7
Installation Instructions LVLYXX 120-277 or 347VAC Recessed Linear Light Fixture GlowbackLED ® 16409 NW 8 th Ave Miami Gardens, FL 33169 1-800-679-4902 • [email protected] GlowbackLED® is a registered trademark of Bluegate Inc ©2018 Bluegate Inc. All Rights Reserved Specifications subject to change without notice WARNING! Luminaire must be installed by a qualified electrician. Refer to local codes for proper installation. To prevent shock discon- nect power before installation on service. Fixture Dimension Required Opening Weight 2” x 3” x 24” 2¼” x 3¼” x 24¼” 2¼” x 3¼” x 46¼” 2¼” x 3¼” x 68¼” 2¼” x 3¼” x 90¼” 3¼” x 3¼” x 24¼” 3¼” x 3¼” x 46¼” 3¼” x 3¼” x 68¼” 5 Lbs 7 Lbs 9 Lbs 12 Lbs 6 Lbs 9 Lbs 12 Lbs 14 Lbs 7 Lbs 10 Lbs 14 Lbs 17 Lbs 2” x 3” x 46” 2” x 3” x 68” 2” x 3” x 90” 3” x 3” x 24” 3” x 3” x 46” 3” x 3” x 68” 3” x 3” x 90” 4” x 3” x 24” 4” x 3” x 46” 4” x 3” x 68” 4” x 3” x 90” 2ft Y23 4ft Y23 6ft Y23 8ft Y23 2ft Y33 4ft Y33 6ft Y33 8ft Y33 2ft Y43 4ft Y43 6ft Y43 8ft Y43 3¼” x 3¼” x 90¼” 4¼” x 3¼” x 24¼” 4¼” x 3¼” x 46¼” 4¼” x 3¼” x 68¼” 4¼” x 3¼” x 90¼” 2.875” 3.938” 2.875” 2.938” 2.875” 1.938” Y23 Y33 Y43 & Y43C Light Fixture Direct Screw Installation Twist Clip Installation Trimless Installation Drop-Ceiling Installation Required Opening Size
Transcript
Page 1: Recessed Linear Light Fixture Mounting Instructions for ... Line Voltage... · 120-277 or 347VAC Recessed Linear Light Fixture ... Drop light fixture down into the opening that was

Installation InstructionsLVLYXX

120-277 or 347VAC Recessed Linear Light Fixture

GlowbackLED®

16409 NW 8th Ave Miami Gardens, FL 33169 1-800-679-4902 • [email protected]

GlowbackLED® is a registered trademark of Bluegate Inc ©2018 Bluegate Inc. All Rights Reserved

Specifications subject to change without notice

WARNING! Luminaire must be installed by a qualified electrician. Refer to local codes for proper installation. To prevent shock discon-nect power before installation on service.

Fixture Dimension Required Opening Weight

2” x 3” x 24” 2¼” x 3¼” x 24¼”

2¼” x 3¼” x 46¼”

2¼” x 3¼” x 68¼”

2¼” x 3¼” x 90¼”

3¼” x 3¼” x 24¼”

3¼” x 3¼” x 46¼”

3¼” x 3¼” x 68¼”

5 Lbs

7 Lbs

9 Lbs

12 Lbs

6 Lbs

9 Lbs

12 Lbs

14 Lbs

7 Lbs

10 Lbs

14 Lbs

17 Lbs

2” x 3” x 46”

2” x 3” x 68”

2” x 3” x 90”

3” x 3” x 24”

3” x 3” x 46”

3” x 3” x 68”

3” x 3” x 90”

4” x 3” x 24”

4” x 3” x 46”

4” x 3” x 68”

4” x 3” x 90”

2ft Y23

4ft Y23

6ft Y23

8ft Y23

2ft Y33

4ft Y33

6ft Y33

8ft Y33

2ft Y43

4ft Y43

6ft Y43

8ft Y43

3¼” x 3¼” x 90¼”

4¼” x 3¼” x 24¼”

4¼” x 3¼” x 46¼”

4¼” x 3¼” x 68¼”

4¼” x 3¼” x 90¼”

2.875”

3.938”

2.875”

2.938”

2.875”

1.938”

Y23 Y33 Y43 & Y43C

Light Fixture

Direct Screw Installation

Twist Clip Installation

Trimless Installation

Drop-Ceiling Installation

Required Opening Size

Page 2: Recessed Linear Light Fixture Mounting Instructions for ... Line Voltage... · 120-277 or 347VAC Recessed Linear Light Fixture ... Drop light fixture down into the opening that was

Installation InstructionsLVLYXX

120-277 or 347VAC Recessed Linear Light Fixture

GlowbackLED®

16409 NW 8th Ave Miami Gardens, FL 33169 1-800-679-4902 • [email protected]

GlowbackLED® is a registered trademark of Bluegate Inc ©2018 Bluegate Inc. All Rights Reserved

Specifications subject to change without notice

Direct Screw Installation

Framing Mounting Screw

Drywall

Light Fixture

1 2 3

5

Pass mounting screws through light fix-ture housing using pre-drilled mounting holes on rear of housing.

