RE208_Hardwire_to_Honeywell-Compat_Translator Page 1 of 4 24-Hour Tech Support Line: (715)808-0164 30-Oct-14 www.ResolutionProducts.com RE208 Hardwire-to-Honeywell ® or 2GIG ® Wireless Translator™ Features Converts hardwire zones into Honeywell-compatible wireless signals. 8 Hardwire loops with end-of-line resistor detection. Unique wireless ID for each zone, plus 1 for main device. Transmit diversity for long reliable range. PIR powering (via external supply). 3 year operation on batteries (contacts only). Complete supervision of zone tampers and low battery. Key Instructions DO NOT MOUNT IN A METAL CAN. DO NOT PUT POWER ON HARDWIRE TERMINALS. Use with normally closed contacts in-line with 4.7 K-ohms resistors (mandatory). Not for use with life safety devices, such as Smoke or CO sensors. External supply requirements: Contacts-only installations may use wall plug power supply (see specifications) Installations with PIRs or Glassbreaks (powered devices) require battery-backed external power supply (see diagram). Without backed-up power, PIRs or Glass Breaks could alarm when power is lost. Translator AA batteries drive contacts only, and do not drive powered devices. Ensure that external supply has sufficient current to supply all powered devices including Translator. 4-wire powered devices only. Not for use with 2-wire powered devices. If using old panel as the battery-backed 12V DC supply, verify supply and battery operation. DO NOT MOUNT IN OLD CAN… the wireless will not get out! Installation Hook up PIR and Glass Break power lines to external power supply. Alarm contact hook-up: Works only with normally-closed contacts (alarm = open). Remove any existing end-of-line resistors. Connect 4.7K end-of-line resistor (included) IN-LINE with contact. Resistor should NOT be across (between) terminals. Honeywell® Enrollment Sensors: RF Learning tripping enrollment mode. Set up for any behavior desired. Input Type: 3 (Supervised RF) When prompted, open/close each zone twice to enroll serial number. Ensure it is set to Loop: 2. Translator itself: RF Learning tripping enrollment mode. Zone Type: 8 (24 hour Aux) Input Type: 3 (Supervised RF), When prompted, toggle the tamper switch to enroll serial number. Loop 2 (but Loop doesn’t really matter). 2GIG® Enrollment: Sensors: Q1 RF Sensor Set up for any behavior desired. At “Enter RF Serial Number”, press SHIFT LEARN, and trip sensor. Ensure it is set to Loop 2. Translator itself: Sensor Type: (08) 24 Hour Aux Equipment Type: (1) contact Equipment Code: (0000) other Other Equipment Code: (208) meaning RE208 Enter RF Serial Number: [press SHIFT,Learn, then toggle the tamper switch to enroll the serial number] Equipment Age: (0) new Loop Number: (2) but Loop doesn’t really matter Dialer Delay: (1) enabled RE208_Hardwire_to_Honeywell-Compat_Translator Page 2 of 4 24-Hour Tech Support Line: (715)808-0164 30-Oct-14 www.ResolutionProducts.com Application Diagram Connection Diagram 4.7K Contact (Normally Closed) Loop x PIR To Enroll zone, Open and close contact. This sends a open/close signal to panel. Translator AA Batteries DO NOT power external devices Altronix AL100UL 12VDC Supply With Lead-acid battery Old Panel may be used, if operation fully verified +12 VDC GND PIR Power Input PIR Contact Output (Normally Closed) 4.7K Loop y Altronix TP1620 16.5VAC, 20VA Transformer with securing screw Resolution RE012 12 VDC Power Supply NON-Switched Outlet Use Battery-Backed 12VDC if powering PIRs or Glass Breaks Use Non-Battery-Backed Supply ONLY if installation is all non-powered contacts Power Supply polarity DOES NOT matter! End of Line Resistor New Wireless System Existing Hardwire Sensors New Honeywell Self-Contained System in living area Taking over old Hardwire panel, usually mounted in utility area Honeywell Wireless May use GE 60-898-ITI supply here, if securing screw is desired
Transcript
Page 1: RE208 Hardwire-to-Honeywell or 2GIG Wireless …resolutionproducts.com/wp-content/uploads/2015/01/RE208_Hardwire... · RE208 Hardwire-to-Honeywell ... PIRs or Glass Breaks could alarm

RE208_Hardwire_to_Honeywell-Compat_Translator Page 1 of 4 24-Hour Tech Support Line: (715)808-0164 30-Oct-14

www.ResolutionProducts.com

RE208 Hardwire-to-Honeywell® or 2GIG® Wireless Translator™

Features

• Converts hardwire zones into Honeywell-compatible wireless signals.

