"REDBRICK" BUILDING ANNEX RENOVATION TAMPA, FL STATE OF FLORIDA DEPARTMENT OF MILITARY AFFAIRS FDMA PROJECT NUMBER 215004 PROJECT LOCATION: 2316 W LEMON STREET STREET, TAMPA, FL 33606 LOCATION MAP SHEET INDEX GENERAL G0.1 COVER SHEET G0.2 GENERAL INFORMATION AND ABBREVIATIONS G0.3 CODE ANALYSIS LS1.1 FIRST FLOOR LIFE SAFETY PLAN LS1.2 SECOND FLOOR LIFE SAFETY PLAN CIVIL C001 OVERALL EXISTING SITE PLAN C002 SITE DEMO / EROSION CONTROL PLAN C101 SITE DEVELOPMENT PLAN C201 GRADING AND DRAINAGE PLAN C301 UTILITY PLAN C401 SITE DETAILS ARCHITECTURAL AD1.1 DEMOLITION FIRST FLOOR PLAN AD1.2 DEMOLITION SECOND FLOOR PLAN AD1.3 DEMOLITION ROOF PLAN AD3.1 DEMOLITION BUILDING ELEVATIONS AD9.1 DEMOLITION FIRST FLOOR REFLECTED CEILING PLAN AD9.2 DEMOLITION FIRST FLOOR REFLECTED CEILING PLAN A1.1 FIRST FLOOR PLAN A1.2 SECOND FLOOR PLAN A2.1 ROOF PLAN A3.1 RENOVATED BUILDING ELEVATIONS A4.1 BUILDING SECTION AND WALL SECTIONS A4.2 PORCH COLUMN AND BARRIER FENCE A4.3 ELEVATOR PLAN AND DETAILS A5.1 STAIR DETAILS A6.1 DOORS AND WINDOWS A6.2 DOOR AND STROREFRONT DETAILS A7.1 PARTITION TYPES AND UL505 1-HR CEILING-FLOOR ASSEMBLY A7.2 UL419 1-HR AND 2-HR WALL ASSEMBLY A7.3 PEI AER-09038 2-HR HORIZONTAL ASSEMBLY A8.1 ENLARGED TOILET ROOM AND BREAKROOM PLANS A8.2 ENLARGED TOILET ROOM PLANS A8.3 ENLARGED TOILET ROOM ELEVATIONS A9.1 FIRST FLOOR REFLECTED CEILING PLAN A9.2 SECOND FLOOR REFLECTED CEILING PLAN ID1.0 FINISH SCHEDULES ID2.0 FLOOR TRANSITIONS AND SIGNAGE STRUCTURAL S0.1 STRUCTURAL SYMBOLS AND LEGEND S0.2 GENERAL NOTES S0.3 GENERAL NOTES 5032 GODDARD AVENUE, SUITE A, ORLANDO, FL 32804 TELEPHONE: (407)245-3660 ARCHITECTURAL GROUP, INC. [email protected] FL. LIC. # AA0002264 PROJECT TEAM Cocoa, Florida 32922 EB #0000015 874 Dixon Boulevard Phone: 321-636-0274 Fax: 321-639-8986 www.tlc-engineers.com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email protected] COPYRIGHT © 2015 MRI ARCHITECTURAL GROUP INC. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 15 06/22/15 PETER M. IKEGAMI AR0013065 8/9/2015 12:40:09 PM C:\Users\PIkegami\Documents\A4 -2014 MRI - Proposals\1411 - Tampa Armory\DMS TAMPA- REDBRICK BUILDING BID AND RESPONSE TO BLDG.rvt G0.1 RJV PMI FDMA PROJECT NO. 215004 COVER SHEET "RED BRICK" BUILDING ANNEX TAMPA NATIONAL GUARD ARMORY DEPARTMENT OF MILITARY AFFAIRS ST AUGUSTINE, FLORIDA PERMIT AND CONSTRUCT 1 RESPONSE TO BLDG DEPT 07-27-15 2 RESPONSE TO FIRE MARSHAL 08-07-15
Transcript
Page 1: REDBRICK BUILDING ANNEX RENOVATION TAMPA, FL - Florida€¦ · "redbrick" building annex renovation tampa, fl state of florida department of military affairs fdma project number 215004

"REDBRICK" BUILDING ANNEX RENOVATION TAMPA, FLSTATE OF FLORIDA DEPARTMENT OF MILITARY AFFAIRS FDMA PROJECT NUMBER 215004

PROJECT LOCATION: 2316 W LEMON STREET STREET, TAMPA, FL 33606

LOCATION MAP

N

SHEET INDEXGENERALG0.1 COVER SHEETG0.2 GENERAL INFORMATION AND ABBREVIATIONSG0.3 CODE ANALYSISLS1.1 FIRST FLOOR LIFE SAFETY PLANLS1.2 SECOND FLOOR LIFE SAFETY PLAN

CIVILC001 OVERALL EXISTING SITE PLANC002 SITE DEMO / EROSION CONTROL PLANC101 SITE DEVELOPMENT PLANC201 GRADING AND DRAINAGE PLANC301 UTILITY PLANC401 SITE DETAILS

ARCHITECTURALAD1.1 DEMOLITION FIRST FLOOR PLANAD1.2 DEMOLITION SECOND FLOOR PLANAD1.3 DEMOLITION ROOF PLANAD3.1 DEMOLITION BUILDING ELEVATIONSAD9.1 DEMOLITION FIRST FLOOR REFLECTED CEILING PLANAD9.2 DEMOLITION FIRST FLOOR REFLECTED CEILING PLANA1.1 FIRST FLOOR PLANA1.2 SECOND FLOOR PLANA2.1 ROOF PLANA3.1 RENOVATED BUILDING ELEVATIONSA4.1 BUILDING SECTION AND WALL SECTIONSA4.2 PORCH COLUMN AND BARRIER FENCEA4.3 ELEVATOR PLAN AND DETAILSA5.1 STAIR DETAILSA6.1 DOORS AND WINDOWSA6.2 DOOR AND STROREFRONT DETAILSA7.1 PARTITION TYPES AND UL505 1-HR CEILING-FLOOR ASSEMBLYA7.2 UL419 1-HR AND 2-HR WALL ASSEMBLYA7.3 PEI AER-09038 2-HR HORIZONTAL ASSEMBLYA8.1 ENLARGED TOILET ROOM AND BREAKROOM PLANSA8.2 ENLARGED TOILET ROOM PLANSA8.3 ENLARGED TOILET ROOM ELEVATIONSA9.1 FIRST FLOOR REFLECTED CEILING PLANA9.2 SECOND FLOOR REFLECTED CEILING PLANID1.0 FINISH SCHEDULESID2.0 FLOOR TRANSITIONS AND SIGNAGE

STRUCTURALS0.1 STRUCTURAL SYMBOLS AND LEGENDS0.2 GENERAL NOTESS0.3 GENERAL NOTES

5032 GODDARD AVENUE, SUITE A, ORLANDO, FL 32804TELEPHONE: (407)245-3660

ARCHITECTURAL GROUP, INC.

[email protected] FL. LIC. # AA0002264

PROJECT TEAM

Cocoa, Florida 32922

EB #0000015

874 Dixon Boulevard

Phone: 321-636-0274Fax: 321-639-8986www.tlc-engineers.com

VICINITY MAP

PROJECT LOCATIONN NTSTAMPA, FLORIDA

BUILDING DATA AND PROJECT DESCRIPTION

S0.4 WIND PRESSURE DIAGRAMS1.1 FOUNDATION PLANS1.2 SECOND FLOOR FRAMING PLANS1.3 ROOF FRAMING PLANS2.1 STRUCTURAL SECTIONS AND DETAILSS2.2 STRUCTURAL SECTIONS AND DETAILSS2.3 STRUCTURAL SECTIONS AND DETAILSS2.4 STRUCTURAL SECTIONS AND DETAILSS2.5 STRUCTURAL SECTIONS AND DETAILS

MECHANICALM0.1 MECHANICAL LEGEND AND NOTESMD1.1 MECHANICAL FIRST FLO0R DEMOLITION PLANMD1.2 MECHANICAL SECOND FLOOR DEMOLITION PLANM1.1 MECHANICAL FIRST FLOOR PLANM1.2 MECHANICAL SECOND FLOOR PLANM4.0 MECHANICAL DETAILSM4.1 MECHANICAL CONTROLSM5.0 MECHANICAL SCHEDULESM5.1 MECHANICAL LOAD CALCULATIONS

PLUMBINGP0.1 PLUMBING LEGEND, NOTES, AND SCHEDULESPD1.1 PLUMBING FIRST FLOOR DEMOLITION PLANPD1.2 PLUMBING SECOND FLOOR DEMOLITION PLANP1.1 PLUMBING FIRST FLOOR GRAVITY PLANP1.2 PLUMBING SECOND FLOOR GRAVITY PLANP2.1 PLUMBING FIRST FLOOR PRESSURE PLANP2.2 PLUMBING SECOND FLOOR PRESSURE PLANP3.0 PLUMBING RISER DIAGRAMSP4.0 PLUMBING DETAILS

FIRE PROTECTIONF0.1 FIRE PROTECTION LEGEND, NOTES AND DETAILSF1.1 FIRE PROTECTION FIRST FLOOR PLANF1.2 FIRE PROTECTION SECOND FLOOR PLAN

ELECTRICALE0.1 ELECTRICAL LEGEND AND NOTESE1.0 ELECTRICAL SITE PLANED1.1 FIRST FLOOR ELECTRICAL DEMOLITION PLANED1.2 SECOND FLOOR ELECTRICAL DEMOLITION PLANE1.1 FIRST FLOOR LIGHTING PLANE1.2 SECOND FLOOR LIGHTING PLANE2.1 FIRST FLOOR POWER AND SYSTEMS PLANE2.2 SECOND FLOOR POWER AND SYSTEMS PLANE3.1 ELECTRICAL ONE-LINE DIAGRAME4.1 ELECTRICAL SCHEDULESE4.2 PANEL SCHEDULESE5.1 ELECTRICAL DETAILSE5.2 ELECTRICAL DETAILS

PERMIT AND CONSTRUCT

1

2

GENERAL PROJECT DESCRIPTION:PROJECT INCLUDES A RENOVATION TO AN EXISTING HISTORIC BUILDING.

