Capacity (Btu/h) 47,309 39,146 28,797 57,780 49,374 41,313 61,595 60,165 51,357
Electric Power (W) 4,955 4,994 5,031 4,962 4,998 5,038 4,997 5,001 5,041Leaving Air Temperature (°F db/°F wb) 55.5/54.1 58.8/58.4 63.2/62.7 56.1/54.0 59.7/58.3 63.1/62.6 59.4/53.4 60.2/58.1 63.9/62.5
2,400
Total Capacity (Btu/h) 55,486 59,130 62,696 56,445 59,269 63,233 59,805 60,153 63,429Sensible Capacity (Btu/h) 46,582 37,056 28,547 56,445 48,424 39,234 59,805 59,172 50,702
Electric Power (W) 4,934 4,969 5,005 4,947 4,972 5,012 4,982 4,985 5,016Leaving Air Temperature (°F db/°F wb) 57.4/54.0 61.0/59.5 64.3/63.7 58.6/55.0 61.7/59.4 65.3/63.6 62.3/54.5 62.6/59.2 65.9/63.5
2,600
Total Capacity (Btu/h) 56,017 59,692 63,181 57,467 59,893 63,755 60,908 60,941 63,929Sensible Capacity (Btu/h) 48,440 38,555 29,454 57,467 50,610 40,611 60,908 60,941 52,772
Electric Power (W) 4,924 4,939 4,977 5,010 4,956 4,957 4,980 5,018 4,993Leaving Air Temperature (°F db/°F wb) 56.0/51.4 58.1/55.8 61.6/60.0 64.8/64.3 59.8/50.9 59.9/55.5 62.4/59.9 65.9/64.2 63.5/50.3
NOTES: 1. Above performance assumes 95.0 °F db/75.0 °F wb ambient temperature and reflects gross capacities.
HE
AT
ING
CFMAMBIENT TEMPERATURE (°F)
10 17 20 30 40 47 50 60
2,200Total Capacity (Btu/h) 33,407 36,959 38,699 45,786 54,589 57,762 60,863 69,041
Electric Power (W) 3,377 3,458 3,497 3,646 3,792 3,918 3,976 4,182
2,400Total Capacity (Btu/h) 33,530 37,082 38,835 45,953 54,896 58,069 60,633 69,684
Electric Power (W) 3,347 3,423 3,460 3,601 3,738 3,857 3,916 4,103
2,600Total Capacity (Btu/h) 33,628 37,185 38,942 46,159 55,105 58,329 60,927 70,046
Electric Power (W) 3,321 3,394 3,429 3,563 3,692 3,806 3,862 4,040
NOTES: 1. Above performance assumes 70.0 °F db/ 60.0 °F wb entering air temperature.
5
UNIT DATA - RCH074 WITH HCH074 / VCH074RATED IN ACCORDANCE TO ANSI/AHRI STANDARD 340/360-2007.
PE
RF
OR
MA
NC
E
DA
TA
NET COOLING
Total Capacity (Btu/h) 79,200Sensible Capacity (Btu/h) 58,746
Electric Power (W) 6,348Leaving Air Temperature (°F db / °F wb) 59.5 / 57.4
Energy Efficiency Ratio (EER) 12.4Integrated Energy Efficiency Ratio (IEER) 13.4
Nominal Airflow (CFM) 2,600
HEATINGTotal Capacity (Btu/h) 78,600
Electric Power (W) 6,212Coefficient of Performance (COP) 3.7
EL
EC
TR
ICA
L D
AT
A
COMPRESSOR(S)
Qty-Nominal Tons-Type 2 - 3.2 - ScrollCapacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 230/1/60 208-230/3/60 460/3/60 575/3/60Run Load Amps (RLA) 17.9 13.5 6.0 4.9
Locked Rotor Amps (LRA) 112 88 44 34
CONDENSER FAN MOTOR(S)
Qty - Horsepower (HP) 1 - 1FLA (ea) 6.2 5.4 2.7 2.0
Type PSC
UNITUnit Minimum Circuit Ampacity 46.5 35.8 16.2 13.1
Max. Time Delay Fuse or HACR Breaker 60 45 20 15
ME
CH
AN
ICA
L D
AT
A
CONDENSER FAN(S)Airflow (CFM) 6,200
Diameter (in)-Pitch (deg) 26 - 26
CONDENSER COIL(S)
Quantity 3Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft.) 23.1Rows - Fins per Inch 4 - 12
REFRIGERANT CONNECTION(S)
Suction Line (in OD) 7/8 (Qty 2)Liquid Line (in OD) 3/8 (Qty 2)
Optional Hot Gas Bypass (in OD) 3/8 (Qty 2)Optional Hot Gas Reheat (in OD) 3/8 (Qty 2)
CABINET
Sheet Metal G90 GalvanizedFinish Polyester Coating
Top Pan Thickness (ga) 16Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
REFRIGERANT - R410A Charge based on 25' line set (lbs per circuit) 14
WEIGHTSUnit Weight (lbs) 695
Shipping Weight (lbs) 745
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 22 - 23.
CO
OL
ING
CFMENTERING AIR TEMPERATURE (°F)
75 DB 80 DB 85 DB63 WB 67 WB 71 WB 63 WB 67 WB 71 WB 63 WB 67 WB 71 WB
2,200
Total Capacity (Btu/h) 72,272 76,762 81,262 72,526 77,730 82,788 74,728 77,808 83,130Sensible Capacity (Btu/h) 54,158 44,854 35,668 65,660 56,576 46,988 74,728 67,782 58,234
Electric Power (W) 6,284 6,334 6,382 6,288 6,344 6,398 6,338 6,338 6,404Leaving Air Temperature (°F db/°F wb) 54.5/52.6 58.1/57.0 61.6/61.4 55.1/52.5 58.6/56.8 62.4/61.1 56.6/52.1 59.4/56.7 63.1/61.0
2,400
Total Capacity (Btu/h) 73,246 78,286 82,176 73,310 78,610 83,690 74,942 78,892 84,138Sensible Capacity (Btu/h) 56,466 46,654 36,670 68,268 616,203 48,366 74,942 70,944 60,764
Electric Power (W) 6,300 6,350 6,394 6,288 6,354 6,410 6,306 6,358 6,424Leaving Air Temperature (°F db/°F wb) 55.3/53.4 58.8/57.6 62.3/62.1 56.1/53.3 59.5/57.5 63.2/61.8 58.7/53.0 60.2/57.4 63.9/61.7
2,800
Total Capacity (Btu/h) 73,850 78,922 82,958 74,068 79,348 84,466 76,396 79,466 84,932Sensible Capacity (Btu/h) 58,020 47,496 37,646 70,690 60,672 49,682 76,396 73,584 62,930
Electric Power (W) 6,252 6,298 6,348 6,404 6,310 6,302 6,362 6,420 6,352Leaving Air Temperature (°F db/°F wb) 53.0/49.9 56.2/54.0 59.7/58.3 62.9/62.7 56.1/49.2 57.0/54.0 60.4/58.2 64.0/62.5 59.6/48.6
NOTES: 1. Above performance assumes 95.0 °F db/75.0 °F wb ambient temperature and reflects gross capacities.
HE
AT
ING
CFMAMBIENT TEMPERATURE (°F)
10 17 20 30 40 47 50 60
2,200Total Capacity (Btu/h) 47,718 47,584 53,756 62,754 73,312 80,332 84,222 95,066
Electric Power (W) 5,536 5,872 5,728 5,916 6,156 6,366 6,470 6,908
2,400Total Capacity (Btu/h) 46,274 51,214 54,236 63,056 73,714 80,826 84,748 95,734
Electric Power (W) 5,474 5,616 5,668 5,840 6,062 6,254 6,352 6,762
2,800Total Capacity (Btu/h) 46,470 51,418 54,222 63,200 73,656 83,602 42,394 96,958
Electric Power (W) 5,428 5,566 5,614 5,776 5,982 6,254 6,258 6,636
NOTES: 1. Above performance assumes 70.0 °F db/ 60.0 °F wb entering air temperature.
6
UNIT DATA - RCH104 WITH HCH104 / VCH104RATED IN ACCORDANCE TO ANSI/AHRI STANDARD 340/360-2007.