• 8 Hardwire loops with end-of-line resistor detection.

• Unique wireless ID for each zone, plus 1 for main device.

• Transmit diversity for long reliable range.

• PIR powering (via external supply).

• 3 year operation on batteries (contacts only).

• Complete supervision of zone tampers and low battery. Key Instructions

• DO NOT MOUNT IN A METAL CAN.

• DO NOT PUT POWER ON HARDWIRE TERMINALS.

• Use with normally closed contacts in-line with 4.7 K-ohms resistors (mandatory).

• Not for use with life safety devices, such as Smoke or CO sensors.

• External supply requirements: � Contacts-only installations may use wall plug power supply (see specifications) � Installations with PIRs or Glassbreaks (powered devices) require battery-backed

external power supply (see diagram). � Without backed-up power, PIRs or Glass Breaks could alarm when

power is lost. � Translator AA batteries drive contacts only, and do not drive powered

devices. � Ensure that external supply has sufficient current to supply all

powered devices including Translator. � 4-wire powered devices only. Not for use with 2-wire powered

devices. � If using old panel as the battery-backed 12V DC supply, verify supply

and battery operation. DO NOT MOUNT IN OLD CAN… the wireless will not get out!

Installation • Hook up PIR and Glass Break power lines to external power supply.

• Alarm contact hook-up: � Works only with normally-closed contacts (alarm = open). � Remove any existing end-of-line resistors.

� Connect 4.7K end-of-line resistor (included) IN-LINE with contact. � Resistor should NOT be across (between) terminals.

Honeywell® Enrollment Sensors: RF Learning tripping enrollment mode. Set up for any behavior desired. Input Type: 3 (Supervised RF) When prompted, open/close each zone twice to enroll serial number. Ensure it is set to Loop: 2. Translator itself: RF Learning tripping enrollment mode. Zone Type: 8 (24 hour Aux) Input Type: 3 (Supervised RF), When prompted, toggle the tamper switch to enroll serial number. Loop 2 (but Loop doesn’t really

matter).

2GIG® Enrollment: Sensors: Q1 RF Sensor Set up for any behavior desired. At “Enter RF Serial Number”, press SHIFT LEARN, and trip sensor. Ensure it is set to Loop 2. Translator itself: Sensor Type: (08) 24 Hour Aux Equipment Type: (1) contact Equipment Code: (0000) other Other Equipment Code: (208) meaning RE208 Enter RF Serial Number: [press SHIFT,Learn, then toggle the tamper switch to enroll the serial number] Equipment Age: (0) new Loop Number: (2) but Loop doesn’t really matter

Dialer Delay: (1) enabled RE208_Hardwire_to_Honeywell-Compat_Translator Page 2 of 4 24-Hour Tech Support Line: (715)808-0164 30-Oct-14

www.ResolutionProducts.com

• Application Diagram

• Connection Diagram

4.7K

Contact

(Normally Closed)

Loop

x

PIRTo Enroll zone,

Open and close contact.

This sends a open/close

signal to panel.

Translator AA

Batteries DO NOT

power external

devices

Altronix AL100UL

12VDC Supply

With Lead-acid

battery

Old Panel may be used,

if operation fully verified

+12 VDC GND

PIR

Power

Input

PIR Contact

Output

(Normally

Closed)

4.7KLoop

y

Altronix TP1620

16.5VAC, 20VA

Transformer

with securing screw

Resolution

RE012

12 VDC

Power Supply

NON-Switched

Outlet

Use Battery-Backed 12VDC

if powering

PIRs or Glass Breaks

Use Non-Battery-Backed

Supply ONLY if installation is

all non-powered contacts

Power Supply polarity

DOES NOT matter!