INTERIOR WORK:SCOPE OF WORK INCLUDES INTERIOR RENOVATIONS AND MINOR INTERIOR STRUCTURAL MODIFICATIONS (TO THE EXISTING INTERIOR LOAD BEARINGWALLS TO ALLOW FOR THE CONSTRUCTION OF A NEW AMERICAN'S WITH DISABILITIES ACT (ADA) COMPLIANT ELEVATOR, NEW LIFE SAFETYSTAIRWAY, AND ENLARGEMENT OF EXISTING SPACES FOR A NEW MULTI-PURPOSE HALL). INTERIOR RENOVATIONS INCLUDE RELOCATION AND BUILD-OUT FOR NEW ADA TOILET ROOMS AND ADA SHOWERS, AN SUPPLY AND WEAPON'S ARMORY, AND OFFICES. MECHANICAL WORK INCLUDES NEWHVAC SYSTEMS. PLUMBING WORK INCLUDES NEW PLUMBING WORK INCLUDES NEW SANITARY AND SUPPLY WATER LINES AND FIXTURES. NEWELECTRICAL WORK INCLUDES NEW POWER AND DATA SYSTEMS.

EXTERIOR WORK:THE EXTERIOR WORK IS LIMITED TO REPLACEMENT AND REPAIR OF WOOD ROT AND REPAIR TO DAMAGE OF EXISTING BRICK WORK. EXTERIORWINDOWS WILL BE REPLACED WITH NEW THERMALLY EFFICIENT WINDOWS AND NEW STOREFRONT FRAMES WILL MATCH CURRENT MULLIONPRESENTATION OF EXISTING. EXISTING EXTERIOR HOLLOW METAL DOORS WILL BE REFINISHED TO MATCH EXISTING.

SITEWORK:SITE WORK IS LIMITED TO REGRADING AND RE-PAVING OF DETERIORATED ASPHALT THAT OCCURS AT FRONT (WEST SIDE) OF BUILDING . PARKINGLOT STRIPING WILL ALSO BE IDENTIFIED OVER NEW RE-PAVING AND OVER EXISTING PAVING TO REMAIN. EXISTING DETERIOATED SIDEWALKS AROUNDTHE BUILDING WILL ALSO BE REPLACED. A NEW DECORATIVE SECURITY WALL AND FENCE WILL BE DESIGNED AND LOCATED ON N. HOWARD STREET(EAST SIDE) OF BUILDING ATHE THE INTERSECTION OF CASS STREET TO PREVENT VEHICLES FROM RUNNING INTO PROPERTY AND BUILDING (THEREHAVE BEEN TWO INCIDENTS IN PAST YEARS WHERE CARS HAVE CRASHED INTO THIS BUILDING). LANDSCAPING WILL BE PROVIDED, BUT MUST MEETTHE CRITERIA OF THE GOVERNMENTS FORCE PROTECTION / ANTI-TERRORISM CRITERIA.

SITE UTILITIES WORK:EXISTING SITE UTILITIES WILL BE REPLACED FROM BUILDING TO POINTS OF SERVICE DUE TO UNCERTAINTY OF CONDITION AND AGE OF SYSTEMS.

BUILDING DATA:ADDRESS:2316 W LEMON STREETTAMPA, FL 33606

LEGAL DESCRIPTION OF PROPERTY:ALL OF BLOCK 6, BENJAMIN'S 4TH ADDITION, ACCORDING TO MAP OR PLAT THEREOF AS RECORDED IN PLATBOOK 2, PAGE 60, OF THE PUBLIC RECORDS OF HILLSBOROUGH COUNTY, FLORIDA TOGETHER WITH VACATEDALLEY WAYS LYING WITHIN SAID BLOCK.

TOGETHER WITH:THE SOUTHWEST QUARTER (SW1/4) OF THE NORTHWEST QUARTER (NW1/4) OF SECTION TWENTY-THREE(23), TOWNSHIP TWENTY-NINE (29) SOUTH, RANGE EIGHTEEN (18) EAST, LESS RIGHTS OF WAY FOR EXISTINGSTREETS ALONG THE EXTERIOR BOUNDARIES OF SAID TRACT, SAID TRACT COMMONLY KNOWN AS FORTHOMER HESTERLY AND FORMALLY KNOWN AS BENJAMIN FIELD.

1

2

ARCHITECTURAL GROUP, INC.

A

B

C

1 2 3 4

D

E

F

G

H

5 6 7 8 9 10

J

K

L

M

11 12 13 14

PROJECT TITLE AND OWNERS NAME

CONSULTANTS

SEAL AND SIGNATURE

REVISIONS

DRAWN BY

CHECKED BY

JOB NUMBER

DATE

DRAWING TITLE

DRAWING NUMBER

SHEET OF

FL LIC. # AA0002264

5032 GODDARD AVENUEORLANDO, FLORIDA 32804(407) [email protected]

COPYRIGHT © 2015 MRI ARCHITECTURAL GROUP INC.

1 2 3 4 5 6 7 8 9 10 11 12 13 14

15

15

06/22/15

PETER M. IKEGAMIAR0013065

8/9/

2015

12:

40:0

9 P

MC

:\Use

rs\P

Ikeg

ami\D

ocum

ents

\A4

-201

4 M

RI -

Pro

posa

ls\1

411

- Tam

pa A

rmor

y\D

MS

TAM

PA-

RED

BR

ICK

BU

ILD

ING

BID

AN

D R

ESPO

NS

E TO

BLD

G.rv

t

G0.1

RJV

PMI

FDMA PROJECT NO.215004

COVER SHEET

"RED BRICK"BUILDING ANNEXTAMPA NATIONALGUARD ARMORY

DEPARTMENT OFMILITARY AFFAIRSST AUGUSTINE, FLORIDA

PERMIT ANDCONSTRUCT

1 RESPONSE TO

BLDG DEPT

07-27-15

2 RESPONSE TO

FIRE MARSHAL

08-07-15

Page 2: REDBRICK BUILDING ANNEX RENOVATION TAMPA, FL - Florida€¦ · "redbrick" building annex renovation tampa, fl state of florida department of military affairs fdma project number 215004

PLUMBING CALCULATIONS

PLUMBING CALCULATIONS: 2010 FBC PLUMBING CODE

BUSINESS OCCUPANCY (CALCULATED PER FLORIDA FIRE PREVENTION CODE AND FLORIDA BUILDING CODE) = 57 PEOPLE

MEN AND WOMEN WC = 1/25 FOR FIRST 50 AND 1/50 THERE AFTER:= (1/25 X 50) + (1/50 X 7 PEOPLE) = 2.14 TOTAL WCREQUIRED WC = 2 + 0.14 = 2.14 WC = 1.07 MENS WC AND 1.07 WOMENS WC

MEN AND WOMEN LAV = 1/40 FOR FIRST 50 AND 1/80 THERE AFTER:= (1/40 X 40) + (1/80 X 17 PEOPLE) = 1.21 TOTAL LAVSREQUIRED LAV = 1 + 0.21 = 1.21 LAV = 0.61 MEN LAV AND 0.61 WOMENS LAV

DRINKING FOUNTAINS = 1/100 = 57 X 1/100 = .57 DF

ASSEMBLY OCCUPANCY (175 PEOPLE):= 175 PEOPLE = 87.5 MEN AND 87.5 WOMEN

REQUIRED MEN WC = 1/125 = 1/125 X 87.5 = 0.7 MEN WCREQUIRED WOMEN WC = 1/65 = 1/65 X 87.5 = 1.34 WOMEN WCTOTAL LAV REQUIRED = 1/200 = 1/200 X 175 = 0.87 LAVREQUIRED MEN LAV = 0.44 MEN LAVREQUIRED WOMEN LAV = 0.44 WOMEN LAV