PE
RF
OR
MA
NC
E
DA
TA
NET COOLING
Total Capacity (Btu/h) 94,500Sensible Capacity (Btu/h) 76,566
Electric Power (W) 8,088Leaving Air Temperature (°F db / °F wb) 59.2 / 58.0
Energy Efficiency Ratio (EER) 11.6Integrated Energy Efficiency Ratio (IEER) 12.9
Nominal Airflow (CFM) 3,400
HEATINGTotal Capacity (Btu/h) 90,900
Electric Power (W) 7,514Coefficient of Performance (COP) 3.5
EL
EC
TR
ICA
L D
AT
A
COMPRESSOR(S)
Qty-Nominal Tons-Type 2 - 3.8 - ScrollCapacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 230/1/60 208-230/3/60 460/3/60 575/3/60Run Load Amps (RLA) 21.8 13.7 6.2 4.8
Locked Rotor Amps (LRA) 117 83 41 33
CONDENSER FAN MOTOR(S)
Qty - Horsepower (HP) 1 - 1FLA (ea) 6.2 5.4 2.7 2.0
Type PSC
UNITUnit Minimum Circuit Ampacity 55.3 36.2 16.7 12.8
Max. Time Delay Fuse or HACR Breaker 75 45 20 15
ME
CH
AN
ICA
L D
AT
A
CONDENSER FAN(S)Airflow (CFM) 6,200
Diameter (in)-Pitch (deg) 26 - 26
CONDENSER COIL(S)
Quantity 3Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft.) 23.1Rows - Fins per Inch 4 - 12
REFRIGERANT CONNECTION(S)
Suction Line (in OD) 7/8 (Qty 2)Liquid Line (in OD) 1/2 (Qty 2)
Optional Hot Gas Bypass (in OD) 3/8 (Qty 2)Optional Hot Gas Reheat (in OD) 3/8 (Qty 2)
CABINET
Sheet Metal G90 GalvanizedFinish Polyester Coating
Top Pan Thickness (ga) 16Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
REFRIGERANT - R410A Charge based on 25' line set (lbs per circuit) 18
WEIGHTSUnit Weight (lbs) 870
Shipping Weight (lbs) 945
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 22 - 23.
CO
OL
ING
CFMENTERING AIR TEMPERATURE (°F)
75 DB 80 DB 85 DB63 WB 67 WB 71 WB 63 WB 67 WB 71 WB 63 WB 67 WB 71 WB
3,000
Total Capacity (Btu/h) 86,922 92,602 98,278 87,986 92,864 98,838 92,124 93,992 99,182Sensible Capacity (Btu/h) 69,190 57,732 43,366 83,918 71,582 60,182 92,124 86,792 74,354
Electric Power (W) 8,024 8,072 8,120 8,034 8,074 8,126 8,070 8,086 8,130Leaving Air Temperature (°F db/°F wb) 54.0 / 53.1 57.6 / 57.3 62.0 / 61.7 54.5 / 52.9 58.4 / 57.3 61.9 / 61.6 57.0 / 52.3 58.7 / 57.1 62.6 / 61.5
3,400
Total Capacity (Btu/h) 88,368 93,992 99,760 90,252 94,540 100,432 95,378 96,130 100,886Sensible Capacity (Btu/h) 73,070 61,180 45,240 89,398 76,556 64,546 95,378 93,202 79,628
Electric Power (W) 8,024 8,084 8,132 8,054 8,088 8,138 8,098 8,104 8,144Leaving Air Temperature (°F db/°F wb) 55.5 / 54.2 58.7 / 58.4 63.0 / 62.8 56.1 / 53.9 59.6 / 58.3 62.9 / 62.6 59.4 / 53.3 60.1 / 58.1 63.9 / 62.6
3,800
Total Capacity (Btu/h) 89,648 95,222 100,948 92,600 95,864 101,672 98,120 98,222 102,272Sensible Capacity (Btu/h) 77,554 64,960 47,144 92,600 81,330 68,690 98,120 98,222 84,852
Electric Power (W) 8,034 8,094 8,142 8,072 8,100 8,152 8,120 8,122 8,156Leaving Air Temperature (°F db/°F wb) 56.5 / 55.1 59.5 / 59.3 63.8 / 63.6 57.8 / 54.7 60.6 / 59.2 63.7 / 63.5 61.4 / 54.2 61.5 / 58.9 64.8 / 63.4
NOTES: 1. Above performance assumes 95.0 °F db/75.0 °F wb ambient temperature and reflects gross capacities.
HE
AT
ING
CFMAMBIENT TEMPERATURE (°F)
10 17 20 30 40 47 50 60
3,000Total Capacity (Btu/h) 52,506 57,530 60,168 66,082 81,852 90,820 94,442 108,282
Electric Power (W) 6,276 6,448 6,532 6,348 7,004 7,192 7,248 7,506
3,400Total Capacity (Btu/h) 52,854 57,780 60,610 70,556 82,332 91,646 95,408 109,278
Electric Power (W) 6,190 6,352 6,430 6,664 6,864 6,826 7,080 7,300
3,800Total Capacity (Btu/h) 55,438 58,302 60,952 70,932 82,756 92,298 96,632 110,042
Electric Power (W) 6,128 6,276 6,348 6,576 6,754 6,898 6,936 7,138
NOTES: 1. Above performance assumes 70.0 °F db/ 60.0 °F wb entering air temperature.
7
UNIT DATA - RCH134 WITH HCH134 / VCH134RATED IN ACCORDANCE TO ANSI/AHRI STANDARD 340/360-2007.
PE
RF
OR
MA
NC
E
DA
TA
NET COOLING
Total Capacity (Btu/h) 124,700Sensible Capacity (Btu/h) 99,280
Electric Power (W) 10,618Leaving Air Temperature (°F db / °F wb) 57.4/57.2
Energy Efficiency Ratio (EER) 11.7Integrated Energy Efficiency Ratio (IEER) 12.6
Nominal Airflow (CFM) 4,000
HEATINGTotal Capacity (Btu/h) 116,500
Electric Power (W) 8,970Coefficient of Performance (COP) 3.8
EL
EC
TR
ICA
L D
AT
A
COMPRESSOR(S)
Qty-Nominal Tons-Type 2 - 4.5 - ScrollCapacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60Run Load Amps (RLA) 16.0 7.8 5.7
Locked Rotor Amps (LRA) 110 52 39
CONDENSER FAN MOTOR(S)
Qty - Horsepower (HP) 1 - 1FLA (ea) 5.4 2.7 2.0
Type PSC
UNITUnit Minimum Circuit Ampacity 41.4 20.3 14.8
Max. Time Delay Fuse or HACR Breaker 55 30 20
ME
CH
AN
ICA
L D
AT
A
CONDENSER FAN(S)Airflow (CFM) 6,200
Diameter (in)-Pitch (deg) 26 - 26
CONDENSER COIL(S)
Quantity 3Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft.) 23.1Rows - Fins per Inch 4 - 12
REFRIGERANT CONNECTION(S)
Suction Line (in OD) 7/8 (Qty 2)Liquid Line (in OD) 1/2 (Qty 2)
Optional Hot Gas Bypass (in OD) 3/8 (Qty 2)Optional Hot Gas Reheat (in OD) 3/8 (Qty 2)
CABINET
Sheet Metal G90 GalvanizedFinish Polyester Coating
Top Pan Thickness (ga) 16Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
REFRIGERANT - R410A Charge based on 25' line set (lbs per circuit) 20
WEIGHTSUnit Weight (lbs) 915
Shipping Weight (lbs) 990
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 22 - 23.