End of Line

Resistor

New Wireless System

Existing Hardwire Sensors

New Honeywell Self-Contained System in living area

Taking over old Hardwire panel,

usually mounted in utility area

Honeywell Wireless

May use GE 60-898-ITI supply here,

if securing screw is desired

Page 2: RE208 Hardwire-to-Honeywell or 2GIG Wireless …resolutionproducts.com/wp-content/uploads/2015/01/RE208_Hardwire... · RE208 Hardwire-to-Honeywell ... PIRs or Glass Breaks could alarm

RE208_Hardwire_to_Honeywell-Compat_Translator Page 3 of 4 24-Hour Tech Support Line: (715)808-0164 30-Oct-14

www.ResolutionProducts.com

Operation

• 8 Hardwire 4.7K-ohm Zones – transmit 8 unique wireless IDs: Alarm, when device sees open circuit. Tamper, when device sees short circuit. Supervisories, every hour for each zone.

• Translator Main Zone wireless transmission (9th unique ID): Tamper, when cover opened. Low battery, when either low AA batteries, OR loss of 12V DC external. Supervisory every hour.

• LED Operation Green LED: On if AC power present. Red LED: When 12V DC is present: “Blinks” on transmit to panel;

“on” if device tamper or device low battery. Specifications

Honeywell Loop: Loop 2 for zones 1-8, Loop 4 for Translator tamper. Zone sensing duration: State sensed if held more than 600ms. End-of-line Resistors: 4.7k-ohm, 5%. Max wire run: 1000 feet. Backup batteries: Two AA Alkaline. External supply: 8.5 to 13 VDC or 6-9 VAC

Standard: Resolution RE012: 12VDC, 50mA. Optional: GE 60-898-ITI, for securing screw Wire connection polarity DOESN’T matter!

Current draw with supply: 4mA, normal operation. PIR usage: PIR may need tight voltage tolerance. Add PIR and

device current requirements together to get total current need.

AC Fail Indication: Translator ID sends Low Battery signal if its external 12V is gone for 15 minutes. Restores on external 12V restore.

AA Low Battery Conditions: Low battery for 1 minute. Restores on device tamper, external 12V restore.

AA Battery Life on AC Fail: 3-5 years, when monitoring contacts. Housing dimensions: 4x6x1 inches Specifications subject to change without notice.

Internal Picture

Terminals for Zones 1, 2

Terminals for Zones 4-8

Power Terminals

Tamper / Enroll Switch

Terminals for Zone 3

RE208_Hardwire_to_Honeywell-Compat_Translator Page 4 of 4 24-Hour Tech Support Line: (715)808-0164 30-Oct-14

www.ResolutionProducts.com

Notices “GE”, “Honeywell”, “DSC”, “2GIG” and “Napco” are trademarks owned by General Electric Company, Honeywell International Inc., Tyco Safety Products Canada LTD, 2GIG Technologies Inc., and NAPCO Security Systems, Inc., respectively. Resolution Products, Inc. products will function with one of either GE, Honeywell, DSC or Napco systems. However, no Resolution product is produced by, endorsed by, nor is officially associated with GE, Honeywell, DSC or Napco. Resolution recommends verifying proper enrollment and operation, per control panel installation instructions, at installation. Do not use Translator for life safety devices, such as smoke or CO sensors. Warranty Resolution Products, Inc. will replace products that are defective in their first five (5) years. FCC Notice

This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:

This device may not cause harmful interference. This device must accept any interference that may be received, including interference that may cause undesired operation.

Changes or modifications not expressly approved by the Resolution Products, Inc. could void the user's authority to operate this equipment.

FCC ID: U5X-RE208

IC Notice

This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1)This device may not cause interference, and (2)This device must accept any interference, including interference that may cause undesired operation of the device. Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : (1)l'appareil ne doit pas produire de brouillage, et (2)l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement. IC: 8310A-RE208