DF = 1/500 = 1/500 X 175 = 0.35 DF1 SERVICE SINK REQUIRED

REQUIRED AND PROVIDED TOILET FIXTURESMEN WC REQUIRED = 1.07 BUSINESS + 0.70 ASSEMBLY = 1.77 = MEN WC REQUIRED, 6 MEN WC PROVIDED

WOMEN WC REQUIRED = 1.07 BUSINESS + 1.34 ASSEMBLY = 2.41 WOMEN WC REQUIRED, 3 WOMEN WC PROVIDED

MEN LAV REQUIRED = 0.61 BUSINESS + 0.44 ASSEMBLY = 1.05 MEN LAV REQUIRED,3 MEN LAV PROVIDED

WOMEN LAV REQUIRED = 0.61 BUSINESS + 0.44 ASSEMBLY = 1.05 WOMEN LAV REQUIRED, 3 WOMEN LAV PROVIDED

SERVICE SINKS REQUIRED: 0 BUSINESS + 1 ASSEMBLY = 1 SERVICE SINKS REQUIRED, 1 SERVICE SINKS PROVIDED

DRINKING FOUNTAINS REQUIRED: 1 REQUIRED, 4 PROVIDED

SHOWERS REQUIRED: 0 SHOWER REQUIRED, 4 SHOWERS PROVIDED (2 MEN AND 2 WOMEN)

CODE DATACODE REFERENCE

OCCUPANCY CLASSIFICATIONFBC 2010, SECTION 304: BUSINESS OCCUPANCY WITH ASSEMBLY A-3 (ACCESSORY USE)

OCCUPIED AREA FIRST FLOOR: 3,515 SF = 874 SF ASSEMBLY + 2,858 SF + (657 SF TOILET ROOMS)OCCUPIED AREA SECOND FLOOR: 3,277 SF (OMITS STAIR AND ELEVATOR OPENINGS) + 2,815 SF +(462 SF TOILET ROOMS AND HVAC ROOM)

OCCUPANT LOAD FIRST FLOOR:BUSINESS OCCUPANCY = 2,858 SF X 1 PERSON/100 SF = 28.5= 29 PEOPLEASSEMBLY OCCUPANCY = 874 SF X 1 PERSON / 5 SF = 175 PEOPLE

OCCUPANT LOAD SECOND FLOOR:BUSINESS OCCUPANCY = 2,815 SF X 1 PERSON/100 SF = 28.1= 28 PEOPLE

TYPE OF CONSTRUCTIONFBC 2010, SECTION 602.5, TABLE 601 TYPE VB, SPRINKLERED

HEIGHT AND AREA LIMITATIONSFBC 2010, TABLE 503:MAXIMUM AREA = 9,000 SF, SECTION 503.3, SPRINKLEREDMAXIMUM HEIGHT = 2 STORIES

MAXIMUM TRAVEL DISTANCE:FBC 2010, TABLE 1016.1, OCCUPANCY B:SPRINKLERED = 300'-0"NON-SPRINKLERED = 200'-0"

SINGLE EXIT:75'-0"

DEAD ENDS: 20'-0" MAX

COMMON PATH OF TRAVELFBC 2010, SECTION 1014.3, = 75'-0"

LEVEL OF ALTERATION

EXISTING HISTORIC BUILDING:2-STORY - MASONRY LOAD BEARING WALLS, SECOND FLOOR WOOD STRUCTURE, PRE-ENGINEERED WOOD ROOF TRUSSES.

EXISTING BUILDING AREA = 3,515 SF FIRST FLOOR + 3,277 SF SECOND FLOOR = 6,792 SF

FBC 2010, SECTION 404: LEVEL 2

FIRE RESISTANCE RATING REQUIREMENTSFBC 2010, TABLE 601: NONE REQUIRED

FIRE SEPARATION RATINGSFBC 2010, TABLE 508.4: BUSINESS AND ASSEMBLY SEPARATION:1 HR SPRINKLERED2 HRS NON-SPRINKLERED.

VERTICAL SHAFTS: STAIRS AND ELEVATORS: 1 HR

FLORIDA BUILDING CODE FLORIDA BUILDING CODE 2010

LIFE SAFETY CODE FLORIDA BUILDING CODE 2010FLORIDA FIRE PREVENTION CODE 5TH EDITIONNFPA 1, LIFE SAFETY CODE 2012 EDITIONNFPA 101, LIFE SAFETY CODE 2012 EDITIONNFPA 10, INSTALLATION OF PORTABLE FIRE EXTINGUISHERS 2012 EDITIONNFPA 13, AUTOMATIC SPRINKLER SYSTEMS, 2010 EDITIONNFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES, 2010 EDITIONNFPA 72, NATIONAL FIRE ALARM CODE, 2012 EDITION

PLUMBING CODE FLORIDA PLUMBING CODE 2010

ELECTRICAL CODE FLORIDA BUILDING CODE 2010 / NATIONAL ELECTRIC CODE 2011

MECHANICAL CODE FLORIDA MECHANICAL CODE 2010

ACCESSIBILITY CODE FLORIDA ACCESSIBILITY CODE 2010

FBC 2010 SECTION 1021 "NUMBER OF EXITS"FBC 2010, SECTION 1021.2 "SINGLE EXITS" FROM SECOND STORY:TABLE 1021.2MAXIMUM NUMBER OF OCCUPANTS = 29 PEOPLEMAXIMUM TRAVEL DISTANCE = 75'-0" MAX.

2010 FLORIDA FIRE PREVENTION CODE38.2.4.3 A single exit shall be permitted for a room or area with a totaloccupant load of less than 100 persons, provided that all of the followingcriteria are met:(1) The exit shall discharge directly to the outside at the level of exitdischarge for the building.(2) The total distance of travel from any point, including travel within theexit, shall not exceed 100 ft (30 m).(3) The total distance of travel specified in 38.2.4.3(2) shall be on the samestory, or, if traversing of stairs is necessary, such stairs shall not exceed15 ft (4570 mm) in height, and both of the following also shall apply:(a) Interior stairs shall be provided with complete enclosures to separatethem from any other part of the building, with no door openings therein.(b) A single outside stair in accordance with 7.2.2 shall be permitted toserve all stories permitted within the 15 ft (4570 mm) vertical travellimitation.

THIS PROJECT WAS PRE-REVIEWED BY FOR ONE SECOND FLOOR EXIT:KARL K. THOMPSON, CFPSENGINEERING, IVBUREAU OF FIRE PREVENTIONDIVISION OF STATE FIRE MARSHAL200 E. GAINES STREETTALLAHASSEE, FL 32399-0342

FLORIDA PRODUCT APPROVAL

ROOF SYSTEM: EXISTING TO REMAIN

SOFFIT SYSTEM: EXISTING TO REMAIN

PARAPET COPINGS AND FLASHINGS: EXISTING TO REMAIN.

EXTERIOR WALL SYSTEMS: EXISTING TO REMAIN. REFER TOSTRUCTURAL DRAWINGS FOR WINDOW AND DOOR INFILLS WHEREUNITS ARE TO BE REMOVED.

EXTERIOR DOORS: EXISTING TO REMAIN

ALUMINUM REPLACEMENT WINDOWS WITH 1" INSUALTED LOW-EGLASS: REFER TO STRUCTURAL DRAWINGS FOR WIND PRESSURESCHEDULE.

YKK YVS-410 TUH SERIES IMPACT RATED, LARGE MISSILE SINGLE HUNGOPERABLE WINDOWS. FLORIDA PRODUCT APPROVAL FL12217-R2

YKK YFW-400 TUH SERIES IMPACT RATED, LARGE MISSILE HUNGWINDOWS. FLORIDA PRODUCT APPROVAL FL13239-R2

ALUMINUM LOUVERS:

GREENHECK MODEL EHH601D RAINPROOF WALL LOUVER. FLORIDAPRODUCT APPROVAL FL 10088.1, MIAMI DADE NOA 12-0830.08

ARMORY VAULT CLASSIFICATIONSELF CONTAINED AND FIRE RATED (INCLUDING ALL PENETRATIONS) FORHAZARD GROUP 2 CLASSIFICATION FOR EXPLOSIVES (EXCEPTION FROM H-1 OCCUPANCY FBC 307.3) FOR TYPES, QUANTITIES AND WEIGHTS OFAMMUNITION TO BE STORED: GSA AA-V-2737 Approved MEGAvault ModularVault Panel System Meeting Army Regulation AR 190-11, Physical Security ofArms, Ammo & Explosives. Panel thickness: 4", 2 HOUR FIRE SEPARATIONFROM BUSINESS OCCUPANCY.

FIRE SEPARATION FROM ARMORY VAULT AND BUSINESSOCCUPANCY:FBC SECTION 307.3 HIGH HAZARD GROUP 1 EXCEPTION TO PERMITTEDTO HAZARD GROUP 2. FIRE SEPARATION 2 HOURS PER TABLE 508.4HBUSINESS FROM H-2 = 2 HOURS FOR SPRINKLERD BUILDING.