CO
OL
ING
CFMENTERING AIR TEMPERATURE (°F)
75 DB 80 DB 85 DB63 WB 67 WB 71 WB 63 WB 67 WB 71 WB 63 WB 67 WB 71 WB
3,800
Total Capacity (Btu/h) 117,930 125,334 133,010 118,974 126,070 133,742 124,114 126,706 134,370Sensible Capacity (Btu/h) 95,178 77,138 59,388 113,492 98,984 80,860 124,114 116,550 102,378
Electric Power (W) 9,876 9,994 10,126 9,894 10,012 10,140 9,978 10,012 10,156Leaving Air Temperature (°F db/°F wb) 52.3 / 52.0 58.2 / 57.8 61.0 / 58.0 52.8 / 52.0 56.5 / 56.5 61.3 / 60.8 55.2 / 51.5 57.1 / 56.4 60.7 / 60.1
4,000
Total Capacity (Btu/h) 118,852 126,196 133,900 120,098 126,948 134,700 126,006 128,018 134,978Sensible Capacity (Btu/h) 98,036 78,744 60,368 116,880 101,854 83,134 126,006 120,842 104,950
Electric Power (W) 9,890 9,998 10,142 9,916 10,026 10,158 10,008 10,046 10,162Leaving Air Temperature (°F db/°F wb) 52.8 / 52.0 57.2 / 57.0 61.5 / 61.0 53.4 / 52.6 57.0 / 56.1 61.8 / 61.0 56.2 / 55.8 57.6 / 56.8 61.3 / 61.0
4,200
Total Capacity (Btu/h) 119,664 127,058 134,714 121,192 127,568 135,572 127,768 128,890 136,094Sensible Capacity (Btu/h) 100,836 81,040 61,352 120,006 104,290 85,382 127,768 123,946 108,740
Electric Power (W) 9,906 10,024 10,156 9,928 10,032 10,176 10,038 10,058 10,186Leaving Air Temperature (°F db/°F wb) 53.2 / 53.0 57.6 / 57.0 61.9 / 61.0 54.0 / 53.0 57.5 / 57.0 61.8 / 61.0 57.2 / 56.8 58.2 / 57.3 61.7 / 61.0
NOTES: 1. Above performance assumes 95.0 °F db/75.0 °F wb ambient temperature and reflects gross capacities.
HE
AT
ING
CFMAMBIENT TEMPERATURE (°F)
10 17 20 30 40 47 50 60
3,800Total Capacity (Btu/h) 71,334 74,564 77,866 89,562 103,464 116,136 119,712 134,418
Electric Power (W) 7,874 8,016 8,096 8,386 8,714 9,060 9,160 9,410
4,000Total Capacity (Btu/h) 71,534 74,756 78,066 89,796 103,724 116,548 120,098 134,894
Electric Power (W) 7,830 7,966 8,044 8,322 8,638 8,970 9,074 9,312
4,200Total Capacity (Btu/h) 71,718 74,934 78,250 90,014 103,962 116,932 120,590 135,350
Electric Power (W) 7,790 7,922 7,996 8,266 8,568 8,890 8,982 9,224
NOTES: 1. Above performance assumes 70.0 °F db/ 60.0 °F wb entering air temperature.
8
UNIT DATA - RCH154 WITH HCH154 / VCH154RATED IN ACCORDANCE TO ANSI/AHRI STANDARD 340/360-2007.
PE
RF
OR
MA
NC
E
DA
TA
NET COOLING
Total Capacity (Btu/h) 160,200Sensible Capacity (Btu/h) 125,896
Electric Power (W) 14,154Leaving Air Temperature (°F db / °F wb) 59.0 / 57.6
Energy Efficiency Ratio (EER) 11.3Integrated Energy Efficiency Ratio (IEER) 12.3
Nominal Airflow (CFM) 5,500
HEATINGTotal Capacity (Btu/h) 157,300
Electric Power (W) 13,302Coefficient of Performance (COP) 3.4
EL
EC
TR
ICA
L D
AT
A
COMPRESSOR(S)
Qty-Nominal Tons-Type 2 - 6.0 - ScrollCapacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60Run Load Amps (RLA) 23.2 11.2 7.9
Locked Rotor Amps (LRA) 164 75 54
CONDENSER FAN MOTOR(S)
Qty - Horsepower (HP) 2 - 1FLA (ea) 3.4/5.4 1.7/2.7 2.0/2.0
Type PSC
UNITUnit Minimum Circuit Ampacity 61.0 29.6 17.8
Max. Time Delay Fuse or HACR Breaker 80 40 25
ME
CH
AN
ICA
L D
AT
A
CONDENSER FAN(S)Airflow (CFM) 12,400
Diameter (in)-Pitch (deg) 26 - 32
CONDENSER COIL(S)
Quantity 4Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft.) 30.8Rows - Fins per Inch 4 - 12
REFRIGERANT CONNECTION(S)
Suction Line (in OD) 7/8 (Qty 2)Liquid Line (in OD) 1/2 (Qty 2)
Optional Hot Gas Bypass (in OD) 3/8 (Qty 2)Optional Hot Gas Reheat (in OD) 1/2 (Qty 2)
CABINET
Sheet Metal G90 GalvanizedFinish Polyester Coating
Top Pan Thickness (ga) 16Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
REFRIGERANT - R410A Charge based on 25' line set (lbs per circuit) 25
WEIGHTSUnit Weight (lbs) 1,335
Shipping Weight (lbs) 1,435
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 22 - 23.
CO
OL
ING
CFMENTERING AIR TEMPERATURE (°F)
75 DB 80 DB 85 DB63 WB 67 WB 71 WB 63 WB 67 WB 71 WB 63 WB 67 WB 71 WB
5,000
Total Capacity (Btu/h) 157,094 167,410 177,552 157,484 167,940 178,962 162,482 168,506 179,300Sensible Capacity (Btu/h) 119,052 98,954 74,618 144,056 122,706 103,550 162,482 148,316 126,802
Electric Power (W) 14,862 14,998 15,138 14,862 15,000 15,162 14,932 15,008 15,162Leaving Air Temperature (°F db/°F wb) 53.4/ 52.1 57.1/ 56.4 61.6/ 60.8 53.8 / 52.0 57.8 / 56.4 61.3 / 60.7 55.3 / 51.6 58.1 / 56.3 62.1 / 60.6
5,500
Total Capacity (Btu/h) 158,698 169,166 179,234 159,662 169,820 180,378 166,444 170,664 180,922Sensible Capacity (Btu/h) 124,000 103,298 76,468 151,458 128,824 107,296 166,444 156,894 132,792
Electric Power (W) 15,070 15,214 15,356 15,080 15,220 15,368 15,174 15,236 15,378Leaving Air Temperature (°F db/°F wb) 54.5 /53.1 58.0 / 57.4 62.5 / 61.8 54.9 / 53.0 58.8 / 57.3 62.4 / 61.6 57.4 / 52.5 59.1/ 57.2 63.2 / 61.5
6,000
Total Capacity (Btu/h) 159,896 170,228 180,520 161,338 171,080 181,980 169,822 172,354 182,208Sensible Capacity (Btu/h) 128,828 106,548 78,176 158,190 134,280 112,618 169,822 163,962 138,654
Electric Power (W) 15,154 15,274 15,414 15,566 15,284 15,294 15,430 15,588 15,410Leaving Air Temperature (°F db/°F wb) 52.0 / 49.7 55.5 / 53.9 58.9/ 58.2 63.3 / 62.5 55.6 / 49.0 56.0 / 53.8 59.7 / 58.1 63.1/ 62.4 59.1/ 48.3
NOTES: 1. Above performance assumes 95.0 °F db/75.0 °F wb ambient temperature and reflects gross capacities.
HE
AT
ING
CFMAMBIENT TEMPERATURE (°F)
10 17 20 30 40 47 50 60
5,000Total Capacity (Btu/h) 96,016 107,718 112,460 129,822 148,948 163,478 173,150 193,480
Electric Power (W) 12,558 12,926 13,094 13,694 14,344 14,878 15,054 15,696
5,500Total Capacity (Btu/h) 98,884 108,684 113,454 126,990 150,184 164,972 174,978 195,386
Electric Power (W) 12,636 12,988 13,148 13,720 14,338 14,848 15,010 15,640
6,000Total Capacity (Btu/h) 99,710 109,600 114,382 132,068 151,322 166,310 176,458 197,014
Electric Power (W) 12,730 13,070 13,224 13,774 14,364 14,858 15,010 15,628
NOTES: 1. Above performance assumes 70.0 °F db/ 60.0 °F wb entering air temperature.
9
UNIT DATA - RCH194 WITH HCH194 / VCH194RATED IN ACCORDANCE TO ANSI/AHRI STANDARD 340/360-2007.