Secure light fixture housing to framing using screws suitable to your installation type. #6 Screw Reccommended

Lift and connect inner channel using pro-vided connectors. Refer to inner-channel assembly notes for detailed instructions.

Reccomended Installation Method!

Framing Required! Build framing on sides and top of light fixture for support. Create Opening: Refer to chart on Page 1 for re-quired opening size. Type IC: Suitable for IC contact.

Inherently Protected

4

Once the inner channel has been prop-erly connectec and installed. Snap lens into place.

Make electrical connections once light fixture installation is complete. Refer to the wiring diagram, for detailed instructions for making electrical connections.

Page 3: Recessed Linear Light Fixture Mounting Instructions for ... Line Voltage... · 120-277 or 347VAC Recessed Linear Light Fixture ... Drop light fixture down into the opening that was

Lift and connect inner channel using pro-vided connectors. Refer to inner-channel assembly notes for detailed instructions.

Twist Clip Mounting: Specialized clip secures light fixture to drywall. Create Opening: Refer to chart on Page 1 for re-quired opening size. Type IC: Suitable for IC contact.

Inherently Protected

Installation Instructions

LVLYXX 120-277 or 347VAC Recessed Linear Light Fixture

GlowbackLED®

16409 NW 8th Ave Miami Gardens, FL 33169 1-800-679-4902 • [email protected]

GlowbackLED® is a registered trademark of Bluegate Inc ©2018 Bluegate Inc. All Rights Reserved

Specifications subject to change without notice

Twist-Clip Installation

Twist Clip

Clip Screw

Drywall

Light FixtureLight Fixture

Make electrical connections once light fix-ture installation is complete. Refer to the wiring diagram, for detailed instructions for making electrical connections.

1

4

2

5

3

6

Pass twist clip bolts through pre-drilled holes on rear of rear of light fixture housing.

When clip is engaged. It will open up behind drywall to secure light fixture in place.

Twist clip bolts pass through rear of housing and are fed through

twist clip. Light fixtrure is lifted into cavity with clips hugging the side of the body

of the light fixture.

Once light fixture is lifted into place. Use a screw-driver to engage bolt. As bolt is tightened, the light fix-ture will grip onto drywall.

Page 4: Recessed Linear Light Fixture Mounting Instructions for ... Line Voltage... · 120-277 or 347VAC Recessed Linear Light Fixture ... Drop light fixture down into the opening that was

Installation Instructions

LVLYXX 120-277 or 347VAC Recessed Linear Light Fixture

GlowbackLED®

16409 NW 8th Ave Miami Gardens, FL 33169 1-800-679-4902 • [email protected]

GlowbackLED® is a registered trademark of Bluegate Inc ©2018 Bluegate Inc. All Rights Reserved

Specifications subject to change without notice

Drop Ceiling Installation

Ceiling Grid T-Grid Set Screw Light Fixture

Ceiling Tile

Grid Bracket

Light Fixture

Adjust Here

1 2 3

Adjust grid bracket as needed to acco-modate your grid structure using the screws shown.

Drop light fixture down into the opening that was created when ceiling structure was built. Make sure light fixture sits flat and grid brackets go over grid structure.

Secure light fixture to grid structure using provided set screws.

Adjustable Grid-Bracket: Adaptable to any grid structure and configuration. Opening: Refer to chart on Page 1 for required opening size. Opening created using grid-structure. Suspension: Grid system must be suspended from ceiling and able to support weights listed on Page 1. Type IC: Suitable for IC contact.

Inherently Protected

4

Once light fixture is secured to grid structures make electrical connections. Refer to the wiring diagram, for de-tailed powering instructions.

Page 5: Recessed Linear Light Fixture Mounting Instructions for ... Line Voltage... · 120-277 or 347VAC Recessed Linear Light Fixture ... Drop light fixture down into the opening that was

Framing Required! Build framing on either side of light fixture. Create Opening: Refer to chart on Page 1 for re-quired opening size. Screw Spacing: Mounting screws are required every 16” on center. #6 Screw ReccomendedType IC: Suitable for IC contact.