1

1

1

1 ARCHITECTURAL GROUP, INC.

A

B

C

1 2 3 4

D

E

F

G

H

5 6 7 8 9 10

J

K

L

M

11 12 13 14

PROJECT TITLE AND OWNERS NAME

CONSULTANTS

SEAL AND SIGNATURE

REVISIONS

DRAWN BY

CHECKED BY

JOB NUMBER

DATE

DRAWING TITLE

DRAWING NUMBER

SHEET OF

FL LIC. # AA0002264

5032 GODDARD AVENUEORLANDO, FLORIDA 32804(407) [email protected]

COPYRIGHT © 2015 MRI ARCHITECTURAL GROUP INC.

1 2 3 4 5 6 7 8 9 10 11 12 13 14

15

15

06/22/15

PETER M. IKEGAMIAR0013065

8/9/

2015

12:

40:1

0 P

MC

:\Use

rs\P

Ikeg

ami\D

ocum

ents

\A4

-201

4 M

RI -

Pro

posa

ls\1

411

- Tam

pa A

rmor

y\D

MS

TAM

PA-

RED

BR

ICK

BU

ILD

ING

BID

AN

D R

ESPO

NS

E TO

BLD

G.rv

t

G0.3

PMI

JLR

FDMA PROJECT NO.215004

CODE ANALYSIS

"RED BRICK"BUILDING ANNEXTAMPA NATIONALGUARD ARMORY

DEPARTMENT OFMILITARY AFFAIRSST AUGUSTINE, FLORIDA

PERMIT ANDCONSTRUCT

1 RESPONSE TO

BLDG DEPT

07-27-15

Page 3: REDBRICK BUILDING ANNEX RENOVATION TAMPA, FL - Florida€¦ · "redbrick" building annex renovation tampa, fl state of florida department of military affairs fdma project number 215004

4. SEMI RECESSED FIRE EXTINGUISHER CABINETAND EXTINGUISHER PER NFPA 10, STANDARDFOR PORTABLE FIRE EXTINGUISHERS, LATESTEDITION

WALL MOUNTED FIRE EXTINGUISHER PERNFPA 10, STANDARD FOR PORTABLE FIREEXTINGUISHERS, LATEST EDITION

FEC

FE

1-HR FIRE-RATED WALL CONSTRUCTION

EXIT LIGHT

2. RECESSED FIRE EXTINGUISHER CABINET AND #10 ABC FIRE EXTINGUISHER PER LATESTEDITION NFPA 10, STANDARD FOR PORTABLEFIRE EXTINGUISHERS. ALL FE WITHINCORRIDORS AND LOBBIES SHALL BE IN A SEMI-RECESSED FIRE EXTINGUISHER CABINET. ALLFIRE EXTINGUISHERS IN STORAGE ROOMSSHALL BE SURFACE MOUNTED. FIREEXTINGUISHERS SHALL BE LOCATED SO THAT,FROM ANY POINT WITH IN THE BUILDING, THETRAVEL DISTANCE TO THE EXTINGUISHER ISLESS THAN 50'-0".

3.

5.

6.

1. FOR BUILDING CODE AND LIFE SAFETYINFORMATION AND PLUMBING CALCULATIONSSEE SHEET G0.3 CODE ANALYSIS.

P34"[864]

1707.EXIT UNIT WIDTH AND NUMBEROF PEOPLE EXIT WILLACCOMMODATE

EMERGENCY LIGHT. SEE ELECTRICAL8.

LIFE SAFETY NOTES

REFER TO ELECTRICAL SHEETS FORADDITIONAL LIFE SAFETY DEVICES NOTSHOWN ON THIS SHEET.

9.

750 SF HATCHED AREA750 SF / 7 SF PER PERSON = 107 PEOPLE

DRILL HALL108

3500 LBELEVATOR

103HVAC RM 1

107

IT110B

BREAKROOM106

W TLT104

M TLT101

HA SHWR101B

HA SHWR104A

BRICK WALLINFILLAND FINISHBRICK ATDEMOLISHED DOOR

SUPPLY114

SUPPLYDISTRIBUTION

111

HVAC114A

NEW STRUCTURAL BEAM

EXISTING BEARING WALLS TO REMAIN

EXISTING BEARING WALLS TO REMAIN

EXISTING BEARING WALLS TO REMAIN

EXISTINGOPENING INEXISTINGBEARINGWALL

NEWOPENING INEXISTINGBEARINGWALL

FIRE STAIRS100A

ARMORYVAULT

112

SUPPLY DISTRIBUTION COUNTER?

SUPPLY113

300 SF

STORAGE109

SUPPLY115

CORR102

ELECT110

NEW WINDOWAND BRICK INFILLBELOW INEXISTING DOOROPENING

FIRESPRINKLER

RISER105

109

115

114A

114

112

111A

108A

108B

100A

101

104

107

110B

106B

108C

100B

102

P54 27

0

P54 27

0P

34"

170

P34

"17

0

P34

"17

0

P34"170

FE

FE

FEC

FEC

BRICK WALLINFILLAND FINISHBRICK ATDEMOLISHED DOOR

PROPERTY LINE: REFER TO CIVIL DRAWINGS

AUTOMOTIVE BARRIER: REFER TO CIVIL DRAWINGS

EMERGENCYLIGHT ABOVE

EMERGENCYLIGHT ABOVE

EMER

GENC

YLIG

HT A

BOVE

EMER

GENC

YLIG

HT A

BOVE

EMER

GENC

YLIG

HT A

BOVE

EMER

GENC

YLIG

HT A

BOVE

EMER

GENC

YLIG

HT A

BOVE

EMERGENCY

LIGHT AB0V

E

EMERGENCYLIGHT AB0VENOTE: 2-HR UL 505 CEILING FLOOR

ASSEMBLY ABOVE SUSPENEDACOUSTICAL CEILING SYSTEM WITHINROOMS 100, 100A, 110 AND 110B.

THIS FLOOR ONLY: HATCHDENOTES 1-HOUR UL505 CEILING -FLOOR ASSEMBLY AT ROOM 108,110, 110B AND 100 (FIRST FLOORONLY)

THIS BUILDING WILL BE PROTECTEDBY A FIRE SPRINKLER SYSTEM

EM LI

GHT

111B

EMER

GENC

YLIG

HT A

B0VE

S-7 OCCUPANCY LOAD

RATED EXIT100

2

(2-HR D00R W/2-HR GLAZING)

2

ARCHITECTURAL GROUP, INC.

A

B

C

1 2 3 4

D

E

F

G

H

5 6 7 8 9 10

J

K

L

M

11 12 13 14

PROJECT TITLE AND OWNERS NAME

CONSULTANTS

SEAL AND SIGNATURE

REVISIONS

DRAWN BY

CHECKED BY

JOB NUMBER

DATE

DRAWING TITLE

DRAWING NUMBER

SHEET OF

FL LIC. # AA0002264

5032 GODDARD AVENUEORLANDO, FLORIDA 32804(407) [email protected]

COPYRIGHT © 2015 MRI ARCHITECTURAL GROUP INC.

1 2 3 4 5 6 7 8 9 10 11 12 13 14

15

15

06/22/15

PETER M. IKEGAMIAR0013065

8/9/

2015

12:

40:1

2 P

MC

:\Use

rs\P

Ikeg

ami\D

ocum

ents

\A4

-201

4 M

RI -

Pro

posa

ls\1

411

- Tam

pa A

rmor

y\D

MS

TAM

PA-

RED

BR

ICK

BU

ILD

ING

BID

AN

D R

ESPO

NS

E TO

BLD

G.rv

t

LS1.1

PMI

JLR

FDMA PROJECT NO.215004

FIRST FLOOR LIFESAFETY PLAN

"RED BRICK"BUILDING ANNEXTAMPA NATIONALGUARD ARMORY

DEPARTMENT OFMILITARY AFFAIRSST AUGUSTINE, FLORIDA

PERMIT ANDCONSTRUCT

12'8'4'2'0

1/4" = 1'-0"

N

1/4" = 1'-0"LS1.1

A1 FIRST FLOOR LIFESAFETY PLAN

2 RESPONSE TO

FIRE MARSHAL

08-07-15

Page 4: REDBRICK BUILDING ANNEX RENOVATION TAMPA, FL - Florida€¦ · "redbrick" building annex renovation tampa, fl state of florida department of military affairs fdma project number 215004

4. SEMI RECESSED FIRE EXTINGUISHER CABINETAND EXTINGUISHER PER NFPA 10, STANDARDFOR PORTABLE FIRE EXTINGUISHERS, LATESTEDITION

WALL MOUNTED FIRE EXTINGUISHER PERNFPA 10, STANDARD FOR PORTABLE FIREEXTINGUISHERS, LATEST EDITION

FEC

FE

1-HR FIRE-RATED WALL CONSTRUCTION

EXIT LIGHT

2. RECESSED FIRE EXTINGUISHER CABINET AND #10 ABC FIRE EXTINGUISHER PER LATESTEDITION NFPA 10, STANDARD FOR PORTABLEFIRE EXTINGUISHERS. ALL FE WITHINCORRIDORS AND LOBBIES SHALL BE IN A SEMI-RECESSED FIRE EXTINGUISHER CABINET. ALLFIRE EXTINGUISHERS IN STORAGE ROOMSSHALL BE SURFACE MOUNTED. FIREEXTINGUISHERS SHALL BE LOCATED SO THAT,FROM ANY POINT WITH IN THE BUILDING, THETRAVEL DISTANCE TO THE EXTINGUISHER ISLESS THAN 50'-0".