PE
RF
OR
MA
NC
E
DA
TA
NET COOLING
Total Capacity (Btu/h) 186,000Sensible Capacity (Btu/h) 144,308
Electric Power (W) 16,410Leaving Air Temperature (°F db / °F wb) 58.1 / 57.2
Energy Efficiency Ratio (EER) 11.3Integrated Energy Efficiency Ratio (IEER) 12.2
Nominal Airflow (CFM) 6,000
HEATINGTotal Capacity (Btu/h) 181,800
Electric Power (W) 14,704Coefficient of Performance (COP) 3.6
EL
EC
TR
ICA
L D
AT
A
COMPRESSOR(S)
Qty-Nominal Tons-Type 2 - 7.2 - ScrollCapacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60Run Load Amps (RLA) 25.0 12.2 9.0
Locked Rotor Amps (LRA) 164 100 78
CONDENSER FAN MOTOR(S)
Qty - Horsepower (HP) 2 - 1FLA (ea) 3.4/5.4 1.7/2.7 2.0/2.0
Type PSC
UNITUnit Minimum Circuit Ampacity 65.1 31.9 24.3
Max. Time Delay Fuse or HACR Breaker 90 40 30
ME
CH
AN
ICA
L D
AT
A
CONDENSER FAN(S)Airflow (CFM) 12,400
Diameter (in)-Pitch (deg) 26 - 32
CONDENSER COIL(S)
Quantity 4Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft.) 30.8Rows - Fins per Inch 4 - 12
REFRIGERANT CONNECTION(S)
Suction Line (in OD) 7/8 (Qty 2)Liquid Line (in OD) 5/8 (Qty 2)
Optional Hot Gas Bypass (in OD) 3/8 (Qty 2)Optional Hot Gas Reheat (in OD) 1/2 (Qty 2)
CABINET
Sheet Metal G90 GalvanizedFinish Polyester Coating
Top Pan Thickness (ga) 16Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
REFRIGERANT - R410A Charge based on 25' line set (lbs per circuit) 26
WEIGHTSUnit Weight (lbs) 1,335
Shipping Weight (lbs) 1,435
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 22 - 23.
CO
OL
ING
CFMENTERING AIR TEMPERATURE (°F)
75 DB 80 DB 85 DB63 WB 67 WB 71 WB 63 WB 67 WB 71 WB 63 WB 67 WB 71 WB
5,500
Total Capacity (Btu/h) 172,622 183,780 194,806 174,284 184,244 195,960 180,222 185,700 196,678Sensible Capacity (Btu/h) 134,064 108,578 81,890 159,462 139,170 113,240 180,222 164,726 144,410
Electric Power (W) 16,924 17,138 17,340 16,954 17,146 17,364 17,076 17,172 17,380Leaving Air Temperature (°F db/°F wb) 52.8 / 52.1 57.1 / 56.5 61.6 / 60.9 53.6 / 52.0 57.1/ 56.4 61.4/ 60.7 55.1 / 51.5 57.8 / 56.2 61.3 / 60.6
6,000
Total Capacity (Btu/h) 174,312 185,412 196,456 176,510 186,208 197,648 184,276 188,180 198,146Sensible Capacity (Btu/h) 136,418 112,692 83,632 167,004 142,498 117,996 184,276 172,982 151,016
Electric Power (W) 17,146 17,362 17,566 17,186 17,378 17,590 17,342 17,412 17,598Leaving Air Temperature (°F db/°F wb) 54.3 / 53.0 58.0 / 57.3 62.5 / 61.7 54.6 / 52.8 58.5 / 57.2 62.3 / 61.6 57.0 / 52.3 58.8 / 57.1 62.3 / 61.5
6,500
Total Capacity (Btu/h) 175,828 186,690 197,748 178,572 187,760 199,016 187,810 190,190 199,702Sensible Capacity (Btu/h) 142,202 116,790 85,376 173,854 187,760 122,614 187,810 180,874 153,078
Electric Power (W) 17,228 17,384 17,580 17,784 17,414 17,416 17,600 17,812 17,596Leaving Air Temperature (°F db/°F wb) 51.5 / 49.4 55.1/ 53.8 58.8 / 58.1 63.2 / 62.4 55.0 / 48.7 55.6 / 53.6 59.3 / 58.0 63.0 / 62.3 58.5/ 48.1
NOTES: 1. Above performance assumes 95.0 °F db/75.0 °F wb ambient temperature and reflects gross capacities.
HE
AT
ING
CFMAMBIENT TEMPERATURE (°F)
10 17 20 30 40 47 50 60
5,500Total Capacity (Btu/h) 116,036 128,804 132,846 151,636 172,030 190,540 196,386 224,798
Electric Power (W) 14,038 14,426 14,590 15,142 15,644 16,128 16,274 17,028
6,000Total Capacity (Btu/h) 118,332 129,790 133,904 152,846 173,370 192,226 197,952 226,634
Electric Power (W) 14,096 14,460 14,618 15,154 15,624 16,078 16,218 16,928
6,500Total Capacity (Btu/h) 119,194 130,720 134,910 153,970 174,514 193,750 199,444 228,710
Electric Power (W) 14,168 14,516 14,670 15,194 15,636 16,068 16,202 16,868
NOTES: 1. Above performance assumes 70.0 °F db/ 60.0 °F wb entering air temperature.
10
UNIT DATA - RCH254 WITH HCH254 / VCH254RATED IN ACCORDANCE TO ANSI/AHRI STANDARD 340/360-2007.
PE
RF
OR
MA
NC
E
DA
TA
NET COOLING
Total Capacity (Btu/h) 247,400Sensible Capacity (Btu/h) 189,120
Electric Power (W) 23,910Leaving Air Temperature (°F db / °F wb) 58.4 / 57.2
Energy Efficiency Ratio (EER) 10.3Integrated Energy Efficiency Ratio (IEER) 11.4
Nominal Airflow (CFM) 8,000
HEATINGTotal Capacity (Btu/h) 249,200
Electric Power (W) 20,444Coefficient of Performance (COP) 3.5
EL
EC
TR
ICA
L D
AT
A
COMPRESSOR(S)
Qty-Nominal Tons-Type 2 - 10.5 - ScrollCapacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60Run Load Amps (RLA) 33.3 17.9 12.8
Locked Rotor Amps (LRA) 239 125 80
CONDENSER FAN MOTOR(S)
Qty - Horsepower (HP) 2 - 1FLA (ea) 3.4/5.4 1.7/2.7 2.0/2.0
Type PSC
UNITUnit Minimum Circuit Ampacity 83.7 44.7 32.8
Max. Time Delay Fuse or HACR Breaker 110 60 40
ME
CH
AN
ICA
L D
AT
A
CONDENSER FAN(S)Airflow (CFM) 12,400
Diameter (in)-Pitch (deg) 26 - 32
CONDENSER COIL(S)
Quantity 4Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft.) 30.8Rows - Fins per Inch 4 - 12
REFRIGERANT CONNECTION(S)
Suction Line (in OD) 13/8 (Qty 2)Liquid Line (in OD) 5/8 (Qty 2)
Optional Hot Gas Bypass (in OD) 1/2 (Qty 2)Optional Hot Gas Reheat (in OD) 5/8 (Qty 2)
CABINET
Sheet Metal G90 GalvanizedFinish Polyester Coating
Top Pan Thickness (ga) 16Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
REFRIGERANT - R410A Charge based on 25' line set (lbs per circuit) 30
WEIGHTSUnit Weight (lbs) 1,335
Shipping Weight (lbs) 1,435
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 22 - 23.
CO
OL
ING
CFMENTERING AIR TEMPERATURE (°F)
75 DB 80 DB 85 DB63 WB 67 WB 71 WB 63 WB 67 WB 71 WB 63 WB 67 WB 71 WB
6,000
Total Capacity (Btu/h) 224,002 238,604 253,264 224,066 239,340 254,768 226,862 239,476 255,644Sensible Capacity (Btu/h) 162,440 132,770 104,524 189,964 166,260 137,702 221,674 195,310 172,056
Electric Power (W) 23,840 24,160 24,554 23,838 24,178 24,564 23,910 24,212 24,618Leaving Air Temperature (°F db/°F wb) 50.4/ 49.8 55.0/ 54.2 59.3/ 58.6 51.2 /49.8 54.9 / 54.1 59.3 / 58.5 51.3 /49.5 55.4/ 54.0 59.1 / 58.4
7,000
Total Capacity (Btu/h) 228,418 243,462 258,184 230,524 244,294 256,958 236,150 245,866 260,500Sensible Capacity (Btu/h) 169,718 141,062 108,116 207,260 180,116 146,614 236,150 212,606 186,668
Electric Power (W) 24,308 24,676 25,076 24,392 24,696 25,050 24,534 24,766 25,142Leaving Air Temperature (°F db/°F wb) 53.0/ 51.7 56.8 /56.0 61.1 / 60.4 53.0 / 51.5 56.7 /55.9 61.1 /60.4 54.2 /51.1 57.4 /55.7 60.9/ 60.2
8,000
Total Capacity (Btu/h) 232,230 246,892 261,736 233,972 245,632 263,498 240,208 249,336 263,920Sensible Capacity (Btu/h) 182,066 149,142 111,472 221,282 186,394 157,450 240,208 228,026 194,926
Electric Power (W) 24,506 24,828 25,158 25,544 24,698 24,872 25,158 25,620 25,014Leaving Air Temperature (°F db/°F wb) 50.6 / 48.8 54.3/ 53.0 58.1/ 57.3 62.5 / 61.7 54.0 / 48.3 54.8 /52.9 58.9 / 57.3 62.3 / 61.6 57.5 / 47.6
NOTES: 1. Above performance assumes 95.0 °F db/75.0 °F wb ambient temperature and reflects gross capacities.