Inherently Protected

Installation Instructions

LVLYXX 120-277 or 347VAC Recessed Linear Light Fixture

GlowbackLED®

16409 NW 8th Ave Miami Gardens, FL 33169 1-800-679-4902 • [email protected]

GlowbackLED® is a registered trademark of Bluegate Inc ©2018 Bluegate Inc. All Rights Reserved

Specifications subject to change without notice

Twist-Clip Installation

Fram

ing

Mounting Screws

Light Fixture

Drywall

Plaster

Light FixtureLight Fixture

Drywall Tape

Contractor Tape

1

54

2 3

Mounting screws are passed through pre-drilled holes on plaster bead attached to the side of the light fixture housing.

Use compound knife for a smooth finish. Sand, paint, and finish all drywall work before removing contractor’s tape.Make electrical connections (See page 6)

Prepare Light Fixture for Plaster Work: Apply single layer of contractor’s tape to channel opening (if lens removed), or lens. Do not use multiple layers of tape. If cover-ing channel opening, make sure to cover area where lens snaps into place. Plaster Preperation: Apply single layer of drywall tape over plaster bead to avoid crack-ing. Plaster Notes: For areas experiencing regular vibration (by doors) use Durabond to avoid cracking.

DO NOT USE “Soft-Mud” (Pre-Mixed Joint Compound)

Counter-Sink flat head screws so screws sit flush with the integrated

bead.

Once light fixture has been secured to ceiling and framing, plas-ter-work can begin for trimless installa-tion look.

Page 6: Recessed Linear Light Fixture Mounting Instructions for ... Line Voltage... · 120-277 or 347VAC Recessed Linear Light Fixture ... Drop light fixture down into the opening that was

Installation Instructions

LVLYXX 120-277 or 347VAC Recessed Linear Light Fixture

GlowbackLED®

16409 NW 8th Ave Miami Gardens, FL 33169 1-800-679-4902 • [email protected]

GlowbackLED® is a registered trademark of Bluegate Inc ©2018 Bluegate Inc. All Rights Reserved

Specifications subject to change without notice

Linking Plate

Hex Key

Linkable Connector

Inner Channel

Inner Channel

Set screw

Hex Key

Linkable/Continous Run Connections

Inner Clip Connection

Use linking plate, linkable connectors, and hex key to acheive continous runs. Firmly insert male connector from one fixture to the next

Using provided hex-key, secure linking plate to both light fixtures. Insert inner channel and lens once electrical connectins have been made.

PINCH!

“CLICK!!!”1 2 3

Pinch the tabs at the bottom of the inner clips.

Drop light fixture down into the opening that was created when ceiling structure was built. Make sure light fixture sits flat and grid brackets go over grid structure.

Drop light fixture down into the opening that was created when ceiling structure was built. Make sure light fixture sits flat and grid brackets go over grid structure.

Make sure that every clip is engaged and resting in its locked position.

Before inserting in-ner-channel be sure to make electrical connec-tions using the provided connectors. Connection should be secure.

Page 7: Recessed Linear Light Fixture Mounting Instructions for ... Line Voltage... · 120-277 or 347VAC Recessed Linear Light Fixture ... Drop light fixture down into the opening that was

Installation Instructions

LVLYXX 120-277 or 347VAC Recessed Linear Light Fixture

GlowbackLED®

16409 NW 8th Ave Miami Gardens, FL 33169 1-800-679-4902 • [email protected]

GlowbackLED® is a registered trademark of Bluegate Inc ©2018 Bluegate Inc. All Rights Reserved

Specifications subject to change without notice

Power-Feed Entry and Electrical Connections

Non-Dimmable Configuration

Dimmable Configuration

Encap Power EntryAcess electrical using knockouts on endcap.

Rear Power EntryAcess electrical using knockouts on rear of light fixture (2).

White | Neutral

Purple | Dim +

Gray | Dim -Green | Ground

Black | Line Internal Driver

On

Off

Light Fixture

Dimming wires capped when not in use

White | NeutralPurple | Dim +

Gray | Dim -Green | Ground

Black | Line Internal Driver

0-10V Dimmer

Light Fixture

0-10V Dimmable Standard | Other Controls Available

Note: For Emergency Back-Up, Follow Battery Manufacturer Instructions


Recommended