3.

5.

6.

1. FOR BUILDING CODE AND LIFE SAFETYINFORMATION AND PLUMBING CALCULATIONSSEE SHEET G0.3 CODE ANALYSIS.

P34"[864]

1707.EXIT UNIT WIDTH AND NUMBEROF PEOPLE EXIT WILLACCOMMODATE

EMERGENCY LIGHT. SEE ELECTRICAL8.

LIFE SAFETY NOTES

REFER TO ELECTRICAL SHEETS FORADDITIONAL LIFE SAFETY DEVICES NOTSHOWN ON THIS SHEET.

9.

FIRE STAIRS200

AGR RRNCOOFFICE

201

ADMINISTRATIONOFFICE

204

READINESSOFFICE

205

HVAC208

COMMANDMEETING

213

CDR OFFICE216

1SG OFFICE214

PLATOON AWORK ROOM

2063'-8" X 8'-0"CONFERENCETABLE

COPY /MAIL207

M TLT211

W TLT212

FILES / STO

PLATOON BWORK ROOM

209

XO OFFICE215

70'-0" TRAVEL DISTANCE TO PROTECTED 1- HR VERTICAL STAIRWAY(75'-0" MAX ALLOWED FOR SINGLE EXIT)

KEY

SAFE

S

2 HR FIRE RATEDGLAZING

2-HR FIRE RATEDGLAZING

LOBBY202

STOREFRONTWINDOW

MAINTENANCEOFFICE

203

EXISTING PORCH STANDING SEAM ROOF TO REMAIN(PROTECT FROM DAMAGE)

NEW GUTTERS AND DOWNSPOUTS AND FLASHINGS GUTTERNEW GUTTERS AND DOWNSPOUTS AND FLASHINGS TO GUTTER

215

200B

204B205

213

211

212

216

214

204A

200A

208

P34

"17

0

P34"170

FEC

FEC

STO210

203

201

FEC

(6 PEOPLE)

(1 PEOPLE) (1 PEOPLE)

(1 PEOPLE)

(5 PEOPLE)

(5 PEOPLE)

(1 PEOPLE) (1 PEOPLE) (6 PEOPLE)

(2 PEOPLE)

PROTECTED 2-HR VERTICAL STAIRWAY 78'-0"TRAVEL DISTANCE To EXTERIOR DOOR

HATCH THIS FLOOR ONLY DENOTES 2-HOUR HORIZONTAL SHAFT WALL CEILING ASSEMBLY(PROTECTED FROM TOP AND BOTTOM) BELOW EXISTING ROOF TRUSSES. BASIS OFDESIGN USG GYPSUM COMPANY: 20 GA 6" CH STUDS AT 24" O.C. WITH 1" FIRE CODE "C"CORE BOARD (TOP SIDE) AND TWO LAYERS 1/2" FIRE CODE "C" (BOTTOM SIDE): ICCEVALUATION REPORT NER-258 AND PROGRESSIVE ENGINEERING REPORT AER-09038.

THIS BUILDING WILL BE PROTECTED BY A FIRE SPRINKLER SYSTEM

EMERGENCYLIGHT ABOVE

EMER

GENC

YLIG

HT A

BOVE

EMER

GENC

YLIG

HT A

BOVE

EMER

GENC

YLIG

HT A

BOVE

EMER

GENC

YLIG

HT A

BOVE

EMERGENCYLIGHT ABOVE

EMERGENCYLIGHT ABOVE

EMERGENCYLIGHT AB0VE

EM LIGHT

EM LI

GHT

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

FIXEDWINDOW

FIXEDWINDOW

S-6

2

2

ARCHITECTURAL GROUP, INC.

A

B

C

1 2 3 4

D

E

F

G

H

5 6 7 8 9 10

J

K

L

M

11 12 13 14

PROJECT TITLE AND OWNERS NAME

CONSULTANTS

SEAL AND SIGNATURE

REVISIONS

DRAWN BY

CHECKED BY

JOB NUMBER

DATE

DRAWING TITLE

DRAWING NUMBER

SHEET OF

FL LIC. # AA0002264

5032 GODDARD AVENUEORLANDO, FLORIDA 32804(407) [email protected]

COPYRIGHT © 2015 MRI ARCHITECTURAL GROUP INC.

1 2 3 4 5 6 7 8 9 10 11 12 13 14

15

15

06/22/15

PETER M. IKEGAMIAR0013065

8/9/

2015

12:

40:1

4 P

MC

:\Use

rs\P

Ikeg

ami\D

ocum

ents

\A4

-201

4 M

RI -

Pro

posa

ls\1

411

- Tam

pa A

rmor

y\D

MS

TAM

PA-

RED

BR

ICK

BU

ILD

ING

BID

AN

D R

ESPO

NS

E TO

BLD

G.rv

t

LS1.2

PMI

JLR

FDMA PROJECT NO.215004

SECOND FLOOR LIFESAFETY PLAN

"RED BRICK"BUILDING ANNEXTAMPA NATIONALGUARD ARMORY

DEPARTMENT OFMILITARY AFFAIRSST AUGUSTINE, FLORIDA

PERMIT ANDCONSTRUCT

12'8'4'2'0

1/4" = 1'-0"

N

1/4" = 1'-0"LS1.2

A1 SECOND FLOOR LIFESAFETY PLAN

2 RESPONSE TO

FIRE MARSHAL

08-07-15

Page 5: REDBRICK BUILDING ANNEX RENOVATION TAMPA, FL - Florida€¦ · "redbrick" building annex renovation tampa, fl state of florida department of military affairs fdma project number 215004

UP

REF. REF.

874 SF HATCHED AREA874 SF / 5 SF PER PERSON = 175 PEOPLE

DRILL HALL108

3500 LBELEVATOR

103

HVAC RM 1107

IT110B

BREAKROOM106

W TLT104

M TLT101

HA SHWR101B

HA SHWR104A

SUPPLY114

SUPPLYDISTRIBUTION

111

HVAC114A

NEW STRUCTURAL BEAM

PROVIDE FURRED WALLTIGHT TO NEW COLUMN

24'-0" +/-

EXISTING BEARING WALLS TO REMAIN

EXISTING BEARING WALLS TO REMAIN

EXISTING BEARING WALLS TO REMAIN

EXISTINGOPENING INEXISTINGBEARINGWALL

NEWOPENING INEXISTINGBEARINGWALL

FIRE STAIRS100A

ARMORYVAULT

112

18' - 1"0' - 0" 16' -

8"

SUPPLY113

300 SF

STORAGE109

SUPPLY115

CORR102

ELECT110

8' - 4

"12

' - 4"

6' - 11" 2' - 8"

8' - 0" 10' - 0 1/2"

NEW WINDOW AND BRICKINFILL BELOW IN EXISTINGDOOR OPENING

2' - 8

"6'

- 4" 0'

- 10"

4' - 0

"

2' - 4"

FIRESPRINKLER

RISER105

4' - 5

1/2"

4' - 0

"8'

- 8 5/

8"4'

- 0"

8' - 1

0 1/8"

4' - 0

"4'

- 3 1/

4"

1' - 4

"

1' - 4"

2' - 0

"9'

- 2 1/

2"

3' - 10 7/8" 4' - 0" 6' - 7 1/4" 4' - 0" 5' - 3 1/8" 4' - 0" 3' - 9 1/4" 5' - 3"

3' - 9 1/4"

4' - 0" 5' - 3 7/8" 4' - 0" 4' - 7 3/4" 4' - 0" 5' - 3 1/2" 4' - 0" 3' - 9 1/2" 5' - 3" 3' - 10" 4' - 0" 4' - 1 1/2" 4' - 0" 4' - 0 1/2"

100' - 10 3/8"

7' - 4 7/8" 3' - 6" 2' - 9 5/8" 4' - 0" 2' - 0 1/8" 12' - 8 1/2" 3' - 10 1/8" 2' - 9 1/2" 4' - 0" 2' - 1" 3' - 10 1/8" 3' - 10 1/8" 2' - 9 7/8" 4' - 0"

3' - 1

1/2"

4' - 0

"2'

- 11 1

/2"4'

- 0"

3' - 1

3/4"

4' - 0

"3'

- 1 1/

2"3'

- 3 1/

2"10

' - 7 3

/4"

14' - 2 3/8" 14' - 2 1/4" 13' - 11 1/4" 13' - 11 1/4" 13' - 10 1/2" 13' - 10 1/4" 13' - 11 1/2" 0' - 9"0' - 10"

38' -

3 1/2"

3' - 4

"

1' - 4" 3' - 4" 5' - 4"

EQ EQ

9' - 4

"5'

- 8 1/

2"