HE
AT
ING
CFM AMBIENT TEMPERATURE (°F)10 17 20 30 40 47 50 60
6,000Total Capacity (Btu/h) 95,980 106,570 169,288 194,538 224,342 249,184 267,042 289,514
Electric Power (W) 10,712 11,084 19,370 20,170 21,074 10,946 22,044 23,328
7,000Total Capacity (Btu/h) 96,362 101,244 170,360 195,750 226,566 259,042 270,818 292,654
Electric Power (W) 10,608 10,966 18,872 19,588 20,378 22,530 21,262 22,368
8,000Total Capacity (Btu/h) 96,686 101,522 177,176 192,724 228,184 262,506 273,786 298,106
Electric Power (W) 10,520 10,868 18,510 18,762 9939*2 22,312 20,660 20,964
NOTES: 1. Above performance assumes 70.0 °F db/ 60.0 °F wb entering air temperature.
11
UNIT DATA - RCH314 WITH HCH314 / VCH314RATED IN ACCORDANCE TO ANSI/AHRI STANDARD 340/360-2007.
PE
RF
OR
MA
NC
E
DA
TA
NET COOLING
Total Capacity (Btu/h) 332,400Sensible Capacity (Btu/h) 248,138
Electric Power (W) 29,504Leaving Air Temperature (°F db / °F wb) 58.4 / 57.3
Energy Efficiency Ratio (EER) 11.2Integrated Energy Efficiency Ratio (IEER) 12.6
Nominal Airflow (CFM) 10,000
HEATINGTotal Capacity (Btu/h) 312,100
Electric Power (W) 28,110Coefficient of Performance (COP) 3.2
EL
EC
TR
ICA
L D
AT
A
COMPRESSOR(S)
Qty-Nominal Tons-Type 2 - 12 - ScrollCapacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60Run Load Amps (RLA) 48.1 18.6 14.7
Locked Rotor Amps (LRA) 245 125 100
CONDENSER FAN MOTOR(S)
Qty - Horsepower (HP) 2 - 1FLA (ea) 3.4/3.4/5.4/5.4 1.7/1.7/2.7/2.7 2.0/2.0/2.0/2.0
Type PSC
UNITUnit Minimum Circuit Ampacity 125.8 50.7 41.1
Max. Time Delay Fuse or HACR Breaker 170 65 50
ME
CH
AN
ICA
L D
AT
A
CONDENSER FAN(S)Airflow (CFM) 12,400
Diameter (in)-Pitch (deg) 26 - 32
CONDENSER COIL(S)
Quantity 4Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft.) 30.8Rows - Fins per Inch 4 - 12
REFRIGERANT CONNECTION(S)
Suction Line (in OD) 13/8 (Qty 2)Liquid Line (in OD) 5/8 (Qty 2)
Optional Hot Gas Bypass (in OD) 1/2 (Qty 2)Optional Hot Gas Reheat (in OD) 5/8 (Qty 2)
CABINET
Sheet Metal G90 GalvanizedFinish Polyester Coating
Top Pan Thickness (ga) 16Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
REFRIGERANT - R410A Charge based on 25' line set (lbs per circuit) 35
WEIGHTSUnit Weight (lbs) 1,945
Shipping Weight (lbs) 2,115
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 22 - 23.
CO
OL
ING
CFMENTERING AIR TEMPERATURE (°F)
75 DB 80 DB 85 DB63 WB 67 WB 71 WB 63 WB 67 WB 71 WB 63 WB 67 WB 71 WB
8,000
Total Capacity (Btu/h) 277,586 295,776 313,692 279,556 296,440 315,326 285,208 298,700 316,068Sensible Capacity (Btu/h) 209,494 172,074 133,444 246,562 216,650 178,528 285,208 254,200 223,212
Electric Power (W) 26,084 26,350 26,606 26,118 26,364 26,630 26,182 26,404 26,644Leaving Air Temperature (°F db/°F wb) 51.2/50.9 55.6/55.2 60.0/59.6 53.7/48.1 55.5/55.1 59.9/59.5 52.5/50.4/ 56.1/54.9 59.8/59.4
9,000
Total Capacity (Btu/h) 282,768 300,994 319,052 285,860 301,856 320,580 295,576 304,784 321,424Sensible Capacity (Btu/h) 217,348 181,538 138,126 262,836 225,476 189,180 295,576 271,306 232,982
Electric Power (W) 26,172 26,422 26,682 26,220 26,438 26,710 26,358 26,484 26,724Leaving Air Temperature (°F db/°F wb) 53.1/52.1 56.8/56.4 61.2/60.9 51.9/50.7 57.3/56.4 61.1/60.7 55.0/51.5 57.6/56.2 61.6/60.6
10,000
Total Capacity (Btu/h) 287,384 305,004 323,058 291,222 306,446 324,944 304,496 310,414 326,060Sensible Capacity (Btu/h) 228,968 190,592 142,742 278,474 237,836 199,424 304,496 288,070 246,238
Electric Power (W) 26,024 26,234 26,478 26,740 26,250 26,290 26,504 26,774 26,478Leaving Air Temperature (°F db/°F wb) 50.5/48.8 54.2/53.2 57.8/57.5 62.2/61.9 53.7/48.1 54.6/53.0 58.4/57.4 62.0/61.7 57.1/47.4
NOTES: 1. Above performance assumes 95.0 °F db/75.0 °F wb ambient temperature and reflects gross capacities.
HE
AT
ING
CFMAMBIENT TEMPERATURE (°F)
10 17 20 30 40 47 50 60
8,000Total Capacity (Btu/h) 181,000 206,780 216,400 256,154 267,700 291,002 300,380 334,200
Electric Power (W) 22,570 23,270 23,500 25,244 25,240 26,038 26,100 27,100
9,000Total Capacity (Btu/h) 182,200 210,480 216,800 263,128 269,600 289,568 303,140 335,700
Electric Power (W) 22,250 22,900 23,200 24,694 25,000 25,504 25,580 26,400
10,000Total Capacity (Btu/h) 183,190 210,300 218,800 261,026 290,500 296,004 305,350 338,160
Electric Power (W) 21,900 22,600 22,800 24,224 24,000 25,072 25,100 25,900
NOTES: 1. Above performance assumes 70.0 °F db/ 60.0 °F wb entering air temperature.
12
UNIT DATA - RCH374 WITH HCH374 / VCH374RATED IN ACCORDANCE TO ANSI/AHRI STANDARD 340/360-2007.
PE
RF
OR
MA
NC
E
DA
TA
NET COOLING
Total Capacity (Btu/h) 345,700Sensible Capacity (Btu/h) 266,200
Electric Power (W) 32,362Leaving Air Temperature (°F db / °F wb) 59.6/58.0
Energy Efficiency Ratio (EER) 10.7Integrated Energy Efficiency Ratio (IEER) 13.0
Nominal Airflow (CFM) 12,000
HEATINGTotal Capacity (Btu/h) 359,800
Electric Power (W) 29,984Coefficient of Performance (COP) 3.5
EL
EC
TR
ICA
L D
AT
A
COMPRESSOR(S)
Qty-Nominal Tons-Type 2 - 13.5 - ScrollCapacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60Run Load Amps (RLA) 51.3 23.1 19.9
Locked Rotor Amps (LRA) 300 150 109
CONDENSER FAN MOTOR(S)
Qty - Horsepower (HP) 4 - 1FLA (ea) 3.4/3.4/5.4/5.4 1.7/1.7/2.7/2.7 2.0/2.0/2.0/2.0
Type PSC
UNITUnit Minimum Circuit Ampacity 133.1 60.8 52.8
Max. Time Delay Fuse or HACR Breaker 180 80 70
ME
CH
AN
ICA
L D
AT
A
CONDENSER FAN(S)Airflow (CFM) 28,000
Diameter (in)-Pitch (deg) 26 - 32
CONDENSER COIL(S)
Quantity 4Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft.) 70.0Rows - Fins per Inch 2 - 14
REFRIGERANT CONNECTION(S)
Suction Line (in OD) 13/8 (Qty 2)Liquid Line (in OD) 7/8 (Qty 2)
Optional Hot Gas Bypass (in OD) 5/8 (Qty 2)Optional Hot Gas Reheat (in OD) 5/8 (Qty 2)
CABINET
Sheet Metal G90 GalvanizedFinish Polyester Coating
Top Pan Thickness (ga) 16Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
REFRIGERANT - R410A Charge based on 25' line set (lbs per circuit) 38
WEIGHTSUnit Weight (lbs) 2,210
Shipping Weight (lbs) 2,380
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 22 - 23.