109

115

114A

114

112

111A 10

8A

108B

100A

101

104

107

110B

106B

108C

100B

102

10

10

10B 10B

10B

10 10

10B

10

10B

10

6

6

10B

10B

10B

10B

10B10C

10

6

10

6D

1C

10

6C

6C

6C

6C

10B6B6B

13

136

1

1

6C

6C

10B

10B

10B

10

10B

10

10

10B

6B

6B

10B10B

6B

10

10B

10B

1010B 10B

10B

10B 10B

10B

10

10B

10B

30X4

8AD

ACL

R

30X4

8AD

ACL

R

30X4

8AD

ACL

R

30X4

8AD

ACL

R

30X4

8AD

ACL

R

1' - 11 3/4" 4' - 0" 1' - 10 3/4" 13' - 11 1/4"

ADA COMPLIANT

RELOCATED EXISTINGDRINKING FOUNTAIN. MOUNTPER ADA

105

CMUINFILL

106A

110

103

10' -

4"

2' - 9"4' - 0"

3' - 6

"

FIRE TREATEDPLYWOODFULL HEIGHT

HATCH DENOTES: 4'-0" X3'-0" CLEAR SPACE FORELEVATOR SERVICE

W3 W3 W3 W3 W3 W3 W3 W3 W3

W3

W3

W3

W3

W3W3W3W3W3W3W4

W1

W3

W2

W2

W1 W1

EXISTING DOORS AND FRAMESTO BE REFINISHED

EXISTING DOOR

6' - 0"10' -

0"

6' - 0"

REFE

R TO

CIV

IL DR

AWIN

GS1'

- 10"

4'-0"

+ MA

X

2' - 0

"4'

- 0"

PROPERTY LINE: REFER TO CIVIL DRAWINGS

ABI-1: DECORATIVE BARRIER WALL AND FENCE: REFER TO DETAILS A10 AND B10, SHEET A4.2 AND CIVIL DRAWINGS

PROVIDE FURRED WALLTIGHT TO NEW COLUMN

5' - 0"

JAN101A

101A

ALL WINDOW GLASS IN ALLTOILET ROOMS:PROVIDE TRANSLUCENTOBSCURE WINDOW FILM(INTERIOR SIDE) FORPRIVACY. SUBMIT SAMPLEFOR SELECTION

AT EXISTING DOOR AND FRAMETO BE REMOVED: PROVIDE NEWCMU AND BRICK INFILL TOMATCH EXISTING BRICK ANDPATTERNS

ALL WINDOW GLASS IN ALL TOILET ROOMS:PROVIDE TRANSLUCENT OBSCURE WINDOW FILM(INTERIOR SIDE) FOR PRIVACY. SUBMIT SAMPLEFOR SELECTION

AT EXISTING DOOR AND FRAME TO BE REMOVED:PROVIDE NEW CMU AND BRICK INFILL TO MATCHEXISTING BRICK AND PATTERNS

LANDING AND STEPS: CONSTRUCT LANDING AS DEEP AS POSSIBLE TO ACHIEVE 5'-0" DEPTH (FIELD VERIFYAGAINST EXISTING PROPERTY LINE AND PROPOSED SIDEWALK AND EXISTING SECURITY FENCE TO REMAIN)

6' - 0

"

REFRIGERATORS,GOVERNMENT FURNISHED,GOVERNMENT INSTALLED

S-5DIRECTORY

S-3

S-2

S-1

S-1

S-1

S-1

S-1

S-1

S-1

S-1

S-1

S-1

S-1

10

6

6

6

9

9

9

9

9

9

8

8

7 777777 777

7

7

7

7

7 7 7 7 7 7 7 7 7 7

11

7

7

7

7

7

S-1

S-1

10B

A8.1H8

A8.2A1

A1

A4.3

A10

A4.1

B10

A4.2

A3.1

A1

A3.1 J1

A3.1

E1

A3.1J8

W3 W1

6D6D

A4.2B1

A4.2B1

A4.2B1

A4.2B1

A4.2B1

A4.2B1

A4.2B1

A4.2B1

6' - 0

"

3' - 4

"

5' - 0"

2' - 0

"

3' - 0" CLR

9'-0"

+/-

1' - 0

"

1C

2' - 6"

10C

10C10

10B

10B

10B

3' - 0

" CLR

CLR

1' - 4

"

4'-8"+ 4' - 0" CLR

4' - 0

1/2"

4' - 0

"

3' - 0" CLR

4' - 4"4' - 0" CLR

6C6C

6

6D6C

CLR

3' - 0"6C

3' - 6" CLR

SLOPETO DRAIN

SLOPETO DRAIN

SLOPETO DRAIN

SLOPETO DRAIN

SLOPETO DRAIN

SLOPETO DRAIN

TRENCHDRAIN

SHWRCURTAIN

PARTITION

111B

S-7OCCUPANCYLOAD

7

RECYCLING10 SF

EM (LEED)

EM (LEED)

6' - 0

"

6' - 4

1/2"

1' - 6

"

EM (LEED)

RECY

CLIN

G20

SF

RECYCLING20 SF

RECYCLING20 SF

RECYCLING20 SF

3' - 8"

3' - 8

"

BOTTOM RAIL TOEXTEND BELOWSTAIR TO WALL

1' - 11"

5'-0".

5' - 7 1/4"

2'-6". 3'-1 1/4".

(2-HR D00R W/2-HR GLAZING)

RATED EXIT100

12"

2

100C

2-HR FIRE SEPARATION(INCLUDING PENETRATIONS)

1

1

1.

2.

3.

4.

6.

7.

8.

9.

10.

PARTITION TYPE (SEE A7.1)XX

STOREFRONT GLAZING TYPE(SEE SHEET A6.1)

XX

DOOR NUMBER (SEE SHEET A6.1)

SEE SHEET ID1.0 FOR ROOM FINISHSCHEDULES.

XXX

ALL DIMENSIONS TO FACE OF CONCRETEOR MASONRY AND TO FACE OF INTERIORMETAL STUD WALLS OR CENTER LINE OFCOLUMN UNLESS NOTED OTHERWISE.

1-HR FIRE-RATED WALL CONSTRUCTION

REFER TO LIFE SAFETY PLANS LS1.1 ANDLS1.2 FOR FIRE EXTINGUISHER CABINETAND WALL MOUNTED FIRE EXTINGUISHERS.

GENERAL CONSTRUCTION CONTRACTORSHALL PROVIDE ALL BLOCKING /SUPPORTS WITHIN WALLS AND ABOVECEILINGS FOR OWNER FURNISHEDFINISHES / MATERIALS, DEVICES ANDEQUIPMENT. ALL BLOCKING SHALL BE OFNON-COMBUSTIBLE MATERIAL. FIRETREATED LUMBER MAY BE USED IFPERMITTED BY BUILDING CODE ANDAGENCY HAVING JURISDICTION. ALLSUPPORTS SHALL BE FIELD LOCATED ANDAPPROVED BY THE GOVERNMENTREPRESENTATIVE PRIOR TO FINALINSTALLATION.GENERAL CONSTRUCTION CONTRACTORSHALL COORDINATE ALL TRADES ANDSHALL PROVIDE ELECTRICAL,MECHANICAL, PLUMBING SERVICES ANDHOOKUPS TO OWNER FURNISHEDDEVICES AND EQUIPMENT. SUCHINCLUDES, BUT ARE NOT LIMITED TOSPECIALTY LIGHT FIXTURES, CEILINGMOUNTED PROJECTORS, TV MONITORS,PROJECTOR SCREENS, AUDIOEQUIPMENT, CASEWORK, ETC.ALL WORK SHALL COMPLY WITH ALLAPPLICABLE CODES AND STATUES,INCLUDING THE AMERICAN WITHDISABILITIES ACT AND INTERNATIONALBUILDING CODE.

11.

THE EXACT LOCATION OF ALLELECTRICAL DEVICES EXPOSED TO VIEWOR SERVING GOVERNMENT FURNISHEDEQUIPMENT (INCLUDING BUT NOTLIMITED TO RECEPTACLES, LIGHTSWITCHES, FLOOR BOXES, TELEPHONE /DATA BOXES, WALL SCONCES, ALARMSAND THERMOSTATS) SHALL BEPHYSICALLY MARKED ON THE FLOOR,WALL AND CEILING AND APPROVED BYTHE GOVERNMENT REPRESENTATIVEPRIOR TO INSTALLATION.ANY DAMAGE TO EXTERIOR WALLSSHALL BE REPAIRED AND FINISHED TOMATCH ADJACENT SURFACES, UNLESSNOTED OTHERWISE.

12.

13.

GENERAL NOTESINDICATES EXISTING WALLSTO REMAIN

5. SEE SHEET A0.1 FOR GENERALINFORMATION AND ABBREVIATIONS

ARCHITECTURALLY THE FINISHED FLOORELEVATION 0 FEET 0 INCHES EQUALS22.66 FEET CIVIL

14.

15. REFER TO SHEET ID2.0FOR SIGNAGES-#

2-HR FIRE-

KEYNOTESDIMENSION IS FROM FACE OF EXISTING MASONRYWALL

DIMENSION IS CLEAR OPENING FROM FACE OFFINISHES.

ALIGN FRAMING/FINISHED WALL WITH ADJACENTFRAMING/FINISHED WALL AT EXISTING MASONRYWALL.