HE
AT
ING
CFM AMBIENT TEMPERATURE (°F)10 17 20 30 40 47 50 60
10,000Total Capacity (Btu/h) 246,532 268,726 278,106 316,260 355,684 391,734 407,144 445,474
Electric Power (W) 29,740 30,630 31,098 32,136 33,320 34,314 34,702 35,888
12,000Total Capacity (Btu/h) 246,794 280,040 290,582 318,864 359,194 398,742 410,406 444,540
Electric Power (W) 29,024 29,870 30,240 31,228 32,244 33,184 33,508 34,512
14,000Total Capacity (Btu/h) 248,524 284,694 295,470 319,226 361,770 402,332 413,190 449,040
Electric Power (W) 28,526 29,310 29,652 30,594 31,494 32,336 32,584 33,510
NOTES: 1. Above performance assumes 70.0 °F db/ 60.0 °F wb entering air temperature.
CO
OL
ING
CFMENTERING AIR TEMPERATURE (°F)
75 DB 80 DB 85 DB63 WB 67 WB 71 WB 63 WB 67 WB 71 WB 63 WB 67 WB 71 WB
10,000
Total Capacity (Btu/h) 367,532 390,292 413,028 369,722 391,070 414,644 374,710 393,622 415,516Sensible Capacity (Btu/h) 273,848 225,792 179,036 321,596 281,670 232,996 368,290 329,954 289,308
Electric Power (W) 31,686 32,072 32,522 31,774 32,090 32,510 31,812 32,188 32,532Leaving Air Temperature (°F db/°F wb) 50.1 / 50.0 54.6 / 54.4 58.9 / 58.0 50.7 / 49.9 54.5 / 54.3 59.0 / 58.8 51.4 / 49.6 55.0 / 54.2 58.9 / 58.7
12,000
Total Capacity (Btu/h) 377,622 400,540 423,398 381,404 401,260 425,598 394,366 404,778 427,130Sensible Capacity (Btu/h) 292,012 243,810 188,726 351,894 301,570 255,672 394,366 362,114 314,478
Electric Power (W) 31,854 32,254 32,712 31,924 32,270 32,754 32,196 32,338 32,796Leaving Air Temperature (°F db/°F wb) 52.9 / 52.2 56.6 / 56.5 60.9 / 60.3 55.3 / 51.9 57.2 / 56.4 60.8 / 60.0 55.0 / 51.5 57.6 / 56.2 61.3 / 60.7
14,000
Total Capacity (Btu/h) 385,858 408,272 431,134 391,720 409,574 433,254 410,744 414,886 435,282Sensible Capacity (Btu/h) 314,304 262,486 198,104 380,670 325,784 276,964 410,744 394,140 339,974
Electric Power (W) 31,996 32,394 32,860 32,104 32,422 32,904 32,488 32,524 32,946Leaving Air Temperature (°F db/°F wb) 54.6 / 53.0 58.0 / 57.9 62.3 / 62.0 55.2 / 53.4 58.9 / 57.8 62.6 / 62.0 58.2 / 52.8 59.4 / 57.6 63.1 / 62.1
NOTES: 1. Above performance assumes 95.0 °F db/75.0 °F wb ambient temperature and reflects gross capacities.
13
UNIT DATA - RCH414 WITH HCH374 / VCH374RATED IN ACCORDANCE TO ANSI/AHRI STANDARD 340/360-2007.
PE
RF
OR
MA
NC
E
DA
TA
NET COOLING
Total Capacity (Btu/h) 436,100Sensible Capacity (Btu/h) 334,544
Electric Power (W) 40,084Leaving Air Temperature (°F db / °F wb) 58.4 / 57.1
Energy Efficiency Ratio (EER) 10.8Integrated Energy Efficiency Ratio (IEER) 12.1
Nominal Airflow (CFM) 14,000
HEATINGTotal Capacity (Btu/h) 422,400
Electric Power (W) 36,188Coefficient of Performance (COP) 3.4
EL
EC
TR
ICA
L D
AT
A
COMPRESSOR(S)
Qty-Nominal Tons-Type 2 - 18 - ScrollCapacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60Run Load Amps (RLA) 30.1 16.7 12.2
Locked Rotor Amps (LRA) 225 114 80
CONDENSER FAN MOTOR(S)
Qty - Horsepower (HP) 4 - 1FLA (ea) 3.4/3.4/5.4/5.4 1.7/1.7/2.7/2.7 2.0/2.0/2.0/2.0
Type PSC
UNITUnit Minimum Circuit Ampacity 85.3 79.8 59.9
Max. Time Delay Fuse or HACR Breaker 170 95 70
ME
CH
AN
ICA
L D
AT
A
CONDENSER FAN(S)Airflow (CFM) 28,000
Diameter (in)-Pitch (deg) 26 - 32
CONDENSER COIL(S)
Quantity 4Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft.) 70.0Rows - Fins per Inch 2 - 14
REFRIGERANT CONNECTION(S)
Suction Line (in OD) 15/8 (Qty 2)Liquid Line (in OD) 7/8 (Qty 2)
Optional Hot Gas Bypass (in OD) 5/8 (Qty 2)Optional Hot Gas Reheat (in OD) 7/8 (Qty 2)
CABINET
Sheet Metal G90 GalvanizedFinish Polyester Coating
Top Pan Thickness (ga) 16Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
REFRIGERANT - R410A Charge based on 25' line set (lbs per circuit) 40
WEIGHTSUnit Weight (lbs) 2,330
Shipping Weight (lbs) 2,500
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 22 - 23.
CO
OL
ING
CFMENTERING AIR TEMPERATURE (°F)
75 DB 80 DB 85 DB63 WB 67 WB 71 WB 63 WB 67 WB 71 WB 63 WB 67 WB 71 WB
10,000
Total Capacity (Btu/h) 378,364 402,958 426,928 381,434 403,374 429,126 384,688 405,098 430,522Sensible Capacity (Btu/h) 273,082 225,858 176,978 321,684 277,796 232,224 371,560 325,844 287,242
Electric Power (W) 42,964 43,512 44,072 43,032 43,442 44,120 43,108 43,484 44,114Leaving Air Temperature (°F db/°F wb) 50.2/ 49.6 54.6/ 54.0 59.1/ 58.5 50.7/ 49.4 54.8/ 53.9 59.1/ 58.3 51.1/ 49.2 55.4/ 53.8 59.1/ 58.2
12,000
Total Capacity (Btu/h) 387,764 411,544 436,668 390,948 415,892 438,434 399,622 415,760 440,736Sensible Capacity (Btu/h) 291,194 238,504 184,452 350,422 309,214 248,582 399,622 358,332 310,294
Electric Power (W) 43,960 44,434 45,100 43,964 44,590 45,088 44,222 44,518 45,198Leaving Air Temperature (°F db/°F wb) 52.9/ 51.8 57.0 / 56.1 61.2/ 60.6 53.4/ 51.6 56.7/ 56.0 61.3/ 60.4 54.6/ 51.3 57.9/ 55.9 61.7/ 60.3
14,000
Total Capacity (Btu/h) 395,024 417,604 442,304 398,564 421,396 445,678 414,680 424,416 447,590Sensible Capacity (Btu/h) 310,036 253,558 189,372 375,986 322,350 269,750 414,680 388,436 335,542
Electric Power (W) 44,454 44,838 45,346 46,024 44,838 44,908 45,452 46,120 45,352Leaving Air Temperature (°F db/°F wb) 51.1/ 49.0 54.9/ 53.4 58.6/ 57.7 62.8/ 62.1 54.4 / 48.4 55.5/ 53.2 59.1/ 57.6 62.6/ 61.9 57.9 / 47.8
NOTES: 1. Above performance assumes 95.0 °F db/75.0 °F wb ambient temperature and reflects gross capacities.
HE
AT
ING
CFMAMBIENT TEMPERATURE (°F)
10 17 20 30 40 47 50 60
10,000Total Capacity (Btu/h) 266,484 294,540 308,260 348,132 391,228 447,240 466,872 517,944
Electric Power (W) 35,068 36,170 36,464 38,022 39,494 40,688 41,186 43,644
12,000Total Capacity (Btu/h) 267,354 299,004 309,938 375,182 397,384 445,256 461,386 511,792
Electric Power (W) 34,910 35,944 36,308 37,420 38,740 40,020 40,240 42,506
14,000Total Capacity (Btu/h) 275,600 302,992 317,742 373,472 405,594 470,676 466,948 535,950
Electric Power (W) 35,008 36,004 36,226 37,310 38,468 39,424 39,768 41,492
NOTES: 1. Above performance assumes 70.0 °F db/ 60.0 °F wb entering air temperature.
14
TYPICAL WIRING DIAGRAM
NOTES: 1. For systems without electric heat, disregard heater power connection at air handler disconnect and heater thermostat/circuit. 2. All electrical wiring and connections, including electrical grounding must comply with: a. United States: Refer to NFPA 70- latest revision, National Electrical Code, and local ordinances. b. Canada: Refer to CSA C22.1, Part 1- latest revision, Canadian Electrical Code and local ordinances. 3. Class 1 circuit 4. Class 2 circuit 5. Terminal Y is factory-wired to compressor lockout thermostat. 6. Terminal W2 and EHT2 are only used when air handler includes optional two-stage electric heat. 7. Condensing unit disconnect is not provided with condensing unit as standard. Disconnect may be obtained from factory as optional equipment or provided by others. Air handler disconnect must be provided by others. 8. Terminal Y2 is only used on dual circuit units.
15
Outside Air or Return Air
Liquid Line
Suction Line
Sleeve And Flashing
Disconnect
Interconnecting Control Wiring
Condensing Unit
Optional Hot Gas ReheatOptional Hot Gas Bypass
Air Handler
OptionalElectric Heat
Supply Air
Disconnect
Trap And Drain Connection
NOTES: 1. Condensing unit disconnect is not provided with condensing unit as standard. Disconnect may be obtained from factory as optional equipment or provided by others. 2. Air handler disconnect, interconnecting control wiring, all refrigerant line piping and sleeve/flashing materials are by others. 3. Suction, hot gas bypass, and hot gas reheat lines should be insulated with 5/8” minimum thickness closed cell foamed insulation. Liquid line exposed to high ambient temperatures should be insulated 5/8” minimum thickness closed cell foamed insulation.
TYPICAL SPLIT SYSTEM INSTALLATION
16
TYPICAL INSTALLATION WITH CONDENSING UNIT ON BOTTOM
Optional Hot Gas Reheat
Optional Hot Gas Bypass
Condensate Trap And Pipe
Loop To Top Of Coil
Suction
Liquid
Slope Down Towards Condensing Unit
NOTES: 1. To prevent oil migration, lines should slope downwards towards the condensing unit and should slope downward away from the air handler. 2. Vertical risers greater than 4' in height should have a “P” trap installed at the base of the air handler. 3. Vertical risers greater than 20' in height require an extra “P” trap for every 20' of riser height in addition to the “P” trap installed at the base of the air handler. The trap is inverted at the top of the vertical rise. 4. Schematic depicts a single-circuit unit. Dual circuit units have two suction lines as standard, two liquid lines as standard and, if selected, the option of either one or two hot gas bypass lines and either one or two hot gas reheat lines.
17
Slope Down From Air Handler
Condensate Trap And Pipe
Suction
Liquid
Optional Hot Gas Reheat
Optional Hot Gas Bypass
NOTES: 1. To prevent oil migration, lines should slope downwards towards the condensing unit and should slope downward away from the air handler. 2. Vertical risers greater than 4' in height should have a “P” trap installed at the base of the air handler. 3. Vertical risers greater than 20' in height require an extra “P” trap for every 20' of riser height in addition to the “P” trap installed at the base of the air handler. The trap is inverted at the top of the vertical rise. 4. Schematic depicts a single-circuit unit. Dual circuit units have two suction lines as standard, two liquid lines as standard and, if selected, the option of either one or two hot gas bypass lines and either one or two hot gas reheat lines.
TYPICAL INSTALLATION WITH CONDENSING UNIT ON TOP
18
DIMENSIONS - RCH 044/054/064
COIL
COIL
CON
TRO
LSEL
ECTR
ICA
L
DISCONNECTLOCATED HERE
COMPRESSOR
LIQUID
REHEAT
HGBP
SUCTION
39 1/8
47 3/8
2 3
52 1/442 1/4
47 3/8
3
O 3/4
53 3/8
B
DETAIL B
59 1/16
13 1/16
20 1/16
3 11/32
3 1/2
19
DIMENSIONS - RCH 074/104/134
DISCONNECTSWITCH
(OPTIONAL)
CONDENSER
ELECTRICAL BOX
COMPRESSOR
SUCTIONLINE
LIQUID LINE
HOT GAS LINE
A
DETAIL A
56 1/8
48 3/840
8 3/8
11 3/8
14 1/8
5 1/2
8 1/2
68 1/2
74
40
3
20
DIMENSIONS - RCH 154/194/254
ELECTRICAL PANEL
SUCTION LINE
LIQUID LINE
HOTGAS REHEAT(OPTIONAL)
HOTGAS BYPASS(OPTIONAL)
CONDENSER
COMPRESSOR
ELECTRICAL PANEL
DISCONNECT SWITCH(OPTIONAL)
A
DETAIL A
79 3/4
64 1/2
1917
12
1421 3/4
26 1/429 1/4
6 1/4
59 1/252 3/4
21
DIMENSIONS - RCH 314/374/414
ELECTRICAL BOX
SUCTION LINE
LIQUID LINE
HOTGAS REHEAT(OPTIONAL) HOTGAS BYPASS
(OPTIONAL)
COMPRESSOR
CONDENSER
DISCONNECTSWITCH(OPTIONAL)
A
DETAIL A
84 7/8
56 3/4
101 3/4
101 3/4
19 1/8
17 1/8
12 1/8
6 5/8
11 1/818 7/8
23 3/826 3/8
49 7/8
22
REFERENCE INFORMATIONAMBIENT TEMPERATURE CORRECTION FACTORS
AMBIENT TEMPERATURE (°F) 85 90 95 100 105 110 115TOTAL CAPACITY (Btu/h) 1.05 1.03 1.00 0.98 0.95 0.91 0.87
SENSIBLE CAPACITY (Btu/h) 1.03 1.02 1.00 0.99 0.97 0.97 0.93ELECTRIC POWER (W) 0.95 0.98 1.00 1.03 1.05 1.08 1.11
RECOMMENDED REFRIGERANT LINE SIZES- AIR HANDLER LOCATED BELOW CONDENSING UNIT (IN OD)
NOMINAL CAPACITY (Btu/h)0-25 FT. EQUIVALENT LENGTH 26-50 FT. EQUIVALENT LENGTH
SUCTION LIQUID HOT GAS REHEAT
HOT GAS BYPASS
SUCTION LIQUID HOT GAS REHEAT
HOT GAS BYPASS
36,000 5/8, 5/8 3/8 1/2 3/8 3/4, 3/4 1/2 1/2 1/248,000 3/4, 3/4 3/8 5/8 3/8 3/4, 3/4 1/2 5/8 1/260,000 3/4, 3/4 1/2 5/8 1/2 7/8, 7/8 1/2 5/8 1/272,000 7/8, 7/8 1/2 5/8 1/2 7/8, 7/8 1/2 5/8 1/284,000 1-1/8, 1-1/8 1/2 3/4 1/2 1-1/8, 1-1/8 1/2 3/4 1/296,000 1-1/8, 1-1/8 5/8 3/4 1/2 1-1/8, 1-1/8 5/8 3/4 1/2