PROVIDE STUD INFILL @ 16" [406 MM] O.C. MAX ATEXISTING OPENINGS.

DIMENSION CLEAR BETWEEN FACE OF CABINETSBELOW COUNTER OR BETWEEN FACE OFCABINETS TO FINISHED WALL.

1

2

3

4

5

ELEVATOR: VERIFY CLEAR DIMENSIONS ANDCLEARANCES WITH ELEVATOR MANUFACTURER.

FIELD VERIFY ROUGH OPENING DIMENSION FORREPLACEMENT OF EXISTING WINDOW SYSTEMS.

PROVIDE BRICK INFILL FINISH EXTERIOR WALL TOMATCH ADJACENT. INSTALL SALVAGED BRICKWHERE APPLICABLE.

ALL WINDOW GLASS IN ALL TOILET ROOMS:PROVIDE TRANSLUCENT OBSCURE WINDOW FILM(INTERIOR SIDE) FOR PRIVACY. SUBMIT SAMPLE FORSELECTION

6

7

8

9

THIS DOOR: PROVIDE METAL SIGN WITH REBACKGROUND AND WHITE HELVETICA BOLDLETTERS "FIRE SRPINKLER ROOM". SUBMITT SHOPDRAWINGS FOR REVIEW AND APPROVAL.

THIS DOOR: MODIFY FRAME AND PROVIDECONCEALED POWER AND CONDUIT/WIRE ASREQUIRED FOR COMPLETE INSTALLATION FORDOOR MONITORING CAMERA AND DOORMAGNETIC LOCK/STRIKE FROM DOOR TOACTIVATION SWITCH AND MONITORING SYSTEM(C.F.C.I.) LOCATED IN ADMINISTRATIVE OFFICE 204.LOCATION OF SWITCH AND MONITOR TO BEDETERMINED BY GOVERNMENT REPRESENTATIVE.REFER ALSO TO ELECTRICDAL DRAWINGS ANDHARDWARE SCHEDULE.

10

11 ARCHITECTURAL GROUP, INC.

A

B

C

1 2 3 4

D

E

F

G

H

5 6 7 8 9 10

J

K

L

M

11 12 13 14

PROJECT TITLE AND OWNERS NAME

CONSULTANTS

SEAL AND SIGNATURE

REVISIONS

DRAWN BY

CHECKED BY

JOB NUMBER

DATE

DRAWING TITLE

DRAWING NUMBER

SHEET OF

FL LIC. # AA0002264

5032 GODDARD AVENUEORLANDO, FLORIDA 32804(407) [email protected]

COPYRIGHT © 2015 MRI ARCHITECTURAL GROUP INC.

1 2 3 4 5 6 7 8 9 10 11 12 13 14

15

15

06/22/15

PETER M. IKEGAMIAR0013065

8/9/

2015

12:

39:5

0 P

MC

:\Use

rs\P

Ikeg

ami\D

ocum

ents

\A4

-201

4 M

RI -

Pro

posa

ls\1

411

- Tam

pa A

rmor

y\D

MS

TAM

PA-

RED

BR

ICK

BU

ILD

ING

BID

AN

D R

ESPO

NS

E TO

BLD

G.rv

t

A1.1

PMI

JLR

FDMA PROJECT NO.215004

FIRST FLOOR PLAN

"RED BRICK"BUILDING ANNEXTAMPA NATIONALGUARD ARMORY

DEPARTMENT OFMILITARY AFFAIRSST AUGUSTINE, FLORIDA

PERMIT ANDCONSTRUCT

1/4" = 1'-0"A1.1

A1 RENOVATED FIRST FLOOR12'8'4'2'0

1/4" = 1'-0"

N

FF

FF

F

F

F

F

NG

F

F

F

NG

NG F

F

F

F

F

1 RESPONSE TO

BLDG DEPT

07-27-15

2 RESPONSE TO

FIRE MARSHAL

08-07-15

Page 6: REDBRICK BUILDING ANNEX RENOVATION TAMPA, FL - Florida€¦ · "redbrick" building annex renovation tampa, fl state of florida department of military affairs fdma project number 215004

4' - 1 1/2" 4' - 0" 6' - 7 1/4" 4' - 0" 5' - 3 1/8" 4' - 0" 4' - 5" 4' - 0" 4' - 4 1/2" 4' - 0" 5' - 3 7/8" 4' - 0" 4' - 7 3/4" 4' - 0" 5' - 3 1/2" 4' - 0" 4' - 5 1/4" 4' - 0" 4' - 5 1/4" 4' - 0" 4' - 1 1/2" 4' - 0" 3' - 9 7/8"

1' - 1

1 3/4"

4' - 0

"2'

- 11 1

/2"4'

- 0"

FIRE STAIRS200

AGR RRNCOOFFICE

201

ADMINISTRATIONOFFICE

204

READINESSOFFICE

205

HVAC208

23' - 10"

COMMANDMEETING

213

CDR OFFICE216

1SG OFFICE214

7' - 6" 2' - 0" 7' - 6" 4' - 9"

PLATOON AWORK ROOM

2063'-8" X 8'-0"CONFERENCETABLE

COPY /MAIL207

M TLT211

W TLT212

FILES / STO

5' - 0"

PLATOON BWORK ROOM

209

XO OFFICE215

KEY

SAFE

S

2 HR FIRERATED GLAZING

2-HR FIRE RATEDGLAZING

LOBBY202

18'-4".

15' -

6 7/8"

20' -

6"

5' - 0 1/4"

STOREFRONT WINDOW(NO FIRE RATING)

11' - 4" 13' - 11" 18' - 4"

MAINTENANCEOFFICE

203

6' - 11"

8' - 4

"

3' - 6

"1'

- 6"3'

- 6"

1' - 6

"2'

- 0"5' - 0"

3' - 1

1/2"

4' - 0

"2'

- 11 1

/2"4'

- 0"

4' - 3

1/4"

4' - 0

"8'

- 10 1

/8"4'

- 0"

4' - 5

1/2"

4' - 0

"

7' - 4 7/8" 4' - 0" 2' - 3 5/8" 4' - 0" 7' - 3 1/2" 4' - 0" 10' - 0 3/4" 4' - 0" 8' - 0 5/8" 4' - 0" 2' - 9 7/8" 4' - 0" 7' - 10 1/2" 4' - 0" 9' - 6" 4' - 0" 5' - 8 3/4" 4' - 0" 3' - 9 7/8"

EXISTING PORCH STANDING SEAM ROOF TO REMAIN(PROTECT FROM DAMAGE)

ADD-ALT #4: NEW GUTTERS AND DOWNSPOUTS AND FLASHINGS GUTTERADD-ALT #4: NEW GUTTERS AND DOWNSPOUTS AND FLASHINGS TO GUTTER

12' - 6" 11' - 4"

15' -

4"

15' -

4"

12' -

0"4'

- 0"

7' - 1

0 1/2"

12' -

5"

10

6

6

6

6

6

6

6

6

6

6

6B

6B

6B

6C

6C

6

1

1 13 1

1

1

6

6

6

66

6

6

10B

10B

10B

10B

101010 10

10

10 1010

10 10 10

10

10

1010

215

200B

204B205

213

211

212

216

214

204A

200A

208

ALIG

N W

/ ELE

V FR

AMIN

G

9'-10

"+

NEW HI-LO ADA DF 30X4

8AD

ACL

R

30X48ADACLR

30X48ADACLR

6B

6

6B

STO210 21

0

6' - 2"

W5

W5

W5 W5 W5 W5 W5 W5 W5 W5 W5 W5 W5

W5

W5W5W5W5W5W5W5

W8

HG

HG

HG

HG

HG

HG HG

HG

F

F

F

FF

F

OPERABLEWINDOW

OPERABLEWINDOW

203

201

1' - 4

"

8' - 0

"

2-HR FIRE RATEDGLAZING IN DOOR

2-HR FIRE RATEDGLAZING IN DOOR

W5 W5

14'-1

0"+/

-

OF W

ALL T

O FA

CE O

F W

A LL

9'-0"

CLE

AR F

ROM

FACE

FACE OF FINISHED WALL BELOW

42" HIGH WALLWITH SOLIDSURFACE CAP

42" WALL WITH SOLIDSURFACE CAP

NEW FLOOR STRUCTUREINFILL (REFER TOSTRUCTURAL DRAWINGS)

NEW FLOOR STRUCTUREINFILL (REFER TOSTRUCTURAL DRAWINGS)

S-1

S-1S-1S-1

S-3

S-1

S-2

S-1

S-1

S-4

S-4

S-6

S-1

S-1

7 7 7 7 7 7 7 7 7 7 7

7

7

7

A8.1H8

A1

A4.3

A10

A4.1

A3.1

A1

A3.1A1

A3.1 J1

A3.1

E1

W6

W7

OPERABLEWINDOW

7

OPERABLEWINDOW

7

OPERABLEWINDOW

7

OPERABLEWINDOW

7

OPERABLEWINDOW

7

FIXEDWINDOW

7

FIXEDWINDOW

7

OPERABLEWINDOW

7

OPERABLEWINDOW

W5

OPERABLEWINDOW

7

W5

OPERABLEWINDOW

7

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

OPERABLEWINDOW

W5

OPERABLEWINDOW

7

OPERABLEWINDOW

7

W5

OPERABLEWINDOW

7

6

6

1' - 5"

HANDRAILS AND GUARDRAILS,REFER TO SHEET A5.1

10

(2)-KEY SAFE EYE HOOK ANCHORAGE. REFER TOSTRUCTURAL DRAWINGS, DETAIL 4/SHEET A2.5.COORDINATE EXACT LOCATION WITH GOVERNMENT.