120,000 1-1/8, 1-1/8 5/8 3/4 5/8 1-3/8, 1-3/8 5/8 3/4 5/8150,000 1-1/8, 1-1/8 5/8 7/8 5/8 1-3/8, 1-3/8 5/8 7/8 5/8180,000 1-3/8, 1-3/8 5/8 7/8 5/8 1-3/8, 1-3/8 5/8 7/8 5/8220,000 1-3/8, 1-3/8 5/8 1-1/8 5/8 1-3/8, 1-3/8 3/4 1-1/8 3/4250,000 1-3/8, 1-3/8 5/8 1-1/8 3/4 1-3/8, 1-3/8 3/4 1-1/8 3/4300,000 1-5/8, 1-5/8 7/8 1-1/8 3/4 1-5/8, 1-5/8 7/8 1-1/8 7/8
NOMINAL CAPACITY (Btu/h) 51-75 FT. EQUIVALENT LENGTH 76-100 FT. EQUIVALENT LENGTH
SUCTION LIQUID HOT GAS REHEAT
HOT GAS BYPASS
SUCTION LIQUID HOT GAS REHEAT
HOT GAS BYPASS
36,000 7/8, 5/8 1/2 5/8 1/2 7/8, 3/4 1/2 5/8 N/A48,000 7/8, 3/4 1/2 3/4 1/2 7/8, 7/8 1/2 5/8 N/A60,000 1-1/8, 7/8 1/2 3/4 1/2 1-1/8, 7/8 1/2 3/4 N/A72,000 1-1/8, 7/8 1/2 3/4 5/8 1-1/8, 7/8 5/8 3/4 N/A84,000 1-1/8, 1-1/8 5/8 7/8 5/8 1-1/8, 1-1/8 5/8 3/4 N/A96,000 1-1/8, 1-1/8 5/8 7/8 5/8 1-1/8, 1-1/8 5/8 3/4 N/A
120,000 1-3/8, 1-3/8 5/8 7/8 3/4 1-3/8, 1-3/8 5/8 7/8 N/A150,000 1-3/8, 1-3/8 5/8 1-1/8 3/4 1-3/8, 1-3/8 3/4 7/8 N/A180,000 1-3/8, 1-3/8 3/4 1-1/8 3/4 1-3/8, 1-3/8 3/4 1-1/8 N/A220,000 1-3/8, 1-3/8 3/4 1-1/8 7/8 1-5/8, 1-3/8 3/4 1-1/8 N/A250,000 1-5/8, 1-3/8 3/4 1-1/8 7/8 1-5/8, 1-3/8 7/8 1-1/8 N/A300,000 1-5/8, 1-5/8 7/8 1-1/8 7/8 2-1/8, 1-5/8 7/8 1-1/8 N/A
NOTES: 1. Line sizes are calculated assuming single scroll compressors in Models 044-064 and dual or dual tandem scroll compressors in Models 074-414. Contact the factory for any other compressor configuration. 2. Line sizes are calculated assuming single circuits. For a dual circuit unit, calculate the capacity per circuit by dividing the total capacity by two. Use the result to calculate line sizes. 3. All piping must comply with standard refrigeration piping techniques. Consult the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Handbook-Refrigeration. 4. Suction, hot gas bypass and hot gas reheat lines should be insulated with a 5/8” minimum thickness closed cell foam insulation. Liquid line exposed to high ambient temperatures should be insulated with a 5/8” minimum thickness closed cell foam insulation. 5. First suction line diameter size is for horizontal runs. Second suction line diameter size is for vertical risers. 6. Maximum suction line vertical lift is 60’. Riser-sized traps are required for every 20’ of vertical riser starting at the lowest point. 7. If ordered, hot gas reheat and hot gas bypass require only one line per circuit. 8. Standard hot gas bypass is not recommended for use with greater than 75’ of equivalent line length. Internal hot gas bypass should be used as an alternative. 9. Contact factory for applications with digital scroll compressors. 10. Contact factory for layouts requiring more than 75’ of actual line length.
23
REFERENCE INFORMATIONRECOMMENDED REFRIGERANT LINE SIZES- AIR HANDLER LEVEL WITH OR LOCATED ABOVE OUTDOOR UNIT (IN OD)
NOMINAL CAPACITY (Btu/h) 0-25 FT. EQUIVALENT LENGTH 26-50 FT. EQUIVALENT LENGTH
SUCTION LIQUID HOT GAS REHEAT
HOT GAS BYPASS
SUCTION LIQUID HOT GAS REHEAT
HOT GAS BYPASS
36,000 3/4 1/2 1/2 3/8 3/4 1/2 1/2 3/848,000 7/8 1/2 1/2 3/8 7/8 1/2 1/2 1/260,000 7/8 5/8 1/2 1/2 1-1/8 5/8 1/2 1/272,000 1-1/8 5/8 1/2 1/2 1-1/8 5/8 5/8 1/284,000 1-1/8 5/8 5/8 1/2 1-1/8 5/8 5/8 1/296,000 1-1/8 5/8 5/8 1/2 1-1/8 5/8 5/8 5/8
120,000 1-1/8 5/8 5/8 1/2 1-3/8 5/8 3/4 5/8150,000 1-3/8 3/4 3/4 5/8 1-3/8 3/4 3/4 5/8180,000 1-3/8 3/4 3/4 5/8 1-3/8 7/8 3/4 3/4220,000 1-5/8 7/8 3/4 5/8 1-5/8 7/8 7/8 3/4250,000 1-5/8 7/8 7/8 3/4 2-1/8 7/8 7/8 3/4300,000 2-1/8 7/8 7/8 3/4 2-1/8 1-1/8 1-1/8 7/8
NOMINAL CAPACITY (Btu/h) 51-75 FT. EQUIVALENT LENGTH 76-100 FT. EQUIVALENT LENGTH
SUCTION LIQUID HOT GAS REHEAT
HOT GAS BYPASS
SUCTION LIQUID HOT GAS REHEAT
HOT GAS BYPASS
36,000 7/8 1/2 1/2 1/2 7/8 5/8 5/8 N/A48,000 7/8 5/8 5/8 1/2 1-1/8 5/8 5/8 N/A60,000 1-1/8 5/8 5/8 1/2 1-1/8 3/4 5/8 N/A72,000 1-1/8 3/4 5/8 1/2 1-1/8 3/4 3/4 N/A84,000 1-1/8 3/4 5/8 5/8 1-3/8 3/4 3/4 N/A96,000 1-3/8 3/4 3/4 5/8 1-3/8 3/4 3/4 N/A
120,000 1-3/8 7/8 3/4 5/8 1-3/8 7/8 3/4 N/A150,000 1-3/8 7/8 7/8 3/4 1-5/8 7/8 7/8 N/A180,000 1-5/8 7/8 7/8 3/4 1-5/8 1-1/8 7/8 N/A220,000 1-5/8 1-1/8 7/8 7/8 2-1/8 1-1/8 7/8 N/A250,000 2-1/8 1-1/8 1-1/8 7/8 2-1/8 1-1/8 7/8 N/A300,000 2-1/8 1-1/8 1-1/8 7/8 2-1/8 1-3/8 1-1/8 N/A
NOTES: 1. Line sizes are calculated assuming single scroll compressors in Models 044-064 and dual or dual tandem scroll compressors in Models 074-414. Contact the factory for any other compressor configuration. 2. Line sizes are calculated assuming single circuits. For a dual circuit unit, calculate the capacity per circuit by dividing the total capacity by two. Use the result to calculate line sizes. 3. All piping must comply with standard refrigeration piping techniques. Consult the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Handbook-Refrigeration. 4. Suction, hot gas bypass and hot gas reheat lines should be insulated with a 5/8” minimum thickness closed cell foam insulation. Liquid line exposed to high ambient temperatures should be insulated with a 5/8” minimum thickness closed cell foam insulation. 5. Maximum suction line vertical lift is 60’. Loop piping to the top of the coil. 6. Maximum liquid line vertical lift is 60’. 7. If ordered, hot gas reheat and hot gas bypass require only one line per circuit. 8. Standard hot gas bypass is not recommended for use with greater than 75’ of equivalent line length. Internal hot gas bypass should be used as an alternative. 9. Contact factory for applications with digital scroll compressors. 10. Contact factory for layouts requiring more than 75’ of actual line length.
These products (with the exception of the CGTH and UHA[X][S] 30 - 75) are not for residential use.This document is intended to assist licensed professionals in the exercise of their professional judgment.Specifications are subject to change without notice.
© 2017 Addison All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Addison.