RECYCLING10 SF

44".

44"

1' - 11" 1' - 0"

44".

1

2

1.

2.

3.

4.

6.

7.

8.

9.

10.

PARTITION TYPE (SEE A7.1)XX

STOREFRONT GLAZING TYPE(SEE SHEET A6.1)

XX

DOOR NUMBER (SEE SHEET A6.1)

SEE SHEET ID1.0 FOR ROOM FINISHSCHEDULES.

XXX

ALL DIMENSIONS TO FACE OF CONCRETEOR MASONRY AND TO FACE OF INTERIORMETAL STUD WALLS OR CENTER LINE OFCOLUMN UNLESS NOTED OTHERWISE.

1-HR FIRE-RATED WALL CONSTRUCTION

REFER TO LIFE SAFETY PLANS LS1.1 ANDLS1.2 FOR FIRE EXTINGUISHER CABINETAND WALL MOUNTED FIRE EXTINGUISHERS.

GENERAL CONSTRUCTION CONTRACTORSHALL PROVIDE ALL BLOCKING /SUPPORTS WITHIN WALLS AND ABOVECEILINGS FOR OWNER FURNISHEDFINISHES / MATERIALS, DEVICES ANDEQUIPMENT. ALL BLOCKING SHALL BE OFNON-COMBUSTIBLE MATERIAL. FIRETREATED LUMBER MAY BE USED IFPERMITTED BY BUILDING CODE ANDAGENCY HAVING JURISDICTION. ALLSUPPORTS SHALL BE FIELD LOCATED ANDAPPROVED BY THE GOVERNMENTREPRESENTATIVE PRIOR TO FINALINSTALLATION.GENERAL CONSTRUCTION CONTRACTORSHALL COORDINATE ALL TRADES ANDSHALL PROVIDE ELECTRICAL,MECHANICAL, PLUMBING SERVICES ANDHOOKUPS TO OWNER FURNISHEDDEVICES AND EQUIPMENT. SUCHINCLUDES, BUT ARE NOT LIMITED TOSPECIALTY LIGHT FIXTURES, CEILINGMOUNTED PROJECTORS, TV MONITORS,PROJECTOR SCREENS, AUDIOEQUIPMENT, CASEWORK, ETC.ALL WORK SHALL COMPLY WITH ALLAPPLICABLE CODES AND STATUES,INCLUDING THE AMERICAN WITHDISABILITIES ACT AND INTERNATIONALBUILDING CODE.

11.

THE EXACT LOCATION OF ALLELECTRICAL DEVICES EXPOSED TO VIEWOR SERVING GOVERNMENT FURNISHEDEQUIPMENT (INCLUDING BUT NOTLIMITED TO RECEPTACLES, LIGHTSWITCHES, FLOOR BOXES, TELEPHONE /DATA BOXES, WALL SCONCES, ALARMSAND THERMOSTATS) SHALL BEPHYSICALLY MARKED ON THE FLOOR,WALL AND CEILING AND APPROVED BYTHE GOVERNMENT REPRESENTATIVEPRIOR TO INSTALLATION.ANY DAMAGE TO EXTERIOR WALLSSHALL BE REPAIRED AND FINISHED TOMATCH ADJACENT SURFACES, UNLESSNOTED OTHERWISE.

12.

13.

GENERAL NOTESINDICATES EXISTING WALLSTO REMAIN

5. SEE SHEET A0.1 FOR GENERALINFORMATION AND ABBREVIATIONS

ARCHITECTURALLY THE FINISHED FLOORELEVATION 0 FEET 0 INCHES EQUALS22.66 FEET CIVIL

14.

15. REFER TO SHEET ID2.0FOR SIGNAGES-#

2-HR FIRE-

KEYNOTESDIMENSION IS FROM FACE OF EXISTING MASONRYWALL

DIMENSION IS CLEAR OPENING FROM FACE OFFINISHES.

ALIGN FRAMING/FINISHED WALL WITH ADJACENTFRAMING/FINISHED WALL AT EXISTING MASONRYWALL.

PROVIDE STUD INFILL @ 16" [406 MM] O.C. MAX ATEXISTING OPENINGS.

DIMENSION CLEAR BETWEEN FACE OF CABINETSBELOW COUNTER OR BETWEEN FACE OFCABINETS TO FINISHED WALL.

1

2

3

4

5

ELEVATOR: VERIFY CLEAR DIMENSIONS ANDCLEARANCES WITH ELEVATOR MANUFACTURER.

FIELD VERIFY ROUGH OPENING DIMENSION FORREPLACEMENT OF EXISTING WINDOW SYSTEMS.

PROVIDE BRICK INFILL FINISH EXTERIOR WALL TOMATCH ADJACENT. INSTALL SALVAGED BRICKWHERE APPLICABLE.

ALL WINDOW GLASS IN ALL TOILET ROOMS:PROVIDE TRANSLUCENT OBSCURE WINDOW FILM(INTERIOR SIDE) FOR PRIVACY. SUBMIT SAMPLE FORSELECTION

6

7

8

9

THIS DOOR: PROVIDE METAL SIGN WITH REBACKGROUND AND WHITE HELVETICA BOLDLETTERS "FIRE SRPINKLER ROOM". SUBMITT SHOPDRAWINGS FOR REVIEW AND APPROVAL.

THIS DOOR: MODIFY FRAME AND PROVIDECONCEALED POWER AND CONDUIT/WIRE ASREQUIRED FOR COMPLETE INSTALLATION FORDOOR MONITORING CAMERA AND DOORMAGNETIC LOCK/STRIKE FROM DOOR TOACTIVATION SWITCH AND MONITORING SYSTEM(C.F.C.I.) LOCATED IN ADMINISTRATIVE OFFICE 204.LOCATION OF SWITCH AND MONITOR TO BEDETERMINED BY GOVERNMENT REPRESENTATIVE.REFER ALSO TO ELECTRICDAL DRAWINGS ANDHARDWARE SCHEDULE.

10

11 ARCHITECTURAL GROUP, INC.

A

B

C

1 2 3 4

D

E

F

G

H

5 6 7 8 9 10

J

K

L

M

11 12 13 14

PROJECT TITLE AND OWNERS NAME

CONSULTANTS

SEAL AND SIGNATURE

REVISIONS

DRAWN BY

CHECKED BY

JOB NUMBER

DATE

DRAWING TITLE

DRAWING NUMBER

SHEET OF

FL LIC. # AA0002264

5032 GODDARD AVENUEORLANDO, FLORIDA 32804(407) [email protected]

COPYRIGHT © 2015 MRI ARCHITECTURAL GROUP INC.

1 2 3 4 5 6 7 8 9 10 11 12 13 14

15

15

06/22/15

PETER M. IKEGAMIAR0013065

8/9/

2015

12:

39:5

2 P

MC

:\Use

rs\P

Ikeg

ami\D

ocum

ents

\A4

-201

4 M

RI -

Pro

posa

ls\1

411

- Tam

pa A

rmor

y\D

MS

TAM

PA-

RED

BR

ICK

BU

ILD

ING

BID

AN

D R

ESPO

NS

E TO

BLD

G.rv

t

A1.2

PMI

JLR

FDMA PROJECT NO.215004

SECOND FLOOR PLAN

"RED BRICK"BUILDING ANNEXTAMPA NATIONALGUARD ARMORY

DEPARTMENT OFMILITARY AFFAIRSST AUGUSTINE, FLORIDA

PERMIT ANDCONSTRUCT

N12'8'4'2'0

1/4" = 1'-0" 1/4" = 1'-0"A1.2

A1 RENOVATED SECOND FLOOR

1 RESPONSE TO

BLDG DEPT

07-27-15

2 RESPONSE TO

FIRE MARSHAL

08-07-15

ON ALL WALLS WITHIN THIS ROOM:PROVIDE AND INSTALL MARLITE WOODPANEL SYSTEM (OR EQUAL) WITH 2'-0"WIDE X 2'-0" HIGH O.C. PANELS. HEIGHTTO BE 4'-0" FROM FINISHED FLOOR TO 4'-0" A.F.F. WITH 1/4" SATIN STAINLESS STEELREVEALS ALL SIDES OF PANELS. PROVIDEDECORATIVE 1-1/2" WOOD CAP WITHEASED EDGES AT TOP. AT WINDOWOPENINGS: SYSTEM TO TURN ANDTERMINATE AT WINDOW FRAMESSTAINCOLOR TO MATCH STAINED DOORS.SUBMIT SAMPLES FOR APPROVAL


Recommended